Daikin Altherma/Viessmann Integration Notes (used with schematics M1 thru M5)

Size: px
Start display at page:

Download "Daikin Altherma/Viessmann Integration Notes (used with schematics M1 thru M5)"

Transcription

1 March 15, 2011 Daikin Altherma/Viessmann Integration Notes (used with schematics M1 thru M5) Our Daikin Altherma project involves integrating an indoor unit (EKHBX054BA3VJU) with an existing domestic hot water, high temperature radiant panel, and low temperature radiant floor heating system. The existing system is built around a Viessmann Vitola 200 propane fired boiler, a Vitotronic 200 control system, a Divicon mixing station, and a Vitocell 300 domestic hot water tank. The Divicon serves 6 radiant zones; each zone has a thermostat that controls its respective circulator through a Taco circulator control. There is one zone of high temperature radiant wall panels served by a high temperature circulator. Both high temp and mixed temp boiler circuits utilize heating curves reset using outside temperature. The Vitocell 300 tank is served by a domestic hot water circulator. This existing system is approximately 6 years old and represents what once was the state of the art in hydronic heating. Overall system efficiency is on the order of 80 to 90%. Until recently, there was no realistic or cost effective way to significantly reduce system operating costs or improve upon this level of energy efficiency. We see the arrival of the Altherma in the United States as a tremendous opportunity to rectify this situation. Our perception is that owners of Viessmann hydronic systems are typically willing to invest in an efficient heating system and are very interested in energy efficiency and are therefore ideal candidates for an Altherma retrofit project. The purpose of the notes that follow is to outline our approach to the integration of the Altherma with the Viessmann system what the pre-existing system looks like, different approaches to integrating the two heat sources, and determining the optimum use of the Altherma s capabilities. Pre-existing Viessmann System: Schematic M1 (left illustration) The existing boiler has a domestic hot water (dhw) circuit, a high temperature circuit, and a mixed temperature circuit. The domestic hot water circuit uses the factory default schedule that enables operation from 5:30 AM to 10:30 PM every day. Whenever dhw tank temp falls below the dhw setpoint (currently 130F) the boiler temp rises to 180 F and the dhw circulator operates. The high temp circuit is a single zone of radiant wall panels served by a high temp circuit circulator controlled by a Taco switching relay and zone thermostat. The high temp circuit

2 operates on the factory default schedule that enables boiler operation from 6 AM to 10 PM every day. Based on an outside reset curve with a high temp of 180 F at 0 F outside, the boiler maintains the appropriate reset temp at all times of enabled operation. As this high temp circuit is used infrequently, there are quite a few hours of unnecessary propane consumption to maintain boiler standby temperature. The mixed temp circuit has constant circulation provided by the built in circulator in the Divicon mixing station. Connected to this mix temp circuit are six radiant zone circulators controlled by a Taco circulator control from zone thermostats. The returns from the six zones (some in concrete floors and some in wood floors) feed back into the mix temp circuit right after the last radiant zone supply. Use of large diameter tubing in the mix temp circuit (resulting in negligible pressure drop) and the pressure gradient from the Divicon mixing circulator help to ensure that system pressures are fairly uniform and that the zone and mixing circulators work well with each other. Based on an outside reset curve with a mix temp of 120 F at 0 F outside, the boiler maintains the appropriate reset temp at all times of enabled operation. As the high temp circuit reset curve is always hotter than necessary for the radiant zones, the Divicon mixing station is constantly mixing radiant loop return water with boiler supply to reduce the radiant supply temperature. Altherma Integration With Viessmann: Schematic M1: (right illustrations) Parallel versus Series: We feel that installing the Altherma in series with the Viessmann presents several advantages over alternating or parallel installations. Installation instructions for the Altherma indicate in Application 5 the use of either a boiler or the hydrobox as a source for a hydronic system. If return temperatures of the system can be held below 120 F, we feel that there are several advantages to operating the two sources in series and simultaneously: Maximize Heat Output from Altherma with the Coldest Return Water: If the Altherma hydrobox and Viessmann boiler are in series then we can ensure that the coldest return water will go to Altherma first resulting in the greatest opportunity to extract heat from the hydrobox (if return temperature is too high, the hydrobox will reach a point where it can no longer heat the hydronic flow through the heat exchanger). Maximize Heat Output from Altherma as First Stage: Given a fixed hydronic input temp, the hydrobox output temp will rise and fall with the capacity of the heat pump as a function of outside temperature. As the hydrobox output temp drops the Viessmann Divicon mixing station will add hot water to bring the supply temp up to the reset setpoint. Having the hydrobox first in a series arrangement will automatically ensure that the Altherma will always have the opportunity to add as much heat as possible to the hydronic flow.

