APPLICATION OF HYDROCARBON REFRIGERANTS IN LOW TEMPERATURE CASCADE SYSTEMS

Size: px
Start display at page:

Download "APPLICATION OF HYDROCARBON REFRIGERANTS IN LOW TEMPERATURE CASCADE SYSTEMS"

Transcription

1 APPLICATION OF HYDROCARBON REFRIGERANTS IN LOW TEMPERATURE CASCADE SYSTEMS B. M. ADAMSON Refrigeration Engineering Pty Ltd PO Box 1197 Unanderra NSW 2526 Australia Fax ; ben_adamson@refeng.com.au ABSTRACT The paper reviews choice of hydrocarbon refrigerants for cascade refrigeration systems, and criteria to be considered in selecting various system components. It also discusses the author s experience of problems in application of hydrocarbon refrigerants at temperatures down to -100 C, and solutions to many of these problems. Two case studies are included, one for a small direct expansion system using scroll compressors, and one for a large system with flooded evaporators using oil-flooded screw compressors. 1. INTRODUCTION Refrigeration Engineering is active in the process refrigeration market, mainly for oil, gas and petrochemical industries, and particularly in refrigerated vapour recovery systems. The vapours for recovery are generally hydrocarbons the most common application is gasoline (petrol) vapour recovery at loading terminals, but these systems are also used to recover other hydrocarbons, such as benzene, propylene oxide, naphtha, acrylonitrile, methylene chloride etc. In order to meet the required emission limits, it is necessary to cool vapour streams typically to -75 C or lower, to condense out the vapours to be recovered. As most applications are in areas already classified as hazardous due to flammability of the vapours handled by the vapour recovery system, and in industries which are comfortable with handling flammable materials, there is generally no objection to hydrocarbon refrigerants on the grounds of flammability, nor additional cost involved. Refrigeration Engineering uses hydrocarbon refrigerants as standard in these vapour recovery units, rather than hydrofluorocarbons, for reasons of lower cost of refrigerants and lower environmental effects in case of leakage. Power cost is generally not a major factor, although there can be small advantages for hydrocarbons in some cases. These refrigerants have been applied in cascade refrigeration systems over a wide range of sizes, using screw, reciprocating and scroll compressors. 2. REFRIGERANT PROPERTIES Properties of refrigerants relevant to cascade systems, comparing hydrocarbons to other refrigerants, are summarised in table CHOICE OF REFRIGERANT For the high stage of the cascade, typically working between about -30 C evaporating and +45 C condensing, commonly available hydrocarbons are propane (R-290) and propylene (R-1270). Refrigerant grade high purity propane is readily available in some countries, but in others only commercial grade is available. Commercial propane varies quite significantly in composition it

2 may be as high as 99% or as low as 90% propane. The balance is mainly ethane and butane, and depending on relative amounts of these, the properties as a refrigerant may be significantly affected, with large temperature glide in direct expansion systems and partial fractionation in flooded systems. Propylene is widely used in making polypropylene, and polymer grade which is better than 99% propylene is readily available in most areas where refineries and petrochemical plants are located. For this reason we generally prefer to use propylene rather than propane, unless there are other particular reasons favouring propane. The higher pressure of propylene, allowing effectively a 5K lower evaporating temperature than propane, is also useful in cascade systems, although can be a disadvantage in air-cooled systems operating areas with high summer temperatures. Choice of refrigerant for the low stage of the cascade system follows similar logic to the high stage. Ethylene is widely used in making polyethylene and high-purity polymer grade is readily available, although obtaining the relatively small quantities for refrigerant is occasionally difficult. (Ethylene is also commercially used in fruit ripening, especially bananas and tomatoes.) Ethane has fewer direct uses, and is less readily available, so we have standardised on ethylene as the low stage refrigerant when using hydrocarbons. The higher pressure of ethylene also allows effectively a 15K lower evaporating temperature than ethane, which is critical in the temperature ranges where we commonly work. The main disadvantage of ethylene is its high specific heat ratio (see table 1) which leads to relatively high discharge temperature. This can be controlled easily in oil-flooded screw compressors, but can be a problem at high compression ratios in scroll and reciprocating compressors if suction superheat is high. Table 1. Refrigerant properties relevant to cascade systems (Coolpack) High temperature refrigerants Boiling point* at 1 atm, C Sat. temp* at 2000 kpag, C Specific heat ratio, k = C p /C v Suction vol. flow, m 3 /hr for 10 kw load at -30/45 C Propane Propylene R-134a R-404a R-407c R Low temperature refrigerants Boiling point* at 1 atm, C Sat. temp* at 2000 kpag, C Specific heat ratio, k = C p /C v Suction vol. flow m 3 /hr for 10 kw load at -80/-25 C Ethane Ethylene R R-508a * Dewpoint used for zeotropic refrigerants ** Isentropic efficiency 0.7 for all cases 4. COMPONENT SELECTION Power**, kw for 10 kw load at -30/45 C Power**, kw for 10 kw load at -80/- 25 C Selection of components such as compressors, expansion valves, condensers and other components for hydrocarbon service is complicated by the fact that there are generally no published ratings for

