Technical guide Pro-Pac H HY. Air/water heat pumps

Size: px
Start display at page:

Download "Technical guide Pro-Pac H HY. Air/water heat pumps"

Transcription

1 Technical guide Pro-Pac H HY Air/water heat pumps

2 Comprehensive support Comprehensive engineering support is provided by our experienced and well qualified team. Calorex units are designed, tested and manufactured in the UK, and supported by our comprehensive customer service organisation Calorex reserves the right to modify these specifications at any time. For accurate sizing please contact Calorex.

3 Contents Calorex model system identification 4 Air/water heat pumps 5 The heat pump cycle 6 Installation 7 1. Siting/positioning 7 2. Air flow 8 3. Plumbing 9 4. Typical installation diagram 9 Electrical 10 Specification of Calorex Pro-Pac BH BHY 12 What is a WRAS approval? 13 Technical data Heat pumps, specialist applications heaters H models 14 Heat pumps, specialist applications heaters HY models 15 Performance graphs 16 Installation drawings 18 Winterising procedure 23 Start up procedure after winterisation 23

4 Calorex model system identification PP B H Y Heat pump with reverse cycle defrost, operation down to -15 C Heat pump down to 7 C ambient H=water flow up to 70 C M= water flow up to C Electrical supply 0V ~ 3N ~ Hz Model size Product "Pro-Pac" 4

5 Air/water heat pumps Models covered in this manual The machines detailed in this manual are specifically designed for heating potable water. The heat pumps use R134a as a refrigerant and operate in air temperatures from 7 C to 55 C providing heated water to 68 C. As an option, machines are available with reverse cycle defrost which allows the heat pumps to operate in temperatures down to -15 C. All units are supplied as a package and have integral safety devices to protect the heat pump from internal and external faults. Indicator lamps indicate operating mode. An adjustable thermostat controls water temperature. Also a six minute cycle time delay is incorporated. The units are weatherproof and can be installed either outside or within a ventilated plant-room (as detailed in section 1 of this manual). A 12 hour delay timer is incorporated into machines, which after a power interruption or from initial start up will prevent the machine compressor(s) from starting for a 12 hour period. This feature is to protect the compressors from liquid pumping which can cause internal compressor damage. Health and Safety This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance Important Note Calorex heat pumps Limited is an ISO9001:2000 certified company. All Calorex heat pumps are CE approved. Heat exchangers within the heat pumps are compliant to WRAS (British Water Regulation Authority Standards) and listed under UL standards. 5

6 The heat pump cycle The Calorex heat pump provides thermodynamic heating by means of a vapour compression cycle, (similar to that employed in a conventional refrigerator), in addition to operating as an active solar collector. The COMPRESSOR, where it is compressed, which has the effect of upgrading the gas to a much higher temperature. The electrical energy that is used to drive the compressor is also absorbed by the refrigerant gas. The hot gas now enters: The EVAPORATOR collects the heat from the air. This is either atmospheric air, which has been heated by the sun, or internal air, which has been heated by heat lost from another process. In Calorex heat pumps, high volumes of air are drawn into the unit by the fan and passed across the evaporator fins. The evaporator has liquid refrigerant passing through it, which is at a considerably lower temperature than the ambient air. Therefore the air gives up its heat to the refrigerant which then vaporises to a gas. This pre-heated refrigerant gas then passes to: THE HEAT PUMP CYCLE HOT GAS COMPRESSOR COOL GAS WATER OUT AMBIENT AIR HEAT EXCHANGER EVAPORATOR WATER IN CONDENSED REFRIGERANT HIGH PRESSURE SIDE EXPANSION VALVE COLD LIQUID REFRIGERANT LOW PRESSURE SIDE The HEAT EXCHANGER (or CONDENSER), where it is surrounded by the water to be heated in adjacent tubes. The refrigerant vapour, at a higher temperature, gives up its heat to the water which is returned to a storage tank. As the refrigerant cools it returns back to its liquid state, i.e. it condenses, but remains under high pressure from the compressor. The pressure is released by passing the liquid refrigerant through: The EXPANSION DEVICE, and from there, now at normal pressure, it is returned to the evaporator and the cycle starts again. Coefficient of Performance The efficiency of a heat pump is usually called its Coefficient of Performance (C.O.P.) which is simply a ratio of heat output to energy input, both being expressed in. Thus a heat pump absorbing 1 of electricity, collecting 4 of energy from the air, and delivering 5 of heat to the water is said to have a C.O.P. of 5:1. Naturally this ratio will vary according to the temperature of the ambient air. 6

7 Installation 1. Siting/positioning a) Ensure heat pump on site is as ordered, i.e. model, electrical supply and factory fitted options. b) Inspect unit for damage, in particular inspect the evaporator (finned side) to ensure that it is undamaged. (Minor indentations in the fins do not affect performance). If severely damaged, endorse delivery note in presence of the driver and send a recorded delivery letter to transport company giving details. c) Protect unit if installation is delayed. d) Provide a firm level base capable of supporting operational weight of unit; spread load on timber floor. e) Ensure water cannot collect under unit recommend units are installed on plinths 100mm above finished floor level and to also aid condensate drainage. f) Allow adequate clearance to service panels on unit; recommend 0mm minimum (see installation drawings). g) All Calorex heat pumps are by design as quiet as is practical, however due consideration should be given to siting in order to fully exploit this feature, i.e. ensure that the inlet and outlet grilles face away from occupied property. h) Ensure loose debris such as leaves, grass cuttings, etc will not block air inlet grilles. i) Consider protection from extreme weather conditions if installed externally, i.e. lean-to-cover or building. 7

