1 HPWH 300 HPWH 300HE Installation and Operating Instructions Hot Water Heat Pump for Outdoor Installation FD 9501

2 Table of contents 1 Please read immediately... EN Important notes... EN Intended use... EN Regulations / safety information... EN-2 2 Description... EN General... EN Refrigerant circuit (heat pump operating principle)... EN Safety and control devices... EN-3 3 Storage and transport... EN General... EN Fork lift (or lift truck) transport... EN Manual transport... EN-4 4 Installation... EN Installation location... EN Installation... EN-5 5 Assembly... EN Connecting the water pipes... EN Connecting the condensate hose... EN Electrical connection... EN-6 6 Commissioning... EN Domestic hot water system... EN Operating the domestic hot water heat pump... EN-6 7 Maintenance / repair... EN Water circuit / condensate drain... EN Air circuit supply... EN Corrosion protection anode... EN-8 8 Faults / troubleshooting (for the user)... EN-8 9 Decommissioning... EN-8 10 Environmental requirements... EN-8 11 Device information... EN-9 Appendix... A-I Dimensioned drawing... A-II Integration Diagram... A-III Circuit Diagrams... A-VI FD 9501 EN-1

3 1 Please read immediately 1.1 Important notes Work on the domestic hot water heat pump may only be performed by qualified personnel. Observe accident prevention regulations. The device cover cannot be used for carrying (the cover cannot withstand significant forces). If devices are installed in locations with a risk of frost and are no longer operated or will not be connected to the power for a long period (several hours), the water must be drained from the cylinder. If this is not done, frost may destroy the device. The domestic hot water heat pump must only be operated when filled with water! Disconnect the power supply before opening the domestic hot water heat pump; possible fan coasting must be considered! Malfunctioning protection anodes reduce the service life of the device! (Electrically insulated magnesium anode with selenium complying with DIN 4753 part 6) Work on the domestic hot water heat pump is to be performed by qualified personnel only! Observe accident prevention regulations! DANGER! Failure to operate the PTR Valve easing gear every six months may lead the water heater exploding. Continuous water leaking from the drain may indicate a problem with the water heater. Water may drip from both the pressure relief device and the condensate drain. These pipes must be left open to the atmosphere. 1.3 Regulations / safety information NOTE Read these installation and operating instructions before commissioning! The domestic hot water heat pump is used exclusively to heat water for domestic use and drinking water within the specified operating temperature limits! The heating of fluids other than domestic water is not permitted. The installation must take place in accordance with the Australian standard AS/NZS For domestic use in Australia and New Zealand a TEMPER- ING VALVE must be fitted by the installer. The following are not permitted: - Operating the pump with solvent-based, explosive or chloric exhaust air - The use of exhaust air containing grease, heavy dust or adherent aerosols - Connecting extractor hoods to the ventilation system A PTR Valve must be fitted It is not permissible to operate the device: - With an empty cylinder The refrigerating system meets the requirements of ISO :2014. The technician must ensure that the refrigerant is flushed adequately to allow maintenance and repair work to be carried out on refrigerant circuit components without risk. Refrigerant must be properly handled and disposed of; it must not be released into the environment! The refrigeration circuit is "hermetically sealed" and contains the fluorinated refrigerant R134a with a GWP value of 1430, incorporated in the Kyoto protocol. The refrigerant is CFCfree, non-ozone depleting and non-combustible. Always disconnect the power supply before carrying out any work on the domestic hot water heat pump. When connecting the domestic hot water heat pump to the power supply, the relevant IEC standards and the AS 3000 must be complied with. Also observe the technical connection requirements of the electrical utility companies. Work on the domestic hot water heat pump may only be performed by qualified personnel. Observe accident prevention regulations. 1.2 Intended use This device is only intended for use as specified by the manufacturer. Any other use beyond that intended by the manufacturer is prohibited. This requires the user to abide by the relevant project planning documents. Please refrain from tampering with or alter-ing the device. Persons, especially children, who are not capable of operating the device safely due to their physical, sensory or mental abilities or due to their inexperience or lack of knowledge, must not operate this device without supervision or instruction by the person in charge. Children must be supervised to ensure that they do not play with the device. EN FD

