Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Size: px
Start display at page:

Download "Executive Summary. Number of Low Number of High Number of Faults , Number of OK"

Transcription

1 Unit Lower limit Upper limit Air on Model no evap. F Air off evap. F dt air evap. F Executive Summary Evapo. F This is a summary chart for quick reference and view of all the systems tested. Red boxes indicate measured levels that were out of range. There were faults in evaporator dt, condenser dt, superheat, subcool, and isentropic efficiency of the compressors. Fault levels are determined from manufacturer s recommendations and testing experience. EER at Ambient Temperatures dt air- Super Air on Air off dt air Conde dt air- Sub cool Comp evap heat cond. F cond. F cond. F n. F cond F eff. AH 10 C1 Model# 50HJQ AH 10 C2 Model# 50HJQ GE 2 Model#48TJE GE 3 Model# 48TJE GE 7 Model# 48TJD GE 8 Model# 48TJD GE 13 Model# 48TJD GE 15 C1 Model# 48TJD GE 15 C2 Model# 48TJD Mean Max Min Number of Low Number of High Number of Faults , Number of OK EER Power kw Cooling cap Note: these are measured EER, not equipment rating. This graph shows the EER each circuit was operating at during the test at the average ambient. It would be expected to see a drop in EER the further to the right the units get, as EER should drop as ambient temperature rises.

2 EER and Return Air Temperature Note: these are measured EER, not equipment rating. This graph shows the EER of each circuit during the test with the Return air to the evaporator. You would expect to see a drop in EER the further right each unit gets, as the higher the return air temperature gets the lower the EER should be. 2 P a g e

3 Measured EER Results AH-10 C1 AH-10 C2 GE-2 GE-3 GE-7 GE-8 GE-13 GE-15 C1 GE-15 C2 ClimaCheck Measured EER Nominal EER for the compressor at measured conditions (Copeland Compressor design EER) Expected Nominal EER This Graph shows three different EER metrics. ClimaCheck takes multiple measurements then uses thermodynamic calculations to get the EER level. A Copeland software program was used to calculate design EER levels for the compressor. A compressor in Copeland s software was chosen that was closest in comparison to the compressor on the Carrier unit, but as it is not identical, the data will vary somewhat. Measurements that the ClimaCheck took were imported into the software to get the nominal EER level. This is essentially the EER that the compressor should be running in these conditions. The expected EER was derived from the software by averaging data from multiple conventional RTUs with no known problems that were tested previously with the ClimaCheck. This is not a perfect calculation, but a reasonable expectation of unit performance if there are no problems. Below are the averages used for Expected Nominal EER. Evaporation Temperature = evaporator entering air -35 F (the average delta T entering air to evaporation temperature on previous units tested without issues) Condensing Temperature = ambient Temperature + 25 F (the average delta T entering air to condensing temperature on previous units tested without issues) Superheat = Average temperature of 10 F Subcool = Average temperature of 15 F 3 P a g e

4 Compressor Isentropic Efficiency Compressor isentropic efficiency is a comparison of the actual compression process efficiency vs. the theoretical efficiency of a perfect compression process. This compressor is averaging about 63% isentropic efficiency. Most of the other compressors in this test were around 70%. This unit and GE-3 are the only two units tested that have Tecumseh compressors. It is interesting to see that these two units also have the lowest EER of all units tested. The difference between 63% and 70% is only 7% but the difference in performance is actually 11%. 4 P a g e

5 GE-15 GE-15 conditions a large break room with refrigerated vending machines in it that produce a constant load. This unit conditions with 2-stage mechanical cooling and natural gas heat. Refrigeration Process Discharge Temp Circuit 1 Discharge Temp Circuit 2 Superheat Circuit 1 Superheat Circuit 2 This unit has two stages of cooling using the same evaporator and condenser coils though the refrigeration circuits are separate. Both refrigeration circuits are almost identical and should run almost identical. However, this graph shows that this is not the case during this test. Circuit 2 has 0 superheat. Superheat this low brings the discharge temperature down. 5 P a g e

