Wiring Instructions. High-Capacity Steam Humidifiers
|
|
- Preston Lambert
- 6 years ago
- Views:
Transcription
1 Wiring Instructions for High-Capacity Steam Humidifiers Including Instructions for Compensating Humidistat and Safety Control Shutoff CONTRACTOR: Read these instructions before installing or servicing humidifier. HOMEOWNER: Save this manual for future reference. Model No. Mfg. Date (see label on unit) Installation Date
2 Table of Contents Connecting to a Power Source...2 Wiring the Air Mover...3 Wiring Variations...5 Installing the Compensating Humidistat...8 Installing the Humidistat to Operate Manually...10 System Checkout...10 Compensating Humidistat Troubleshooting Guide...11 Installing the Safety Control Shutoff...13 Safety Control Shutoff Troubleshooting Guide...14 Connecting to a Power Source READ AND SAVE THESE INSTRUC- TIONS. When selecting a location for mounting the humidifier, make sure that electrical connections can be made without the use of an extension cord. CAUTIONS: This product is for residential applications only and must be installed by a qualified HVAC contractor. Failure to comply could invalidate the product warranty, or result in serious injury or electrocution. The electrical receptacle must be rated at the correct voltage and amperage, or hazardous conditions could result. 120 volt, 1500 watt steam units require a receptacle rated at 120 VAC, 15 amperes (NEMA configurations 5-15R). 240 volt, 2000 watt units require a receptacle rated at 240 VAC, 15 amperes (NEMA configurations 6-15R). All wiring must comply with local codes and ordinances. 2
3 Wiring the Air Mover NOTE: Blower systems that run continuously and change speed by ramping up and down may require a setting change on the furnace board to prevent the blower from ramping down to its lowest speed. Prolonged minimal airflow can allow condensation to build up in the ductwork. To guard against condensation buildup, consult the furnace/heat pump manufacturer for procedures to prevent extremely low air flow. General wiring diagrams follow: Figure 1 (below) 120 volt, 1500 watt high-capacity steam humidifier Figure 2 (pg. 4) 240 volt, 2000 watt high-capacity steam humidifier Wiring for variable applications can be found on pages 5, 6 & 7. Be sure to read all CAUTIONS and WARNINGS before wiring humidifiers. LOW VOLTAGE CONNECTION ONLY Figure Volt, 1500 Watt Steam Humidifier Wiring Blue lines indicate field (installer) wiring 3
4 Due to the high-capacity design of the humidifiers, it is necessary that the furnace air mover be wired to function in cooperation with the humidifier s operation (see Figures 3, 4 and 5, pages 5-7). To achieve synchronization and prevent condensation inside the ductwork, a thermostatic sensor for 24-volt thermal fan control applications has been incorporated into the humidifier s design. The sensor/switch, attached to the humidifier wall, is a sealed unit, preset to turn on when the humidifier s water temperature reaches 170ºF, and to turn off when it falls below 120ºF. NOTE: Even if the heating and cooling system s fan switch is left in the ON position, it cannot be assumed that the homeowner will allow constant operation of the fan motor. Therefore, it is essential that the steam humidifier be wired according to instructions in this manual. CAUTION: Do not activate or alter the normal functions of the home s heating and cooling system, except to coordinate the system s air mover (blower) with the humidifier. Failure to heed this caution could result in serious damage to the heating and cooling system, and/or to the home. LOW VOLTAGE CONNECTION ONLY Figure Volt, 2000 Watt Steam Humidifier Wiring Blue lines indicate field (installer) wiring 4
5 Wiring Variations IMPORTANT: Once the unit is completely installed (including plumbing see humidifier installation manual), check the fan control circuit repeatedly to ensure proper operation. (It may take up to 15 minutes for the humidifier to heat the water and signal the furnace blower to come on.) NOTE: The compensating humidistat is programmed to prevent operation above 50ºF or 45 percent relative humidity. If conditions exceed either of these set points, it may be necessary to bypass the humidistat to perform this test. Diagrams for three steam humidifier wiring variations follow: Figure 3 (below) a SINGLE-SPEED air mover application without air conditioning Figure 4 (pg. 6) a DUAL-SPEED air mover application with air conditioning Figure 5 (pg. 7) a LOW-SPEED air mover application with air conditioning, or a heat pump with air conditioning NOTE: Humidifier terminals provided on the heating system control board should NOT be used for wiring the steam humidifier. Figure 3 Typical Wiring for a Humidifier in a SINGLE-SPEED Air Mover Application without Air Conditioning Blue lines indicate field (installer) wiring 5
6 Figure 4 Typical Wiring for a Humidifier in a DUAL-SPEED Air Mover Application with Air Conditioning Blue lines indicate field (installer) wiring NOTE: Humidifier terminals provided on the heating system control board should NOT be used for wiring the steam humidifier. 6
7 Figure 5 Typical Wiring for a Humidifier to Run on a LOW-SPEED System with Air Conditioning, or a Heat Pump with Air Conditioning Blue lines indicate field (installer) wiring CAUTION: If the heat pump in the fan relay is pre-wired to a speed other than Low, do not change the wiring. The system will function best at the factory settings. NOTES: When attaching the fan safety control shutoff, it is acceptable on 220 volt blower systems to use either power-carrying conductor. Humidifier terminals provided on the heating system control board should NOT be used for wiring the steam humidifier. 7
