ll. Consistency Questions

Size: px
Start display at page:

Download "ll. Consistency Questions"

Transcription

1 Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and buildings economically viable to serve the needs of our community. We strive for: EXCELLENT CUSTOMER SERVICE! and QUALITY INSPECTIONS! May 10th, 2017 ELECTRICAL CONSISTENCY MEETING OUR NEXT MEETING is June 15 th l. Customer Service Tips ll. Consistency Questions

2 1) Am I required to use a GFCI breaker on a refrigerator within 6 of a sink in a commercial breakroom, or will a GFCI receptacle suffice. The refrigerator has wheels and is easily moved B 5 directly addresses this. It requires the GFCI on any receptacle in 6 of the sink, with two exceptions that do not apply here. If a GFCI receptacle is used for compliance it cannot be behind the refrigerator. 2) I have a unit wall heater in a stairwell. It is a 208 volt single phase unit that draws 14 amps made by Honeywell. The blower motor is 1/8 HP. It has an integral thermostat, but it has no marked-off position. Does this unit require a disconnect within sight, or will a breaker lock-off suffice? B 1 allows for the disconnect to be insight of the unit or lockable per

3 3) I wired a rooftop HVAC unit that has an integral breaker disconnect. It also has an integral GFCI receptacle. I was turned down for not having a disconnect on the unit because the receptacle transformer is wired from the line side of the unit s breaker disconnect. Is this correct? Technically, by The King s English yes. Let s look at the big picture though. Is the transformer and receptacle isolated? Is the unit listed? Will it be safe? We are to interpret the code requirements as liberally as possible, so if we can see that its listed, safe and meets the purpose or intent of the code we should pass it. It can t have the receptacle connected to the load side by code. 4) On a multi-tenant building with mains inside we allow the house panel w/main to be outside. If tenant mains are outside can house panel main be inside a service room accessible from outside or does it require a main grouped with other tenant mains?

4 We have not made that a policy, but there seems to be no issue either way if the building qualifies for multiple services. 5) In the 2014 NEC article requires surge protection for the 700 system. Will the SPD (Surge Protection Device) I installed on the service cover this? No requires a listed SPD installed on or in ALL emergency switchboards and panelboards. 6) In dwellings that are roughed in for a stackable washer and dryer supplied by a 30 amp, 240-volt circuit, do I have to install a 20 amp 120 volt laundry circuit since there is no need for it? Yes, per 2014 NEC 210. (C)(2) and (F) at least one 20-amp branch circuit shall be provided and at least 1 receptacle installed.

5 7) My inspector turned me down for installing LFMC above the ceiling to serve 2 RTU s. He stated this could not be installed in an air return (plenum) ceiling. Your inspector was correct. Please see (C)(1) 8) Is it permissible for a 100-amp breaker and a set of # 1 AWG cu. conductors from one panel to serve a 200 amp sub-panel that has a 85 amp load? Yes. We can exceed the code at anytime. 9) I have a clothes closet with a box roughed in for the light. The GC installed deeper shelves than I had planned for. Now that we do not have the proper clearance can I blank this box off or would I be forced to remove the wiring? A blank outlet would be acceptable. Inspectors would need to note that in their inspections. We would suggest that the contractors remove the

6 outlet or disable the conductor to failsafe the outlet and prevent an accident. 10) Are the receptacles located in a food serving area/serving line portion of a restaurant at the mall required to be GFCI protected? If we assume this is not a kitchen or not within 6 of a sink, then we see no requirement for GFCI. 11) If I use metal Romex connectors in a PVC J-box, do I have to ground them? Yes, per , so use nm connectors on nm boxes. 12) Is it permissible to protect conductors that have been de-rated for ambient temperature, or voltage drop at the next standard rating of overcurrent devices as detailed in 240.4?

7 Yes. All requirements must be met per the specific application. The load can t exceed the demanded ampacity though. 13) I installed a service disconnect for a piece of equipment, the equipment did not have a neutral load and there did not require a grounded conductor. The power company informed me they were installing an ungrounded service. I installed the disconnect and grounded the service to the two grounds I installed, and requested the inspection, and was subsequently failed due to 1. Service is grounded, grounded conductor required, per C I was acting as told why should I receive the failure, and what right does the inspector have to override the power company? And What are ground fault indicators? (C) Grounded Conductor Brought to Service Equipment. Where an ac system operating at 1000 volts or less is grounded at any point, the grounded conductor(s) shall be routed with the ungrounded conductors to each service

