Rental Boiler Specifications (Nebraska Boiler)
|
|
- Randolph Holt
- 6 years ago
- Views:
Transcription
1 Rental Boiler Specifications (Nebraska Boiler) ESI's 72,000 pph trailer-mounted watertube steam boilers are designed and built in accordance with ASME Code. Each boiler is arranged for natural gas or #2 oil firing, complete with standard boiler trim, low NO x burner, FGR capability, and combustion controls. Boiler Data: Steam Flow Design Pressure Maximum Operating Pressure Minimum Operating Pressure Steam Temperature 72,000 pph 350 psig 325 psig 125 psig Saturated Requirements for Gas Firing: Gas Consumption (100% MCR) 96,720 scfh based on 1,000 btu/ft 3 Minimum Gas Pressure Required at Connection (Regulated) 20 psig Maximum Gas Pressure Required at Connection (Unregulated) 35 psig Requirements for #2 Oil Firing: Oil Consumption (100% MCR) 660 gph based on 140,100 btu/gal Minimum Oil Pressure at Pump Inlet Positive pressure Maximum Oil Pressure at Pump Inlet 30 psig Pilot Gas Pressure Required for Oil Start-Up 2.0 psig Oil Atomization (Air) Minimum Air Pressure 80 psig Maximum Air Pressure 120 psig Air Consumption 85 acfm Minimum Capacity Required for Steam Atomization 25% Oil Atomization (Steam) - Steam Pressure Required 125 psig minimum Feedwater Requirements: Minimum Feedwater Pressure 75 psig above operating pressure Maximum Feedwater Pressure 100 psig above operating pressure Minimum Feedwater Temperature 228 F Pressure Drop Across Feedwater Regulator Valve 25 psi (approximate) Electrical Requirements - Single Point Connection: Electrical Amps - Gas Firing 100 Electrical Amps - Oil Firing 125 FD Fan 75 hp, 60 Hz Oil Pump (#2 Oil) 3 hp, 60 Hz Voltage 480V/3 phase/60 Hz Motor Starter Included for both FD fan and oil pump Dimensions Trailer Height 14'5" Trailer Width 10'7" Trailer Length 52' Shipping Weight 94,000 pounds (approx) Operating Weight 115,000 pounds (approx) Stack Diameter 3'
2 Scope of Supply Summary (Nebraska Boiler) Item Description Supplied By: Installed By: ESI Lessee ESI Lessee Trailer X X Boiler X On trailer Burner/fuel trains X On boiler/trailer Gas pressure reducing valve X On trailer Oil pump X On trailer FD fan and drive X On boiler FGR duct X On boiler Propane pilot Only Required if Natural Gas is not Available Safety valves X X Nonreturn valve X X Economizer X X Second stop valve X X Controls X On boiler Instruments X On boiler Burner management X On burner Feedwater regulator X On boiler Stack X X Feedwater pumps/supply X X Deaerator X X Water conditioning system X X Chemical feed system X X Utilities to trailer limits X X Steam flow meter X X Heat tracing X X Cribbing for trailer X X Foundations X X
3 Item Description Supplied By: Installed By: ESI Lessee ESI Lessee FD motor starter X On boiler Oil pump motor starter X On boiler Blowdown valves X X Remote drum level indicator X X Disconnect switch between rental boiler and power feed X X Pipe supports X X Atomizing media Only Required if Natural Gas is not Available Blowdown separator X X Platforms, ladder, handrail X Handrail only Safety valve vents X X Natural gas vent X X Nuts, bolts, gaskets, etc. X X Transportation permits Operational permits Freight charges Field supervisor Start-up representative X Per Diem Per Diem X X
4 Temporary Boiler Field Connections and Auxiliary Equipment to be Mounted (Nebraska Boiler) Field Connections Steam 8" Flanged Feedwater 2½" Flanged Natural gas 4" Flanged #2 oil 1½" Flanged Oil return ½" Flanged Atomizing air 1½" Flanged Blowdown 1½" Flanged Continuous Blowdown 1" NPT Chemical feed 1" NPT Electrical 480 V / 3 ph / 60 Hz 150 amps Auxiliary Equipment to be Field Mounted by Lessee One 6'6" high stack and transition assembly One 8" 300# steam nonreturn valve One 8" 300# main steam second stop valve Two 1½"bottom blowdown valves and piping Two ASME safety relief valves set at 350 psig One (1) flanged upper FD fan housing Handrails
5 Mobile Boiler Emissions Natural Gas #2 Oil NO x without FGR (lbs/mmbtu input) NO x with 5% FGR (lbs/mmbtu input) CO (ppm) The above predicted emissions are valid only with the below listed assumed fuel analyses. Emissions using a different, specific fuel analysis can be provided upon request. Constituent Natural Gas (% Vol) #2 Oil (% wgt) CH 4 90 C 2 H 6 5 N S 0.30 H C O Btu/lb 21,746 19,460 Btu/scf 1,000
6 System Components Description Trailer The transportation and support trailer for the rental boiler is a 35-ton capacity tri-axle assembly with an air-ride suspension and manual override system. The trailer has dimensions of 52'-0" overall length by 8'-6" overall width by 26'-0" deck length. The main deck width is 54" and has a loaded fifth wheel height of 48" and a loaded deck height of 22½" (ground to top of rail). Four two-speed landing gear assemblies with cranks are installed at the front and rear of the deck of the trailer to provide support when the unit is in storage. The landing gear assemblies are not to be used for leveling the trailer/boiler. The trailer meets all DOT guidelines. Boiler The boiler is an "O" type design, watertube unit specifically designed for rental boiler applications. The unit is constructed with a welded membrane furnace and outside