6 Superheat Superheat Circuit 1 Avg. 22 F Superheat Circuit 2 Avg. 0 F Most RTUs are efficient between F of superheat and many manufacturers suggest this range. However, with Carrier s Acutrol fixed orifice metering device the refrigerant charge is the greatest determining factor of the superheat level. As outside ambient temperatures and indoor space temperatures change this affects the superheat and causes it to change as well. Circuit 1 is averaging about 22 F of superheat. The charging chart on page 59, shows the superheat should be at about 9 F (±5 suction temp) in these conditions. Circuit 2 rapidly drops to 0 of superheat as the test starts. The charging chart on page 58 shows this circuit should be operating at about 11 F of superheat (±5 suction temp). 6 P a g e

7 Subcool Subcool Circuit 2 Avg. 25 F Subcool Circuit 1 Avg. 17 F Both refrigeration circuits should have the same refrigerant charge in them. If the circuits have the same charge and are operating the same you would see the subcool of both circuits at the same level. It would be expected that with the very low superheat of circuit 2, it would have a lower subcool as well because too much refrigerant is in the evaporator and not the condenser. That is not the case. Circuit 2 has high subcool that may be causing the low superheat. Similar units to this one would run around F subcool in these conditions, however, all of the units on this roof have issues with condenser coil corrosion. It is difficult to measure the level of corrosion so it is very difficult to say where the subcool should be with a corroded condenser coil. If the refrigerant charge is correct it would be expected that the worse the corrosion is the higher the subcool would be. Although evaporator air inlet temperature would have to be taken into account as well. 7 P a g e

8 Condenser Condensing Temperature circuit 2 Condensing Temperature circuit 1 Avg. DT of 40 F Avg. DT of F Air inlet temperature at Condenser The blue and green at the top of the graph shows the condensing temperature of circuits 1 and 2. At the bottom of the graph, (in light blue) is the air temperature at the inlet of the condenser. The difference of these would be referred to as the delta T air inlet to condensing temperature. During the test the delta T air inlet to condensing averaged close to 40 F on circuit 1 and F on circuit 2. A new higher efficiency RTU with good controls could run F dt. Older units are usually around 20 to 25 F dt. This higher dt level than usually seen on DX air conditioners and may indicate a problem with the condenser s ability to transfer heat. The 60 F dt of circuit 2 is indicating a major problem. 8 P a g e

9 Evaporator Evaporation Temperature Circuit 2 Evaporation Temperature Circuit 1 The high pressure side of the system and the low pressure side of the system are only separated by the fixed orifice metering device (Carrier Acutrol) on this system. If the high pressure increases, there will be more gas forced through the metering device at a higher pressure causing the low pressure side of the system to rise in pressure as well. On the condenser graph on previous page circuit 2 is operating at a higher condensing temperature than circuit 1. This higher temperature comes from a higher pressure. The evaporator shows evidence of this as well circuit 2 has a higher evaporation temperature than circuit 1. This higher evaporation temperature comes from a higher suction pressure that is caused by a higher condensing pressure. The saturated suction pressure of circuit 2 is higher than circuit 1 because the condensing temperature and pressure of circuit 2 are very high. 9 P a g e

10 Charging Chart GE-15 Circuit 1 and 2 Suction line temperature = 46 R-22 refrigerant at 65# psig = = 9 super Suction line temperature = 54 R-22 refrigerant at 73# psig = = 11 superheat This is a Carrier Charging Chart. All Carrier units have this sticker mounted on them to help a technician make sure there is a correct refrigerant charge. The red is plotted on the chart from test data. The green represents where the plot should be. Circuit 1 chart shows refrigerant should be added to the circuit. Circuit 2 shows that refrigerant should be removed from the circuit. They also indicate that the superheat on circuit 1 should be 9 F and circuit 2 should be 11 F at these temperatures and pressures. It is not recommended that the unit run at this superheat. If refrigerant were to be added and removed the pressures and temperatures will change causing the superheat to change. 10 P a g e

