1 HVAC PRO for Windows User s Manual OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence 5 Configuration Questions and Answers 7 Compressor Lead/Lag Control? 10 Stage Selection 11 Cooling Diagnostics 11 Reset Control Function 11 - No Reset 11 - Outdoor Air Reset 11 - Zone Temperature Reset 12 - Return Water Reset 13 - Remote Reset 14 - Ramping Strategy 15 Leaving Water Low Limit? 16 Outdoor Temperature Lockout? 16 Ice Mode Control? 16 Is a Demand Limiting Input Needed? 17 Select Pump Logic 17 - Single Pump Control 17 - Dual Pump Control 17 Flow Interlock Input? Johnson Controls, Inc. 1 Code No. LIT

2 Modes of Operation Page 18 - Occupied Mode 18 - Unoccupied Mode 19 - Select Method to Initiate Occupied Mode 19 - Shutdown Mode 19 - Select Method to Initiate Shutdown Mode 19 2 OEM Reciprocating Chiller

3 Reciprocating Chiller Description The AS-UNT33n-1 microprocessor-based leaving water controller performs multiple capacity steps of cooling from a single sensor. Its operation is based on an adjustable setpoint and control band. The controller can be used as a standalone controller or it can be connected to a Companion or Metasys Network. When connected to a network, the controller provides point and control information to the rest of the network and communicates over the N2 Bus. For a smaller facility, the controller can stand alone in conjunction with a Zone Terminal. The controller is configured using the HVAC PRO for Windows software tool, Release 4.00 or later. For certain specific original equipment manufacturers, this controller comes factory-configured. Figure 1: Reciprocating Chiller Controller OEM Reciprocating Chiller 3

4 4 OEM Reciprocating Chiller

5 Theory of Operation Overview Operation of the reciprocating chiller controller is based on an adjustable setpoint and control band. If the leaving chilled water temperature begins to rise to the desired setpoint plus control band divided by two (upper limit), the first stage of cooling is energized. Additional stages of cooling follow, after a time delay for each stage, as long as the leaving water temperature remains above the upper limit of the control band. As the leaving water temperature begins to drop to setpoint minus control band divided by two (lower limit) cooling stages begin to de-energize--also with a time delay between each stage. 57 PB LWSP DB DB Control Band algorthm.drw Figure 2: Leaving Water Control Algorithm Operation No stages energize or de-energize as long as the leaving water temperature is within the control band. Generally, anytime the leaving water temperature goes above the control band, stages energize. Conversely, when the leaving water temperature falls below the control band, stages de-energize. At initial start of the unit, a time delay occurs. There is a 60 second interstage on delay between stages. Each stage incorporates minimum on and off timers with a maximum cycle rate of six cycles per hour. Control Sequence Leaving Water is controlled to the Actual Leaving Water Setpoint. The Actual Leaving Water Setpoint is a function of what mode of operation the controller is in and if a reset option is used. The Control Band potentiometer (AI-6), located on the front of the controller, is used to determine the Actual Leaving Water Deadband and Prop Band. OEM Reciprocating Chiller 5

6 Actual Leaving Water Deadband: Control Band (AI-6) 2 Actual Leaving Water Prop Band: Actual Leaving Water Deadband Number of Stages Example: Control Band = 4 F Number of Stages = 6 Deadband = 4 2 = 2 F Prop Band = 2 * 6 = 12 F As the Leaving Water Temperature (AI-3) rises above the Actual Leaving Water Setpoint, but within the Actual Leaving Water Deadband, there is no increase in the Compressor Command. As the Leaving Water Temperature continues to rise above the Deadband and into the Prop Band, the Compressor Command increases. When Leaving Water Integration Gain is used, a Proportional plus Integral Command is calculated. As the Compressor Command increases, stages of cooling capacity energize. Minimum on/off, interstage times, and cycles per hour attributes control the outputs. As the Leaving Water Temperature decreases towards the Actual Leaving Water Setpoint, the Compressor Command decreases. Upon re-entering the Deadband, the current Compressor Command is maintained. If the Leaving Water Temperature falls below the Actual Leaving Water Setpoint minus the Deadband, the Compressor Command continues to decrease. 6 OEM Reciprocating Chiller

7 Configuration Questions and Answers The Reciprocating Chiller Control is configured by responding to a programmed sequence of questions using HVAC PRO for Windows. The flowchart explains the order of the questions. OEM Reciprocating Chiller 7