4 2 Description 2.1 General The domestic hot water heat pump is a ready-for-use heating device whose main components are a domestic hot water cylinder, the components of the refrigerant, air and water circuits and the control, regulation and monitoring devices required for automatic operation. The domestic hot water heat pump is supplied with electrical energy and uses the heat stored in the intake air for domestic hot water preparation. The domestic hot water heat pump with internal heat exchanger can be connected to additional heat generators such as boilers and solar energy systems. A vertical cladding tube (inner 12 mm) houses an external temperature sensor. The devices are equipped as standard with an electric heating element (1.5 kw). The temperature of the intake air (the heat source) provides the reference value for the energy consumption and the domestic hot water preparation heating-up time. Falling exhaust air temperatures reduce the heat pump output and increase the heating-up time. In order for the heat pump to be operated economically, the air intake temperature should not fall below 15 C. If the air intake temperature falls below 0 C ±1.5, the heat pump is switched off and the domestic hot water heating is heated by the standard heating element (1.5 kw). 2.2 Refrigerant circuit (heat pump operating principle) The refrigerant circuit is a closed system in which the R134a refrigerant is the energy source. The finned heat exchanger extracts heat from the drawn-in air at a low evaporation temperature, and transfers it to the refrigerant. The vaporous refrigerant is taken in by a compressor, where it is compressed to a higher pressure and temperature level before being transported to the liquefier, where the heat absorbed in the evaporator and part of the compressing energy is transferred to the water. Subsequently, the high condensation pressure is lowered to the evaporation pressure by a throttle mechanism (expansion valve), and the refrigerant can again extract heat from the intake air in the evaporator. 2.3 Safety and control devices The domestic hot water heat pump is equipped with the following safety devices: High pressure switch (HP) The high pressure switch protects the heat pump against unacceptably high operating pressure in the refrigerant circuit and switches the heat pump off in the event of a fault. The heat pump restarts automatically as soon as the pressure in the refrigerant circuit has dropped again. The electric heating element fulfils four functions: Supplementary heating The heat-up time is approximately halved by switching on the heating element (via the "Heating element" switch, see Cap. 6.2 on pag. 6) in addition to the heat pump. Frost protection If the air temperature falls below 0 C ±1.5, the electric heating element switches on automatically and (nominally) heats the water up to the domestic hot water setpoint temperature of 60 C. Emergency heating In the event of a heat pump fault, the domestic hot water supply is maintained by the heating element. Higher water temperature If the required domestic hot water temperature is higher than the temperature achievable by the heat pump (approx. 60 C), it can be raised to a max. of 85 C by means of the heating element. NOTE When the domestic hot water temperature reaches 60 C, the heat pump switches off and the domestic hot water is heated solely by the heating element. The factory setting for the heating element controller is 65 C. Safety temperature limiter for heating element (STL) The STL protects the domestic hot water system against unacceptable temperature increases. The heating element is disconnected all-pole if the set switching value (99 C) is exceeded. The heating element cannot be switched on again until the domestic hot water temperature has decreased to 90 C and the reset button (see illustration) on the STL is pressed (this must only be done by qualified personnel). The domestic hot water heat pump is also equipped with the following regulation and control devices: FD 9501 EN-3

5 Heating element temperature controller (TC) The heating element thermo controller regulates the domestic hot water temperature during heating element operation. The maximum controller temperature is factory set to 65 C (the controller and the STL are installed together in a casing). Temperature settings can be changed using suitable tools (see illustration). Changes to this setting may only be carried out by qualified personnel. In automatic operation (activated via air temperature sensor), the water is heated by the heating element until the setpoint has been reached (60 C). In contrast to heat pump only operation, a smaller amount of water is heated up to minimise the operating period of the heating element. In continuous manual operation, the domestic hot water is heated until the set maximum temperature of the heating element controller has been reached. Heat pump temperature controller Temperature control in the domestic hot water cylinder and the regulation for compressor operation is carried out by the control electronics. A temperature sensor (R3) records the water temperature in the cylinder and another sensor (R1) records the air intake temperature before the evaporator. A further temperature sensor (R10) prevents the evaporator from freezing. 3 Storage and transport 3.1 General The domestic hot water heat pump should always be stored and transported packaged in an upright position, without being filled with water. If handled carefully, the device can be transported over short distances with a maximum tilt angle of 45. Ambient temperatures between -20 and +60 C are permissible during transport and storage. 3.2 Fork lift (or lift truck) transport The domestic hot water heat pump must remain mounted on the pallet when being transported with a fork lift. The pump should be lifted slowly. Because of its high centre of mass, the domestic hot water heat pump must be secured against toppling. To prevent damage, the domestic hot water heat pump must be lowered onto a level surface. 3.3 Manual transport The pallet can be used underneath the device for manual transportation. A second or third carrying position can be created with the help of ropes or carrying slings (these may be wrapped around the cylinder casing and attached to the water pipe nipples). When transporting the heat pump in this manner (or with a hand truck), do not, under any circumstances, exceed the max. tilt angle of 45 (see illustration). If the heat pump can only be transported in a tilted position, the domestic hot water heat pump ("Heat Pump" switch) should not be operated for at least one hour after installation in its final location. The device cover cannot be used for carrying (the cover cannot withstand significant forces). EN FD