8 Installation cont. 2. Air flow Due consideration must be given to air flow, i.e. do not obstruct inlet or outlet and ensure discharge air cannot recirculate to inlet (See figures 1 and 2). Fig. 1 Fig. 2 Typical outside installation Typical inside or plant-room installation (not recommended for long duct runs) Grill or apertures MUST comply with figures (see table 1) Required free areas to provide air flow to and from heat pumps when installed in an enclosed area or where required to pass air through a wall, etc. Free area is the available area that air can pass through a grille or louvres. BUT discharge from each unit must be kept separate and must not be incorporated into one common duct system. 2. If the unit is installed within a plant-room, connected to ductwork, Calorex can supply the unit with an uprated fan motor. Please consult Calorex before ordering a unit. 1. Note: If multiple units are installed in an enclosed area then the inlet free areas required for each unit can be added together to form one inlet aperture. Table 1 Model Minimum Free Area m² Inlet Discharge Pro-Pac Pro-Pac Pro-Pac Pro-Pac Pro-Pac

9 Installation cont. 3. Plumbing a) Calorex Pro-Pac range heat pumps have water inlet/outlet connections as follows: Table 2 Model Pro-Pac Pro-Pac 45 Pro-Pac 70 Pro-Pac 90 Pro-Pac 1 Water in/out connection size 1½" BSPM 1½" BSPM 1½" BSPM 1½" BSPM 2" BSPM b) If an existing heater is retained, the Calorex heat pump should be connected in parallel with it. c) Suitable breakable couplings, isolating valves and flow meters should be installed local to the heat pump. d) Drain valve or plug should be fitted to lower pipe to facilitate drain down in winter period. e) The condensate drain at the base of the unit collects condensation from the evaporator fins. This should be run away to waste via 1½" domestic waste piping. It is therefore necessary to ensure that the Calorex heat pump is placed on a level plinth so that the condensate can run away with adequate fall to waste i.e. ½" per foot minimum. A U trap should also be incorporated into the pipework f) When the pipework installation is complete the system should be run and tested for leaks. If everything is then working normally the water circulating system is ready to use. g) Water circuit to and from unit to be capable of maintaining within specified limits the rate of flow required by heat pump (see data sheet). h) All pipework must be adequately supported with allowance for expansion/contraction especially with plastic pipework. i) It is recommended that when installing water system the last connections to be made in the system should be breakable couplings to avoid any stresses on to the unit connections. 4 Typical installation diagram AIR VENT CALOREX HEAT PUMP STORAGE TANK CLOSED TYPE HOT WATER SUPPLY HOT WATER RETURN PUMP DRAIN VALVE MAKE UP COLD WATER Important note Maximum pressure of water in heat pump circuit should not exceed 10 bar. 9

10 Electrical Electrical (machine wiring and supply) All electrical work to be carried out in accordance with I.E.E. standards, latest issue, or local codes of practice as applicable. Fig. 4 The machine should be installed in accordance with EMC2004/108/EC. Location of mains input and external interlock terminals Protected supply To incorporate fuses or motor type circuit breakers (Type GU, FAZC) to specified rating, (see Data Sheet). H.R.C. fuses are recommended. An isolator which disconnects all poles must be fitted within 2m and in sight of machine.* All units must be correctly earthed-grounded and an earth leakage trip installed. Inconsistent electrical supply The following limits of operation must not be exceeded if Calorex machines are to be guaranteed either in performance or warranty terms. Voltage Minimum Maximum Three-phase machines (UK) 3V 4V Three phase machines (Hz) 187V 253V Three phase machines + N (Hz) 3V 4V Cycle frequency (Hz) 47.5Hz 52.5Hz Cycle frequency (Hz) 57.0HZ 63.0Hz Interlock These units have an interlock circuit incorporated into the control circuit, brought out to two terminals. These terminals are shorted out for factory testing. On site the shorting loop is to be removed and two wires taken to a pair of volt free contacts in the water pump starter/ contactor/relay or flow switch so that the heat pump cannot operate unless the water pump is operating. (See figures 5 and 6). N.B. This voltage must be available at the heat pump whilst running. The voltage must not drop below the above figures when starting the machine. *Note the isolator must have a minimum of 3mm air gap when turned off. Note All machines are fitted with a phase protection relay and will not run if the phases are not connected in correct order (phase sequence) or if the supply voltage is 15% less than the nominal voltage. (415V for 3N~ Hz). The lamp on the phase rotation relay, situated in the electric box, is illuminated when the phases are correctly connected and the voltage is sufficient. The under voltage protection feature is not present in phase protection relays fitted in 220V 3~ Hz machines. 10

11 Electrical Electrical (machine wiring and supply) Fig. 5 Recommended electrical installation for Calorex heat pump with single phase water pump Fig. 6 Recommended electrical installation for Calorex heat pump with three phase water pump 11

