REG NO FM BS EN ISO HEADER TANK HEAT EXCHANGER. Installation, Operation & Maintenance Guide
|
|
- Dina Olivia Casey
- 6 years ago
- Views:
Transcription
1 REG NO FM BS EN ISO HEADER TANK HEAT EXCHANGER Installation, Operation & Maintenance Guide
2 Foreword Dear Customer, BOWMAN has been manufacturing high quality header tank heat exchangers for over 30 years. Your BOWMAN Stockist/dealer will be happy to provide you with advice and practical assistance. Please read these instructions fully and carefully. Keep the Installation, Operation & Maintenance Guide for future reference. All rights reserved E.J. Bowman (Birmingham) Ltd, reserve the right to change specification and technical alteration without prior notice. No part of this guide may be reproduced or transmitted in any form or by any means including reproduction or recording without written permission from E.J. Bowman (Birmingham) Ltd. 2
3 H E A D E R T A N K H E A T E X C H A N G E R Installation, Operation & Maintenance Guide Contents Foreword 2 1. S A F E T Y 1.1 Hazards when handling the heat exchanger Approved use Potential hazards 4 2. I N S T A L L A T I O N 2.1 Transport / storage Fitting Connecting the heat exchanger Notes on zinc anodes 6 3. O P E R A T I O N 7 4. C O M M I S S I O N I N G 7 5. M A I N T E N A N C E / R E P A IR 5.1 General maintenance Cleaning End cover bolt tightening sequence 8 6. PO T E N T I A L S E R V I C E I S S U E S 6.1 Tube failures Fault finding 9 7. WA R R A N T Y S P A R E P A R T S C E M A R K I N G 10 E.J.Bowman (Birmingham) Ltd Chester Street Birmingham B6 4AP United Kingdom Tel: +44 (0) Fax: +44 (0) info@ejbowman.co.uk website: 3
4 1 Safety 1.1 Hazards when handling the heat exchanger BOWMAN Hydraulic Oil Coolers are constructed to current practice and recognised safety standards. Hazards may still arise from operation, such as: - Injury of the operator or - Third parties or - Damage to the heat exchanger or - Damage to property and equipment Any person involved with the installation, commissioning, operation, maintenance or repair of the heat exchanger must be: - Physically and mentally capable of performing such work - Appropriately qualified. - Comply completely with the installation instructions The heat exchanger must only be used for its intended purpose. In the event of breakdowns which may compromise safety a suitably qualified person must always be contacted. 1.2 Approved use BOWMAN Header tank heat exchangers are only approved for cooling engine jacket water. Any other use unless specified by BOWMAN is not approved. BOWMAN declines all liability for damage associated or arising from such use. The maximum permissible operating pressure must not exceed: Engine Jacket Water : 1.0 bar max. (Filler cap rating dependant) Cooling Water (secondary side) : 15 bar max. Applies to EH-PH three pass threaded connections only for other versions please contact BOWMAN for guidance. The maximum permissible operating temperature must not exceed: Engine Jacket Water : 110 Deg.C Cooling Water (secondary side) : 110 Deg.C Variants with higher temperature and pressure ratings are available. Please contact the Sales for further details. 1.3 Potential hazards Ensure the maximum permissible operating pressure on the primary or secondary side of the heat exchanger is not exceeded. The heat exchanger or surrounding equipment may be damaged. NB: before the oil cooler is disconnected it must be allowed to cool sufficiently and be depressurized to prevent injury. The supply and returns to the heat exchanger should be isolated to minimise fluid loss. 4
5 2 Installation 2.1 Transport / storage The heat exchanger must be fully drained down prior to transportation. Once drained and fully dry, the heat exchanger must only be stored indoors within a non aggressive atmosphere. The connections should be capped to avoid ingress of dirt and contaminants. 2.2 Fitting Before fitting, the heat exchanger should be checked for visible signs of damage. The header tank should be mounted horizontally and above the cylinder head level and with the engine water circuit arranged so that it self-venting on initial filling. The unit should be connected as shown below: A by-pass type thermostat should be used and arranged so that only the heat exchanger is by-passed when the engine is cold. All the other components including a water jacketed exhaust manifold if fitted, any oil coolers, charge air coolers and exhaust gas heat exchangers should be positioned in the circuit so that they always receive the full flow of the engine water pump. Thermostats of the type used on some automotive engines, which simply interrupt the cooling water flow when the engine is cold, are not recommended. For unattended operation, automatic engine shut down equipment should be provided. A filter with a maximum permeability of 2.5mm should be used prior to the inlet of the cooling water circuit. Nothing should be welded to any part of the header tank. Each unit has threaded holes on its underside to facilitate mounting. 5
