1 5 th International Conference on Energy Sustainable Energy Polices and Technologies October 2014 Chilled Ceilings / Beams Working Principles & Applications Francis W H Yik ATAL Building Services Engineering Ltd. 16 October

2 Contents Chilled Ceilings / Beams Working Principles & Application Introduction Operating principles Key advantages and concerns Application to buildings in Hong Kong Trial calculations Experience with pilot installations 2

3 Introduction 58% Overall Reduction in Energy Consumption Chilled ceilings or chilled beams are widely used in buildings designed for an energy use level below those of conventional buildings by 50% or more 3

4 Introduction Chilled ceiling / beam originated and are widely used in Europe 4

5 Introduction Chilled ceiling / beam are penetrating the US market 5

6 Introduction Chilled ceiling / beam projects in Beijing 6

7 Introduction Chilled ceiling / beam projects in Guangzhou PEARL RIVER TOWER 2.3 million sq ft 71 storeys, 310m 7

8 Introduction Chilled ceiling / beam projects in Hong Kong # Project Project Nature System installed Area (m 2 ) Year of Completion Owner/ User 1 HAECO CLK Building - Office Renovation Chilled Ceiling HAECO 2 Chinese University, meeting room Renovation Chilled Beam Chinese University 3 Wong & Ouyang BS Ltd. Office, Renovation Chilled Beam W&O BS Ltd. 4 Hang Seng Tower, 10 Floors Renovation Chilled Beam 10, Hang Seng Bank 5 Hang Seng Management College, Block D, 3/F 8/F (6 Floors) New Construction Chilled Ceiling 5, Hang Seng Management College 6 HSBC Data Centre at STTL 433, Shek Mun, Shatin, 7/F 10/F office New Construction Chilled Ceiling + Chilled Beam 9, HSBC 7 Hong Kong Science Park Phase 3, Conference Room New Construction Chilled Beam 80 in progress HK Science Park 8

9 Introduction What are the key concerns that hinder wider adoption of chilled ceilings / beams in buildings in Hong Kong? How can the perceived problems be resolved? 9

10 Operating principles Comfort air-conditioning Heat exchange of human body with the environment Heat transfer by radiation, R Heat transfer by convection, C 10

11 Operating principles Comfort air-conditioning Heat exchange of human body with the environment Conventional AC system Heat transfer by radiation, R SA Heat transfer by convection, C RA EA FA AHU Ch. W S&R 11

12 Operating principles Comfort air-conditioning Heat exchange of human body with the environment Conventional AC system Heat transfer by radiation, R SA Actively controlling the indoor air temperature, t a Heat transfer by convection, C No active control over the temperatures of surfaces enclosing the space RA EA FA AHU Ch. W S&R 12

13 Operating principles Comfort air-conditioning Heat exchange of human body with the environment Conventional AC system Heat transfer by radiation, R SA Actively controlling the indoor air temperature, t a Heat transfer by convection, C No active control over the temperatures of surfaces enclosing the space RA EA FA AHU t r = mean radiant temperature (a weighted mean value of temperatures of all surfaces to which the occupant is exposed) Ch. W S&R 13

14 Operating principles Comfort air-conditioning Heat exchange of human body with the environment Conventional AC system Heat transfer by radiation, R SA Actively controlling the indoor air temperature, t a Heat transfer by convection, C No active control over the temperatures of surfaces enclosing the space Operative temperature, t o, represents the combined RA EA effect of t a and t r AHU t r = mean radiant temperature (a weighted mean value of temperatures of all surfaces to which the occupant is exposed) FA t o hrtr = h r + + hct h c a Ch. W S&R 14

15 Operating principles Comfort air-conditioning Heat exchange of human body with the environment Conventional AC system Heat transfer by radiation, R SA Actively controlling the indoor air temperature, t a Heat transfer by convection, C No active control over the temperatures of surfaces enclosing the space Operative temperature, t o, represents the combined RA EA effect of t a and t r AHU t r = mean radiant temperature (a weighted mean value of temperatures of all surfaces to which the occupant is exposed) FA t o hrtr = h r + + hct h c a Ch. W S&R 15

16 Operating principles Comfort air-conditioning Heat exchange of human body with the environment Heat transfer by convection, C Heat transfer by radiation, R Lowering mean radiant temperature (t r ) allows indoor air temperature (t a ) to be raised without affecting operative temperature (t o ) and thus thermal comfort sensation of occupants SA RA Conventional AC system Actively controlling the indoor air temperature, t a No active control over the temperatures of surfaces enclosing the space Operative temperature, t o, represents the combined EA effect of t a and t r AHU t r = mean radiant temperature (a weighted mean value of temperatures of all surfaces to which the occupant is exposed) FA t o = hrt h r r + + hct h c a Ch. W S&R 16

