Demand Control Ventilation What, When and Where?

Size: px
Start display at page:

Download "Demand Control Ventilation What, When and Where?"

Transcription

1 Demand Control Ventilation What, When and Where? Presented by: Todd Bell Sr. Energy Analyst Fisher-Nickel Inc. Rich Swierczyna Sr. Engineer Fisher-Nickel Inc. The Food Service Technology Center (FSTC) program is funded by California utility customers through the public purpose program and administered by the Pacific Gas and Electric Company under the auspices of the California Public Utilities Commission. Fisher Nickel Inc. has managed the FSTC for PG&E since Our Mission: Promote Energy Efficiency in Commercial Food Service

2 Upcoming FSTC Seminars Submetering 101 Field Guide for Finding Big Ticket Energy Waste December 16 th Fast Five Fundamentals Energy & Water Best Practices for the Beginner January 21 st 2016 Foodservice Forecast Featuring Special Guest Speaker Robin Ashton (FER) February 9 th Register online at fishnick.com Demand Control Ventilation Rebate! $700 / Exhaust Fan HP

3 Fishnick.com

4 Fundamentals of Commercial Kitchen Ventilation Package Air Handler Dedicated Kitchen Make up Air Unit Exhaust Fan 3000 cfm 6000 cfm 3000 cfm Exhaust air volume is expressed in Cubic Feet/Minute (CFM) 1 cfm = 1 cubic foot per minute 1 cubic foot is about the size of a basketball The hood eats a lot of basketballs!

5 Common Exhaust Hood Styles Wall Mounted Canopy Single Island Canopy Double Island Canopy Back Shelf Pass Over The Problem: Typical Hotel Kitchen at 3:00 PM No appliance use but exhaust at 100%! Front Line Back Line

6 Solution: Demand Ventilation Control Technologies Duct Temperature Sensor & Infrared Sensors Duct Temperature Sensor & Vapor Detection Duct Temperature Sensor DCKV System Energy Use Profiles 16 Exhaust and Makeup Air Fan Power 16 Exhaust and Makeup Air Fan Power Power (kw) Avg. without DVC = 12.7 kw 8 6 Power (kw) Avg. without DVC = 14.0 kw Avg. with DVC = 5.8 kw Time Avg. with DVC = 5.3 kw Time Clarke Kerr Dining Commons Mark Hopkins Hotel

7 Retrofitting Demand Controlled Kitchen Ventilation (DCKV) Does it Make Sense? START (1) Do you know about DCKV hood control and its energy saving potential? Refer to industry literature on DCKV (6) Do the exhaust hoods fail to capture & contain cooking heat & smoke? Undertake a hood tuneup or upgrade to improve capture (2) Do you have more than 12 (linear) feet of exhaust hood (typically more than 3000 cfm)? (5) Are there times during the day when appliances are not actively cooking food while the hood is operating? (3) Are the exhaust hoods in your kitchen a backshelf or proximity sytle (versus canopy style) Backshelf hoods are generally more efficient and typically operate at lower airflow.. ROI caution (4) Do you operate your exhaust hoods less than 8 hrs per day? (7) Do you have single island hoods over heavy duty equipment? (8) Do you have multiple exhaust hoods connected to one exhaust fan? (9) Do you have a large underfired broiler (charbroiler) on your cookline? DCKV caution. Caution. Charbroiler exhaust reduction is limited (12) Is the noise from the exhaust hood excessive? (11) Do you cool your makeup air? (10) Do you heat your makeup air? Noise reduction not ROI caution justification for DCKV (13) Are the utility rates in your area considered high? (ex. $.06/kWh is low, $.15/kWh is high) Gas rates over $1.00/therm are considered high) (14) Do you know the total exhaust air flow rate (in cfm) for your exhaust hoods? Do you know your nameplate horsepower of the exhaust and makeup fans? Engage an energy professional YOU ARE LIKELY TO GET GOOD ROI ON A DCKV SYSTEM END

8 Is a Demand Controlled Kitchen Ventilation (DCKV) START (1) Do you know about DCKV hood control (variable speed exhaust) and its energy saving potential? Refer to industry literature on DCKV Check out the Food Service Technology Center s DCKV Webpage: Is a Demand Controlled Kitchen Ventilation (DCKV) (2) Do you have more than 12 (linear) feet of exhaust hood (typically more than 3000 cfm)?

9 Is a Demand Controlled Kitchen Ventilation (DCKV) (3) Are the exhaust hoods in your kitchen a backshelf or proximity style (versus canopy style)? Backshelf hoods are generally more efficient and typically operate at lower airflow Note: Several leading QSR chains are rolling out DCKV systems that communicate directly with the cooking appliances, making the ROI more attractive. Is a Demand Controlled Kitchen Ventilation (DCKV) (4) Do you operate your exhaust hoods less than 8 hrs per day?

10 Is a Demand Controlled Kitchen Ventilation (DCKV) (5) Are there times during the day when appliances are not actively cooking food while the hood is operating? Is a Demand Controlled Kitchen Ventilation (DCKV) (6) Do the exhaust hoods fail to capture & contain cooking heat & smoke? Caution: Undertake a hood tune up or upgrade to improve capture Note: An exhaust hood that is not working satisfactorily at full speed is not going to work well at reduced speed.

11 Is a Demand Controlled Kitchen Ventilation (DCKV) (7) Do you have single island hoods over heavy duty equipment? DCKV Caution! Note: Single island hoods are notorious for not capturing and containing smoke produced by heavy duty cooking equipment. They may perform even worse when the DCKV system reduces the exhaust airflow. Is a Demand Controlled Kitchen Ventilation (DCKV) (8) Do you have multiple exhaust hoods connected to one exhaust fan? Note: It is difficult to reduce the exhaust airflow from multiple hoods serving different production roles when connected to one exhaust fan. For example, if cooking is going on under one hood, then all hoods need to be operating at full speed. Exception: When the DCKV system incorporates code approved dampers to modulate air flow to the individual hoods.

