APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps

Size: px
Start display at page:

Download "APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps"

Transcription

1 APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual Suggestions for the hydraulic integration of chillers and heat pumps

2 Table of Contents From practical experience, for your practical needs Chiller/heat pump with single-circuit buffer tank and one consumer... 4 Chiller/heat pump with plate heat exchanger for system separation, single-circuit buffer tank and one consumer... 9 Chiller/heat pump with dual circuit-buffer tank and extensive system hydraulics Chilled/warm water generator with plate heat exchanger for the system separation, dual circuit buffer tank and extensive system hydraulics Chiller/heat pump with single-circuit buffer tank and several different consumers Chiller/heat pump with single-circuit buffer tank and several consumers of the same power rating Production of chilled/warm water with plate heat exchanger for system separation and secondary-sided inverter pump Sequence control gear of chiller/heat pump with dual circuit buffer tank and extensive system hydraulics Chiller, water-cooled plant, integration of a heat-rejection system Chiller, water-cooled plant, integration in the heat-rejection system with cold weather start control for all-year operation Chiller, water-cooled plant, with heat-rejection system and free cooling function Chiller, air-cooled, integration of desuperheater for heat recovery Chiller, water-cooled plant, with heat recovery and heat-rejection system Cold/warm water generator with variable-speed pump, single-circuit buffer tank and 2-way valves (VPS A-Control) Cold-/warm water generators with variable speed pumps in primarily and secondary circuits (VPS D-Control) Cold/warm water generator with variable-speed pump and single-circuit buffer tank with 3-way valves (VPS A-Control) Legend PR GB Subject to modifications R2-02/2017

3 _0 From practical experience, for your practical needs This is the basic idea behind the creation of this manual. Engineers and technicians should be optimally supported in their work when it concerns system integration of chillers or heat pumps. The following pages outline and explain the most common hydraulic circuits for integrating these units in various application areas. This document presents recommendations and useful notices, which however do not replace individual system planning and configuration of hydraulic components. COPYRIGHT NOTE The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design. PR GB Subject to modifications R2-02/2017 3

4 01 Chiller/heat pump with single-circuit buffer tank and one consumer Area of application Generation of cold or warm water for comfort air conditioning or for process applications. The deployment of a single-circuit buffer tank system is a simple consumer network condition, which however requires the satisfaction of important prerequisites. Unit Buffer tank Consumers Functional principle of the hydraulics For released units, the medium flows from the buffer tank to the water pump in the unit. The medium is chilled or warmed up for the required load reduction. The chilled/warm water now flows to the consumer and is then warmed up or chilled down again there. The 3-way valve in the position A AB is fully opened at maximum capacity reduction. The bypass line B is closed. If the load reduction of the consumer drops, then the bypass line B is opened. This ensures a constant water/volume flow across the unit, regardless of the load reduction. The unit requires a constant water/volume flow for trouble-free operation. Therefore variable speed pumps must not be used. If the bypass line B is completely opened because of the lack of load reduction, water no longer circulates to the consumer. The water temperature approaches the unit setpoint and the compressors gradually switch off. The water pump continuously remains in operation in order to record the current water temperatures in the system. If the load reduction increases again, the unit switches on the individual compressors again depending on how far the temperature deviates from the setpoint. It is important for the regulation of the unit that a constant water quantity is transported over the evaporator / condenser at all times. Variable water quantities lead to discontinuous heat transfers and thus to undefined fluctuating ratings of the heat exchanger. This can lead to operational malfunctions, which are recorded with the unit controller. 4 PR GB Subject to modifications R2-02/2017

5 The possible fault signals are: Insufficient evaporating pressure Low pressure Frost protection Flow switch Low water flow in the plant 01 For this reason, no 2-way valves can be employed for the depicted hydraulic system! Important hydraulic components Single circuit buffer tank: Water filter: Paddle-type flow switch: Expansion tank: Water system pressure switch: The buffer tank primarily serves to increase the water volume in the hydraulic system in order to ensure a minimum runtime of the compressors and to prevent unnecessarily frequent on and off switching of the compressors. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. The unit control system processes the falling system pressure, stops the unit and the pump and prevents expensive plant failures. PR GB Subject to modifications R2-02/2017 5

6 01 Regulating valves: Ventilation: Charging and draining: In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. External enabling device: Pump enabling: Alarm signal: Control and regulation The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity of the unit and the associated water temperature may only be controlled with the internal unit controls. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After successful release, the unit switches the pump on and checks the current with an internal differential pressure switch and additionally with a paddle-type flow switch mounted on-site. As soon as a stable water flow is ensured, the water temperature is measured and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill the water to the setpoint. After reaching the setpoint, the first compressor switches off. Additional compressors are switched off or on depending on the temperature change. The water pumps remain in continuous operation so that the plant can perform readings of the current water temperature in the system. After switching the unit off with the remote ON/OFF contact, the compressors are driven down and then switched off. The pump is switched off after the expiration of a programmed delay period. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. If the internal pump ON/OFF contact is used, the unit can embed the pumps into the internal control system. The required pump leading and overrun times, as well as pump switch-off when the unit is turned off, are taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. 6 PR GB Subject to modifications R2-02/2017

7 Frost protection 01 Remember: If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. If glycol is not used as an antifreeze agent, note that you must use trace heating for the pipework and other components like expansion tank and pump that are subjected to outside temperatures below 5 C. For the water-based components in the unit, suitable options are available and provided by the factory. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. PR GB Subject to modifications R2-02/2017 7

8 01 Unit Buffer tank Consumers 8 PR GB Subject to modifications R2-02/2017

9 Chiller/heat pump with plate heat exchanger for system separation, single-circuit buffer tank and one consumer 02 Area of application Generation of cold or warm water for comfort air conditioning or for process applications. By using a single-circuit buffer tank system and a plate heat exchanger for system separation, a simple consumer network is conditioned, where however important prerequisites must be satisfied. Unit Plate heat exchanger Buffer tank Consumers Primary page Secondary side Functional principle of the hydraulics A plate heat exchanger creates a system separation in this hydraulic scheme in order to ensure freeze resistance for low outside temperatures without requiring the entire plant to be filled with a water-glycol mixture. The buffer tank is fitted in the secondary circuit of the plate heat exchanger in order to reduce the quantity of glycol required and thereby to reduce costs. In order to be able to make use of the entire system content, primary and secondary side, it is mandatory to always operate both pumps together. The entire plant can thereby be employed to guarantee the minimum system contents, especially because the buffet tank is in the secondary circuit. The minimum system content is required to guarantee the minimum runtime of the compressors. For the released unit, the medium flows to the secondary side of the buffer tank through the water pump in the secondary side of the plate heat exchanger of the system separation, which provides the primary side of the unit with the chilled/ heated water-glycol mixture. The medium is chilled or warmed up for the required load reduction. The chilled/warm water now flows to the consumer and is once again warmed up or cooled down. The 3-way valve in the position A AB is fully opened at maximum capacity reduction. The bypass line B is closed. If the load reduction of the consumer drops, then the bypass line B is opened. This ensures that, independent of the load reduction, a PR GB Subject to modifications R2-02/2017 9

10 02 constant water volume flow over the plate heat exchanger is present. Abrupt temperature variations on the primary part of the plate heat exchanger are thereby avoided. The unit requires a constant water/volume flow for trouble-free operation. Therefore, pumps that are speed-regulated during operation must not be used. If the bypass line B is completely opened because of the lack of load reduction, water no longer circulates to the consumer. The water temperature approaches the unit setpoint and the compressors gradually switch off. Both water pumps remain continuously in operation in order to record the current water temperatures in the system. If the load reduction increases again, the unit switches on the individual compressors again depending on how far the temperature deviates from the setpoint. It is important for the regulation of the unit that a constant water quantity is transported in the unit over the evaporator / condenser at all times. Variable water quantities lead to discontinuous heat transfers and thus to undefined fluctuating ratings of the heat exchanger. This can lead to operational malfunctions, which are recorded with the unit controller. The possible fault signals are: Insufficient evaporating pressure Low pressure Frost protection Flow switch Low water flow in the plant For this reason, no 2-way valves can be employed for the depicted hydraulic system! Important hydraulic components Single circuit buffer tank: Water filter: Paddle-type flow switch: Expansion tank: The buffer tank primarily serves to increase the water volume in the hydraulic system in order to ensure a minimum runtime of the compressors and to prevent unnecessarily frequent on and off switching of the compressors. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, 10 PR GB Subject to modifications R2-02/2017

11 Water system pressure switch: Regulating valves: Ventilation: Charging and draining: Plate Heat Exchangers: 02 this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. The unit control system processes the falling system pressure, stops the unit and the pump and prevents expensive plant failures. In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. The plate heat exchanger is used in a hydraulic plant as system separation. Reasons for the use of a plate heat exchanger could be: Separation between water-glycol circuit and water circuit Different temperature ranges and protection of a circuit against too high or too low temperatures Different pressure ranges and protection of a circuit against too high pressure Functioning as hydraulic switch Control and regulation External enabling device: The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity of the unit and the associated water temperature may only be controlled with the internal unit controls. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After successful release, the unit switches the pump on and checks the current with an internal differential pressure switch and additionally with a paddle-type flow switch mounted on-site. As soon as a stable water flow is ensured, the water temperature is measured and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill or heat the water to the setpoint. After reaching the setpoint, the first compressor switches off. Additional compressors are switched off or on depending on the temperature change. The water pumps remain in continuous operation so that the plant can perform readings of the current water temperature in the system. PR GB Subject to modifications R2-02/

12 02 Pump enabling: Alarm signal: After switching the unit off with the remote ON/OFF contact, the compressors are driven down and then switched off. The pump is switched off after the expiration of a programmed delay period. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. Both the water pump in the primary as well as in the secondary circuit must be operated with the enabling contact. Both pumps must always be simultaneously in operation. If the internal pump ON/OFF contact is used, the unit can embed the pumps into the internal control system. The required pump leading and overrun times, as well as pump switch-off when the unit is turned off, are taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. Frost protection If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30 % ethylene glycol. All components installed outdoors are, in this case, protected from freezing with a water-glycol mixture. Since a plate heat exchanger was employed as a system separation, filling the entire plant with anti-freeze is not required. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. 12 PR GB Subject to modifications R2-02/2017

13 02 Plate heat Unit exchanger Buffer tank Primary page Secondary side Consumers PR GB Subject to modifications R2-02/

14 03 Chiller/heat pump with dual circuit-buffer tank and extensive system hydraulics Area of application Generation of cold or warm water for comfort air conditioning or for process applications. The consumer network can take on complex forms with the deployment of a dual circuit buffer tank system, where however important prerequisites must be satisfied. Consumers Unit Buffer tank Plant circuit Consumer circuit Functional principle of the hydraulics For released units, the medium flows from the buffer tank to the water pump in the unit. The medium is chilled or warmed up for the required load reduction. The chilled/warm water now once again flows into the buffer tank. In case there are no requirements on chilled/warm water, the buffer tank guarantees the minimum runtime of the compressors. A constant water volume flow through the unit is guaranteed with the dual circuit buffer tank. The consumer circuit can be designed in any number of complex forms. This includes e.g.: Employment of speed-regulated pumps Employment of 2-way or 3-way valves Consumer circuits in different temperature ranges. Consumer circuits with various power capacities and water/volume flows No influence on the plant circuit can arise and a constant water quantity to the unit is guaranteed at all times. 14 PR GB Subject to modifications R2-02/2017

15 Important hydraulic components 03 Dual circuit buffer tank Water filter: Paddle-type flow switch: Expansion tank: Water system pressure switch: The dual circuit buffer tank fulfills the following functions: Assurance of the entire minimum system contents. The minimum runtimes of the compressors are observed and unnecessarily frequent compressor switch on and off is prevented. Hydraulic switch for the separation of plant and consumer circuits Guarantee of a thermal stratification within the container Standing buffer tanks must be used for this purpose. The chilled water supply in the plant circuit and the chilled water inlet in the consumer circuit must be attached at the lower connections of the buffer tank. In order to determine the minimum system content of the unit, only the volume of the buffer tank and the volume of the piping between device and buffer tank may be used. However, the volume of the consumer circuit is not taken into account. Dual circuit buffer tanks for chillers are characterized by their special design whose structure favors chilled-water stratification. Perforated perfusion pipes or perforated separation plates are used in the upper and lower area of the tank. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. The unit control system processes the falling system pressure, stops the unit and the pump and prevents expensive plant failures. PR GB Subject to modifications R2-02/

