Study on the Effect of Blade Angle on the Performance of a Small Cooling Tower

Size: px
Start display at page:

Download "Study on the Effect of Blade Angle on the Performance of a Small Cooling Tower"

Transcription

1 Kasetsart J. (Nat. Sci.) 42 : (2008) Study on the Effect of Blade Angle on the Performance of a Small Cooling Tower Montri Pirunkaset* and Santi Laksitanonta ABSTRACT This paper presents the effect of blade angles on the packing characteristic curves of a small cooling tower on the site experimental data. The volumetric heat transfer coefficient (KaV/L) can be illustrated graphically and varied with the water to air flow ratio (L/G) for the blade angles of 59, 67, 75, and 83, respectively. The curves can be constructed by the experimental data from the cooling tower testing in accordance with the procedure of CTI standard. It was found that the characteristic curves can be represented in the form of KaV/L = C(L/G) -n in the different range of L/G for each blade angle. Finally, it was found that the cooling tower can operate under all the given approaches (5 C, 6 C, 7 C and 8 C) at the blade angle of 67 by maintaining the cooling range of 5 C, wet bulb temperature of 26 C, and water flow rate of 3.9 m 3 /h. Key words: blade angles, performance of a small cooling tower INTRODUCTION During installation, the manufacturer must set up the proper blade angle for controlling the air flow through the tower as much as possible. The commercial cooling tower must provide the high heat transfer between the hot water and cold air by adjusting the proper blade angle during installation. Therefore, the manufacturer must determine the tower characteristic curves at various blade angles under the given wet bulb temperature, approach, hot water temperature, and water flow rate((nicholas et al., 1983). For residential air conditioning duty, the small packaged cooling towers usually have the adjustable blade angles. Therefore, the purpose of this research is to study the effect of the blade angles on the performance of the counter flow cooling tower with a small size (3 to 10 tons of refrigeration). MATERIALS AND METHODS The counter-flow cooling tower testing laboratory includes the circulated system of cooled water and hot water as shown in Figure1. The counter-flow cooling tower system includes heater tank, cold water tank, balancing tank, cooling tower, cold water pump, hot water pump, control panel, and measuring devices. 1) The counter-flow cooling tower is the heat exchanger between the hot water and air, and the specifications are following as: - The cooling tower size (using the corrugated packing) 5 tons of refrigeration Department of Mechanical Engineering, Faculty of Engineering, Kasetsart University, Bangkok 10900, Thailand. * Corresponding author, fengmtp@ku.ac.th

2 Kasetsart J. (Nat. Sci.) 42(5) 379 Figure 1 The apparatus of counter-flow cooling tower system for the experiment and testing. -Water volume flow rate ( V w ) 65 L/min - Air volume flow rate ( V a ) 55 m 3 /min - Hot water temperature (HWT) 37 C - Cold water temperature (CWT) 32 C - Inlet wet bulb temperature (WBT) 27 C - Fan horsepower 0.20 hps 2) There are 3 units of water pumps, namely 2.1 Cold water pump is used to pump the water from cold water tank to heater tank and it has the discharge pressure of 22 m of water, pumping flow rate from 10 to 80 L/min, motor horsepower of 0.37 kw, motor speed of 2900 rpm, and water connection diameter of 25 mm. 2.2 Hot water pump is used to pump water from the heater tank to the cooling tower and it has the same specifications as the cold water pump. 2.3 Balancing pump is used to control the level of water in heater tank, cold water tank, and cooling tower. It has the discharge pressure of 35 m, pumping flow rate of 30 L/min, motor horsepower of 0.33 kw, motor speed of 2900 rpm, and water connection diameter of 25 mm. 3) There are 3 units of water tanks, namely 3.1 Heater tank is used to supply the hot water for testing of the cooling tower and it has the 7 units of heater. Each unit has capacity of 2 kw by using current at 9.09 A and 220 V. 3.2 Cold water tank is used to supply cold water to the heater tank by pump and it has volume of 240 liters. 3.3 Balancing tank is used to supply water for controlling water level in the heater tank, cold water tank, and cooling tower during testing and experiment. It has volume of 200 liters, height of 85 cm, and diameter of 55 cm. 4) Measuring Devices, consisted of: 4.1 The orifice meter is used to measure pressure drop across the orifice plate by different height of mercury with range from 0 to 300 mm of Hg and its dimension of 60mm 440mm 28mm. The relationship between the different height of mercury, h Hg (mm) and the water flow rate, V w (L/min) can be found from the experiment and written as:

