Description of All Alternatives Considered-
|
|
- Dorthy O’Neal’
- 5 years ago
- Views:
Transcription
1 Description of All Alternatives Considered- Energy efficiency is an area where the Tubman design can be improved. The design heating load is MBH and the design cooling load is MBH or 142 tons. There are (2) 1040 MBH boilers which are slightly oversized. There are (2) ton air-cooled chillers or 243 tons of cooling. Approximately 70 tons of that cooling is for areas where exhibits are either displayed or stored, so there is redundancy for those critical spaces The first alternative investigated was resizing the chillers so there is a smaller chiller for off-hours cooling and a larger one for occupied mode. This would make sense since the museum will have low load profiles during the evenings when only the exhibit spaces needed to be cooled. The second alternative was adding a cooling tower. The chillers could be switched from air cooled to water cooled. Water-side economizers can be installed to allow efficient winter cooling. Recovery of condenser heat is efficient way to provide reheat for dehumidification, which reduces energy cost. Although all of these advantages are good, the ultimate problem is the lack of a cooling tower in the original design. Based on conversation with the engineer who designed the building, the owner did not want a cooling tower on top of the building distracting from the large dome shape on the top of the roof. There is no where on the ground around the footprint of the building to place a cooling tower. The third alternative was switching from constant speed pumping to variable speed pumping. There are many advantages to such system. They are: improved efficiency (motor and pump) and consequently energy savings; reduced system noise; improved control of system flow to respond to flow and pressure requirements of the system; extended motor life due to soft stops & starts which puts less wear and tear on the parts of the pump; control valve in the bypass ensures that neither of the chillers would become starved during a low load situation, as flow is diverted directly from the supply back to the chillers. I choose to look at the first and third alternatives based on the potential energy savings and feasibility.
2 Description of Existing System- The following is a sequence of operation of the air side and water side of the HVAC system. AHU-1A & 1B: These air handling units are constant volume and serve the gallery spaces. Therefore, the system is always running (occupied mode) since the artifacts always need to have a very controlled environment. Occupied Mode- The fan runs continuously throughout the cycle after the supply and return dampers are closed. The discharge air temperature is set at 50.5 F leaving the cooling coil. In order to maintain this temperature, the control valve modulates the chilled water running through the cooling coil. The variable frequency drives (VFD) on the supply fans shall modulate in order to maintain the necessary duct static pressure which the constant volume terminal boxes need to function properly. CO 2 Demand Controlled Ventilation- The minimum outdoor air damper is open for all hours of operation, which is set at 2,000 CFM for the base ventilation rate. The maximum outdoor air set point is 15,000 CFM. CO 2 demand controls the secondary outdoor air damper. The return air and outdoor air dampers are modulated as required to satisfy all the CO 2 space sensor requirements. The maximum CO 2 set point is 900 PPM. The DDC system monitors the outdoor air CO 2 to ensure permissible levels. This value needs to be investigated because it is higher than the allowance given in Standard 62, which states the maximum is 700 PPM plus ambient CO 2.
3 AHU-2: This air handling unit is variable volume and serves the offices and meeting spaces. Occupied Mode- The unit runs continuously under static pressure control. It has an economizer cycle for free cooling. When the outdoor air temperature is below 55 F, the secondary outdoor air damper opens and the return air damper closes while maintaining the same discharge air temperature. When the outdoor air temperature is above 55 F, the secondary outdoor air damper closes and the return air damper will fully open since there is no economizing possibility. The cooling coil valve will modulate open. When cooling is required the following steps will be taken: 1) Utilize outdoor air for cooling. 2) When the return air damper is closed, if the cooling coil leaving air temperature raises 3 F above the set point for 60 seconds, the control valve for the cooling coil opens allowing chilled water flow. 3) When the outside air temperature rises above the economizer set point, the secondary outside air damper will close 100% and Unoccupied Mode- The outdoor and exhaust dampers close and the supply and return fans cycle as required keeping the space at 85 F during the summer and 65 F during the winter. CO 2 Demand Controlled Ventilation- The minimum outdoor air damper is open for all hours of operation, which is set at 1,000 CFM for the base ventilation rate. The maximum outdoor air set point is 4,000 CFM. CO 2 demand controls the secondary outdoor air damper. The return air and outdoor air dampers are modulated as required to satisfy all the CO 2 space sensor requirements. The maximum CO 2 set point is 900 PPM. The DDC system monitors the outdoor air CO 2 to ensure permissible levels. This value needs to be investigated because it is higher than the allowance given in Standard 62, which states the maximum is 700 PPM plus ambient CO 2.