8 Installing the Compensating Humidistat (Automatic Humidifier Control) DANGER: Disconnect electrical power to the furnace before beginning installation. Contact with a live electrical wire can cause serious injury or electrocution. Use caution when cutting plenum openings and handling ductwork. Sharp edges can cause serious cuts and bleeding. CAUTION: Do not mount the compensating humidistat on the supply duct or plenum. The unit will not withstand supply temperatures. Do not set the humidity so high that condensation forms on windows or walls. Indoor condensation may result in damage to the home. STEP 1: Check Contents of the Humidistat Carton Make sure the following components are enclosed (see Figure 6, below): Compensating Humidistat Outdoor Temperature Sensor Sensor Shield Manual Mode Faceplate Mounting Template Figure 6 STEP 2: Disassemble the Humidistat Pull the knob off, then remove the cover by inserting a screwdriver in the slot on the right side of the humidistat. STEP 3: Mount the Humidistat on the Cold Air Return Select a location to mount the compensating humidistat that is at least 6 inches upstream from the fresh air intake ductwork, if applicable (see Figure 7, below). Figure 7 Once a location has been selected, carefully position the compensating humidistat template, then drill and cut the opening. Use four sheet metal screws and the gasket (provided) to mount the unit over the duct opening. Make sure the humidistat is sealed tightly to the duct. STEP 4: Select an Exterior Location to Mount the Outdoor Temperature Sensor Placement of the outdoor temperature sensor must meet these requirements: It must be mounted on the North, Northeast or Northwest side of the house, where direct sunlight will not influence the sensor. 8
9 It must be placed at least 3 feet from all exhaust vents. It must be installed above the expected snow line (see Figure 8). Figure 9 Figure 8 STEP 6: Route the Sensor Wire to the Selected Location CAUTION: Incorrect indoor humidity levels will result if these requirements are not met. NOTE: For manual operation, do not install the outdoor sensor wire. STEP 5: Locate an Existing Indoor/ Outdoor Access Hole If possible, insert the sensor cable through an existing indoor/outdoor access hole for cable TV lines, telephone lines, A/C lines, etc. CAUTION: Make sure there are no active high-voltage wires in the hole. As an alternative, the sensor can be mounted in the center of a 6-inch fresh air intake duct. However, the sensor bulb must be no further than 30 inches from the outside wall. (See Figure 9, top right.) NOTE: If it is not possible to install the outdoor temperature sensor in any of these configurations, the compensating humidistat can be installed to operate manually. (See Installing the Compensating Humidistat to Operate Manually, page 10.) Run wire between the compensating humidistat and the outdoor sensor lead. If the sensor is outdoors, snap the probe end of the sensor into the sensor shield and attach it to an exterior wall. The probe must be completely covered by the shield. NOTE: The outdoor temperature sensor wire must not exceed 30 feet in length. CAUTION: Do not run outdoor temperature sensor wire alongside wires carrying high voltage (120 VAC or higher). Do not run the sensor wire through conduit. STEP 7: Attach the Sensor Wire to the Humidistat Strip the connecting wire 1/4" and attach the two internal wires to the terminals labeled Outdoor Temperature Sensor on the humidistat. STEP 8: Select a Power Source Select a source for 24 VAC to power the compensating humidistat, based on the SINGLE-SPEED, DUAL-SPEED and LOW- SPEED wiring variations shown in Figures 3-5 (pages 5-7). The voltage to the humidistat must be between 22 and 30 VAC. 9
10 NOTE: The compensating humidistat will operate properly only with a continuous power source. A minimum 10 VA (volt amperes) is required. STEP 9: Connect the Compensating Humidistat to the Humidifier Strip the wires used for all the humidistat terminal connections 1/4 inch. Wire the humidistat based on the SINGLE-SPEED, DUAL-SPEED and LOW-SPEED wiring variations shown in Figures 3-5 (pages 5-7). Do not use a current-sensing (A50) relay. STEP 10: Set the Humidistat Consult the compensating humidistat homeowner s manual for proper humidity settings. INSTALLING THE HUMIDISTAT TO OPERATE MANUALLY If it is not possible to use the outdoor temperature sensor, or if the homeowner wants to control the humidifier manually, the humidistat can be reconfigured for manual operation. (See Figure 10, below.) Automatic Figure 10 Manual 1. Locate the three-pin arrangement marked AUTO/MAN, protruding from the control board (directly to the right of the wiring connections). 2. Pull upward to remove the black, twopin connector from the auto position. Reinstall it in the manual position (on the center and right-hand pins). CAUTION: Do not attach sensor wire to the blue wiring connection block. 3. Follow Steps 8 (Select a Power Source) and 9 (Connect the Compensating Humidistat to the Humidifier) to complete the wiring. Apply the manual mode faceplate to the compensating humidistat cover. Reattach the cover to the base and reinstall the knob. SYSTEM CHECKOUT NOTE: If conditions exceed 50ºF or 45 percent relative humidity, it may be necessary to bypass the humidistat to perform this test. 1. To conduct a system test, be sure that 24 VAC is applied to the 24 VAC terminals of the compensating humidistat. 2. Reattach the humidistat cover and knob to the base. 3. Rotate the knob on the humidistat clockwise ( ) to the Test position. If everything is set up correctly, the humidifier should begin operating. In Test mode, the humidistat will operate for approximately one minute. If the humidifier does not activate properly in Test mode, refer to the Troubleshooting Guide on page Set the compensating humidistat. If the home is occupied, set the humidistat knob to 5. (For manual operation, set the knob to 35%.) If the home is vacant, turn the humidistat knob counterclockwise ( ) to Off. 5. Tell the homeowner to refer to the Compensating Humidistat Operating Instructions for direction regarding initial adjustment. 10