3 380 Kasetsart J. (Nat. Sci.) 42(5) V w = h Hg (1) 4.2 Anemometer is used to measure and record the air velocity by measuring the outlet air velocity (at the top of packing). 4.3 The digital instrument and recorder of temperature is used to measure water and air temperatures namely, wet bulb and dry bulb temperature, inlet and outlet water temperature of packing, and water film temperature. 4.4 The wet bulb and dry bulb thermometer on glass tube type, this instrument is used to measure wet bulb and dry bulb temperature of the inlet air (at the bottom of packing). Methods Tower characteristics and performance Cooling tower characteristics are generally presented in the form of an empirical correlation. This correlation defines the relationship between the heat transfer coefficient, KaV/L and water-air flow ratio, L/G under the operating condition. Cooling tower data are most often plotted in the form of KaV/L versus L/G for the various wet bulb temperature (approach) and cooling range. These graphs have been published by the Cooling Tower Institute (Cooling Tower Institute, 1982). Common practice is to neglect the effect of air velocity and develop the tower correlation in the form of a power law relation as (Mills, 1995): KaV C L n = (2) L G A commercial cooling tower of 5 tons of refrigeration is used to perform the structural equipment of model, which can be operated and tested in accordance with CTI standard. Cooling tower performance is specified in term of the cooling range, approach, wet bulb temperature and water flow rate. The rating of a tower is established by developing series of charts that related these variables (Hill et al., 1990). Calculation of KaV/L The Tchebycheff method for numerically b evaluating the integral ydx uses values of y at a predetermined values of x within interval a to b. It can be selected that the sum of these values of y multiplied by a constant times the interval (b- a) gives the desired value of integral. In its four-point form, the values of y are taken at selected values of x of , , , and of the interval (b-a). For the determination of KaV/ L, rounding off these values to the nearest tenth is entirely adequate. The approximate formula becomes (Cooling Tower Institute, 1982): b ( b a) ydx = a ( y 1 + y 2 + y 3 + y 4 ) (3) 4 where y 1 = value of y at x = a + 0.1( b-a ), y 2 = value of y at x = a + 0.4( b-a ) y 3 = value of y at x = a + 0.6( b-a ), y 5 = value of y at x = a + 0.9( b-a ) The water temperatures on the divided cross section of packing can be calculated in 4 positions. Each position can be determined from bottom to top of the packing as T (T 1 -T 2 ), T (T 1 -T 2 ), T (T 1 -T 2 ), and T (T 1 -T 2 ), respectively. So, the enthalpy difference at each position can be calculated and the value of KaV/ L can be evaluated as KaV Cw ( T T = 1 2) L 4 h1 h2 h3 h4 (4) where h 1 = saturated air and moist air enthalpy difference at T (T 1 -T 2 ) h 2 = saturated air and moist air enthalpy difference at T (T 1 -T 2 ) h 3 = saturated air and moist air enthalpy difference at T (T 1 -T 2 ) h 4 = saturated air and moist air enthalpy difference at T (T 1 -T 2 ) C w = specific heat of water, T 1 = hot water temperature, T 2 = cold water temperature