16 03 Regulating valves: Ventilation: Charging and draining: In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. External enabling device: Pump enabling: Alarm signal: Control and regulation The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity of the unit and the associated water temperature may only be controlled with the internal unit controls. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After successful release, the unit switches the pump on and checks the current with an internal differential pressure switch and additionally with a paddle-type flow switch mounted on-site. As soon as a stable water flow is ensured, the water temperature is measured and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill or heat the water to the setpoint. After reaching the setpoint, the first compressor switches off. Additional compressors are switched off or on depending on the temperature change. The water pumps remain in continuous operation so that the plant can perform readings of the current water temperature in the system. After switching the unit off with the remote ON/OFF contact, the compressors are driven down and then switched off. The pump is switched off after the expiration of a programmed delay period. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. If the internal pump ON/OFF contact is used, the unit can embed the pumps into the internal control system. The required pump leading and overrun times, as well as pump switch-off when the unit is turned off, are taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. 16 PR GB Subject to modifications R2-02/2017

17 Frost protection 03 Remember: If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. If glycol is not used as an antifreeze agent, note that you must use trace heating for the pipework and other components like expansion tank and pump that are subjected to outside temperatures below 5 C. For the water-based components in the unit, suitable options are available and provided by the factory. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. PR GB Subject to modifications R2-02/

18 03 Unit Buffer tank Plant circuit Consumer circuit Consumers 18 PR GB Subject to modifications R2-02/2017

19 04 Chilled/warm water generator with plate heat exchanger for the system separation, dual circuit buffer tank and extensive system hydraulics Area of application Generation of cold or warm water for comfort air conditioning or for process applications. Chilled/warm water generator with plate heat exchanger for the system separation, dual circuit buffer tank and extensive system hydraulics Consumers Unit Plate heat exchanger Buffer tank Primary page Secondary side Plant circuit Consumer circuit Functional principle of the hydraulics A plate heat exchanger creates a system separation in this hydraulic scheme in order to ensure freeze resistance for low outside temperatures without requiring the entire plant to be filled with a water-glycol mixture. The buffer tank is fitted in the secondary circuit of the plate heat exchanger in order to reduce the quantity of glycol required and thereby to reduce costs. In order to be able to employ the buffer tank correctly, it is absolutely required that the pumps on the primary and secondary side of the plate heat exchanger are always operated together. The dual circuit buffer tank can thereby be employed to guarantee the minimum system contents, especially because these are in the secondary circuit. The minimum system content is required to guarantee the minimum runtime of the compressors. For a released unit, the medium of the buffer tank flows through the water pump to the secondary side of the plate heat exchanger of the system separation, which provides the primary side of the unit with chilled/heated water glycol mixture. The medium is chilled or warmed up for the required load reduction. The chilled/warm water now once again flows into the buffer tank. In case there are no requirements on chilled/warm water, the buffer tank guarantees the minimum runtime of the compressors. PR GB Subject to modifications R2-02/

20 04 A constant water volume flow in the unit is guaranteed because of the plate heat exchanger for the system separation. The minimum system content is guaranteed by the parallel operation of the primary and secondary pump as well as the dual circuit buffer tank. The consumer circuit can be designed in any number of complex forms. This includes e.g.: Employment of speed-regulated pumps Employment of 2-way or 3-way valves Consumer circuits in different temperature ranges. Consumer circuits with various power capacities and water/volume flows No influence on the generator circuit can arise and a constant water quantity to the unit is guaranteed at all times. Important hydraulic components Dual circuit buffer tank Water filter: Paddle-type flow switch: Expansion tank: The dual circuit buffer tank fulfills the following functions: Assurance of the entire minimum system contents. The minimum runtimes of the compressors are observed and unnecessarily frequent compressor switch on and off is prevented. Hydraulic switch for the separation of plant and consumer circuits Guarantee of a thermal stratification within the container Standing buffer tanks must be used for this purpose. The chilled water supply in the plant circuit and the chilled water inlet in the consumer circuit must be attached at the lower connections of the buffer tank. In order to determine the minimum system content of the unit, in this case only the volume of the buffer tank, the plate heat exchanger, and the piping on the primary and secondary side may be employed. However, the volume of the consumer circuit is not taken into account. Dual circuit buffer tanks for chillers are characterized by their special design whose structure favors chilled-water stratification. Perforated perfusion pipes or perforated separation plates are used in the upper and lower area of the tank. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pres- 20 PR GB Subject to modifications R2-02/2017

21 Water system pressure switch: Regulating valves: Ventilation: Charging and draining: Plate Heat Exchangers: 04 sure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. The unit control system processes the falling system pressure, stops the unit and the pump and prevents expensive plant failures. In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. The plate heat exchanger is used in a hydraulic plant as system separation. Reasons for the use of a plate heat exchanger could be: Separation between water-glycol circuit and water circuit Different temperature ranges and protection of a circuit against too high or too low temperatures Different pressure ranges and protection of a circuit against too high pressure Functioning as hydraulic switch Control and regulation External enabling device: Pump enabling: The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity of the unit and the associated water temperature may only be controlled with the internal unit controls. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After successful release, the unit switches the pump on and checks the current with an internal differential pressure switch and additionally with a paddle-type flow switch mounted on-site. As soon as a stable water flow is ensured, the water temperature is measured and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill or heat the water to the setpoint. After reaching the setpoint, the first compressor switches off. Additional compressors are switched off or on depending on the temperature change. The water pumps remain in continuous operation so that the plant can perform readings of the current water temperature in the system. After switching the unit off with the remote ON/OFF contact, the compressors are driven down and then switched off. The pump is switched off after the expiration of a programmed delay period. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. Both the water pump in the primary as well as in the secondary circuit must be operated with the enabling contact. Both pumps must always be simultaneously in operation. PR GB Subject to modifications R2-02/

22 04 Alarm signal: If the internal pump ON/OFF contact is used, the unit can embed the pumps into the internal control system. The required pump leading and overrun times, as well as pump switch-off when the unit is turned off, are taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. Frost protection If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. All components installed outdoors are, in this case, protected from freezing with a water-glycol mixture. Since a plate heat exchanger was employed as a system separation, filling the entire plant with anti-freeze is not required. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (Data & Facts) of each unit include diagrams of the operating limits which must be taken into account. 22 PR GB Subject to modifications R2-02/2017

23 04 Unit Plate heat exchanger Primary page Secondary side Consumers Buffer tank Plant circuit Consumer circuit PR GB Subject to modifications R2-02/

24 05 Chiller/heat pump with single-circuit buffer tank and several different consumers Area of application Generation of cold or warm water for comfort air conditioning or for process applications. The deployment of a single-circuit buffer tank system is a simple consumer network condition, which however requires the satisfaction of important prerequisites. Geko Geko Geko Geko Geko Geko Geko Unit Buffer tank Functional principle of the hydraulics For released units, the medium flows from the buffer tank to the water pump in the unit. The medium is chilled or warmed up for the required load reduction. The chilled/warm water now flows through the consumer and is once again warmed up or cooled down. In this case, it can be about consumers of the same or unequal power consumption at identical water temperatures. The required water quantity must be adjusted individually for every consumer with balancing valves. The use of 3-way valves regulates the consumer's capacity and ensures a constant volume flow through the unit. For maximum capacity reduction, the 3-way valve is fully opened to the position A AB. The bypass line B is closed. If the load reduction of the consumer drops, then the bypass line B is opened. This ensures a constant water/volume flow across the unit, regardless of the load reduction. The unit requires a constant water/volume flow for trouble-free operation. Therefore variable speed pumps must not be used. If the bypass line B is completely opened because of the lack of load reduction, water no longer circulates to the consumer. The water temperature approaches the unit setpoint and the compressors gradually switch off. The water pump continuously remains in operation in order to record the current water temperatures in the system. If the load reduction increases again, the unit switches 24 PR GB Subject to modifications R2-02/2017

25 05 on the individual compressors again depending on how far the temperature deviates from the setpoint. Since a constant water volume flow is required for the fault-free operation of the unit, no variable-speed pumps may be used. It is important for the regulation of the unit that a constant water quantity is transported over the evaporator / condenser at all times. Variable water quantities lead to discontinuous heat transfers and thus to undefined fluctuating ratings of the heat exchanger. This can lead to operational malfunctions, which are recorded with the unit controller. The possible fault signals are: Insufficient evaporating pressure Low pressure Frost protection Flow switch Low water flow in the plant For this reason, no 2-way valves can be employed for the depicted hydraulic system! Important hydraulic components Single circuit buffer tank: Water filter: Paddle-type flow switch: Expansion tank: The buffer tank primarily serves to increase the water volume in the hydraulic system in order to ensure a minimum runtime of the compressors and to prevent unnecessarily frequent on and off switching of the compressors. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. PR GB Subject to modifications R2-02/

26 05 Water system pressure switch: Regulating valves: Ventilation: Charging and draining: If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. The unit control system processes the falling system pressure, stops the unit and the pump and prevents expensive plant failures. In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. Control and regulation External enabling device: Pump enabling: Alarm signal: The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity of the unit and the associated water temperature may only be controlled with the internal unit controls. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After successful release, the unit switches the pump on and checks the current with an internal differential pressure switch and additionally with a paddle-type flow switch mounted on-site. As soon as a stable water flow is ensured, the water temperature is measured and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill or heat the water to the setpoint. After reaching the setpoint, the first compressor switches off. Additional compressors are switched off or on depending on the temperature change. The water pumps remain in continuous operation so that the plant can perform readings of the current water temperature in the system. After switching the unit off with the remote ON/OFF contact, the compressors are driven down and then switched off. The pump is switched off after the expiration of a programmed delay period. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. If the internal pump ON/OFF contact is used, the unit can embed the pumps into the internal control system. The required pump leading and overrun times, as well as pump switch-off when the unit is turned off, are taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. 26 PR GB Subject to modifications R2-02/2017

27 Frost protection 05 Remember: If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. If glycol is not used as an antifreeze agent, note that you must use trace heating for the pipework and other components like expansion tank and pump that are subjected to outside temperatures below 5 C. For the water-based components in the unit, suitable options are available and provided by the factory. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (Data & Facts) of each unit include diagrams of the operating limits which must be taken into account. PR GB Subject to modifications R2-02/

28 05 Geko Geko Geko Geko Geko Geko Unit Buffer tank Geko 28 PR GB Subject to modifications R2-02/2017

29 Chiller/heat pump with single-circuit buffer tank and several consumers of the same power rating 06 Area of application Generation of cold or warm water for comfort air conditioning or for process applications. The deployment of a single-circuit buffer tank system is a simple consumer network condition, which however requires the satisfaction of important prerequisites. Geko Geko Geko Geko Geko Geko Geko Unit Buffer tank Functional principle of the hydraulics For released units, the medium flows from the buffer tank to the water pump in the unit. The medium is chilled or warmed up for the required load reduction. The chilled/warm water now flows through the consumer and is once again warmed up or cooled down. This applies for consumers with the same power rating, who in this case are connected according to the Tichelmann principle to ensure an almost equal water quantity at full load via every individual consumer. Balancing valves are not needed for this reason. The use of 3-way valves regulates the consumer's capacity and ensures a constant volume flow through the unit. Since a constant water volume flow is required for the fault-free operation of the unit, no variable-speed pumps may be used. For maximum capacity reduction, the 3- way valve is fully opened to the position A AB. The bypass line B is closed. If the load reduction of the consumer drops, then the bypass line B is opened. This ensures a constant water/volume flow across the unit, regardless of the load reduction. The unit requires a constant water/volume flow for trouble-free operation. Therefore variable speed pumps must not be used. If the bypass line B is completely opened because of the lack of load reduction, water no longer circulates to the consumer. The water temperature approaches the unit setpoint and the compressors gradually PR GB Subject to modifications R2-02/

30 06 switch off. The water pump continuously remains in operation in order to record the current water temperatures in the system. If the load reduction increases again, the unit switches on the individual compressors again depending on how far the temperature deviates from the setpoint. It is important for the regulation of the unit that a constant water quantity is transported over the evaporator / condenser at all times. Variable water quantities lead to discontinuous heat transfers and thus to undefined fluctuating ratings of the heat exchanger. This can lead to operational malfunctions, which are recorded with the unit controller. The possible fault signals are: Insufficient evaporating pressure Low pressure Frost protection Flow switch Low water flow in the plant For this reason, no 2-way valves can be employed for the depicted hydraulic system! Important hydraulic components Single circuit buffer tank: Water filter: Paddle-type flow switch: Expansion tank: Water system pressure switch: The buffer tank primarily serves to increase the water volume in the hydraulic system in order to ensure a minimum runtime of the compressors and to prevent unnecessarily frequent on and off switching of the compressors. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. The unit control system processes the falling system pressure, stops the unit and the pump and prevents expensive plant failures. 30 PR GB Subject to modifications R2-02/2017