3 Increased Heat Pump Annual Run Time: If the hydrobox and boiler are installed in parallel, we feel that the instantaneous burner/divicon mixing station output of the boiler would be much greater than the output of the hydrobox. Mix temp circuit target temperature would be achieved quickly and the overall runtime of the heat pump would be reduced. A series installation may reduce instantaneous heat input to the mix temp circuit but will increase Altherma run time as stage 1 to almost 100% or continuous operation during the coldest parts of the heating seaon. Our perception is that operation of the Altherma is more economical than operation of the Viessmann boiler as the Altherma annual operating hours increase, the annual operating cost of the entire system will decrease. Altherma/Viessmann Integration: (Schematic M1 inset, upper right illustration and Schematic M2) The return flow from the mixed temp circuit goes to a 40 gallon buffer tank (necessary to ensure adequate hydronic system volume) and into the inlet of the hydrobox. The Daikin motorized 3 way valve directs hydrobox output to either the Daikin domestic hot water tank or the heating system. (Application 3) The heating output from the Daikin 3 way valve goes to a motorized 3 way valve (labeled RadMV1) that directs flow either directly to the radiant system or through the Viessmann Divicon mixing station. In the Altherma only heating mode, hydronic flow bypasses the Divicon mixing station and circulates through the mixed temp circuit. Operation of the Altherma is controlled by the normally open end switch of the Taco circulator control (as room thermostat ) that operates the radiant zone circulators. Target temperature for the hydronic flow is determined by the reset curve calculated by the Altherma user interface. In the Altherma Viessmann series heating mode, motorized valve RadMV1 connects the Altherma hydrobox output to the Viessmann Divicon mixing station inlet and the Divicon circulator starts. (Though the motorized valve has a 90 second actuator we feel that the addition of the Viessmann circulator to the Altherma circulator will ensure that flow will be sufficient for the hydrobox throughout the valve travel). The Divicon mixing station will add boiler hot water as necessary to the Altherma input to raise the supply temperature to the mix temp circuit reset setpoint. Due to the ample size of the mix temp circuit the additional flow from both hydrobox and Divicon circulators operating in series (with additive pump head) should not create interaction problems with the existing radiant zone circulators. Both hydrobox and Divicon circulators will be on together during the periods of highest building heat loss when more radiant zone circulators will be operating. During periods of lower building heat loss, only the hydrobox circulator will be operating.

4 Buffer Tank Connection Choices: (Schematic M1, right illustrations) There are several ways to connect the heat sources (Altherma hydrobox and Viessmann boiler) to the mix temp circuit that serves the radiant zones. A buffer tank is used to ensure that the hydronic system volume is adequate for hydrobox operation. A buffer tank can also be used to isolate system circulators and reduce undesired flow issues by creating a region of common pressure. This approach requires a somewhat different control strategy with consequent benefits and drawbacks. Buffer tank in series: (Schematic M1 inset, upper right illustration and Schematic M2): In this approach, the buffer tank is in series with the Altherma and Viessmann circulators. The radiant zone thermostats activate the zone circulators via a Taco circulator control. The normally open end switch of the Taco control calls the Altherma directly (as a room thermostat ) and the user interface activates the Altherma hydrobox circulator. This hydrobox circulator runs in addition to any radiant zone circulator anytime there is a radiant call. This will somewhat increase annual hydrobox circulator run time but the ability of the Altherma to modulate hydronic output saves energy (compared to a typical on/off American heat pump). Temperature control is also improved as there is very little system lag between the radiant zone call and heat pump operation. When temperature outside drops below Radiant Stat setting and the Taco end switch is calling, the Viessmann is brought in as the second stage. This arrangement runs the Viessmann Divicon mixing circulator in series with the Altherma hydrobox circulator. As the Divicon mixing station is fully modulating and fairly fast acting, temperature control is not affected and there is little system lag introduced by starting the second stage. Due to the ample size of the mix temp circuit piping the operation of the radiant zone circulators should not be affected by the operation of the Altherma and Viessmann circulators. Buffer tank hydraulically separating: (Schematic M1 inset, lower right illustration) In this approach, the buffer tank serves as a hydraulic isolator between the radiant zone circulators and the Altherma and Viessmann circulators. The supply and return sides of the radiant zones are separated (note the connection is removed in the illustration). This arrangement would permit the operation of the radiant zone circulators independently of the Altherma and Viessmann circulators. We use this connection approach with non-modulating heat sources (typical American on/off heat pumps) that have one heat output level. A buffer tank decouples the heat output level of the heat pump from the heat input level going to a radiant zone and reduces short cycling of the heat source. It can also reduce annual circulator energy use by permitting radiant zone circulators to remove heat from the buffer tank without always running the heat source circulator.

5 The buffer tank temperature would drive operation of the Altherma and Viessmann sources. One possibility would be to use a Tekmar 264 staging control to look at buffer tank temp the 264 would take the radiant zone Taco end switch input and operate the Altherma as a first stage and the Viessmann as a second stage. It would use the radiant supply manifold input temp as a control input. Typically, a buffer tank installed this way permits multiple circulators of different sizes to peacefully coexist and lets non-modulating heat sources cycle more efficiently independent of small heating loads. This approach usually experiences an increased lag in system response (buffer tank and radiant zone temperatures vary to a greater degree) and increased cost of system controls when compared to a modulating system (as with the buffer tank in series as depicted in the upper illustration). Domestic Hot Water System: (Schematic M2: (upper inset)) A Daikin domestic hot water tank is connected to the Altherma hydrobox via the Daikin 3 way motorized valve. An existing Viessmann domestic hot water tank is connected to the boiler via a dedicated dhw circulator. A DHW Stat is used to select a changeover point between Altherma and Viessmann production of domestic hot water (initial setting of 40 F outside). Below this setting, we wish to dedicate all of the heat pump output to space heating through the radiant zones. The Viessmann boiler will be responsible for the entire dhw load. Above an initial setting of 40 F, we wish to disable Viessmann dhw production and have the Altherma continue with both space heating and dhw production. A motorized 3 way valving arrangement switches between the preheat and final dhw tank; below the initial setting of 40 F, the Daikin dhw tank is preheat and the Viessmann is final above 40 F their roles reverse. As the climate of Martha s Vineyard experiences great temperature swings in the transitional seasons, this switching arrangement ensures that any energy spent heating domestic hot water is not lost as the outside temperature rises above and falls below the 40 F setpoint. From a sanitary perspective, this arrangement also ensures that both tanks are always filled with potable water fit for human consumption. Building and DHW Loads: Schematic M3 The upper illustration is a depiction of the building heat loss as a function of outside temperature (at a maximum at 0 F outside down to a minimum at 68 F warm weather shutdown). Plotted against this is the heating output of the Altherma as a function of outside temperature (blue shaded area). There will be a balance temperature above which the Altherma output will be able to meet the entire building heat loss. Below this balance temperature, the Viessmann boiler output will be added as a second stage (orange shaded area) to meet the increasing building heat loss.