12 Specifications Calorex Pro-Pac BH BHY Automatic hot water heat pumps The heat pump shall be a packaged design with all necessary refrigeration / control functions fitted within the unit as a hermetically sealed system. The cabinet shall be weatherproof to IP24. The machine chassis shall be constructed of 14 gauge hot dipped galvanised steel and all panels exposed to ambient conditions shall be 20 gauge steel, phosphate protected and plastisol coated to RAL7038 Agate Grey (fixed panels) or RAL9002 Grey White (service panels) semi-gloss. The air-cooled evaporator shall be constructed from rifled copper tube, aluminium fins and end-plates, all phenolically coated to prevent corrosion from airborne contaminants and salt. The water-cooled condensers shall be of tube in shell type constructed from copper (tube) and steel (shell). WRAS approved condensers with 90/10 marine grade cupro-nickel (tube) shall be available as an option. The condensers shall be of seamless construction and the maximum working water pressure shall be 10 bar. BH models shall be provided with a defrost limit thermostat to provide automatic evaporator defrosting. BHY models shall be provided with fully automatic reverse cycle defrost mechanism to give operation down to -15ºC air temperature. All units are designed, assembled and individually tested in the UK under ISO 9001:2008 accreditation. All units are designed, assembled and individually tested in the UK under ISO 9001:2008 accreditation. Optional features The following optional features shall be available on request: WRAS approved cupro-nickel condensers Compressor soft-start High pressure fan RS485 compatible thermostat The Pro-Pac shall utilise a 0mm, 880rpm vertical discharge axial owlet fan. The Pro-Pac 45 and 90 shall utilise a 710mm, 690rpm, vertical discharge, axial fan (two for the Pro- Pac 90). The Pro-Pac 70 and 1 shall use an 800mm, 700rpm vertical discharge, axial fan (two for the Pro-Pac 1). Fans shall be ERP 2015 compliant FE2 owlet rated to IP 54. The compressor shall be a fully compliant hermetic, high back pressure, scroll unit with built in overload protection. The Pro- Pac 90 and 1 shall utilise twin scroll compressors. The refrigeration circuit shall utilise R134a refrigerant and contain a sight glass, drier and expansion valve control, reversing valve and pump down valve. Suction accumulators shall be sized for 100% of the unit refrigerant capacity. The refrigeration circuit shall be protected by HP, LP, thermal overloads, MCBs, phase rotation protection and delay timers. The refrigeration circuit shall be capable of operating in air temperatures ranging from 10 C to C and water temperatures up to 68 C. Heating operation shall be controlled by an integral digital water thermostat with a 4 C differential. 12

13 What is a WRAS approval? Any water fitting which, when installed, will carry or receive water from the public mains water supply in the UK, must comply with the Water Supply (Water Fittings) Regulations or Scottish Byelaws. These require that a water fitting should not cause waste, misuse, undue consumption or contamination of the water supply and must be of an appropriate quality and standard. Operational envelope Water off temperature ( C) Air temperature ( C) 13

14 Technical data Heat pumps, specialist applications heaters H models Pro-Pac BH Pro-Pac 45BH Pro-Pac 70BH Pro-Pac 90BH Pro-Pac 1BH Units Duty - output to C/55 C Air C, 90%RH Electrical input Air 20 C, %RH Electrical input Air 10 C, 85%RH Electrical input 24.5/ / / / / /6.5.6/ / / / / / /.7 9.1/ / / / / / / / / / / / / / / / /23.9 Electrical data Electrical supply ( Hz, 3PH) Minimum supply capacity (3PH) Recommended supply fuse (3PH) Max starting curent STD (LRA) Max starting current soft start (LRA) V amps amps amps amps Air data Nominal air flow Fan external resistance Fan external resistance (F) m³/h Pa Pa 50 0 n/a Water Data Water flow ±10% Pressure drop (water) Water connections Condensate water connections l/min m hd inch inch BSPM General data Gas charge (R134a) BH Compressor type Fan type Sound pressure 3m AIR ON Sound 3m AIR OFF Sound 3m SIDE kg db(a) db(a) db(a) x SCROLL 1 x AXIAL x SCROLL 1 x AXIAL x SCROLL 1 x AXIAL x 2 2 x SCROLL 2 x AXIAL x 2 2 x SCROLL 2 x AXIAL Dimensions Width (unpacked) Depth (unpacked) Height (unpacked) Weight (unpacked) mm mm mm kg Width (export, packed) Depth (export packed) Height (export, packed) Weight (export, packed) mm mm mm kg NOTES: 1) Weight and dimensions nett. 2) Allow 0mm clearance to service panels. 3) Minimum air temperature standard models (BH) 7 C. 4) Calorex reserve the right to change or modify models without prior notice. 5) Global warming potential (GWP) R134a 10. 6) Performance data below 10 C is derated to account for defrost periods. 1 mm WG = 9.8 Pa 1 m hd = 1.4 psi 1 l/min = 0.22 gall/min 14

15 Technical data cont. Heat pumps, specialist applications heaters HY models Pro-Pac BHY Pro-Pac 45BHY Pro-Pac 70BHY Pro-Pac 90BHY Pro-Pac 1BHY Units Duty output to C/55 C Air C, 90%RH Electrical input Air 20 C, %RH Electrical input Air 10 C, 85%RH* Electrical input Air 0 C, 90%RH Electrical input Air -3 C, 99%RH Electrical input 24.5/ / / / / / / / / /6.6.6/ / / / / / / / / / /.7 9.1/ / / / / / / / / / / / / / / / / / / / / / / / / / / / /24.25 Electrical data Electrical supply ( Hz, 3PH) Minimum supply capacity (3PH) Recommended supply fuse (3PH) Max starting current STD (LRA) Max starting current soft start (LRA) V amps amps amps amps Air data Nominal air flow Fan external resistance Fan external resistance (F) m³/h Pa Pa 50 0 n/a Water Data Water flow ±10% Pressure drop (water) Water connections Condensate water connections (optional factory fit) l/min m hd inch inch BSPM General data Gas charge (R134a) BH Compressor type Fan type Sound pressure 3m AIR ON Sound 3m AIR OFF Sound 3m SIDE kg db(a) db(a) db(a) 17 1 x SCROLL 1 x AXIAL x SCROLL 1 x AXIAL x SCROLL 1 x AXIAL x 2 2 x SCROLL 2 x AXIAL x 2 2 x SCROLL 2 x AXIAL Dimensions Width (unpacked) Depth (unpacked) Height (unpacked) Weight (unpacked) mm mm mm kg TBA TBA TBA TBA Width (export, packed) Depth (export packed) Height (export, packed) Weight (export, packed) mm mm mm kg TBA TBA TBA TBA NOTES: 1) Weight and dimensions nett. 2) Allow 0mm clearance to service panels. 3) Minimum air temperature standard models (BH) 7 C. Reverse cycle defrost models (BHY) -15 C. 4) Calorex reserve the right to change or modify models without prior notice. 5) Global warming potential (GWP) R134a 10. 6) Performance data below 10 C is derated to account for defrost periods. * use selection overleaf 1 mm WG = 9.8 Pa 1 m hd = 1.4 psi 1 l/min = 0.22 gall/min 15