31 Regulating valves: Ventilation: Charging and draining: 06 In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. Control and regulation External enabling device: Pump enabling: Alarm signal: The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity of the unit and the associated water temperature may only be controlled with the internal unit controls. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After successful release, the unit switches the pump on and checks the current with an internal differential pressure switch and additionally with a paddle-type flow switch mounted on-site. As soon as a stable water flow is ensured, the water temperature is measured and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill or heat the water to the setpoint. After reaching the setpoint, the first compressor switches off. Additional compressors are switched off or on depending on the temperature change. The water pumps remain in continuous operation so that the plant can perform readings of the current water temperature in the system. After switching the unit off with the remote ON/OFF contact, the compressors are driven down and then switched off. The pump is switched off after the expiration of a programmed delay period. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. If the internal pump ON/OFF contact is used, the unit can embed the pumps into the internal control system. The required pump leading and overrun times, as well as pump switch-off when the unit is turned off, are taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. PR GB Subject to modifications R2-02/

32 06 Frost protection Remember: If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. If glycol is not used as an antifreeze agent, note that you must use trace heating for the pipework and other components like expansion tank and pump that are subjected to outside temperatures below 5 C. For the water-based components in the unit, suitable options are available and provided by the factory. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. 32 PR GB Subject to modifications R2-02/2017

33 06 Geko Geko Geko Geko Geko Geko Unit Buffer tank Geko PR GB Subject to modifications R2-02/

34 07 Production of chilled/warm water with plate heat exchanger for system separation and secondary-sided inverter pump Area of application Generation of cold or warm water for comfort air conditioning or for process applications. The consumers are primarily equipped with straight-way valves for regulation. The secondary-sided consumer network therefore has a variable plant characteristics curve. To optimize energy consumption and flow pattern, a speed-regulated pump is used as a secondary pump. Geko Geko Geko Geko Geko Geko Geko Unit Buffer tank Plate Heat Exchanger Primary page Secondary side Functional principle of the hydraulics The secondary side is equipped with a speed-regulated pump. The unit requires a constant water flow-rate for trouble-free operation, therefore a system separation is created using a plate heat exchanger. Thus, the primary circuit has a constant water flow and the secondary circuit has a variable water flow. Due to the variable water flow in the secondary circuit, the necessary buffer tank must be arranged in the primary circuit to guarantee the minimum system contents. To ensure freeze resistance, the primary circuit is operated with a water-glycol mixture. For the released unit, pump P1 is in operation and provides the unit with a constant water-glycol mass flow. Via the plate heat exchanger, a heat exchange with the secondary-sided consumer network takes place, depending on the operation of the secondary-sided speed-regulated pump. The secondary-sided consumer network can be freely designed. By using a speedregulated pump, straight-way regulating valves can be used. The secondary pump can adjust the pump characteristics of a variable plant characteristics curve within the variable pump characteristics range and can set an optimal operating point. 34 PR GB Subject to modifications R2-02/2017

35 Important hydraulic components 07 Single circuit buffer tank: Water filter: Paddle-type flow switch: Expansion tank: Water system pressure switch: Regulating valves: Ventilation: The buffer tank primarily serves to increase the water volume in the hydraulic system in order to ensure a minimum runtime of the compressors and to prevent unnecessarily frequent on and off switching of the compressors. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. The unit control system processes the falling system pressure, stops the unit and the pump and prevents expensive plant failures. In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. PR GB Subject to modifications R2-02/

36 07 Charging and draining: Plate Heat Exchanger Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. The plate heat exchanger is used in a hydraulic plant as system separation. Reasons for the use of a plate heat exchanger could be: Separation between water-glycol circuit and water circuit Different temperature ranges and protection of a circuit against too high or too low temperatures Different pressure ranges and protection of a circuit against too high pressure Functioning as hydraulic switch External enabling device: Pump release: Error messaging: Control and regulation The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity of the unit and the associated water temperature may only be controlled with the internal unit controls. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After successful release, the unit switches the pump on and checks the current with an internal differential pressure switch and additionally with a paddle-type flow switch mounted on-site. As soon as a stable water flow is ensured, the water temperature is measured and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill or heat the water to the setpoint. After reaching the setpoint, the first compressor switches off. Additional compressors are switched off or on depending on the temperature change. The water pumps remain in continuous operation so that the plant can perform readings of the current water temperature in the system. After switching the unit off with the remote ON/OFF contact, the compressors are driven down and then switched off. The pump is switched off after the expiration of a programmed delay period. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. Both the water pump in the primary as well as in the secondary circuit can be operated with the enabling contact. Both pumps do not have to be in operation simultaneously. If the internal pump ON/OFF contact is employed, the unit can embed the pumps in the internal control system. The required pump leading and overrun times, as well as pump switch-off when the unit is turned off, are taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. 36 PR GB Subject to modifications R2-02/2017

37 Frost protection 07 If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. All components installed outdoors are, in this case, protected from freezing with a water-glycol mixture. Since a plate heat exchanger is employed as a system separation, filling the entire plant with anti-freeze is not required. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. PR GB Subject to modifications R2-02/

38 07 Geko Geko Geko Geko Geko Unit Buffer tank Plate Heat Exchanger Primary page Secondary side Geko Geko 38 PR GB Subject to modifications R2-02/2017

39 Sequence control gear of chiller/heat pump with dual circuit buffer tank and extensive system hydraulics 08 Area of application Generation of cold or warm water for comfort air conditioning or for process applications. The consumer network and the plant network can take on complex forms with the deployment of a dual circuit buffer tank system, where however important prerequisites must be satisfied. Sequencer Unit n Consumers Unit 2 Unit 1 Buffer tank Plant circuit Consumer circuit Functional principle of the hydraulics In this case, several units are switched in sequence in order to render the required total performance or to build a redundant system. The units can have various different power ratings. Every unit must have its own pump. For released units, the medium flows from the buffer tank to the water pump in the unit. The medium is chilled or warmed up for the required load reduction. The chilled/warm water now once again flows into the buffer tank. In case there are no requirements on chilled/warm water, the buffer tank guarantees the minimum runtime of the compressors. A constant water volume flow through the unit is guaranteed with the dual circuit buffer tank. The consumer circuit can be designed in any number of complex forms. This includes e.g.: Employment of speed-regulated pumps Employment of 2-way or 3-way valves Consumer circuits in different temperature ranges. Consumer circuits with various power capacities and water/volume flows No influence on the plant circuit can arise and a constant water quantity to the unit is guaranteed at all times. PR GB Subject to modifications R2-02/

40 08 Dual circuit buffer tank Water filter: Paddle-type flow switch: Expansion tank: Water system pressure switch: Important hydraulic components The dual circuit buffer tank fulfills the following functions: Assurance of the entire minimum system contents. The minimum runtimes of the compressors are observed and unnecessarily frequent compressor switch on and off is prevented. Hydraulic switch for the separation of plant and consumer circuits Guarantee of a thermal stratification within the container Standing buffer tanks must be used for this purpose. The chilled water supply in the plant circuit and the chilled water inlet in the consumer circuit must be attached at the lower connections of the buffer tank. In order to determine the minimum system content of the unit, only the volume of the buffer tank and the volume of the piping between device and buffer tank may be used. However, the volume of the consumer circuit is not taken into account. Dual circuit buffer tanks for chillers are characterized by their special design whose structure favors chilled-water stratification. Perforated perfusion pipes or perforated separation plates are used in the upper and lower area of the tank. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. The unit control system processes the falling system pressure, stops the unit and the pump and prevents expensive plant failures. 40 PR GB Subject to modifications R2-02/2017

41 Regulating valves: Ventilation: Non-return valves: Charging and draining: 08 In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. The deployment of several pumps may require the use of non-return valves in order to guarantee the correct flow direction of the heat transfer medium. This is the only way to guarantee the faultless functioning of the hydraulic system in all operating states. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. Control and regulation Sequential switching: External enabling of the unit: Pump enabling: In order to ensure an optimal management of the units relatively easily, a sequence control unit (sequencer) is available for such applications. Up to five units can be operated with this unit. The water inlet and water outlet temperature serves as the controlled variable that is measured in the common collecting pipe line of all units. In order for the sequencer to communicate with the units, every unit must be furnished with a Modbus interface. Now only the sequencer is accessed for all additional management activities. It is not necessary to control every unit individually. The unit must be enabled with the external floating contact of the sequencer. After being enabled with the remote ON/OFF contact of the sequencer, a data exchange with the connected units takes place with a bus signal. The unit with the fewest operating hours is given priority. As soon as a unit receives a command from the sequencer, the unit switches on the water pump assigned to it. After the expiration of the pump lead time, the first compressor of the unit goes into operation. Depending on the requirements and the associated setpoint deviation from the preset water temperature, additional compressors of the same unit or of the next unit go into operation, depending on the settings in the sequencer. If the compressor of the next unit is requested, it also switches its pump on beforehand. When the water temperature drops, the compressor and the pumps successively switch off. Only the pump of the last still running unit continues to operate in order to continually provide the temperature sensor of the sequencer with the current water temperature. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. If the internal pump ON/OFF contact is used, the unit can embed the pumps into the internal control system. The required pump leading and overrun times, as well as pump switch-off when the unit is turned off, are taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. PR GB Subject to modifications R2-02/

42 08 Alarm signal: A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. Frost protection Remember: If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. If glycol is not used as an antifreeze agent, note that you must use trace heating for the pipework and other components like expansion tank and pump that are subjected to outside temperatures below 5 C. For the water-based components in the unit, suitable options are available and provided by the factory. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. 42 PR GB Subject to modifications R2-02/2017

43 08 Unit n Unit 2 Unit 1 Sequencer Buffer tank Plant circuit Consumer circuit Consumers PR GB Subject to modifications R2-02/

44 09 Chiller, water-cooled plant, integration of a heat-rejection system Area of application Heat-rejection circuits for water-cooled units that are exclusively employed in the warm season for generating chilled water for comfort air conditioning or for process applications. Heat-rejection system Unit Chilled-water circuit Functional principle of the hydraulics When the unit is enabled, the medium flows to the water pump into the unit. At the required load reduction, the medium takes up the waste heat and flows on to the heat-rejection system where the heat is returned to the ambient air. Important hydraulic components Water filter: Expansion vessel: Ventilation: Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. 44 PR GB Subject to modifications R2-02/2017

45 Charging and draining: 09 Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. Control and regulation For water-cooled units, it is necessary to remove non-required heat from the cooling process and conduct it to the outdoor air. The operating limits must be observed for the reliable operation of the unit. The corresponding operating limits are provided in the technical documentation of the unit. Pump enabling: It is necessary to regulate the power of the dry cooler in order to observe the operating limits of the unit. It is recommended to regulate the speed of the fan motor depending on the dry cooler water discharge temperatures from the dry cooler. This ensures optimal heat-rejection water temperatures and constant operating conditions throughout the year. In order to achieve an optimal energy efficiency of the unit, the cooling water temperature must be kept as low as possible within the operating limits. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. If the internal pump ON/OFF contact is used, the unit can embed the pumps into the internal control system. The required pump leading and overrun times, as well as the pump switch-off when turning off the compressors, is taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. Frost protection In order to protect the heat-rejection circuit from frost, the employment of a water/ glycol mixture is definitely required. DencoHappel recommends to use at least 30% ethylene glycol. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. PR GB Subject to modifications R2-02/

46 09 Heat-rejection system Unit Chilled Water Circuit 46 PR GB Subject to modifications R2-02/2017

47 Chiller, water-cooled plant, integration in the heat-rejection system with cold weather start control for all-year operation 10 Area of application Heat-rejection circuit for water-cooled units that is employed throughout the year for the generation of chilled water for comfort air conditioning or for process applications. Heat-rejection system Unit Chilled-water circuit Functional principle of the hydraulics When the unit is enabled, the medium flows to the water pump into the unit. At the required load reduction, the medium takes up the waste heat and flows on to the heat-rejection system where the heat is returned to the ambient air. When the condensation pressure is too low, the 3-way valve conducts the medium once again into the condenser to increase the condensation pressure. Operation within the permissible condensation pressure is thereby guaranteed throughout the year. Important hydraulic components Water filter: Expansion vessel: Ventilation: Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. PR GB Subject to modifications R2-02/