wall assembly, membrane water-cooled rear wall, and membrane water-cooled front wall. The unit is designed for operation between psig with a system design pressure of 350 psig. Maximum capacity is 72,000 pph saturated steam based on an inlet feedwater temperature of 228 F at an operating pressure of 325 psig. The unit is manufactured by Nebraska Boiler, built in Burner and Fuel Trains The burner and windbox attached to the front wall of the boiler is a low NO x design, capable of firing natural gas or #2 fuel oil. The burner assembly includes the capability for air or steam atomization with air atomization being used for cold start-up on #2 fuel oil. The burner pilot system includes the provision for propane pilot in the event natural gas is not available. The natural gas burner system is a ring type burner with multiple spuds for optimum burner performance. The fuel oil and the atomizing steam trains are all welded construction as much as possible to prevent leakage and is constructed with steel valves wherever possible for longevity purposes. The main gas fuel train includes a PRV to regulate supply pressure for proper burner performance. The system can bypass the PRV if desired. The burner is manufactured by Todd Combustion, built in Forced Draft Fan and Electric Motor Drive The combustion air requirements are supplied by a windbox-mounted forced draft fan and 75 hp 480 volt electric motor. An inlet damper provides control of the combustion air based on firing rate requirements. The top portion of the forced draft fan housing is removable for shipment purposes and must be installed before fan operation. The fan is manufactured by Chicago Blower and includes static pressure provisions for addition of a future economizer. Flue Gas Recirculation System A flue gas recirculation system is included to extract flue gas from the boiler outlet and induce flue gas into the fan inlet to minimize nitrous oxide emissions. The flue gas recirculation system consists of a 10" diameter carbon steel duct and manually positioned butterfly damper.
7 Controls and Instrumentation The trailer-mounted boiler system includes all required combustion controls and instrumentation for automatic operation. The control system is a jackshaft positioning system. A steam pressure signal from the steam drum pressure transmitter is sent to the Moore Fieldpac master controller. Essentially, the Moore Fieldpac in turn sends a signal to the Beck actuator to adjust the firing rate in order to maintain steam pressure. The Beck actuator is connected via mechanical linkage to a jackshaft system which connects the fuel control valves and forced draft fan damper. The relative positions of the forced draft fan damper and fuel control valves are field adjustable by qualified service personnel to optimize operation throughout the boiler operating range. Burner Management System The flame safety or burner management system provided is a Fireye E100 system including an E300 annunciator for burner limits. The Fireye E300 will annunciate all alarms including low water alarm. Further, it will indicate the cause of a boiler trip and will display the reason for the trip until the unit is reset. This will assist plant operations personnel in troubleshooting. The burner management system is in full compliance with NFPA Feedwater Control System Control of the boiler feedwater supply is accomplished with a boiler-mounted electronic feedwater control valve. A transmitter responding to drum level conditions in the temporary boiler system sends a signal to the Moore Fieldpac which in turn opens or closes the control valve. The response of this valve is field set in accordance with the requirements at the specific site. An optional steam flow correction feature can be provided to enable two-element drum level control with both drum level and steam flow as inputs. Fuel Oil Pump and Drive A #2 fuel oil supply booster pump is provided, mounted to the trailer including a 3 hp electric motor drive. The pump is capable of supplying the required burner fuel flow at a discharge pressure of 150 psig based on an inlet supply pressure of 30 psig maximum and 0 psig minimum. Platforms and Access Ladder OSHA-approved platforms and access ladder are provided for the boiler rear drum head and right-hand side of the steam drum. Removable handrails (for shipment) are provided and required to be installed at the site for proper operation. Access to these platforms is via an uncaged ladder extending from the trailer main deck area. Electrical System A complete electrical system is included to receive 480 volt, three phase, 60 Hz power from an external source at the main electrical control panel mounted on the side of the windbox. A 480 volt to 120 volt transformer is included for operation of electrical auxiliaries requiring 120 volt power including burner front lighting and auxiliary electrical outlets for maintenance purposes. The motor starters for both the forced draft fan electric motor and fuel oil pump electric motor are included as are fusible disconnects as required. Grounding of the trailer is accomplished by a connection on the trailer deck to an appropriate site ground source.