3 these, particularly in the smaller sizes of equipment. In addition, many manufacturers do not want to be involved in applications for their products with hydrocarbon refrigerants or in hazardous areas. Application assistance, as well as any warranty, is usually not available from manufacturers and techniques have been developed within our company for calculation of capacity ratings on hydrocarbon refrigerants. Capacity rating techniques are regarded as proprietary information, and are not discussed here. The discussion below is confined to mechanical issues. 4.1 Compressors The required compressor capacities for the common sizes of vapour recovery systems can mainly be handled with either fully hermetic scroll compressors or semi-hermetic reciprocating compressors, with up to two in parallel. The main mechanical issue is ensuring discharge temperature is kept within acceptable limits, especially for the low stage ethylene compressors. Compatibility between compressor materials (particularly motor winding insulation for hermetic compressors) and refrigerants was checked as far as possible before trials were started, but full information was not always available. These compressors are designed to operate with the windings exposed to lubricating oils which are a mixture of many hydrocarbons, and have also been operating in domestic refrigeration in Europe and other areas for many years. On this basis, compatibility of windings with hydrocarbon refrigerants was not expected to be a problem, and this has been proven in operation. There are no problems between hydrocarbon refrigerants and the metals commonly used in refrigeration compressors, including steel, aluminium, zinc, copper, tin, lead and their alloys. 4.2 Lubricating oils Selection of lubricating oils for hydrocarbon applications operating down to about -50 C is not difficult. The solubility of hydrocarbons in oils is similar to solubility of common HFC and HCFC refrigerants in their respective lubricants, so similar oil viscosity grades are generally used. For the low side of the cascade, operating at -70 C to -100 C, there are again few problems with the oil as long as some care is taken. Oil return in DX systems has proven trouble-free in systems down to -85 C (the limit of our DX experience) provided normal good practice is followed in piping design for oil return. Although the oil may be returning at temperatures well below its rated pour point, the remaining dissolved refrigerant in oil returning from DX evaporators reduces viscosity and pour point and allows normal oil return. Oil return from flooded evaporators can also be managed using normal techniques, but after the oil-refrigerant mixture has been distilled to remove excess liquid refrigerant, care must be taken to avoid exposing this oil to low temperatures in the suction line or inlet area of the compressor, as oil freezing will occur. Oil flooded screw compressors operating in the low temperature stage of cascade systems can experience several problems due to the low temperatures at the suction end, unless special precautions are taken. Oil management in the low temperature sections of cascade systems with oilflooded screw compressors and flooded evaporators is critical to successful operation of these systems. Oil-flooded screw compressors are mainly used in larger systems, where flooded evaporators are also more common. In a screw compressor, oil flows into the suction gas inlet area from various sources - escaping from the suction end bearings, lubricating oil from the slide valve, hydraulic oil from the slide valve cylinder, as well as oil returning from the evaporators. This oil is carried back through the compressor by the suction vapour, which may be at -70 C to -100 C. The lubricating oil is initially warm, which reduces solubility of hydrocarbon, and after pressure is reduced to suction pressure,

4 solubility is further reduced, with the result that the oil may contain quite low concentrations of dissolved refrigerant, and so pour point may be close to that of the pure oil. When this oil contacts the cold surfaces of the compressor in the suction area, the oil may freeze and significant accumulations of the solid oil can occur. For screw compressors in the low stage of cascade systems, another problem can occur if the capacity control slide valve remains in one position for a long period typically, this can occur either at maximum or minimum capacity. On many common makes of screw compressor, the hydraulic cylinder used to drive the slide valve is below the suction inlet, and attached to the suction casting. Heat transfer from the cylinder to the cold suction area can result in excessively viscous oil in the cylinder, leading to slow or no response when the capacity control system tries to move the slide valve. Heating of the capacity control cylinder may be required. 4.3 Expansion and solenoid valves As for compressors, there are no metal compatibility issues with standard components such as expansion and solenoid valves when used with hydrocarbon refrigerants. In the author s experience, obtaining mechanical thermostatic expansion (TX) valves with suitable charges for hydrocarbon service ranges from difficult to impossible, especially for ethylene some manufacturers will not supply them at all, and the few who do generally quote long lead times and high prices, such that they are impractical. Future availability of spare parts (such as TX valve power elements with special charges) is also a significant consideration. In direct expansion hydrocarbon systems, the author s company has used only electronic expansion valves, and the problem with these can be obtaining them with suitable certification for use in hazardous areas. Because the large majority of our work is in hazardous areas, many years ago we developed solenoid coils with hazardous area certification to fit Danfoss solenoid valves. The same coils can also be used on Danfoss electronic expansion valves, and for this reason, we have used only these valves on our direct expansion systems. In our particular systems, the electronic expansion valves also offer us other advantages in controllability down to extremely low load conditions, which is an essential feature of vapour recovery systems where load can vary anywhere between 100% and zero. Sizing of expansion valves usually must be done from basic principles, as manufacturers generally will not provide ratings on hydrocarbons, particularly for the low temperature side of the cascade. 4.4 Seals and O-rings Elastomers which are compatible with mineral oils are generally also compatible with ethane, propane and butane, which are similar molecules to natural or synthetic hydrocarbon oils, but smaller. Some literature suggests that excessive swelling may occur when some elastomers are exposed to propylene, although the literature is not unanimous. In the case of O-rings, limited swelling is not a major problem as long as the O-ring remains confined, but if the item is disassembled then re-assembly may be difficult or impossible with a swollen O-ring. A less well-known effect may occur when an elastomer absorbs significant amounts of hydrocarbon under pressure, and is then rapidly depressurised. The hydrocarbon absorbed within the elastomer may not be able to desorb sufficiently rapidly by diffusion through the elastomer, and gas bubble formation within the elastomer can cause an explosive deterioration (Parker), leading to a shredded or blistered appearance. The effect is uncommon, but if it occurs, it can cause leakage from an O-ring without the O-ring being disassembled or otherwise disturbed. Higher pressure systems are more prone to this problem, so it should be considered for the low temperature stage of the cascade, where shutdown pressures may be substantially higher than is usually seen in normal refrigeration systems. The relatively small molecule size of ethane and ethylene (molecular weight