48 10 Charging and draining: Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. Control and regulation Pump enabling: For water-cooled units, it is necessary to remove non-required heat from the cooling process and conduct it to the outdoor air. The operating limits must be observed for the reliable operation of the unit. The corresponding operating limits are provided in the technical documentation of the unit. The pump P2 is activated in parallel for requested compressor operation. As soon as the setpoint temperature is achieved and all compressors are disabled, the pump P2 is also switched off. All-year operating mode is required for this version. For this reason, the heat-rejection circuit is furnished with a cold-weather start control in the form of a 3-way valve (MV1). The 3-way valve is actuated by a 0-10 V signal directly from the unit, depending on the condensation pressure. This method ensures the observance of the minimum water temperature also at very low outdoor air temperatures. When the condensation pressure is too low, connection B of the 3-way valve (MV1) opens. The temperature of the inlet medium thereby increases in the condenser of the unit and the condensation pressure rises. The unit works within the range of application. As soon as the condensation pressure of the unit has reached the upper limit value, the connection B of the 3-way valve is once again slowly closed. When the heat-rejection circuit has achieved a required high temperature, as a rule the system is regulated only via the fan control of the heat-rejection system. The power of the heat-rejection system is additionally controlled by the speed of the fan motor, depending on the cooling water discharge temperatures from the dry cooler. This ensures optimal heat-rejection water temperatures and constant operating conditions throughout the year. In order to achieve an optimal energy efficiency of the unit, the cooling water temperature must be kept as low as possible within the operating limits. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. If the internal pump ON/OFF contact is used, the unit can embed the pumps into the internal control system. The required pump leading and overrun times, as well as the pump switch-off when turning off the compressors, is taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. 48 PR GB Subject to modifications R2-02/2017

49 Frost protection 10 In order to protect the heat-rejection circuit from frost, the employment of a water/ glycol mixture is definitely required. DencoHappel recommends to use at least 30% ethylene glycol. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. PR GB Subject to modifications R2-02/

50 10 Heat-rejection system Unit Chilled Water Circuit 50 PR GB Subject to modifications R2-02/2017

51 11 Chiller, water-cooled plant, with heat-rejection system and free cooling function Area of application Generation of chilled water for comfort air conditioning or process applications. In this case, the chilling unit is water-cooled and must be set up within a building. A heat-rejection system is employed for heat dissipation to achieve a free cooling function at low outside temperatures. This provides an energy-saving operation for yearround cooling demands. Heat-rejection Plate heat exchanger Primary page Secondary side Unit Heat-rejection circuit Producer circuit Consumer circuit Functional principle of the hydraulics The following operating modes are possible for this plant system: Unit operation (as water-cooled chiller) Free cooling operation Unit operation in connection with the pumps P1 and P2 When the unit is enabled, the pump P1 supplies the medium from the buffer tank in the unit. The medium is cooled down in the evaporator and then once again flows back into the buffer tank. If there is no chilled water requirement from the consumer, the buffer tank ensures a minimum runtime of the compressors. The dual circuit buffer tank maintains a constant water volume flow into the unit. The consumer circuit can be designed in any number of complex forms. This includes e.g.: Employment of speed-regulated pumps Employment of 2-way or 3-way valves Consumer circuits in different temperature ranges. PR GB Subject to modifications R2-02/

52 11 Consumer circuits with various power capacities and water/volume flows The plant circuit is not influenced and the water quantity through the unit is constant at all times. A water-glycol mixture must be employed as the medium in the heat-rejection circuit. When enabled, pump P2 supplies the medium through the condenser of the unit where the waste heat is taken up. At sufficiently high condensation pressure, the medium continues to be transported to the heat-rejection system in order for the waste heat to be conducted into the ambient air. The 3-way valve MV1 ensures the observance of the operating limits of the unit in the heat-rejection circuit. When the condensation pressure is too low, the 3-way valve MV1 conducts the medium via a bypass once again into the condenser. The temperature of the medium thereby continues to rise, which in turn also continues to increase the condensation pressure. Operation within the permissible condensation pressure is thereby guaranteed throughout the year. The 3-way valve MV1 is likewise necessary for the switchover from free cooling operation to unit operation, because the medium temperature lies below the application range of the unit. Without a 3-way valve, the unit would break down. Free cooling operation with a heat-rejection system in connection with the pumps P3 and P4 For free cooling operation, the pump P3 supplies the medium from the buffer tank through the secondary side of the plate heat exchanger. The medium is cooled down there and then once again flows back in the buffer tank. The pump P4 supplies the medium through the primary side of the plate heat exchanger where the heat is taken up from the cooling process. The heated medium continues to flow to the heat-rejection system in order to deliver the waste heat into the ambient air. Important hydraulic components Dual circuit buffer tank Water filter: The dual circuit buffer tank fulfills the following functions: Assurance of the entire minimum system contents. The minimum runtimes of the compressors are observed and unnecessarily frequent compressor switch on and off is prevented. Hydraulic switch for the separation of plant and consumer circuits Guarantee of a thermal stratification within the container Standing buffer tanks must be used for this purpose. The chilled water supply in the plant circuit and the chilled water inlet in the consumer circuit must be attached at the lower connections of the buffer tank. In order to determine the minimum system content of the unit, only the volume of the buffer tank and the volume of the piping between device and buffer tank may be used. However, the volume of the consumer circuit is not taken into account. Dual circuit buffer tanks for chillers are characterized by their special design whose structure favors chilled-water stratification. Perforated perfusion pipes or perforated separation plates are used in the upper and lower area of the tank. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. 52 PR GB Subject to modifications R2-02/2017

53 Paddle-type flow switch: Expansion tank: Water system pressure switch: Regulating valves: Ventilation: Non-return valves: Charging and draining: Plate Heat Exchangers: 11 The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. The unit control system processes the falling system pressure, stops the unit and the pump and prevents expensive plant failures. In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. The deployment of several pumps may require the use of non-return valves in order to guarantee the correct flow direction of the heat transfer medium. This is the only way to guarantee the faultless functioning of the hydraulic system in all operating states. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. The plate heat exchanger is used in a hydraulic plant as system separation. Reasons for the use of a plate heat exchanger could be: Separation between water-glycol circuit and water circuit Different temperature ranges and protection of a circuit against too high or too low temperatures Different pressure ranges and protection of a circuit against too high pressure Functioning as hydraulic switch PR GB Subject to modifications R2-02/

54 11 Control and regulation Unit operation in connection with the pumps P1 and P2 The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity of the unit and the associated water temperature may only be controlled with the internal unit controls. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After successful release, the unit switches the pump P1 on and checks the current with an internal differential pressure switch and additionally with a paddle-type flow switch mounted on-site. As soon as a stable water flow is ensured, the water temperature is measured and compared with the preset setpoint. Depending on setpoint deviation, the individual compressors are switched on or off. The pump P2 is activated in parallel for requested compressor operation. As soon as the setpoint temperature is achieved and all compressors are disabled, the pump P2 is also switched off. On continued active unit release, the water pump P1 continuously remains in operation to record the water temperatures in the system. The pumps P3 and P4 for the free cooling operation remain OFF. The heat removed from the cooling process in the heat-rejection circuit is conducted off into the outdoor air. The operating limits must be observed for the reliable operation of the unit. These are provided in the technical documentation of the unit. The heat-rejection circuit is furnished with a cold weather start control, in the form of a 3-way valve (MV1). The 3-way valve is actuated by a 0-10 V signal directly from the unit, depending on the condensation pressure. The water temperature in the heat-rejection circuit can thereby be ensured even after switchover between free cooling operation and unit operation. When the condensation pressure is too low, connection B of the 3-way valve (MV1) opens. The temperature of the inlet medium thereby increases in the condenser of the unit and the condensation pressure rises. The unit works within the range of application. As soon as the condensation pressure of the unit has reached the upper limit value, the connection B of the 3-way valve is once again slowly closed. When the heat-rejection circuit has achieved a required high temperature, as a rule the system is regulated only via the fan control of the heat-rejection system. The power of the heat-rejection system is additionally controlled by the speed of the fan motor, depending on the cooling water discharge temperatures from the heatrejection unit. This ensures optimal heat-rejection water temperatures and constant operating conditions throughout the year. In order to achieve an optimal energy efficiency of the unit, the cooling water temperature must be kept as low as possible within the operating limits. Pump release: After unit switch-off or switchover to the free cooling operation, the compressor is driven down and switched off. The pumps are switched off after the expiration of a programmed delay period. The on-site pump must be enabled with the pump ON/OFF contacts on the unit. In case the unit is not standardly supplied with pump ON/OFF contacts, then these can be provided as an option. If the internal pump ON/OFF contact is employed, the unit can embed the pumps in the internal control system. The required pump leading and overrun times, as well as pump switch-off when the unit is turned off, are taken into consideration by the internal regulation. Furthermore, additional energy-saving functions can be used. If the unit does not have an integrated water pump, no voltage supply is available at the unit for the water pumps installed on-site. The on-site pumps must therefore be provided with voltage. 54 PR GB Subject to modifications R2-02/2017

55 11 Free cooling operation with a heat-rejection system in connection with the pumps P3 and P4 An external control with the following requirements is needed for the management of free-cooling operation: Switch-off of unit operation Actuation of the pumps P3 and P4 Actuation of the fans of the heat-rejection unit with a changed setpoint Actuation of the 3-way valve MV2 The change-over point between free cooling operation and unit operation must be precisely determined on the basis of the system configuration, in order to guarantee the required cooling needs in free cooling operation. Frequently switching between unit operation and free cooling operation should be especially avoided in seasons with strongly fluctuating daily temperatures. The switching hysteresis must be set accordingly high. The delay period of the pump P1 must be taken into consideration for the switchover from unit operation to free cooling operation. After release of the pumps P3 and P4, the fans of the heat-rejection system must be controlled depending on the medium outlet temperature of the heat-rejection unit. Make sure that the chilled water temperature is controlled for free cooling operation, for instance between +4 to +10 C, whereas for unit operation the heat-rejection water temperature must be regulated between +25 to +30 C. In order to avoid frost damages at very low outside temperatures on the secondary side of the plate heat exchanger, the 3-way valve MV2 must be installed. The control must ensure that the primary side inlet temperatures in the plate heat exchanger do not fall below +2 C. Frost protection In order to protect the heat-rejection circuit from frost, the employment of a waterglycol mixture is definitely required. DencoHappel recommends to use at least 30% ethylene glycol. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (Data & Facts) of each unit include diagrams of the operating limits which must be taken into account. PR GB Subject to modifications R2-02/

56 11 Heat-rejection circuit Heat-rejection Plate heat exchanger Primary page Secondary side Unit Buffer tank Producer circuit Consumer circuit 56 PR GB Subject to modifications R2-02/2017

57 12 Chiller, air-cooled, integration of desuperheater for heat recovery Area of application If emphasis is also put on heat recovery in addition to the generation of chilled water, a unit with integrated desuperheater is a good opportunity to reduce operating costs for the production of warm water. Unit Chilled-water circuit Fresh water outlet Auxiliary heating Desuperheater circuit Combi storage tank E heating Fresh water inlet Functional principle of the hydraulics As soon as at least one compressor of the unit is running for the generation of chilled water, warm water can be produced for comfort or process applications via the desuperheater which is integrated in the unit. Consequently, the pump P1 should only be enabled with an activated compressor to avoid causing unnecessary energy costs. For the released pump P1, the medium flows through the water pump to the desuperheater of the unit. If the compressor is running, the medium is heated and can be made available for a heating process. For the desuperheater there are operating limits which must be maintained. The medium discharge temperature from the desuperheater must not fall below 30 C. In order to ensure this, a 3-way valve must be used. Important hydraulic components Water filter: Expansion tank: Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compen- PR GB Subject to modifications R2-02/

58 12 Regulating valves: Ventilation: Charging and draining: Combi storage tank: sates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. In order to ensure correct operating conditions for the entire plant, the pump and plant characteristics curve have to be matched with one another. If a pump with a variable pump characteristics curve is not available, regulating valves must be used. These valves are used for rebalancing the water pumps and consumers with each other. In plants with only one consumer, the water flow rate can be adjusted. Hydraulic rebalancing is used in plants with multiple consumers for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. The combi storage tank is a drinking water heater for which different heat sources can be used to heat up drinking water. Since the maximum attainable discharge temperature from the desuperheater does not exceed 60, only combi storage tanks with a large internal heat exchanger should be used to operate the system as efficiently as possible. To ensure drinking water hygiene, the relevant basic standards and national supplementary standards must be considered and strictly adhered to. Therefore, it must also be possible to thermally disinfect the combi storage tank through corresponding heating. For this purpose the following components can be used: Additional heat exchanger, heater supported Electric heating rod Control and regulation As soon as one of the compressors is running, the desuperheater can be used for heat recovery. The enabling of pump P1 should be performed via the operating status contact of the compressors and via an enabling contact of the heating request on-site. To ensure an operation within the operating limits, a 3-way valve is used which ensures a minimum discharge temperature of 30 C from the desuperheater. As alternative, an inverter controlled pump can be used which regulates the medium volume flow via the desuperheater in such a way that this requirement is observed. 58 PR GB Subject to modifications R2-02/2017