11 Conclusion Superheat The superheat of circuit 1 is dangerously low and will be causing lubrication issues in this compressor every time it runs. These lubrication issues will damage the compressor and shorten its life expectancy. Condenser The difference between condenser air inlet temperature and condensing temperature are very high. This would indicate poor heat transfer at the condenser coil between the air and the refrigerant on circuit 1. However, Circuit 2 is much worse and both circuits are using the same condenser. There were no visual conditions of the condenser to suggest either circuit would get more or less air flow or heat transfer than the other. Summary The condenser coil is where heat is removed from the conditioned space and released into the ambient conditions. The better the heat transfer is at the coil the more efficient the unit is. As the heat transfer drops at the coil the unit becomes less efficient. GE-15 had 69 F air onto the evaporator and 74 F air onto the condenser with 113 F and 132 F condensing temperatures. This was a low load situation and the unit should not have produced condensing temperatures this high under these conditions. With these problems this unit would be extremely inefficient at higher load conditions and may cause damage or compressor failure. It is evident this condenser coil has serious problems transferring heat. Efficiency would be increased if this condenser coil was replaced. Circuit 2 seems to have more problems than just poor heat transfer between the refrigerant and the air at the condenser coil. The manufacturers charging chart suggests removing refrigerant from this circuit. It is a good recommendation, but with a condensing temperature this high, it would be expected that the subcooling would be much higher than it is. It is possible for non-condensables in the refrigerant circuit to cause this. The ClimaCheck is a great tool for detecting non-condensables, such as air or nitrogen in a refrigeration circuit, even in very small amounts. Typically, the isentropic efficiency would rise to a fictitious range and conversions such as superheat and subcool could show impossible negative readings. The superheat dropped to 0 F, which is the lowest level possible and stayed right there without going below 0 F. The isentropic efficiency was in an expected range. This is a good indication there are not any non-condensables in the system. The compressor of circuit 2 is in danger of failure running the way it is now. It would be much more cost effective to take action now than wait for it to fail, costing the owner replacement cost, down time, and occupant discomfort. Even with all of the problems circuit 2 has shown, it is only running about 2.5% less efficient than circuit 1. Circuit 1 averaged a 12.9 EER and Circuit 2 averaged a 12.6 EER. Both of these EER levels should be higher in these conditions. The issue with the condenser is the reason for the lower than expected EER levels. The ClimaCheck only measures the actual performance of the unit in real time at the conditions during the test. It is hard to estimate what the unit should run at under different conditions or with no problems opposed to problems. On the next page, there are illustrations to help show performance at different conditions. The three illustrations below show the compressor data for the compressors in GE-15. This is nominal data supplied by Copeland software, the manufacturer of the compressors in GE-15. The top illustration shows the temperatures and pressures of circuit 1 and the expected performance of the compressor with a EER. The second illustration shows the expected performance at these conditions with a EER. If this unit was operating at this EER, it would be a 20% increase in performance at these conditions. The second chart shows the temperatures and pressures circuit 2 running at and the expected performance of the compressor with a EER. The bottom chart shows temperatures and pressures that would be expected of this unit under these conditions, if there were no issues. It shows an EER of 14.93, this is a 43% increase in performance at these conditions. 11 P a g e

12 Example: nominal running performance at these conditions Circuit 1 Example: nominal running performance at these conditions Circuit 2 12 P a g e

13 Example: expected nominal performance at these conditions Circuits 1 and 2 13 P a g e

Public Services Building 155 N First Avenue Hillsboro, OR March 2012

Public Services Building 155 N First Avenue Hillsboro, OR March 2012 Public Services Building 155 N First Avenue Hillsboro, OR 97124 March 2012 Tests and report done by: Joel Klobas Emerging Energy Solutions Technical Director joelk@eeswest.com Contents Introduction...

More information

Otherwise, you can continue reading the file on the following pages.

Otherwise, you can continue reading the file on the following pages. If you d like to be able to print this file out to study off-line or use on the job, a printable version is available for an administrative fee of $3.97 USD. To download the unlocked file, click here.