5 30 and 28) also increases diffusion of the gas into the O-ring material (compared to R-23 for example, molecular weight 70) and therefore increases the tendency of this type of failure. Another problem can occur on screw compressors with O-ring seals between casing sections. The O-ring sealing the joint between the suction section and the rotor section of the compressor casing may see temperatures close to suction temperature in some parts of the joint. O-ring elastomers generally lose their elasticity at very low temperatures, and leakage can result from hardening of the O-ring at low temperatures. (The Challenger space shuttle disaster was attributed to this problem.) Selection of O-ring material which will retain elasticity at very low temperatures and will resist explosive decompression failure as well as meeting all the other compatibility criteria is not always possible, and redesign to ensure that O-rings never see these temperatures may be required in some cases. 4.5 Heat exchangers There are no particular problems with heat exchangers for hydrocarbon refrigerant service. Commercial software, such as that from HTFS and HTRI, is available for thermal design of shell and tube chillers with hydrocarbon refrigerants. Commercial software is not generally available for hydrocarbons in direct expansion evaporators, and these must be sized using basic design principles, where ratings with hydrocarbon refrigerants are not available from manufacturers. 5. CASE STUDIES 5.1 Gasoline vapour recovery A system was commissioned in October 2005 at an oil refinery for recovery of mixed gasoline and benzene vapour from air. In order to meet the required emission standard, the vapour was cooled in three stages to -75 C, all at atmospheric pressure. Propylene was used in the 0 C and -30 C stages, and ethylene was chosen for the -80 C stage, for reasons outlined in section 3 above. Basic data for the system is shown in table 2, and the system is shown in Fig. 1. Table 2. Gasoline vapour recovery unit refrigeration data First stage Second stage Third stage Process vapour outlet temperature, C Refrigerant evaporating temperature, C Refrigerant Propylene Propylene Ethylene Process cooling load, kw 50 11* 6 Compressor type Hermetic scroll Hermetic scroll Hermetic scroll Evaporator type * excludes condensing load from third stage 2 x 50% Direct expansion, plate fin & tube 2 x 50% Direct expansion, plate fin & tube 2 x 50% Direct expansion, plate fin & tube The compressors were all hermetic scroll type. The only modification from standard was addition of a certified Ex d terminal box for hazardous area operation. High discharge temperatures were anticipated under some conditions on the low stage, and for this reason the third stage compressors were provided with liquid injection (this was a manufacturer s standard option.) Oil used in all compressors was an ISO VG32 grade polyol ester (POE) oil, with antiwear additives, specifically formulated for scroll compressors.

6 The load on the system can fluctuate rapidly and the system was designed to run anywhere between 100% and zero load, while remaining on line. Hot gas bypass maintains suction pressure at low or zero load conditions for all stages. Some intermittent flooding from the TX valves was anticipated after load changes, so suction separators have been used on all stages. The system operates over wide load range and can spend long periods at or close to zero capacity, but there have been no problems with oil return under any conditions. Figure 1. Gasoline vapour recovery unit (not complete, before shipment). 5.2 Ethylene liquefaction This system was commissioned in January 2001, for liquefaction of ethylene produced in a nearby petrochemical plant. The ethylene is stored as liquid at atmospheric pressure, at its saturation temperature of -104 C. The liquefaction process takes place under a slight pressure, normally at about -82 C, and the resulting liquid is then flashed into the storage tank with flash gas returned to the process stream via a compressor. A closed-loop ethylene two-stage refrigeration system is used as the low stage of a cascade refrigeration system, with propane used in the higher temperature stages, again in a two stage system. The process ethylene is cooled in four stages, two by the propane system and two by the ethylene system, and remains separated from the refrigerant ethylene at all times. (An open ethylene system, using the process ethylene also as refrigerant, was not used in order to prevent contamination of the process ethylene by oil used in the ethylene compressor.) High quality propane (>97%)was readily available for the high stage refrigerant. Basic data for the system is shown in Table 3, and the two-stage ethylene compressor is shown in Fig.2.