12 Is a Demand Controlled Kitchen Ventilation (DCKV) (9) Do you have a large under fired broiler (charbroiler) on your cookline? Note: A charbroiler needs almost as much exhaust airflow in a ready to cook mode of operation as it does when cooking meat products. Thus the reduction in exhaust air may be limited and the ROI challenged. However, if a charbroiler part of a much larger cookline, this issue may be less significant. Is a Demand Controlled Kitchen Ventilation (DCKV) (10) Do you heat your makeup air? Note: Makeup air heating savings with DCKV can be significant, supporting the ROI.

13 Is a Demand Controlled Kitchen Ventilation (DCKV) (11) Do you cool your makeup air? Note: The energy required to cool makeup air in many areas of the country is not significant and does not impact ROI. Is a Demand Controlled Kitchen Ventilation (DCKV) (12) Is the noise from the exhaust hood excessive? Noise reduction not justification for DCKV

14 Is a Demand Controlled Kitchen Ventilation (DCKV) (13) Are the utility rates in your area considered high? (eg. $.06/kWh is low, $.15/kWh is high) Gas rates over $1.00/therm are considered high) Is a Demand Controlled Kitchen Ventilation (DCKV) (14) Do you know the total exhaust air flow rate (in cfm) for your exhaust hoods? Do you know your nameplate horsepower of the exhaust and makeup fans? Engage an energy professional

15 Is a Demand Controlled Kitchen Ventilation (DCKV) YOU ARE LIKELY TO GET GOOD ROI ON A DCKV SYSTEM Secure quote(s) from DCKV supplier/installer 16 Exhaust and Makeup Air Fan Power 14 Example of Savings: Mark Hopkins Hotel Power (kw) Avg. without DVC = 14.0 kw Design Exhaust Ventilation Rate (cfm) 22,500 Average Fan Power Reduction (kw) 8.70 Total Exhaust Fan (HP) 15.0 Yearly Fan Energy Cost Savings ($) 12,064 Yearly Heating and Cooling Energy Cost Savings ($) 9,460 Total Yearly Operating Cost Savings ($) 21,524 DVC System Installed Cost ($) 15,000 PG&E Rebate ($) 10, Avg. with Time DVC = 5.3 kw Pay Back Period (yrs) 0.2 Calculated using $0.14/kWh, $1.00/therm, operating 365 days per year.

16 Example of Savings: Savings: U.C. Berkeley Clark Kerr Campus Avg. without DVC = kw Power (kw) Exhaust and Makeup Air Fan Power Avg. with DVC = 5.8 kw Time Design Exhaust Ventilation Rate (cfm) 12,200 Average Fan Power Reduction (kw) 6.98 Total Exhaust Fan (HP) 8.0 Yearly Fan Energy Cost Savings ($) 4,990 Yearly Heating and Cooling Energy Cost Savings ($) 2,350 Total Yearly Operating Cost Savings ($) 7,340 DVC System Installed Cost ($) 16,000 PG&E Rebate ($) 5,600 Pay Back Period (yrs) 1.4 Calculated using $0.14/kWh, $1.00/therm, operating 365 days per year. DCKV Recap the Ideal Candidate Long Exhaust Hood(s) (12 ft or more) = More cfm = More HP = More Rebate $ Dedicated fans for individual hoods Long Operating Hours ( 8+ hours/day) Long appliance idle periods Light to Medium duty appliances = Ovens, Steamers, Fryers & Griddles Minimal Charbroiling

17 Target Customers Hotels Hospitals University Cafeterias Corporate Campus Cafes Large Full Service Restaurants Super Markets Cautions Exhaust System must be working effectively as single speed before Considering DCKV Proper commissioning is key Existing Three Phase fan motors for compatibility with variable frequency drives

18 Todd Bell Sr. Energy Analyst Fisher-Nickel Inc Rich Swierczyna Sr. Engineer Fisher-Nickel Inc

New Era in Energy Efficiency!

New Era in Energy Efficiency! Presentation by: David Zabrowski Director of Engineering Energy & Water Efficiency in Commercial Kitchens June 30, 2009 June 30, 2009 The Food Service Technology Center (FSTC) program is funded by California

More information

Demand-Controlled Ventilation for Commercial Kitchen Ventilation

Demand-Controlled Ventilation for Commercial Kitchen Ventilation Demand-Controlled Ventilation for Commercial Kitchen Ventilation Welcome. Today s webinar is being recorded and will be posted at: www.e3tnw.org www.conduitnw.org You may submit questions at any time during

More information

Innovative Technologies [and Design Concepts] in Commercial Foodservice

Innovative Technologies [and Design Concepts] in Commercial Foodservice Innovative Technologies [and Design Concepts] in Commercial Foodservice Don Fisher, P. Eng. Fisher Consultants PG&E Food Service Technology Center 925-866-5770 dfisher@fishnick.com Food Service Technology

More information

Fishnick.com. RFMA 2015 Feb 1-3, Fisher-Nickel, Inc. Field Notes: An Energy Auditor s 10 Year Odyssey in the. in Commercial Food Service

Fishnick.com. RFMA 2015 Feb 1-3, Fisher-Nickel, Inc. Field Notes: An Energy Auditor s 10 Year Odyssey in the. in Commercial Food Service Field Notes: An Energy Auditor s 10 Year Odyssey in the World of Commercial Food Service Presented by: Todd Bell, Sr. Energy Auditor Fisher Nickel, Inc. The Food Service Technology Center (FSTC) program