6 The Vitotronic control on the Viessmann has two outside reset temperature curves that serve the high temp and mix temp circuits. An additional Viessmann control, the Switching Module V, permits the external control of the boiler burner. Below the initial setting of 40 F outside, the Radiant Stat enables the burner and the boiler will maintain the high temp reset curve. While this is somewhat inefficient, it is the Viessmann approach so that the boiler is ready if there is a call from the high temp circuit radiant panel zone. Above the initial setting of 40 F, the Radiant Stat will disable the boiler burner and the building heat loss will be met by the Altherma output. The lower illustration is a depiction of domestic hot water production by either the Viessmann boiler or the Daikin Altherma. The orange shaded rectangle indicates the temperature range in which the Viessmann boiler will perform dhw heating; the blue rectangle represents Altherma dhw heating. On the y axis we show hourly domestic hot water output the Viessmann hourly output of dhw will be somewhat greater than the Altherma output. We expect that due to projected use, the Altherma dhw output will be entirely satisfactory. Below an initial setting of 40 F, the DHW Stat will enable boiler burner operation and switch the motorized valves so that the Daikin dhw tank serves as preheat to the Viessmann tank. The Vitotronic control will sense tank temperature and operate the burner and dhw circulator to maintain 130 F in the Viessmann tank. The Altherma output will be devoted to space heating and domestic hot water production will be disabled via a field setting. Above 40 F, the DHW Stat will switch dhw roles by changing the motorized valve positions and disabling the Viessmann boiler burner. The Viessmann dhw tank will now serve as preheat and the Daikin dhw tank will maintain 125 F. Smart Grid Integration: The project location is also part of a SmartGrid integration project with General Electric and the Vineyard Energy Project, a local energy group. We are serving as their technical liaison with the 50 families in the pilot project. Real time information about current electricity pricing (3 price tiers) will be available at a local GE interface device and can be used as an input to the Altherma. We wish to use this kwh pricing information and the benefit rate kwh power supply field settings on the Altherma to determine backup and booster heater operation. A comparison can be made between the price of propane (at a projected system efficiency of 90% for the Viessmann installation) versus the current electricity price tier (at a projected COP of 1 for the booster and backup heater).

7 Control Details: Schematics M4 and M5 This schematic shows one approach to the controls necessary to integrate the Daikin Altherma with the existing Viessmann system. As described above, the external interface to the Viessmann system will be their Switching Module V which permits remote control of the boiler burner. When the contact X7 on this module is closed, burner operation is disabled. Therefore, the domestic hot water, radiant, and hi temp relays all have their burner disable contacts in series. Any one of these relays may call for burner operation independently of each other. Domestic Hot Water Controls: Schematics M4 and M5 A DHW Stat responds to a drop in outside temperature below the initial setpoint of 40 F and closes an internal contact which powers the DHW Relay. (For the sake of simplicity we depict this DHW Stat as a Honeywell remote bulb controller T675A1508 with adjustable differential and operating range of 0 F to 100 F. We expect that this switching function can easily be provided by a web based DDC system that we hope to use to trend system operation.) When powered, the DHW Relay will power the motorized valves DHWMV1, DHWMV2, and DHWMV3 to their Daikin dhw preheat/viessmann dhw final position. The DHW Relay will also close the circulator contact and connect the Viessmann dhw circulator to the Vitotronic 200 on the boiler. The normally closed contacts on the burner disable points will open and enable burner operation. The Vitotronic control on the boiler will monitor Viessmann dhw tank temperature and will now be able to heat domestic hot water as necessary. Similarly, when the DHW Stat experiences a rise in outside temperature above the initial setpoint (plus the adjustable differential) of 40 F, the internal contacts will open and the DHW Relay will return to its unpowered state. The DHW Relay will then power the motorized valves DHWMV1, DHWMV2, and DHWMV3 to their Viessmann dhw preheat/ Daikin dhw final position. The DHW Relay will also open the circulator contact and disconnect the Viessmann dhw circulator from the Vitotronic 200 on the boiler. The burner disable points will return to their normally closed position. The field settings on the Altherma hydrobox will ensure that domestic hot water is now generated by the heat pump system. Radiant Heating Controls: Schematics M4 and M5 A Radiant Stat responds to a drop in outside temperature below the initial setpoint of 40 F and closes its internal contacts. Local radiant zone thermostats connected to a Taco circulator control operate their respective radiant zone circulators and close a normally open end switch on the Taco