8 Start HVAC PRO for Windows Select File, New, OEM Applications,* Reciprocating Chiller Is Compressor Lead/Lag Control Desired? No Yes Method to Initiate Lead/Lag of Compressors? N2 Software Command BI Command Both (N2 Priority) Both (Equal Priority) Occupied Transition Compressor Runtime Compressor Starts Number of Stages? 1 through 8 AI Selectable 2/3/4 AI Selectable 4/6/8 Number of Stages? AI Selectable 4/6/8 2, 4, 6, or 8 Stages Cooling Diagnostics? Yes / No Select Reset of Chilled Water Option None Outdoor Air Reset Zone Temperature Reset Return Water Reset Location of Zone Temperature Value? Analog Input N2 Command Control from Return Water if Leaving Water Sensor is unreliable? Yes / No Is Leaving Water Low Limit needed? Yes / No Is Outdoor Temperature Lockout needed? Yes / No FLOW2A Go to A Figure 3a: Question and Answer Flowchart 8 OEM Reciprocating Chiller

9 A Is Ice Mode Control needed? No Yes Method to Initiate Ice Mode? N2 Software Command BI Command Both (N2 Priority) Both (Equal Priority) Is Demand Limit Input needed? Yes / No Select Pump Logic None Single Pump Dual Pump Is Flow Interlock needed? Yes / No Select Method to Initate Lead/Lag of Dual Pump N2 Software Command BI Command Both (N2 Priority) Both (Equal Priority) Select Method to Initiate Occupied Mode N2 Software Command BI Command Both (N2 Priority) Both (Equal Priority) Select Method to Initiate Shutdown Mode N2 Software Command BI Command Both (N2 Priority) Both (Equal Priority) Stop FLOW2B Figure 3b: Question and Answer Flowchart (Cont.) OEM Reciprocating Chiller 9

10 Following is an explanation of the questions along with a brief description of some of the corresponding control logic. Compressor Lead/Lag Control? If Lead\Lag Control is selected, four options to initiate the mode of operation are available: Binary Input (BI) N2 Command from FMS both BI and N2 with N2 priority both BI and N2 with equal priority Equal priority means first on, last off. An Automatic Lead\Lag control is also available. Each option is described below. If you choose the BI or N2 points, the controller changes the lead circuit depending upon the status of the input. A circuit is defined as a group of binary outputs. All odd number stages are considered part of circuit one and all even number stages are considered part of circuit two. If the Automatic control is selected, then an Automatic Enable (BD) point must be configured allowing the Automatic Control to turn on or off. When the BD point is enabled (by default), the control reverses the sequencing of refrigeration circuits based on these user selected trigger points: Occupied Transition--a change from Shutdown, Unoccupied or Ice Mode to Occupied mode Compressor Runtime--based on which circuit has the least cumulative compressor runtime Compressor Starts--based on which compressors have the fewest number of starts All comparisons are based on the actual activity of the lead compressor of each circuit. A monitor only Lead Circuit Index (BD) point indicating which circuit is currently leading is provided. If the Automatic Enable is off, the compressors sequence in numerical order. Note: The Lead\Lag reversing of circuits takes place only when all compressors are off. Changing the Lead Circuit BI or N2 command has no effect unless all stages are off. This means the BI could read Lead Circuit is two, and the Lead Circuit Index reads one. This means the controller is awaiting an opportunity to change the Lead Circuit. 10 OEM Reciprocating Chiller

11 Stage Selection Cooling Diagnostics Reset Control Function No Reset Outdoor Air Reset You choose the number of stages of cooling in one of two ways. First, you can select the exact number of stages available through the HVAC PRO for Windows software. One through eight stages are available. If this option is chosen, the only way to modify the number of controlled stages is by modifying the configuration. A read-only Number of Cooling Stages point displays the chosen number of stages. The second way allows you to select between two, three, or four stages, or four, six, or eight stages depending upon the position of DIP switches one and two (SW-1 and SW-2) associated with Analog Input number two. With SW-1 in the T position and SW-2 in the 2V position, the controller controls three or six stages. With SW-1 in the V position and SW-2 in the 2V position, the controller controls two or four stages. With SW-1 in the T position and SW-2 in the 10V position, the controller controls four or eight stages. A read-only point displays the chosen number of stages. Note: When you choose the multi-stage option, the number of stages desired must be set while the controller is de-energized. If the settings are changed after the controller is energized, any changes are ignored. Diagnostics of the Cooling Outputs are available when chosen with HVAC PRO for Windows. The Leaving Water Temperature sensor determines a drop in Leaving Water Temperature over time whenever an output is energized. Diagnostic Temp and Diagnostic Time are the two adjustable variables that are used to set up the change in temperature over time function. Each output has a read-only failure point associated with it that acknowledges when a failure occurs. Once a failure occurs for a particular output, the alarm can only be cleared by producing the change in temperature over time, or by cycling power. Available options for reset of controlled water temperature include: No Reset, Reset from Outdoor Air, Reset from Zone Temperature, Reset from Return Water Temperature, and Remote Reset. Each is described below. Leaving Water Temperature is controlled to the Leaving Water Setpoint which is adjustable from the front panel of the controller (AI-4). This adjustable setpoint is in effect during the Occupied mode of operation. Likewise, the Unoccupied Leaving Water Setpoint is maintained during the Unoccupied mode. If the Leaving Water Sensor (AI-3) becomes unreliable, the compressor command is forced to zero. An Outdoor Air Temperature (OAT) sensor (AI-1) is required when Outdoor Air Reset is chosen. Four variables are used to set up the reset ramp that calculates the Actual Leaving Water Setpoint. OEM Reciprocating Chiller 11