4 Kasetsart J. (Nat. Sci.) 42(5) 381 The blade angle adjustment The blade angles can be adjustable in four positions as shown in Figure 2. In each position of the blade angle, the performance of cooling tower can be tested by maintaining the speed of fan motor at 900 revolutions per minute Procedure of experiment The procedure of this research can be discussed as: 1) To fill water into a system (cold water tank, hot water tank, and balancing tank). 2) To set up the blade angle of 59. 3) To set up the different height of mercury at 10 mm (the water volume flow rate of L/min). 4) To start the heater and fan motor until the water temperature reaches 40 C and system reaches steady state. 5) To record the air volume flow rate, the outlet water temperature, the wet bulb temperature, and the dry bulb temperature. 6) To set up the new values of water flow rate by increasing the different height of 14, 18, 22,.., 50 mm and repeat from the item (4) to (5) for each different height. 7) For the other blade angles (67, 75, and 83 ), the experiment can be repeated as the item (3) to (6). RESULTS AND DISCUSSIONS The experiments are based on the setting of blade angles in cooling tower of 5 tons of refrigeration at the blade angle 59, 67, 75, and 83 of respectively. For the testing of cooling tower, the hot water temperature remains constant at 40 C and the variation of circulating water flow rates are from to L/min and wet bulb temperatures varied from 25 to 27 C. The characteristic curves for each blade angle in Figure 3 can be fit in the form of equation (2). The exponent, n and constant, C of the equation (2) for the various blade angles are shown in Table 1. The cooling tower with 5 tons of refrigeration and the packing area of ft 2 can be operated under the cooling range of 5 C, wet bulb temperature of 26 C, and water flow rate of 3.9 m 3 /h. The approach of 5 C, 6 C, 7 C and 8 C for cooling tower can be drawn in the same graph of the characteristic curves for each blade angle and the operating points can be represented as Table 2 to Table 5. Figure 2 Adjustment of blade angles at 59, 67, 75 and 83.

5 382 Kasetsart J. (Nat. Sci.) 42(5) Figure 3 The volumetric heat transfer coefficient at blade angles of 59, 67, 75 and 83. Table 1 The exponent, n and constant, C of the equation (2) for the various blade angles. Blade angle n C the range of L/G to to to to Table 2 The operating point (L/G, KaV/L) under the approach of 5 C, 6 C, 7 C and 8 C, range of 5 C, and wet bulb temperature of 26 C for blade angle of Out off range of L/G Table 3 The operating point (L/G, KaV/L) under the approach of 5 C, 6 C, 7 C and 8 C, range of 5 C, and wet bulb temperature of 26 C for blade angle of

6 Kasetsart J. (Nat. Sci.) 42(5) 383 Table 4 The operating point (L/G, KaV/L) under the approach of 5 C, 6 C, 7 C and 8 C, range of 5 C, and wet bulb temperature of 26 C for blade angle of Out off range of L/G Table 5 The operating point (L/G, KaV/L) under the approach of 5 C, 6 C, 7 C and 8 C, range of 5 C, and wet bulb temperature of 26 C for blade angle of Out off range of L/G Out off range of L/G For the adjustment of blade angle at 67 o, the cooling tower can operate in all approaches (5 C, 6 C, 7 C and 8 C) by maintaining the cooling range of 5 C, wet bulb temperature of 26 C, and water flow rate of 3.9 m 3 /h. Under the constant demand of WBT = 26 C, CWT = 32 C, HWT = 37 C, it was found that L/G, KaV/L and CFM are dependent upon the blade angles of fan as shown in Figure 4. The air quantities decreased with blade angles by maintaining the water flow rate of GPM. So, the ratio of L/G and KaV/L increased with blade angle. GPM,(gallon/min), CFM (ft 3 /min x100) CFM GPM Blade angle L/G KaV/L KaV/L, L/G Figure 4 The effect of blade angle on KaV/L, L/G, and CFM for HWT = 37 C, CWT = 32 C and WBT = 26 C.