17 Operating principles Comfort air-conditioning Heat exchange of human body with the environment Chilled ceiling panels Heat transfer by radiation, R PA Ch. W S&R Heat transfer by convection, C DOAS or PA system RA EA OA PAU Ch. W S&R DOAS = Dedicated Outdoor Air System PA = Primary Air 17 17

18 Operating principles Comfort air-conditioning Heat exchange of human body with the environment Chilled ceiling panels Heat transfer by radiation, R PA Ch. W S&R Sensible heat only Sensible heat only Heat transfer by convection, C DOAS or PA system Sensible and latent heat RA EA OA PAU Ch. W S&R DOAS = Dedicated Outdoor Air System PA = Primary Air 18 18

19 Operating principles Chilled ceiling 19

20 Operating principles Chilled ceiling Where the cooling requirement exceeds the capacity limit of chilled ceiling panels (~80W/m 2 ), chilled beams may be used instead 20

21 Operating principles Chilled beam 21

22 Operating principles Chilled beam The cooling capacity of passive chilled beams can be up to W/m 2 (Based on their exposed face area clearance spaces needed between chilled beams) 22

23 Operating principles Chilled beam Active chilled beam 23

24 Operating principles Chilled beam Active chilled beam The cooling capacity of active chilled beams can be up to W/m 2 (Based on their exposed face area even greater clearance spaces needed between chilled beams) 24

25 Operating principles Key characteristics of a chilled ceiling or chilled beam system: There must be two systems operating in parallel: Chilled ceiling panels or chilled beams Which extract (only) sensible heat from the spaces A primary air (PA) system or dedicated outdoor air system (DOAS) Which supply ventilation air as well as remove ALL moisture gains (latent cooling loads) and a fraction of the sensible heat gains of the spaces 25

26 Key advantages and concerns Key advantages Radiant cooling by using chilled ceiling Enhances thermal comfort and Allows use of slightly higher indoor dry-bulb temperature set point ASHRAE Handbook, HVAC Systems and Equipment, 2008, Chapter 6 Panel Heating and Cooling Principal advantages of panel systems are the following: Because not only indoor air temperature but also mean radiant temperature can be controlled, total human thermal comfort may be better satisfied. Comfort levels can be better than those of other space-conditioning systems because thermal loads are satisfied directly and air motion in the space corresponds to required ventilation only. 26

27 Key advantages and concerns Key advantages Separation of dehumidification (solely by PA system) from sensible cooling (by both PA system and chilled ceiling / beams) allows: Air flow rate (V PA < V SA ), and thus fan power and noise, to be reduced (although fan power saving also achievable in VAV systems) Use of higher temperature chilled water for the chilled ceilings / beams, which helps save chiller energy use (low temp. Ch.W. still needed for PA system unless desiccant dehumidification is used) 27

28 Key advantages and concerns Key advantages Reduced ceiling space required for installation Reduced maintenance cost When controlled properly, will not promote the formation of condensate which can lead to bacterial and mould growth Do not require drain pans which require cleaning Do not contain fans or filters to maintain and require only simple periodic service including vacuuming of the dry coil 28

29 Key advantages and concerns Must ensure: The PA supply flow rate (V PA ) is sufficient, and the difference in moisture content between the indoor air and the PA supply (w r w s ) is large enough for the PA to offset the total moisture gain (M r ) of the room s r M = ρ V r a PA( wr ws ) w r w s t s t r 29

30 Key advantages and concerns Must ensure: The surface temperatures of the chilled ceilings / beams must be above the dew point temperature of the indoor air (t dpr ) M = ρ V r a PA( wr ws ) t dpr s r w r w s t s t r 30

31 Key advantages and concerns Must ensure: The total sensible cooling capacity of the chilled ceilings / beams (Q SCC/B ) is sufficient to offset the remainder of the room sensible load (with the sensible cooling effect of the PA discounted) Q SR = Design room sensible cooling load Q SPA = Sensible cooling capacity of PA Where Q SPA = ρ V a PA Cp a ( tr ts ) Required sensible cooling capacity of chilled ceilings / beams Q SCC/B >= Q SR Q SPA 31

32 Key advantages and concerns Key concerns Stagnant air flow and cold air dumping onto occupants Condensation risk Limited cooling capacity of chilled ceiling / beam modules Impact on whether CC/B can be used 32

33 Key advantages and concerns Key concerns Stagnant air flow and cold air dumping onto occupants Condensation risk Can be overcome by careful building and system design and operation Maintain at least 1m clear headroom between passive chilled beam and occupied zone (1.7m from finished floor level) Limited cooling capacity of chilled ceiling / beam modules Use active chilled beam Adequate selection and layout of chilled beams and/or diffusers for PA Raise PA supply flow rate if absolutely needed 33