6 4 Installation 5 Assembly 4.1 Installation location Condensate drainage (with a siphon) must be provided. The condensate must be discharged without frost. The air taken in may not be excessively contaminated or contain large amounts of dust. The load-bearing capacity of the foundation must be sufficient (the weight of the domestic hot water heat pump is approx. 440 kg!). For fault-free operation and for any maintenance and repair work, minimum clearances of 0.6m are required on all sides of the device. If the BWP is installed in any kind of enclosure, the clearances set out in the figure must be maintained If devices are installed in locations with a risk of frost and are no longer operated or will not be connected to the power for a long period (several hours), the water must be drained from the cylinder. If this is not done, frost may destroy the device. 4.2 Installation Remove the three transport restraint screws (M12 - fixing the device to the pallet) from the bottom of the pallet. Remove the pallet and mount the three M12 supporting feet (in the plastic bag attached to the nipple of the cylinder pipe). Position the domestic hot water heat pump and align it vertically by adjusting the device feet. Then tighten the counter nuts on the device feet. 5.1 Connecting the water pipes The water connections (see Cap. 1 on pag. II) are located on the rear of the unit. Important information: Circulation pipe For energy efficiency reasons, a circulation pipe should not be used if this can be avoided. If a circulation pipe is installed in the domestic hot water distribution system, a valve or a similar device must be provided as shut-off facility to avoid unnecessary energy losses. Circulation is enabled according to use (time or requirement control). The nominal pipe widths for the on-site sanitary installation must be determined by taking into account the available water pressure and any pressure drops expected to occur in the pipework. Water installations must be executed according to the Australian standard AS , also observe local regulations for domestic water installations! The heat pump must be permanently connected to the water mains! Both rigid and flexible water pipes may be used. Install a 500 kpa pressure and temperature relief valve (PTRV)(see Cap. 2.3 on pag. IV) Observe the corrosion behaviour of the pipework materials used in order to avoid corrosion damage (see section "Commissioning"). Pipe nipples (on the cylinder) and water pipes must be protected from frost! The pipe nipples are protected from corrosion with a heat shrinkable tubing. In the connection thread area, the heat shrinkable tubing should only be removed as far as necessary. The transition or interface area should be protected (e.g. with silicon) to provide corrosion protection. A safety valve (PTR valve) must be mounted on-site by the installer. This valve must not be lockable and must not have a shutoff device. NOTE Domestic hot water, cold water, circulation connections: These pipe nipples contain plastic inserts, the purpose of which is to protect against corrosion (in particular to the pipe nipple flange surfaces). These plastic inserts remain in their positions after installation. NOTE When installing the on-site pipework, ensure that the pipes are not contaminated (flush pipes before connecting the domestic hot water heat pump if necessary)! NOTE The PTR Valve must be installed as per the Hydraulic Drawing on page A-IV. Both the PTR Valve and Pressure Reduction Valve must comply with AS FD 9501 EN-5