12 Leaving Water Setpoint (AI-4) (LWSP)0 Leaving Reset Band (AI-5) (LWRB) Outdoor Air High Limit (OAHL) Outdoor Air Reset Band (OARB) LWRB LWSP (OALL=OAHL-OARB) OALL OARB OAHL RESETS1 Figure 4: Outdoor Air Reset, OEM, Reciprocating Chiller As the OAT increases above the Outdoor Air Low Limit (OALL), the Actual Leaving Water Setpoint decreases from its Leaving High Limit (Leaving Water Setpoint + Leaving Reset Band) to the Leaving Water Setpoint. When OAT reaches the Outdoor Air High Limit, the Actual Leaving Water Setpoint equals the Leaving Water Setpoint (AI-4). If the OAT sensor is missing or unreliable, no reset occurs and the Actual Leaving Water Setpoint equals the Leaving Water Setpoint (AI-4). If the Leaving Water Sensor (AI-3) becomes unreliable, the compressor command is forced to zero. Zone Temperature Reset When this option is chosen, a zone temperature must be made available to the controller. There are two ways of letting the controller know the zone temperature. The first is through an adjustable Analog Data Float (ADF) point. With the use of a facility management system, a zone temperature, or average of multiple zone temperatures, can be shared with the controller. The second way is with the use of a zone temperature sensor hooked directly to the controller. Regardless of which method is used, the control strategy is the same. 12 OEM Reciprocating Chiller

13 Four variables are used to set up the reset ramp that calculates the Actual Leaving Water Setpoint: Leaving Water Setpoint (AI-4) (LWSP) Leaving Reset Band (AI-5) (LWRB) Zone Temperature High Limit (ZTHL) Zone Temperature Reset Band (ZTRB) LWRB LWSP (ZTLL=ZTHL-ZTRB) ZTLL ZTRB ZTHL RESETS2 Figure 5: Zone Temperature Reset, OEM, Reciprocating Chiller As the Zone Temperature increases above the Zone Temperature Low Limit (ZTLL), the controller decreases the Actual Leaving Water Setpoint from its Leaving High Limit (Leaving Water Setpoint + Leaving Reset Band) to the Leaving Water Setpoint. When zone temperature reaches the Zone Temperature High Limit, the Actual Leaving Water Setpoint equals the Leaving Water Setpoint (AI-4). If the zone temperature sensor is missing or unreliable, or if there is an unreliable zone temperature value at the ADF point, no reset occurs and the Actual Leaving Water Setpoint equals the Leaving Water Setpoint (AI-4). If the Leaving Water Sensor (AI-3) becomes unreliable, the compressor command is forced to zero. Return Water Reset When the Return Water Reset option is chosen, a Return Water Temperature (RWT) sensor (AI-1) is required. Four variables are used to set up the reset ramp that calculates the Actual Leaving Water Setpoint: Leaving Water Setpoint (AI-4) (LWSP) Leaving Water Reset Band (AI-5) (LWRB) Return Water High Limit (RWHL) Return Water Reset Band (RWRB) OEM Reciprocating Chiller 13

14 LWRB LWSP (RWLL=RWHL-RWRB) RWLL RWRB RWHL RESETS3 Figure 6: Return Water Reset, OEM, Reciprocating Chiller As the Return Water Temperature increases above the Return Water Low Limit (RWLL), the controller decreases the Actual Leaving Water Setpoint from its Leaving Water High Limit (Leaving Water Setpoint + Leaving Water Reset Band) to the Leaving Water Setpoint. When Return Water Temperature reaches the Return Water High Limit, the Actual Leaving Water Setpoint equals the Leaving Water Setpoint (AI-4). If the Return Water Temperature sensor is missing or unreliable, no reset occurs and the Actual Leaving Water Setpoint equals the Leaving Water Setpoint (AI-4). If the Leaving Water Sensor (AI-3) becomes unreliable, the compressor command is forced to zero. When Return Water Reset is chosen, a Fail Smart Logic option is also available. When chosen it has the following characteristics. If the Leaving Water Sensor (AI-3) becomes unreliable, the controller switches from Leaving Water control to Return Water control. Actual Return Water Setpoint equals Leaving Water Setpoint (AI-4) plus an adjustable Leaving Water Setpoint Offset. This value takes into account the temperature differential between leaving and returning water temperatures; typically, about 10 F. If both the Leaving and Return Water sensor are unreliable, the compressor command is forced to zero. Remote Reset This is not an option in HVAC PRO for Windows software for the reciprocating chiller path. This is an application where a customer wants to reset Leaving Water Setpoint from a remote signal, such as a 4-20 ma source, rather than Outdoor Air, Zone Temperature, or Return Water. 1. To offer this remote signal feature, select Outdoor Air Reset during the question and answer session. Answer all other questions. When finished, the Outdoor Air Temp input is AI1. 14 OEM Reciprocating Chiller