34 Key advantages and concerns Key concerns Stagnant air flow and cold air dumping onto occupants Can be overcome by careful building and system design and operation Minimize moisture gains of spaces Condensation risk Limited cooling capacity of chilled ceiling / beam modules Ensure PA system has sufficient dehumidification capacity; if needed, use heat pipes or desiccant dehumidification Use an appropriate Ch.W supply temperature setting Monitor and control ceiling / beam surface temperature 34

35 Key advantages and concerns Key concerns Stagnant air flow and cold air dumping onto occupants Can be overcome by careful building and system design and operation Minimize envelope heat gains Condensation risk Limited cooling capacity of chilled ceiling / beam modules Use energy efficient lighting Use energy efficient appliances Use active chilled beams 35

36 Application to buildings in Hong Kong Trial calculations reference conditions (office building in HK) Design conditions Unit Value Design conditions Unit Value Design OA temperature, To oc 33.3 Design OA RH, RHo % 66 Design OA moisture content, wo kg/kg Design OA enthalpy, ho kj/kg Design RA temperature, Tr oc 25 Design RA RH, RHr % 55 Design RA dew point, Tdpr oc 15.4 Design RA moisture content, wr kg/kg Design RA enthalpy, hr kj/kg Room floor area (Interior Zone) m Room height m 3.2 Room volume m Lighting and app. power density W/m2 35 Lighting and appliances heat gain, Qsi kw Occupancy rate m2/p 9 No. of Occupants No Sensible heat gain per person W/p 75 Rad. Sen. heat gain from occupant % 60 Latent heat gain per person W/p 55 Moisture gain per person g/s-p Sensible load from occupants, Qsp kw Latent heat gain from occupants, Qlp kw Moisture gain from occupants, Mp kg/s FA requirement l/s-p 10 FA flow rate, Vfa m3/s Infiltration ACH ACH 0.1 Infiltration flow rate, Vinf m3/s Sensible load from infiltration, Qsinf kw Latent load from infiltration, Qlinf kw Moisture gain from infiltration, Minf kg/s

37 Application to buildings in Hong Kong Trial calculations cooling load intensity Design cooling load predictions for Model Office Building by BEEP Floor Space DSL DLL DTL Area DSL DLL DTL kw kw kw m2 W/m2 W/m2 W/m2 Typical North Typical West Typical East Typical South Typical Interior Typical SimTot

38 Application to buildings in Hong Kong Trial calculations cooling load intensity Design cooling load predictions for Model Office Building by BEEP Floor Space DSL DLL DTL Area DSL DLL DTL kw kw kw m2 W/m2 W/m2 W/m2 Typical North Typical West Typical East Typical South Typical Interior Typical SimTot Shared between chilled ceilings / beams and PA system By PA system 38

39 Application to buildings in Hong Kong Trial calculations PA flow rate PA Supply Flow Rate m3/s FA Flow Rate 25oC / 55% RH (tdpr 15.40oC) 24oC / 55% RH (tdpr 14.41oC) 25oC / 50% RH (tdpr 13.87oC) 24oC / 50% RH (tdpr 12.95oC) PA Supply Dew Point Temperature oc Indoor design temperature, relative humidity and dew point temperature 39

40 Application to buildings in Hong Kong Trial calculations PA flow rate PA Supply Flow Rate m3/s The higher the t dpr, the smaller the V pa The required PA supply flow rate (V pa ) is highly sensitive to the choices of the indoor air state (t dpr ) and the PA supply air state (t dps ) FA Flow Rate 25oC / 55% RH (tdpr 15.40oC) 24oC / 55% RH (tdpr 14.41oC) 25oC / 50% RH (tdpr 13.87oC) 24oC / 50% RH (tdpr 12.95oC) The lower the t dps, the smaller the V pa PA Supply Dew Point Temperature oc Indoor design temperature, relative humidity and dew point temperature 40

41 Application to buildings in Hong Kong Trial calculations PA flow rate 3 PA Supply Flow Rate m3/s Selected condition: Sensible cooling provided by PA = 18.13W/m 2 FA Flow Rate 25oC / 55% RH (tdpr 15.40oC) 24oC / 55% RH (tdpr 14.41oC) 25oC / 50% RH (tdpr 13.87oC) 24oC / 50% RH (tdpr 12.95oC) PA Supply Dew Point Temperature oc Indoor design temperature, relative humidity and dew point temperature 41