7 384 Kasetsart J. (Nat. Sci.) 42(5) CONCLUSIONS This research studied the effect of blade angles on the packing characteristic curves of a small cooling tower. The curves can be constructed by the experimental data from the cooling tower testing in accordance with the procedure of CTI standard. As the lack of performance curves at the various blade angles, the fan blades may not be adjusted properly by manufacturers during installation. In each blade angle, it is important to find the operating points between the characteristic curves and approach curves and these points must not be out-off range of L/G for each characteristic curve. It was found that the cooling tower can operate in all approaches (5 C, 6 C, 7 C and 8 C), the cooling range of 5 C, wet bulb temperature of 26 C, and water flow rate of 3.9 m 3 /h by the adjustment of blade angle at 67. LITERATURE CITED Cooling Tower Institute Acceptance Test Code for Water Cooling Towers. CTI Code ATC p. Hill, G.B., E.J. Pring and P.D. Osborn Cooling Towers Principles and Practice. 3 rd ed. Butterworth-Heinemann Ltd., London. 191 p. Mills, A. F Heat and Mass Transfer. Richard D. Irwin Inc., Chicago.1239 p. Nicholas P.Ch. and N.Ch. Paul Cooling Tower (Selection Design and practice). 2 nd ed. Ann arbor Science Publishers, the Butterworth-Group, Michigan. 347 p.

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning ISBN 978-93-84468-94-1 International Conference on Education, Business and Management (ICEBM-2017) Bali (Indonesia) Jan. 8-9, 2017 An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University Scientific Principals and Analytical Model Charcoal Cooler Lisa Crofoot MECH 425, Queens University 1.0 Scientific Principles Evaporative cooling is based on the principle that water requires heat energy

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS Chainarong Chaktranond *, and Peachrakha Doungsong Department of Mechanical Engineering, Faculty of Engineering,

More information

Numerical Simulation of Window Air Conditioner

Numerical Simulation of Window Air Conditioner Numerical Simulation of Window Air Conditioner Mathewlal T 1, Kalpesh Patil 2, Gauri Thorat 3, Anisha Ankush 4, Ambarish Pote 5, Kartik Doshi 6 ( 1 Associate ProfessorMechanical Engineering Department,

More information

Optimizing Electric Humidifier Operation with an Air Side Economizer

Optimizing Electric Humidifier Operation with an Air Side Economizer Optimizing Electric Humidifier Operation with an Air Side Economizer Usama F. Shami, P.E. Senior Project Engineer Savage Engineering, Inc. Foster City, CA Abstract Air side economizer cycle is a control

More information

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING M. POIRIER, D. GIGUÈRE, Z. AIDOUN, M. OUZZANE Natural Resources Canada, CANMET Energy Technology Centre-Varennes 1615, Lionel

More information

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total. 1. State 2 75 o F Exhaust M amb T amb State 3 Room Q chiller State 1 60 o F M total A room at steady state has a supply air stream of cool air entering at 60 o F. The lights, office appliances and people

More information

ENSC 388: Engineering Thermodynamics and Heat Transfer

ENSC 388: Engineering Thermodynamics and Heat Transfer ENSC 388: Engineering Thermodynamics and Heat Transfer Experiment 3: Free and Forced Convection Objective Determination of heat transfer coefficient for free and forced convection for different geometries.

More information

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device J R Mehta 1, A A Sujela 2 1 Department of Mechanical Engineering, Faculty of Technology and Engineering,The Maharaja

More information

Bench Top Cooling Tower H893

Bench Top Cooling Tower H893 Bench Top Cooling Tower H893 Figure 1: H893 Shown with Column B (fitted) and Optional Column E Demonstrates all processes found in a full scale forced draught cooling tower Rapid stabilisation allows experimental

More information

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes

More information

CTI Sponsored Educational Program

CTI Sponsored Educational Program Presented By: Kent Martens SPX Cooling Technologies, Inc. Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Psychrometry One of the Fundamental Series D C B A C B D A July 2012 TRG-TRC001-EN Psychrometry One of the Fundamental Series A publication of Trane Preface Psychrometry A Trane

More information

AR/IA/UP 241 Lecture 5: Psychrometrics

AR/IA/UP 241 Lecture 5: Psychrometrics Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is

More information

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler International Journal of Thermal Technologies E-ISSN 2277 4114 2015 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Effect of Operating Parameters on the

More information

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM - 1 - EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM Shun YOSHIOKA, Hyunyoung KIM, Kazushige KASAI, Daikin Industries,