15 2. Double click on AI1 (Outdoor Air Temp) and change the name (i.e., Remote Signal). Change sensor type to voltage. Update input low range to 0V (0 ma) or 2V (4 ma) to input high range 10V (20 ma). Update output low range to 0 and output high range to Go to parameters and double click on Outdoor Air High Limit. Change the name to Remote Signal High Limit (RSHL). Change the value to 100. Remote Signal Low Limit (RSLL) remains at zero. 4. Double click on Outdoor Air Reset Band. Change name to Remote Signal RB (RSRB). Change value to 100. LWRB LWSP (RSLL=RSHL-RSRB) RS = Remote Signal RSLL RSRB Figure 7: Remote Signal Reset RSHL RESETS4 As the RS increases above the Remote Signal Low Limit (RSLL), the Actual Leaving Water Setpoint decreases from it s Leaving High Limit (Leaving Water Setpoint + Leaving Reset Band) to the Leaving Water Setpoint. When the RS reaches the Remote Signal High Limit, the Actual Leaving Water Setpoint equals the Leaving Water Setpoint (AI-4). If the RS sensor is missing or unreliable, no reset occurs and the Actual Leaving Water Setpoint equals the Leaving Water Setpoint (AI-4). If the Leaving Water Sensor (AI-3) becomes unreliable, the compressor command is forced to zero. Ramping Strategy The ramping strategy applies to all three reset options. When a reset function is used, a Ramping of the Compressor Command is also issued. Two adjustable variables setup the ramp as needed. These are Ramp Output and Ramp Time. The Ramp is used to meter the Proportional Command into the Sequencer when conditions don t require a quick startup of all stages. For example, if the Outdoor Air Temperature (OAT) is at Outdoor Air Low Limit (OALL), with OALL being equal to Outdoor Air High Limit minus Outdoor Air High Limit (OAHL). When the OAT is at OAHL, the Proportional Command is fed to the sequencer at the same rate as it is calculated. But if the OAT drops below the OAHL, the Proportional Command is ramped to the Sequencer. The allows for a slower start up of stages. OEM Reciprocating Chiller 15

16 Leaving Water Low Limit? Outdoor Temperature Lockout? Ice Mode Control? If the Leaving Water Temperature drops below an adjustable Leaving Water Low Limit for more than three seconds, the compressor command is forced to zero immediately. A Leaving Water Low Limit Alarm (BD) point triggers on. Once the Leaving Water Temperature rises above the Leaving Water Low Limit by an adjustable Leaving Water Low Limit Differential, a normal control sequence is initiated just as in startup. Default values are 15 F for the Leaving Water Low Limit and 5 F for the Leaving Water Low Limit Differential. Leaving Water Low Limit affects compressor commands only. All Pump logic, if used, remains unaffected. Outdoor Temperature Lockout, if chosen with the HVAC PRO for Windows software puts the controller into a Shutdown mode whenever it senses the temperature is below the adjustable Outdoor Temperature Lockout setpoint for more than five minutes. The Outdoor Temperature Lockout Status (BD) point is triggered. Once the Outdoor Temperature rises above the Outdoor Temperature Lockout by an adjustable Outdoor Temperature Lockout Differential, a normal transition from shutdown to the prevailing mode occurs. Outdoor Temperature Lockout affects any used pump control. Note: This feature requires an outdoor air sensor. If Ice Mode Control is selected, four options to initiate the mode of operation are available: Binary Input (BI) N2 Command from FMS Both BI and N2 with N2 priority Both BI and N2 with equal priority Equal priority means first on, last off. Upon entering the ice mode from either BI or N2 activation, the main PI control loop is disabled. The current Leaving Water Temperature is compared to the Ice Mode Setpoint. If it is above the setpoint, the Compressor Command is forced to 100%. When the Leaving Water Temperature drops below the Ice Mode Setpoint minus 0.1 F, the Compressor Command is forced to 0%. The Compressor Command is not a proportional change from 100 to 0%. These are the only two levels of Compressor Command during the Ice Mode. Once the Compressor Command falls to 0%, or the Ice Mode deactivates, the control returns to the Occupied or Unoccupied mode as required by binary inputs or software commands. The control does not cycle to maintain an Ice Mode Setpoint. The BI or N2 command that started the Ice Mode must be released and enabled to start the procedure again. Leaving Water Low Limit is not in effect during this mode. 16 OEM Reciprocating Chiller