42 Application to buildings in Hong Kong Trial calculations Required chilled ceiling / beam cap. Floor Space DSL PA S Cap CC/B Cap W/m2 W/m2 W/m2 Typical North Typical West Typical East Typical South Typical Interior Chilled beams need to be used for the perimeter zones but chilled ceilings may be used for the interior zone 42

43 Application to buildings in Hong Kong Key design considerations Minimize sensible cooling load through Reducing external heat gains by improving thermal performance of building envelope Reducing internal heat gains by using energy efficient lighting and appliances Minimize latent cooling load through reducing ingress of humid air into airconditioned space by Improving air-tightness of building envelope Positive pressurization of air-conditioned space Use of anteroom (lobby with double-door) if needed 43

44 Application to buildings in Hong Kong Key design considerations Adequate selection of design indoor air state (an increase in RH by 5% can make a big difference) Adequate selection of design PA supply air state (the lower the moisture content in it the smaller the required PA supply flow rate), subject to the constraints of Temperature of chilled water supply to PAU (may use desiccant dehumidification) Minimum FA supply flow rate for air-conditioned spaces Adequate selection of temperature of chilled water supply to chilled ceilings / beams (at or slightly above dew point temperature of indoor air) 44

45 Experience with pilot installations Hui & Leung (2012) Study on chilled ceiling application in Hong Kong Simulation results: ~20% energy saving achievable Field study offices of an aircraft engineering company: Chilled ceiling in use since mid % of the occupants satisfied with thermal sensation, though 40% felt temperature sometimes too hot 51% felt air movement too low Findings similar for another field study (construction site office) 45

46 Experience with pilot installations 46

47 Experience with pilot installations 47

48 Experience with pilot installations 48

49 Experience with pilot installations 49

50 End of Presentation Thank you 50

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed

More information

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

NOVEMBER 2012 THE EUROPEAN EXPERIENCE Radiant-cooling systems have progressed in the last few decades, garnering attention as a comfortable and energy- and material-efficient option. 1 Compared with air radiant-cooling hydronic systems use

More information

7. MECHANICAL SYSTEM DESIGN

7. MECHANICAL SYSTEM DESIGN 7. MECHANICAL SYSTEM DESIGN The second primary topic of this thesis is to investigate the application of a dedicated outdoor air system (DOAS) to the SLCC. The stated goals for this thesis of improved

More information

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled

More information

Chilled Beams. Getting a Warmer Reception

Chilled Beams. Getting a Warmer Reception Chilled Beams Getting a Warmer Reception Gain an understanding of how chilled-beam technology works, the difference between active/passive chilled beams and potential applications for its use. B y G r

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

The new ASHRAE-REHVA Active and Passive Beam Application Design Guide

The new ASHRAE-REHVA Active and Passive Beam Application Design Guide Swegon Air Academy Seminar. Tallinn. 2015 December 3 The new ASHRAE-REHVA Active and Passive Beam Application Design Guide Carlos Lisboa carlos.lisboa@blcnavitas.pt Office +351 214 415 546 Cell +351 919

More information

Integrated Building Environmental Design Case Study: Beijing Parkview Green

Integrated Building Environmental Design Case Study: Beijing Parkview Green Integrated Building Environmental Design Case Study: Beijing Parkview Green The 7th International Energy Agency Annex 44 Forum 24 October 2007 Dr Raymond Yau Director Ove Arup & Partners Hong Kong Ltd.

More information

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle Chilled Beam and Radiant Cooling Basics Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle nsearle@dadanco.com Contents Radiant Ceilings & Chilled Beam Basics Energy & Space Savings First and

More information

Integrated Building Environmental Design. Beijing Parkview Green. 10 May 2008

Integrated Building Environmental Design. Beijing Parkview Green. 10 May 2008 Integrated Building Environmental Design Beijing Parkview Green 10 May 2008 Developer : Beijing Chyau Fwu Properties Co., Ltd. Architect : Integrated Design Associates Engineering Consultant : Ove Arup

More information

High Performance Buildings and Occupant comfort

High Performance Buildings and Occupant comfort Nicolaus Copernicus High Performance Buildings and Occupant comfort The Earth moves, in two ways. It rotates on an axis (period = 1 day). It revolves around the sun (period = 1 year). Peter Simmonds, Ph.D.,

More information

KLIMA Active Chilled Beams

KLIMA Active Chilled Beams KLIMA 2 600 Active Chilled Beams Index Subject Page Index 1 Introduction 2 General description 3-4 Product features 5-6 Dimensions 7 Performance data 8-11 Section example Guide specifications 13 1 Introduction

More information

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

White Paper Dehumidification in Humid Climates - A Theoretical Case Study White Paper Dehumidification in Humid Climates - A Theoretical Case Study This white paper provides details of a theoretical comparison of operating costs associated with mechanical dehumidification systems