59 Frost protection 12 Remember: If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. If glycol is not used as an antifreeze agent, note that you must use trace heating for the pipework and other components like expansion tank and pump that are subjected to outside temperatures below 5 C. For the water-based components in the unit, suitable options are available and provided by the factory. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. PR GB Subject to modifications R2-02/

60 12 Unit Desuperheater circuit Chilled-water circuit Combi storage tank Fresh water inlet Auxiliary heating E heating Fresh water outlet 60 PR GB Subject to modifications R2-02/2017

61 13 Chiller, water-cooled plant, with heat recovery and heatrejection system Area of application Heat-rejection circuit with heat recovery for water-cooled units which are used for generating chilled or warm water for comfort air conditioning or for process applications. Heat-rejection system Unit Chilled-water circuit Plate Heat Exchanger Buffer tank Primary page Secondary side Functional principle of the hydraulics If a compressor is operating and produces waste heat, the pump P1 is also operating and transports the water-glycol mixture through the condenser of the unit where the waste heat is taken in. The heated water-glycol mixture is directed through the primary side of a plate heat exchanger. If necessary, the heat is transferred to a secondary sided water circuit and stored in a buffer tank. When the temperature of the water-glycol mixture is too low, the 3-way valve MV1 conducts the water-glycol mixture back into the condenser which causes another rise in temperature. If the allowable temperature of the water-glycol mixture is reached, the 3-way valve MV1 opens, adds chilled water-glycol mixture from the heat-rejection system and achieves an operation within the allowable operating limits. Important hydraulic components Water filter: Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. PR GB Subject to modifications R2-02/

62 13 Expansion tank: Ventilation: Charging and draining: Buffer tank of heat recovery Plate Heat Exchangers: The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. In the field of heat recovery it is recommended to use a buffer tank. Thus, transition periods in which heat is required during inactive heat recovery are well compensated. The plate heat exchanger is used in a hydraulic plant as system separation. Reasons for the use of a plate heat exchanger could be: Separation between water-glycol circuit and water circuit Different temperature ranges and protection of a circuit against too high or too low temperatures Different pressure ranges and protection of a circuit against too high pressure Functioning as hydraulic switch Control and regulation For water-cooled units, it is necessary to remove heat from the cooling process. The heat coming from the condenser of the unit can be used for other processes or can be given off to the outside air. The operating limits must be observed for the reliable operation of the unit. The corresponding operating limits are provided in the technical documentation of the unit. In this case, heat recovery is possible and therefore a distinction is made between: Cooling operation without heat recovery Cooling operation with heat recovery Cooling operation without heat recovery In this operating mode, heat recovery is not required. The unit is to be operated as efficiently as possible. In order to achieve this, the 3-way valve MV1 is to be regulated so that the lowest possible cooling water inlet temperature T1 is ensured in the condenser, within the operating limit. The pump P1 is activated in parallel for requested compressor operation. The 3-way valve MV1 controls the minimum medium inlet temperature T1 in the condenser, depending on the water volume flow. Thus, the minimum medium discharge temperature from the condenser can be ensured and optimal conditions for an economic compressor operation are created. If the medium inlet temperature T1 exceeds the minimum allowable temperature, the 3-way valve MV1 opens the connection A and uses the heat-rejection system to dissipate excessive heat. 62 PR GB Subject to modifications R2-02/2017

63 13 The power of the heat-rejection system is controlled by the speed of the fan motor, depending on the medium discharge temperature T4 from the heat-rejection unit. This ensures optimal heat-rejection water temperatures and constant operating conditions within the operating limits of the unit. The setpoint of the medium discharge temperature T4 corresponds to the minimum medium discharge temperature in the condenser, considering the water volume flow. Cooling operation with heat recovery In this operating mode, the heat recovery is required and the transmission of heat via the plate heat exchanger should be as efficient as possible. In order to achieve this, the 3-way valve MV1 is to be regulated so that the highest possible cooling water inlet temperature T1 is ensured in the condenser, within the operating limit. The pump P1 is activated in parallel for requested compressor operation. The 3-way valve MV1 controls the maximum medium inlet temperature T1 in the condenser, depending on the water volume flow. Therefore, optimal conditions for the heat recovery are created. If the water temperature T3, measured in the buffer tank, is lower than the medium temperature T2 coming from the condenser, pump P2 is activated and heat recovery takes place. The pump P2 is deactivated as soon as the water temperature T3 in the buffer tank exceeds the water/glycol temperature T2 coming from the condenser. This can be the case if the load request of the unit decreases. If the medium inlet temperature T1 exceeds the maximum allowable temperature, since the heat demand of the heat recovery is reduced, the 3-way valve MV1 opens the connection A and ensures a release of the non-required heat via the heat-rejection system. The power of the heat-rejection system is controlled by the speed of the fan motor, depending on the medium discharge temperature T4 from the heat-rejection unit. This ensures optimal heat-rejection water temperatures for heat recovery and constant operating conditions within the operating limits of the unit. The setpoint of the medium discharge temperature T4 corresponds in this operating mode with heat recovery to the maximum medium discharge temperature in the condenser, considering the water volume flow. PR GB Subject to modifications R2-02/

64 13 Frost protection In order to protect the heat-rejection circuit from frost, the employment of a water/ glycol mixture is definitely required. DencoHappel recommends to use at least 30% ethylene glycol. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. 64 PR GB Subject to modifications R2-02/2017

65 13 Heat-rejection system Chilled-water circuit Buffer tank Unit Plate Heat Exchanger Secondary side Primary page PR GB Subject to modifications R2-02/

66 14 Cold/warm water generator with variable-speed pump, singlecircuit buffer tank and 2-way valves (VPS A-Control) Area of application Generation of cold or hot water for comfort air conditioning or for process applications. The consumer network is easily formed and the consumers are equipped with 2-way valves. By the use of a variable-speed pump, the hydraulic system can be planned securely and in an energy saving way. p DP2 Unit Buffer tank P P P P T DP1 p P V1 FL T Advantages of a variable-speed pump By the deployment of variable-speed pumps with the correct hydraulic integration of the device, many crucial advantages result compared to pumps without speed control: The maximum rotational speed of the pump is set after pressure loss in the hydraulic network. The oversizing of a pump with fixed rotational speed and the associated high power consumption is precluded. Es is important to create an exact computation of the piping in order to adapt the speed-controlled pump to the plant characteristic curve and to ensure a correct control system. Costly and energy-destroying control valves can be done without. Constant control of the water outlet temperature in stationary operation High energy-saving potential at full and partial load operation as well as also in stand-by operation Longer pump lifetime Lower noise emission 66 PR GB Subject to modifications R2-02/2017

67 14 In full-load operation, an energy savings potential results, since the pump adapts the rotational speed to the actual demand and the pressure loss in the system. For pumps without speed control, the superfluous energy must be compensated by control valves. In partial-load mode, the reduced rotational speed lowers the air flow, since the maximum air flow is not required in partial-load mode. Depending on application case, the partial-load mode of the device with up to 97% of the time once again reflects the largest portion the operating time The water-air flow is reduced to 50% of the maximum volume of water. The system temperatures are still recorded reliably and energy saving. For systems without speed control, the pump also works during stand-by operation at maximum rotational speed and power consumption. The theoretical pump characteristics at speed change as follows: The pump feed rate behaves proportional to the change in pump speed. A reduction the rotational speed by 50% therefore leads to a halving of the pump feed rate. The pump lift behaves proportional to the square of the change of the pump speed. Therefore leads a reduction the rotational speed by 50% to a reduction of the pump lift by 25%. The power demand the pump behaves proportional to the third potential of the change of the pump speed. Therefore a reduction the rotational speed by 50% leads to a reduction the power consumption to 12.5%. The energy savings potential decisively depends on the following factors: Design and pressure losses of the hydraulic network Load acceptance of the consumer Operating and stand-by time of the device Design of the device for the required demand Functional principle of the hydraulics For released units, the medium flows from the buffer tank to the water pump in the unit. The medium is chilled or warmed up for the required load reduction. The cold/ hot water now flows over the consumers and is warmed or cooled down once again. In this case, it can be about consumers of the same or unequal power consumption at identical water temperatures. The required volume of water must be individually adjusted for every consumer with control valves, only so can the respective performance be ensured at full load. The power control of every consumer takes place by 2-way valves. At partial load, the changing pressure losses is compensated by the speed-controlled pump. For fault-free operation of the device, a minimum water-air flow through the heat exchanger of the device is required. To ensure this, the bypass valve V1 is employed. Is the minimum water flow over the heat exchanger not achieved, the bypass valve V1 opens and thereby ensures fault-free operation. Important hydraulic components One cycle buffer tank The buffer tank primarily serves to increase the water volume in the hydraulic system in order to ensure a minimum runtime of the compressors and to prevent unnecessarily frequent on and off switching of the compressors. PR GB Subject to modifications R2-02/

68 14 Water filter: Paddle-type flow switch Expansion tank: Water system pressure switch: Regulating valves: Ventilation: Charging and draining: Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. A falling system pressure is processed in the control system of the device, then at of this malfunction stops both the unit as well as also the pump and prevents cost intensive plant breakdowns. Hydraulic rebalancing is used in plants with multiple consumers of different power ratings for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. Control and regulation External enabling device: The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity control of the device and the associated control system of the water temperature may only take place with the internal control of the device. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. 68 PR GB Subject to modifications R2-02/2017

69 Pump release: Differential pressure over consumers (pressure sensor DP2): Differential pressure over the heat exchanger of the device (pressure sensor DP1): Bypass valve V1: Error messaging: 14 After completed release, the unit the speed-controlled pump P1 switches with a specified start rotational speed, examines the air flow with the internal differential pressure switch and additionally with the on-site mounted paddle-type flow switch. As soon as a stable water flow is ensured, the water outlet temperature is recorded and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill or heat the water to the setpoint. In addition, the controller of the device continually records the differential pressure over the most unfavorable consumers (pressure transducer DP2) and also the differential pressure over the heat exchanger of the device (pressure transducer DP1), in order to regulate the rotational speed of the pump or to control the bypass valve V1. The position of the most unfavorable consumer should be determined by the computation of piping. As control variable for the speed control of the pump, the differential pressure of the consumer lying farthest removed and in the most unfavorable pipe section is used. Which pipe section and consumers it is thereby about, must be taken from the piping computation. The differential pressure of the consumer network minimum and maximum limit values must be entered in the controller of the device. Within these limit values, the rotational speed of the pump remains unchanged. If the differential pressure increases above the maximum limit value because individual consumers close their valves, the rotational speed of the pump is reduced so that the differential pressure is once again within the limit values. If the differential pressure decreases below the minimum limit value because individual consumers open their valves, the rotational speed of the pump is increases so that the differential pressure is once again within the limit values. Since the plant characteristics is variable in certain limits by the 2-way valves to the consumers and by the speed-controlled pump, the differential pressure over the heat exchanger of the device is monitored by the pressure differential sensor DP1. In order to avoid operational breakdowns of the device, it is important to always promote a minimum water flow over the heat exchanger. As soon as the limit value for the minimum water flow is undershot, the rotational speed the pump increases and a bypass valve is opened in order to increase the differential pressure and thereby the water flow over the exchanger of the device. If the differential pressure over the heat exchanger is once again within of the required limit value, the rotational speed of the pump is reduced. The bypass valve is slowly closed. The bypass valve serves the assurance of a minimum water volumetric flow over the heat exchanger of the device when there is only little or no load and a large number of 2-valves are closed. In order to make a correct adjustment of the bypass line, it is important to only use the bypass valve in connection with a regulating valve. This is the only possibility of regulating the bypass air flow for an energy-saving operating mode. A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. PR GB Subject to modifications R2-02/

70 14 Frost protection Remember: If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. If glycol is not used as an antifreeze agent, note that you must use trace heating for the pipework and other components like expansion tank and pump that are subjected to outside temperatures below 5 C. For the water-based components in the unit, suitable options are available and provided by the factory. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. 70 PR GB Subject to modifications R2-02/2017