11 COMPENSATING HUMIDISTAT TROUBLESHOOTING GUIDE (applies to automatic and manual operation, unless otherwise indicated) PROBLEM: Humidifier does not operate in Test mode SOLUTION(S): Make sure the furnace blower is operating and the thermostat is calling for heat. Confirm that the outdoor temperature sensor is connected to the Outdoor Temperature Sensor terminals on the compensating humidistat. (For manual operation, make sure the jumper pins are positioned correctly.) Check the wiring diagrams (Figures 1-5) for correct installation. Check the voltage at the humidistat 24 VAC terminals. (Voltage should be between 22 and 30 VAC.) Make sure the control knob has not been left in the Test position. In Test mode, the humidifier will not continue to operate after approximately one minute. PROBLEM: Humidifier operates only in Test mode SOLUTION(S): Check the resistance of the sensor by removing the leads from the humidistat terminals, and measuring the resistance across the wires with an ohmmeter. Compare the reading to the temperature/ resistance chart, top right. For automatic applications Make sure the outdoor temperature sensor is mounted completely outside the house (i.e., not recessed into the hole) on the North, Northeast or Northwest side, away from direct sunlight. Make sure the outdoor temperature sensor is mounted at least 3 feet away from all exhaust vents. If the outdoor temperature sensor is mounted in the fresh air intake duct, make sure the probe is no further than 30 inches from an outside wall. NOTES: Temperature/Resistance Chart 100 F 6,000 ohms 38 C 90 F 7,500 ohms 32 C 80 F 9,500 ohms 27 C 70 F 11,500 ohms 21 C 60 F 14,000 ohms 16 C 50 F 18,000 ohms 10 C 40 F 23,000 ohms 4 C 30 F 28,500 ohms -1 C 20 F 37,000 ohms -7 C 10 F 46,500 ohms -12 C 0 F 61,500 ohms -18 C -10 F 78,500 ohms -23 C -20 F 105,500 ohms -29 C -30 F 135,000 ohms -34 C In AUTOMATIC applications, if the outdoor temperature is greater than +50ºF (+10ºC) or less than 32ºF (-35.6ºC), the compensating humidistat will not operate (except in Test mode). In both AUTOMATIC and MANUAL applications, if the relative humidity in the home is higher than the knob setting, the compensating humidistat will not operate the humidifier. Similarly, the humidistat 11
12 will not operate if the indoor relative humidity exceeds 45 percent. PROBLEM: Humidifier operates constantly SOLUTION(S): Check the humidistat setting. If the relative humidity in the home is less than the knob setting, the humidifier will operate until the humidity level is higher than the knob setting. In Test mode, verify that the humidifier will shut off after approximately one minute. Check the resistance of the sensor. (See previous problem/solution.) For automatic applications Make sure the outdoor temperature sensor is mounted completely outside the house (i.e., not recessed into the hole) on the North, Northeast or Northwest side, away from direct sunlight. Turn the compensating humidistat knob counterclockwise ( ) to the Off position and observe whether the humidifier turns off. If the humidifier continues to operate, perform the following: Check the wiring diagrams (Figures 1-5) for correct installation. Remove the wires from the humidistat s Out terminals. If the humidifier continues to operate, check the humidifier. For automatic applications, make sure the outdoor temperature sensor wiring does not run alongside wires carrying high voltage (120 VAC or higher). PROBLEM: Furnace or heat pump blower system runs continuously; condensation is building up in ductwork SOLUTION(S): It may be necessary to make a setting change on the furnace or heat pump board to prevent the blower from shifting down to its lowest idling speed. Consult the furnace/heat pump operating manual or contact the manufacturer for procedures to prevent extremely low air flow. PROBLEM: Humidifier or compensating humidistat chatters or clicks on and off rapidly SOLUTION(S): Use a voltmeter to check for a steady 22-to-30 VAC. 12
13 Installing the Safety Control Shutoff* *This is NOT a fan control relay. It is strictly an automatic shutoff for added safety. This safety control shutoff is designed to prevent the humidifier from operating if the furnace blower fails, thereby helping to protect HVAC equipment and the home from water damage and/or mold. NOTE: New steam humidifier installations that do not include the safety control shutoff are not warranted by the manufacturer if property damage is linked to blower failure. WARNINGS: The safety control shutoff is intended for use with steam humidifiers only. Other uses may damage the shutoff, the wiring and/or devices to which the shutoff is connected. Wiring from other electric devices can interfere with the safety control shutoff s performance. Such devices should be kept as far away from the shutoff as possible preferably six or more inches. INSTALLATION INSTRUCTIONS NOTE: Humidifier fan control wiring must be connected according to instructions in the humidifier installation manual. 1. Remove the screw from the cover of the safety control shutoff. Open the hinged cover and install the shutoff onto the furnace blower common wire. (See Figure 11.) CAUTION: Figure 11 Place the wire inside the open end of the safety control shutoff so that it runs straight (no slack or 13 bends) through the four flanges designed to hold the wire in place. NOTE: For small-diameter wire, pass the wire through the flanges, wrap it around the base of the safety control shutoff and pass the wire through the flanges again. This helps ensure a solid contact with the sensor on the shutoff circuit board. 2. Replace the screw to hold the cover in place. (See Figure 12.) CAUTION: Make sure all other wires are at least 6 inches away from the safety control shutoff. Figure Wire the safety control shutoff in series with the humidifier, humidistat and any other control devices installed with the humidifier, as follows (refer to Figures 3-5, pages 5-7): a. Connect the wire from the humidistat terminal block to the safety control shutoff, then from the other connection on the safety shutoff to the terminal on the humidistat. b. Connect the remaining humidistat terminal to the remaining humidifier terminal. 4. Verify that the safety control shutoff 30-minute test phase (see Operation and Troubleshooting Guide, page 14) is functioning correctly.