More information

Modular Active. Chilled. Beams

Modular Active. Chilled. Beams Modular Active Chilled Beams How Twa MAC Beams Work Primary air (100% outside air) is dehumidified to between 50-57 F dew point and is used to: control the latent requirements of the space, provide fresh

More information

Heat pump and energy recovery systems

Heat pump and energy recovery systems SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air

More information

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active. TRACE 700 incorporates two chilled beam strategies: passive and active. Passive chilled beams consist of a fin-and-tube cooling coil, contained in a housing (or casing), suspended from the ceiling. Chilled

More information

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems CBE Timothy Moore CENTER FOR THE BUILT ENVIRONMENT SimBuild

More information

Munters Heat Exchangers

Munters Heat Exchangers Munters Heat Exchangers Brad Perdew Applications Engineer 8/27/12 DOAS Configurations Cheryl Hughes Regional Sales Manager October 11, 2016 cheryl.hughes@munters.com Munters DOAS Configurations Presentation

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Space Air Diffusion II

Space Air Diffusion II MEBS6008 Environmental Services II http://me.hku.hk/bse/mebs6008/ Space Air Diffusion II Ir. Dr. Sam C. M. Hui Visiting Assistant Professor Department of Mechanical Engineering The University of Hong Kong

More information

Designing Energy Efficient Outdoor Air Systems

Designing Energy Efficient Outdoor Air Systems Designing Energy Efficient Outdoor Air Systems Joseph Thorndal Applied Products Sales Manager Greenheck, Schofield, Wisconsin 1 Joseph Thorndal BS Industrial Engineering North Dakota State University Work

More information

Active Chilled Beams. Technical Data Concealed Ceiling Mounted Model With Vertical Coil and Integral Drain Pan

Active Chilled Beams. Technical Data Concealed Ceiling Mounted Model With Vertical Coil and Integral Drain Pan ACB35 Concealed Ceiling-Mounted With Vertical and Integral Drain Pan (Vertical down discharge) Technical Data Concealed Ceiling Mounted Model With Vertical and Integral Drain Pan Active Chilled Beams APPLICATION

More information

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to

More information

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory Overview of Chilled Beam Technology Purpose Chilled beam technology is new to the United States but has been used in Europe since the 1950 s. Chilled beams can reduce energy costs, improve indoor air quality,

More information

A study of radiant cooling for a room with daytime application in tropical climate

A study of radiant cooling for a room with daytime application in tropical climate International Journal of Smart Grid and Clean Energy A study of radiant cooling for a room with daytime application in tropical climate Satinee Wongkee, Surapong Chirarattananon, Pipat Chaiwiwatworakul

More information

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN Introduction to HVAC Agenda Psychrometrics Human Comfort Heat Transfer Refrigeration Cycle HVAC Terminology HVAC Systems Introduction to HVAC Psychrometrics 2000 TRG-TRC002-EN Properties of Air Dry-bulb

More information

Comfort and health-indoor air quality

Comfort and health-indoor air quality Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental

More information

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001 This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.

More information

Building Systems: HVAC

Building Systems: HVAC Building Systems: HVAC Committee on Microbiomes of the Built Environment June 21, 2016 Washington DC Dennis Stanke (dstanke47@gmail.com) Retired rane (IR) Outline Ventilation Systems Moisture sources Low

More information

Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation

Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation Author:John Vavrin, PE Presenter: Dale Herron US Army Corps of Engineers Engineer Research

More information

Innovative and energy efficient humidity control. Peter Lau Application Manager Ingersoll Rand

Innovative and energy efficient humidity control. Peter Lau Application Manager Ingersoll Rand Innovative and energy efficient humidity control Peter Lau Application Manager Ingersoll Rand CDQ (Cool Dry Quiet) : Dehumidification Innovative and energy efficient humidity control 2 CDQ (Cool Dry Quiet)

More information

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1 Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9

More information

SECTION H. Engineering Guide Radiant Products. Please refer to the Price Engineer s HVAC Handbook for more information on Radiant Heating and Cooling

SECTION H. Engineering Guide Radiant Products. Please refer to the Price Engineer s HVAC Handbook for more information on Radiant Heating and Cooling SECTION H Radiant Products Please refer to the Price Engineer s HVAC Handbook for more information on Radiant Heating and Cooling Introduction To Radiant Heating and Cooling Radiant heating and cooling

More information

BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT

BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT Ashak Nathwani AM Adjunct Senior Lecturer ashak.nathwani@sydney.edu.au PRESENTATION THREE SESSIONS This presentation will be in three parts addressing