16 Performance graphs.00 PPBHY Water temperature ( C) Heat output () Heat output to water () Water temperature ( C) Power input () Air temperature ( C) PP45BHY Water temperature ( C) Heat output () Heat output to water () Water temperature ( C) Power input () Air temperature ( C) 16

17 .00 PP70BHY Heat output to water () Water temperature ( C) Water temperature ( C) Heat output () Power input () Air temperature ( C) PP90BHY Water temperature ( C) Heat output ().00 Heat output to water () Water temperature ( C) Power input () Air temperature ( C) PP1BHY Heat output to water () Water temperature ( C) Water temperature ( C) Heat output () Power input () Air temperature ( C) 17

18 Installation drawings Propac Pro-Pac Dimensions in in mm Allow 0mm for access to to service panels Allow 1000mm clearance in in front of of evaporator Allow 00mm clearance above machine Water connections 1½" BSPM Condensate 1½" 18

19 Installation drawings cont. Pro-Pac 45 Dimensions in mm Allow 0mm for access to service panels Allow 1000mm clearance in front of evaporator Allow 00mm clearance above machine Water connections 1½" BSPM Condensate 1½" 19

20 Installation drawings cont. Pro-Pac 70 Dimensions in mm Allow 0mm for access to service panels Allow 1000mm clearance in front of evaporator Allow 00mm clearance above machine Water connections 1½" BSPM Condensate 1½" 20

21 Installation drawings cont. Pro-Pac 90 Dimensions in mm Allow 0mm for access to service panels Allow 1000mm clearance in front of evaporator Allow 00mm clearance above machine Water connections 1½" BSPM Condensate 1½" 21

22 Installation drawings cont. Pro-Pac 1 Dimensions in mm Allow 0mm for access to service panels Allow 1000mm clearance in front of evaporator Allow 00mm clearance above machine Water connections 2" BSPM Condensate 1½" 22

23 Winterising procedure Warning Isolate machine before opening! As the heat pump embodies electrical and rotational equipment, it is recommended for your own safety that a competent person carries out the following procedure. Drain down procedure ALL MODELS Objective To provide frost protection To eliminate corrosion problems To inhibit electrical components 1. Switch off electric supply to heat pump. 2. Remove external fuses and keep in safe place away from heat pump to prevent accidental operation of heat pump. 3. Ensure water circulation pump is switched off. 4. Drain water from heat pump by: a drain valve if fitted. b disconnecting pipework to and from heat pump. c note that on units fitted with more than one condenser, there are also multiple drain down points. Each condenser water circuit will need to be drained when the winterisation process is carried out. 5. Flush through water circuit in heat pump by using CLEAN TAP WATER via hose into outlet connection run for 10 minutes minimum; use spray nozzle if available. 6. Allow to drain, after draining fit plastic bags secured by elastic bands over water connections. 7. Uncover electrical enclosure (see page 10) and liberally spray interior of unit with moisture-repellant aerosol WD or similar; reseal enclosure. 8. If heat pump located outside, protect from weather by covering with VENTILATED cover. Do not use plastic sheet as condensation can occur within unit. Start up procedure after winterisation 1. Replace covers (if not fitted). 2. Remove front grille using soft brush clean finned surfaces of heat pump. Replace panel. 3. Remove plastic covers on water connections and reconnect water piping or close drain valve. 4. Start up water circulating pump and leave running for at least 1/4 hour to establish flow and enable any air in piping to escape. 5. Replace fuses to heat pump circuit. 6. Switch on heat pump. 7. Check control thermostat is set to required pool temperature. 8. Check daily to ensure water is at correct ph (if applicable) and has correct chemical balance. See warranty conditions. N.B. If this procedure is not adopted and frost or corrosion damage results then the warranty will become invalid. 23

24 Technical support and service Comprehensive technical support is provided by our experienced and well qualified team Calorex Heat Pumps Ltd The Causeway Maldon Essex CM9 4XD United Kingdom t. +44 (0) e. w. calorex.com Pro-Pac technical guide v1.1 24

CALOREX TECHNICAL GUIDE PRO-PAC H HY. Air/water heat pumps

CALOREX TECHNICAL GUIDE PRO-PAC H HY. Air/water heat pumps PRO-PAC 30 45 70 90 140 H HY Air/water heat pumps Comprehensive support Comprehensive engineering support is provided by our experienced and well qualified team. Calorex units are designed, tested and

More information

Owner Installation Manual for PROPAC 30/45/70/90/140 M/MY AIR/WATER HEAT PUMPS (SD ISSUE 28) 18/03/11 CONTENTS

Owner Installation Manual for PROPAC 30/45/70/90/140 M/MY AIR/WATER HEAT PUMPS (SD ISSUE 28) 18/03/11 CONTENTS Owner Installation Manual for PROPAC 0/4/70/90/40 M/MY AIR/WATER HEAT PUMPS (SD66 ISSUE 8) 8/0/ CONTENTS AIR/WATER HEAT PUMPS... THE HEAT PUMP CYCLE... INSTALLATION... 4. SITING... 4. AIR FLOW... 4. PLUMBING...