14 Safety Control Shutoff (SCS) Operation and Troubleshooting Guide CONDITION SCS LED (Light-Emitting Diode) shows rapid series of red, green and yellow lights, followed by no LED display. Humidifier won t operate. No SCS LED display. Humidifier operates. SCS LED shows continuous yellow. Humidifier won t operate SCS LED displays continuous red. Humidifier operates. SCS LED shows continuous green. Humidifier won t operate. SCS LED shows flashing red. CAUSE Condition Normal. SCS processor is powering up and checking internal operation. Problem! SCS circuit is not closing or humidistat is not calling for humidity. Condition Normal. This is a test phase. SCS will wait 30 minutes to detect furnace blower operation. If the furnace blower is detected, the system will function properly. Problem! During the 30-minute test phase, the SCS has failed to detect the furnace blower and turned the humidifier off. Condition Normal. All systems (furnace, humidistat, humidifier and SCS) are operating properly. Problem! The SCS has failed to detect the furnace blower for the third time and, as a safety precaution, has locked out the humidifier. This is an indication that some aspect of the system (furnace, humidistat, humidifier or SCS) has malfunctioned. Figure 13 ACTION REQUIRED No action required. Check SCS for power; check humidistat operation. If humidity is about 45% or outdoor temperature is above 50ºF, the humidifier won t operate unless the humidistat is set to Test Mode. No action required. Turn the humidistat off, then on again, to reset the system. Although unlikely to happen, this failure/reset process can occur twice before further action is necessary. No action required. Contact your HVAC contractor ASAP to check and repair the system. IMPORTANT: Before the SCS can be reset, the system must be checked and repaired by a licensed contractor. To reset the SCS, the contractor must insert a thin, rigid rod, such as an unfolded paperclip, into the smallest hole in the face of the SCS, next to the green connector block. (See Figure 13, left.) Gentle pressure will depress the internal button to reactivate the safety control shutoff. The red light will stop flashing, indicating that the system is reset. 14
15 Notes 15
16 2006 Part No HBP 2/06 16
Safety, Installation, and Operation Manual
Automatic Steam Humidifier Control Safety, Installation, and Operation Manual READ COMPLETE INSTALLATION INSTRUCTIONS BEFORE STARTING. WARNING This product must be installed by a qualified heating and
More informationAutomatic Digital Humidifier Control
Automatic Digital umidifier Control Safety and Installation Instructions EAD COMPLETE INSTALLATION INSTUCTIONS AND TEMPLATE BEFOE STATING. WANING ATTENTION INSTALLE: This product must be installed by a
More informationModel 8120 and 8126 Safety & Installation Instructions
Ventilation Controller Model 8120 and 8126 Safety & Installation Instructions FAMILIARIZE YOURSELF WITH THE INSTALLATION INSTRUCTIONS BEFORE STARTING DANGER ATTENTION INSTALLER: To prevent serious injury
More informationInstallation Instructions
FAVXXR6C2100-A01 Vent Damper and Control Installation Instructions FAMILIARIZE YOURSELF WITH THE INSTALLATION INSTRUCTIONS BEFORE STARTING ATTENTION INSTALLER: This product must be installed by a qualified
More informationInstallation Instructions. SPANISH Installation Instructions. FRENCH Installation Instructions
Installation Instructions for Models 45, 90 and 190 Bypass Drum Humidifiers Inside Front Cover Model / Modelo / Modèle 45 Contractor: Read these instructions before installing or servicing humidifier.
More informationInstallation Instructions Owner s Manual
Installation Instructions Owner s Manual FOR USE WITH GAS, OIL and HYDRONIC FORCED AIR FURNACES SEQUENCE OF OPERATION The AUTOFLO Model s SC15 & 250 use the evaporative principal to add moisture to the
More informationSafety & Installation Instructions
Premium Programmable Thermostat Safety & Installation Instructions Model 8570 READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS PAGE SPECIFICATIONS............................. 1 WIRE REQUIREMENTS.........................
More informationinstallation and start-up instructions HUMIDIFIERS AND HUMIDISTAT
installation and start-up instructions HUMIDIFIERS AND HUMIDISTAT HUM Cancels: II 912D-56-3 II HUM-56-1 7-98 MODEL HUMBBLFP1025-A-- FAN-POWERED HUMIDIFIER MODEL HUMBBLBP2018-A-- BYPASS HUMIDIFIER MODEL
More informationHE220, HE260 Humidifier Installation Kit
HE220, HE260 Humidifier Installation Kit WELCOME To the comfortable world of humidified air. When you use your Honeywell humidifier, you notice that your skin is not as dry, and that your scratchy throat
More informationModel Smart Digital Humidistat
Model 072000 Smart Digital Humidistat Installation and Owner's Manual TB 213 P/N 090375A0213 REV. E December 5, 2006 Copyright 2004-2006, EWC Controls Inc., All Rights Reserved RH OD %RH TEMP Package includes:
More informationOperator: Save these instructions for future use!
F145-1328/F145-1378 Indoor /Outdoor INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS
More informationModel 1750A/ 1770A Dehumidifier Installation Instructions
Model 1750A/ 1770A Dehumidifier Installation Instructions Safety Instructions WARNING 1. Improper installation may cause property damage or injury. Installation, service, and maintenance must be performed
More informationInstallation Instructions
HUMBBSFP1016 HUMCCSFP1016 Small Fan Powered Humidifier and Humidistat Installation Instructions! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.
More informationHE360 Humidifier Installation Kit
HE360 Humidifier Installation Kit INSTALLATION INSTRUCTIONS WELCOME To the comfortable world of humidified air. When you use your Honeywell humidifier, you notice that your skin is not as dry, and that
More informationContinue to next pages for Template instructions, Owners Guide, Humidistat Instructions.