More information

for Energy & Water Savings in Commercial Food Service

for Energy & Water Savings in Commercial Food Service F S T C W o r k f o r c e E d u c a t i o n & T r a i n i n g Top 10 Tips for Energy & Water Savings in Commercial Food Service Presented by: Todd Bell Sr. Energy Analyst Fisher-Nickel Inc. Download today

More information

Energy & Water Savings in Commercial Food Service

Energy & Water Savings in Commercial Food Service Energy & Water Savings in Commercial Food Service Don Fisher Manager Food Service Technology Center 925-866-5770 dfisher@fishnick.com The Food Service Technology Center (FSTC) program is funded by California

More information

Kitchenology: Tales of Transformation and Efficient and Effective Operations

Kitchenology: Tales of Transformation and Efficient and Effective Operations Kitchenology: Tales of Transformation and Efficient and Effective Operations Kitchenologist: Mark Finck Download Today s Handouts: www.fishnick.com/handouts/03062017 Back-ground Started in QSR as Crew

More information

BETTER BUILDINGS BY DESIGN CONFERENCE 2008 Designing a Sustainable Commercial Kitchen FEBRUARY 13 BURLINGTON, VERMONT

BETTER BUILDINGS BY DESIGN CONFERENCE 2008 Designing a Sustainable Commercial Kitchen FEBRUARY 13 BURLINGTON, VERMONT BETTER BUILDINGS BY DESIGN CONFERENCE 2008 Designing a Sustainable Commercial Kitchen FEBRUARY 13 BURLINGTON, VERMONT Don Fisher Manager PG&E Food Service Technology Center 925-866-5770 dfisher@fishnick.com

More information

Effective ventilation is necessary for the comfort

Effective ventilation is necessary for the comfort NEWS FROM THE NETWORK Understanding Kitchen Ventilation Clearing the Air and Eliminating the Myths by Tom Stroozas CFE, RCGC, CFSP GFEN Consulting Editor Effective ventilation is necessary for the comfort

More information

25 Energy Saving Tips

25 Energy Saving Tips 25 Energy Saving Tips Easy Money Todd Bell, Victor Kong, & Richard Young Copyright 2010 Fisher Nickel. All Rights Reserved. Vern Smith Vernon.A.Smith@gmail.com 720-320-9154 The Food Service Technology

More information

90.1 and Designing High Performance Commercial Kitchen Ventilation Systems BY DON FISHER, P.ENG., RICH SWIERCZYNA,

90.1 and Designing High Performance Commercial Kitchen Ventilation Systems BY DON FISHER, P.ENG., RICH SWIERCZYNA, 90.1 and Designing High Performance Commercial Kitchen Ventilation Systems BY DON FISHER, P.ENG., RICH SWIERCZYNA, The energy intensity associated with operating commercial kitchen ventilation (CKV) systems

More information

Food Service Technology Center Promoting Energy Efficiency in Food Service

Food Service Technology Center Promoting Energy Efficiency in Food Service Account Information & Energy Potential Date Month/Day/Year 6-Oct-10 Account Number(s) Account Id # Customer Information Business Name Rubios Contact Name Tabitha Smith Title Manager Street Address on UCSD

More information

Demand Controlled Kitchen Ventilation (DCKV) [Strategy]

Demand Controlled Kitchen Ventilation (DCKV) [Strategy] [Strategy] BRIEF DESCRIPTION DCKV equipment automatically varies kitchen ventilation by monitoring cooking activity to increase the exhaust airflow and makeup air when needed. DCKV equipment monitors cooking

More information

Designing and Operating an Energy Efficient Foodservice Facility March 12, 2014 Winnipeg, MB

Designing and Operating an Energy Efficient Foodservice Facility March 12, 2014 Winnipeg, MB Designing and Operating an Energy Efficient Foodservice Facility March 12, 2014 Winnipeg, MB Don Fisher, P. Eng. Fisher Consultants PG&E Food Service Technology Center 925-866-5770 dfisher@fishnick.com

More information

General Session Lab Meets the Real World: Case Studies of Energy Efficient Upgrades that Saved Money

General Session Lab Meets the Real World: Case Studies of Energy Efficient Upgrades that Saved Money General Session Lab Meets the Real World: Case Studies of Energy Efficient Upgrades that Saved Money Richard Young Saturday, April 16 8:45-10:00 a.m. Presentation by: Richard Young Director of Education

More information

for commercial kitchen ventilation

for commercial kitchen ventilation Energy efficient solutionszag Energy efficient solutions for commercial kitchen ventilation Andrey Livchak, Dr., Halton Introduction Restaurants are among commercial buildings with the highest energy consumption

More information

REQUIREMENTS FOR HOOD PLANS

REQUIREMENTS FOR HOOD PLANS DEPARTMENT OF PUBLIC HEALTH Division of Environmental Health REQUIREMENTS FOR HOOD PLANS Submit one (1) set of plans drawn to scale of at least ¼-inch per foot. Plans shall conform to applicable California

More information

FOOD SERVICE EQUIPMENT REBATES

FOOD SERVICE EQUIPMENT REBATES FOOD SERVICE EQUIPMENT REBATES 2 Save money, increase productivity, and get great rebates when you purchase energy-efficient food service equipment! According to the Food Service Technology Center, 80%

More information

TECHNOLOGY AND MARKET ASSESSMENT FORUM: NATIONAL ACCOUNT PRESENTATION Presented by Melisa Marks October 26, 2011

TECHNOLOGY AND MARKET ASSESSMENT FORUM: NATIONAL ACCOUNT PRESENTATION Presented by Melisa Marks October 26, 2011 TECHNOLOGY AND MARKET ASSESSMENT FORUM: NATIONAL ACCOUNT PRESENTATION Presented by Melisa Marks October 26, 2011 Southern California Gas Company Our History Delivering for nearly 140 years. Clean, safe,