6 2.3 Connecting the heat exchanger Shut off all drainage valves in the flow and return pipes of the primary and secondary circuits. When fitting the heat exchanger into the pipe work care must be taken to ensure that no debris has been introduced into the primary or secondary circuit of the heat exchanger. Unsupported lengths of pipework should be avoided so as not to subject the heat exchanger to excessive loads. Water side pipework diameter should not reduce to less than the connection size within a distance of 1m from the oil cooler. Measures should be taken to isolate the header tank heat exchanger from excessive vibration. Taper fittings are not recommended as these can split the shell and end cover castings if over tightened. The correct length of fitting should be used as too long a fitting will damage the tubestack. Pipework materials must be compatible with the heat exchanger materials. Stainless steel sea water pipes and fittings should not be used adjacent to the heat exchanger. If the sea water supply is taken from the ships main, ensure that the recommended flow rate cannot be exceeded. This will normally mean that an orifice plate must be fitted in the pipe work at least 1m before the cooler with the orifice size calculated to ensure that the maximum sea water flow rate cannot be exceeded. If these precautions are not taken, it is possible that the sea water flow rate through the cooler may be several times the recommended maximum which will lead to rapid failure. For our header tank heat exchangers, the maximum permitted cooling water flow rates are stated in the header tank brochure available to download from the Bowman website. The maximum cooling water flow rate varies and is dependent on the cooling water used (fresh water or sea water) and how many passes the water makes on the tube side (single pass, two pass or three pass). 2.4 Notes on zinc anodes The use of zinc anodes in heat exchangers has been employed for some years, generally by manufacturers using admiralty brass tube or its variants. The purpose of the zinc anode, or zinc pencil as it is sometimes called, is to prevent dezincification of the brass alloy tubes. As such zinc anode acts sacrificially in favour of the tube. There are a number of American and European manufacturers that use these anodes in their products. Bowman, do not fit zinc anodes as the tubes used in the construction of our heat exchangers are of copper nickel alloy and as such do not require a zinc anode. It is possible that if this anode is fitted it can actually destroy the copper oxide film built up by the tube as a natural defence which can allow the tube material to be attacked. It is usual with the copper nickel alloys to use an iron anode which allows an iron oxide film to build up inside the tube which breaks down as a sacrificial element reducing the possibility of corrosion to the heat exchanger. In Bowman designs it is not practical to fit iron anodes as their size has to be very generous. Therefore as an alternative a piece of black iron pipework can be placed before the heat exchanger which in itself acts as sacrificial element protecting the cooler. The Royal Navy has often used this technique and when the black iron pipework corrodes, it is simply replace with a fresh piece. We do know that some manufacturers of heat exchangers, mostly those providing copies of the better known products, often fit zinc anodes incorrectly with copper nickel alloys in error. 6
7 3 Operation It is essential that the following instructions are followed to prevent corrosion/erosion of the heat exchanger: a) Always maintain the water ph to within correct levels. The ideal water ph should be kept within 7.4 to 7.6. On no account should it fall below 7.2 or above 7.8. b) Maximum fluid velocity through the tube side of 2m/s for sea water (maximum sea water flow rates are detailed in the Header tank brochure) or 3m/s for fresh water must not be exceeded. If in doubt contact BOWMAN for guidance. c) Minimum tube side water velocity of 1m/s should be used. d) Ensure compliance with water quality and maximum permissible pressure requirements. e) Air must be adequately vented from both circuits. f) Stagnant water should not be allowed to accumulate in the heat exchanger. If it is not in use for any period of time the water should be drained off. 4 Commissioning Commissioning of the heat exchanger should not be undertaken until such time that this document has been fully read and understood. The primary and secondary circuits of the heat exchanger must be fully closed prior to commissioning. Adequate provision should be made to ensure that correct operating/service equipment along with personal protection (PPE) in accordance with current standards/legislation is utilised prior to the commencement of any working. Both circuits should be vented initially and again when operating temperatures and pressures are reached. The system should be checked for leaks. 5 Maintenance / Repair 5.1 General maintenance While the unit is in operation, weekly inspection of the heat exchanger and its connections should be maintained for leaks and externally visible damage. BOWMAN recommend that the tubestack should be cleaned and inspected annually and the O ring seals should be renewed at this time. Removal of the screws around the periphery of each end cover will allow the end covers and seals to be removed. The tubestack can then be withdrawn from either end of the body. 7