This.Pdf document is for informational purposes only and contains an Installation Template. The Template in this.pdf document is not to scale. Do not use for sizing purposes. Continue to next pages for
More informationCOMBUSTION AIR SYSTEM
COMBUSTION AIR SYSTEM MODEL: CAS-4JR This product is designed for use with any natural gas or LP burning furnace, water heater, or boiler with a 24 VAC control system. It may be used with a residential
More informationModel 8140 & 8141 Fresh Air Ventilator Installation and Operations Manual
Model 8140 & 8141 Fresh Air Ventilator Installation and Operations Manual FILTER COVER VENTILATION CONTROLLER INLET COLLAR OUTLET COLLAR SAFETY INSTRUCTIONS WARNING 1. 120 Volts may cause serious injury
More informationRECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS
FOR USE WITH ALL FORCED AIR SYSTEMS SEQUENCE OF OPERATION The AUTOFLO Model s 200P, 800BP and 97 Humidifiers use the evaporative by-pass principal to add moisture into the return air duct of your central
More informationSafety and Installation Instructions Model 1700
Dehumidifier Filter Access Humidity Control Inlet Filter Access Outlet Service Access Port Wiring Access Wire Routing Port Drain On/Off Switch Safety and Installation Instructions Model 1700 INSTALLER
More informationRSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...
Installation & Operating Manual RSIF Power Venter USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration... Chapter
More informationDISHWASHER INSTALLATION GUIDE SPECIFICATIONS, INSTALLATION, AND MORE
DISHWASHER INSTALLATION GUIDE SPECIFICATIONS, INSTALLATION, AND MORE COVE DISHWASHER Contents 3 Cove Dishwasher 4 Specifications 7 Door Panel 9 Installation 15 Troubleshooting Features and specifications
More informationInstallation Instructions
Installation Instructions 30" ELECTRIC Downdraft Cooktop Modules selected at time of purchase IMPORTANT: Read and save these instructions. Part No. 208040 A 438589 Quick Reference Table of Contents: Pages
More informationR Series B & T2 Model
FRONT R Series B & T2 Model Fan Forced Wall Heaters 4-1/4 (108mm) NOTE: Knockouts in top same dimensions 3-1/4 3-1/4 (108mm) (108mm) as bottom 16-7/8 (429mm) 13-7/8 (352mm) BOTTOM 13-7/8 (352mm) 7-3/4
More informationNOTICE . SAFE SERVICING PRACTICES. Electric Wall Oven with Electronic Oven Control
SERVICE DATA SHEET 318047418 (0504) Rev. A Electric Wall Oven with Electronic Oven Control NOTICE This service data sheet is intended for use by persons having electrical and mechanical training and a
More informationCom-Pak Heater Benefits You Can Depend On Com-Pak Models Line Model w/o Model w/ Voltage Thermostat Thermostat Watts Amps (1) (2)
Benefits You Can Depend On Dual safety features Primary: power reset thermal switch Secondary: over temperature thermal fuse Heating element style quickly warms your room, and quickly cools when heater
More informationRSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2
3002239 RSIF 2014-04-04 Installation and operation manual RSIF power venter READ AND SAVE THESE INSTRUCTIONS! Product information Chapters 1 + 2 Mechanical installation Chapter 3 Electrical installation
More informationResidential Steam Humidifier
Residential Steam Humidifier Model HUMXXSTM3034 Residential Steam Humidifier Owner s Manual Includes Safety & Operating Instructions READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS Safety... 2 Introduction...
More informationCAUTION WARNING INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER MODEL HCWH-065 (Y3013) DEHUMIDIFIERS
DEHUMIDIFIERS 506451-01 04/2012 HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER MODEL HCWH-065 (Y3013) FRONT VIEW (with alternate outlet location
More informationSEA FROST SHORE ASSIST SA-1 R-12 THIS MANUAL IS SUPPLEMENTAL TO THE SEA FROST R-12 ENGINE DRIVE MANUAL INSTALLATION INSTRUCTIONS
148 OLD CONCORD TURNPIKE BARRINGTON, NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 E-Mail:sales@seafrost.com www.seafrost.com SEA FROST SHORE ASSIST SA-1 R-12 THIS MANUAL IS SUPPLEMENTAL
More informationInstallation, Safety & Maintenance Manual Model 1750A/1770A
Central Dehumidifier Filter Access Humidity Control Inlet Outlet Service Access Port Filter Access Wiring Access Wire Routing Port Drain On/Off Switch Installation, Safety & Maintenance Manual Model 1750A/1770A
More informationINSTALLATION & USER MANUAL
INSTALLATION & USER MANUAL HC Digital Automatic Humidistat (Y3760) CONTROLS 506808-01 3/2016 Supersedes 6/2011 picture goes here THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE NOTICE
More informationTECHNICAL BULLETIN. Model Smart Digital Humidistat. Installation and Owner's Manual. General Description
TECNICAL BULLETIN Model 072000 Smart Digital umidistat Installation and Owner's Manual TB 213 P/N 090375A0213 REV. G Copyright 2004-2008, EWC Controls Inc., All Rights Reserved R %R TEMP Package includes:
More informationModel 8142 and 8142NC Fresh Air Ventilator Installation and Operating Instructions
Model 8142 and 8142NC Fresh Air Ventilator Installation and Operating Instructions MODEL 8142 FRESH AIR ILATOR MODEL 8142NC FRESH AIR ILATOR OUTLET COLLAR MOUNTING BRACKET ILATION CONTROLLER OUTLET COLLAR
More informationOperator: Save these instructions for future use!