4 Hot Water System: The hot water boiler plant runs continuously year round. The base hot water supply temperature is 140 F and maximum is 160 F. Hot Water Pumps- The first pump is turned on by the automatic temperature control (ATC). The second pump starts if, when the first pump is operating, the hot water return temperature drops 25 F below the hot water supply set point for 10 minutes. The second pump turns off when the hot water return temperature is 10 F below the hot water supply temperature set point for 10 minutes. Chilled Water System: The ATC in unison with the DDC controls all aspect of cycling the chillers. When cooling is called for, the control valve at the chiller opens and the associated chilled water pump turns on. When flow through the piping is proven by evaporator differential pressure, the chiller starts and runs. The chiller shall operate to maintain 45 F chilled water supply temperature. The lead/lag chiller shall be switched by the building management system. Both chillers and associated pumps shall be programmed in a leadlag scenario. Both chiller 1 and 2 can be turned off. The second chiller is turned off when both chillers are running at below 40% of capacity for 10 minutes. The drawings do not clearly state what is being measured to determine the percentage of capacity of the chillers. This control system must be investigated. The following is a summary of the components of the chilled water system: (2) Trane (Model RTAA125) air-cooled water chillers. - Capacity = tons - Flow Rate = 290 GPM - Entering Water Temperature (EWT) = 55 F - Leaving Water Temperature (LWT) = 45 F - Screw compressor
5 (3) Bell & Gossett pumps (Model ½ BB) [Note: One of the pumps is stand-by] GPM - 55 ft. head ft. NPSHR impeller RPM BHP motor HP Although the controls at the loads (the three air handling units) are not shown on any of the construction drawings that I possess, it appears to be a constant primary-only system. Two of the air handling units are constant volume and serve the gallery spaces. Therefore, the system is constantly running since the artifacts continuously need to have a very controlled environment. The other unit air handling unit is variable volume and serves the offices and meeting spaces. If the load goes to half and it is all on one air handling unit (such would be the case at night when the offices and other spaces were empty), with the current system the water separates into both branches of the supply piping, but goes straight through the bypass for the air handling unit that doesn t need chilled water. The other air handling unit is potentially starved when this situation arises.
6 Description of Proposed Redesign (Mechanical Considerations)- The three-way valves are replaced with two-way valves at the air handling units with two-way valves costing less than three-way valves. There is also less piping that needs to be around the load. The omitted fittings and welds also increase the cost savings. A flow meter could be installed instead of a differential pressure loss sensor around the evaporator. There is currently a combination flow meter/shutoff/balancing valve (circuit setter) shown on the plans. There is no manufacturer listed or any accuracy measurements given for it. This information would have to be checked before deciding whether the flow meter would have to be replaced in the new system. Calculating the actual pumps savings- There are several different techniques available for calculating the energy savings of variable speed pumps. I plan on using the following to determine the kwh saved switching to variable speed pumps. Carrier s Hourly Analysis Program (HAP) Bell & Gossett ESP-Plus Online Program EES Simulation Determining the payback period of time to justifying the additional cost will be performed using Microsoft Excel. Calculating the actual chiller savings- I plan on using Carrier s Hourly Analysis Program (HAP) to determine savings switching to a smaller and a larger chiller than the current two, equally sized chillers.
7 Preliminary Research Biography- ASHRAE Applications 1999, Chapter 20, Bernier, M., B. Bourret Pumping Energy and Variable Frequency Drives. ASHRAE Journal December 1999: Bahnfleth, W., E.Peyer Comparative Analysis of Variable and Constant Primary- Flow Chilled-Water-Plant Performance. HPAC Engineering April 2001: Coad, W A Fundamental Prospective on Chilled Water Systems. HPAC Heating/Piping/AirConditioning August 1998: Ellis, R., Commissioning a Museum and Archival Storage Facility. ASHRAE Transactions Pt. 1, 1996, p Gill, N Adjustable Speed Pumps: Your Control Valve Alternative? Hartman, T., Library and Museum HVAC: New Technologies/New Opportunities Part 1. HPAC Heating/Piping/AirConditioning April 1996: Hartman, T., Library and Museum HVAC: New Technologies/New Opportunities Part 2. HPAC Heating/Piping/AirConditioning May 1996: 63, 64, 67, 68, 72 & 103. Hegberg, R Converting Constant-Speed Hydronic Pumping System to Variable- Speed Pumping. ASHRAE Transactions Pt ASHRAE Winter Meetings Technical Papers: Pacific Gas and Electric Company CoolTools Chilled Water Plant Design and Specification Guide.