7 Table 3. Ethylene liquefaction system refrigeration data 1st stage 2nd stage 3rd stage 4th stage Refrigerant Propane Propane Ethylene Ethylene Refrigerant evaporating temperature, C Compressor type Single-stage screw, 1 x 100% Single stage screw, 1 x 100% Two stage screw 1 x 100% Evaporator type All evaporators flooded shell & tube, TEMA K shell type Design process cooling load is 685 kw at -88 C, with additional smaller loads at the intermediate temperatures. Ethylene compressor motor is 900 kw and propane compressor motor 1600 kw. The normal operating temperature for the low stage is -88 C, but the system must operate down to -100 C under some conditions. Use of an oil-flooded screw compressor in the low stage was not considered initially by the end user, due to concerns over oil management down to -100 C, despite the large cost saving compared to oil-free compressors which are normally used at these temperatures. Only after all the problems outlined above had been addressed in detail was the oilflooded screw concept accepted. This system is thought to be the lowest temperature application of an oil-flooded screw compressor anywhere in the world. Oil used was a VG150 polyglycol in the propane system, selected for its low hydrocarbon solubility and good resistance to dilution, and a VG68 synthetic hydrocarbon in the ethylene system, selected for its stability and low pour point. Figure 2. Two-stage oil-flooded screw ethylene compressor

8 The system has been operating continuously since commissioning, and demonstrates that hydrocarbon refrigerants can be successfully applied in large cascade systems with flooded evaporators. REFERENCES Coolpack software V.1.46, Department of Mechanical Engineering, Technical University of Denmark. Parker Hydraulics, Technical bulletin 5704B1-USA Explosive decompression resistant fluorocarbon polymers

VAPOUR RECOVERY DURING FUEL LOADING. Ben Adamson Principal Engineer Refrigeration Engineering Pty Ltd, NSW Australia

VAPOUR RECOVERY DURING FUEL LOADING. Ben Adamson Principal Engineer Refrigeration Engineering Pty Ltd, NSW Australia VAPOUR RECOVERY DURING FUEL LOADING Ben Adamson Principal Engineer Refrigeration Engineering Pty Ltd, NSW Australia ben_adamson@refeng.com.au ABSTRACT Volatile fuels such as gasoline and naphtha, and to

More information

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications. TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there

More information

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane.

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane. 1/1/12 RS-45 (R434A): Q & A 1 Q: What is RS-44? 1.Q: What is RS-45 A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-45 contain? A: RS-45 is

More information

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications: TECHNICAL DATA SHEET Features and uses of is a non-azeotropic blend of HFC with zero Ozone Depletion Potential et low Global Warming Potential (GWP), formulated to meet the requirements of the F-Gas Regulation

More information

Chapter 2. Alternatives to HCFCs and their Characteristics

Chapter 2. Alternatives to HCFCs and their Characteristics Alternatives to HCFCs and their Characteristics Refrigerant - General Chemical used in a cooling system, such as an air conditioner or refrigerator, as the heat carrier which changes from vapour to liquid

More information

R-407A R-448A R-449A

R-407A R-448A R-449A GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants

More information

HEAT PUMPS WITH HYDROCARBONS AS REFRIGERANTS FOR SMALL RESIDENTIAL BUILDINGS

HEAT PUMPS WITH HYDROCARBONS AS REFRIGERANTS FOR SMALL RESIDENTIAL BUILDINGS HEAT PUMPS WITH HYDROCARBONS AS REFRIGERANTS FOR SMALL RESIDENTIAL BUILDINGS E. Wobst, Professor, Main Department of Refrigeration & Cryogenics, Institute for Air-Conditioning and Refrigeration, Dresden,

More information

HFCs or the Old Refrigerants - what is the best Choice?

HFCs or the Old Refrigerants - what is the best Choice? HFCs or the Old Refrigerants - what is the best Choice? Hermann Halozan Institute of Thermal Engineering, Graz University of Technology Inffeldgasse 25 / B, A-8010 Graz, Austria, Phone: +43 316 873-7303

More information

Parilla Thermal Storage Project Case Study. May Page 1 of 11

Parilla Thermal Storage Project Case Study. May Page 1 of 11 Parilla Thermal Storage Project Case Study May 2014 Page 1 of 11 BACKGROUND Parilla Premium Potatoes is a large refrigerated storage facility (Figure 1) located in South Australia; the facility consists

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration

More information

PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR /R a. R E Low, B E Gilbert, T W Dekleva.

PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR /R a. R E Low, B E Gilbert, T W Dekleva. PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR- 1 2 5/R- 1 34 a R E Low, B E Gilbert, T W Dekleva IC1 Klea ABSTRACT IC1 Klea has developed HFC alternatives to R-22 and R-502 which include

More information

REFRIGERANT CHANGEOVER

REFRIGERANT CHANGEOVER Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants

More information

July 2012 was a significant date for the HVAC and Refrigeration industry as it saw the introduction of the Carbon Tax and the HFC Levy.