HITE-RODERS 1F97-51 7-Day Electronic Digital Thermostat INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLO ALL INSTRUCTIONS CAREFULL BEFORE INSTALLIN OR
More informationModel 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions
Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions ON/OFF button used to turn the ventilator on and off Up/Down buttons used to change humidity or vent time setting
More informationInstaller Guide. WARNING Important Safety Information. 1 Specifications
1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Conventional and Heat Pump Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE READ ALL
More informationDRAFT INSTALLATION INSTRUCTIONS. Solid-State Series !! NOTE!! Covers the following models: Refer to INSERT for additional information
INSTALLATION INSTRUCTIONS Solid-State Series!! NOTE!! Covers the following models: " CS6100 - CS7100 " CS6200 - CS9200 " CS6220 - CS9220 " CS6230 - CS9230 " CS6500 - CS7500 " CS6330 - CS9300 " CS9400 -
More informationThe Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury.
The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury. The Warning signal alerts you to potential hazards or unsafe practices which,
More informationHE420A Steam Power Humidifier
READ AND SAVE THESE INSTRUCTIONS HE420A Steam Power Humidifier OWNER S GUIDE 69-1112-2 HE420A STEAM POWER HUMIDIFIER WELCOME... to the comfortable world of humidified air. With your Honeywell humidifier
More informationModel 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions
Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions ON/OFF button used to turn the ventilator on and off Up/Down buttons used to change humidity or vent time setting
More informationPlease read this manual completely before attempting to install, operate or service this equipment.
Service Manual POWER OVEN OFF COOL DOWN COOK LIGHT OFF OVEN READY TEMPERATURE GAS CONVECTION OVEN TIME GAS SHUTOFF ON OFF MODELS 6/13 THE OVEN E SERIES Please read this manual completely before attempting
More informationHE120, HE160 Humidifier Installation Kit
HE120, HE160 Humidifier Installation Kit INSTALLATION INSTRUCTIONS WELCOME To the comfortable world of humidified air. When you use your Honeywell humidifier, you notice that your skin is not as dry, and
More informationInstaller Guide. WARNING Important Safety Information. 1 Specifications
1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Heat Pump or 2 Heat / 2 Cool Conventional Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE
More informationFCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual
FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual FAN POWERED TERMINALS Receiving Inspection Prior to removing the shipping material, visually inspect the packing materials. There
More informationDryAire DRYING CABINET
CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS L-72 DryAire DRYING CABINET Model LMA1053L JOB AID Part No. 8178202 FORWARD This Whirlpool Job Aid, DryAire Drying Cabinet, (Part No. 8178202), provides
More information27 ELECTRIC & GAS DRYERS
CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS L-63 27 ELECTRIC & GAS DRYERS JOB AID Part No. 4322260 I INTRODUCTION This Job Aid, 27 ELECTRIC & GAS DRYERS, (Part No. 4322260), provides specific
More informationECM OPERATION MANUAL
ECM OPERATION MANUAL FOR USE WITH MODEL: SINGLE STAGE OH6FA072DV4 OH8FA119DV5 OD6F/RA072DV5 OL6F/RA072DV5 2-STAGE OH6FX072DV4 OD6F/RX072DV5 OL6F/RX072DV5 : IF YOU DO NOT FOLLOW THE SAFETY PRECAUTIONS BELOW
More informationBESF Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4
Installation & Operating Manual BESF Box Ventilator USA CAN Product Information... Chapter 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration...
More informationT8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase
M3375 M3375 T890A/908AJ Heating or Cooling Thermostat/Wallplate; T890A/Q68B Heating/Cooling Thermostat/Subbase Installation Instructions for the Trained Service Technician. Preparation NOTE: Order Q68B
More informationDS 2001 REVISED Humidifier Assembly and Instruction Manual
DS 2001 REVISED Humidifier Assembly and Instruction Manual Contents Parts list Selecting a location Assembly Hanging the Basin Electrical connections Water connections 2 4 4 Installing the Disk Wheel Installing
More informationHE420A,B and HE460A,B Steam Power Humidifiers OWNER S GUIDE
HE420A,B and HE460A,B Steam Power Humidifiers OWNER S GUIDE U.S. Registered Trademark Copyright 1998 Honeywell Inc. All Rights Reserved 69-1112-1 WELCOME... to the comfortable world of humidified air.
More informationV SERIES HDR GAS RANGES
SERVICE MANUAL ONE POWERFUL PACKAGE V SERIES HDR GAS RANGES TOPS Open Top Hot Top Griddle Top Work Surface BASES Standard Oven Convection Oven Cabinet Base - NOTICE - This manual is prepared for use by
More informationCT500 Electronic Thermostat
CT500 Electronic Thermostat OWNER'S GUIDE MERCURY NOTICE If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of it properly.
More informationBK AND BKT BLOWER ACCESSORY INSTALLATION INSTRUCTIONS
BK AND BKT BLOWER ACCESSORY INSTALLATION INSTRUCTIONS MODEL BK MANUALLY CONTROLLED BLOWER MODEL BKT THERMOSTATICALLY CONTROLLED BLOWER WARNING: ELECTRICAL GROUNDING INSTRUCTIONS This appliance is equipped
More informationInstallation Guide.