8 control. This end switch and the Radiant Stat contacts are in series; if both contacts are made then the Radiant Relay is powered. (As with the DHW Stat we depict the Radiant Stat as a Honeywell remote bulb controller T675A1508 with adjustable differential and operating range of 0 F to 100 F. We expect that this switching function can easily be provided by a web based DDC system that we hope to use to trend system operation.) When powered, the Radiant Relay will power the motorized valve RadMV1 to direct hydronic flow from the Altherma hydrobox outlet to the Viessmann Divicon mixing station inlet. The Radiant Relay will also close the circulator contact and connect the Divicon mix circulator to the Vitotronic 200 on the boiler. The normally closed contacts on the burner disable points will open and enable burner operation. The Vitotronic control on the boiler will monitor Viessmann boiler and will heat the boiler to the high temp reset curve (only because this reset curve is always hotter than the mix temp reset curve). Similarly, when the Radiant Stat experiences a rise in outside temperature above the initial setpoint (plus the adjustable differential) of 40 F or all of the radiant zone thermostats are satisfied and the Taco end switch opens, the Radiant Relay will return to its unpowered state. The Radiant Relay will then power the motorized valve RadMV1 to direct hydronic flow to bypass the Viessmann Divicon mixing station. In this mode, only the Altherma hydrobox output will be connected to the mix temp circuit and the radiant zones. The Radiant Relay will also open the circulator contact and disconnect the Viessmann Divicon mix circulator from the Vitotronic 200 on the boiler. The burner disable points will return to their normally closed position. Hi Temp Heating Controls: Schematics M4 and M5 The hi temp thermostat connected to a Taco switching relay circulator control operates the hi temp zone circulator and closes a normally open end switch on the Taco control. When this end switch closes the Hi Temp Relay is powered. When the Hi Temp Relay is powered, the normally closed contacts on the burner disable points will open and enable burner operation. The Vitotronic control on the boiler will monitor Viessmann boiler temp and will heat the boiler to the high temp reset curve. When the hi temp thermostat is satisfied and the Taco end switch opens, the Hi Temp Relay will return to its unpowered state. The burner disable points will return to their normally closed position.

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

prestige Control Application Supplement - ACVMax

prestige Control Application Supplement - ACVMax 2015-10 Prestige ACVMax Control Sup 12-14-15_ACVMax_Control 12/15/15 7:36 AM Page 1 prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

Control Application. Supplement - ACVMax

Control Application. Supplement - ACVMax prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

Outdoor Reset Control Theory FULL versus PARTIAL reset

Outdoor Reset Control Theory FULL versus PARTIAL reset Outdoor Reset Control Theory FULL versus PARTIAL reset Conventional boilers must be protected against sustained operation at low temperatures. If not, they will be damaged by sustained flue gas condensation.

More information

- Data Brochure Universal Reset Module 422

- Data Brochure Universal Reset Module 422 - Data Brochure Universal Reset Module 422 D 422 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

Public. Altherma by Daikin. Altherma Commissioning Service Field Settings

Public. Altherma by Daikin. Altherma Commissioning Service Field Settings Public Altherma by Daikin Altherma Commissioning Service Field Settings Altherma Service Settings There are several service codes that can be altered to maximise the efficiency of the Altherma system.

More information

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control.

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control. Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA 02717 The first totally integrated multiple boiler management control. USING THIS MANUAL USING THIS MANUAL A. INSTALLATION SEQUENCE Follow

More information

- Data Brochure Universal Reset Module 423

- Data Brochure Universal Reset Module 423 - Data Brochure Universal Reset Module 423 D 423 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

FREQUENTLY ASKED QUESTIONS

FREQUENTLY ASKED QUESTIONS HEAT PUMP INVERTER R-410A All-in-one, all year round heating, cooling and domestic hot water supply solution FREQUENTLY ASKED QUESTIONS WANT TO KNOW MORE? AVERAGE ANNUAL CO 2 EMISSIONS Daikin Altherma

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Applications and Piping Strategies for Condensing Boilers - Introduction

Applications and Piping Strategies for Condensing Boilers - Introduction Applications and Piping Strategies for Condensing Boilers - Introduction Foil 2, 10/2015 Viessmann Manufacturing Applications and Piping Strategies for Condensing Boilers Webinar Objectives: 1. Control

More information

GEOTHERMAL HYDRONIC CONTROL MODULE By TERRA-THERM, INC.

GEOTHERMAL HYDRONIC CONTROL MODULE By TERRA-THERM, INC. GEOTHERMAL HYDRONIC CONTROL MODULE By TERRA-THERM, INC. Physical Dimensions: 15-11/16 H x 11-13/16 W x 6-19/32 D M2-0152 HEAT PUMP HYDRONIC CONTROL MODULE With 2-stage heat, 2-stage cooling setpoint controls

More information

- Data Brochure Boiler Control 274

- Data Brochure Boiler Control 274 - Data Brochure Boiler Control 274 274_D 03/17 The Boiler Control 274 operates up to four on/off boilers to provide outdoor reset operation, domestic hot water and setpoint operation with priority. When

More information

Technical Data Manual

Technical Data Manual VITOTRONIC 300 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits Technical Data Manual Vitotronic 300 Model KW3, Part No. Z001 231 For operation

More information

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL The SF-10 Temperature Control () is an efficient boiler operator with a digital LCD display with backlight, a boiler pump output, and an alarm. The

More information

Parameter guide 95M-200 GAS-FIRED DIRECT VENT MODULATING HOT WATER BOILER WARNING WARNING

Parameter guide 95M-200 GAS-FIRED DIRECT VENT MODULATING HOT WATER BOILER WARNING WARNING 95M-200 GAS-FIRED DIRECT VENT MODULATING HOT WATER BOILER! WARNING Revise boiler control parameters only if you fully understand the purpose and result of the changes and on the advice of ECR Technical

More information

- Essay Control Functions and Benefits

- Essay Control Functions and Benefits - Essay Control Functions and Benefits E 005 07/01 A hydronic heating control system performs many complex and important functions. Each of these functions provide benefits that make the system comfortable,

More information

DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override

DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override Date Code - Data rochure oiler Control 265 D 265 10/03 The tekmar oiler Control 265 can control the supply water temperature on up to three modulating boilers based on outdoor temperature or setpoint requirements.