July 2012 was a significant date for the HVAC and Refrigeration industry as it saw the introduction of the Carbon Tax and the HFC Levy. Parilla Thermal Storage Project In 2013 Glaciem Cooling Technologies undertook the commercialisation of its Thermcold Thermal Storage system, the system which has been operating now for over two years

More information

10/4/2013. The Changing State of Refrigerants

10/4/2013. The Changing State of Refrigerants 10/4/2013 The Changing State of Refrigerants Refrigerant Chemistry CFC = Chlorofluorocarbon Rapid phase-out Stopped U.S. production in 1996 R-11, R-12, R-113, R-114, R-500, R-502 HCFC = Hydrochlorofluorocarbon

More information

Refrigerant changeover guidelines

Refrigerant changeover guidelines Refrigerant changeover guidelines HCFC R-22 to HFC R-407A/F, R-448A or R-449A for medium and low temperature applications HCFC R-22 to HFC R-407C for high, medium and low temperature applications HCFC

More information

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore

More information

Refrigeration and Boil Off Compression Systems for NGL Export Facilities

Refrigeration and Boil Off Compression Systems for NGL Export Facilities Refrigeration and Boil Off Compression Systems for NGL Export Facilities February 2015 2015 Gas/Electric Partnership Conference IHS INTERNATIONAL: US POISED TO LEAD WORLD EXPORTS OF LPG From Oil and Gas

More information

Gary Parker Refrigerants Product Manager

Gary Parker Refrigerants Product Manager Gary Parker Refrigerants Product Manager Refrigerant History Status of the HCFC ( R22) Phase out Ozone Friendly Alternatives Choosing the Best Retrofit Solution Lubricants and how they impact performance

More information

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved. GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant

More information

Scroll Chillers Transition from HCFC-22 to HFCs

Scroll Chillers Transition from HCFC-22 to HFCs Scroll Chillers Transition from HCFC-22 to HFCs An HVAC Manufacturer s Perspective Todd Brown McQuay International Business Development Manager Chillers todd.brown@mcquay.com ICF Workshop, Montreal Canada,

More information

SUBCRITICAL & TRANSCRITICAL SYSTEMS

SUBCRITICAL & TRANSCRITICAL SYSTEMS R744 CO2 SYSTEMS SUBCRITICAL & TRANSCRITICAL SYSTEMS ORIGINAL MANUFACTURED EQUIPMENT R744 CO2 Systems BA-508-3 AUS In 2004 BITZER Australia introduced the Enviro-Cold CO 2 System to the Australian Refrigeration

More information

Air Conditioning Operation and Troubleshooting Matt Dunham

Air Conditioning Operation and Troubleshooting Matt Dunham Air Conditioning Operation and Troubleshooting Matt Dunham Major Components (10 Minutes) Compressor heart of the system, causes refrigerant to flow by increasing the pressure of the refrigerant Metering

More information

The Essentials Of Working With R-410A

The Essentials Of Working With R-410A The Essentials Of Working With R-410A By Norm Christopherson Several major manufacturers are producing comfort air conditioning equipment using refrigerant 410A. The trend towards the use of 410A continues

More information

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Air Conditioning Clinic Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Absorption Water Chillers One of the Equipment Series A publication of The Trane Company Worldwide Applied Systems

More information

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Low Global Warming Refrigerants For Commercial Refrigeration Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel

More information

Low GWP Refrigerants for Air Conditioning Applications

Low GWP Refrigerants for Air Conditioning Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta

More information

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Main Anthropogenic Sources of Greenhouse Gases Refrigerants Main Anthropogenic Sources of Greenhouse Gases Refrigerants Content Refrigerant definition Refrigerants Refrigerants as a source of GHG Refrigerant Definition A refrigerant is a substance or mixture, usually

More information

Refrigeration Systems and Accessories

Refrigeration Systems and Accessories As with the Chapter Review Tests and the Final Exam, the tests your understanding of the materials underlying the learning objectives. After you ve reviewed your answers to the Chapter Review Tests, try

More information

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs Lesson 1 - Introduction to Refrigeration and Air Conditioning Define refrigeration. Identify the basic components of a refrigeration cycle. Identify the various gas laws and their importance to a basic

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties

More information

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING Sample Questions and Answers CHAPTER 5 EVAPORATORS 1. What is Evaporator? Classify the various types of evaporator. Evaporator

More information

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION Thomas Leck, PhD DuPont Fluorochemicals 2010 NEXT ACR Tokyo International Exchange Center 17 Feb 2010 DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

More information

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit

More information

Gary Parker Refrigerants Product Manager

Gary Parker Refrigerants Product Manager Gary Parker Refrigerants Product Manager Refrigerant f i t History Status of the HCFC ( R22) Phase out Ozone Friendly Alternativesti Choosing the Best Retrofit Solution Lubricants and how they impact performance

More information

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS ORTEC Compressed Air, Gas & Fluid Technologies HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS Energy Lean Planet Green Cycling and Non-Cycling Design Energy Efficient s Fluctuating and Intermittent Loads Capacity,0