Installation Guide www.evergreendealer.com www.thedealertoolbox.com When Regal Beloit acquired General Electric s Commercial and HVACR Motors and Capacitors businesses in 2004, it also acquired the rights
More informationSC Installation, Operation & Application Guide
SC 5211 2-Stage Heat Pump Auto Changeover Hardwire Programmable Electronic Thermostat 7-Day, 5-2-Day or 5-1-1-Day Programmable Configurable 2-Stage Heat Pump Systems Large Display With Backlight Selectable
More informationInstallation and Operation Manual
Model 8120X Digital Ventilation Controller CODE MIN/ HR Installation and Operation Manual TABLE OF CONTENTS WARNINGS AND CAUTIONS Warnings and Cautions... 3 Package Contents... 4 Specifications.... 4 Mounting
More informationULTRAMAX GOLD UMX REMOTE LAMP AIR DISINFECTION SYSTEMS w/ ODOR REDUCING TECHNOLOGY (PCO) OWNERS GUIDE
ULTRAMAX GOLD UMX REMOTE LAMP AIR DISINFECTION SYSTEMS w/ ODOR REDUCING TECHNOLOGY (PCO) OWNERS GUIDE Models: UMX-1200T/ UMX-1900T / UMX-1202T/ UMX-1902T 120-240VAC Power Input with Remote Mount Lamps
More informationENERVEX ADC100 DRAFT CONTROL
ENERVEX ADC100 DRAFT CONTROL 3916067 04.16 Installation & Operating Manual READ AND SAVE THESE INSTRUCTIONS! ENERVEX Inc. 1685 Bluegrass Lakes Parkway Alpharetta, GA 30004 USA P: 770.587.3238 F: 770.587.4731
More informationInstallation Instructions Part No , Part No Part No
Torsion-Flex Motor mount for PSC motors and Rigid-Mount for ECM motors Replacement Kit Cancels: New Installation Instructions Part No. 327752-401, Part No. 327753-401 Part No. 327754-401 IIK-310A-45-11
More informationINSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT
RV Products Division INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330A755 CONTROL BOX KIT (12 VDC HEAT/COOL) 8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)
More informationOperation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.
Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause
More informationComfortSTEAM TM. Humidification System
Notice to Contractor: Once installation is complete, please leave this manual with the customer for future reference. READ AND SAVE THESE INSTRUCTIONS Humidification System TRION www.trioniaq.com COMFORTSTEAM
More informationCooktop Chimney Ventilation Hoods
INSTALLATION GUIDE Cooktop Chimney Ventilation Hoods Contents Wolf Cooktop Chimney Ventilation Hoods.......... 3 Cooktop Chimney Hood Specifications............ 4 Cooktop Chimney Hood Installation.............
More informationWARNING WARNING TROUBLESHOOTING GUIDE INTEGRATED FURNACE CONTROL MODULE
TROUBLESHOOTING INTEGRATED FURNACE Failure to read and follow all instructions carefully before installing or operating this control, could cause personal injury and/ or property damage. 50A55 INTEGRATED
More informationThree Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.
Three Phase Simplex Installation Instructions and Operation/Troubleshooting Manual This control panel must be installed and serviced by a licensed electrician in accordance with the National Electric Code
More informationInstallation Instructions VITOTRONIC 300
Installation Instructions Vitotronic 300 Model KW3 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits Part No. Z001 231 VITOTRONIC 300 Certified
More informationCONTENTS CONSIDERATIONS. General Plumbing Component Connection ILLUSTRATION. Control System CONFIGURATION. Voltage Verification CONNECTION
AIR SERIES SYSTEM INSTALLATION MANUAL CONTENTS CONSIDERATIONS General Plumbing Component Connection 2 2 2 ILLUSTRATION Control System 3 CONFIGURATION Voltage Verification 4 CONNECTION Component Connection
More informationELECTRONIC AIR CLEANER SAFETY AND INSTALLATION MANUAL MODEL 5000 TABLE OF CONTENTS
ELECTRONIC AIR CLEANER SAFETY AND INSTALLATION MANUAL MODEL 5000 TABLE OF CONTENTS Safety Instructions...2 Specifications...2 Components...3 Installation...4 Operating Instructions...6 Trouble Shooting
More informationINSTALLATION INSTRUCTIONS FOR MOUNTING KIT
RV Products Division INSTALLATION INSTRUCTIONS FOR 8330-5501 MOUNTING KIT 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330B755 CONTROL BOX KIT (12 VDC HEAT/COOL) 8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)
More informationHT-2 / 9600 Series Control Contents
HT-2 / 9600 Series Control Contents Tools & Parts Tools Required Parts Required Error Messages 3 Flashing Dots Pressure or Flow Switch Not Activated Pressure or Flow Switch Activated Temperature Sensor
More informationWARNING: ELECTRICAL GROUNDING INSTRUCTIONS
BK AND BKT BLOWER ACCESSORY INSTALLATION INSTRUCTIONS Model BK Manually led Blower Model BKT Thermostatically led Blower WARNING: ELECTRICAL GROUNDING INSTRUCTIONS This appliance is equipped with a three-prong
More informationType 300 Series Electrode Stabilization Ovens
OPERATING INSTRUCTIONS Type 300 Series Electrode Stabilization Ovens MODEL PART # DESCRIPTION (All 50-60 Cycles) TEMP RANGE** INSULATION CHAMBER SIZE CAPACITY WEIGHT & DIMENSIONS 120/240 Volt Models with
More informationCUSTOMER SERVICE. Toll-free:
Rev Aug/1 Rotary Disc Humidifier (All Models) Installation & User Manual IMPORTANT Thank you for selecting the Desert Spring Rotary Disc Humidifier. Carefully read this manual before starting your installation.
More informationElectronic Air Cleaner
by White-Rodgers Electronic Air Cleaner 240 Volt 50/60 Hz SST Super Slim Twin Model Number 10C27S-010 14C27S-010 20C27S-010 UST Universal Slim Twin Model Number 16C27S-010 OWNERS MANUAL WHITE-RODGERS SUPER
More informationInstallation Instructions
Installation Instructions EHMA SERIES ELECTRIC HEATERS FOR PAM3 SERIES PACKAGE AIR CONDITIONERS PHM3 SERIES PACKAGE HEAT PUMPS TABLE OF CONTENTS SAFE INSTALLATION REQUIREMENTS... 2 GENERAL INFORMATION...
More informationService Manual Model 3163
Service Manual Model 3163 Contents Important Safety Information.......... 1 Specifications.................. 2 General Information.............. 2 Direct Vent Requirements........... 2 Propane System................