8 Stack A single-wall 36" diameter by 6'6" high carbon steel stack and transition is included to be mounted on the boiler outlet flange. The stack includes four 1" instrument connections. Nonreturn Valve and Main Steam Stop Valve One Edwards 8" nonreturn valve is provided for mounting on the main steam outlet and connecting to the process steam supply. One 8" gate valve is provided, including vent port and shut-off valve. Safety Relief and Blowdown Valves Field-mounted safety relief valves are provided to be mounted to several of four potential connections on the steam drum for proper relief and installation of the temporary boiler system. Likewise, tandem blowdown valves are supplied to be mounted to the bottom drum blowoff connection. Valves All valves to the first valve point of the temporary boiler are included and installed for proper isolation and shutoff of drains, supply pressures, instrumentation, etc. All valves provided are fabricated from cast steel material included all welded piping as required.
9
10
11
12
Guidelines for Preparing for a Temporary Steam Plant
Guidelines for Preparing for a Temporary Steam Plant Trailer-Mounted Boilers Skid Mounted Boilers Mobile Boiler Rooms Mobile Feedwater Vans Mobile Steam Plants Emergency Preparedness Plan Table of Contents
More informationDeaerator. Specifications
ESI, INC. OF TENNESSEE RENTAL EQUIPMENT Deaerator Description The deaerator, built in 1996, is a spray-type deaerating feedwater heater and storage tank with stainless steel internals. The deaerator is
More informationSECTION HEATING BOILERS
SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,
More informationSection B1. Flexible Watertube Boilers TABLE OF CONTENTS
Section B1 Flexible Watertube Boilers TABLE OF CONTENTS FEATURES AND BENEFITS.................................................. B1-3 PRODUCT OFFERING......................................................
More informationBoiler Walkdown Field Device Checklist. Customer. Date
Boiler Walkdown Field Device Checklist Customer Date Plant-Wide Control Field Devices Fig. 1 Typical Steam Plant Fig. 2 Typical High Temp Hot Water Plant Boiler / Generator Control Field Devices Fig.
More informationFUEL-FIRED VERTICAL TUBELESS BOILERS
FUEL-FIRED VERTICAL TUBELESS BOILERS 4 60 P orizontal and Vertical Feedwater / Condensate Return Systems and Blow-down Tanks FULTON FUEL-FIRED VERTICAL TUBELESS BOILERS FULTON: AN INDUSTRY LEADER SINCE
More informationPROFIRE -E SERIES BURNERS
PROFIRE -E SERIES BURNERS 8.4-42.0 MMBTU/HR High-efficiency burner technology for the most stringent emissions requirements Integration Starts with the Burner Suitable for firetube, firebox and watertube
More informationBryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired
Form No. 8700 Bryan Flexible Water Tube TM Triple-Flex Series Ultra-High Efficiency Condensing Hot Water Boilers 3,000,000 BTUH Natural Gas Fired Minimum 90% Thermal Efficiency at 160 F Return with 20
More informationINDUSTRIAL WATERTUBE BOILERS
INDUSTRIAL WATERTUBE BOILERS Innovative solutions for maximum efficiency Cleaver-Brooks Engineered Boiler Systems Manufacturers of Nebraska Boilers, NATCOM Burners and ERI HRSG Systems Industrial Watertube
More informationConsiderations for INDUSTRIAL COMBUSTION
August 2016 Volume 23, Number 8 Considerations for INDUSTRIAL COMBUSTION Systems Follow us on: COMBUSTION CONTROLS FOR BOILERS Understand the advantages and disadvantages of combustion control schemes
More informationA-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents
Boiler specifications A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Burner General: Q. Burner and burner safeguards shall comply with the CGA
More informationHCLEARFIRE. High-efficiency, modular steam boiler HP
HCLEARFIRE High-efficiency, modular steam boiler 10-60 HP High-Efficiency, Low-Emission Steam Boiler in a Compact Footprint The ClearFire -H compact, gas-fired horizontal boiler is designed specifically
More informationSECTION WATER-TUBE BOILERS
SECTION 23 52 33 WATER-TUBE BOILERS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable in the Section. Deleted paragraphs