8 5.2 Cleaning Any cleaning solutions used must be compatible with the heat exchanger materials. This should be confirmed with the chemical s supplier before use. The chemical solution can be circulated through the heat exchanger or the unit can be disassembled and the tubestack submerged in a container filled with cleaning fluid. If necessary the fluid should be neutralized after cleaning and the unit should be flushed with fresh water and dried. Small diameter rods and brushes for tube cleaning are available from companies such as Easy Products Replacement O rings should be fitted and the end cover bolts should be initially be hand tightened then tightened in the sequence and to the torque figures below: Oil Cooler Series Bolt Size Torque (Nm) Oil Cooler Series Bolt Size Torque (Nm) EH M6 8 KH M12 54 FH M8 22 JH M16 95 GH M10 37 PH M End cover bolt tightening sequence End covers must be refitted in the correct orientation to ensure correct performance. 8
9 6 Potential Service Issues 6.1 Tube failures The majority of problems facing a heat exchanger are those of corrosion or erosion on the water side. Three common types of failure are: a) Impingement attack (or corrosion/erosion) This is caused by water containing air bubbles flowing at high speed through the tubes. The impingement of rapidly moving water may lead to a breakdown of the protective copper oxide film built up by the tube thus allowing corrosion/erosion. This is worse with water containing sand or grit. The effect of these conditions would be pockmarking and pinholing of the tubes. b) Oxide corrosion This is caused by water containing organic matter such as that found in polluted estuaries. Usually this water produces hydrogen sulphide, which is very corrosive and can cause failure of the tubes, particularly if excessive water flows are used c) Pitting This problem is caused by very aggressive sea water in the tubes, especially in partially filled coolers where the sea water is stagnant. Low sea water flow rates can create a high temperature rise on the sea water side. Under these conditions deposits may build or settle in the tube, allowing pitting corrosion to take place under the deposits. This is only a brief introduction to corrosion problems. The subject is complex and the purpose of these notes is to outline in very general terms what may occur under extreme conditions. 6.2 Fault finding Symptoms Possible Causes Remedy Increase in temperature on shell side or excessive pressure loss Pressure loss is as expected, but the temperature of the engine water rises Engine water leaking into the cooling water circuit or vice versa Inadequate performance Tube scaling or build up resulting in an insulating film covering the tubes Film, scale or restrictions on the inside of the tubes Split or perforated tubes Flow rates too low Unit connected in parallel flow The complete heat exchanger should be thoroughly cleaned The complete heat exchanger should be thoroughly cleaned Tubes should be blocked with hard wooden plugs as a temporary measure & the tubestack replaced asap Check flow rates & increase if necessary Reconnect in counterflow as per section 2.2 9
10 7 Warranty All BOWMAN Header tank heat exchangers are guaranteed against manufacturing and material defects for a period of twelve months from the date of delivery. BOWMAN should be contacted immediately if a unit is received damaged. No attempt should be made to repair a faulty unit as this will invalidate the warranty. For full warranty terms, please see the BOWMAN Conditions of Sale. A copy of which is available on request or via download from the website: 8 Spare Parts A comprehensive stock of spare parts is always available. Please contact our sales department for price and availability or nearest stockist. 9 CE Marking Documentation Heat exchangers are covered by the Pressure Equipment Directive 97/23/EC which is mandatory for all EU member states.. This manual is part of the compliance and points out all essential safety requirements to be observed. BOWMAN Header Tank Heat Exchangers fall within the Sound Engineering Practice category of the Pressure Equipment Directive 97/23/EC and as such cannot be CE marked. 10
11 Bowman products can also be found in the following industries: - CHP Power Generation Engine Test House Cooling Marine Cooling Swimming Pool Heating Fishing Industry Cooling The product range includes: - Aquatic Heat Exchangers Calorifiers Exhaust Gas Heat Exchangers Hydraulic Oil Coolers Plate Type Heat Exchangers Shell & Tube Oil Coolers Stainless Steel Heat Exchangers Swimming Pool Heat Exchangers 11
HYDRAULIC OIL COOLER. Installation, Operation & Maintenance Guide
HYDRAULIC OIL COOLER Installation, Operation & Maintenance Guide HYDR AULIC OIL C OOLER Installation, Operation & Maintenance Guide Contents Foreword 2 1. SAFETY 1.1 Hazards when handling the heat exchanger