More informationInstallation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324
Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324 To prevent accidents, which could cause serious injury or death, as well as machine damage read these instructions before installation
More informationINSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000R Part No. 4028407 Dehumidifier & Ventilation System Controller 4201 Lien Road, Madison, WI 53704 TOLL-FREE (800)-533-7533
More informationINSTALLATION GUIDE Dual Fuel Ranges
INSTALLATION GUIDE Dual Fuel Ranges Contents Wolf Dual Fuel Ranges......................... 3 Safety Instructions............................ 4 Dual Fuel Range Specifications.................. 5 Dual Fuel
More informationHot Water Boilers 810(E), 815(E), 830(E), 850(E) Table of Contents
Hot Water Boilers 810(E), 815(E), 830(E), 850(E) Operator Manual Model 810(E) Safety Information...2 Rough-In Drawing...3 General Description...4 Installation...4 Priming...5 Cleaning...5 Table of Contents
More informationW43A Humidistat. Features and Benefits
Master Catalog 125 Humidity Controls Section W Product/Technical Bulletin W43A Issue Date 1095 W43A The W43A controls humidifying and/or dehumidifying equipment. Typical uses include the control of humidity
More informationD2E Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS D2E Duct Smoke Detector Specifications Operating Temperature: 20 to 60 C Storage Temperature: 20 to 60 C Humidity: 0% to 93% Relative Humidity Non-condensing Air
More informationWARNING Important Safety Information
Builder Series Non-Programmable Thermostat MODEL 00NC Heat Only or Cool Only Thermostat Before Installing, Programming or Operating, PLEASE READ ALL INSTRUCTIONS Specifications Temperature Adjustment WARNING
More informationINSTRUMENTATION AND CONTROL DEVICES FOR HVAC
PART 1 GENERAL 1.01 RELATED REQUIREMENTS SECTION 23 0913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC A. Section 26 2717 - Equipment Wiring: Electrical characteristics and wiring connections. 1.02 ADMINISTRATIVE
More informationWARNING Important Safety Information
Builder Series Non-Programmable Thermostats MODEL 1000 MODEL 0 1 2 3 4 Single Stage Heat / Cool Conventional and Heat Pump Multi-Stage 2 Heat / 1 Cool Conventional and Heat Pump Before Installing, Programming
More informationSchneider Electric Erie T155 Series
Schneider Electric Erie T Series Non-Digital, On/Off Thermostat General Instructions Application The T series thermostat provides on/off control for low voltage and line voltage valves, relays and fan
More informationSteam Humidification Light Commercial Applications. Better technology means better business.
Steam Humidification Light Commercial Applications Better technology means better business. Aprilaire Steam Humidifiers are built to last. Through extensive research and over 50 years expertise in humidification
More informationSPECIFICATIONS - IMPORTANT -
SPECIFICATIONS - IMPORTANT - THE SPECIFICATIONS GIVEN IN THIS PUBLICATION DO NOT INCLUDE NORMAL MANUFACTURING TOLERANCES. THEREFORE, THIS UNIT MAY NOT MATCH THE LISTED SPECIFICATIONS EXACTLY. ALSO, THIS
More informationπ H-7147 SANITAIRE EON QUIET CLEAN VACUUM SAFETY uline.com
π H-7147 SANITAIRE EON QUIET CLEAN VACUUM 1-800-295-5510 uline.com SAFETY PAGE 1 OF 9 NOTE: When using an electrical appliance, basic precautions should always be followed, including the following: READ
More informationDH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630-377-6495 www.systemsensor.com
More informationIntegrated Ventilation System
Integrated Ventilation System For use with models: IVS1, IVSR1, IVS2, IVSR2 Installation Instructions Part No. 65278 Rev. K Table of Contents Important Safety Instructions... 1 Important Information About
More informationB.C.S. Shop Heaters 26, 30 & 36 (36 shown)
BIOMASS COMBUSTION SYSTEMS, INC. 67 MILLBROOK ST., SUITE 502 WORCESTER, MA 01606 508-798-5970 - FAX 508-798-5971 B.C.S. Shop Heaters 26, 30 & 36 (36 shown) INSTALLATION MANUAL HAND FIRED SYSTEMS 8-09 Biomass
More informationTable of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5
Introduction The Scotsman Compact Refrigerator is a unique product, capable of being built into a cabinet because of its front vented, forced-air cooling system. It s also designed to be a companion to
More informationCommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET
CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or
More informationINSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS
RV Products Division INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330C755 CONTROL BOX KIT (12 VDC HEAT READY) 8530-750 CONTROL BOX KIT
More informationInstallation, Service, and Troubleshooting Instructions
Installation, Service, and Troubleshooting Instructions GENERAL...2 INSTALLATION...2-11 Thermostat Placement...2 Wiring Requirements...2 VVT Relay Packs...4 Wiring Connections for Monitor Thermostat...4
More informationSAFETY AND INSTALLATION MANUAL MODEL 8100
SAFETY AND INSTALLATION MANUAL ENERGY RECOVERY VENTILATORS MODEL 8100 Provides year-round fresh air Recovers 77% of the apparent heating or cooling energy from the exhausted air See Warnings Page 3 Table
More informationSERVICING S-15 CHECKING CAPACITOR
S-15 CHECKING CAPACITOR The direct drive motors are of the permanent split capacitor design. A run capacitor is wired across the auxiliary and a portion of the main windings. The capacitors primary function
More informationIMPORTANT WARNINGS IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT WARNINGS IMPORTANT SAFETY INSTRUCTIONS Suncourt recommends professional installation of the Airiva (or by an accomplished DIY person) Please read and save these entire instructions before starting
More information