More informationZeeco, Inc. Doc. No Tulsa, Ok Cover Page GLSF-14 Free-Jet and RWSF-4 Radiant Wall Burners. Range Fuels Soperton Plant, LLC
Zeeco, Inc. Doc. No. 17928-601 Tulsa, Ok Cover Page + 10 Client : P.O.: SOP 10606 Item : Burner Data Sheets Zeeco S.O.: 17928 GLSF-14 Free-Jet and RWSF-4 Radiant Wall Burners FOR AT Soperton, Georgia Burner
More informationModel CB-LE. Packaged Boiler HP. Operation, Service, and Parts Manual /09. and Model CB Ohio Special HP
Model CB-LE Packaged Boiler 125-200 HP and Model CB Ohio Special 125-225 HP Operation, Service, and Parts Manual 750-184 04/09 ii CLEAVER-BROOKS Model CB-LE Packaged Boiler 125-200 HP Light Oil, Heavy
More informationSAMPLE SPECIFICATIONS
Page 1 of 6 3-03 SAMPLE SPECIFICATIONS The following sample specifications are provided by Superior Boiler Works to assist you in providing your customer with the specific needs for that application. The
More informationSAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER
SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section
More informationPower Flame Incorporated
Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas
More informationADDENDUM # 2 TO RFP #
ADDENDUM # 2 TO RFP # 0056018 VIRGINIA POLYTECHNIC INSTITUTE AND STATE UNIVERSITY (Virginia Tech) Procurement Department (MC 0333) North End Center, Suite 2100 300 Turner Street NW Blacksburg, Virginia
More informationMODEL M5M. High-Efficiency Packaged Watertube Boiler MMBTU
MODEL M5M High-Efficiency Packaged Watertube Boiler 2.0-6.0 MMBTU Low Emissions, High Efficiency Whether your application is a small batch load for food processing, or you are considering a hybrid heating
More informationSolution builder. in energy management.
Solution builder in energy management Catalog of products 1 COMPANY PROFILE 2 HTHW (High Temperature Hot Water) GENERATOR 3 AQT - WATERTUBE STEAM BOILER 4 AQT - WATERTUBE HOT WATER HEATER 5 AQT HEATER
More informationFuel-Fired Vertical Tubeless Boilers
Fuel-Fired Vertical Tubeless Boilers Fulton Classic (4-60P), The EDGE (6-30P) orizontal and Vertical Feedwater / Condensate Return Systems and Blow-down Separators FULTON FUEL-FIRED VERTICAL TUBELESS BOILERS
More informationCleaver-Brooks Webinars
Cleaver-Brooks Webinars Today s Topic: Insights in Optimal Boiler Room Controls If you ve missed any of our previous live webinars You can view our archived webinars by going to www.cleaverbrooks.com/webinars
More information.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.
Issued 2005/06/01 Section 15510 Packaged Boilers Page 1 of 13 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3 Section 01780 Closeout
More informationNOx REDUCTION EXPERIENCE ON NATURAL GAS FIRED TURBO FURNACES
NOx REDUCTION EXPERIENCE ON NATURAL GAS FIRED TURBO FURNACES by D. E. Dorman, Staff Engineer DB Riley, Inc. Presented at the International Joint Power Generation Conference Miami Beach, Florida July 23-25,
More informationVCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower
VCLEARFIRE High-Efficiency, Commercial Steam Boiler 9.5-60 Horsepower High-Efficiency, Low-Emissions Steam Boiler in a Compact Footprint The Cleaver-Brooks compact, gas-fired ClearFire -V vertical boiler
More informationMath & Physics. Complete combustion requires an Air-FuelRatio of 14.7 to 1 for combustion.
Plant OPS Math & Physics Complete combustion requires an Air-FuelRatio of 14.7 to 1 for combustion. Math & Physics Increasing oxygen levels by 9 to 15% improves boiler efficiency. Math & Physics Draft
More informationA Newsletter published by ESI. The Steam and Power SPECIAL FORCES
ENERGY SOURCE A Newsletter published by ESI The Steam and Power SPECIAL FORCES Spring 2003 THE BUYER S GUIDE TO PACKAGE BOILER DESIGN By: William L. Reeves, P.E., President, ESI Editor s Note: This article
More informationmith Mills Smith Mills 6500A 6500A-4 OIL OR GAS CAST IRON BOILER/BURNER CAST IRON
mith Mills Mills 00A OIL OR GAS CAST IRON BOILER/BURNER Smith CAST IRON 00A- - Gas I=B=R Ratings: Gross Output 7,19 to 1, FRONT VIEW WITH INDUS COMB BURNER SIDE VIEW WITH INDUS COMB BURNER SIDE VIEW -
More informationPower Flame Incorporated
Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,
More informationHORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).