More information

Mechanical Engineering Laboratory

Mechanical Engineering Laboratory Mechanical Engineering Laboratory MEE 416 Professor H. Ezzat Khalifa Syracuse University http://lcs.syr.edu/faculty/khalifa/mee416/ MEE416 1 A. Experiment 1 Air-Conditioning: Air-side Experiment 0031 Link

More information

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a CHAPTER 9 REFRIGERATION & AIR-CONDITIONING YEAR 2012 ONE MARK Common Data For Q. 1 and Q.2 A refrigerator operates between 120 kpa and 800 kpa in an ideal vapour compression cycle with R-134a as the refrigerant.

More information

Prediction of Sweet Corn Seeds Field Emergence under Wet Soil Condition

Prediction of Sweet Corn Seeds Field Emergence under Wet Soil Condition Kasetsart J. (Nat. Sci.) 41 : 227-231 (27) Prediction of Sweet Corn Seeds Field Emergence under Wet Soil Condition Vichai Wongvarodom* and Wikanate Rangsikansong ABSTRACT Field emergence prediction of

More information

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this lecture are to: 1. Importance of complete vapour compression refrigeration

More information

Performance Optimization of the Evaporative Condenser Design

Performance Optimization of the Evaporative Condenser Design Performance Optimization of the Evaporative Condenser Design Mit. C. Patel P.G.Student, Mech. Engg.Dept. Institute of Technology, Nirma University, Ahmadabad, Prof. B. A. Shah Mechanical Engineering Department

More information

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS MASS BALANCES, PSYCHROMETRICS & HVAC 1 Copyright 2018. All rights reserved. How to use this book The exam specifications in effect since

More information

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump Available online at www.sciencedirect.com Procedia Engineering 8 (2011) 165 170 2 nd International Science, Social-Science, Engineering and Energy Conference 2010: Engineering Science and Management Hot

More information

Heating Ventilation and Air Conditioning Laboratory

Heating Ventilation and Air Conditioning Laboratory Heating Ventilation and Air Conditioning Laboratory Lab.Incharge: Mr.Adnan Qamar (Lecturer) Coordinating Staff: Khawar Siddique (Lab Assistant) Muhammad Usman Saleem (Lab Assistant) Description of Lab.

More information

R07. Answer any FIVE Questions All Questions carry equal marks *****

R07. Answer any FIVE Questions All Questions carry equal marks ***** Set No: 1 III B.Tech. II Semester Supplementary Examinations, April/May 2013 REFRIGERATION AND AIR CONDITIONING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions

More information

14 Drying. I Basic relations and definitions. Oldřich Holeček, Martin Kohout

14 Drying. I Basic relations and definitions. Oldřich Holeček, Martin Kohout 14 Drying Oldřich Holeček, Martin Kohout I Basic relations and definitions Drying is a process which is used for removing the liquid from the solid material. In standard chemical engineering practice drying

More information

Thermo-physical properties found on most psychrometric charts

Thermo-physical properties found on most psychrometric charts Psychrometric Chart The psychrometric chart displays the relationship between dry-bulb, wet-bulb, and dew point temperatures and specific and relative humidity. Given any two properties, the others can

More information

THERMAL ENGINEERING LABORATORY II. To train the students with principles and operation of thermal Engineering equipments.

THERMAL ENGINEERING LABORATORY II. To train the students with principles and operation of thermal Engineering equipments. AIM: THERMAL ENGINEERING LABORATORY II To train the students with principles and operation of thermal Engineering equipments. OBJECTIVES: To experimentally analyze conduction, convection and radiation.