71 14 p DP2 Unit p DP 1 FL T P T P P P P Buffer tank V1 PR GB Subject to modifications R2-02/

72 15 Cold-/warm water generators with variable speed pumps in primarily and secondary circuits (VPS D-Control) Area of application Generation of cold or hot water for comfort air conditioning or for process applications. The consumer network can be made arbitrarily complex. Both on the primarily as well as also on the secondary side, speed-controlled pumps are employed. With the use of variable speed pumps, primarily and secondary circuits can be planned securely and in an energy saving manner. Consumers T T T T T T P P P P P P P2-P4 AB B A T2 Unit Buffer tank P P P P T1 T DT P P1 FL T Advantages of a variable-speed pump By the deployment of variable-speed pumps with the correct hydraulic integration of the device, many crucial advantages result compared to pumps without speed control: The maximum rotational speed of the pump is set after pressure loss in the hydraulic network. The oversizing of a pump with fixed rotational speed and the associated high power consumption is precluded. It is important to create an exact computation of the piping in order to adapt the speed-controlled pump to the plant characteristic curve and to ensure a correct control system. Costly and energy-destroying control valves can be done without. Constant control of the water outlet temperature in stationary operation High energy-saving potential at full and partial load operation as well as also in stand-by operation Longer pump lifetime Lower noise emission 72 PR GB Subject to modifications R2-02/2017

73 15 In full-load operation, an energy savings potential results, since the pump adapts the rotational speed to the actual demand and the pressure loss in the system. For pumps without speed control, the superfluous energy must be compensated by control valves. In partial-load mode, the reduced rotational speed lowers the air flow, since the maximum air flow is not required in partial-load mode. Depending on application case, the partial-load mode of the device with up to 97% of the time once again reflects the largest portion the operating time During of the stand-by-facility, if the system temperature is achieved, the pump controls down to the minimum possible rotational speed. The water-air flow is reduced to 50% of the maximum volume of water. The system temperatures are still recorded reliably and energy saving. For systems without speed control, the pump also works during stand-by operation at maximum rotational speed and power consumption. The theoretical pump characteristics at speed change as follows: The pump feed rate behaves proportional to the change in pump speed. A reduction the rotational speed by 50% therefore leads to a halving of the pump feed rate. The pump lift behaves proportional to the square of the change of the pump speed. Therefore leads a reduction the rotational speed by 50% to a reduction of the pump lift by 25%. The power demand the pump behaves proportional to the third potential of the change of the pump speed. Therefore a reduction the rotational speed by 50% leads to a reduction the power consumption to 12.5%. The energy savings potential decisively depends on the following factors: Design and pressure losses of the hydraulic network Load acceptance of the consumer Operating and stand-by time of the device Design of the device for the required demand Functional principle of the hydraulics By the use of a bypass line in the secondary side consumer circuits, this hydraulic system is separated from the primary side generator circuit. Since the unit is in the position to demand-dependently regulate the rotational speed of the primary pump P1, speed-controlled pumps can also be employed for the on-site secondary pumps. For released units, the medium flows from the buffer tank to the water pump in the unit. On required load acceptance, the medium is refrigerated or warmed and therefore available to the secondary network with the pumps P2 to P4. If there is only a small or no cooling/heating requirement and the volume of water was thereby reduced over the secondary side consumers, the water is with a bypass line between supply line and return flow distributer once again supplied to the primary circuit. A minimum volume of water is thereby ensured with the unit. The consumer circuit can be designed in any number of complex forms. Among these are e.g. Employment of speed-regulated pumps Employment of 2-way or 3-way valves Consumer circuits in different temperature ranges. Consumer circuits with various power capacities and water/volume flows The volume of water of the primarily circuit must always be greater than the volume of water of the secondary circuit over the consumers. PR GB Subject to modifications R2-02/

74 15 One cycle buffer tank Water filter: Paddle-type flow switch Expansion tank: Water system pressure switch: Ventilation: Charging and draining: Important hydraulic components The buffer tank primarily serves to increase the water volume in the hydraulic system in order to ensure a minimum runtime of the compressors and to prevent unnecessarily frequent on and off switching of the compressors. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. A falling system pressure is processed in the control system of the device, then at of this malfunction stops both the unit as well as also the pump and prevents cost intensive plant breakdowns. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. Control and regulation As already mentioned as the functional principle the hydraulic system, the control of the secondary circuit separated from the primary circuit must be observed. Since the unit does not perform the actuation and control of the secondary pumps P2-P4, this must be regulated on-site with the load. The control system of the primary circuit is taken over by the unit with the pump P1. 74 PR GB Subject to modifications R2-02/2017

75 15 External enabling device: Pump release: Temperature sensor T1 and T2: The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity control of the device and the associated control system of the water temperature may only take place with the internal control of the device. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After completed release, the unit the speed-controlled pump P1 switches with a specified start rotational speed, examines the air flow with an internal differential pressure switch and additionally with the on-site mounted paddle-type flow switch. As soon as a stable water flow is ensured, the water outlet temperature is recorded and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill or heat the water to the setpoint. In addition, the controller of the device continually records the values the temperature sensor T1 and T2 and also the temperature difference with the heat exchanger of the device. The rotational speed the primary pump is determined with the values of this parameter. The sensor T1 must be assembled on-site in the water outlet line and the sensor T2 in the bypass line between the supply and return flow distributer. The rotational speed the pump P1 is corrected by analysis of this temperature sensor so that the volume of water of the primary circuit is never less than the volume of water of the secondary circuit. The presupposes that the on-site secondary pumps are designed or limited for this purpose. The speed of the primary pump P1 is regulated according to the following criteria: T1=T2 The rotational speed of the primary pump remains constant and is not corrected T1<T2 This means that the secondary volume of water is greater than the primarily volume of water. The rotational speed of the primary pump is slowly increased until T1 and T2 have the same values. For units in heat pump operation, the logic is vice versa (T1 > T2) Temperature difference over the heat exchanger of the unit (DT): The actual speed control the pump P1 takes place with the water-side temperature difference over the heat exchanger of the device. The temperature difference ΔT over the evaporator is compared at regular intervals with a reference value. The rotational speed of the primary pump P1 is regulated according to the following criteria: the rotational speed of the primary pump P1 is regulated according to the following criteria: DT HEATEXCHANGER > reference value DT HEATEXCHANGER > reference value speed of pump P1 is slowly increased speed of pump P1 is slowly decreased Especially in the partial load mode of the device, the performance of pump P1 can be adapted and energy saved. Error messaging: A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. Frost protection If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. PR GB Subject to modifications R2-02/

76 15 Remember: If glycol is not used as an antifreeze agent, note that you must use trace heating for the pipework and other components like expansion tank and pump that are subjected to outside temperatures below 5 C. For the water-based components in the unit, suitable options are available and provided by the factory. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. 76 PR GB Subject to modifications R2-02/2017

77 15 FL T T T T T T T T P P P P P P P P P P1 P P P2-P4 AB A T1 B Unit DT Buffer tank Consumers T2 PR GB Subject to modifications R2-02/

78 16 Cold/warm water generator with variable-speed pump and single-circuit buffer tank with 3-way valves (VPS A-Control) Area of application Generation of cold or hot water for comfort air conditioning or for process applications. The consumer network is easily formed and the consumers are equipped with 3-way valves. By the use of a variable speed pump, the hydraulic system can be planned securely and to save energy. A A A A A A A B B B B B B B AB AB AB AB AB AB AB Unit Buffer tank P P P P T DT P FL T Advantages of a variable-speed pump By the deployment of variable-speed pumps with the correct hydraulic integration of the device, many crucial advantages result compared to pumps without speed control: The maximum rotational speed of the pump is set after pressure loss in the hydraulic network. The oversizing of a pump with fixed rotational speed and the associated high power consumption is precluded. It is important to create an exact computation of the piping in order to adapt the speed-controlled pump to the plant characteristic curve and to ensure a correct control system. Costly and energy-destroying control valves can be done without. Constant control of the water outlet temperature in stationary operation High energy-saving potential at full and partial load operation as well as also in stand-by operation Longer pump lifetime Lower noise emission 78 PR GB Subject to modifications R2-02/2017

79 16 In full-load operation, an energy savings potential results, since the pump adapts the rotational speed to the actual demand and the pressure loss in the system. For pumps without speed control, the excessive energy must be compensated by regulating valves. In partial-load mode, the reduced rotational speed lowers the air flow, since the maximum air flow is not required in partial-load mode. Depending on application case, the partial-load mode of the device with up to 97% of the time once again reflects the largest portion the operating time During of the stand-by-facility, if the system temperature is achieved, the pump controls down to the minimum possible rotational speed. The water-air flow is reduced to 50% of the maximum volume of water. The system temperatures are still recorded reliably and energy saving. For systems without speed control, the pump also works during stand-by operation at maximum rotational speed and power consumption. The theoretical pump characteristics at speed change as follows: The pump feed rate behaves proportional to the change in pump speed. A reduction the rotational speed by 50% therefore leads to a halving of the pump feed rate. The pump lift behaves proportional to the square of the change of the pump speed. Therefore leads a reduction the rotational speed by 50% to a reduction of the pump lift by 25%. The power demand the pump behaves proportional to the third potential of the change of the pump speed. Therefore a reduction the rotational speed by 50% leads to a reduction the power consumption to 12.5%. The energy savings potential decisively depends on the following factors: Design and pressure losses of the hydraulic network Load acceptance of the consumer Operating and stand-by time of the device Design of the device for the required demand Functional principle of the hydraulics For released units, the medium flows from the buffer tank to the water pump in the unit. The medium is chilled or warmed up for the required load reduction. The cold/ hot water now flows over the consumers and is warmed or cooled down once again. In this case, it can be about consumers of the same or unequal power consumption at identical water temperatures. The required volume of water must be individually adjusted for every consumer with control valves, only so can the respective performance be ensured at full load. The power control of every consumer takes place by 3-way valves. Important hydraulic components One cycle buffer tank Water filter: Paddle-type flow switch The buffer tank primarily serves to increase the water volume in the hydraulic system in order to ensure a minimum runtime of the compressors and to prevent unnecessarily frequent on and off switching of the compressors. Water filters must always be installed before the immediate entry of all water-side heat exchangers in the system. The water filter protects the heat exchanger from deposits and soiling of all kinds. For reliable protection, only use dirt traps with a mesh width of maximum 1 mm. Water filters are a prerequisite for the reliable and faultless function of the unit. The paddle-type flow switch protects the unit evaporator if there is no or inadequate water volume flow. The flow switch must be installed at the unit outlet and electrically connected to the unit, according to the wiring diagram. The flow switch acts as a safety device and not as a regular control element of the unit. The unit's remote PR GB Subject to modifications R2-02/

80 16 ON/OFF may therefore not be switched with the flow switch. The flow switch is a prerequisite for the reliable and faultless functioning of the unit. Expansion tank: Water system pressure switch: Regulating valves: Ventilation: Charging and draining: The expansion tank is mandatory, since this hydraulic system is a closed water circulation system. The expansion tank provides a required hydraulic seal and compensates temperature-related volume changes in the hydraulic system. The entire system volume must be taken into consideration for the dimensioning of the expansion tank. If the plant configuration unit is used with a pre-integrated hydraulic module, it often contains pumps, single-circuit buffer tanks, and possibly (apart from other installations) also expansion tanks. In most cases, however, these expansion tanks are only dimensioned for the water volume of the unit and no longer suffice for the connected hydraulic circuit. The volume of the required additional expansion tank must be harmonized with the total water volume in the hydraulic system. The volume of the expansion tank integrated in the unit usually must be supplemented with an additional expansion vessel on-site. The unit is very frequently mounted on the roof of the building and thereby at the highest point of the system. If an incorrect inlet pressure is the reason for the pressure fall on the highest point of the plant, where the water pumps is often mounted, this leads to cavitation on the suction side of the pump. If cavitation is not noticed in time, water pumps and other plant components can be damaged. If units and water pumps are mounted on the highest point of the plant, then the water pressure switch of the plant should be used at all times. All units are usually equipped with an electrical input that can process the floating contact of the water pressure switch of the plant. A falling system pressure is processed in the control system of the device, then at of this malfunction stops both the unit as well as also the pump and prevents cost intensive plant breakdowns. Hydraulic rebalancing is used in plants with multiple consumers of different power ratings for regulating different volume flows or compensating different pressure drops in the pipework. Vent valves and air collector must be positioned in such a way to ensure correct venting of the hydraulic plant before the unit is commissioned for use. Air-vent valves are not considered in the schematic diagram. Filling and drain valves must be positioned in such a way that the hydraulic plant can be correctly filled and drained. Filling and drain valves are not taken into account in the schematic diagram. Control and regulation External enabling device: Pump release: The unit can be released with an external zero-voltage contact. The release-/changeover contact can be switched to outside temperature or be time-dependent. The enabling contact may not be used to control capacity or temperature. The capacity control of the device and the associated control system of the water temperature may only take place with the internal control of the device. Otherwise the consequence is a cycle operation of the compressors with too short runtimes as well as a considerably worsened energy efficiency of the overall system. After completed release, the unit the speed-controlled pump P1 switches with a specified start rotational speed, examines the air flow with the internal differential pressure switch and additionally with the on-site mounted paddle-type flow switch. As soon as a stable water flow is ensured, the water outlet temperature is recorded and compared with the preset setpoint. Depending on the extent of the deviation, the individual compressors are switched on in order to chill or heat the water to the setpoint. 80 PR GB Subject to modifications R2-02/2017