More information

Refrigeration System Report March 2017

Refrigeration System Report March 2017 New Seasons Market 7703 SW Nyberg Street Tualatin, OR 97062 Refrigeration System Report March 2017 Commissioning done by: N/A Manufacturer: Contractor: Report published by: Roupen Ohannessian, ClimaCheck

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

Checking the Charge on a Heat Pump in the Winter

Checking the Charge on a Heat Pump in the Winter Checking the Charge on a Heat Pump in the Winter When you ask many people nowadays how to check the charge on a heat pump during low outdoor temps they will say that you need to weigh in and weigh out

More information

A Comparison Between Refrigerants Used In Air Conditioning

A Comparison Between Refrigerants Used In Air Conditioning A Comparison Between Refrigerants Used In Air Conditioning Derya Özkan, Özden Agra and Özlem Çetin University of Yildiz Technical University, Turkey Corresponding email: tumer@yildiz.edu.tr SUMMARY It

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.

More information

R32 Compressor for Air conditioning and Refrigeration applications in China

R32 Compressor for Air conditioning and Refrigeration applications in China Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua

More information

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During

More information

Low GWP Refrigerants for Air Conditioning Applications

Low GWP Refrigerants for Air Conditioning Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems . Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems PRESENTED BY NIRAJ MISTRY aircon@stroma.com Cooling Load The Refrigeration Load Cooling load on refrigeration system

More information

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

SERVICE ASSISTANT OVERVIEW FDSI Online Training

SERVICE ASSISTANT OVERVIEW FDSI Online Training Author: Dale T. Rossi Online Editor: Zachary Williams SERVICE ASSISTANT OVERVIEW FDSI Online Training May 5, 2009 Table Service Assistant Description... 2 Installing the Main Unit... 3 Ambient Temperature...

More information

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A900-22007), 120/208/240/1/60, R404A, LT/MT APPS Introduction The superheat controller is designed

More information

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING UNIT OBJECTIVES After studying this unit, the reader should be able to Describe how refrigerant is charged into systems in

More information

10/4/2013. The Changing State of Refrigerants

10/4/2013. The Changing State of Refrigerants 10/4/2013 The Changing State of Refrigerants Refrigerant Chemistry CFC = Chlorofluorocarbon Rapid phase-out Stopped U.S. production in 1996 R-11, R-12, R-113, R-114, R-500, R-502 HCFC = Hydrochlorofluorocarbon

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7

More information

Superheat charging curves for technicians

Superheat charging curves for technicians This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block.

More information

RTP Technical Bulletin

RTP Technical Bulletin RTP Technical Bulletin Category: REFRIGERATION REGISTERED TECHNICIANS PROGRAM Volume 1 Bulletin 2 the information contained in this bulletin contains some important c o n c e p t s regarding pressure/

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

COMPARATIVE STUDY OF NEW ECOLOGICAL GASES

COMPARATIVE STUDY OF NEW ECOLOGICAL GASES 2017 COMPARATIVE STUDY OF NEW ECOLOGICAL GASES JOSE LUIS URIBE-ECHEBARRIA JAVIER MARTINEZ DE ILARDUYA ANARTZ ITURRIOTZ LEIRE LONBIDE INTXAUSTI FRINSA S.L. 1. INTRODUCTION The purpose of the study is to

More information

Air Cooled Packaged Systems AIRAH Back to Basics

Air Cooled Packaged Systems AIRAH Back to Basics Air Cooled Packaged Systems AIRAH Back to Basics What s changed? New Refrigerants R410a MEPS EER / AEER / SEER Manufacturing Technologies Research, Development and Testing New technologies, controls, reliability

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Marco Alexandre Onofre Dias This paper presents a model that was implemented

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

c Dr. Md. Zahurul Haq (BUET) Refrigeration Cycles ME 6101 (2013) 2 / 25 T270 COP R = Q L

c Dr. Md. Zahurul Haq (BUET) Refrigeration Cycles ME 6101 (2013) 2 / 25 T270 COP R = Q L Refrigeration Cycles Dr. Md. Zahurul Haq Professor Department of Mechanical Engineering Bangladesh University of Engineering & Technology (BUET) Dhaka-1000, Bangladesh zahurul@me.buet.ac.bd http://teacher.buet.ac.bd/zahurul/