More information

David Reynolds, Business Development Manager. Halton Group Foodservice Division

David Reynolds, Business Development Manager. Halton Group Foodservice Division David Reynolds, Business Development Manager Halton Group Foodservice Division www.haltoncompany.com M.E. DESIGN VIEW OF COMMERCIAL KITCHENS BLACK HOLE Sucking Energy from Building Why are Campus Kitchens

More information

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY STAFF USE ONLY Thurston County Resource Stewardship 2000 Lakeridge Dr. S.W. Olympia, WA 98502 (360)786-5490 / (360)754-2939 (Fax) TDD Line (360) 754-2933 Email: permit@co.thurston.wa.us www.co.thurston.wa.us/permitting

More information

Case Studies: Restaurant Energy Efficiency. hosted by:

Case Studies: Restaurant Energy Efficiency. hosted by: Case Studies: Restaurant Energy Efficiency hosted by: June 30, 2016 All materials copyright Fisher Nickel, Inc. 2016 The Food Service Technology Center (FSTC) program is funded by California utility customers

More information

Design Guide Improving Commercial Kitchen Ventilation System Performance

Design Guide Improving Commercial Kitchen Ventilation System Performance Design Guide Improving Commercial Kitchen Ventilation System Performance This design guide provides information about achieving and maintaining optimum performance and energy efficiency in commercial kitchen

More information

Natural Gas Energy Efficiency Program. The Hotel/Lodging Industry

Natural Gas Energy Efficiency Program. The Hotel/Lodging Industry Natural Gas Energy Efficiency Program The Hotel/Lodging Industry 1 Agenda Welcome Hotel EE Opportunities Natural Gas C&I Energy Efficiency Offerings Gas Equipment & End Uses Supported Prescriptive Rebates

More information

WHAT YOU NEED TO KNOW BEFORE THE NRA SHOW

WHAT YOU NEED TO KNOW BEFORE THE NRA SHOW Workforce Education & Training WHAT YOU NEED TO KNOW BEFORE THE NRA SHOW May 1st, 2018 Today s Speakers: David Zabrowski Vice President Mark Moose Finck Lab Manager Richard Young Director Two Important

More information

LACLEDE ENERGY EFFICIENCY PROGRAMS

LACLEDE ENERGY EFFICIENCY PROGRAMS LACLEDE ENERGY EFFICIENCY PROGRAMS JUNE 10, 2015 S T. L O U I S G R E E N B U S I N E S S C H A L L E N G E WHAT I LL COVER TODAY Commercial/Industrial Rebate Program Building Operator Certification Residential

More information

Demand-Controlled Ventilation For Commercial Kitchens

Demand-Controlled Ventilation For Commercial Kitchens Demand-Controlled Ventilation For Commercial Kitchens Tetra Images/Corbis By Derek Schrock, Member ASHRAE; Jimmy Sandusky, Associate Member ASHRAE; Andrey Livchak, Ph.D., Member ASHRAE Food service facilities

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center Eloma Genius T6-11 Gas Combination Oven Test Report FSTC Report # 501311112-R0 Application of ASTM Standard Test Method F2861-10 August 2012 Prepared by: Michael Karsz Denis

More information

AccuTemp Steam n Hold, Model 208-D8-300 and 400 Electric Steamers In-Kitchen Appliance Performance Report

AccuTemp Steam n Hold, Model 208-D8-300 and 400 Electric Steamers In-Kitchen Appliance Performance Report AccuTemp Steam n Hold, Model 208-D8-300 and 400 Electric Steamers In-Kitchen Appliance Performance Report FSTC Report 5011.01.90 Food Service Technology Center Manager Final Report, December 2001 Prepared

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center CMA-180 / CMA-180-VL Dishwashing Machine Expanded Test Report FSTC Application of ASTM Standard Test Methods F1696-07 and F2474-09 January 2013 Prepared by: Denis Livchak

More information

Benefits of ENERGY STAR Commercial Water Heaters in the Food Service Industry

Benefits of ENERGY STAR Commercial Water Heaters in the Food Service Industry Benefits of ENERGY STAR Commercial Water Heaters in the Food Service Industry Nov 5 th, 2012 Presented by: Amin Delagah Lab Research Test Method Development Product Test & Evaluation Field Research Product

More information

INTELLINOX DEMAND CONTROL KITCHEN VENTILATION

INTELLINOX DEMAND CONTROL KITCHEN VENTILATION INTELLINOX DEMAND CONTROL KITCHEN VENTILATION COMMERCIAL KITCHEN VENTILATION EXPERTS FOR OVER 25 YEARS WHO WE ARE WE REALLY UNDERSTAND AIRFLOW IN YOUR KITCHEN Extensive experience with all kitchen hood

More information

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS (630) 620-5750 Fax: (630) 629-2374 www.villageoflombard.org COMMERCIAL HOOD & DUCT SYSTEM PLAN REVIEW REQUIREMENTS International

More information

Variable Ventilation for the Kitchen:

Variable Ventilation for the Kitchen: Variable Ventilation for the Kitchen: How It Works and Why It s Important for Your Restaurant YOUR ENERGY COSTS $ JAN FEB MAR MAP LEGEND lighting & signage control hvac & kitchen ventilation control energy

More information

Commercial Kitchen Ventilation (CKV) Design and Recent Innovations and Developments in the Industry.