8 disconnecting means and shall be connected to each disconnecting means grounded conductor(s) terminal or bus. A main bonding jumper shall connect the grounded conductor(s) to each service disconnecting means enclosure. The grounded conductor(s) shall be installed in accordance with (C)(1) through (C)(4). requires the grounded conductor. The service to the building is regulated by NCEC in this section. Many times, the utility uses a grounded system to deliver an ungrounded service in violation of this requirement. If this were an ungrounded system, then there would be a need for indicators and alarms as indicated by NCEC These alarms indicate when a phase is in fault. 14) In the question above if there is no required neutral load what is the minimum size grounded conductor required to be brought to the service? With no grounded load, we in effect are bonding. See C 1

9 15) Is it required to protect the emergency system feeder conductors of a 700 system, using the more restrictive measures listed in 695.6, from the point of origin at the generator, to the point of separation of the separate systems? Per A 2 the special protection is required from the last OCP permitted by B or a feeder connected directly to the generator. The code has allowed taps from a trough set up for different systems including the fire pump and for sectionalized switchboards. The key to this question would be in the individual layout of the project. 16) Are weather/rain tight conduit connections required where conduits terminate into the end of a Type 3R raintight auxiliary gutter? If no equipment connections are made to the bottom of the gutter? If the gutter is exposed to a wet location all connections should be rated for the environment.

10 17) Does the branch circuit rating for a steam generator used in a residential sauna required to be sized at 125%? We need to look at the spec. sheet and nameplate from the manufacturer and at ) Is it permissible to wire to cable pendant fixtures using SJOO cord, being fed with 20 amp circuits? What is the minimum size SJOO cord allowed for the installation? allows cords to be used for pendant lighting. SJOO has no prohibited provisions and can be rated for 20 amps, a # ) Per NEC , in a hotel room is a microwave fastened in place considered permanent cooking equipment? Does a dedicated circuit for a microwave mean it is permanent cooking equipment? If a sink and a fastened in place/dedicated circuit microwave are installed,

11 does this guest room have to meet the requirements of a dwelling unit? In Article 100 we are given definitions to use in our understanding of the code. Our first consideration is dwelling unit. Per the code Dwelling Unit. A single unit, providing complete and independent living facilities for one or more persons, including permanent provisions for living, sleeping, cooking, and sanitation. Secondly we look at kitchen in the code, Kitchen. An area with a sink and permanent provisions for food preparation and cooking. Next if we look at the appliance itself per its listing with UL Standards (KQSQ) we see that its title is MICROWAVE COOKING APPLIANCE. This category covers cooking equipment incorporating one or more microwave generators operating in the normal ISM bands of or 25 and or - 50 MHz. This equipment includes portable and stationary microwave cooking appliances employing resistive-type heating elements for baking, broiling,

12 browning, convection cooking, or similar operations. This category also covers combination microwave oven vent-hood fans, and kits for converting counter-top units to built-in, undercabinet, wallmounted or similar installations. Per the plans examiner we have a sink, refrigerator, dishwasher, disposal and a microwave present within these units. Additionally, there will be provisions for a coffee pot and toaster. It seems the total meets the definitions above and we have in fact a kitchen which then qualifies this as a dwelling unit. In the past we had several times when the question was asked concerning whether or not the microwave was a permanent provision for cooking. In our meetings with the OSFM at code seminars we were informed if the unit had a dedicated circuit or was attached it should be considered permanent.

13 20) In plan review the last several restaurant projects the design team have taken NEC demands for equipment such as hood exhaust fans, make up air fans, hood control circuit, hood lighting, cooler compressor and evaporator, dishwasher exhaust fan, POS circuits, drink station circuits, bar area and bar equipment circuits. What is the definition of other kitchen equipment? Does this equipment qualify as other kitchen equipment? Kitchen Equipment Other Than Dwelling Unit(s). It shall be permissible to calculate the load for commercial electric cooking equipment, dishwasher booster heaters, water heaters, and other kitchen equipment in accordance with Table These demand factors shall be applied to all equipment that has either thermostatic control or intermittent use as kitchen equipment. These demand factors shall not apply to space-heating, ventilating, or air-conditioning equipment. However, in no case shall the feeder or service calculated load be less than the sum of the largest two kitchen equipment loads. So, for the equipment listed in the question;

14 hood exhaust fans, ventilation - no reduction make up air fans, ventilation no reduction hood control circuit, ventilation no reduction dishwasher exhaust fan, ventilation no reduction hood lighting, lighting no reduction by cooler compressor and evaporator no reduction by unless in the kitchen POS circuits as cooler drink station circuits as cooler bar area and bar equipment circuits as cooler THE PROVISION IS FOR MAJOR APPLIANCES ONLY as shown in the example list! 21) Is a private RV lot such as a country club RV lot at the lake subject to NEC 551? The definition refers to the general public? Yes. The public is the customer of the club through its membership program and deserves the same protections as all others. 22) Do we require GFCI receptacles for all outlets designated for vending machines? What if the machine is on site and has a GFCI attachment plug?