More information

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System

More information

Refrigeration Cycles. Refrigerators, Air-conditioners & Heat Pumps. Refrigeration Capacity/Performance. Dr. Md. Zahurul Haq

Refrigeration Cycles. Refrigerators, Air-conditioners & Heat Pumps. Refrigeration Capacity/Performance. Dr. Md. Zahurul Haq Refrigeration Cycles Dr. Md. Zahurul Haq Professor Department of Mechanical Engineering Bangladesh University of Engineering & Technology (BUET) Dhaka-1000, Bangladesh zahurul@me.buet.ac.bd http://teacher.buet.ac.bd/zahurul/

More information

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration

More information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient

More information

Evaporative Cooling in a Hot-Dry Climate

Evaporative Cooling in a Hot-Dry Climate Evaporative Cooling in a Hot-Dry Climate David Springer Davis Energy Group SWEEP Workshop July 10, 2007 Sponsors: Clarum Homes California Energy Commission U.S.Department of Energy Issues for Discussion

More information

T270 COP R = Q L. c Dr. Md. Zahurul Haq (BUET) Refrigeration Cycles ME 6101 (2017) 2 / 23 T354

T270 COP R = Q L. c Dr. Md. Zahurul Haq (BUET) Refrigeration Cycles ME 6101 (2017) 2 / 23 T354 Refrigerators, Air-conditioners & Heat Pumps Refrigeration Cycles Dr. Md. Zahurul Haq Professor Department of Mechanical Engineering Bangladesh University of Engineering & Technology (BUET) Dhaka-1000,

More information

A Treatise on Liquid Subcooling

A Treatise on Liquid Subcooling A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance

More information

5. ASSESSMENT RECOMMENDATIONS

5. ASSESSMENT RECOMMENDATIONS 5. ASSESSMENT RECOMMENDATIONS AR No. 1 Reduce Discharge Pressure Recommended Action Reduce the minimum condensing temperatures on your warehouse refrigeration systems from 110 F to 60 F. In order to reduce

More information

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM 551B 581B DuraPac Plus Series Sizes 036-150 3to12 1 / 2 Tons Cancels: New PAD 551B.36.2 10/1/04 CONTENTS Page INTRODUCTION.................................

More information

(Refer Slide Time: 00:00:40 min)

(Refer Slide Time: 00:00:40 min) Refrigeration and Air Conditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 10 Vapour Compression Refrigeration Systems (Refer Slide

More information

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)

More information

Energy Performance of Low Charge NH3 Systems in Practice. Stefan S. Jensen

Energy Performance of Low Charge NH3 Systems in Practice. Stefan S. Jensen Energy Performance of Low Charge NH3 Systems in Practice Stefan S. Jensen Introduction Central type, dual compression stage, ammonia vapour compression systems. Main Design Features: Reciprocating Compressors

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

Case 8 Basic Performance of Screw Compressor

Case 8 Basic Performance of Screw Compressor Case 8 Basic Performance of Screw Compressor Copy Right By: Thomas T.S. Wan ) June 24, 2010 All Rights Reserved Case Background: The basic rating and performance given by a compressor manufacturer is usually

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou Condensers ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM A. Hadawey, Y. T. Ge, S. A. Tassou 4 7 8 5 3 2 6 1 Produced by: The Centre for Energy and Built Environment

More information

THE FIVE W s SYSTEMES LMP MECHANICAL SUB-COOLING. I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS

THE FIVE W s SYSTEMES LMP MECHANICAL SUB-COOLING. I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS THE FIVE W s WHO: WHAT: WHERE: WHY: SYSTEMES LMP MECHANICAL SUB-COOLING I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS WHEN: TIME LAPSE May 2013 to May 2014 Système LMP`s

More information

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012 SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

MASS. MARITIME ACADEMY

MASS. MARITIME ACADEMY MASS. MARITIME ACADEMY REFRIGERATION LAB OUTLINE Rev.3 Fall 2015 Table of Content Page Lab #1: Introduction to refrigeration system components, tools and procedures 1 Lab #2: Familiarization, operation,

More information

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system. Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs the unwanted heat, this raises the refrigerant

More information

2016 Annual Conference

2016 Annual Conference 2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance

More information

Understanding Head Pressure Control. Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration

Understanding Head Pressure Control. Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration Understanding Head Pressure Control Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration WE WILL LOOK AT: 1. Why We Need Head Pressure Control? 2. How Do We Control Head Pressure - Methods?