SECTION 15555 HORIZONTAL FIRE TUBE BOILERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15510 - Piping (HVAC). 2. 15540 - Pumping Equipment (HVAC). 1.02 SUBMITTALS A. Submit properly identified
More informationproduct Industrial burners Industrial burners sizes 30 to 70 flexible and reliable Information on oil, gas and dual fuel burners
product Information on oil, gas and dual fuel burners Industrial burners Industrial burners sizes to flexible and reliable Weishaupt Industrial Burners: Flexible and reliable For more than years, Weishaupt
More informationBoiler Basics. Design and operation
Boiler Basics Design and operation A boiler is an enclosed vessel that provides a means for combustion heat to be transferred into water until it becomes heated water or steam. The hot water or steam under
More informationGB Condensing Gas Boiler
Engineering Submittal Sheet Boiler Overview C US Engineering Specifications There shall be provided and installed a quantity of Buderus GB162/100 wall-hung condensing hot water boiler(s), suitable for
More informationSECTION WATER-TUBE BOILERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections
More informationSilhouette. Feedwater Heater. Boiler Feedwater
Roth Roth Low Low Silhouette Silhouette TRAY DEAERATORS Boiler Boiler Feedwater Feedwater Heater Heater Capacities Capacities to to 50,000 50,000 lb/hr lb/hr Model RDTV-150-5-1-2 vertical tray type deaerator
More informationWeishaupt dual fuel burners Sizes 30 to 70 Version 1LN (NO X -reduction on gas operation) 1/2003 CA
Weishaupt dual fuel burners Sizes 30 to 70 Version 1LN (NO X -reduction on gas operation) 1/2003 CA Description Weishaupt burners of sizes 30 to 70 were specially designed and developed for industrial
More informationMOHICAN. MOHICAN 4-Pass Water Boiler, HP, PSI Section
SPECIFICATION SHEETS Steam Sample Specification Water Sample Specification MOHICAN SPECIFICATION SHEET The following sample specifications are provided by Superior Boiler Works to assist you in providing
More informationmith Mills 4500A Smith Mills 4500A 4500A-3R OIL, GAS OR COMBINATION GAS/OIL COMMERCIAL BOILER/BURNER CAST IRON
Mills 00A mith Mills 00A Smith CAST IRON OIL, GAS OR COMBITION GAS/OIL COMMERCIAL BOILER/BURNER 00AR STEAM GAUGE OPERATING CONTROL MODULATING CONTROL HI LIMIT PRESSURE CONTROL 0" STEAM DRUM TEST COCK /"
More informationLATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners
1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):
More informationClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler
ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750-293 www.cleaverbrooks.com Improper installation, adjustment, service, or maintenance can cause equipment damage, personal injury, or death.
More informationAnnex A-8 CONCENTRATED SOLAR POWER UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES
Annex A-8 CONCENTRATED SOLAR POWER UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES SOLAR ENERGY GATHERING EQUIPMENT Solar Field 6500-6559 Thermal Storage 6570-6589 Operational Problems 6590-6599 STEAM TURBINE
More informationLattner Boiler Company Scotch Marine Steam & Hot Water Boilers
Lattner Boiler Company Scotch Marine Steam & Hot Water Boilers INSTRUCTION MANUAL December 2005 Lattner Boiler Company 1411 9 th St. SW Cedar Rapids, IA 52404 T: (800) 345-1527 F: (319) 366-0770 E: info@lattner.com
More informationRevitalize Building Mechanical Systems (4619)
SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationFGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP)
FGR Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM FGR-8 through FGR-22 (25 HP to 1000 HP) Gas, Light Oil or Combination MANUFACTURED BY JOHN ZINK COMPANY, LLC
More informationC. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.
Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED
More informationELITE SERIES Lo-Boy. AFUE - 83% Heating Input - 101,000 to 151,000 Btuh Nominal Add-on Cooling to 5 Ton. OIL FURNACES El0183b
PRODUCT SPECIFICATIONS OIL FURNACES El083b ELITE SERIES Lo-Boy Bulletin No. 20629 February 209 Supersedes July 202 MODEL NUMBER IDENTIFICATION el O 83 bf 0/4 p 60 AFUE - 83% Heating Input - 0,000 to 5,000
More informationWATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E
WATER HEATERS / BOILERS -E PRODUCT SPECIFICATIONS Gas-Fired Steam Boiler Bulletin No. 20653 September 202 Supersedes Bulletin No. 20263 AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh MODEL NUMBER
More informationGB Condensing Gas Boiler
Engineering Submittal Sheet Boiler Overview C US Engineering Specifications There shall be provided and installed a quantity of Buderus GB142/45 wall-hung condensing hot water boiler(s), suitable for induced
More informationBy Authority Of THE UNITED STATES OF AMERICA Legally Binding Document
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has
More informationSECTION HEATING BOILER FEEDWATER EQUIPMENT
SECTION 23 53 00 HEATING BOILER FEEDWATER EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes boiler feedwater pumps, de-aerators, accessories, controls and tanks. 1.2 REFERENCES A. ASME (American
More informationPACKAGED COMMERCIAL WATERTUBE BOILERS
PACKAGED COMMERCIAL WATERTUBE BOILERS PACKAGED COMMERCIAL WATERTUBE BOILER American Boiler Manufacturers Association 4001 N. 9 th Street, Suite 226 Arlington, VA 22203-1900 703/522-7350 2003, American
More informationG315/6 Cast Iron Boiler
Engineering Submittal Sheet Boiler Overview LISTED Engineering Specifications There shall be provided and installed G315-6 Buderus sectional cast iron hot water boiler(s), suitable for forced draft firing
More informationSERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job
SERIES Commercial, Forced Draft, Hot Water or Steam Boiler Sizes from to,8 MBH output The right fit for any commercial job The Series is built to handle any installation - businesses, institutions, apartments,
More informationClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV
ClearFire Economizer Model ECF Integral or External Addendum to manuals 750-295 CFH and 750-269 CFV CB-8466 08/2011 1-GENERAL The Model ECF economizer is a stainless steel coil tube arrangement using
More informationNFPA 85 COMPLIANCES OF BMS: A CASE STUDY OF BOILER CONTROL AT SBM OFFSHORE MALAYSIA COMPANY 1. AHMED ABOUELRISH 2 Universiti Teknologi Petronas
Journal of Contemporary Issues in Business Research ISSN 2305-8277 (Online), 2013, Vol. 2, No. 4, 109-123. Copyright of the Academic Journals JCIBR All rights reserved. NFPA 85 COMPLIANCES OF BMS: A CASE
More informationINSTALLATION AND OPERATION MANUAL FOR 2 STAGE RIELLO BURNER ADDENDUM TO ( Mo 437 manual )
INSTALLATION AND OPERATION MANUAL FOR 2 STAGE RIELLO BURNER ADDENDUM TO ( Mo 437 manual ) FOR USE WITH MODEL: OH6FX072DV4 PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION, INITIAL FIRING, AND BEFORE
More informationDescription Model Weil-McLain part number. Vent Termination Kit for 3" Stainless Steel All
Replacement parts Figure 96 Miscellaneous parts Description Model Weil-McLain part number Vent Termination Kit for 3" PVC All 383-500-397 Vent Termination Kit for 3" Stainless Steel All 382-200-430 Vent
More informationYou can view our archived webinars by going to
Cleaver-Brooks Webinars Today s Topic: Six Steps for Proper Industrial Watertube Boiler Selection If you ve missed any of our previous live webinars You can view our archived webinars by going to www.cleaverbrooks.com/webinars
More informationSuggested Specifications Prestige Excellence 110
Suggested Specifications Prestige Excellence 110 General Requirements A. Furnish and install (qty) completely assembled, modulating, sealed combustion, high efficiency, combination gas-fired boiler(s)
More informationG315/5 Cast Iron Boiler
Engineering Submittal Sheet Boiler Overview LISTED Engineering Specifications There shall be provided and installed G315-5 Buderus sectional cast iron hot water boiler(s), suitable for forced draft firing
More informationDiocese of Cleveland Facilities Services Corporation
Diocese of Cleveland Facilities Services Corporation BOILER MAINTENANCE and SERVICING SEASONAL MAINTENANCE - to be performed by trained boiler technician or boiler contractor only: 1. Disassemble the low
More informationSTEAMPAK Series BurnerPAK BMS Burner Management Systems
BurnerPAK BMS Burner Management Systems Sequence of operation, ignition and control of burners Meets NFPA 85 safety standard MFT alarming with manual reset, first-out indication Optional enhanced alarming
More informationThermal Fluid Heaters
Thermal Fluid Heaters Vertical Coil, Vertical Tubeless, Electric and Horizontal Sizes from 75,000 to 40,000,000 BTU/HR The heat transfer innovators. THERMAL FLUID FEATURES AND BENEFITS KEY FEATURES No