15 Per the units that are cord supplied are to have GFCI as part of the cord assembly if manufactured on or after Jan.1, If before that the GFCI protection is to be provided. We can only go by what is in place on the project and the time of inspection. 23) I have a service on a strip shop with a trough feeding a house panel and 5 shop mains. The engineer calculated 8,598 AIC on the house panel and a different engineer had 33,300 on the shop mains. How do I deal with this? Bussman has an app that can ballpark this for you. It is Bussman FC2. It can help put you in the correct direction. Both engineers need to be advised of this issue for resolution. We would need a bullentin for any changed values and markings to reflect real conditions. 24. I have an area of rescue assistance system installed in an apartment building. The main unit has an approved NRTL label on it. The other remote

16 units do not. Am I required to get these field evaluated and labeled? Maybe not. If the remaining units are just slave units (like speakers) we need no other labels per NCDOI. These units may be built to meet code as well. 25) Does NFPA 72 apply to a single-family home? NO, per the administrative code it does not apply to one and two family, or townhomes. 26)The inspector turned me down for not having a disconnect at the well pump. I have a disconnect at the tank/pressure switch (controller) in the crawl space. Was he correct? If the switch at the pressure tank is lockable it would meet code. See B 2. (Per S131 we currently only look at the ocp and wire in the panel for wells.)

17 27) Can I spray foam a ceiling with IC rated recessed cans up to and enveloping the cans or must I maintain space around the cans? The only applications we have seen require boxing out around the fixtures or creating a shell of foam away from the fixture. However, if the manufacturer of the IC fixture and the foam insulation do not prohibit the use, we will accept it as in the question. See UL White Book IEZX and NEC B and Incandescent Recessed Luminaires (IEZX) GENERAL This category covers luminaires intended for installation in recessed cavities in walls, ceilings and similar locations in accordance with Article 410, Parts XI and XII of ANSI/NFPA 70, National Electrical Code (NEC). TYPE IC LUMINAIRE Luminaires marked TYPE IC may be installed such that insulation and other combustible materials are in contact with, and over the top of, the luminaire. Type IC luminaires are provided with

18 thermal protection to deactivate the lamp should the luminaire be mislamped (B) Installation and Use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling Clearance and Installation. (A) Clearance. (2) Type IC. A recessed luminaire that is identified for contact with insulation, Type IC, shall be permitted to be in contact with combustible materials at recessed parts, points of support, and portions passing through or finishing off the opening in the building structure. lll. PV Checklist

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Is low voltage cable allowed to be run through drilled

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

2009 ELECTRICAL CODE REQUIREMENTS

2009 ELECTRICAL CODE REQUIREMENTS 2009 ELECTRICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Inspection Request Line (231) 533-3510 Electrical requirements

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

WIRING AND PROTECTION

WIRING AND PROTECTION 5997ch02.qxd_mg_cc 4/6/05 12:42 PM Page 5 2 WIRING AND PROTECTION (Excerpts from Chapter 2) 210.1 Scope ARTICLE 210 BRANCH CIRCUITS I. General Provisions Article 210 applies to all branch circuits except

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004 Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004 1. A 2 PVC conduit was installed in the ground prior to setting a factory manufactured home on the foundation. The required service

More information

Electrical Essentials corrected calculation slides only

Electrical Essentials corrected calculation slides only Electrical Essentials corrected calculation slides only IAEI Southern Nevada Chapter/Educode 2015 Electrical Theory 1 Feeders and OCP 5 NEC Structure 2 Service and Grounding 6 Print Reading 3 Fault Current

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch

More information

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016 IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS June 17th, 2016 RE: City Council Adopts 2014 National Electrical Code with Pool Alarm Requirements On April 25th, 2016 the

More information

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016)

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016) Cheboygan County Department of Building Safety 870 South Main Street P.O. Box 70 Cheboygan, Michigan 49721 TX: (231) 627-8813 FX: (231) 627-8454 www.cheboygancounty.net Service Entrance ONE- AND TWO-FAMILY

More information

RESIDENTIAL OVER. 4. Would it be permissible to hard- wire the dishwasher in question 3? If so, under what conditions?