More information

Zoning Solutions. Thermostats & Wiring Centers Designed to Maximize Indoor Comfort. A Watts Water Technologies Company

Zoning Solutions. Thermostats & Wiring Centers Designed to Maximize Indoor Comfort. A Watts Water Technologies Company Zoning Solutions Thermostats & Wiring Centers Designed to Maximize Indoor Comfort HVAC Systems Multi-Staging Alternative Energy Zoning Snow Melting Setpoint A Watts Water Technologies Company Zoning in

More information

Radiant Heating. Systems

Radiant Heating. Systems O p t i m i z i n g t h e P e r f o r m a n c e o f Radiant Heating Systems Minimizing costly mistakes and maximizing a radiant project s performance by focusing on building and system efficiency Radiant

More information

PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY. 3/16/2012 Fred Ferrara 1

PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY. 3/16/2012 Fred Ferrara 1 PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY 3/16/2012 Fred Ferrara 1 Typical Hydronic System Problems Low Delta T s resulting in: 1. Chillers operating at higher capacities and/or longer than necessary

More information

MODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL

MODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL MODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL The EM-10 Boiler Temperature Control (BTC) is an efficient boiler operator with a digital LCD display with backlight, a boiler pump

More information

- Application A Boiler Control 262 & One Stage Setpoint Control 150. Mechanical Remote Display Module (D1) 040 MODE 1

- Application A Boiler Control 262 & One Stage Setpoint Control 150. Mechanical Remote Display Module (D1) 040 MODE 1 - Application Boiler Control & One Stage Setpoint Control 150 A -1 07/99 echanical Remote Display odule () 040 Outdoor Sensor () 070 150 ODE 1 Class II Transformer 120 V (ac) 24 V (ac) R1 A2 Z1 Z2 Z3 T1

More information

Hydronic & HVAC Control Systems

Hydronic & HVAC Control Systems tekmar 218 Full Line Catalog Hydronic & HVAC Control Systems HVAC Multi-Staging Alternative Energy Zoning Snow Melting Setpoint tekmarcontrols.com tekmarcontrols.com Better Design, Better Control, Better

More information

heat interface units A BOILER WITHOUT A FLAME

heat interface units A BOILER WITHOUT A FLAME A BOILER WITHOUT A FLAME heat interface units Communal Heat Networks A central boiler house will generate heat which is distributed through a network of pipe to each home or apartment in the building.

More information

Better Design, Better Control, Better Systems.

Better Design, Better Control, Better Systems. Product Catalog Better Design, Better Control, Better Systems. At tekmar Control Systems, we believe the indoor comfort of a building depends on the performance of its heating, ventilating & air conditioning

More information

Installation & Operation Manual

Installation & Operation Manual Boiler Control 275 Installation & Operation Manual Multi-Staging D 275 01/12 Replaces:03/09 The Boiler Control 275 is designed to stage up to four condensing or non-condensing, modulating or on-off boilers

More information

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler WARNING: Improper installation, setup, modification, operation or maintenance of the heating system can cause personal injury and property damage. Follow each appliances' instructions precisely. For assistance

More information

Multi Boiler Guide. Kit #

Multi Boiler Guide. Kit # Multi Boiler Guide Kit # 550002186 Technical Support @ 800-325-5479 Phone: (315) 797-1310 Fax: (866) 432-7329 e-mail: info@ecrinternational.com web site: www.ecrinternational.com Information and specifications

More information

Leading Word on Lag Modules

Leading Word on Lag Modules Electronic Service Inc. KW Electronic Service Inc. and Viessmann, partners in heating technology. Controls newsletter, May 2002, Issue 2 T hank you to everyone who responded to our first edition of VITOTALK.

More information

prestige Control Application Supplement - Type 5 MCBA WARNING

prestige Control Application Supplement - Type 5 MCBA WARNING prestige Control Application Supplement - Type 5 MCBA L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all

More information

prestige Control Application Supplement - Type 5 MCBA WARNING

prestige Control Application Supplement - Type 5 MCBA WARNING prestige Control Application Supplement - Type 5 MCBA WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

Boiler Demand Mix 1 Demand Mix 2 Demand DHW Demand Setpoint Demand

Boiler Demand Mix 1 Demand Mix 2 Demand DHW Demand Setpoint Demand Date Code - Data Brochure Universal Reset Control 374 D 374 10/03 The tekmar Universal Reset Control 374 is designed to maximize the comfort and effi ciency provided by a hydronic heating system. The control

More information

- Data Brochure Steam Control 279

- Data Brochure Steam Control 279 - Data Brochure Steam Control 279 D 279 12/07 The tekmar Steam Control 279 can operate a single on-off steam boiler or an on-off steam valve using outdoor reset. The control determines the on time of the

More information

WWSD. Power. DHW Demand. Maximum. Supply. Minimum Boiler DHW. Zone 1 / Cooling. Pump / Vlv. System Pump. UnOccupied. of full output NRTL/C LR 58223

WWSD. Power. DHW Demand. Maximum. Supply. Minimum Boiler DHW. Zone 1 / Cooling. Pump / Vlv. System Pump. UnOccupied. of full output NRTL/C LR 58223 Dial the desired duration of the period. Press start button at the time of day you want the UnOcc. period to begin. light turns on. 0 = always = always Pump / Vlv System Pump Zone / Cooling NRTL/C LR 58

More information

Frequently Asked Questions. A 3 in 1 Renewable Energy Solution For Home Heating, Cooling and Domestic Hot Water

Frequently Asked Questions. A 3 in 1 Renewable Energy Solution For Home Heating, Cooling and Domestic Hot Water Frequently Asked Questions A 3 in 1 Renewable Energy Solution For Home Heating, Cooling and Domestic Hot Water Why use a Heat Pump? Space Heating, Domestic Hot Water, and Cooling WHERE DOES IT ALL START?