More informationHYDRAULIC OIL COOLER Installation, Operation & Maintenance Guide
REG NO FM 38224 BS EN ISO 9001-2008 HYDRAULIC OIL COOLER Installation, Operation & Maintenance Guide Foreword Dear Customer, BOWMAN has been manufacturing high quality hydraulic oil coolers for over 60
More informationInstallation, Operation & Maintenance Guide
REG NO FM 38224 BS EN ISO 9001-2008 SWIMMING POOL HEAT EXCHANGERS For use with Boilers, Solar Panels & Heat Pumps Installation, Operation & Maintenance Guide Foreword Dear Customer, Congratulations on
More informationREG NO FM BS EN ISO EXHAUST GAS HEAT EXCHANGERS. Installation, Operation & Maintenance Guide
REG NO FM 38224 BS EN ISO 9001-2008 EXHAUST GAS HEAT EXCHANGERS Installation, Operation & Maintenance Guide Foreword BOWMAN has been manufacturing high quality "Exhaust Gas Heat Exchangers" for over 30
More informationHeader Tank Heat Exchangers
Header Tank Heat Exchangers Heat Transfer Technology from owman Heat Exchanger Technology by World Leader in Heat Exchanger Technology Staying cool under owman Header Tank Heat Exchangers For marine propulsion
More informationInstallation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier
OM001 Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier These operating and maintenance instructions are for standard semi-storage calorifiers (vessels fitted with
More informationInstallation, Operation and Maintenance Instructions for Electric Storage Calorifier
OM004 Installation, Operation and Maintenance Instructions for Electric Storage Calorifier The operating and maintenance instructions contained within this package are for standard electric storage calorifiers
More informationInstallation, Operation and Maintenance Instructions Electric Flow Heater OM009
Installation, Operation and Maintenance Instructions Electric Flow Heater OM009 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail: sales@gmsthermal.co.uk
More informationSwimming Pool Heat Exchangers
Swimming Pool Heat Exchangers BSP/PN6/10/16 Connections Heat Transfer Technology from Bowman Heat Exchanger Technology by A World Leader in Heat Exchanger Technology Bowman Dominates Swimming Pool Heat
More informationInstallation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers
Bulletin 1200/4 (Revised 5/12) Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers INNOVATORS IN HEAT TRANSFER I. INSTALLATION OF HEAT EXCHANGERS A. HEAT EXCHANGER SETTINGS 1)
More informationRycroft Storage & Non-Storage Calorifiers. Installation, Operation & Maintenance Manual
Ormandy Rycroft Duncombe Road Bradford BD8 9TB England TEL +44 (0)1274 490911 FAX +44 (0)1274 498580 www.rycroft.com Rycroft Storage & Non-Storage Calorifiers Installation, Operation & Maintenance Manual
More informationGreenstar System Filter
Installation and Servicing Instructions Greenstar System Filter For sealed and open vented central heating systems with 22 or 28mm central heating pipes 672087500-00.Wo UK/IE 6 720 87 500 (205/07) Contents
More information4 route 147, C.P.33 Coaticook, Qc J1A 2S8
4 route 147, C.P.33 Coaticook, Qc J1A 2S8 TABLE OF CONTENTS INSTALLATION Nozzles p.3 Clearance for dismantling p.4 Foundations p.4 Foundation bolts p.5 Leveling p.5 Bolted joints p.5 Recommended bolt tightening
More informationInstallation and Maintenance Manual Forbes Marshall Tracer Line Trap FMMST63
Installation and Maintenance Manual Forbes Marshall Tracer Line Trap Energy Conservation Environment Process Efficiency www.forbesmarshall.com Table of Contents 1. Preface...1 2. Important Safety Notes...1
More informationInstallation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010
Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail:
More informationSERVICE MANUAL. For Service & Parts please call APK THERMAL at or SAFETY INSTRUCTION
SERVICE MANUAL Installation, Operation and Maintenance Manual for Standrd Pre-Engineered Shell & Tube Models BCF, HCF, HFF, SSCF & SX2000 Fixed Tube Sheet Heat Exchangers For Service & Parts please call
More informationWATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00
I&M NUMBER: 316-42-8-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to
More informationZIP Varipoint III. Installation, Maintenance and User Instructions. Models VP303, VP503 VP803, VP953 direct unvented water heaters. Issued August 2008
Varipoint cover qxd:varipoint cover qxd 22/8/08 11:14 Page 1 Installation, Maintenance and User Instructions ZIP Varipoint III Models VP303, VP503 VP803, VP953 direct unvented water heaters Issued August
More informationGeneral Maintenance and Operating Instructions for Heat Exchangers
General Maintenance and Operating Instructions for Heat Exchangers Preamble Due to the diversity of operating conditions and the necessity for transparency and clarity of presentation, the maintenance
More informationSteam Trap BK 45 BK 45-U BK 45-LT BK 46
Steam Trap BK 45 BK 45-U BK 45-LT BK 46 Original Installation Instructions 810437-08 Contents Foreword... 3 Availability... 3 Formatting features in the document... 3 Safety... 3 Use for the intended purpose...