More information

HVAC Fundamentals & Refrigeration Cycle

HVAC Fundamentals & Refrigeration Cycle HVAC Fundamentals & Refrigeration Cycle Change of State of Water & the Refrigeration Cycle Change of State Water The Basic Refrigeration Cycle Types of DX Systems The Chilled water System The Cooling Tower

More information

Bulletin , March Electric Hot Gas Bypass Valves

Bulletin , March Electric Hot Gas Bypass Valves Bulletin 100-60, March 2018 Electric Hot Gas Bypass Valves PAGE 2 / Bulletin 100-60 10 FEATURES AND BENEFITS SDR-4 Direct temperature control Tight shutoff when closed Can be interfaced with direct digital

More information

Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C

Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C McQuay International (A Member of the DAIKIN Group) Hydrofluorocarbon (HFC) refrigerants are critical to the safe and cost-effective phase-out

More information

NATURAL REFRIGERANT SYSTEMS

NATURAL REFRIGERANT SYSTEMS R744 CO 2 SYSTEMS NATURAL REFRIGERANT SYSTEMS SINGLE & MULTIPLE COMPRESSOR SYSTEMS SUB-CRITICAL / TRANS-CRITICAL ORIGINAL MANUFACTURED EQUIPMENT R744 CO2 SYSTEMS In 2004 BITZER Australia introduced the

More information

Ammonia. Background on ammonia as a refrigerant

Ammonia. Background on ammonia as a refrigerant Ammonia Danfoss Industrial refrigeration has written a technical paper on things to consider when changing from HFC/HCFC s to ammonia. It outlines some of the main differences between the different plant

More information

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures Experimental Study on Performance Parameters for Refrigerants, R41a and R44a at Various Air Outlet Temperatures P. Nagaraju P. G. Student Sanketika Institute of Technology and Management Ch. Kiran Kumar

More information

Refrigerants and lubricants

Refrigerants and lubricants Refrigerants and lubricants GENERAL INFORMATION When choosing a refrigerant, different aspects must be taken into consideration: Legislation (now and in the future) Safety Application envelope in relation

More information

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.

More information

Positively Innovative R32 R32. Instructions for Use and Handling

Positively Innovative R32 R32. Instructions for Use and Handling Positively Innovative R32 Refrigerants R32 Instructions for Use and Handling 2 Contents Foreword 4 1 Characteristics 5 1.1 Characteristics 5 1.2 Flammability 6 1.3 Saturated Vapor Pressure / Temperature

More information

BRA FACT FINDER Number 19

BRA FACT FINDER Number 19 BRA FACT FINDER Number 19 Issue: 1 Date: March 2017 A practical guide to using refrigerants with a temperature glide This document is the second in a series of bulletins produced by the BRA following the

More information

Why Hydrocarbons Save Energy

Why Hydrocarbons Save Energy Why Hydrocarbons Save Energy I. L. Maclaine-cross E. Leonardi School of Mechanical and Manufacturing Engineering The University of New South Wales Sydney NSW, Australia 2052 Internet: ian@ilm.mech.unsw.edu.au

More information

Development of centrifugal chiller and heat pump using low GWP refrigerant

Development of centrifugal chiller and heat pump using low GWP refrigerant Development of centrifugal chiller and heat pump using low GWP refrigerant Ryosuke Suemitsu 1*, Naoya Miyoshi 1, Yasushi Hasegawa 1, Kazuki Wajima 1, Yoshinori Shirakata 1, Kenji Ueda 1 1 Mitsubushi Heavy

More information

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES November 2006 / BULLETIN -60 ELECTRIC DISCHARGE BYPASS VALVES PAGE 2 / Bulletin -60 10 FEATURES AND BENEFITS Direct temperature control Tight shutoff when closed Can be interfaced with direct digital controls

More information

Trends and Perspectives in Supermarket Refrigeration

Trends and Perspectives in Supermarket Refrigeration Trends and Perspectives in Supermarket Refrigeration Prof. Dr.-Ing. Michael Kauffeld Karlsruhe University of Applied Sciences Mechanical Engineering and Mechatronics Department Institute of Refrigeration,

More information

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc. The Refrigeration Cycle Jerry Cohen President Jacco & Assoc. Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative

More information

Technical Bulletin (TB-0037)

Technical Bulletin (TB-0037) Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant

More information

FACT SHEET 6 Transport Refrigeration

FACT SHEET 6 Transport Refrigeration UNEP Ozone Secretariat Fact Sheets on HFCs and Low GWP Alternatives UNEP Ozone Secretariat Background Material on HFC Management October 205 FACT SHEET 6 Transport Refrigeration. Description of market

More information

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1998 A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional

More information

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) 4-1280 Application Engineering Bulletin AE-1280R4 Revised April, 1995 APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) Introduction The Compliant Scroll Compressor has been

More information

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration Calhoon MEBA Engineering School Study Guide for Proficiency Testing Refrigeration 1. To prevent an injury when working with refrigerants, what safety precautions are necessary? 2. When halogens are in

More information

Commercial CO 2 Refrigeration Systems

Commercial CO 2 Refrigeration Systems Commercial CO 2 Refrigeration Systems Guide for Subcritical and Transcritical CO 2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section