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

BHSAPPMAN 08/00 USA. Applications Manual. Ecomatic / Logamatic Controls. Save These Instructions!

BHSAPPMAN 08/00 USA. Applications Manual. Ecomatic / Logamatic Controls. Save These Instructions! BHSAPPMAN 08/00 USA Applications Manual Ecomatic / Logamatic Controls Save These Instructions! TABLE OF CONTENTS 1 2 3 4 5 6 7 8 Introduction 1 Terms 2-4 Description of Wiring Terminals 5-7 Application

More information

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference.

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference. Installation and Service Instructions for use by heating contractor Solar Control Module for solar connections to the Vitotronic control SM1 SOLAR CONTROL MODULE Product may not be exactly as shown IMPORTANT

More information

VITOSOL. Solar hot water heating systems Flat plate and vacuum tube solar collectors

VITOSOL. Solar hot water heating systems Flat plate and vacuum tube solar collectors VITOSOL Solar hot water heating systems Flat plate and vacuum tube solar collectors Solar energy can account for up to 70% or more of the energy required to heat the domestic hot water of an average family

More information

This is one of several geothermal projects designed and installed by contractor Nelson Mechanical Design, Martha s Vineyard.

This is one of several geothermal projects designed and installed by contractor Nelson Mechanical Design, Martha s Vineyard. Energy Excellence in Martha s Vineyard by Barb Checket-Hanks May 17, 2010 Nelson Mechanical Design (NMD) has a long standing reputation for being a green contractor, and it goes beyond the steps many HVAC

More information

The Universal Reset Control 363 is a microprocessor based control designed to maximize the comfort and efficiency provided by a hydronic

The Universal Reset Control 363 is a microprocessor based control designed to maximize the comfort and efficiency provided by a hydronic R Vie Menu % % 1 2 Item F! WWS Vie Menu % % 1 2 Item F! WWS 70 LR 58233 E150539 Universal Reset Control 363 - Data Brochure D 363 12/08 The Universal Reset Control 363 is a microprocessor based control

More information

Heating Zone Control. How to apply RESOL MX controller

Heating Zone Control. How to apply RESOL MX controller Heating Zone Control How to apply RESOL MX controller Basic Diagram Sensor No Description Relay No. Description S4 Boiler Supply Sensor R5 DHW Loading Pump S5 DHW Tank Temperature Sensor R6 Zone Valve

More information

Installation & Operation Manual

Installation & Operation Manual 557_D tekmarnet Thermostat 557 09/14 Zoning Replaces: 09/13 Installation & Operation Manual Introduction The tekmarnet Thermostat 557 is a communicating touchscreen thermostat designed to operate either:

More information

TOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal TOTAL SYSTE EFFICIENCY: CONTROL STRATEGIES & SYSTE DISTRIBUTION David Grassl PE echanical Engineer Principal This is the second paper in the total system efficiency series that will detail various control

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2004-28 TSG-SOLO-9/04 Table of Contents INTRODUCTION Page 1 SERVICING TIPS AND INSTRUCTIONS Page 3 CONTROL MODULE DISPLAY -

More information

TRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE.

TRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE. Slide 1 TRACE 700 Chiller Sequencing and Controls Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE. Today, we will be talking about the Plant Sequencing and Controls

More information

ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY (Corporate Sales) 85 Middle Road

ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY (Corporate Sales) 85 Middle Road ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY 13501 (Corporate Sales) 85 Middle Road An ISO 9001-2000 Certified Company Dunkirk, NY 14048 www.argoindustries.com P/N 240005498A, Rev. 1.5 [02/07]

More information

- Data Brochure Universal Reset Control 364

- Data Brochure Universal Reset Control 364 70 7 8 9 - Data Brochure Universal Reset Control 364 D 364 07/01 The Universal Reset Control 364 is designed to maximize the comfort and efficiency provided by a hydronic heating system. The control automatically

More information

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

1 DOCUMENT REVISION CONTROL ELEMENTS... 9 CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11

More information

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS David Grassl PE Mechanical Engineer Principal Similar to traditional boiler systems, condensing boiler systems have many designs they can operate

More information

- Data Brochure Mixing Control 360

- Data Brochure Mixing Control 360 - Data Brochure Mixing Control 360 D 360 03/09 The Mixing Control 360 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or setpoint operation. The

More information

Radiant Mixing Block

Radiant Mixing Block EFFECTIVE: arch 1, 2004 Taco Radiant ade Easy Application Guide Radiant ixing Block Products & Applications PA09 SUPERSEDES: New OVERVIEW Radiant ixing Block The Taco Radiant ixing Block (RB) is a complete

More information

prestige Control Application Supplement WARNING

prestige Control Application Supplement WARNING prestige Control Application Supplement WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions within this

More information

HEAT TROL ELITE SERIES HWE-Single Stage, HWE-MOV, HWE-Mulit Stage Hot Water Reset Control for Light Commercial and Residential Applications Provides q

HEAT TROL ELITE SERIES HWE-Single Stage, HWE-MOV, HWE-Mulit Stage Hot Water Reset Control for Light Commercial and Residential Applications Provides q SIGNAL REPEATER RC2100 WI-CON Wireless Heating Control for Steam and Hot Water Boilers No sensor wiring required Intelligent sensing algorithm saves energy Low limit control and alarm alert operator of

More information

- Data Brochure D 260. Boiler Control /09

- Data Brochure D 260. Boiler Control /09 - Data Brochure Boiler Control 260 D 260 03/09 The Boiler Control 260 is designed to control a single stage heat source in order to provide outdoor reset or Domestic Hot Water () operation. The control

More information

ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International Presentation Overview Water Heater Piping Strategies How to size a water heater?