More information! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or
I&M NUMBER: 316-42-10-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to
More informationPedestal Range. Installation and user manual. Kiosk. Trafalgar. Tube. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk
Pedestal Range Installation and user manual Kiosk Trafalgar Tube Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk Contents Introduction 2 Declaration of conformity 3 Symbols used in this guide 3
More informationWATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00
I&M NUMBER: 316-42-5-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Watlow heaters are built to comply with UL and CSA dielectric requirements, it may be
More informationTechnical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT
Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT
More informationTREVI BLEND SINGLE LEVER SHOWER VALVES. INSTALLER After installation pass to user for future reference
11 A4000, A4100 & A4110 TREVI BLEND PARTS LIST Ref. Description 1 Lever handle complete 1a/1b Nut and washer 2 Handle cover cap 3 Shield 4 Cover plate fixing screw 5.1 Cover plate for built in version
More informationWATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00
I&M NUMBER: 316-42-2-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to elements
More informationOPERATING AND MAINTENANCE MANUAL FOR VERTICAL IMMERSION HEATED STEAM BOILERS. Technical Control Systems Limited MODELS "VIHS"
OPERATING AND MAINTENANCE MANUAL FOR VERTICAL IMMERSION HEATED STEAM BOILERS Technical Control Systems Limited MODELS "VIHS" Technical Control Systems Ltd Treefield Industrial Estate Gildersome, Leeds
More informationHozelock Ltd. Midpoint Park, Birmingham B76 1AB. England Tel: +44 (0)
7825 flood PUMP Hozelock Ltd. Midpoint Park, Birmingham B76 1AB. England Tel: +44 (0) 121 313 1122 info@hozelock.com www.hozelock.com 33713-001? 1 AUTO ON AUTO OFF 400mm 190mm 2 3 25mm 32mm 4 5 50cm 50cm
More informationADVANCE ELECTRIC THERMAL STORE
ISSUE 13 1118 INSTALLATION AND USER GUIDE ADVANCE ELECTRIC THERMAL STORE ADVANCE APPLIANCES LTD HOUSEHOLDER PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE. 2 INTRODUCTION Advance thermal
More informationUSER MANUAL INSTALLATION INSTRUCTIONS WARRANTY REGISTER
USER MANUAL INSTALLATION INSTRUCTIONS WARRANTY REGISTER GREENGLO MAINS PRESSURE INTEGRATED WATER HEATER SINGLE COIL SERIES & DOUBLE COIL SERIES GREENGLO SAVER Customer Congratulations for choosing a GreenGlo
More informationsubmersible water pumps
instructions for submersible water pumps model no s: WPC100.V2 WPC100A.V2 WPC150.V2 WPC150A.V2 WPC235.V2 WPC235A.V2 WPC250 WPC250A Thank you for purchasing a Sealey product. Manufactured to a high standard,
More informationEN transition from BS 1387 Structural & Conveyance Business
Corus Tubes EN 10255 transition from BS 1387 Structural & Conveyance Business EN 10255 A smooth transition with Corus Install Contents 1 Introduction 2 The new standard 4 Detailed comparison 7 Comparison
More informationORIGINAL INSTRUCTIONS
WARNING: Read the instructions before using the machine. POWER WASHER MODEL NO: JETSTAR 1950 PART NO: 7336010 OPERATION & MAINTENANCE INSTRUCTIONS ORIGINAL INSTRUCTIONS LS0617 - ISS 3 INTRODUCTION Thank
More informationSelf-help Temperature Adjustment
Self-help Temperature Adjustment The Shower Valve temperature is pre-set to 42 C, but on certain installations the temperature may need to be adjusted. Note: The hot water supply must be above 60 C. Turn
More informationLONGONI ENGINEERING SRL
INDEX 1.1 Classification of heat exchanger and components 1.1.2 Type of heat exchanger and components 1.2 Purpose and scope of the manual 1.3 General instruction 1.4 Warning installation 1.5 Notes for
More informationWATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.
I&M NUMBER: 316-42-3-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to elements
More informationSB Series Brazed Plate Heat Exchanger Installation Manual
SB Series Brazed Plate Heat Exchanger Installation Manual HOT COLD Exploded view of Schmidt SB Brazed Plate Heat Exchanger. WARNING Before proceeding with installation and operation read entire manual
More informationInstallation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers
OM010 Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers The operating and maintenance instructions contained within this package are for ThermaFlex gasketed
More informationCROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15
CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 COMPACT PLUS 10 and 15 Litre Unvented Under and Over Sink Water Heater INSTALLATION AND USER GUIDE 1 DIMENSIONS 10L - 250mm 15L - 310mm 100mm 80mm 410mm
More informationAXUS - SC Short Cased Axial Flow Fans Installation and Maintenance
1.0 INTRODUCTION AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance The Nuaire Short Cased Axial Fan range is produced in a range of sizes from 250mm to 1600mm diameter. Cases are manufactured
More information1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450
1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside
More informationTarget Monobloc Kitchen Mixer Chrome
Target Monobloc Kitchen Mixer Chrome Installation Instructions & User Guide Please keep these instructions for future reference and request of replacement parts Contents Thank you for choosing Bristan,
More informationOK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.
INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance
More informationCENTRIFUGAL PUMPS OPERATING INSTRUCTIONS
CENTRIFUGAL PUMPS OPERATING INSTRUCTIONS Please leave this instruction booklet with the pump as it contains maintenance and safety information (Original Instructions) MODELS This operating manual covers
More informationInstallation Guide. Termix Distribution unit. 1.0 Table of Contents. 1.0 Table of Contents
1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................