RESIDENTIAL OVER. 4. Would it be permissible to hard- wire the dishwasher in question 3? If so, under what conditions? WELCOME TO THE EASTERN SECTION CODE BREAKFAST CODE BREAKFAST QUESTIONS FOR THE EASTERN SECTION ANNUAL MEETING 93 rd ANNUAL EASTERN SECTION MEETING, KING OF PRUSSIA, PA RESIDENTIAL ALL QUESTIONS BASED ON

More information

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 1. Is a standard wire-nut approved for a wet location as in an outside j-box? Is there a listed

More information

2011 and 2014 National Electrical Code Changes Residential Only

2011 and 2014 National Electrical Code Changes Residential Only 2011 and 2014 National Electrical Code Changes Residential Only Sponsored By: and.net Instructor: Fritz Gunther, Chief Electrical Inspector 585-436-4460 www.nyeia.com NEW YORK ELECTRICAL INSPECTION AGENCY

More information

2017 NEC Presented by: Russ LeBlanc

2017 NEC Presented by: Russ LeBlanc 2017 NEC Presented by: Russ LeBlanc 1. 90.2(A)-installation and removal 2. 90.3-code layout 3. 100-readily accessible 4. 100-field evaluation body (FEB) 5. 100-field labeled 6. 100-receptacle 7. 100-structure

More information

NEC CODE QUESTIONS. Western Section IAEI 103 rd Annual Meeting September 17-19, 2007

NEC CODE QUESTIONS. Western Section IAEI 103 rd Annual Meeting September 17-19, 2007 NEC CODE QUESTIONS Western Section IAEI 103 rd Annual Meeting September 17-19, 2007 1. Can a fire pump controller be fed from a UPS? Or is a separate service and separate transfer switch required? 2. Section

More information

TOM BURNS, PLANNING DIRECTOR

TOM BURNS, PLANNING DIRECTOR ~~ 0 173 COUNTY OF SANTA CRUZ August 4,2005 PLANNING DEPARTMENT 701 OCEAN STREET, qth FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 TOM BURNS, PLANNING DIRECTOR Agenda:

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 17 From: Kimberly Shea, Project Administrator

More information

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 The City of Portsmouth adopts the State Building Code, which adopts by reference The National Electrical Code, 2017(NEC), as Chapter 15, Part IV, of the

More information

Residential Wiring (2017 NEC) (Homestudy)

Residential Wiring (2017 NEC) (Homestudy) Residential Wiring (2017 NEC) (Homestudy) Idaho Electrical License This course will cover the requirements in the 2017 NEC for installing electrical systems in dwelling units. Code sections for residential

More information

National Electrical Code

National Electrical Code National Electrical Code 409.30 Disconnecting Means Disconnecting means that supply motor loads shall comply with Part IX of Article 30. 410.81 Control (A) Disconnection Luminaires (fixtures) or lamp installation

More information

2014 National Electrical Code & NFPA 70E/Arc Flash

2014 National Electrical Code & NFPA 70E/Arc Flash Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the

More information

HVAC Equipment Access Equipment Location

HVAC Equipment Access Equipment Location City of Lancaster- Building Department 121 East Chestnut Street, Suite 102, Lancaster, Ohio 43130-3825 (740) 687-6649, Fax (740) 681-5030 Web site: www.ci.lancaster.oh.us/dept/building HVAC Heating, Ventilating,

More information

SDEC 2017 Questions, Group 1

SDEC 2017 Questions, Group 1 SDEC 2017 Questions, Group 1 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing? Answer: NEC 410.36(B)

More information

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS. Part I Administrative... 1 Part I Administrative............................ 1 CHAPTER 1 ADMINISTRATION............... 1 R101 Title, Scope and Purpose.................... 1 R102 Applicability.............................. 1 R103

More information

Residential Wiring (2014 NEC) (Homestudy)

Residential Wiring (2014 NEC) (Homestudy) Residential Wiring (2014 NEC) (Homestudy) Oregon Electrical License This course will cover the requirements in the 2014 NEC for installing electrical systems in dwelling units. Code sections for residential

More information

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices. SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance

More information

Graded Project. National Electrical Code

Graded Project. National Electrical Code Graded Project National Electrical Code National Electrical Code INTRODUCTION This next portion of your program is a project-based assignment designed for you to demonstrate your understanding of the

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

Electrical Systems. Electrical Plans. Electrical Plans. Essential to ensure. National Electrical Code (NES) Consider electrical needs.