More information

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS Copyright 2011. R. Trethewey, All rights reserved. No part of this document or file may be used without permission of the author. All diagrams are conceptual

More information

Heating and D.h.w. Controller RVL482 Basic Documentation

Heating and D.h.w. Controller RVL482 Basic Documentation Heating and D.h.w. Controller RVL482 Basic Documentation Edition: 1.0 Controller series: A CE1P2542en 20.05.2008 Building Technologies Siemens Switzerland Ltd Building Technologies Group International

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Circulators high efficiency ECM Circulators

Circulators high efficiency ECM Circulators Circulators high efficiency ECM Circulators Circulators high efficiency ECM Circulators Small ECM circulators now available in North America Grundfos Alpha: Provides constant and proportional differential

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

- Data Brochure Boiler Control 264

- Data Brochure Boiler Control 264 - Data Brochure Boiler Control 264 D 264 11/03 The tekmar Boiler Control 264 can control the supply water temperature from up to 4 on / off stages based on outdoor temperature, control for Domestic Hot

More information

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating

More information

6 PIPING ARRANGEMENTS

6 PIPING ARRANGEMENTS 6 PIPING ARRANGEMENTS The design of a panel radiator based heating system involves selection of a piping system, pipe sizes, overall design temperature drop, required flow rates and desired type of system

More information

Vitocrossal 300, CU3A - Introduction

Vitocrossal 300, CU3A - Introduction - Introduction Sales Presentation Foil 2, 04/2015 Viessmann Manufacturing Floor standing, high mass, gas-fired condensing boiler Sales Presentation Foil 3, 04/2015 Viessmann Manufacturing Features: Floor

More information

BOILER APPLICATION GUIDE for:

BOILER APPLICATION GUIDE for: T MFC Series Boiler Application Guide GF-148-B TECHNICAL APPLICATION GUIDE BOILER APPLICATION GUIDE for: Piping and Controls, Water Quality, and Single/Multi Installations Applies to MFC Series Models:

More information

The natural ombination

The natural ombination The natural ombination DAikin Altherma Hybrid heat pump 2 A new pportunity in residential heating! There is a growing demand from home owners to replace heating systems, especially replacing of gas boilers,

More information

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR 5:1 FIRING RATE MODULATION LESS THAN 20 ppm NOx DIRECT VENT FLEXIBILITY TO 100 FEET 96% AFUE

More information

INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

INSTALLATION MANUAL AND OPERATING INSTRUCTIONS AMB4/AMB8 MULTIPLE BOILER SEQUENCERS INSTALLATION MANUAL AND OPERATING INSTRUCTIONS ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY 13501 (Corporate Sales) 85 Middle Road An ISO 9001-2000 Certified

More information

Logamax plus GB142. Applications Manual. Gas condensing boiler

Logamax plus GB142. Applications Manual. Gas condensing boiler Applications Manual Gas condensing boiler WARNING! Improper installation, adjustment, alteration, service or maintenance can cause injury, loss of life or property damage. Refer to the installation and

More information

Versa- Hydro. up to 96% Efficient

Versa- Hydro. up to 96% Efficient Versa- Advanced Heating & Hot Water Systems Hydro up to 96% Efficient The cost effective Versa-Hydro combines space heating, domestic hot water, and total system control into one compact, high efficiency

More information

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502* User's Guide VI.7B.D5.02 2005.10 P20 *VI7BD502* *087R8014* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8014* *VI7BD502* Boiler controller P20 VI.7B.D5.02

More information

Instruction Sheet. Press & Hold: Item, to view settings, to test. 24 V ±10% 50/60 Hz 3 VA 120 V (ac) 5 A 1/6 hp pilot 240 VA 20 to 260 V (ac) 2 VA

Instruction Sheet. Press & Hold: Item, to view settings, to test. 24 V ±10% 50/60 Hz 3 VA 120 V (ac) 5 A 1/6 hp pilot 240 VA 20 to 260 V (ac) 2 VA Instruction Sheet PC2 1 Two Stage Reset & Control SUPERSEDES : 102-106, dated June 1, 2000 EFFECTIVE: March 1, 2004 Plant ID# 9300-1059 Item 102-106 The PC2-1 is a microprocessor-based control designed

More information

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode Operating instructions for the system user VIESMANN Heating system with Vitotronic 100 control unit for constant temperature mode VITODENS VITOPEND 4/2007 Please keep safe. Safety instructions For your

More information

The iqe Boiler Range. Combination and System T Boilers.

The iqe Boiler Range. Combination and System T Boilers. The iqe Boiler Range Combination and System T Boilers www.iqe.co.uk iqe - Max Technology Max Efficiency iqe is a select group of partners that have come together to create a unique product range of highly

More information

Application Guide. Vitodens 100-W B1HA/B1KA Residential Boiler

Application Guide. Vitodens 100-W B1HA/B1KA Residential Boiler Application Guide Vitodens 100-W B1HA/B1KA Residential Boiler APPLICATION GUIDE The application examples contained in this document serve as a guideline only. These are not engineered drawings and are