Commercial Kitchen Ventilation (CKV) Design and Recent Innovations and Developments in the Industry. Commercial Kitchen Ventilation (CKV) Design and Recent Innovations and Developments in the Industry. Prepared by Dialectic, Inc. INTRODUCTION Commercial Kitchen Ventilation (CKV) Design and Recent Innovations

More information

Sustainable Hot Water: Better Design, Delivery, and Use

Sustainable Hot Water: Better Design, Delivery, and Use Sustainable Hot Water: Better Design, Delivery, and Use March 24, 2009 Don Fisher Amin Delagah Fisher-Nickel, inc. PG&E Food Service Technology Center The Food Service Technology Center (FSTC) program

More information

Market Forge, STP-6E Electric Steamer Performance Test

Market Forge, STP-6E Electric Steamer Performance Test Market Forge, STP-6E Electric Steamer Performance Test Application of ASTM Standard Test Method F 1484-99 FSTC Report 5011.01.05 Food Service Technology Center Final Report, December 2001 Prepared by:

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center CMA-180-VL-FL Electric Door-Type Heat Recovery Dishwashing Machine Test Report Application of ASTM Standard Test Method F1696-15 and F2474-09 May 2016 Prepared by: Edward

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center Hobart PW10eR Electric Pot and Pan Door-Type Dishwashing Machine Test Report Application of ASTM Standard Test Method F1696-15 & F2474-09 February 2016 Prepared by: Rich

More information

FOUNDATIONS OF MODERN KITCHEN VENTILATION (CKV) DESIGN HANDBOOK

FOUNDATIONS OF MODERN KITCHEN VENTILATION (CKV) DESIGN HANDBOOK FOUNDATIONS OF MODERN KITCHEN VENTILATION (CKV) DESIGN HANDBOOK A Design Guide offering ideas and resources to focus on sustainable design for the modern CKV System. Optimize CKV applications, manage energy

More information

CONVECTION OVENS FOR FOOD SERVICE APPLICATIONS BLODGETT SHO-E

CONVECTION OVENS FOR FOOD SERVICE APPLICATIONS BLODGETT SHO-E Design & Engineering Services CONVECTION OVENS FOR FOOD SERVICE APPLICATIONS BLODGETT SHO-E Report ` Prepared by: Design & Engineering Services Customer Service Business Unit Southern California Edison

More information

Customer Advanced Technologies Program Technology Evaluation Report

Customer Advanced Technologies Program Technology Evaluation Report Customer Advanced Technologies Program Technology Evaluation Report Prepared by Dave Bisbee, CEM Energy Efficiency, Customer Research & Development Sacramento Municipal Utility District January 11, 2008

More information

Food Service Technology Center Promoting Energy Efficiency in Food Service

Food Service Technology Center Promoting Energy Efficiency in Food Service Account Information & Energy Potential Date Month/Day/Year 6-Oct-10 Account Number(s) Account Id # Customer Information Business Name Espresso Roma Contact Name Aaron Luetta Title Manager Street Address

More information

MSYS 4490 AC Systems

MSYS 4490 AC Systems MSYS 4490 AC Systems Winter 2015 KITCHEN VENTILATION SYSTEMS By Satwinder Singh 12/02/2015 1 12/02/2015 2 By Satwinder Singh 1 12/02/2015 3 12/02/2015 4 By Satwinder Singh 2 Type I: Types of Hoods used

More information

Ducted Propeller. Airflow Volume

Ducted Propeller. Airflow Volume Total Pressure Radial-Blade Centrifugal Tubeaxial Backward-inclined Airfoil Centrifugal Forward-curved Centrifugal Ducted Propeller Airflow Volume Figure 2: Forward-Curved Centrifugal Fan

More information

Halton - Meeting the Kitchen Ventilation challenges of multiple venues in Hotels, Casinos and Resorts

Halton - Meeting the Kitchen Ventilation challenges of multiple venues in Hotels, Casinos and Resorts Halton - Meeting the Kitchen Ventilation challenges of multiple venues in Hotels, Casinos and Resorts Form#: BR-011 Hotels, Casinos & Resorts Brochure Halton Foodservice specializes in indoor climate solutions

More information

* Peak kw is determined by the average kw load reduction occurring between 1PM and 4PM on weekdays during June, July and August.

* Peak kw is determined by the average kw load reduction occurring between 1PM and 4PM on weekdays during June, July and August. overview Summary of Services & Incentives Effective through March 31, 2014 Last updated April 1, 2013 business programs The goal of the Focus on Energy Business Programs is to help Wisconsin s non-residential

More information

F Prepared by: Kong Sham. Prepared for: PO Box Technology Center

F Prepared by: Kong Sham. Prepared for: PO Box Technology Center Food Service Technology Center Merrychef eikon e2 Appliance Test Report FSTC Report # 501311081 Application of ASTM Standard Test Method F2238-09 December 2011 Prepared by: Kong Sham David Zabrowski Fisher-Nickel,

More information

DEMAND CONTROL KITCHEN VENTILATION

DEMAND CONTROL KITCHEN VENTILATION DEMAND CONTROL KITCHEN VENTILATION Avtec efficient ventilation solutions a new level of performance. EcoAzur, Demand Control Kitchen Ventilation (DCKV) The Avtec EcoAzur takes DCKV to a new level of performance,

More information

DEMAND CONTROL KITCHEN VENTILATION

DEMAND CONTROL KITCHEN VENTILATION DEMAND CONTROL KITCHEN VENTILATION Avtec efficient ventilation solutions a new level of performance. HOW DCKV WORKS: During cooking, steam or fumes are produced and the temperature rises. EcoAzur, Demand

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center IR Energy Habanero HAB-M50 Gas Patio Heater Test Report Application of ASTM Standard Test Method FF2644-07 September 2014 Prepared by: Elan Frantz Trey Young Fisher-Nickel,

More information

Metcraft Power Soak Performance Test

Metcraft Power Soak Performance Test Metcraft Power Soak Performance Test FSTC Report 5011.02.11 Food Service Technology Center Final Report, May 2002 Prepared by: Charles Bohlig Victor Kong Fisher-Nickel, inc. 2002 by Fisher-Nickel, inc.