More information

LECTURE-17. Multi-Stage Vapour Compression Refrigeration. 1. Introduction

LECTURE-17. Multi-Stage Vapour Compression Refrigeration. 1. Introduction Lecturer: -Dr. Esam Mejbil Abid Subject: Air Conditioning and Refrigeration Year: Fourth B.Sc. Babylon University College of Engineering Department of Mechanical Engineering LECTURE-17 Multi-Stage Vapour

More information

for Valve Types P-H-M-V-W-D-A

for Valve Types P-H-M-V-W-D-A August 2004 / Bulletin 60-15 for Types P-H-M-V-W-D-A FOR USE ON REFRIGERATION and/or AIR CONDITIONING SYSTEMS ONLY Bulletin 60-15 August 2004 Supersedes Bulletin 60-15 August 1996 and all prior publications.

More information

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM 1 RONANKI SURESH, 2 Dr. K. KALYANI RADHA 1 M.Tech, Mechanical Engineering, JNTUA College of Engineering

More information

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

CH2351 Chemical Engineering Thermodynamics II Unit V Refrigeration. Dr. M. Subramanian

CH2351 Chemical Engineering Thermodynamics II Unit V  Refrigeration.  Dr. M. Subramanian CH2351 Chemical Engineering Thermodynamics II Unit V www.msubbu.in Refrigeration www.msubbu.in Dr. M. Subramanian Associate Professor Department of Chemical Engineering Sri Sivasubramaniya Nadar College

More information

Use of R1234yf, R744 (CO 2 ) and R134a in automotive air conditioning

Use of R1234yf, R744 (CO 2 ) and R134a in automotive air conditioning Use of R1234yf, R744 (CO 2 ) and R134a in automotive air conditioning This initiative was developed by: Content and guidance kindly provided by the following organisations: Cool Drive CPS Asia Pacific

More information

Refrigeration Systems

Refrigeration Systems Refrigeration Systems COP COP = coefficient of performance Air conditioners, refrigerators: COP=QL/Wnet Heat pumps: COP=QH/Wnet Energy balance: Wnet+QL=QH From Cengel, Thermodynamics: An Engineering Approach,

More information

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad- 500 043 B.Tech (III II SEM) MECHANICAL ENGINEERING REFRIGERATION AND AIR CONDITIONING Prepared by, Dr. CH V K N S N Moorthy, Professor

More information

Refrigerants for commercial refrigeration applications

Refrigerants for commercial refrigeration applications Refrigerants for commercial refrigeration applications March 2015 Contents Executive summary... 2 Introduction and background... 2 Environmental drivers... 3 Regulations and timing... 5 Criteria for refrigerant

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate Technologies, Inc. does not advocate

More information

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11 SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-479 Supersedes: NEW File: Volume

More information

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case: Case-16 Cascade Refrigeration System for LPG Subcooling Copy Right By: Thomas T.S. Wan ( ) Mar. 28, 2003 All Rights Reserved Case Background: This is a case of using a cascade refrigeration system to subcool

More information

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2004 Development and Performance Measurements of a Small Compressor for Transcritical CO2

More information

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT Proceedings of the International Conference on Mechanical Engineering and Renewable Energy 217 (ICMERE217) 18 2 December, 217, Chittagong, Bangladesh ICMERE217-PI-48 IR-REVERSIBILITY ANALYSIS OF A SPLIT

More information

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Mukesh K. Agrawal, Dr. Ashok G. Matani Abstract- The performance of heat transfer is one of the most important research

More information

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager INTRODUCTION The science of creating vacuum is often misunderstood and when the desired vacuum condition is not being achieved in a manufacturing setting this usually means production comes to a halt and

More information

COMPRESSORS. Technical information. Practical Application of Refrigerant R290 Propane in Small Hermetic Systems REFRIGERATION AND AIR CONDITIONING

COMPRESSORS. Technical information. Practical Application of Refrigerant R290 Propane in Small Hermetic Systems REFRIGERATION AND AIR CONDITIONING COMPRESSORS Technical information Practical Application of Refrigerant R290 Propane in Small Hermetic Systems REFRIGERATION AND AIR CONDITIONING Refrigerant R 290, or propane, is a possible replacement

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

APPLICATION and INSTALLATION

APPLICATION and INSTALLATION Page 2 / Bulletin 60-15 5 BENEFITS OF THE 1 2 3 4 5 Modulated flow The Level-Master Control provides a modulated flow and maintains practically a static liquid level in the low side. No moving parts The

More information

REFRIGERANT REFERENCE GUIDE

REFRIGERANT REFERENCE GUIDE United States National Refrigerats, Inc. 1140 Roosevelt Boulevard Philadelphia, PA 19154 215-698-6620 800-262-0012 Fax: 215-698-7466 United Kingdom National Refrigerants of America Ltd. 4 Watling Close

More information

CHARACTERISTICS OF REFRIGERANTS. By: Dr. Ralph C. Downing Freon Products Division E. I. du Pont de Nemours & Co. Inc.