More information

Installation Manual Compac 6/8

Installation Manual Compac 6/8 OWNER AND INSTALLATION MANUAL FOR COMPAC 6/8 SWIMMING POOL HEAT PUMPS (SD636650 Iss.2 23/12/10) Health and Safety Warning: As the heat pump includes electrical and rotational components it is required

More information

Installation Manual PPT8/12/16/22LX/LY SLIMLINE

Installation Manual PPT8/12/16/22LX/LY SLIMLINE OWNER/INSTALLATION MANUAL FOR (SD638153 Iss.10 08/11/12) Health and Safety Warning: As the heat pump includes electrical and rotational components it is required that only trained and competent persons

More information

Heat Cool system. Take control of your pool heating and cooling with the Calorex 34 and new Pro-Pac ranges

Heat Cool system. Take control of your pool heating and cooling with the Calorex 34 and new Pro-Pac ranges Heat Cool system Take control of your pool heating and cooling with the Calorex 34 and new Pro-Pac ranges Full range of heat pumps for indoor and outdoor use Zero ozone depleting refrigerant Specifically

More information

Condensing Units CUS 15-60

Condensing Units CUS 15-60 Condensing Units CUS 15-60 General Description UNIT IDENTIFICATION AIR COOLED CONDENSING UNIT CUS... Condensing Unit with Propeller Fan and Scroll Compressor 15-60... Model Size D... Double Circuit e.g....

More information

Saving energy comes naturally to us.

Saving energy comes naturally to us. Domestic Heat Pumps Saving energy comes naturally to us. Low carbon solutions for heating and hot water The sustainable heating solution for today and tomorrow Home heating with lashings of hot water Whether

More information

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS TC SERIES OPTIONS TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15,, 5 AIR COOLED PACKAGED WATER CHILLERS CONTENTS EQUIPMENT AND COMPONENT DETAILS PERFORMANCE AND TECHNICAL DATA SCHEMATIC FLOW & SYSTEM

More information

High temperature air-to-water heat pumps

High temperature air-to-water heat pumps Designed to replace conventional boilers and produce domestic hot water 4 High temperature hot water (+65 C) 4 Winter operation (-20 C) 4 High energy efficiency (CP) 4 Compact and quiet 4 Scroll compressors

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N E S A RE F R E IG RA N T G TECHNICAL MANUAL -FRIEND Y CONDENSING UNITS FOR OUTDOOR INSTALLATION O L CMA C 2 The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual,

More information

PRODUCT RANGE POOL HEATING AND COOLING. Swimming pool heat pumps, heat cool systems and water chillers

PRODUCT RANGE POOL HEATING AND COOLING. Swimming pool heat pumps, heat cool systems and water chillers PRODUCT RNGE POOL HETING ND COOLING Swiing pool heat pumps, heat cool systems and water chillers BOUT THE DNTHERM GROUP Control your climate The Dantherm Group is a leading provider of climate control

More information

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017 Zeta Rev LN HP 10.2 Configured unit accessories 1PS - One user-side pump with tank LN - Low noise RG - Condensation control with fan speed regulator CSP - Set point compensation depending on external air

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION ECO-FRIENDLY REFRIGERANT GAS INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies Pakistan s Largest Manufacturers of Air-Conditioners PACKAGE TYPE UNIT FOR MOBILE APPLICATIONS Provides Turnkey Projects Conceptual Planning to Commissioning of HVACR Projects THE LARGEST MANUFACTURER

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Compact, Self-Contained unit that offer low installation cost plus dependable performance. 0 Compact, Self-Contained unit that offer low installation cost plus dependable performance. From carrier s excellence in engineering come a new, compact of single package horizontal and vertical water

More information

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax: TECHNICAL MANUAL CX(E) SPLIT SYSTEMS CONTENTS INDEX PART NUMBERS, OPTIONS, UNIT COMBINATIONS, DIMENSIONS & WEIGHTS 3 PERFORMANCE DATA & AIR FLOW 4 SOUND POWER AND SOUND PRESSURE LEVELS 5 ELECTRICAL DATA

More information

2 shp 13 lc 1 36 t - 1 a

2 shp 13 lc 1 36 t - 1 a HEAT PUMPs 2SHP3 PRODUCT SPECIFICATIONS Dry Charge Split System - 60 HZ Bulletin No. 20645 July 203 Supersedes June 202 3 to 5 Tons MODEL NUMBER IDENTIFICATION 2 shp 3 lc 36 t - a Refrigerant Type 2 =

More information

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors infolinia: +48 691 262 691-15 C +63 C +43 C E.V.I. HP The series of high efficiency heat pumps has been specifically designed for use with

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

Technical Data OPA 101, 150, 180. Ducted Three Phase Packaged Air Conditioner kw 18.5 kw. Extra Long Life Epoxy Coated Outdoor Coil

Technical Data OPA 101, 150, 180. Ducted Three Phase Packaged Air Conditioner kw 18.5 kw. Extra Long Life Epoxy Coated Outdoor Coil Ducted Three Phase Packaged Air Conditioner Technical Data, 0, 180 Extra Long Life Epoxy Coated Outdoor Coil Nominal Cooling Capacity 10.0 kw 18.5 kw JUNE 5 , 0, 180 DUCTED PACKAGED ROOF TOP AIR CONDITIONERS

More information

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1 UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS GPE 802 Kc + CF + GP + MV + P1 130 Above picture is only indicative and is not binding. AIR R-410A