More information

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Figure 1: Schematic of internal heat exchanger vapor-injection cycle Vapor-injection technique Development Guideline 1. Introduction This guideline shows the advantage and characteristics of Mitsubishi vapor injected-scroll compressor. The vapor injected-scroll compressor

More information

Technical Bulletin (TB-0037)

Technical Bulletin (TB-0037) Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant

More information

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment HVAC&R Research ISSN: 1078-9669 (Print) 1938-5587 (Online) Journal homepage: http://www.tandfonline.com/loi/uhvc20 Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor-

More information

Study Final Report. Priority Cool Refrigerant Study

Study Final Report. Priority Cool Refrigerant Study Refrigerant Study Study Final Report Prepared for: Greenway Solutions Company, Inc. 120 Bethpage Road, Suite 304 Hicksville, New York 11801 Prepared by: WSP Flack + Kurtz 512 Seventh Avenue New York, NY

More information

NO: 9-16 DATE: 2/11/16 EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -EMERSON TM TECHNICAL SPECIALISTS -BRANCH PERSONNEL

NO: 9-16 DATE: 2/11/16 EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -EMERSON TM TECHNICAL SPECIALISTS -BRANCH PERSONNEL NO: 9-16 DATE: 2/11/16 TO: EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -EMERSON TM TECHNICAL SPECIALISTS -BRANCH PERSONNEL SUBJECT: Procedure for Changing CS Compressor to Copeland

More information

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL BY DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL In the September/October 2005 issue of HPAC Magazine, the case was made for reducing head pressure to increase compressor efficiency, thereby lowering its

More information

A/C Cooling Load calculation and measurement

A/C Cooling Load calculation and measurement Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying

More information

HVAC/R Refrigerant Cycle Basics

HVAC/R Refrigerant Cycle Basics HVAC/R Refrigerant Cycle Basics This is a basic overview of the refrigeration circuit and how it works. It isn t a COMPLETE description by any means, but it is designed to assist a new technician or HVAC/R

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Comparative Performance of HFO Blends in a Condenser

Comparative Performance of HFO Blends in a Condenser The knowledge hub for refrigeration, air conditioning and heat pumps Nick Atkins MInstR Simon Jones MInstR Gary Bell Comparative Performance of HFO Blends in a Condenser Paper 2 research laboratory tests

More information

REFRIGERANT CHANGEOVER

REFRIGERANT CHANGEOVER Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants

More information

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton

More information

Presented By: John Dolan, P.E.

Presented By: John Dolan, P.E. Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience jdolan@thermohvac.com

More information

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)

More information

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications Commercial CO2 Refrigeration Systems Guide for Subcritical and Transcritical CO2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section 1.

More information

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems . Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems PRESENTED BY NIRAJ MISTRY aircon@stroma.com Cooling Load The Refrigeration Load Cooling load on refrigeration system

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the MYSTICOOL Max Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study www.amec.com Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study DISCUSSION TOPICS Brief Overview of Air-Cooled and Evaporative-Cooled Condenser Technologies Pros and Cons Scope and Results

More information

DIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.)

DIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.) : new refrigerant replacement for R-22 with low Global Warming Potential (GWP). Performance comparison with six existing refrigerants. CARRIED OUT BY DIRA S.L. (Desenvolupament, Investigació i Recerca

More information

500 EX Fusion Compressor Series

500 EX Fusion Compressor Series 500 EX Fusion Compressor Series R404A M/T R404A L/T Capacity RANGE 13.8kW - 20.4kW 7.7kW -11.2kW Copeland Fusion Semi-Hermetic Horizontal Scroll Compressors For Medium and Low Temperature Applications

More information

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET

More information

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the XSTREAM Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor? Code No: RR410305 Set No. 1 IV B.Tech I Semester Regular Examinations, November 2006 REFRIGERATION & AIR CONDITIONING (Mechanical Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions All