More informationMini Tender Section 1.1 External Wall Insulation, Mechanical and Electrical Installation
Mini Tender Section 1.1 External Wall Insulation, Mechanical and Electrical Installation BOILER ONLY INSTALLATION ALL ITEMS BLEOW SHOULD BE INCLUDED WITHIN TENDER COST OR CONSIDER WITHIN BIDDERS SUBMISSION
More informationTECHNICAL NOTICE GH/GHO/GAE V
TECHNICAL NOTICE GH/GHO/GAE V1.0-02.14 INDUSTRIAL COOLING UNITS Identification Marksa SA Industrial cooling 39, avenue du Technicum CH-2400 Le Locle Version Date Modifications 1.0 14.02.14 First edition
More informationBeeline Monobloc Kitchen Mixer Tap
Beeline Monobloc Kitchen Mixer Tap Installation Instructions & User Guide Please keep these instructions for future reference and request of replacement parts Contents Thank you for choosing Bristan, the
More informationInstallation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013
Installation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail:
More informationFriwa Compact. Operating instructions EN
Operating instructions EN Version 1.1 / Edition 09/2013 Contents 1 Key background information... 3 1.1 Limitation of liability... 3 1.2 Responsibilities of the operator... 3 1.3 Documentation... 3 1.3.1
More informationContents. Commissioning 6 Operation 6 Routine Preventative Maintenance 6 Fault Finding 7 Spares Parts 8 Technical Support 9
Contents Product Description 2 Approvals 2 Warranty 2 Warnings 2 Technical Specification 3 Installation 4 Location 4 Plumbing Connection 4 Electrical connection 5 Commissioning 6 Operation 6 Routine Preventative
More informationVIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors
Service instructions for contractors VIESMANN Vitocell 300-B Type EVB DHW cylinder, 300 and 500 l Vitocell 300-V Type EVI DHW cylinder, 200 to 500 l For applicability, see the last page VITOCELL 300-B
More information½ Monitored Pneumatic Valve Patented Technology
½ Monitored Pneumatic Valve Patented Technology PBM4-S (Valve only air service equipment not included) SUITABLE FOR RISK CATEGORY 4 APPLICATIONS As per AS4024.1-Part 1502 & 1502 SIL 3 as per IEC 61508
More informationDecade Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference and request of replacement parts
Decade Tap Range Installation Instructions & User Guide Please keep these instructions for future reference and request of replacement parts Contents Thank you for choosing Bristan, the UK s leading taps
More information1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material
1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside
More informationDOMESTIC WATER RECORDS
DOMESTIC WATER RECORDS LEGIONELLA LOG BOOK RESPONSIBLE SITE STAFF PARSONS HALL INDUSTRIAL ESTATE HIGH STREET IRCHESTER NORTHANTS NN29 7AB TEL: 01933 410066 FAX: 01933 410077 www.beaconwater.co.uk DOMESTIC
More informationThermostatic Concealed Shower Valve
Thermostatic Concealed Shower Valve Product may differ from image. Please retain this booklet for future aftercare reference Component Breakdown - Three Handle Valve Component breakdown Two Handle Valve
More informationPear Kitchen Sink Tap
Pear Kitchen Sink Tap Installation Instructions & User Guide Please keep these instructions for future reference and request of replacement parts Contents Thank you for choosing Bristan, the UK s leading
More informationThe Professional s Choice
SureFlow compact range: 1000-C & 1000-M Auto-Fill Catering Water Boiler Installation And User Instructions The Professional s Choice CONTENTS CONTENTS & INTRODUCTION 2 SAFETY & ENVIRONMENTAL INFORMATION
More informationADVANCE ECB ELECTRIC COMBINATION BOILER
ISSUE ISSUE 45 0115 0317 INSTALLATION AND USER GUIDE ADVANCE ECB ELECTRIC COMBINATION BOILER ADVANCE APPLIANCES LTD HOUSEHOLDER - PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE 1 SCHEMATIC
More informationPRESSURE WASHER MODEL NO: JETSTAR 1750 OPERATION & MAINTENANCE INSTRUCTIONS. WARNING Read the instructions before using the machine PART NO:
WARNING Read the instructions before using the machine PRESSURE WASHER MODEL NO: JETSTAR 1750 PART NO: 7333230 OPERATION & MAINTENANCE INSTRUCTIONS LS0711 INTRODUCTION Thank you for purchasing this CLARKE
More informationM07. Wunda Premium Manifold. Before you start: Check the contents THE BRAND YOU CAN TRUST
Before you start: Check the manifold box contents against the list below. Check the contents 1. 2 x Manifold end blanks 2. 2 x Manual air vent & drain cocks 3. 2x Adjustable mounting brackets 4. Manifold
More informationInstallation and Maintenance Manual Forbes Marshall Bucket Trap FMBT50
Installation and Maintenance Manual Forbes Marshall Bucket Trap Energy Conservation Environment Process Efficiency www.forbesmarshall.com Table of Contents 1. Preface...1 2. Important Safety Notes...1
More informationMODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS
MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS 1. FEATURES The Type N Trap range is particularly suitable for high pressure/high temperature trapping applications
More informationClyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw
90 kw Clyde Alkon 90 LP Gas Floor standing condensing boilers Natural Gas 90 kw Contents General information Dimensions and Data Installation requirements Boiler wiring diagram Hydraulic systems Page Fully
More informationINSTALLATION, OPERATION & MAINTENANCE MANUAL
CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid
More informationSurface Warm Ceiling Heaters
CONSORT Wireless controller CRX2 SLPB SLTI SLVT SLVTB Surface Warm Ceiling Heaters Catalogue Numbers HE7237SL, HE7247SL, HE7267SL, HE7237RX, HE7247RX, HE7267RX Installation and Operating Manual INDEX Section
More informationKinetic. Logic. Astin. THERMOSTATIC INLINE CONTROL SHOWER VALVES Installation & aftercare instructions. Please retain for future reference
THERMOSTATIC INLINE CONTROL SHOWER VALVES Installation & aftercare instructions Please retain for future reference DUAL INLINE CONCEALED VALVE SKN0201, SAS0201, SLG0202 SKN0202, SAS0205 TRIPLE INLINE CONCEALED
More informationINSTRUCTION MANUAL (English version) Water still
INSTRUCTION MANUAL (English version) Water still Model : Brand : W4000 Merit Merit Water Still W4000 & W4000/EURO Cooling water inlet Condenser Constant level control Boiler Thermostat reset buttons To
More informationPanel Radiators. Installation and operating instructions. ThermaRad Classic.
ThermaRad Hurlcon Panel Radiators Installation and operating instructions ThermaRad Classic ThermaDesign ThermaStyle www.hurlconheating.com.au enquiries@hurlconheating.com.au Melbourne: 03 9554 2275 Sydney:
More informationInverted Bucket Steam Traps
INSTALLATION AND MAINTENANCE INSTRUCTIONS IM-2-00-US December 201 Inverted Bucket Steam Traps Safety Information Safe operation of these products can only be guaranteed if they are properly installed,
More informationTechnical Checklist - Plumbing and Heating Fittings - UK Sizes
Technical Checklist - Plumbing and Heating Fittings - UK Sizes July 2008 NOTE: This checklist refers exclusively to fittings and accessories from our range of push-fit products for Plumbing and Heating
More informationMonitored Pneumatic Valves On Series Ported Manifold
Monitored Pneumatic Valves On Series Ported Manifold Patented Technology SUITABLE FOR RISK CATEGORY 4 APPLICATIONS As per EN 954-1 & AS4024.1 SIL 3 as per IEC 61508 Applications Include: Pneumatic Presses
More informationInta City Concealed Shower Mixing Valve CT80010CP
Inta City Concealed Shower Mixing Valve CT80010CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept
More informationSURFACE WARM CEILING HEATERS
SURFACE WARM CEILING HEATERS CATALOGUE NUMBERS HE7237, HE7247, HE7267, HE7237RF, HE7247RF, HE7267RF INSTALLATION AND OPERATING MANUAL INDEX Section General information ------------------------------------------------------------1
More informationWATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2
I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to
More information!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!
Sample Written Program For Your Company For BOILER SAFETY Provided By: P.O. Box 2136 Slidell, LA 70458 Phone: 985-781-1444 Fax: 985-781-1446 Email: info@se-safety.com Purpose Boiler Safety Program The
More informationInstallation, Operation & Maintenance Instructions
Installation, Operation & Maintenance Instructions Please leave this instruction booklet with the owner as it contains important guarantee, maintenance and safety information Read this manual carefully
More informationHOT WASHER MODEL NO: KING150
WARNING: Do not use the hot washer without reading this manual HOT WASHER MODEL NO: KING150 PART NO: 7320175 OPERATION & MAINTENANCE INSTRUCTIONS LS1215 INTRODUCTION Thank you for purchasing this CLARKE
More informationINSTALLATION & USER INSTRUCTIONS
INSTALLATION & USER INSTRUCTIONS LED ELECTRIC STOVE Christchurch, Dorset BH23 2BT Tel: 01202 588 638 Fax: 01202 499 639 www.ekofires.co.uk e-mail: sales@ekofires.co.uk MODELS COVERED BY THESE INSTRUCTIONS
More informationInstallation Instructions Flute Tap Range
Installation Instructions Flute Tap Range Models covered: FLT BAS C, FLT 1HBF C, FLT 2HBSM C, FLT TBAS C Please keep this booklet for future reference. Installer, when you have read these instructions
More informationTechnical information. Remeha P 500. Pressurized boiler. Heat output: kw
Technical information Remeha P 500 R e m e h a P 5 0 0 Pressurized boiler Heat output: 635-1900 kw Remeha P 500 TABLE OF CONTENT Preface 3 1 Description of the unit 3 1.1 General 3 1.2 Burners 3 2 Construction
More informationPRODUCT GUIDE. High performance heating system filter Improves energy efficiency Captures magnetic and nonmagnetic.