8 Martino, F Elusive Energy Savings: Centrifugal Pumps and Variable Speed Drives. Rishel, J The History of HVAC Variable-Speed Pumping. ASHRAE Transactions No. 1, 1995 ASHRAE Winter Meetings Proceedings: R.S. Means 2002 Mechanical Cost Data: pg 194, 240. Schwedler, M., B.Bradley An Idea for Chilled-Water Plant Whose Time Has Come Variable-Primary-Flow Systems. Trane Engineers Newsletter Volume 28, No. 3.
The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and
More informationA. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.
SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate
More informationHVAC Controls Upgrades: Requirement Details ( )
REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in
More informationSubmitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University
More informationAndrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3
Existing System Evaluation Executive Summary The MBNA Career Services Center is a 44,000 square foot, 4-story office type building at Penn State University, University Park Campus. The building is located
More informationMechanical Systems Design
Mechanical Systems Design After much deliberation and a long process of brainstorming ideas for potential mechanical system designs for the, it was finally decided to design a central chilled water plant
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationTechnical Assignment #2a. Atlanta, GA Green Building Mechanical
Tubman African American Museum Technical Assignment #2a Chris Champagne Atlanta, GA Green Building Mechanical Green Building Certification Analysis- The major categories of the U.S. Green Building Council
More informationEnergy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters
Energy Efficiency Through Waste Heat Recovery Heat Recovery Centrifugal Chillers and Templifier Water Heaters Innovative Solutions for Saving Energy McQuay offers two innovative methods of saving energy
More informationSubmitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas
More informationMechanical Technical Report 3. Mechanical Systems Existing Conditions Evaluation
Mechanical Technical Report 3 Lutheran Theological Seminary at Philadelphia The New Learning Center Prepared For: William P. Bahnfleth, Ph.D., P.E. Department of Architectural Engineering Pennsylvania
More informationHVAC Controls Upgrades: Requirement Details ( )
REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,
More informationTechnical Assignment 3. Mechanical Systems Existing Conditions Evaluation
Technical Assignment 3 Mechanical Systems Existing Conditions Evaluation The Milton Hershey School New Supply Center Prepared for: William P. Bahnfleth, Ph.D., P.E., Professor Department of Architectural
More informationUpdate Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South
3/5/2018 1 Update Dedicated Heat Recovery Chiller Technology Don Frye Gulf South Good design is an intentional act Begin with the end in mind Basic Bldg Tenants IAQ (low VOC & CO 2 ) Controlled Temp &
More informationDISTRIBUTION SYSTEMS. Water Piping and Pumps
DISTRIBUTION SYSTEMS Water Piping and Pumps Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are targeted
More informationRetrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems
IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationUrbana Free Library HVAC Analysis. Prepared for the Urbana Free Library. Prepared by Paul Boland, P.E., and Nathan Alderman, E.I.T.