17 Note: The feature may require chiller manufacturer to add/change the components to their system. Make sure manufacturer s representative and/or manufacturer is aware of this feature requirement. Is a Demand Limiting Input Needed? Select Pump Logic Single Pump Control Dual Pump Control If Demand Limit Input (AI-1) is selected with the HVAC PRO for Windows software, it affects the control strategy as follows. This input inversely limits the Compressor Command for external demand limiting control strategies. As the input goes from 0-10 VDC, the Compressor Command is proportionally limited from 100 to 0%. For example, if the Demand Limit Input is 5 VDC, the Compressor Command cannot exceed 50%. If 8 VDC is present, the maximum Compressor Commands is 20% and so on. The Demand Limiting function can operate when the control is in the Occupied or Unoccupied modes only. Demand Limiting does not occur while in the Ice Mode. A monitor-only Demand Limit Override (BD) initiates whenever the Demand Limit Input effects the Compressor Command. After answering yes or no to this question, you must then select pump type. Choose single or dual pumps control. When Single Pump Control is selected, a BO and BI point are assigned as Pump and Pump Status respectively. The pump is commanded on unless it is in the Shutdown or Restart mode, or the Outdoor Temperature Lockout is enabled. After the Pump is energized, an adjustable Pump Status Time Delay occurs allowing verification of Pump Status. If Pump Status is verified within this time period, normal control occurs. If Pump Status is not verified, a Pump Failure Alarm (BD) point initiates. The Pump remains energized. When dual pump control is selected, one BI point and two BO points are assigned as Pump 1 and Pump 2 Pump Status respectively. The user also has the option of controlling the lead pump through the BI or N2 command. The lead pump is commanded on unless it is in the Shutdown or Restart mode, or if the Outdoor Temperature Lockout is enabled. After the lead Pump is energized, an adjustable Pump Status Time Delay occurs allowing verification of Pump Status. If Pump Status is verified within this time period, normal control occurs. If Pump Status is not verified, a Lead Pump Failure Alarm (BD) point is initiated and the lead Pump de-energizes. As soon as a Lead Pump Failure is initiated, the lag Pump energizes. If Pump Status is verified within the Pump Status Time Delay, normal control occurs. If Pump Status is not verified within the Pump OEM Reciprocating Chiller 17

18 Status Time Delay, a Lag Pump Failure Alarm (BD) initiates. The lag pump, however, remains energized. Note: Dual Pump Control is limited to six stages of leaving water control. If the Lag Pump is operating due to lead pump failure, and the lead pump has been repaired, the only way to restart the Lead Pump, is to cycle power on the control or transition to shutdown and back again. This begins a normal startup sequence. If a Chilled Water Pump Control is selected, and the Pump is de-energized for any reason, and Pump Status remains on for more than one minute, a Jumpered Flow Switch Alarm (BD) is initiated. This condition puts the controller in a Shutdown mode where it remains until the Jumpered Flow Switch Alarm is cleared. This condition can be cleared by opening the Pump Status input or cycling power to the controller. Flow Interlock Input? Modes of Operation Occupied Mode If Pump Control is not selected with HVAC PRO for Windows, a Pump Status (BI) point can be assigned to monitor status of an independent pump. Regardless of how the Pump Status point is selected, it has the following characteristics. After a transition from Shutdown mode or Restart Delay, the controller waits an adjustable Pump Status Time Delay for a verification of Pump Status. If Pump Status is verified during this Pump Status Time Delay, normal control occurs. If Pump Status is not verified, a Pump Failure (BD) point is initiated. If Pump Status was previously verified and then lost for a period of three seconds, the Compressor Commands are forced to zero. If Pump Status is lost for a period of one minute, the Pump Failure Alarm is initiated. Once Pump Status is again verified, normal control occurs and the alarm is cleared. Up to four modes of operation are available in the control strategy including Shutdown, Ice Mode, Occupied, and Unoccupied. Each is described below in priority order, first to last. Occupied mode controls the Leaving Water Temperature to the Leaving Water Setpoint (AI-4) located on the front of the controller. If a reset option is used, the Actual Leaving Water Setpoint may vary depending on the reset variable. This mode can be enabled or disabled through a hardware (BI) or software (BD) point or both. Upon entering the Occupied mode from any other mode, the controller goes through an adjustable Occupied Time Delay. This allows a Pump to start and flow to be verified. It also allows for the water loop to equalize in temperature before deciding how much cooling capacity is needed. 18 OEM Reciprocating Chiller