More informationGB Condensing Gas Boiler
Engineering Submittal Sheet Boiler Overview C US Engineering Specifications There shall be provided and installed a quantity of Buderus GB12/90 condensing hot water boiler(s), suitable for induced draft
More informationG515/7 Cast Iron Boiler
Engineering Submittal Sheet Boiler Overview Engineering Specifications There shall be provided and installed G515-7 Buderus sectional cast iron hot water boiler(s), suitable for forced draft firing with
More informationFLX FLEXTUBE. The Widest Range of Hydronic and Steam Watertube Boiler Systems 1,500 to 25,000 MBTU/HR (35-600HP)
FLX FLEXTUBE The Widest Range of Hydronic and Steam Watertube Boiler Systems 1,500 to 25,000 MBTU/HR (35-600HP) Completely Integrated Boiler System Solution Flexible solutions for any application. Cleaver-Brooks
More informationBoiler & Water Heater
MIGHTY THERM2 Date: Project #: Pump-Mounted Boiler & Water Heater MT2H Hydronic Heater MT2V Volume Water Heater Indoor/Outdoor Sizes 500-2000 Submittal Engineer: Project Name: Prepared By: Location: Bid
More informationClearFire - Hydronic Startup Report
ClearFire - Hydronic Startup Report Date Serial No. THIS FORM IS FOR MODEL CFC / CFW CLEARFIRE BOILERS Customer s Name Location Model Design Pressure Working Pressure Rated Input (nameplate rating) BTU/hr
More informationGAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications
ENGINEERING DATA Typical Applications G20RE and G20RXE WhisperHeat DOWN-FLO GAS FURNACES *78.0% A.F.U.E. 50,000 to 150,000 Btuh Input Add-On Cooling 2 thru 5 Nominal Tons *Isolated Combustion System rating
More informationDIVISION FINNED WATER-TUBE BOILERS
MVB, TYPE H - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 2000.932C Effective: 04-01-14 Replaces: 07-15-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section
More informationG615/11 Cast Iron Boiler
Engineering Submittal Sheet Boiler Overview LISTED Engineering Specifications There shall be provided and installed G615-11 Buderus sectional cast iron hot water boiler(s), suitable for forced draft firing
More informationInternet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #
INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED
More informationElectrode Boilers Model CEJS Steam
Model CEJS Steam CONTENTS FEATURES AND BENEFITS...................................................2 PRODUCT OFFERING......................................................2 PERFORMANCE DATA......................................................5
More informationGSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES
P R O D U C T S P E C I F I C AT I O N S W A T E R H E A T E R S / B O I L E R S CONSERVATOR Gas-Fired Steam Boiler Bulletin No. 20263 October 200 Supersedes September 2008 AFUE up to 82.7% Heating Input
More informationINSTRUCTION MANUAL FOR OIL BURNER MODELS
INSTRUCTION MANUAL FOR OIL BURNER MODELS X500-2 Low voltage 12v dc Brushed motor E90-803-001-005-01 Rev 4-1 - Contents Technical specifications Technical data...3 Working field...3 Dimensions...4 Head
More informationBASIL 6000 TUNNEL CAGE WASHER
BASIL 6000 TUNNEL CAGE WASHER APPLICATION For thorough, efficient cleaning of cages, debris pans, bottles, feeder bowls, and miscellaneous items used in the care of laboratory animals. DESCRIPTION The
More informationPART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS
PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project
More informationENERVEX VHX VORTEX HEAT RECOVERY CENTER
ENERVEX VORTEX HEAT RECOVERY CENTER 3002603 06.16 Installation & Operating Manual READ AND SAVE THESE INSTRUCTIONS! ENERVEX Inc. 1685 Bluegrass Lakes Parkway Alpharetta, GA 30004 USA P: 770.587.3238 F:
More informationINDITHERM. Low temperature gas burners
INDITHERM Low temperature gas burners 1-2.3-1 High turndown for maximum operation flexibility. Maximum capacities up to 1800 kw. Designed for firing in indirect fired processes. Excellent combustion throughout
More informationWilliams & Davis Boilers
Williams & Davis Boilers Established 1921 3-Pass Water-Back Scotch Marine Boiler SIZES 15HP THROUGH 1500HP GAS, OIL OR COMBINATION BURNER FIRETUBE HOT WATER & PRESSURE STEAM BOILERS 3000W Standard Features
More informationSPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION FIRE TUBE BOILERS (STEAM)
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
More informationIndiana WX Oil Furnace Inspection Guide
Indiana WX Oil Furnace Inspection Guide Client: Job # : Address: Phone: Client Interview: Oil Dealer: Date of last service: Comments/Billing information: Standard Inspection / Clean and Tune Follow-up:
More informationCHAPTER 3 BASIC STEAM CYCLE
CHAPTER 3 BASIC STEAM CYCLE To understand steam generation, you must know what happens to the steam after it leaves the boiler. A good way to learn the steam plant on your ship is to trace the path of
More informationA. Section Common Motor Requirements for HVAC Equipment: Fan motors.