More information

nzeb office building

nzeb office building nzeb office building Ympäristötalo in Helsinki, Finland City of Helsinki has taken the exemplary role of the public sector seriously. The latest proof is the Environment Centre building Ympäristötalo completed

More information

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System 4 th International Conference On Building Energy Environment Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System J Y Park H W

More information

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong

More information

HVAC 101. H V A C S y s t e m s

HVAC 101. H V A C S y s t e m s H V A C 1 0 1 S y s t e m s Introduction & Overview Should you care? Mechanical System Types Components & operation Popular Application Key Issues and Design Considerations System Comparisons First Cost

More information

Optimizing the use of Chilled Beams for health and comfort GUNNAR SVENSSON

Optimizing the use of Chilled Beams for health and comfort GUNNAR SVENSSON Optimizing the use of Chilled Beams for health and comfort GUNNAR SVENSSON Lighting Sound Level Air Quality Cleaning Temperature Layout Maintenence Furniture Security How can we reduce the energy consumption?

More information

Chilled Ceiling Condensation Control Experience In A Movable Sash Building

Chilled Ceiling Condensation Control Experience In A Movable Sash Building Chilled Ceiling Condensation Control Experience In A Movable Sash Building Introduction: A dedicated outdoor air system (DOAS) with a parallel sensible cooling chilled ceiling, or ceiling radiant cooling

More information

AHU Air Handling Unit Fundamentals. j.ilangumaran

AHU Air Handling Unit Fundamentals. j.ilangumaran AHU Air Handling Unit Fundamentals j.ilangumaran Objectives Review primary components of an AHU Understand the basic progression and advantages of advanced AHU control Understand the basic control sequences

More information

Relative Humidity in Schools Jim Cummings and Chuck Withers

Relative Humidity in Schools Jim Cummings and Chuck Withers to Co n tr o l Relative Humidity in Schools Jim Cummings and Chuck Withers SEEC Southern Energy-Efficiency Center Energy Efficient Strategies to Control Relative Humidity in Schools James Cummings and

More information

EarthWise System Seminar

EarthWise System Seminar EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States

More information

APPLICATION GUIDE BEAMS

APPLICATION GUIDE BEAMS BEAMS There is an increasing need for energy efficient air conditioning systems as energy codes become more stringent. Chilled beam systems are one such alternate to traditional all air conditioning systems.

More information

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang

More information

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions IDL20e (2 way discharge) IDS60e ( way discharge) Frequently Asked Questions UDI (vertical discharge) Inffusers INFFUSER FREQUENTLY ASKED QUESTIONS The following are frequently asked questions (FAQ s) on

More information

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 john.woollett@swegon.se, jonas.akesson@swegon.se SUMMARY The main focus of the paper will be on active beam technology regarding

More information

Dehumidifying with Dedicated Outdoor Air

Dehumidifying with Dedicated Outdoor Air Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,

More information

C o o l i n g a n d h e a t i n g s y s t e m s

C o o l i n g a n d h e a t i n g s y s t e m s 2 C o o l i n g a n d h e a t i n g s y s t e m s Cooling ceiling system description Preliminary remarks Cooling ceilings Cooling ceilings are room cooling systems for placement in the ceiling zone. Their

More information

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi PhEn-602 Pharmaceutical Facility Design Notes #7 J. Manfredi 1 HVAC Design and the Psychrometric Chart 2 HVAC Considerations Pharmaceutical Facility Design Process 1. SPACE REQUIREMENTS Temperature Humidity

More information

HVAC DISTRIBUTION and DELIVERY SYSTEMS

HVAC DISTRIBUTION and DELIVERY SYSTEMS HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 1) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 REMINDER HVAC = Heating, Ventilating, Air-Conditioning The AC part of HVAC implies a system that

More information

Next Generation Passivhaus Archives

Next Generation Passivhaus Archives Next Generation Passivhaus Archives Alan Clarke, Gloucestershire, UK, alan@arclarke.co.uk Nick Grant, Herefordshire, UK, nick@elementalsolutions.co.uk Andy Jarvis E3, Bath, UK, andy.jarvis@e3ce.com 1 Introduction

More information

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Heat Transfer Basics Human Body Heat Exchange Radiant Cooling Basics Radiant Cooling Suitability? Radiant

More information

Appendices. Included in this section are

Appendices. Included in this section are Appendices Included in this section are Appendix A Building Overview Appendix B Alternative Mechanical Designs Appendix C Integration of Structural System and Constructability 68 Appendix A Building Overview

More information

K.F. Fong *, C.K. Lee, T.T. Chow

K.F. Fong *, C.K. Lee, T.T. Chow Investigation on radiative load ratio of chilled beams on performances of solar hybrid adsorption refrigeration system for radiant cooling in subtropical city K.F. Fong *, C.K. Lee, T.T. Chow Building