19 Unoccupied Mode Select Method to Initiate Occupied Mode Shutdown Mode Select Method to Initiate Shutdown Mode Unoccupied mode controls the Leaving Water Temperature to the Unoccupied Leaving Setpoint. This mode can be enabled or disabled through a hardware (BI) or software (BD) point or both. If a reset option is used, it is disabled during this mode. You must choose No or one of the following: Binary Input (BI) N2 Command from FMS Both BI and N2 with N2 priority Both BI and N2 with equal priority Equal priority means first on, last off. Shutdown mode is a multi-purpose catchall mode of operation. It can be enabled or disabled using a hardware (BI) or software (BD) point, or both, depending on how it was configured with HVAC PRO for Windows. Other conditions that affect Shutdown are Outdoor Temperature Lockout, Leaving Water Low Limit, or a Pump Failure. When Shutdown mode is enabled, the compressor command is forced to 0%. Leaving Water Low Limit and Pump Failure has no effect on pump control. Shutdown mode is a multi-purpose catchall mode of operation. It can be enabled or disabled using a hardware (BI) or software (BD) point, or both, depending on how it was configured with HVAC PRO for Windows. Other conditions that affect Shutdown are Outdoor Temperature Lockout, Leaving Water Low Limit, or a Pump Failure. When Shutdown mode is enabled, the compressor command is forced to 0%. Leaving Water Low Limit and Pump Failure has no effect on pump control. OEM Reciprocating Chiller 19

20 Notes Controls Group FAN E. Michigan Street HVAC PRO for Windows User s Manual P.O. Box 423 Printed in U.S.A. Milwaukee, WI OEM Reciprocating Chiller

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units... Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

Microprocessor-Based Leaving Water Control Model AS-UNT33n-l. Installation Maintenance Bulletin No. IM 552 December, 1993 No.

Microprocessor-Based Leaving Water Control Model AS-UNT33n-l. Installation Maintenance Bulletin No. IM 552 December, 1993 No. MeQuw@ nstallation Maintenance Bulletin No. M 552 December, 1993 Form No. 573899Y and Data Microprocessor-Based Leaving Water Control Model AS-UNT33n-l This controller is offered as an option on ALR C

More information

Metasys Integrator Compu-Aire Application

Metasys Integrator Compu-Aire Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Compu-Aire Application lntroduction Page 3 Application Details

More information

Metasys Integrator Vilter Application

Metasys Integrator Vilter Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 1294 APPLICATION NOTE Metasys Integrator Vilter Application lntroduction Page 3 Application Details *3

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

BACnet Points List for Single Compressor Water to Water PROSSWWE-01 The network variables will be listed by point type instance convention. 2:1 would mean point type 2, point instance 1. All volatile (Output) type points will revert to the uncommanded values after a power

More information

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Introduction

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Manual: 200-393O Supersedes: 200-393N Date: 2-26-6 Page of 8 CONTENTS Shipping

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

iworx Air Side Application Wiring Guide

iworx Air Side Application Wiring Guide iworx Side Application Wiring uide Pages ASM2 Sequence of peration & ypical Wiring 1 ALM2 Sequence of peration & ypical Wiring 2 U2 Sequence of peration, Flow iagram & ypical Wiring 3 - U3 Sequence of

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Product Bulletin T601DFH-4, T602DFH-4, T603DFH-4, T604DFH-4, T605DFH-4, T601DFH-4+PIR, T602DFH-4+PIR,

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

GeneSys Air-Cooled Screw Compressor Chiller

GeneSys Air-Cooled Screw Compressor Chiller Operation Manual OM AGSB-5 Group: Chiller Part Number: 331373201 Date: June 2005 Supersedes: OM AGSB-4 GeneSys Air-Cooled Screw Compressor Chiller AGS 230A/B through AGS 475A/B, 60 Hertz AGS 206A/B through

More information

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 Application Note 140-1042 Building Technologies Table of Contents Overview... 4 Hardware

More information

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Open Protocol Data Communications

Open Protocol Data Communications MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

1.0 Digital Controller

1.0 Digital Controller 1.0 Digital Controller...1 1.1 Display Function Keys...1 1.2 Thermostat Display...2 1.3 Controller hardware input output points... 4 2.0 Sequence of Operation...5 2.1 States of Operation...5 2.2 Modes

More information

MicroTech Water-Cooled Screw Chiller Controller

MicroTech Water-Cooled Screw Chiller Controller BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application 2273 Application Note 140-1045 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER BARD MANUFACTURING COMPANY Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual: 2100-393C Supersedes: 2100-393B File: Volume III Tab

More information

Metasys Integrator Cleaver-Brooks Application

Metasys Integrator Cleaver-Brooks Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Cleaver-Brooks Application lntroduction Page Application Details

More information

Ice Rink (Single and Dual Configurations) Custom Control Features

Ice Rink (Single and Dual Configurations) Custom Control Features & M&M Refrigeration, Inc. Computer Control System Ice Rink (Single and Dual Configurations) Custom Control Features REVISION DATE DESCRIPTION - 4/20/05 Original release. A 09/21/98 Update Chiller Pump

More information

Metasys Integrator McQuay Application

Metasys Integrator McQuay Application Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator McQuay Application Introduction Page * Application Details * Component

More information

Product Manual SZ2161. Description The SZ2161 is a microprocessor-based controller designed for water source heat pump plant control applications.