CHARACTERISTICS OF REFRIGERANTS. By: Dr. Ralph C. Downing Freon Products Division E. I. du Pont de Nemours & Co. Inc. HISTORY Modern refrigeration methods, as distinguished from the use of ice and snow, go back to the early part of the 19th century. The following dates and events illustrate the development of the industry

More information

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA Daniel Giguère, Technology Expert Georgi Pajani, Engineer Sophie Hosatte, Section Head, Buildings CETC-Varennes, Natural

More information

How to Select and Size a Chiller

How to Select and Size a Chiller How to Select and Size a Chiller -What is process cooling -Which chiller type is best for your application Dimplex Thermal Solutions FABTECH November 9-12, 2015 What is an Industrial Process Chiller? Uses

More information

PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS

PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS RIO 3 - World Climate & Energy Event, 1-5 December 23, Rio de Janeiro, Brazil 275 PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS G. Venkatarathnam, V. Ravindranatha

More information

Understanding Process Vacuum for Process Improvement

Understanding Process Vacuum for Process Improvement Understanding Process Vacuum for Process Improvement Through this article we wish to give practical tips to boost process capacity, increase product quality and reduce cycle time in batch or continuous

More information

A Comparison Between Refrigerants Used In Air Conditioning

A Comparison Between Refrigerants Used In Air Conditioning A Comparison Between Refrigerants Used In Air Conditioning Derya Özkan, Özden Agra and Özlem Çetin University of Yildiz Technical University, Turkey Corresponding email: tumer@yildiz.edu.tr SUMMARY It

More information

Q. Which hydrocarbons can be used as a refrigerant? The following hydrocarbons can be used as a refrigerant in cooling & heating applications:

Q. Which hydrocarbons can be used as a refrigerant? The following hydrocarbons can be used as a refrigerant in cooling & heating applications: Basic Facts About Hydrocarbons Q. What are hydrocarbons? Hydrocarbon refrigerants are environmentally friendly, non-toxic, non-ozone-depleting replacement for chlorofluorocarbons (CFCs), hydrochlorofluorocarbons

More information

COMMECH SERIES AIR CONDITIONING CSH SEMI-HERMETIC SCREW PACKAGES. ORIGINAL MANUFACTURED EQUIPMENT Commech Series New Models BA AUS

COMMECH SERIES AIR CONDITIONING CSH SEMI-HERMETIC SCREW PACKAGES. ORIGINAL MANUFACTURED EQUIPMENT Commech Series New Models BA AUS COMMECH SERIES AIR CONDITIONING CSH SEMI-HERMETIC SCREW ACKAGES ORIGINAL MANUFACTURED EUIMENT Commech Series New Models BA-509-2 AUS roduct Features The BITZER ComMech Series compact screw compressor pack

More information

CO2 TRANSCRITICAL BOOSTER SYSTEMS

CO2 TRANSCRITICAL BOOSTER SYSTEMS CO2 TRANSCRITICAL BOOSTER SYSTEMS William Katz Sr. Technical Writer Hillphoenix 2016 Gees Mill Road Conyers, GA 30013 Tel: 678-613-9364 Email: william.katz@hillphoenix.com Refrigeration systems for supermarkets

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

Cast Line Heaters The Benefits of This Space Saving Electric Heater

Cast Line Heaters The Benefits of This Space Saving Electric Heater WHITE PAPER Cast Line Heaters The Benefits of This Space Saving Electric Heater Introduction Cast line heaters, or cast-in heaters, offer an alternative to the more common inline process heaters that have

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

Environmentally friendly refrigeration systems for industrial use

Environmentally friendly refrigeration systems for industrial use compindustri Environmentally friendly refrigeration systems for industrial use CO ² refrigeration systems of the future GENERAL INFORMATION compindustri More than 10 years of development of refrigeration

More information

Kirby CO 2 Evaporators

Kirby CO 2 Evaporators Kirby s Kirby Product Overview Prior to the discovery of synthetic refrigerants, liquid (R744) was used as a refrigerant. It is now enjoying renewed interest due to its innate advantages. has a very low

More information

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Effect of capillary diameter on the power consumption of VCRS using different refrigerants Effect of capillary diameter on the power consumption of VCRS using different refrigerants Dr. A. G. Matani 1, Mukesh K. Agrawal 2 1 Asso. Professor, Mechanical Engineering Department, Govt. College of

More information

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Comparative assessment for drop in replacement of R134a in domestic refrigerator. Comparative assessment for drop in replacement of R134a in domestic refrigerator. Pravin K. Katare Research Scholar, Department of Mechanical Engineering, G.H.Raisoni College of Engineering Digdoh Hill,

More information

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING UNIT OBJECTIVES After studying this unit, the reader should be able to Describe how refrigerant is charged into systems in

More information

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications Commercial CO2 Refrigeration Systems Guide for Subcritical and Transcritical CO2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section 1.

More information

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Type of Compressors Compressor Rotary Scroll Reciprocating Screw Centrifugal Air Cooled Chiller 77 ~ 329TR (270 ~ 1156 kw) ACDX Series 100 ~ 520TR

More information

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT Concepcion Carrier Air conditioning Company Philippines INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT CONTENTS Safety Considerations 1 Complete

More information