More information

Cool Savings Program Report

Cool Savings Program Report Cool Savings Program Report Prepared by: Michael Fung Jennifer Wang San Francisco Department of the Environment 1455 Market St. Suite 1200 San Francisco, CA 94103 Technical Contributors: Denis Livchak

More information

Demand Control Kitchen Ventilation Cameron Ritzenthaler, Air Solutions & Balancing, LLC

Demand Control Kitchen Ventilation Cameron Ritzenthaler, Air Solutions & Balancing, LLC Demand Control Kitchen Ventilation Cameron Ritzenthaler, Air Solutions & Balancing, LLC 10.11.2017 YOUR TRADITIONAL KITCHEN HOOD SYSTEM Kitchen hood Exhaust fan (either belt or direct drive) Make-up air

More information

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003 MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003 California Conference of Directors of Environmental Health I. Background Proper venting and capture of the gases, heat, grease,

More information

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives Design Considerations for Commercial Kitchen Ventilation By John A. Clark, P.E., Member ASHRAE Commercial kitchen ventilation (CKV) design must consider everything needed to be coordinated to form a system

More information

Evaluating the Water Savings Potential of Commercial Connectionless Steamers. FINAL REPORT (Revised) April Angelo Karas Don Fisher

Evaluating the Water Savings Potential of Commercial Connectionless Steamers. FINAL REPORT (Revised) April Angelo Karas Don Fisher Evaluating the Water Savings Potential of Commercial Connectionless Steamers FINAL REPORT (Revised) April 2006 Prepared by: Angelo Karas Don Fisher Fisher-Nickel, inc. Food Service Technology Center 12949

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center Rational SCC WE 202G Gas Combination Oven Test Report FSTC Report # 501311101-R0 Application of ASTM Standard Test Method F2861-10 March 2012 Prepared by: Michael Karsz David

More information

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS 1 Ventilation and Exhaust 2 Seminar Introduction Seminar addresses key concepts

More information

Hot Water. The Efficiency Challenge!

Hot Water. The Efficiency Challenge! Hot Water The Efficiency Challenge! and all restaurants use hot water! but how much hot water? How much hot water do you use? Without this you don t know! What we see in the field U.S.

More information

2012 ICC Commercial Kitchen Hoods

2012 ICC Commercial Kitchen Hoods Welcome 2012 ICC Commercial Cooking Hoods Based on the: 2012 International Mechanical Code (IMC ) 2012 International Fire Code (IFC ) 2012 International Fuel Gas Code, (IFGC ) 2012 International Building

More information

REFRIGERATION Open case to New Reach-in Low or Medium Temperature Low Temp Coffin to New High Efficiency Reach-In...

REFRIGERATION Open case to New Reach-in Low or Medium Temperature Low Temp Coffin to New High Efficiency Reach-In... Contents REFRIGERATION... 3 1. Open case to New Reach-in Low or Medium Temperature... 3 2. Low Temp Coffin to New High Efficiency Reach-In... 3 3. Low Temperature Reach-in to High Efficiency Reach-in...

More information

2015 ICC Commercial Cooking Systems

2015 ICC Commercial Cooking Systems 2015 ICC Commercial Cooking Systems Based on the: 2015 International Building Code (IBC ) 2015 International Mechanical Code (IMC ) 2015 International Fire Code (IFC ) 2015 International Fuel Gas Code

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center Ovention M1718 Oven FSTC Report # 501311203-R0 Application of ASTM Standard Test Method F2238-09 December 2013 Prepared by: Kong Sham Fisher-Nickel, Inc.. Prepared for: Pacific

More information

AccuTemp STEAM n HOLD, Model 208-D6-3.0 Electric Steamer Performance Test

AccuTemp STEAM n HOLD, Model 208-D6-3.0 Electric Steamer Performance Test AccuTemp STEAM n HOLD, Model 208-D6-3.0 Electric Steamer Performance Test Application of ASTM Standard Test Method F 1484-93 FSTC Report 5011.98.58 Food Service Technology Center Manager: Don Fisher Final

More information

Low Wall Back Shelf Exhaust Canopy

Low Wall Back Shelf Exhaust Canopy ITEM NO. 710 Powerline Road Suite H Deerfield Beach, FL 33442 (954) 570-9860 (800) 322-8730 FAX (954) 570-9865 Low Wall Back Shelf Exhaust Canopy Model LW APPLICATION Wall mounted canopy style ventilator

More information

Sustainability Best Practices for HVAC Retrofits. Cal Poly State University, San Luis Obispo. Presented to the UC/CSU/CCC Sustainability Conference

Sustainability Best Practices for HVAC Retrofits. Cal Poly State University, San Luis Obispo. Presented to the UC/CSU/CCC Sustainability Conference Sustainability Best Practices for HVAC Retrofits Cal Poly State University, San Luis Obispo Presented to the UC/CSU/CCC Sustainability Conference June 22, 2009 Presented by Dennis K. Elliot, PE, CEM Sustainability

More information

RFMA 2016 March 13 15, 2016

RFMA 2016 March 13 15, 2016 Is Your Restaurant s HVAC Perfectly Tuned To Sing Your Praises? DIY Checkpoints And Fixes For HVAC Audits Sam Rayburn Melink Test & Balance Agenda Overview of building pressure Symptoms of negative building

More information

Ozone Laundry Fundamentals. Special guest: DEL Clean Ozone Laundry Systems

Ozone Laundry Fundamentals. Special guest: DEL Clean Ozone Laundry Systems Ozone Laundry Fundamentals Special guest: DEL Clean Ozone Laundry Systems Presented by Nina Newhouser and John Grillo 11.11.2014 Speakers energysmart overview Rebates for your ozone laundry systems Rebates