Product Manual SZ2161. Description The SZ2161 is a microprocessor-based controller designed for water source heat pump plant control applications. Product Manual SZ2161 Heat Pump Water Loop Controller Description he SZ2161 is a microprocessor-based controller designed for water source heat pump plant control applications. Features Stand-alone or

More information

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of

More information

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application 2070 Application Note 140-1040 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

OWNER S MANUAL. Part Number P

OWNER S MANUAL. Part Number P OWNER S MANUAL CPV230 Commercial Thermostat Part Number P374-2300 CONTENTS Page GENERAL...2 CONFIGURATION...3-12 Thermostat Display...3 Heat or Cool Indicator...4 Thermostat Front Panel Buttons...4 Thermostat

More information

TEC210x-2 Series Networked Thermostats

TEC210x-2 Series Networked Thermostats Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Code No. LIT-1201736 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH,

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH, SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS Options AG3 Unit-Mounted Ductstat Options AG15, AG16 A = Ductstat Temperature Module P/N 115848 B = Stage Adder Module, P/N 115849 (quantity varies

More information

Owner s Manual. Part Number 33CS250-01

Owner s Manual. Part Number 33CS250-01 33CS Commercial Programmable Thermostat IMPORTANT: Read entire instructions before programming the thermostat. Owner s Manual Part Number 33CS250-01 GENERAL Carrier s 7-day, commercial, programmable thermostats

More information

Table of Contents. WSHP Open v3

Table of Contents. WSHP Open v3 WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1

More information

CONTENTS. Installation Guide. VT7200 Series

CONTENTS. Installation Guide. VT7200 Series VT7200 Series Installation Guide For mercial HVAC Applications November 2015 CONTENTS Installation 2 Location 2 Installation 2 Configurable BI/UI inputs overview 4 Network ready 6 Terminal, Identification

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

Application Guide. CCU2 Chiller Controller. Self-Contained Interoperable Controller Model UCP-1 for Software Version 2.

Application Guide. CCU2 Chiller Controller. Self-Contained Interoperable Controller Model UCP-1 for Software Version 2. Application Guide 505-022-2 CCU2 Chiller Controller Self-Contained Interoperable Controller Model UCP-1 for Software Version 2 SUPERSEDES: August 9, 2013 EFFECTIVE: December 20, 2014 Plant ID: 001-4016

More information

OWNER S MANUAL. Part Number P CONTENTS

OWNER S MANUAL. Part Number P CONTENTS OWNER S MANUAL CPV210 Commercial Non-Programmable Thermostat Part Number P374-2100 CONTENTS Page GENERAL...2 CONFIGURATION...3-7 Thermostat Display...3 Heat or Cool Indicator...4 Thermostat Front Panel

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

Installation Guide Bacharach Communications Adapter HGM-MZ to Johnson Controls Metasys N2 Network (Electrically Isolated N2 Port Version)

Installation Guide Bacharach Communications Adapter HGM-MZ to Johnson Controls Metasys N2 Network (Electrically Isolated N2 Port Version) Installation Guide Bacharach Communications Adapter HGM-MZ to Johnson Controls Metasys N2 Network (Electrically Isolated N2 Port Version) 621 Hunt Valley Circle New Kensington, PA 15068 Tel: 724-334-5000

More information

Advanced Installation and Configuration Instructions

Advanced Installation and Configuration Instructions TP-WEM01-A Performance Series AC/HP Wi- Fi Thermostat Carrier Côr Thermostat Advanced Installation and Configuration Instructions Table of contents How to Use This Document... 3 Wiring Diagrams... 4 Installations

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47 WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

INITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER

INITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER INITIAL START-UP CHECKLIST FOR 23XL HERMETIC SCREW LIQUID CHILLER (Remove and use for job file.) MACHINE INFORMATION: NAME ADDRESS JOB NO. MODEL CITY STATE ZIP S/N DESIGN CONDITIONS: TONS BRINE FLOW RATE

More information

TEC2100 Series Networked Thermostats

TEC2100 Series Networked Thermostats Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2018 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-537-01 1/9/2018 Verify that you have the most current version of this document

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

P/N f. HomeWorks QS Palladiom Thermostat Configuration Guide

P/N f. HomeWorks QS Palladiom Thermostat Configuration Guide HomeWorks QS Palladiom Thermostat Configuration Guide Table of Contents Description...4 Step : Identify the HVAC Equipment and Confirm Device Installation...5 Identify the HVAC Equipment...5 Confirm Device

More information

Multistate Alarm. Introduction

Multistate Alarm. Introduction Object Dictionary 1 Multistate Alarm Introduction The Multistate Alarm object adds the alarming capability for a Boolean or multistate attribute for any object, such as the Present Value of a Binary Input

More information

ESSEX ENGINEERING CORPORATION

ESSEX ENGINEERING CORPORATION WATER/WASTEWATER TREATMENT CONTROL SYSTEMS AND SUBSYSTEMS 2000 SERIES CONTROL SYSTEMS: 2000 series are for surface mounting inside a control cabinet Model 2024 Electronic Alternator Duplex (two pump) pump

More information

MC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option

MC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option MC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option The MC4000 has 2 stages of cooling control available for each connected air conditioner. It is

More information

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application 2023 Application Note 140-1052 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 6 Hardware Outputs...