More information

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System A D Parekh, and P R Tailor Abstract Because of damaging effect of CFC refrigerants on stratospheric

More information

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure. 1 PSYCHROMETICS Psychrometry is the study of the characteristics of moist air. We will see soon that evaporation of moisture from the skin can have a significant impact on thermal comfort. The rate of

More information

A/C Cooling Load calculation and measurement

A/C Cooling Load calculation and measurement Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying

More information

In-Field Quantification of Fan Performance in Tunnel-Ventilated Freestall Barns ABSTRACT INTRODUCTION

In-Field Quantification of Fan Performance in Tunnel-Ventilated Freestall Barns ABSTRACT INTRODUCTION In-Field Quantification of Fan Performance in Tunnel-Ventilated Freestall Barns by Katherine Lankering, Research Associate Curt Gooch, P.E., Senior Extension Associate Scott Inglis, Research Associate

More information

2. HEAT EXCHANGERS MESA

2. HEAT EXCHANGERS MESA 1. INTRODUCTION Multiport minichannel and microchannel aluminium tubes are becoming more popular as components in heat exchangers. These heat exchangers are used in various industrial applications and

More information

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED International Journal of Mechanical Engineering and Technology (IJMET) Volume 7, Issue 3, May June 2016, pp.329 341, Article ID: IJMET_07_03_030 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=7&itype=3

More information

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions N. Prabhu Kishore 1, N. Alekhya 2, J. Ugandhar 3 Asst. Professor, Department of Mechanical Engineering, MLR Institute of Technology,

More information

Impacts of room temperature on the performance of a portable propane air conditioner

Impacts of room temperature on the performance of a portable propane air conditioner Impacts of room temperature on the performance of a portable propane air conditioner Ahmad Sharifian 1, Jeri Tangalajuk Siang 2 1,2 Computational Engineering and Science Research Centre (CESRC), School

More information

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack #1 Digvijay A. Shelar, #2 N.S. Gohel, #3 R. S. Jha #1 Mechanical Engineering Department,

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

Optimization of Compressors used in Air Conditioning Units

Optimization of Compressors used in Air Conditioning Units Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2018 Optimization of Compressors used in Air Conditioning Units Joel Vinod Aralikatti Bradley

More information

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Marco Alexandre Onofre Dias This paper presents a model that was implemented

More information

All rights reserved, Armando B. Corripio, PhD, PE, Solid Dryer Design Introduction Continuous Dryer Design...

All rights reserved, Armando B. Corripio, PhD, PE, Solid Dryer Design Introduction Continuous Dryer Design... Solid Dryer Design All rights reserved, Armando B. Corripio, PhD, PE, 2014 Contents Solid Dryer Design... 1 Introduction... 2 1. Continuous Dryer Design... 3 1.1 Mass Balances... 4 1.2 Temperature Profiles...

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Research On Gas Injection High Temperature Heat Pump With

More information

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International Psychrometrics: The Science of Moisture in Air Presented by Tom Peterson, CEO and Founder Climate by Design International www.cdihvac.com Owatonna, MN 507-451-2198 4 02/2014 1 Psychrometrics or psychrometry

More information

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps

More information

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Session 2633 Development of a Psychrometric Test Chamber Michael J. Swedish Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Acknowledgments The design of the Psychrometric

More information

Mathematical Simulation of Longan Fruit Drying

Mathematical Simulation of Longan Fruit Drying Mathematical Simulation of Longan Fruit Drying Aree Achariyaviriya, Somchart Soponronnarit and Jirawan Tiansuwan ABSTRACT The objectives of this study were to develop a mathematical model and to simulate

More information

Redesign of Bennett Hall HVAC System

Redesign of Bennett Hall HVAC System MEE 488 April 18, 2006 Redesign of Bennett Hall HVAC System Greg Andreasen Michael Chicoine Florent Hohxa Jason Jacobe Mechanical Engineering, University of Maine, Orono ME 04473, USA ABSTRACT Our task

More information

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Experimental performance evaluation of heat pump by using CO 2 as a refrigerant To cite this article: V K Venkatesh et al 2016

More information

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) 4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger International Journal of ChemTech Research CODEN( USA) IJCRGG ISSN 0974-4290 Vol.5, No.2, pp 925-934, April-June 2013 ICGSEE-2013[14th 16th March 2013] International Conference on Global Scenario in Environment