Urbana Free Library HVAC Analysis Prepared for the Urbana Free Library Prepared by Paul Boland, P.E., and Nathan Alderman, E.I.T. Report Dated August 8, 2016 1. Introduction The Urbana Free Library is
More informationTechnical Assignment 3 11/15/04. Executive Summary
Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION BASIC MECHANICAL REQUIREMENTS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Assume that buildings will be enlarged and modified in the future. 1. Make provisions for future interconnections, upgrading, and expansion of
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationThe Temperature and Relative Humidity Control in Cushing Library
The Temperature and Relative Humidity Control in Cushing Library Chenggang Liu Research Associate Song Deng Assistant Director Homer L. Bruner, Jr., CEM Mechanical Systems Specialist Utilities Office of
More informationFAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney
FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1
More informationSYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC
VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things
More informationTechnical Report #3 Mechanical Systems Existing Conditions Evaluation
Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents
More informationMECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY
MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY 2018 57 MECHANICAL ASSESSMENT MECHANICAL ASSESSMENT This report section includes an overview of the existing
More informationDesign Standard. Thermal Systems (Chilled Water and Hot Water Systems) Detailed specifications follow. CHW AND HHW SUPPLY TEMPERATURE RESET
Design Standard Detailed specifications follow. PART 1 CHW AND HHW SUPPLY TEMPERATURE RESET 1.1 The Utilities & Energy Services Department (UES) at Texas A&M University is actively identifying and implementing
More informationBES-TECH TECHNOLOGY & SYSTEM INTEGRATION
BES-TECH TECHNOLOGY & SYSTEM INTEGRATION BES-TECH TECHNOLOGY & SYSTEM INTEGRATION DIGI-ACC Digi-ACC is a control kit for air cooled chiller systems, optimizing both chiller and pumps thereby reducing consumption
More informationArchitectural Engineering Senior Thesis Mechanical System Redesign
Saint Joseph Medical Center Architectural Engineering Senior Thesis Mechanical System Redesign Chris Nicolais Building Description Existing Mechanical System Proposed Redesign Alternative Option Emergency
More informationTerminal. Las Vegas, NV. Technical
McCarran International port Terminal 3 Technical Assignment 3 Mechanical System Existing Conditions Evaluation December 3, 2007 Prepared By: Faculty Advisor: Dr. William Bahnfleth, Ph.D., P..E. Table of
More informationUNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationF.W. Olin Physical Science Laboratory
Mechanical Systems Existing Conditions Evaluation Presented on Page 1 of 16 Table of Contents Executive Summary Depth p.3 Executive Summary Breadth p.4 Introduction & Background p.5 Alternatives p.7 Breadth
More informationSenior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1
Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9
More informationSubmitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner
ESL-TR-99/12-09 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Commerce (TAMU-Commerce) Commerce, Texas Submitted to Texas
More informationSECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL
SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division
More informationb.) Technical Information:
Section VI- Strategies a.) Summary: It is important for new construction designers to consider the heating, ventilation, and air conditioning needs within a building. There are many different systems,
More informationChiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off
Application Guide AG 31-003-1 Chiller Plant Design 51.5F Return Water To Chiller Two 400 Ton Chillers Each At 300 Tons (Balanced Load) 51.5F 480 gpm Flow Through Decoupler 44F 54F Building Load 600 Tons
More informationSECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...
SECTION 230001 TABLE OF CONTENTS SECTION 230001 PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS... 1 1.00 FILED SUB BID... 1 1.01 PROJECT OVERVIEW... 2 1.02 DESIGN CRITERIA... 4 1.03 CODE ISSUES...
More informationWater Piping and Pumps
Technical Development Program DISTRIBUTION SYSTEMS Water Piping and Pumps PRESENTED BY: Michael Ho carriertdp@gmail.com 424-262-2144 Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section
More informationINTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings
INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,
More informationDIGI-VAV APPLICATIONS
DIGI-VAV DIGI-VAV APPLICATIONS Digi-VAV: An optimization kit for Variable Air Volume Air Handling Units (VAV AHU) that ensures individual zone indoor air quality (IAQ), and minimizes system energy consumption.
More informationChiller Plant Design. Julian R. de Bullet President debullet Consulting
Chiller Plant Design Julian R. de Bullet President debullet Consulting 703-483-0179 julian@debullet.com This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer ASHRAE
More informationState of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney
Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled
More informationEarthWise System Seminar
EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States
More informationBenefits Offered by Passive Dehumidification Wheel Speed Control
Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle
More informationEnergy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE
This article was published in ASHRAE Journal, March 20145 Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationNET ENERGY WATER LOOPS A clear path to net zero energy buildings
Presents NET ENERGY WATER LOOPS A clear path to net zero energy buildings Alan Niles WaterFurnace International This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer
More informationComputing Services Center
Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationAHU Air Handling Unit Fundamentals. j.ilangumaran
AHU Air Handling Unit Fundamentals j.ilangumaran Objectives Review primary components of an AHU Understand the basic progression and advantages of advanced AHU control Understand the basic control sequences
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#56566/Page 1/May 23, 2017 HVAC Heating Plant The original Town Hall building and Addition building are primarily heated by a gas fired hot water plant that is located in the basement. The boiler plant
More informationDIVISION 15 MECHANICAL
DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with
More informationH3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog
H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...