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

DACC - NMDA BUILDINGS

DACC - NMDA BUILDINGS A PROJECT FOR: LAS CRUCES, NEW MEXICO PROJECT LOCATION LOCATION MAP INDEX OF DRAWINGS: CV001 - COVER SHEET M101 - OVERALL CAMPUS STEAM UTILITY PLAN M102 - DACC DAMA 341 PLAN M103 - DACC LRC & CLASSROOM

More information

Water Source Heat Pump Module Technical Guide

Water Source Heat Pump Module Technical Guide Factory Packaged Controls Tulsa Water Source Heat Pump Module WSHP WSHP Protection Module Module Orion No.: OE334-23-WPM-A NON-DIGITAL COMPRESSORS #1 THRU #4 +5V SUCT. +5V SUCTION PR. SENSOR PRES PRES

More information

Product Manual SZ1022/SZ1031/SZ1035/

Product Manual SZ1022/SZ1031/SZ1035/ Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TPC VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIADI&O062705 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 7,8

More information

TEC Networked Multi-Stage Economizer Thermostat

TEC Networked Multi-Stage Economizer Thermostat Installation Instructions Issue Date January 19, 2005 TEC2104-2 Networked Multi-Stage Economizer Thermostat Application The TEC2104-2 thermostat is an N2 networked thermostat that provides control of single-

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT86X0U5X00B 2 heating / 2 Cooling for Rooftop unit and Indoor air quality 3

More information

INITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER

INITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER INITIAL START-UP CHECKLIST FOR 19XR HERMETIC CENTRIFUGAL LIQUID CHILLER (Remove and use for job file.) MACHINE INFORMATION: NAME JOB NO. ADDRESS MODEL CITY STATE ZIP S/N DESIGN CONDITIONS: TONS BRINE FLOW

More information

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

ZIP Economizer Method of Operation Sequence of Operation States Virgin State The ZIP Economizer comes shipped from the factory in this state. Setup Incomplete will be displayed. No control will occur until

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide SE8600 Series Room Controllers 2 TABLE OF CONTENTS Overview 2 SE8600 Rooftop Unit and Indoor Air Quality Controllers 3 SE8600UxBxx 2 Heating

More information

Application and Instructions for Field Adjustment of the Control (Model FX06) in Digital Control Option D12A, Space Control with Discharge Air Reset

Application and Instructions for Field Adjustment of the Control (Model FX06) in Digital Control Option D12A, Space Control with Discharge Air Reset Form CP-MAPS-D12A with FX06 (Version A.3) Obsoletes CP-MAPS-D12A with FX06 (Version A.2) Applies to: MAPS II Control Option D12A Application and Instructions for Field Adjustment of the Control (Model

More information

Pathfinder Air-Cooled Chillers

Pathfinder Air-Cooled Chillers Operating & Maintenance Manual OMM 1123 Group: Chiller Part Number: OMM 1123 Date: January 2012 Supercedes: December 2011 Rev 00 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes Models

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT8600 Rooftop Unit Heat Pump and Indoor Air Quality Controllers 3 VT86X0U5X00B

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application 2050 Application Note 140-1136 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware Outputs...

More information

Platinum Touch/Rotem One Touch

Platinum Touch/Rotem One Touch User Manual Platinum Touch / Rotem One Touch Platinum Touch/Rotem One Touch Climate Controllers Ag/MIS/UmGB-2583-05/18 Rev 1.0 P/N: 116556 Platinum Touch/Rotem One Touch User Manual Revision: N.1.0 of

More information

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide Factory Packaged Controls MHGRV-X Controller Field Technical Guide TABLE OF CONTENTS CONTROLLER OVERVIEW... 3 Features... 3 INSTALLATION & WIRING... 4 Important Wiring Considerations... 4 MHGRV-X Controller

More information

ACT2-CS Convenience Store Controller

ACT2-CS Convenience Store Controller Refrigeration Systems Technical Manual 804 Product Bulletins Section Product Bulletin Issue Date 0899 ACT2-CS Convenience Store Controller The ACT2-CS Convenience Store Controller is a fully programmable,

More information

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date

More information