More information

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE Service Facts Customer Property: Contains wiring and service information. Please retain. WC*240-SF-1H Library Service Literature Product Section Unitary Product Package Air Conditioner Model WC* Literature

More information

Refrigerant changeover guidelines

Refrigerant changeover guidelines Refrigerant changeover guidelines HCFC R-22 to HFC R-407A/F, R-448A or R-449A for medium and low temperature applications HCFC R-22 to HFC R-407C for high, medium and low temperature applications HCFC

More information

Pack Calculation Pro. Users guide. Version Morten Juel Skovrup

Pack Calculation Pro. Users guide. Version Morten Juel Skovrup Pack Calculation Pro Users guide Version 4.10 Morten Juel Skovrup 1 Contents 2 Introduction... 5 3 Example... 7 3.1 Setup systems... 7 3.1.1 Selecting compressors... 9 3.1.2 Suction side... 12 3.1.3 Discharge

More information

Applications of Thermodynamics: Heat Pumps and Refrigerators

Applications of Thermodynamics: Heat Pumps and Refrigerators Applications of Thermodynamics: Heat Pumps and Refrigerators Bởi: OpenStaxCollege Almost every home contains a refrigerator. Most people don t realize they are also sharing their homes with a heat pump.

More information

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System Numerical Study on Improvement of COP of Vapour Compression Refrigeration System Sanath Kumar K H 1, Arun Kumara K S 2, Nissar Ahmed 3 Assistant Professor, Department of Mechanical Engineering, VVIT, Bangalore,

More information

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc. The Refrigeration Cycle Jerry Cohen President Jacco & Assoc. Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative

More information

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Copy Right By: Thomas T.S. Wan ) Dec. 28, 2012 All Rights Reserved Case Background: Ammonia is one of the important elements to

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

CO2 TRANSCRITICAL BOOSTER SYSTEMS

CO2 TRANSCRITICAL BOOSTER SYSTEMS CO2 TRANSCRITICAL BOOSTER SYSTEMS William Katz Sr. Technical Writer Hillphoenix 2016 Gees Mill Road Conyers, GA 30013 Tel: 678-613-9364 Email: william.katz@hillphoenix.com Refrigeration systems for supermarkets

More information

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled

More information

USING THE P-T CARD AS A SERVICE TOOL

USING THE P-T CARD AS A SERVICE TOOL Service Application Manual SAM Chapter 620-115 Section 2 USING THE P-T CARD AS A SERVICE TOOL Reprinted with permission from Sporlan Division, Parker Hannifin Corporation INTRODUCTION Manufacturers of

More information

Performance of an Improved Household Refrigerator/Freezer

Performance of an Improved Household Refrigerator/Freezer Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical

More information

Study of R161 Refrigerant for Residential Airconditioning

Study of R161 Refrigerant for Residential Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen

More information

Workshop on AFDD for RTUs Moving from R&D to Commercialization July 13, Introduction

Workshop on AFDD for RTUs Moving from R&D to Commercialization July 13, Introduction Workshop on AFDD for RTUs Moving from R&D to Commercialization July 13, 2014 Introduction Jim Braun Ray W. Herrick Laboratories Purdue University West Lafayette, IN 47907 Slide 1 Acknowledgement This workshop

More information

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning ISBN 978-93-84468-94-1 International Conference on Education, Business and Management (ICEBM-2017) Bali (Indonesia) Jan. 8-9, 2017 An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery

More information

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment. Small Commercial Business Energy Audits Recognizing and addressing the special requirements of the small business market segment. Class 7 Class 7: Refrigeration Fundamentals The Vapor-compression cycle

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,

More information

Carwin COMPRESSOR SELECTION PROGRAM

Carwin COMPRESSOR SELECTION PROGRAM Carwin COMPRESSOR SELECTION PROGRAM IMPORTANT! READ CAREFULLY BEFORE USING By using this disk covering a software program entitled CARLYLE SELECTION PROGRAM WINDOWS (Software), you indicate your acceptance

More information