More information

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB R407C EASY_R Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans 5,2 41,5 kw T_ESY_R_0508_GB EASY_R R407C INDEX WORKING LIMITS... 3 SERIES IDENTIFICATION... 4 MODEL

More information

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz EN Technical Catalogue Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: 321-1308 kw 50 Hz EKV/BS business Air cooled water chillers for outdoor installation. Flexibility in the

More information

Technical Data Ducted Three Phase Split System Air Conditioner

Technical Data Ducted Three Phase Split System Air Conditioner ENERGY EFFICIENT ISD / OSA 2 Technical Data Ducted Three Phase Split System Air Conditioner EXTRA LONG LIFE EPOXY COATED OUTDOOR COIL Nominal Cooling Capacity 26.5 kw (Total) JUNE 4 ISD / OSA 2 DUCTED

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

R407C Cellar Cooling. Fansets: Single phase, high efficiency, low

R407C Cellar Cooling. Fansets: Single phase, high efficiency, low R07C Cellar Cooling Introduction The New Cellarmaster from Climate Center is a simple cost effective range to provide cooling for the smaller cellars within the beer and wine cooling industry. A small

More information

ACCENT AIR WATER TO WATER COMMERCIAL HEAT PUMPS

ACCENT AIR WATER TO WATER COMMERCIAL HEAT PUMPS ACCENT AIR WATER TO WATER COMMERCIAL HEAT PUMPS CONTENTS Overview 2 Features & Benefits 3 Performance 4 Accent Pool Water to Water Heat Pumps Technical 5 Accent Hot Water Water to Water Heat Pumps Technical

More information

CENTRAL SPLIT UNIT UNIC

CENTRAL SPLIT UNIT UNIC CENTRAL SPLIT UNIT UNIC sal is equipped to produce a wide range of COOLER Air conditioning and Refrigeration units, conforming to the international standards and works continually to improve its products

More information

LZT High efficiency air to water heat pumps with E.V.I. compressors

LZT High efficiency air to water heat pumps with E.V.I. compressors High efficiency air to water heat pumps with E.V.I. compressors -20 C +43 C +65 C E.V.I. C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw) High Ambient / High Efficiency Series R - 410a 50Hz Ducted Split Air Conditioners (5.0 kw - 17.5 kw) ISO 9001 : 2008 ISO 14001 : 2004 ISO 18001 : 2007 R - 410a 50Hz Introduction: Established in the year

More information

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual u Air-to-Water Reverse Cycle Heat Pumps AQH 40 to 130 40 to 131 kw 45 to 141 kw Engineering Data Manual EDM AQH-W.3GB Date : November 2007 Supersedes : TM AQH-W.2GB/03.04 Specifications The Aqu@Logic air-to-water

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

Indoor Air Handlers with Compressors MVS and MVW

Indoor Air Handlers with Compressors MVS and MVW Indoor Air Handlers with Compressors MVS60-90-120-144 and MVW60-90-120-144 General Description The Marvair Marine self-contained water and air cooled air conditioners are designed for both new installations

More information

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES 60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

LZA High efficiency air to water heat pumps with HP compressor

LZA High efficiency air to water heat pumps with HP compressor High efficiency air to water heat pumps with HP compressor -10 C +43 C +60 C HP C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems

More information

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING

More information

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED EQV R-407C WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED Size Cooling Heating [kw] [kw] 5 1,9 2,2 7 2,4 2,5 9 2,6 2,5 15 3,3 3,2 17 3,7 3,7 REPLACE: BT02E008GB-01 The Versatemp EQV units

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Operation manual. Dehumidifier CFO-20N

Operation manual. Dehumidifier CFO-20N Operation manual Dehumidifier CFO-20N CONTENTS IMPORTANT INSTRUCTIONS... 1 IMPORTANT SAFETY INFORMATION... 2 ABOUT THE CONTROLS ON THE DEHUMIDIFIER... 3 USING THE DEHUMIDIFIER... 4 CARE AND CLEANING OF

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

TOSHIBA AIR CONDITIONING

TOSHIBA AIR CONDITIONING Introduction The following specification describes the Toshiba Estia Air to Water Heat Pump system(s) to be installed at the site below: (ADD SITE NAME) The system(s) shall consist of the following components.

More information

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw) FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz

More information

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION AIR CONDITIONERS 2scu3 PRODUCT SPECIFICATIONS Dry Charge Split System - 60 HZ Bulletin No. 20644 May 204 Supersedes September 203 3 to 5 Tons MODEL NUMBER IDENTIFICATION 2 scu 3 lc 36 t - a Refrigerant

More information

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10 Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW Compressors Scroll Serie: Series: Emissione: Issue: SCAEY Catalogo: Leaflet: Sostituisce: Supersedes: DE 88 04/11 12/10 Index

More information

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION CONDITIONERS DRY CHARGE UNITS PRODUCT SPECIFICATIONS Bulletin No. 20636 May 204 Supersedes March 202.5 to 5 Tons MODEL NUMBER IDENTIFICATION L C S 3 DC - 036-230 - 2 Lennox Minor Revision Number Air Conditioner

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products, Inc. 700 Thimble Shoals Blvd, Suite 109 Newport News, VA. 23606-2575 Tel: (757) 873 6800 Fax: (757) 873 3632

More information

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES LS ir cooled water chillers with axial fans + LS The LS water chiller range has been designed for small and medium residential and commercial applications. They are suitable for generating chilled water

More information

INSTALLATION & TECHNICAL MANUAL

INSTALLATION & TECHNICAL MANUAL The COMET Range of Boilers the ultimate solution for central heating INSTALLATION & TECHNICAL MANUAL If you require any further assistance: Telephone: 01698 820533 Fax: 01698 825697 E-mail: info@electric-heatingcompany.co.uk