SECTION 235533 - FUEL-FIRED UNIT HEATERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Gas fired unit heaters. B. Oil fired unit heaters. C. Tubular infrared heaters. 1.2 RELATED REQUIREMENTS A. Section 230513
More informationTray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com
Tray ST5 Pressurized and Atmospheric Deaerators Tray Type Deaerator Pressurized.005 cc/liter COUNTER FLOW TRAY design provides guaranteed removal of all dissolved oxygen in excess of.005 cc/liter from
More informationREFERENCE SYLLABUS. For FIRED PROCESS HEATER OPERATOR S. CERTIFICATE of COMPETENCY EXAMINATION AB-239. Edition 3, Revision 1, Issued
For CERTIFICATE of COMPETENCY EXAMINATION AB-239 Edition 3, Revision 1, Issued 2018-07-13 Visit our Website at www.absa.ca GENERAL INMATION Introduction: As provided for under the Power Engineers Regulation,
More informationDIVISION FINNED WATER-TUBE BOILERS
MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section
More informationCopyright 2009 Power Flame Incorporated
Power Flame Incorporated Installation and Operation Manual Ultra CMax Copyright 2009 Power Flame Incorporated 2001 South 21 st Street, Parsons, KS 67357 Telephone: 620-421-0480 FAX: 620-421-0948 Website:
More informationBoiler Technical Specifications (2013)
ACT Bioenergy Boiler Dimensions 0.5-0.85 Million Btu/h (150-250kW) Model CP500 CP600 CP750 CP850 Heat Output in MBtu/h (kw) 510 (150) 610 (180) 750 (220) 850 (250) Height ft (mm) 6 1 (1855) 6 1 (1855)
More informationGAS/LOW NOx SERIES. High or Low Pressure Steam Boiler. The most versatile industrial steam boiler in the world
MIURA WX GAS/LOW NOx SERIES High or Low Pressure Steam Boiler NEW XJ1 Micro Computer Boiler Control System The most versatile industrial steam boiler in the world The intelligent boiler that works with
More informationWATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh
HEATERS / BOILERS GWB8-E PRODUCT SPECIFICATIONS Gas-Fired Hot Water Boiler Bulletin No. 065 September 0 Supersedes Bulletin No. 06 AFUE up to 83.9% Heating Input 50,000 to 99,000 Btuh MODEL NUMBER IDENTIFICATION
More informationMINIMUM TANK GAP. Greater of 3 or one-sixth of sum of adjacent tank diameters. one-half of sum of adjacent tank diameters 20
Piping Layout Design Introduction The performance requirements of the equipment are developed by design teams which normally include members from the different departments such as process, engineering,
More informationENGINEERING & INSTALLATION MANUAL
MIURA EX BOILER 170/250 PSI Designs ENGINEERING & INSTALLATION MANUAL C APPROVED EX - HIGH EFFICIENCY SERIES MIURA BOILER WEST, INC. * IN OUR CONTINUING EFFORT TO IMPROVE OUR PRODUCT, INFORMATION IN THIS
More informationDesign and Construction Standards SECTION PLUMBING EQUIPMENT
SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES
More informationG34M Bulletin #69/ August 2003
ENGINEERING DATA G34M MULTI POSITION GAS FURNACE 12.4 to 31.0 kw Output 52.7 to 131.9 Mj Input 3.5 to 17.6 kw Nominal Add-on Cooling GAS FURNACES 50 Hz G34M Bulletin #69/490045 August 2003 Typical Applications
More informationINSTRUCTION MANUAL FOR OIL BURNER MODELS
INSTRUCTION MANUAL FOR OIL BURNER MODELS X400 Bio B10 E90-803-001-001-03 Rev 13-1 - Contents Technical specifications Technical data... 3 Working field... 3 Dimensions... 4 Head and electrode settings...
More informationDrum Level Instrumentation and. The ASME Boiler Code Requirements. Presented by: Jim Kolbus. Topics
Drum Level Instrumentation and The ASME Boiler Code Requirements Presented by: Jim Kolbus Topics ASME Code Section 1 Requirements for Drum Level Instrumentation Water Columns and Water Gage Isolation Valves
More informationmith Mills 3500A Smith Mills 3500A 3500A-3 OIL, GAS OR COMBINATION GAS/LIGHT OIL COMMERCIAL BOILER/BURNER CAST IRON
Mills 300A mith Mills 300A Smith CAST IRON 300A3 OIL, GAS OR COMBINATION GAS/LIGHT OIL COMMERCIAL BOILER/BURNER COMBUSTION CHAMBER DETAILS SIDE VIEW GAS FIRED FRONT VIEW WATER SIDE VIEW NATURAL DRAFT WATER
More informationLattner Boiler Company Model HRT Steam Boilers with Forced Draft Burners
Model HRT Steam Boilers with Forced Draft Burners INSTRUCTION MANUAL 2006 to 2007 T: (800) 345-1527 F: (319) 366-0770 E: info@lattner.com www.lattnerboiler.com Index Page 1 Index Section I: General Description
More information