PRODUCT GUIDE High performance heating system filter Improves energy efficiency Captures magnetic and nonmagnetic debris No block design Fits in Minutes, Protects for Years Black ferrous oxide or sludge
More informationEKF. EC kitchen extract fan range. Installation and Wiring Instructions. Stock Ref. N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3
EKF EC kitchen extract fan range Installation and Wiring Instructions Stock Ref. N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3 PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH THE ILLUSTRATIONS.
More informationTo dismantle and reassemble domestic Gas Geyser i.e. Gas Water Heater
Experiment No. 1 Aim To dismantle and reassemble domestic Gas Geyser i.e. Gas Water Heater Objective 1) To study construction and working of Gas Geyser 2) To study the problems associated and rectify the
More informationParenzo Range. Basin Mixer, Bath Filler & Bath Shower Mixer. Assembly instructions
Parenzo Range Basin Mixer, Bath Filler & Bath Shower Mixer Assembly instructions We have designed these products with your enjoyment in mind. To ensure that they work to their full potential, they need
More informationGEM TRAP FITTING & MAINTENANCE INSTRUCTIONS
GEM TRAP FITTING & MAINTENANCE INSTRUCTIONS IMPORTANT Please read these instructions before fitting any traps. The following pages describe how each type of GEM Trap should be installed. If you are unsure
More informationS and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions
0772150/4 IM-P077-02 ST Issue 4 S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning
More information½ Monitored Pneumatic Valves On Series Ported Manifold
½ Monitored Pneumatic Valves On Series Ported Manifold Patented Technology SUITABLE FOR RISK CATEGORY 4 APPLICATIONS As per AS4024.1-Part 1502 & 1502 SIL 3 as per IEC 61508 & EN ISO 13849-1 Applications
More informationConcealed Twin & Triple Thermostatic Shower Valve with Diverter. Installation & Operating Guide
Concealed Twin & Triple Thermostatic Shower Valve with Diverter Installation & Operating Guide Please leave this installation & user guide with the end user CONTENTS: 1. Important information 1 2. Cleaning
More informationAIRE. Thermostatic bath shower mixer. Installation and Operating Instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER
AIRE Thermostatic bath shower mixer Installation and Operating Instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER 2180427C October 2005 CONTENTS Page Introduction 1 Safety
More informationInstruction Manual M6627 / Version 7.4. Slide Drying Bench MH6616 MH6616X1
Instruction Manual M6627 / Version 7.4 Slide Drying Bench MH6616 MH6616X1 Please take your time to read this Instruction Manual in order to understand the safe and correct use of your new Electrothermal
More informationRECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL
HSPBRF HSTIRF HSVTRF RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL INDEX Section General information -----------------------------------------------------------
More informationBath Shower Mixer
86004490 Bath Shower Mixer Installation and operating instructions The showerhead and hose supplied with this product are a safety critical part of your shower. Failure to use genuine Triton parts may
More informationInstallation and Maintenance Manual
Installation and Maintenance Manual Forbes Marshall Thermodynamic Trap Energy Conservation Environment Process Efficiency www.forbesmarshall.com Table of Contents 1. Preface...1. Important Safety Notes...1
More informationENERSTORE. Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER
ENERSTORE Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER Newark Copper Cylinder Co Ltd Brunel Drive Newark Notts. NG24 2EG Tel: 01636 678437 Fax: 01636 678964 Internet: www.newarkcoppercylinder.co.uk
More informationCENTRIFUGAL PUMPS OPERATING INSTRUCTIONS
CENTRIFUGAL PUMPS OPERATING INSTRUCTIONS Please leave this instruction booklet with the pump as it contains maintenance and safety information (Original Instructions) MODELS Kennet K7-2 Kennet K9-2 Kennet
More informationTwin & Triple Exposed Thermostatic Shower Valve Installation & Operating Guide
Twin & Triple Exposed Thermostatic Shower Valve Installation & Operating Guide Please leave this installation & user guide with the end user CONTENTS 1. Important information 1 2. Cleaning & Aftercare
More informationCOMMERCIAL ELECTRIC WATER HEATER OWNER S MANUAL OPERATION AND MAINTENANCE INSTRUCTIONS
COMMERCIAL ELECTRIC WATER HEATER OWNER S MANUAL OPERATION AND MAINTENANCE INSTRUCTIONS Make sure to follow the instructions mentioned in this manual in order AVERTISSEMENT to reduce the risk of fire, explosion,
More informationPerforma 24 Eco HE. User Guide and Important Warranty Information. Condensing Combination Boiler
0 4 You can rely on User Guide and Important Warranty Information Performa 4 Eco HE Condensing Combination Boiler Please keep these instructions in a safe place. If you move house, please hand them over
More information