More information

LOW TEMPERATURE HYDRONIC HEATING FOR COLD CLIMATES TRAVIS SMITH PRESIDENT T AND T MOUNTAIN BUILDERS INC

LOW TEMPERATURE HYDRONIC HEATING FOR COLD CLIMATES TRAVIS SMITH PRESIDENT T AND T MOUNTAIN BUILDERS INC LOW TEMPERATURE HYDRONIC HEATING FOR COLD CLIMATES TRAVIS SMITH PRESIDENT T AND T MOUNTAIN BUILDERS INC COLD CLIMATES REFERRING SPECIFICALLY TO CLIMATES ZONES 6 & 7 HYDRONIC HEATING USING A FLUID TO TRANSFER

More information

Split Type System. Air to Water Heat Pump

Split Type System. Air to Water Heat Pump Split Type System Air to Water Heat Pump EXPERTISE AND INNOVATION Daikin Altherma offers complete flexibility for new construction and deep energy refurbishment projects. Using a low temperature hydronic

More information

Geothermal Programming Guide. Central Processing Unit 1000 Version 1.33 ECO HBX Control Systems Inc. Page 1

Geothermal Programming Guide. Central Processing Unit 1000 Version 1.33 ECO HBX Control Systems Inc. Page 1 Geothermal Programming Guide Central Processing Unit 1 Version 1.33 ECO-1 HBX Control Systems Inc. Page 1 HBX ECO-1 HVC Control Version 1.33 - ECO 1 CENTRL PROCESSING UNIT - v - v - v DO NOT CONNECT POWER

More information

- Data Brochure Addendum

- Data Brochure Addendum - Data Brochure ddendum Control 268 - ddition of Modes and Setpoint Modes D 268 10/03 The tekmar Control 268 has been modified to include the following features: demand for loads alarm New Setpoint operation

More information

- Data Brochure Mixing Control 361

- Data Brochure Mixing Control 361 TIME PRGM 1 2 AMPM UN OVR S M T W T F S - Data Brochure Mixing Control 361 D 361 05/00 The Mixing Control 361 is designed to control the supply water temperature to a hydronic system in order to provide

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Technical Report #3 Mechanical Systems Existing Conditions Evaluation Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents

More information

Psychrologix Controller W/ DHC

Psychrologix Controller W/ DHC Psychrologix Controller W/ DHC User Manual For Psychrologix version 1.3 Please read this entire document before connecting the Psychrologix controller. 1 *IMPORTANT PLEASE NOTE The Following: First, a

More information

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions - Brochure tekmarnet 4 Thermostat 542 D 542 06/05 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough In Wiring Rough-in 4 Wiring

More information

- Data Brochure Addendum

- Data Brochure Addendum - Data Brochure ddendum Control 264 - ddition of Modes and Setpoint Modes D 264 10/03 The tekmar Control 264 has been modified to include the following features: demand for loads alarm New Setpoint operation

More information

EVERGREEN HIGH EFFICIENCY CONDENSING BOILER

EVERGREEN HIGH EFFICIENCY CONDENSING BOILER www.weil-mclain.com EVERGREEN HIGH EFFICIENCY CONDENSING BOILER Water Natural/Propane Gas 70-399 MBH 6 Sizes Direct Vent 95% AFUE* EASY HEAT, EFFORTLESS COMFORT We ve got you covered. All come equipped

More information

IBC Technologies Venables Street, Vancouver, BC, V5L 2G8 - Ph Fax E -

IBC Technologies Venables Street, Vancouver, BC, V5L 2G8 -   Ph Fax E - TECHNICA NOTES October 2010 MUTIPE BOIER SYSTEMS Version 2.0 Technologies - 1543 Venables Street, Vancouver, BC, V5 2G8 - www.ibcboiler.com Ph - 604 877 0277 Fax - 604 877 0295 E - info@ibcboiler.com IMPORTANT:

More information

aquatherm heat dissipater control unit and aquatherm heating circuit distributor (Product No ) for floor heating

aquatherm heat dissipater control unit and aquatherm heating circuit distributor (Product No ) for floor heating aquatherm NZ Ltd 36 Rockridge Avenue, Penrose, Auckland 1061 P O Box 99 393, Newmarket, Auckland 1149 Tel: (09) 570 7204 Fax: (09) 570 7206 www.aquatherm.co.nz Assembly instructions aquatherm heat dissipater

More information

Best Practices for Condensing Boilers

Best Practices for Condensing Boilers ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cleaverbrooks.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For

More information

Qualifies for up to $ 1500 Energy Tax Credit! CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ALL NEW, ADVANCED USER FEATURES

Qualifies for up to $ 1500 Energy Tax Credit! CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ALL NEW, ADVANCED USER FEATURES CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ALL NEW, ADVANCED USER FEATURES 5 FLOOR-STANDING AND 5 WALL-MOUNT MODELS FROM 50,000 TO 285,000 BTU/HR FIRING RATE MODULATION TO 5:1 LESS THAN 20 ppm NOx

More information

THE HEAT PUMP CHOICE OF PROFESSIONALS

THE HEAT PUMP CHOICE OF PROFESSIONALS THE HEAT PUMP CHOICE OF PROFESSIONALS T H E E N E R G Y E F F I C I E N T H E AT I N G S Y S T E M TIME FOR ENERGY EFFICIENT AND INNOVATIVE SOLUTIONS Expectations of consumers are changing. With the high

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 11/10/08 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1 SERVICING TIPS AND INSTRUCTIONS Page 3 CONTROL

More information

The electrical wattage needed by the circulator is:

The electrical wattage needed by the circulator is: The electrical wattage needed by the circulator is: w e = 0.4344 f P n w/w A current-generation wet-rotor circulator has a maximum wire-towater efficiency in the range of 25 percent. If we put the data

More information

Service Instructions for use by heating contractor

Service Instructions for use by heating contractor Service Instructions for use by heating contracr Please file in Service Binder Vitronic 300 Model KW3 Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating

More information