More information

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Energy and Buildings 39 (2007) 702 708 www.elsevier.com/locate/enbuild Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU Ming-Tsun Ke a, *, Kuo-Liang

More information

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER THERMAL SCIENCE: Year 2016, Vol. 20, No. 1, pp. 267-277 267 PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER by Nurettin YAMANKARADENIZ a, K. Furkan SOKMEN d, Salih COSKUN a*, Omer KAYNAKLI b,

More information

Air & Water Heat Pump R832

Air & Water Heat Pump R832 Figure 1 : R832 P.A. Hilton Ltd Air & Water Heat Pump R832 Vapour Compression Heat Pump that allows Performance Investigation from both Air and Water Sources. Rapid Stabilisation enables detailed Investigation

More information

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE Journal of Sustainability Science and Management Volume 9 Number 1, June 2014: 150-155 ISSN: 1823-8556 Penerbit UMT PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE ARFIDIAN

More information

Drying Parawood with Superheated Steam

Drying Parawood with Superheated Steam American Journal of Applied Sciences 4 (4): 215-219, 2007 ISSN 1546-9239 2007 Science Publications Drying Parawood with Superheated Steam Surachai Bovornsethanan and Somchai Wongwises Department of Mechanical

More information

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal Summary Refrigeration air coolers (evaporators) are widely

More information

Effect of Parameters on Internal Flow Patterns of a Top Heat Mode Closed-loop Oscillating Heat Pipe with Check Valves (THMCLOHP/CV)

Effect of Parameters on Internal Flow Patterns of a Top Heat Mode Closed-loop Oscillating Heat Pipe with Check Valves (THMCLOHP/CV) Australian Journal of Basic and Applied Sciences, 5(7): 638-643, 2011 ISSN 1991-8178 Effect of Parameters on Internal Flow Patterns of a Top Heat Mode Closed-loop Oscillating Heat Pipe with Check Valves

More information

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN ISSN 2229-5518 865 Abstract global warming and as a result, ambient temperature is rising significantly. Refrigeration and air- cooling systems are becoming necessary in almost all parts of India, even

More information

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Experimental

More information

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM Suhail Ahmad Khan Department of Mechanical Engineering, Aligarh Muslim University, Aligarh (India) ABSTRACT Energy analysis

More information

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier Rohit R. Parab Mechanical Engineering Department Vishwakarma Institute of Technology, Pune, India Laxmikant D. Mangate Mechanical Engineering

More information

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER International Journal of Scientific & Engineering Research, Volume 5, Issue 10, October-2014 676 Performance Evaluation of Alternative Evaporative Cooling Media Rajesh Maurya*, Dr. Nitin Shrivastava, Vipin

More information

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James

More information

LOW RECIRCULATION RATE EVAPORATORS

LOW RECIRCULATION RATE EVAPORATORS WHITE PAPER LOW RECIRCULATION RATE EVAPORATORS Written by: Jeff Welch President Welch Engineering Corporation Abstract Fin coil evaporators with enhanced internal tube surfaces allow for optimum performance

More information

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles Available online at www.sciencedirect.com ScienceDirect Agriculture and Agricultural Science Procedia 2 ( 2014 ) 207 211 ST26943, 2nd International Conference on Agricultural and Food Engineering, CAFEi2014

More information

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES THERMAL SCIENCE, Year 2011, Vol. 15, No. 2, pp. 467-475 467 EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES by Krishnasamy SENTHILKUMAR a* and Pss

More information

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES International Journal of Mechanical and Materials Engineering (IJMME), Vol. 2 (2007), No. 2, 109--117. EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES M. Hasanuzzaman

More information

Performance investigation of Air-conditioning system using ejector as expansion device

Performance investigation of Air-conditioning system using ejector as expansion device International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Performance

More information

Mechanical Heat Pump R515

Mechanical Heat Pump R515 P.A.Hilton Ltd Mechanical Heat Pump R515 Above: R515 shown fitted with standard wattmeter Stabilises in minutes allowing many tests to be conducted in a typical laboratory period. Allows a complete refrigerant