More information

Chapter One Commercial Kitchen Fires

Chapter One Commercial Kitchen Fires Table of Contents Table of Contents Chapter One Commercial Kitchen Fires COMMERCIAL KITCHEN FIRES... 2 The Commercial Kitchen Fire Problem... 2 Unreported Fires... 2 Cooking By-Products... 3 Grease Accumulation

More information

Evaluating the Water Savings Potential of Commercial Connectionless Food Steamers. FINAL REPORT June Angelo Karas Victor Kong Don Fisher

Evaluating the Water Savings Potential of Commercial Connectionless Food Steamers. FINAL REPORT June Angelo Karas Victor Kong Don Fisher Evaluating the Water Savings Potential of Commercial Connectionless Food Steamers FINAL REPORT June 2005 Prepared by: Angelo Karas Victor Kong Don Fisher Fisher-Nickel, inc. Food Service Technology Center

More information

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET Colorado Springs Fire Department Division of the Fire Marshal October 2013 Table of Contents PURPOSE... 3 SCOPE... 3 DEFINITIONS... 3 GUIDELINES...

More information

This month we are discussing the basics of

This month we are discussing the basics of News from the Network Getting the Most from Your Cooking Equipment Good Ventilation is Good for Business by Tom Stroozas, CFSP Manager Commercial Marketing Piedmont Natural Gas This month we are discussing

More information

CHAIN BUSINESS UNIT Powerfry Fryers, VCCG Griddle and VTEC Product Training

CHAIN BUSINESS UNIT Powerfry Fryers, VCCG Griddle and VTEC Product Training CHAIN BUSINESS UNIT 2015 Powerfry Fryers, VCCG Griddle and VTEC Product Training Fryers, Griddles & Charbroilers PowerFry VCCG VTEC GTS GR 900RX/MSA/ASA VACB/ACB-VCCB/SCB VHP/AHP VCRH LG VCRG VCRB 2 FRYERS

More information

FIRE PROTECTION SYSTEM FOR INDUSTRIAL KITCHENS

FIRE PROTECTION SYSTEM FOR INDUSTRIAL KITCHENS BLACK by by SEVO Systems SEVO Systems Black Diamond Fire Protection System for Industrial Kitchens is safe for humans and environmentally friendly. It utilizes the most advanced technology available, differentiating

More information

INTEGRATION OF DEMAND RESPONSE INTO TITLE 20 FOR HOT FOOD HOLDING CABINETS

INTEGRATION OF DEMAND RESPONSE INTO TITLE 20 FOR HOT FOOD HOLDING CABINETS Design & Engineering Services INTEGRATION OF DEMAND RESPONSE INTO TITLE 20 FOR HOT FOOD HOLDING CABINETS Phase1: Demand Response Potential DR 09.05.07 Report Prepared by: Design & Engineering Services

More information

Vanguard Powermax 200 Gas-Fired Booster Heater Performance Tests

Vanguard Powermax 200 Gas-Fired Booster Heater Performance Tests Vanguard Powermax 200 Gas-Fired Booster Heater Performance Tests Application of ASTM Standard Test Method F 2022-01 FSTC Report 5011.02.10 November 2002 Prepared by: David Cowen David Zabrowski Fisher-Nickel,

More information

Energy Saving Results for Cheetah. Cheetah Energy Saving in Commercial Kitchens

Energy Saving Results for Cheetah. Cheetah Energy Saving in Commercial Kitchens Energy Saving Results for Cheetah Cheetah Energy Saving in Commercial Kitchens Company profile Belfast Glasgow Cardif f Manchester Birmingham London, Finchampstead Quintex Systems Ltd was established in

More information

Getting the Heat. Out of the Kitchen

Getting the Heat. Out of the Kitchen Getting the Heat special FOODSERVICE section Out of the Kitchen Energy-efficient appliances, maintenance and monitoring hold down costs By Samantha Oller soller@cspnet.com There are rules we try to follow

More information

Montague, Model Vectaire HX63A Gas Full-Size Convection Oven Performance Test

Montague, Model Vectaire HX63A Gas Full-Size Convection Oven Performance Test Montague, Model Vectaire HX63A Gas Full-Size Convection Oven Performance Test Application of ASTM Standard Test Method F 1496-93 FSTC Report 5011.99.79 Food Service Technology Center Final Report, December

More information

Focus on Energy Business Programs Summary of Services and Incentives July 2009

Focus on Energy Business Programs Summary of Services and Incentives July 2009 Focus on Energy Business Programs Summary of Services and Incentives July 2009 OVERVIEW Focus on Energy Business Programs goals are to educate Wisconsin s farmers, businesses, industry, schools and local

More information

MECHANICAL EXHAUST VENTILATION SYSTEMS FOR RETAIL FOOD FACILITIES. Design, Calculations, and Operational Guidelines

MECHANICAL EXHAUST VENTILATION SYSTEMS FOR RETAIL FOOD FACILITIES. Design, Calculations, and Operational Guidelines MECHANICAL EXHAUST VENTILATION SYSTEMS FOR RETAIL FOOD FACILITIES California Conference of Directors of Environmental Health January 22, Page 1 of 30 TABLE OF CONTENTS I. Background 3 II. Purpose and Scope..3

More information

Energy Efficiency Business Rebates Product Catalog

Energy Efficiency Business Rebates Product Catalog Energy Efficiency Business Rebates Product Catalog Product Code FOOD SERVICE PRODUCTS Product Description Rebate/Unit Page # 402135 Steam Cooker Electric $1,250.00/Steamer 402136 Steam Cooker - Gas $2,000.00/Steamer

More information

Nicor Gas Energy Efficiency Program. Business Customer Offerings

Nicor Gas Energy Efficiency Program. Business Customer Offerings Nicor Gas Energy Efficiency Program Business Customer Offerings Agenda General Program Overview Prescriptive Program Custom Program June 1 and Beyond Program Effective Dates Pilot launched May 1, 2010