Electrical Systems. Electrical Plans. Electrical Plans. Essential to ensure. National Electrical Code (NES) Consider electrical needs. Electrical Systems Electrical Plans Essential to ensure Proper wiring National Electrical Code (NES) Electrical Plans Consider electrical needs Office equipment Lighting E t t i t t Entertainment systems

More information

Residential Wiring According to 2011 NEC (Homestudy)

Residential Wiring According to 2011 NEC (Homestudy) Residential Wiring According to 2011 NEC (Homestudy) Utah Electrical License This course will cover the requirements in the 2011 NEC for installing electrical systems in dwelling units. Code sections for

More information

Spring Test 6 due 04/26/2013

Spring Test 6 due 04/26/2013 Spring Test 6 due 04/26/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. The article that covers TV wiring installations in residences

More information

PANELBOARDS & BUILDING DISTRIBUTION

PANELBOARDS & BUILDING DISTRIBUTION 262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic

More information

IEC and NCCER Mapping for Year 1

IEC and NCCER Mapping for Year 1 Craft: 26102-14 Safety IEC and NCCER Mapping for Year 1 Perform a visual inspection on various types of ladders 102.4 STATE GENERAL SAFETY CONSIDERATIONS IN ELECTRICAL INSTALLATIONS (LADDER SAFETY, SLECTION

More information

TECHNICAL ARTICLE. Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009

TECHNICAL ARTICLE. Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009 TECHNICAL ARTICLE Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009 Many inspectors were contractors in some prior life. The progression from contractor to inspecting

More information

For more information on the MARR program or any questions on the product list, please refer to or contact MARR at

For more information on the MARR program or any questions on the product list, please refer to   or contact MARR at Major Appliance Recycling Roundtable Updated Major Appliance Recycling Roundtable - and s Background: The following document provides a detailed list of products and relevant definitions captured by the

More information

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS City of Redwood City Community Development Department Building and Inspection Department 1017 Middlefield Road Redwood City, CA 94063 Phone (650) 780-7350 2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY

More information

Exhibit A. Mechnical, Plumbing, and Electrical Plan Check and Inspection Fees. Total Cost Per Unit FEE TYPES MECHANICAL PERMIT FEES

Exhibit A. Mechnical, Plumbing, and Electrical Plan Check and Inspection Fees. Total Cost Per Unit FEE TYPES MECHANICAL PERMIT FEES Mechnical, Plumbing, and Electrical Plan Check and Inspection Fees MECHANICAL PERMIT FEES FEE TYPES Total Cost Per Unit $ 180.36 Stand Alone Mechanical Plan Check (hourly rate) $ 180 UNIT FEES: Install/Relocate

More information

Kitchen south wall, living room north and south wall outlets 3. not working properly; no GFCI.

Kitchen south wall, living room north and south wall outlets 3. not working properly; no GFCI. UNIT # NOTES Receptacle in living room, south wall not working properly; 1 kitchen east, north, west wall receptacles have no power. Living room north wall outlet not working properly; kitchen 2 south

More information

NEC Study Guide CORRECT: C NEC (A)(1)

NEC Study Guide CORRECT: C NEC (A)(1) 1 According to the NEC, the maximum distance from the point of entrance to the building that the water pipe may be used as a grounding electrode interconnect is: A. 3' B. 4' C. 5' D. 6' CORRECT: C NEC

More information

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod Journeyman and Master Common Exam 2 1 The grounding terminal of a grounding-type receptacle installed in a metal box shall be? A. Connected to the equipment ground B. Bonded to the box C. Connected to

More information

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist

More information

AFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults?

AFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults? RECEPTACLEFAQs AFCI 1 What is an arc fault? UL provides a definition for an arc fault in UL 1699 (Standard for Safety Arc Fault Circuit Interrupters). It is an unintentional arcing condition in a circuit.