More information

Radiant Heating & Cooling for Commercial Buildings

Radiant Heating & Cooling for Commercial Buildings Radiant Heating & Cooling for Commercial Buildings Kaveesh Padiachy, PEng, PMP, LEED AP Business Development Manager Central Canada kaveesh.padiachy@uponor.com www.uponorpro.com/engineering Radiant Heating

More information

Efficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden

Efficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden Efficient energy recovery in AHU DOHA, Qatar 11.04.2010 Timo Schreck Enventus AB, Sweden Main principles for cooling and dehumidification process in AHU 1. With cooling coil and reheater 2. Energy recovery

More information

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,*

More information

Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV)

Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV) Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV) 1 Contents Why Heat Recovery Ventilator(HRV) is required Type of Heat Recovery Ventilator Feature of MITSUBISHI ELECTRIC Lossnay

More information

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING Mehmet Kanoglu Copyright The McGraw-Hill Companies,

More information

Select DOAS, Ceiling Radiant Cooling Panel- Chilled Beam Projects. Updated 9/23/2008

Select DOAS, Ceiling Radiant Cooling Panel- Chilled Beam Projects. Updated 9/23/2008 1 Select DOAS, Ceiling Radiant Cooling Panel- Chilled Beam Projects. Updated 9/23/2008 Classroom Building-1, PA Classroom Building-2, PA Classroom Building-2, PA DOAS-Chilled Ceiling Classroom Building-3,

More information

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully

More information

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386 Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386 Xiaojie LIN 1, Yunho HWANG 1, Reinhard RADERMACHER 1, Saikee OH 2 1 Center for Environmental

More information

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President Humidity Control Design Tips R. Mark Nunnelly, PE, CxA, LEED AP President AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects

More information

SIMULATING A HEAT AND MOISTURE TRANSFER PANEL (HAMP) FOR MAINTAINING SPACE HUMIDITY

SIMULATING A HEAT AND MOISTURE TRANSFER PANEL (HAMP) FOR MAINTAINING SPACE HUMIDITY SIMULATING A HEAT AND MOISTURE TRANSFER PANEL (HAMP) FOR MAINTAINING SPACE HUMIDITY A Thesis Submitted to the College of Graduate Studies and Research in Partial Fulfillment of the Requirements for the

More information

Section 4 of 6 DOAS Core Technologies

Section 4 of 6 DOAS Core Technologies Section 4 of 6 DOAS Core Technologies Desiccant dehumidification Air-to-air energy recovery Evaporative cooling 1 Desiccant dehumidification Industrial Desiccant Dehumidifier Hybrid DX + Desiccant Dehumidifier

More information

Thermodynamics II Chapter 6 Mixtures & Psychrometry

Thermodynamics II Chapter 6 Mixtures & Psychrometry Thermodynamics II Chapter 6 Mixtures & Psychrometry Mohsin Mohd Sies Fakulti Kejuruteraan Mekanikal, Universiti Teknologi Malaysia Objectives Differentiate between dry air and atmospheric air. Define and

More information

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 2) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Contextual Reminder All-air systems Single zone Terminal reheat Multi-zone Dual-duct VAV Combinations

More information

HVAC: The Next. Variable-air-volume systems. Outside-the-box thinking suggests the integration of dedicated

HVAC: The Next. Variable-air-volume systems. Outside-the-box thinking suggests the integration of dedicated cse0301doas.qxd 1/31/2003 9:09 AM Page 38 HVAC: The Next Outside-the-box thinking suggests the integration of dedicated By STANLEY A. MUMMA, Ph.D., P.E., ASHRAE Fellow Professor of Architectural Engineering

More information

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning HVAC 101 The Basics of Heating, Ventilation and Air Conditioning HVAC Heating, Ventilation and Air Conditioning Provides comfort for people Allows humans to exist under adverse conditions. Comfort Comfort

More information

DADANCO Technical Paper

DADANCO Technical Paper DADANCO Technical Paper 260 North Elm Street Westfield, MA 01085 Phone: (413) 564-5657 Fax: (413) 568-2969 March 2013 CLASSROOM SOLUTION USING ACTIVE CHILLED BEAMS (Note: This technical paper assumes the

More information

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2 1 Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program Abhijeet Pande Heschong Mahone Group, Inc. Kristin Heinemeier Western Cooling Efficiency

More information

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface Journal of Mechanical Science and Technology 23 (2009) 528~535 Journal of Mechanical Science and Technology www.springerlink.com/content/738-494x DOI 0.007/s2206-009-0426-0 A study on performance improvement

More information

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.