81 Temperature difference over the heat exchanger of the unit (DT): Error messaging: 16 The actual speed control the pump P1 takes place with the water-side temperature difference over the heat exchanger of the device. The temperature difference ΔT over the evaporator is compared at regular intervals with a reference value. The rotational speed of the primary pump P1 is regulated according to the following criteria: DT HEATEXCHANGER > reference value DT HEATEXCHANGER > reference value speed of pump P1 is slowly increased speed of pump P1 is slowly decreased Especially in the partial load mode of the device, the performance of pump P1 can be adapted and energy saved. A floating contact is available in the unit for monitoring the plant. The contact closes in case of a service breakdown. Never switch the unit off with the external enabling signal, since if a break-down is recorded via the floating contact, information on the cause of the malfunction might no longer be displayed on the unit display. Furthermore, the entire unit is thereby put out of commission, even though possibly only one of several refrigeration circuits was affected. Frost protection Remember: If the pipework with circulating water is run in the outdoor area or if the pipework is not protected against frost within the building, the relevant freeze protection must be ensured. DencoHappel recommends to use at least 30% ethylene glycol. If glycol is not used as an antifreeze agent, note that you must use trace heating for the pipework and other components like expansion tank and pump that are subjected to outside temperatures below 5 C. For the water-based components in the unit, suitable options are available and provided by the factory. Additional notices for planning Every unit is subject to relevant operating limits. The following points must be considered: minimum and maximum ambient temperatures minimum and maximum water temperatures for evaporator and condenser To ensure a trouble-free operation, it is necessary to maintain the required operating limits. The technical documentations (data & facts) of each unit include diagrams of the operating limits which must be taken into account. PR GB Subject to modifications R2-02/

82 16 B A AB A B AB Buffer tank B A AB T P P B A AB B P P T A AB P FL B A AB Unit DT B A AB 82 PR GB Subject to modifications R2-02/2017

83 Legend _i 3-way motor valve Bypass valve / 2-way motor valve Shut-off valve Cap valve Ball valve Regulating valve Safety valve (spring-loaded) Strainer Non-return damper Pipeline compensator Expansion tank Circulating pump Circulating pump with speed regulation FL Paddle-type flow switch TS Temperature sensor sequential control T Thermometer P Pressure gauge P Pressure switch p Differential pressure sensor DT Measurement of temperature difference Pipe connection Electric line PR GB Subject to modifications R2-02/

84 DencoHappel is a global company with expertise in air treatment, air conditioning and air filtration. Our nearest sales and service teams will be glad to discuss ideas and develop creative and effective solutions with you.

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

The Book of AERMEC NRL Sequence of Operation

The Book of AERMEC NRL Sequence of Operation The Book of AERMEC NRL Sequence of Operation Heating and cooling operation. 2 Sequence of operation Aermec air to water chiller/heat pump use Hydronic s in conjunction with refrigerant to provide heating

More information

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS David Grassl PE Mechanical Engineer Principal Similar to traditional boiler systems, condensing boiler systems have many designs they can operate

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

Planning guide. (2010/09) en

Planning guide. (2010/09) en Planning guide (2010/09) en 1 Planning guide for Greenline HE E 21, 28 and HE D 36, 43 Page Contents 3 Documentation and VPW2100 4 Technical data of heatpump 5 Dimensioning of DHW systems 6 Symbol explanations

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic and Seconscrew ranges Manufacturer Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg

More information

Operating Functions Temperature Parameters

Operating Functions Temperature Parameters Operating Functions Temperature Parameters Room set temperature (T set) Room ambient temperature (T amb) Fundamental Functions After powered on, no matter when the compressor is started, the time interval

More information

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs Lesson 1 - Basic Heat Pump Theory (Part 1) Describe the basic operation of a heat pump. Explain the function of various heat pump controls. Interpret the wiring diagrams and performance data provided by

More information

USERS MANUAL FOR GAS BOILERS

USERS MANUAL FOR GAS BOILERS USERS MANUAL FOR GAS BOILERS PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE MODELS: NOVADENS 24 NOVADENS 24C NOVADENS

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 201 C K RAE 482 C K AIR R-407C Series RAE... C K from 19 to 83 kw - 1 and 2 circuits The air cooled chillers of RAE... C K series, with centrifugal fans, are designed for indoor installation and are

More information

EN aquatech.piovan.com

EN aquatech.piovan.com EN aquatech.piovan.com Refrigeration Technologies: scroll-compressor chillers The scroll compressor is the most suitable component for the small and medium duty requirements in the industrial applications.

More information

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application 1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin B40-THERM-PDI-14 1069132 ThermoSaver TM Hot Gas Defrost System For use on select

More information

Operation and Maintenance Haskris LX-Series, R-Series, WW-Series, OPC-Series

Operation and Maintenance Haskris LX-Series, R-Series, WW-Series, OPC-Series Section 1: Temperature Control Your Haskris will have one of three different types of controller. Use table 1-1 to identify the relevant controller. The controller may appear different than examples. Contact

More information

DATA AND FACTS Chillers GLRC CD2. Chillers with External Condenser

DATA AND FACTS Chillers GLRC CD2. Chillers with External Condenser DATA AND FACTS Chillers GLRC 2015-4160 CD2 Chillers with External Condenser Table of contents Unit type code... 4 Overview... 5 Unit series... 5 SL unit with acoustic attenuation... 6 Energy efficiency

More information

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Air Conditioning Clinic Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Absorption Water Chillers One of the Equipment Series A publication of The Trane Company Worldwide Applied Systems

More information

Engineering Bulletin Rev B. Contents. Piping Arrangements for Heat Pump Water Heating Systems

Engineering Bulletin Rev B. Contents. Piping Arrangements for Heat Pump Water Heating Systems Engineering Bulletin 940126-0003 Rev B Piping Arrangements for Heat Pump Water Heating Systems Contents 1. INTRODUCTION... 0 2. WATER PIPING... 0 3. HEAT PUMP WATER HEATER PIPING... 1 4. RINGMAIN (RECIRCULATING

More information

Partial Load Performance Of Refrigeration System

Partial Load Performance Of Refrigeration System Chapter 11 Partial Load Performance Of Refrigeration System Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Hot Gas Bypass & Liquid Injection: When the compressor is under surge condition,

More information

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION Environment IMPORTANT INFORMATION It is not anticipated that this equipment will be exposed to adverse environmental conditions without additional protection. Site the equipment in a frost free area. Ensure

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Packaged Chiller Models CC 6601, 6501, 6401, 6301, 6201, 6101 For Service, please contact Pfannenberg Service Company: U.S.A. Pfannenberg Inc. 68 Ward Road.

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 1402 C O K AIR R-407C Series RAE... C K Cooling capacity from 81 to 250 kw - 2 circuits The air cooled chillers of RAE C K series, with centrifugal fans, are designed for indoor installation and are

More information

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems 12 In Row Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents Table of Contents... 3 Site

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin K40-THERM-PDI-15 Part # 1069130 PRODUCT SUPPORT web: k-rp.com/ts email: mdcu-lgcu@k-rp.com

More information

Heating and D.h.w. Controller RVL482 Basic Documentation

Heating and D.h.w. Controller RVL482 Basic Documentation Heating and D.h.w. Controller RVL482 Basic Documentation Edition: 1.0 Controller series: A CE1P2542en 20.05.2008 Building Technologies Siemens Switzerland Ltd Building Technologies Group International

More information

CALEFFI. Automatic flow regulators GB. AUTOFLOW APPLICATION No AIR CONDITIONING MACHINE

CALEFFI. Automatic flow regulators GB. AUTOFLOW APPLICATION No AIR CONDITIONING MACHINE Automatic flow regulators GB AUTOFLOW APPLICATION No. Air-conditioning machine for aircraft on the ground This system is designed for air-conditioning of aircrafts when they are on the ground, connected

More information

Surna 25-Ton Chiller Operating & Maintenance Manual

Surna 25-Ton Chiller Operating & Maintenance Manual www.surna.com 303.993.5271 Surna 25-Ton Chiller Operating & Maintenance Manual Models: 300F3-3. 300F4-3, 300FW-3 Revised: July 2015 Table of Contents Warranty Information 4 Limited Warranty 4 Limitation

More information

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

HYDROCIAT LW R407C. Water cooled chillers USE RANGE Screw compressors CIAT dry direct expansion shell and tubes evaporator HPS equipment (High Power System) cooling or heating Heat recovery ENVIRONMENTALLY HFC R407C PROTECTION DE FRIENDLY L'ENVIRONNEMENT

More information

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall. Chapter 4 Variable-speed pumps. A variable-speed pump varies the flow rate by maintaining a constant pressure differential as zone valves open and close. A sensor measures the difference in pressure between

More information

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P) 2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment AHRI Guideline T (I-P) IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the

More information

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA242H WA36H NOTE: Electrical data presented in this manualsupersedes any other data for the above listed models. Bard Manufacturing

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps.

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps. Air/water cooled chillers and heat pumps 41 303 kw General BETA ECHOS is a range of chillers and ductable air-water heat pumps. Configurations HP: Reversible heat pump LE: For connection to remote evaporator

More information

Modular Chiller Systems. Application Guide

Modular Chiller Systems. Application Guide Modular Chiller Systems Application Guide Table of Contents Introduction.... 1 References/Nomenclature Conventions... 2 Terms & Definitions.... 2 Module Size Selection...3 Water Source, Cooling Only and

More information

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS Energy saving thanks to a total recovery p Cooling Heating/DHW h Galletti multi-purpose heat pumps are total recovery units used for a simultaneous hot and

More information

Water chillers water/water type SIGMA Technical information manual

Water chillers water/water type SIGMA Technical information manual Water chillers water/water type SIGMA Technical information manual 2 INDEX Technical features 1 Versions 3 Accessory versions 4 Technical data 7 Electrical data 11 Cooling capacity 12 Heating capacity

More information

Technical description. Atec.

Technical description. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job. June 01 / BULLETIN - 3-Way Valves The right solenoid valve for any job. Page 2 / Bulletin - Advantages Sporlan 3-Way Valves 3-Way Pilot eliminates costly high- to low-side leaks. "B" reduces total installed

More information

Process glycol chillers

Process glycol chillers Process glycol chillers The most advanced solutions in refrigeration technology. According to normative EN378 y F-Gas Compact chillers for outdoor installation Natural refrigerant Integrated hydraulic

More information

SUPPLEMENT TO OPERATION MANUAL Modular Air Handling Units CAIRplus ECOTWINcool

SUPPLEMENT TO OPERATION MANUAL Modular Air Handling Units CAIRplus ECOTWINcool SUPPLEMENT TO OPERATION MANUAL Modular Air Handling Units CAIRplus ECOTWINcool Table of Contents Overview of units and packaged content... 3 Adiabatic cooling... 3 Design features... 4 Fan arrangement...