More information

Dwelling unit feeder/service conductor calculations

Dwelling unit feeder/service conductor calculations Dwelling unit feeder/service conductor calculations http://ecmweb.com/code-basics/dwelling-unit-feederservice-conductor-calculations Whether they're for journeymen, master electricians, or contractors,

More information

REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE 2003 IAEI 75 th JUBILEE MEETING

REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE 2003 IAEI 75 th JUBILEE MEETING REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE IAEI 75 th JUBILEE MEETING September 1, 2004 TO: SUBJECT: Attendees of Underwriters Laboratories Inc. Meetings with Electrical

More information

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xiii How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

Photovoltaic (Solar) Array Installation Guide

Photovoltaic (Solar) Array Installation Guide Building & Safety Division Community Development Department 7351 Rosanna Street, Gilroy, CA 95020 Phone: 408 846-0451 Fax: 408 846-0429 Visit us: www.cityofgilroy.org Photovoltaic (Solar) Array Installation

More information

CODE PANEL QUESTIONS

CODE PANEL QUESTIONS NORTH CAROLINA ELECTRICAL INSTITUTE 89 th ANNUAL MEETING APRIL 3-4, 2018 HILTON NORTH RALEIGH RALEIGH, NORTH CAROLINA CODE PANEL QUESTIONS Opinions of the Code Panelist are NOT interpretations issued by

More information

Residential Wiring According to the 2011 NEC

Residential Wiring According to the 2011 NEC Residential Wiring According to the 2011 NEC Utah Electrical License This course will cover the requirements in the 2011 NEC for installing electrical systems in dwelling units. Code sections for residential

More information

10606 Bloomfield Ave Santa Fe Springs, CA USA

10606 Bloomfield Ave Santa Fe Springs, CA USA IAS Accreditation Number FEB-103 Company Name eti Conformity Services Address 10606 Bloomfield Ave Santa Fe Springs, CA 90670 USA Contact Name Sam Daye Telephone (562) 236-9555 Effective Date of Scope

More information

Electrical Tech Note 107

Electrical Tech Note 107 Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State

More information

Habitability Guidelines

Habitability Guidelines Habitability Guidelines for Relocated Manufactured Homes dced.pa.gov/mh @PADCEDnews Purpose The purpose of these habitability guidelines is to provide a reasonable level of assurance that the relocated

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

General Kitchen, Bath & Bedroom Remodeling Notes County of Marin, Building Inspection Division

General Kitchen, Bath & Bedroom Remodeling Notes County of Marin, Building Inspection Division These Notes are intended to assist in issuing simple remodel permits. It provides information on the most common requirements relating to the construction or remodeling of kitchens, bathrooms and bedrooms.

More information

Emergency Generator Safety

Emergency Generator Safety Safety Installing and Operating s Key Points of Safety Read, understand and follow the manufacturer s instructions. Operate your generator outdoors in a clean, dry, well-ventilated area, and never indoors

More information

2010 Residential Ques. & Ans.

2010 Residential Ques. & Ans. 1.I am replacing several existing receptacles in an older apartment building because they no longer hold the plug securely. Do I need to install tamper resistant receptacles? Ans. No 406.11, 210.52, Comm.

More information

INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS

INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS RV Products Division INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330C755 CONTROL BOX KIT (12 VDC HEAT READY) 8530-750 CONTROL BOX KIT

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT RV Products Division INSTALLATION INSTRUCTIONS FOR 8330-5501 MOUNTING KIT 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330B755 CONTROL BOX KIT (12 VDC HEAT/COOL) 8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)

More information

Overview of Significant 2017 NEC Changes

Overview of Significant 2017 NEC Changes Overview of Significant 2017 NEC Changes National Fire Protection Association. All rights reserved. Five New NEC Articles Article 426 Fixed Resistance and Electrode Industrial Heating Equipment Article

More information

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Suppression Systems; and Chapter 34-National Electric

More information

2009 WESTERN SECTION CODE PANEL QUESTIONS

2009 WESTERN SECTION CODE PANEL QUESTIONS 2009 WESTERN SECTION CODE PANEL QUESTIONS 1. The local inspector red-tagged the temporary wiring for a new store of type III construction because he said Romex wasn t allowed to be run in the open according

More information

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2007

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2007 General: 1) (Q) May the gas be turned on temporarily to the gas piping system without the installation of the appliance? (A) NO! 2) (Q) Are traps required on all condensate drains from equipment? (A) Only

More information

Building & Safety PERMIT APPLICATION

Building & Safety PERMIT APPLICATION (661) 255-4935 PERMIT APPLICATION 1 Project Location Please complete all applicable fields. Optional fields are surrounded by dashes --------. Address: Assessor s Parcel No. (APN): Street Number Street

More information

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010 An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010 Putnam County Planning & Development Services Building & Zoning Division Compliance Section PO Box 1486 Palatka, FL 32178 1486 Office