More information

COMMERCIAL. Oregon Incentives

COMMERCIAL. Oregon Incentives COMMERCIAL Oregon Incentives SEE WHAT SAVING ENERGY AND MONEY CAN DO FOR YOUR BUSINESS. EXISTING BUILDINGS STANDARD INCENTIVES FOR OREGON BUSINESS CUSTOMERS EFFECTIVE JANUARY 2018 Contents 1 Standard Incentives

More information

Refrigerated Prep Table Performance Testing

Refrigerated Prep Table Performance Testing Refrigerated Prep Table Performance Testing FSTC Report # 5011.03.16 September 2003 Prepared by: David Zabrowski David Cowen Fisher-Nickel, Inc. Contributor: Scott Miner Fisher-Nickel, Inc. 2003 by Fisher-Nickel,

More information

Conservation & Energy Efficiency Activities

Conservation & Energy Efficiency Activities Conservation & Energy Efficiency Activities Bobbi Sterrett Supervisor, Conservation & DSM November 8, 2010 Southwest Gas Profile Over 1.8 million customers in portions of Arizona, Nevada, and California

More information

ESPAIR E AIRTM ESPA ESPAIRTM. Kitchen Exhaust Air Treatment System KET Series.

ESPAIR E AIRTM ESPA ESPAIRTM. Kitchen Exhaust Air Treatment System KET Series. SMOKE EATER SMOKE EATER E SPAIR AIR AIR Kitchen Exhaust Air Treatment System KET Series KEEPING PACE In today's busy world, more people are going out to eat. For restaurants this growing trend not only

More information

The (Hot) Water Efficient Commercial Kitchen. Charles M. Bohlig East Bay Municipal Utility District

The (Hot) Water Efficient Commercial Kitchen. Charles M. Bohlig East Bay Municipal Utility District The (Hot) Water Efficient Commercial Kitchen Charles M. Bohlig East Bay Municipal Utility District cbohlig@ebmud.com 2 Foodservice is energy intensive... 600 500 BTU per FT2 400 300 200 100 0 Retail Office

More information

Results from a Flight Conveyor

Results from a Flight Conveyor Results from a Flight Conveyor Monitoring Project Fisher-Nickel, a division of Frontier Energy, Inc. Outline Overview, Site Descriptions Water Consumption Energy Consumption Technology comparison Cost

More information

Sunglo Heater Model A270 Patio Heater Performance Test

Sunglo Heater Model A270 Patio Heater Performance Test Sunglo Heater Model A270 Patio Heater Performance Test FSTC Report # 5011.07.01 January 2007 Prepared by: Greg Sorensen David Zabrowski Fisher-Nickel, Inc. 2007 by Fisher-Nickel, inc. All rights reserved.

More information

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys Enabling Wellbeing M.A.R.V.E.L. revolutionises energy footprint in galleys The M.A.R.V.E.L.* is the first truly intelligent,

More information

Commercial Water Heater Performance: Laboratory Testing and Modeling

Commercial Water Heater Performance: Laboratory Testing and Modeling Commercial Water Heater Performance: Laboratory Testing and Modeling Edwin Huestis, P.E. Mechanical Engineer PG&E Applied Technology Services ACEEE Hot Water Forum November 4, 2013 Presentation Objectives

More information

SUMMARY OF SERVICES & INCENTIVES

SUMMARY OF SERVICES & INCENTIVES BUSINESS PROGRAMS 2016 SUMMARY OF SERVICES & INCENTIVES Effective through December 31, 2016 Last updated February 1, 2016 EFFICIENCY INCENTIVES SUMMARY The Focus on Energy Business Programs offer both

More information

Middleby Marshall Conveyor Oven, PS 360WB Conveyor Oven Performance Test

Middleby Marshall Conveyor Oven, PS 360WB Conveyor Oven Performance Test Middleby Marshall Conveyor Oven, PS 360WB Conveyor Oven Performance Test Application of ASTM Standard Test Method F 1817-97 FSTC Report 5011.98.63 Food Service Technology Center Manager: Don Fisher Final

More information

Commercial load calculator instructions (all measurements are imperial)

Commercial load calculator instructions (all measurements are imperial) Commercial load calculator instructions (all measurements are imperial) Basic Tab 1. Enter the design conditions for your area. This only has to be done once unless your performing a load calculation for

More information

Notable Changes in the Mechanical Codes

Notable Changes in the Mechanical Codes Notable Changes in the Mechanical Codes July 2004 The following are some of the changes between the 1997 Uniform Mechanical Code and the 2003 International Mechanical Code(M) and the 2003 International

More information

Energy Efficiency. Intercept HDDperDay <2e 16 kwhperday

Energy Efficiency. Intercept HDDperDay <2e 16 kwhperday Energy Efficiency Energy Use of the Eco House Ben Francis Introduction: Three years ago one of the small houses owned by the college was altered with the goal of being more energy efficient. Among the

More information

Boilers and Water Heating Rebate Catalog Saving energy for a brighter future.

Boilers and Water Heating Rebate Catalog Saving energy for a brighter future. Pacific Gas and Electric Company Energy Efficiency s for Your Business Boilers and Water Heating Catalog Saving energy for a brighter future. Boilers and Water Heating Catalog Energy Efficiency s for Your

More information

INTELLINOX DEMAND CONTROL KITCHEN VENTILATION

INTELLINOX DEMAND CONTROL KITCHEN VENTILATION INTELLINOX DEMAND CONTROL KITCHEN VENTILATION COMMERCIAL KITCHEN VENTILATION EXPERTS FOR OVER 25 YEARS WHO WE ARE WE REALLY UNDERSTAND YOUR KITCHEN Extensive knowledge with all kitchen hood manufacturers

More information