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

ADD-ON AIR CONDITIONING CHANGING THE GAME FOR COMFORT AND PERFORMANCE

ADD-ON AIR CONDITIONING CHANGING THE GAME FOR COMFORT AND PERFORMANCE ADD-ON AIR CONDITIONING CHANGING THE GAME FOR COMFORT AND PERFORMANCE At ActronAir, we see air conditioning differently. Add-on air conditioning The leading Australian owned air conditioning brand, ActronAir

More information

AQUASNAP JUNIOR 30RHV

AQUASNAP JUNIOR 30RHV High-Efficiency Air-To-Water Heat Pumps Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. AQUASNAP JUNIOR 3RHV 6-11

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

Next-Gen Uni-Pak 1/2 TO 6 HP MULTI-REFRIGERANT AIR COOLED CONDENSING UNITS

Next-Gen Uni-Pak 1/2 TO 6 HP MULTI-REFRIGERANT AIR COOLED CONDENSING UNITS Publication No. CZ-CFH-0617A Replaces document CZ-CFH-0117A Next-Gen Uni-Pak 1/2 TO 6 HP MULTI-REFRIGERANT AIR COOLED CONDENSING UNITS 2 1/2 TO 6 HP The Next Generation of Uni-Paks are Here! ColdZone s

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

DRY CHARGE UNITS. 1.5 to 5 Tons. HEAT PUMP OUTDOOR UNITS lps13dc PRODUCT SPECIFICATIONS L P S 13 DC MODEL NUMBER IDENTIFICATION

DRY CHARGE UNITS. 1.5 to 5 Tons. HEAT PUMP OUTDOOR UNITS lps13dc PRODUCT SPECIFICATIONS L P S 13 DC MODEL NUMBER IDENTIFICATION HEAT PUMP OUTDOOR UNITS lps13dc DRY CHARGE UNITS PRODUCT SPECIFICATIONS Bulletin No. 210637 June 2014 Supersedes June 2012 1.5 to 5 Tons MODEL NUMBER IDENTIFICATION L P S 13 DC - 036-230 - 2 Lennox Minor

More information

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors -15 C +63 C E.V.I. The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems or

More information

TECHNICAL MANUAL FOR AIR-COOLED CONDENSING UNITS MTE

TECHNICAL MANUAL FOR AIR-COOLED CONDENSING UNITS MTE GB TECHNICAL MANUAL FOR AIR-COOLED CONDENSING UNITS MTE 5 kw - 213 kw TABLE OF CONTENTS 1 The series...4 2 Constructive features...4 3 Layout of components...5 4 Models and configurations...13 5 Technical

More information

REMOTE COOLER AIR COOLED & WATER COOLED

REMOTE COOLER AIR COOLED & WATER COOLED REMOTE COOLER AIR COOLED & WATER COOLED Installation & User Instructions (To be left with the user) PLEASE READ CAREFULLY BEFORE INSTALLING THE UNIT Please follow these instructions carefully. Only if

More information

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE:

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE: ABOUT THE i-chiller RANGE The fully packaged, EcoDesign compliant, air-cooled i-chiller range is designed specifically for reliable and efficient process cooling. The unique evaporator is immersed within

More information

Pressurisation units & expansion vessels

Pressurisation units & expansion vessels Pressurisation units & expansion vessels Pressurisation units The new generation of microprocessor controlled pressurisation units Standard Unit/Advanced Unit These microprocessor controlled pressurisation

More information

500 EX Fusion Compressor Series

500 EX Fusion Compressor Series 500 EX Fusion Compressor Series R404A M/T R404A L/T Capacity RANGE 13.8kW - 20.4kW 7.7kW -11.2kW Copeland Fusion Semi-Hermetic Horizontal Scroll Compressors For Medium and Low Temperature Applications

More information

Unvented Electric Water Heater 10/15 litre Undersink

Unvented Electric Water Heater 10/15 litre Undersink Unvented Electric Water Heater 10/15 litre Undersink Fitting Instructions and User Guide 1 CONTENTS SECTION PAGE 1.0 INTRODUCTION 2 2.0 TECHNICAL SPECIFICATION 3 3.0 INSTALLATION 4 4.0 COMMISSIONING 9

More information

AIR COOLED PACKAGED CHILLER

AIR COOLED PACKAGED CHILLER AIR COOLED PACKAGED CHILLER UNIC sal is equipped to produce a wide range of COOLER Air conditioning and Refrigeration units, conforming to the international standards and works continually to improve its

More information

30RH B Nominal cooling capacity kw Nominal heating capacity kw

30RH B Nominal cooling capacity kw Nominal heating capacity kw Air-to-Water Heat Pumps with Integrated Hydronic Module AQUASNAP Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products.

More information

CONDENCIAT CD. Condensing units. Quiet operation Low speed fans All year round operation USE. Cooling capacity : 25 to 165 kw.

CONDENCIAT CD. Condensing units. Quiet operation Low speed fans All year round operation USE. Cooling capacity : 25 to 165 kw. Quiet operation Low speed fans All year round operation Cooling capacity : 25 to 165 kw Cooling only USE The offers a solution to both heating and cooling applications encountered in the public, tertiary

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

Please read these instructions carefully as they will enable you to get maximum efficiency and reliability from your new Calorex Dehumidifier.