More information

TABLE LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS ASHRAE Uncovered Parking Areas. Building Grounds. Walkways 10 feet wide or greater

TABLE LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS ASHRAE Uncovered Parking Areas. Building Grounds. Walkways 10 feet wide or greater TABLE 9.4.5 LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS ASHRAE 90.1 Uncovered Parking Areas Parking Lots and drives Building Grounds Walkways less that 10 feet wide Walkways 10 feet wide or greater

More information

Sundance Spas SPA EQUIPMENT SYSTEM. Installation Instructions. P/N Rev. A

Sundance Spas SPA EQUIPMENT SYSTEM. Installation Instructions. P/N Rev. A Sundance Spas SPA EQUIPMENT SYSTEM Installation Instructions P/N 6530-456 Rev. A Contents Important Notices 1 Important Safety Instructions 2 Where to Place the Equipment System 3 Connecting Pipes Between

More information

Municipal Code of Chicago TITLE 14E ELECTRICAL CODE

Municipal Code of Chicago TITLE 14E ELECTRICAL CODE Municipal Code of Chicago TITLE 14E ELECTRICAL CODE Ch. 14E-1 General Ch. 14E-2 Wiring and Protection Ch. 14E-3 General Requirements for Wiring Methods and Materials Ch. 14E-4 Equipment for General Use

More information

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators GPS 140 NEC Requirements for Generators WHAT YOU WILL LEARN NEC requirements for on-site power generation. Recent events have created increased interest in standby power This module organizes NEC requirements

More information

TABLE 1-E (2017) Effective July 1, 2017

TABLE 1-E (2017) Effective July 1, 2017 TABLE 1-E (2017) Effective July 1, 2017 Oregon Amendments to the 2017edition of the National Fire Protection Association (NFPA) 70, National Electrical Code (NEC) for the 2017 Oregon Electrical Specialty

More information

HEATER. Fan Forced IMPORTANT INSTRUCTIONS READ & SAVE OWNER S MANUAL. Model No.: DR W 120V 60Hz DR W 240V 60Hz

HEATER. Fan Forced IMPORTANT INSTRUCTIONS READ & SAVE OWNER S MANUAL. Model No.: DR W 120V 60Hz DR W 240V 60Hz Fan Forced HEATER OWNER S MANUAL Model No.: DR218-1500 1500W 120V 60Hz DR218-3000 3000W 240V 60Hz IMPORTANT INSTRUCTIONS READ & SAVE TABLE OF CONTENTS Important Instructions. 3 Specifications and Wiring

More information

Troy's Home Inspection Services LLC

Troy's Home Inspection Services LLC Cover Page Property Inspection Report 33706 Inspection prepared for: Cord King & Patricia King Real Estate Agent: Jane Freel - RE/MA Date of Inspection: 3/4/2017 Time: 8:30 Age of Home: 2008 Size: 3279

More information

SW District 1. 1 Tony Tadysak Craig Mulder

SW District 1. 1 Tony Tadysak Craig Mulder STATE OF WISCONSIN Department of Safety and Professional Services 1400 E Washington Ave. Madison WI 53703 Web: dsps.wi.gov Governor Scott Walker Secretary Dave Ross Electrical Program Web: Electrical Program

More information

Schedule of Approved Fees

Schedule of Approved Fees Schedule of BUILDINGMISCELLANEOUS Inspection not otherwise covered by a fee and is regulated by LA County Oridnance OCCUPANCY INSPECTIONS Group R or Group M Other Groups other than R or M (Floor Area)

More information

CONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA

CONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA American Electrical Institute 2014 PART 2 83 CONTINUING EDUCATION FOR OREGON ELECTRICIANS AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223 www.aeitraining.com 84 PART 3 American Electrical

More information

Program, Code Panel Questions, & Survey/Comments

Program, Code Panel Questions, & Survey/Comments NORTH CAROLINA ELECTRICAL INSTITUTE 90 th ANNUAL MEETING APRIL 9 th 10 th, 2019 HILTON NORTH RALEIGH RALEIGH, NORTH CAROLINA Program, Code Panel Questions, & Survey/Comments Opinions of the Code Panelist

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

I. STRUCTURAL SYSTEMS

I. STRUCTURAL SYSTEMS I. STRUCTURAL SYSTEMS A. Foundations Type of Foundation(s): Pier & Beam - Crawlspace Opinion: All exposed areas of the foundation were examined visually. Examination of the foundation was limited to photographs