More informationInspection Phase Three. Mechanical, Electrical & Plumbing Section 503
Inspection Phase Three Mechanical, Electrical & Plumbing Section 503 COMCheck Mechanical Field Inspection Checklist Mechanical Mechanical, Electrical & Plumbing Equipment Efficiencies But a lot ore too
More informationASHRAE Illinois Chapter 2015 Excellence in Engineering Awards
ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards PROJECT Chicago Vocational Career Academy Chicago, Illinois OWNER Chicago Public Schools PREPARED FOR American Society of Heating Refrigerating
More informationSequence of Operations (excerpt)
Sequence of Operations (excerpt) Chilled Water System Consists of one (1) 600 cooling ton Trane CVHE 3 stage centrifugal chiller, with associated chilled water pumps, condenser water pumps and one (1)
More informationAgenda and Objectives
Agenda and Objectives Trane Engineers Newsletter Live Series Variable-Speed Drives (VSDs) and Their Effect On HVAC System Components Variable-speed drives (VSDs) can save energy, but the savings may not
More informationMechanical System Redesign. Dedicated Outdoor Air System. Design Criteria
Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed
More informationCOMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume
COMMERCIAL HVAC PACKAGED EQUIPMENT Rooftop Units Level 1: Constant Volume Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#57295/Page 1/July 21, 2017 HVAC SYSTEMS NARRATIVE REPORT The following is the HVAC system narrative, which defines the scope of work and capacities of the HVAC system as well as the Basis of Design.
More information9/18/2017. Nicholas Thornton, CEM. Systems: HVAC, Electrical, and Technology. Overview. Today s Goals Introductions HVAC Electrical Technology Q&A
Nicholas Thornton, CEM 1 Overview Today s Goals Introductions HVAC Electrical Technology Q&A 2 1 Today s Goals An overview, a crash course Maybe a few tangents (ASK QUESTIONS!) Show typical arrangements
More informationMechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013
Mechanical Redesign, Proposal Elizabeth C. Mechanical Option September 18, 2013 State Institute of Rehabilitation T e c h n i c a l R e p o r t I 1 Mechanical Redesign, Proposal... 0 Executive Summary...
More information1 - This title will copy onto other forms Date
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 Mechanical Summary MECH-SUM Project Title: 1 - This title will copy onto other forms Date 1/1/2015
More informationCARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.
Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using
More informationSEQUENCE OF OPERATIONS
SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,
More informationterminal units only provide sensible cooling, a separate dehumidification system is usually needed.
providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can
More informationHigh Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO
High Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO 2012 1 Learning Objectives for this Session Get acquainted with typical systems used in the
More information7. MECHANICAL SYSTEM DESIGN
7. MECHANICAL SYSTEM DESIGN The second primary topic of this thesis is to investigate the application of a dedicated outdoor air system (DOAS) to the SLCC. The stated goals for this thesis of improved
More informationTHERMAL ICE STORAGE: Application & Design Guide
THERMAL ICE STORAGE: Application & Design Guide Table of Contents: 1. Introduction A. History of Thermal Energy Storage B. Operating and Cost Benefits 2. Applications A Fundamental System B. HVAC Cooling
More informationSummary Comparison of Simulation Program Features
Summary Comparison of Simulation Program Features FEATURE DOE2.2 equest TRACE 700 HAP Public/Proprietary Public Domain Proprietary Proprietary Proprietary Simulation Method 8760 hours 8760 hours 8760 hours
More informationAIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University
AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort
More informationPITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS
PITTSBURG STATE UNIVERSITY HVAC and BUILDING AUTOMATION SYSTEM STANDARDS CHILLERS In new construction, liquid-cooled models are preferred for systems larger than 100 ton. o Trane, York and McQuay brands
More informationASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee
ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique CTTC
More informationD-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency
Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)
More informationNEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80
NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80 Carrier Software Systems Carrier Corporation Syracuse, New York rev October 10, 2013 Copyright 2013 Carrier Corporation, All Rights Reserved Page
More informationTrim Pump Impellers. Fredrick/Weinman Engineered Products 2-1/2 KH, 2-1/2 x 3 x 12
Head, ft. w.c. Trim Pump Impellers TRIM THE PUMP IMPELLER SO THE FLOW PRODUCED MATCHES THE DESIGN REQUIREMENT WITH THE DISCHARGE SERVICE VALVE WIDE OPEN. IN MOST CASES, THIS WILL REDUCED THE PUMP ENERGY
More informationLife Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International
Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint Daryl Showalter ChillerApplications Manager McQuay International Equipment Using Different Kinds Of Equipment Or Different Performance
More informationHVAC Myths and Realities Trane Engineers Newsletter Live Series
HVAC Myths and Realities Trane Engineers Newsletter Live Series AGENDA Low delta T is unavoidable 55 F supply air temperature is adequate for today s loads ASHRAE Standard 15 has to be updated before new
More informationMCH Series Drives. HVAC Application Guide. ag-mch-e2
Drives HVAC Application Guide ag-mch-e2 % Flow, Torque, HP AFFINITY LAWS Most HVAC systems are designed to perform during peak load conditions that rarely occur during the year. Various flow control methods
More informationHONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING
ASHRAE s BEST This article was published in ASHRAE Journal, November 2010. Copyright 2010 American Society of Heating, Refrigerating and -Conditioning Engineers, Inc. Reprinted here by permission from
More informationBy Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE
By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE T he advent of the small scroll or screw chiller, capable of producing condenser water as high as 140
More informationMT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS
CARROLL COUNTY PUBLIC SCHOOLS LIFE CYCLE COST ANALYSIS SUMMARY DGS PROCEDURES FOR THE IMPLEMENTATION OF LIFE CYCLE COST ANALYSIS AND ENERGY CONSERVATION OCTOBER, 2010 G.A.I.#09090 GIPE ASSOCIATES, INC.