Please read these instructions carefully as they will enable you to get maximum efficiency and reliability from your new Calorex Dehumidifier. Please read these instructions carefully as they will enable you to get maximum efficiency and reliability from your new Calorex Dehumidifier. Technical Manual VARIHEAT VH3 AA/AW600/900/00A/BVHXF 500BVHXF

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Xcell 270 Longlife DC wholehouse heat recovery unit

Xcell 270 Longlife DC wholehouse heat recovery unit Xcell 270 Longlife DC wholehouse heat recovery unit Installation and maintenance instructions Xpelair Xcell 270 Longlife DC wholehouse heat recovery unit Xcell 270, Xcell 270BP Please leave this leaflet

More information

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01 b cool manufacturers of air-conditioning equipment ltd BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION Ver. 1.01 Ver. 3.02 01_18 BCool# 1 brt c/h r407c / r410a

More information

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata EKS/HE Refrigerant R410A GWP=2.088 Scroll Compressor Shell & Tube exchanger Axial fan Brazed plate heat exchanger MultiScroll Air-cooled liquid chillers High efficiency Solution B - Base I - Integrata

More information

CD30 / CD30E DEHUMIDIFIER (FULL PRODUCT RANGE) OWNER S MANUAL

CD30 / CD30E DEHUMIDIFIER (FULL PRODUCT RANGE) OWNER S MANUAL CD30 / CD30E DEHUMIDIFIER (FULL PRODUCT RANGE) OWNER S MANUAL www.eipl.co.uk Page 1 of 16 UNPACKING Carefully remove the CD30 dehumidifier unit from its transit box and visually check for signs of transit

More information

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser Vitocal 300-A, type AWC-I and AW-O.1 Product description A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser & High operational reliability,

More information

Split-system cooling units and heat pumps SERIES. Outdoor unit. Indoor unit OPERATING LIMITS. Inlet air conditions Cooling Heating.

Split-system cooling units and heat pumps SERIES. Outdoor unit. Indoor unit OPERATING LIMITS. Inlet air conditions Cooling Heating. capacity: Heating capacity: 20,8 to 135,1 kw 22,6 to 144,7 kw Scroll compressors R-410A refrigerant Confi guration fl exibility Silent operation DESCRIPTION The AirDuo cooling units and are units which

More information

PAJ3. Product Specifications

PAJ3. Product Specifications 13 SEER, R 410A PACKAGE AIR CONDITIONER FOR MANUFACTURED HOUSING, RESIDENTIAL, AND LIGHT COMMERCIAL APPLICATIONS 2 5 TONS Single Phase, 208/230 V, 60 Hz BUILT TO LAST, EASY TO INSTALL AND SERVICE Compact,

More information

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation Air-Cooled Liquid Chillers www.eurovent-certification.com www.certiflash.com Quality Management Systems 0RB 008-05 Nominal cooling capacity 8- The new generation of Aquasnap liquid chillers was designed

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 46 Above picture is only indicative and is not binding AIR FC The packaged air cooled chillers of RAS Kp series are suitable

More information

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the operation of reverse-cycle refrigeration (heat pumps) Explain

More information

FWC860 Wine Cooler Installation, Use and Maintenance

FWC860 Wine Cooler Installation, Use and Maintenance FWC860 Wine Cooler Installation, Use and Maintenance Customer Care Department The Group Ltd. Harby Road Langar Nottinghamshire NG13 9HY T : 01949 862 012 F : 01949 862 003 E : customer.care@cda.eu W :

More information

Series PIN. New Construction or Renovation. Application Flexible Quiet Comfort Damage Protection

Series PIN. New Construction or Renovation. Application Flexible Quiet Comfort Damage Protection Series PIN New Construction or Renovation Application Flexible Quiet Comfort Damage Protection ADIRONDACK AIRE New Construction or Renovation The Adirondack-Aire PIN Series zerozone chassis provides environment

More information

Installation, operating and maintenance ECOLEAN - EAC/EAR

Installation, operating and maintenance ECOLEAN - EAC/EAR Installation, operating and maintenance ECOLEAN - / Providing indoor climate comfort Revision 3 MIL103E-0909 12-2009 TABLE OF CONTENTS Page PREFACE 2 DATA PAGE FOR UNIT COMMISSIONING 3 1. 2. 3. 4. General

More information

WZT High Efficiency Air to Water Split System Heat Pumps With E.V.I. Compressors

WZT High Efficiency Air to Water Split System Heat Pumps With E.V.I. Compressors High Efficiency ir to Water Split System Heat Pumps With E.V.I. ompressors -20 +43 +65 HP E.V.I..O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor

More information

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS.

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS. Eclipse Installation and Wiring Instructions Models Eclipse 100X Eclipse 100XP Eclipse 100XT Eclipse 150X Eclipse 150XP Ref No. 42 73 10A 42 72 81A 42 72 82A 42 72 83A 42 73 13A 220-240V~50Hz PLEASE READ

More information

Self-Contained Reverse Cycle Air Conditioners

Self-Contained Reverse Cycle Air Conditioners Self-Contained Reverse Cycle Air Conditioners Models MA 07-10-12-16-24 General Description Marvair's water source self-contained reverse cycle air conditioners are designed for use in either fresh or salt

More information

HHWCH51 Galvanised Hot Water Coil Heater

HHWCH51 Galvanised Hot Water Coil Heater HHWCH51 Galvanised Hot Water Coil Heater Installation and Maintenance Instructions. THESE INSTRUCTIONS MUST BE READ FULLY BEFORE COMMENCING INSTALLATION. Owner / installer: The life of this apparatus and

More information

FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P

FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P 1 of 13 These instructions should be read by: The specifying engineer. The installation engineer. The user. The service engineer. WARNINGS Failure

More information

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts GTIP60 ISO GT Series, Inch Pounds 60 Hz GT010070 (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts Rev: 903 Rev 1 Revisions: 31103 Changed HZ dwg to field convertible 5902 changed Unit

More information