More information

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

S.A. Klein and G.F. Nellis Cambridge University Press, 2011 12.A-1 A mixture of helium and water vapor is flowing through a pipe at T= 90 C and P = 150 kpa. The mole fraction of helium is y He = 0.80. a.) What is the relative humidity of the mixture? b.) What is

More information

Investigation of Evaporator Performance with and without Liquid Overfeeding

Investigation of Evaporator Performance with and without Liquid Overfeeding Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Investigation of Evaporator Performance with and without Liquid Overfeeding

More information

Inbred Planting Technique for Nakhon Sawan 3 Hybrid Maize Seed Production

Inbred Planting Technique for Nakhon Sawan 3 Hybrid Maize Seed Production Kasetsart J. (Nat. Sci.) 44 : 776-782 (2010) Inbred Planting Technique for Nakhon Sawan 3 Hybrid Maize Seed Production Chutima Koshawatana 1 *, Pichet Grudloyma 2 and Wimonrut Indan 2 ABSTRACT In Nakhon

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7

More information

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Experimental Study of Direct Contact Condensation of Steam on Water Droplets , July 1-3, 2015, London, U.K. Experimental Study of Direct Contact Condensation of Steam on Water Droplets Semra GUMRUK, Murat K. AKTAS Abstract Air or water cooled condensers are used to reduce the moisture

More information

Fan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10

Fan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10 Fan Laws Keith Miller Samuel Tepp Associates Paul Cenci, P. E.-Principal Brian England-Principal Basic Terms CFM - Cubic Feet per Minute, volume (amount) of air being moved SP - Static Pressure, resistance

More information

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source

More information

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During

More information

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible

More information

Refrigerant Mass and Oil Migration During Start-up Transient

Refrigerant Mass and Oil Migration During Start-up Transient Refrigerant Mass and Oil Migration During Start-up Transient Steffen Peuker, Predrag Hrnjak* Department of Mechanical and Industrial Engineering University of Illinois at Urbana-Champaign 1206 West Green

More information

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) www.blowtech.in we make air move Blowtech Air Devices Pvt. Ltd. was founded in 1988 and quickly established

More information

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature International Journal Of Computational Engineering Research (ijceronlinecom) Vol 3 Issue 3 Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

More information

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional

More information

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Improving Heating Performance of a MPS Heat Pump System With Consideration

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers University of Nebraska - Lincoln From the SelectedWorks of David Yuill Summer July 9, 2018 Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

More information

Specific Energy Consumption of Heat Pump Drying System

Specific Energy Consumption of Heat Pump Drying System Mindanao Journal of Science and Technology Vol.14 (2016) 131-145 Specific Energy Consumption of Heat Pump Drying System Adonis A. Closas 1* and Eliseo P. Villanueva 2 1 College of Engineering and Architecture

More information

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A

More information

System Modeling of Gas Engine Driven Heat Pump

System Modeling of Gas Engine Driven Heat Pump Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 System Modeling of Gas Engine Driven Heat Pump Isaac Mahderekal shenb@ornl.gov

More information

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes ME 410 - Mechanical Engineering Systems Laboratory Experiment 3 - Mass and Energy Balances in Psychrometric Processes Assist.Prof.Dr. Özgür BAYER, A-123 AIR-CONDITIONING (A/C) Goal: Control temperature

More information

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1 HEFAT27 5 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp PERFORMANCE ANALYSIS OF AIR-COOLED CONDENSER USING MICRO-FIN TUBES P.A.Patil

More information

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc. The Basics - B Practical Psychrometrics Jerry Cohen President Jacco & Assoc. Who is Jacco Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Focused on the Engineered Environment Systems Knowledgeable

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

Fan Selection. and Energy Savings

Fan Selection. and Energy Savings Fan Selection and Energy Savings Reducing power consumption by minimizing system pressure loss and choosing the right equipment HBy BRIAN MLEZIVA Greenheck Fan Corp. Schofield, Wis. Power Consumption HVAC

More information