More information

CONTROLLED CHILLED BEAM PUMP MODULE

CONTROLLED CHILLED BEAM PUMP MODULE FIRST COST SAVINGS PROACTIVE CONTROL CONTROLLED CHILLED BEAM PUMP MODULE Active condensation control system effectively eliminates chilled beam condensation High efficiency, variable speed pump uses a

More information

EP1 Series Portable Chillers

EP1 Series Portable Chillers USER GUIDE UGH036-0613 www.conairgroup.com EP1 Series Portable Chillers Air-Cooled Models EP1A-01, EP1A-02, EP1A-03 Water-Cooled Models EP1W-02, EP1W-03 Remote Condenser Model EP1R-03 Thank you for purchasing

More information

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd Abstract This paper presents the design approach adopted for the expansion of a large existing

More information

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation AIR-TO-WATER HEAT PUMPS 30RQV 017-021 NEW Nominal cooling capacity 15-18 kw Nominal heating capacity 17-21 kw greenspeed Easy and fast installation Hydronic module available Inverter technology compressor

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

ULTIMATE ENERGY SAVING TECHNOLOGY

ULTIMATE ENERGY SAVING TECHNOLOGY ULTIMATE ENERGY SAVING TECHNOLOGY CWM CHILLER SERIES CWM PURESTREAM SERIES WATER CHILLERS The new CWM Purestream chiller range is specifically designed to meet the stringent cooling requirements of today

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

SONAPHONE. Performance test of steam traps Supplement to the operating manual

SONAPHONE. Performance test of steam traps Supplement to the operating manual SONAPHONE Performance test of steam traps Supplement to the operating manual SONOTEC Ultraschallsensorik Halle GmbH Nauendorfer Str. 2 06112 Halle (Saale), Germany Phone: +49 (0)345 133 17-0 Fax: +49 (0)345

More information

APC APPLICATION NOTE #119

APC APPLICATION NOTE #119 #119 InRow RP-CW and InRow RP-DX Environmental Control By Henry Jespersen Abstract The primary function of the InRow RP product is to cool air from the hot aisle and deliver it to the cold aisle at the

More information

MODELS LIST. Nominal Capacity RT

MODELS LIST. Nominal Capacity RT 1. MODELS LIST. NOMENCLATURE 3. FEATURES 4. PRODUCT DATA 5. PERFORMANCE CORRECTION 6. ANTIFREEZE 7. INSTALLATION 8. ELECTRICAL DATA 9. SCHEMATIC WIRING DIAGRAM 10.MICROPROCESSOR CONTROLLER 11.APPLICATION

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office

More information

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2 MARKING This product marked conforms to the essential

More information

Bulletin , March Electric Hot Gas Bypass Valves

Bulletin , March Electric Hot Gas Bypass Valves Bulletin 100-60, March 2018 Electric Hot Gas Bypass Valves PAGE 2 / Bulletin 100-60 10 FEATURES AND BENEFITS SDR-4 Direct temperature control Tight shutoff when closed Can be interfaced with direct digital

More information

Vicot Air Conditioning Co., Ltd. CONTENT

Vicot Air Conditioning Co., Ltd. CONTENT CONTENT I. Introduction 2 II. Absorption Principle 3 III. GAX Absorption Cycle 3 IV. Major Component Description and Function 4 V. Features 4 VI. Performance curve 5 VII. Nomenclature 5 VIII. Technical

More information

Water-cooled chillers with High Speed Centrifugal Compressors

Water-cooled chillers with High Speed Centrifugal Compressors Water-cooled chillers with High Speed Centrifugal Compressors Refrigerant R134a 190-760 (395 to 2660 kw) Refrigerant R1234ze 135 G - 505 G (310 to 1820 kw) Table of Contents Introduction...3 Features and

More information

ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01

ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01 ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01 1. Use and construction of the pump and control unit The pump and control unit is designed to work with solar collectors in systems with required

More information

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a Air-Cooled Variable Speed Drive Screw Chillers Super Efficient Super Quiet Cooling Capacity Range 540-1405 kw R134a World s first low sound Air-Cooled variable speed drive screw chiller The recognition

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS Total heat recovery multi-purpose units LCP Outdoor monobloc air-water unit LCP - kw Heating, cooling, domestic hot water one single system to meet all kinds of needs. Total heat recovery multi-purpose

More information

Wash and Clean By Michael Rasmussen, Industry application team, Grundfos, Denmark

Wash and Clean By Michael Rasmussen, Industry application team, Grundfos, Denmark Wash and Clean By Michael Rasmussen, Industry application team, Grundfos, Denmark Introduction Wash & Clean systems for the food processing industry is an utility application that sets high requirements

More information

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water Designed to replace a conventional boiler and produce domestic hot water Heating capacity : 16 to 25 Heating Hydraulic module ENVIRONMENTALLY HFC R4A PROTECTION DE FRIENDLY L'ENVIRONNEMENT USE CIAT is

More information

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power energy center Paper Report Summary 210-1 174-2 Fixed and Floating Head Pressure Comparison for Madison Ice Arena Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power July 1998 April,

More information

High Density Cooling Systems

High Density Cooling Systems OPERATION MANUAL Close Control Units Controller for Row-DENCO High Density Cooling Systems Table of Contents Controller for Row-DENCO 1 Safety and User Information... 4 1.1 Availability of the operation

More information

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison Emerging Technologies: VFDs for Condensers Douglas T. Reindl Director, IRC University of Wisconsin-Madison University of Wisconsin-Madison 1 We ve looked at VFDs on Evaporators and compressors, what is

More information

Hydronic Mechanical Panels

Hydronic Mechanical Panels Hydronic Assemblies Inc. 56 Horse Hill Rd Concord NH 2015-2016 Hydronic Mechanical Panels Contact 4805 Main St. Waitsfield, Vermont 05673 Phone : 802-583-5500 WWW.Houseneeds.com Hydronic Assemblies Inc.

More information

Pack Calculation Pro. Users guide. Version Morten Juel Skovrup

Pack Calculation Pro. Users guide. Version Morten Juel Skovrup Pack Calculation Pro Users guide Version 4.10 Morten Juel Skovrup 1 Contents 2 Introduction... 5 3 Example... 7 3.1 Setup systems... 7 3.1.1 Selecting compressors... 9 3.1.2 Suction side... 12 3.1.3 Discharge

More information

Screw Water Cooled Chiller SCW210

Screw Water Cooled Chiller SCW210 Screw Water Cooled Chiller SCW210 Nominal Cooling Capacity 185.1 to1480.8 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data 5 Unit Performance 8 Chiller Selection 9 Physical

More information

TCHE-THHE TCEE

TCHE-THHE TCEE K11208-GB ed. 3 TCHE-THHE TCEE Q-Flow range Macrosystem 148,4 262,2 kw TCHE-THHE - Water cooled water chillers and heat pumps units with environmentally friendly refrigerant. Range with hermetic Scroll

More information

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference.

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference. Installation and Service Instructions for use by heating contractor Solar Control Module for solar connections to the Vitotronic control SM1 SOLAR CONTROL MODULE Product may not be exactly as shown IMPORTANT

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Heat recovery systems - Free hot water by total recovery of the heat rejected by the cooling units

Heat recovery systems - Free hot water by total recovery of the heat rejected by the cooling units Heat recovery systems - Free hot water by total recovery of the heat rejected by the cooling units Summary : - Why Boostherm? For whom? - Heat recovery module functioning - Highlights & benefits - Boostherm

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

Cooling Unit for Producing Chilled Water. Envicooler. Operation and Maintenance Instructions. Air handling with the focus on LCC

Cooling Unit for Producing Chilled Water. Envicooler. Operation and Maintenance Instructions. Air handling with the focus on LCC Cooling Unit for Producing Chilled Water Air handling with the focus on LCC Address and telephone list for calling for service Supplier: IV Produkt Box 3103 SE-350 43 VÄXJÖ, Sweden Street address: Sjöuddevägen

More information

Customers. The core of our innovation. Feeding&Conveying Drying Dosing Temperature Control Refrigeration. Granulation

Customers. The core of our innovation. Feeding&Conveying Drying Dosing Temperature Control Refrigeration. Granulation EN Customers. The core of our innovation Feeding&Conveying Drying Dosing Temperature Control Refrigeration Granulation scroll-compressor chillers The scroll compressor is the most suitable component for

More information

How to Cut Chiller Energy Costs by 30%

How to Cut Chiller Energy Costs by 30% How to Cut Chiller Energy Costs by 30% Pre-packaged retrofit cuts centrifugal compressor chiller energy costs by 30% while reducing required maintenance and extending operating life at Duke Realty Corporation

More information

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING

Refrigeration and Air Conditioning Controls. Applications. PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING Refrigeration and Air Conditioning Controls Applications PM Modulating pressure and temperature regulators REFRIGERATION AND AIR CONDITIONING Introduction Danfoss PM regulators have been on the market

More information

K18 PLANT MANUAL. Heating and DHW

K18 PLANT MANUAL. Heating and DHW K18 PLANT MANUAL Heating and DHW 0 - INTRODUCTION This document provides the guidelines on how the Gas Absorption Heat Pump GAHP K18 operates, how to use it and how a designer or a qualified installer

More information

Installation, Operation and Maintenance Manual. LQ Series Portable Chillers

Installation, Operation and Maintenance Manual. LQ Series Portable Chillers Installation, Operation and Maintenance Manual LQ Series Portable Chillers Table of Contents Foreword... 1 Installation... 1 Receiving Inspection... 1 Rigging, Handling, and Locating Equipment... 1 Electrical

More information

Heating controller with optimisation functions

Heating controller with optimisation functions TAC 2112 C-10-42 Heating controller with optimisation functions 1999.12 The TAC 2112 offers for control of hot water systems. The radiator circuit is controlled according to an outdoor -compensated reset

More information

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production SATK0 - SATK0 series ACCREDITED ISO 900 FM 009/ GB replaces dp 009/ GB Function The latest generation of Heat Interface

More information

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES COOLING CAPACITY FROM 76 TO 612 Kw 1 AND 2 COOLING CIRCUITS RAE 1702 F Kc + P2 28 Above picture is only indicative

More information

Installation, Operation and Maintenance Manual. LQ Series. Portable Chillers 7 to 40 Tons

Installation, Operation and Maintenance Manual. LQ Series. Portable Chillers 7 to 40 Tons Installation, Operation and Maintenance Manual LQ Series Portable Chillers 7 to 40 Tons Copyright Thermal Care Inc. 2011 Page intentionally blank Table of Contents Foreword... 1 Installation... 1 Receiving

More information

EQ Series Portable Chillers

EQ Series Portable Chillers EQ Series Portable Chillers Installation, Operation and Maintenance Manual Copyright Thermal Care Inc. 2010 Table of Contents Foreword... 1 Installation... 1 Receiving Inspection... 1 Rigging, Handling,

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou Condensers ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM A. Hadawey, Y. T. Ge, S. A. Tassou 4 7 8 5 3 2 6 1 Produced by: The Centre for Energy and Built Environment

More information

Trouble Shooting Guide PWA, 3-phase (D10571)

Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage Loose wire

More information

Starting current with soft starter Fuse protection. Connection heating Seal of approval MCS (valid until)

Starting current with soft starter Fuse protection. Connection heating Seal of approval MCS (valid until) Data sheet LA 16MS Air-to-water heat pump with deflector hoods Max. flow temperature: 58 C Casing colour: White aluminium (similar to RAL 9006) Air-to-water heat pump for outdoor installation with external

More information

General information on refrigerant controllers

General information on refrigerant controllers General information on refrigerant controllers Condensing pressure controller The condensing or condenser pressure controller is a back pressure controller and its task is to maintain the condensing pressure

More information

HONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING

HONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING ASHRAE s BEST This article was published in ASHRAE Journal, November 2010. Copyright 2010 American Society of Heating, Refrigerating and -Conditioning Engineers, Inc. Reprinted here by permission from

More information

College of Technological Studies Department of Power & Refrigeration Technology. Course Contents

College of Technological Studies Department of Power & Refrigeration Technology. Course Contents College of Technological Studies Department of Power & Refrigeration Technology Course Contents Course Designation: Air Conditioning Control systems Course No. : 272 0463 Credit Hrs.: 3 Lecture Hrs.: 2

More information

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet Attractive design, Compact and quiet Many customisable configurations possible For indoor installation New reliable technologies Version with Plug and Cool hydraulic module Cooling capacity: 23 to 140

More information

Press Release. How can the efficiency of the dryer section be increased? Dryer Section All Paper Grades. Heimbach wherever paper is made.

Press Release. How can the efficiency of the dryer section be increased? Dryer Section All Paper Grades. Heimbach wherever paper is made. Dryer Section All Paper Grades Press Release How can the efficiency of the T. Bock (Dipl.-Ing.), Manager Application & Technical Service, Heimbach GmbH & Co. KG, thomas.bock@heimbach.com I. Durniok (Dipl.-Ing.),

More information

Landfill & Digester Gas Dryers. Features and Benefits

Landfill & Digester Gas Dryers. Features and Benefits Landfill & Digester Gas Dryers Landfill gas is generated by the anaerobic decomposition of organic matter deposited in landfills. Digester gas is produced as a by-product of the digestion of sewage sludge.

More information

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Technical Report #3 Mechanical Systems Existing Conditions Evaluation Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents

More information