More information

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes In Humid Climates BY DAVID A. JOHN, P.E., MEMBER ASHRAE; DREW ELSBERRY, MEMBER ASHRAE Designing g a building s HVAC system requires designers

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

The School District of Philadelphia Administration Headquarters Shell and Core Renovations 440 North Broad Street Philadelphia, PA

The School District of Philadelphia Administration Headquarters Shell and Core Renovations 440 North Broad Street Philadelphia, PA 2.0 Depth Work - Alternative Mechanical Designs 2.1 Objectives The goal of designing alternative systems is to compare energy usage, system costs, emissions, lost rentable space, and constructability.

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

Summary Comparison of Simulation Program Features

Summary Comparison of Simulation Program Features Summary Comparison of Simulation Program Features FEATURE DOE2.2 equest TRACE 700 HAP Public/Proprietary Public Domain Proprietary Proprietary Proprietary Simulation Method 8760 hours 8760 hours 8760 hours

More information

High-Performance VAV Systems

High-Performance VAV Systems This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

Implementation of the Laboratory Air Handling Unit Systems (LAHU)

Implementation of the Laboratory Air Handling Unit Systems (LAHU) University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Architectural Engineering -- Faculty Publications Architectural Engineering 2003 Implementation of the Laboratory Air Handling

More information

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Temperature. In the HVAC area, we talk about two kinds of temperatures. HEATING and COOLING HEATING and COOLING PSYCHROMETRIC CHART Temperature In the HVAC area, we talk about two kinds of temperatures. One is called dry bulb (DB) temperature, a fancy name for the reading

More information

Trane CDQ Desiccant Dehumidification

Trane CDQ Desiccant Dehumidification Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features

More information

AR/IA/UP 241 Lecture 5: Psychrometrics

AR/IA/UP 241 Lecture 5: Psychrometrics Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is

More information

Mold/Moisture Control Case Study

Mold/Moisture Control Case Study Mold/Moisture Control Case Study Presented by Boggarm S. Setty, P.E., FASHRAE Setty & Associates, Ltd. www.clima2005.ch Clima 2005 Lausanne Solothurnstrasse 13 CH-3322 Schönbühl Switzerland th 8 REHVA

More information

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

Air Conditioning for and-humid Climates:

Air Conditioning for and-humid Climates: Air Conditioning for Hot-and and-humid Climates: Commercial Technologies ACEEE Market Transformation Conference Emerging Technologies March 21, 2007 Hugh I Henderson, Jr., P.E. CDH Energy Corp. Cazenovia,

More information

Raised Access Floor - (AE Breadth Area)

Raised Access Floor - (AE Breadth Area) Raised Access Floor - (AE Breadth Area) Currently, the Plaza has a raised access flooring system on both the 7 th and 8 th floors. The 8 th floor is designed with an independent HVAC system utilizing an

More information

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

EADQUARTERS. Technical Report One. Stephanie Kunkel   Mechanical Option EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option

More information

lindab ventilation Lindab Comfort Waterborne indoor climate solutions Product overview

lindab ventilation Lindab Comfort Waterborne indoor climate solutions Product overview lindab ventilation Lindab Comfort Product overview Products within the Lindab Waterborne solutions, e.g. chilled beams, facade systems, radiant heating and cooling panels, uses water to regulate the room

More information

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget VanceFox.com 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal Vol. 49, Jan. 2006. For personal use only. Additional reproduction,

More information

Executive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed

Executive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed Observations, ref ASHRAE May 2013 Journal article Vol. 55, NO 5, pg. 18 VAV Reheat vs. Active Chilled Beams & DOAS. Also published at: http://escholarship.org/uc/item/1jh193x3 Prepared by: S. A. Mumma,

More information

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,

More information

ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES

ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES INTRODUCTION ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES Tom Brooke MBA, PE, CEM May 25, 212 On April 19, 212, ASHRAE conducted a webcast to publicize the concept of Dedicated

More information

IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE

IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE Cooling System RADIANT COOLING PIPING LAYOUT Proposal for the REHAU core temperature control (CCTC) pipe size: RAUTHERM S 20x2,0mm

More information

Pharmaceutical Facility Design

Pharmaceutical Facility Design PhEn-602 Pharmaceutical Facility Design J. Manfredi Notes 9A PhEn-602 J. Manfredi 1 Primary & Secondary HVAC units Primary Primary air handling unit arrangement: One unit is responsible for all of the

More information

Active & Passive Beams

Active & Passive Beams Active & Passive Beams www.price-hvac.com Active & Passive Beams Introduction Beam systems are an alternative to traditional all-air conditioning systems. Beams use water to move energy through a building

More information