More informationB. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.
PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the
More informationHVAC 101. The Basics of Heating, Ventilation and Air Conditioning
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning HVAC Heating, Ventilation and Air Conditioning Provides comfort for people Allows humans to exist under adverse conditions. Comfort Comfort
More informationDesign Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationCOMcheck Software Version Review Mechanical Compliance Certificate
COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project
More informationWelcome To. System Benefits With ECM PUMPS
Welcome To System Benefits With ECM PUMPS Hydronic System Efficiency Should we be focusing on more than just the heat source? 2 The hydronic heating industry has put there main focus on the heat source
More informationGeneral HVAC Recommendations
General HVAC Recommendations DESIGN GUIDELINES FOR ENERGY EFFICIENT HVAC SYSTEMS Thank you for your interest in energy efficiency! Energy efficient heating, ventilation, and air conditioning (HVAC) equipment
More informationENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory
Overview of Chilled Beam Technology Purpose Chilled beam technology is new to the United States but has been used in Europe since the 1950 s. Chilled beams can reduce energy costs, improve indoor air quality,
More informationDehumidifying with Dedicated Outdoor Air
Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,
More informationAHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency
Application Note 24 AHRI 920 Performance Rating and Comparisons I NTRODUCTION In 2015, the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) introduced a performance rating for dedicated outside
More informationDaikin Blueprint: Delivering Hot Water with a Chiller
Daikin Blueprint: Delivering Hot Water with a Chiller Analyzing the design of heat recovery on air-cooled chillers and the effect it has on building energy consumption By Paul Crisman Daikin Chiller Applications
More informationPRODUCT SERIES. VPR Series VPRX Series VPRE Series VPRP Series VPRC Series
PRODUCT SERIES VPR Series VPRX Series VPRE Series VPRP Series VPRC Series Valent Air Management Products Valent Air Management Systems designs and manufactures reliable, high-outdoor-air ventilators. Our
More informationEADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option
EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option
More informationTRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE.
Slide 1 TRACE 700 Chiller Sequencing and Controls Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE. Today, we will be talking about the Plant Sequencing and Controls
More informationOSU Alumni Center Phase I Implementation Review. Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon
OSU Alumni Center Phase I Implementation Review Prepared for Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon 97331 October 31, 2011 Job No. 02.11.00113 Introduction: Glumac was engaged by
More informationTechnical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer
Technical Development Program PRESENTED BY: COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems Ray Chow Sales Engineer TDP Updates Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section
More informationShippensburg University
Shippensburg University Horton Hall HVAC Feasibility Study PREPARED FOR: Shippensburg University 1871 Old Main Dr. Shippensburg, PA 17257 SHIPPENSBURG PROJECT: SU-2017/25 RPA PROJECT: 17118.001 DATE: December
More informationTechnical Investigation, Part Three Elizabeth C. Krauss Mechanical Option September 18, 2013
Technical Investigation, Part Three Elizabeth C. Mechanical Option September 18, 2013 State Institute of Rehabilitation T e c h n i c a l R e p o r t I 1 Technical Investigation, Part Three... 0 Executive
More informationSECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of
More informationPaul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA
Continuous Commissioning of a LEED-EB Gold Certified Office Building Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA KEYWORDS Continuous Commissioning, Retro-Commissioning,
More information