More information

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING SEMINAR 301 Part 1: Changes in the 2005 NEC SEMINAR RULES: There are no Rules All Questions need to be asked Stop at any time for an explanation SEMINAR PARTS: ELECTRIC and NEON SIGN STANDARDS By Randy

More information

Alberta Municipal Affairs

Alberta Municipal Affairs Alberta Municipal Affairs Upcoming Already Approved by Unanimous Vote Not Required to be Considered in Charlottetown in June Clarence C. Cormier, P.Eng. Chief Electrical Inspector Bob Hall, SCO Electrical

More information

SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE

SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE ELECTRICAL CODE COMMITTEE SEPTEMBER 12, 2012 PREFACE This document was developed by the Southern Nevada Building Officials Electrical

More information

Installation Instructions

Installation Instructions Installation Instructions Electric Drop-In Range JDS28, JDP39 Questions? Call 800.GE.CARES (800.432.2737) or Visit our Website at: ge.com BEFORE YOU BEGIN Read these instructions carefully and completely.

More information

Mechanical Systems Submittal Guide

Mechanical Systems Submittal Guide 5200 Dover Center Road 440-777-8000 North Olmsted, OH 44070 North-Olmsted.com Mechanical Systems Submittal Guide Residential Code of Ohio (RCO) n applicant is free to submit any mechanical systems description

More information

NZECP 19: 1994 ISSN COVER PAGE

NZECP 19: 1994 ISSN COVER PAGE NZECP 19: 1994 ISSN 0114-0663 COVER PAGE NZECP:19 1994 NEW ZEALAND ELECTRICAL CODE OF PRACTICE for DETERMINATION OF MAXIMUM DEMAND in ELECTRICAL INSTALLATIONS Issued by the Office of The Chief Electrical

More information

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES LIGHT LEVEL REQUIREMENTS LOCATION Classrooms and instrumental areas- Study Halls, Lecture Rooms, Art Rooms, Offices, Libraries, Conference Rooms, Work Rooms, Shops, Laboratories and Secondary School Cafeterias.

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY RV Products Division INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY DESIGNED AND MANUFACTURED BY THE MAKERS

More information

NORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided:

NORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided: Housekeeping/Laundry/Maintenance NORTH CAROLINA Downloaded 01.15.11 (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided: (3) a soiled utility room with counter,

More information

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT RV Products Division INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330A755 CONTROL BOX KIT (12 VDC HEAT/COOL) 8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)

More information

Revisions for the 2011 National Electrical Code - Part 1

Revisions for the 2011 National Electrical Code - Part 1 PDHonline Course E355 (3 PDH) Revisions for the 2011 National Electrical Code - Part 1 Instructor: Patrick Ouillette 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FCP2400D FCP3000D FCP3600D FCP4200D FCP4800D FCP6000D FCP2400C FCX2400C FCP3000C FCP3600C FCX3600C FCP4200C FCP4800C FCX4800C FCP6000C FCX6000C Require AMF001NHA Accessory No

More information

Dear Concessionaire,

Dear Concessionaire, Dear Concessionaire, In order to provide a comprehensive review & inspection of the Vendor application please review the following as guidance to a complete application and preparedness for inspection.

More information

Effingham County Health Department "Where Prevention Begins" 901 West Virginia Phone (217) Effingham, Illinois Fax (217)

Effingham County Health Department Where Prevention Begins 901 West Virginia Phone (217) Effingham, Illinois Fax (217) Effingham County Health Department "Where Prevention Begins" 901 West Virginia Phone (217) 342-9237 Effingham, Illinois 62401 Fax (217) 342-9324 Opening a Food Establishment in Effingham County Guidelines

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

NEC CODE QUESTIONS and ANSWERS Wisconsin Chapter IAEI Green Lake, Wisconsin May 16-18, 2012

NEC CODE QUESTIONS and ANSWERS Wisconsin Chapter IAEI Green Lake, Wisconsin May 16-18, 2012 NEC CODE QUESTIONS and ANSWERS Wisconsin Chapter IAEI Green Lake, Wisconsin May 16-18, 2012 1. Can we install 120 Volt conductors in the same space with 277 Volt conductors? If the answer is yes, are there

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

District 1. 1 Tony Tadysak Craig Mulder

District 1. 1 Tony Tadysak Craig Mulder STATE OF WISCONSIN Department of Safety and Professional Services 1400 E Washington Ave. Madison WI 53703 Web: dsps.wi.gov Governor Scott Walker Secretary Dave Ross Electrical Program Web: Electrical Program

More information