7 5.2 Connecting the condensate hose The condensate hose is routed out through the sheet metal covering. It should be routed in such a way that the condensate produced (during heat pump operation) can flow away freely - ensure frost-free drainage. There is a pressureless seal valve at the end of the condensate hose, which must be relocated accordingly if the condensate hose is shortened (the valve can be easily removed and re-inserted). 5.3 Electrical connection The domestic hot water heat pump is wired ready for use; power is supplied via the mains power connection, which is plugged into an earthed wall socket (~230 V, 50 Hz). This socket must remain accessible after installation. The installation (electical work) and commissioning, as well as the maintenance of this equipment, must only be carried out by an authorised qualified contractor in accordance with these instructions. Mains power connection replacement The electrical connecting terminal (X2) is located on the partition in the device. Cable type: H07RN-F3G 1.5 mm² Routing in accordance with the original mains power connection via cable entry on the rear wall. Sheath stripping length 85 mm Shorten L/N wires to 55 mm Strip wires 7 mm, fit with cable ferrules and connect to X2: L/ N/PE 6 Commissioning 6.1 Domestic hot water system The domestic hot water heat pump must only be operated when filled with water! Domestic hot water system requirements The following materials can be used in the consumer's domestic hot water system: Copper Stainless steel Brass Plastic Depending on the materials used in the domestic hot water system (customer installation), material incompatibility may lead to corrosion damage. This especially applies to zinc-plated materials and materials containing aluminium. If there is a risk of water contamination during operation, it may be necessary to install a filter. Commissioning the domestic hot water system All installations for the water circuit and air circuit, as well as all electrical installations, must have been carried out correctly and fully completed. Fill the domestic hot water circuit via an external connection. Purge the domestic hot water circuit (open domestic hot water taps at the highest extraction points until there are no more traces of air). Check the entire domestic hot water system for leaks. Establish the power supply. 6.2 Operating the domestic hot water heat pump If the supply cord is damaged, it must be replaced by a special cord or assembly available for the manufacturer or its service agent. Apart from the switch for the electric heating element, there are no other controls on the device. The domestic hot water temperature is preset to 60 C and is regulated automatically. EN FD

8 "Heating Element" switch If there is an increase in hot water consumption or if a higher hot water temperature (60±2 C) is desired, the heating element switch can be used to switch the integrated 1.5 kw radiator on. If the "Heating Element" switch is in the "On" position (switch lit), approx. the upper third of the cylinder will be heated up to the maximum temperature of the heating element controller (factory setting 65 C); at domestic hot water temperatures > 60 C, domestic hot water preparation is carried out using the heating element only. Note Heating element controller The heating element controller is a second control unit for controlling the operating range of the electric heating element, which is completely independent of the domestic hot water controller. The factory set switch-off temperature of 65 C can be changed by a technician (see Cap. 2.3 on pag. 3) Sensor pipe for external temperature sensors A vertical sensor pipe 12mm (opening in the bottom plate sealed with a leading-in tube) for an external temperature sensor is fitted in the rear of the domestic hot water heat pump. 7 Maintenance / repair Disconnect the power supply before opening the domestic hot water heat pump; possible fan coasting must be considered! General The domestic hot water heat pump is virtually maintenance free. Furthermore, a one-off visual inspection for possible leaks in the water system and clogging of the condensate drain must be carried out a few days after commissioning. The refrigeration circuit of the heat pump does not require maintenance. Only use a damp cloth with a little soap solution to clean the domestic hot water heat pump. The installation (water and electical work) and commissioning, as well as the maintenance of this equipment, must only be caried out by an authorised qualified contractor in accordance with these instructions. NOTE Ensure water does not come into contact with the operator controls. Unplug the mains plug and switch off the power supply before beginning any cleaning work. Installation position of the external temperature sensor (device cover removed in illustration) 7.1 Water circuit / condensate drain The water circuit check is limited to filters that may have been installed on site and possible leakages. Dirty water filters should be cleaned and, if necessary, replaced. The seal valve in the end of the condensate hose must only be checked for contamination, and cleaned if necessary. 7.2 Air circuit supply Maintenance work is limited to cleaning the evaporator on a regular basis and as required. NOTE Risk of injury caused by sharp-edged fins. Fins must not be deformed or damaged! If air filters are used, they should be regularly checked for contamination and be cleaned and replaced if required. NOTE The PTR Valve must be discharged every six months to check for correct operation FD 9501 EN-7

9 7.3 Corrosion protection anode The corrosion protection anode installed in the domestic hot water cylinder should be electrically checked on a regular basis (at least every two years after commissioning) and be replaced as necessary. Electrical checking is carried out by means of a suitable ammeter, without draining the cylinder. Procedure: 1) Unplug the PE cable from the protection anode tab. 2) Connect the ammeter (0 to 50 ma) between the PE cable and the tab. 3) Evaluation of wear on the protection anode: Measured value > 1 ma protection anode is in working order. Measured value < 1 ma protection anode must be tested and/or replaced. If electrical testing does not provide any clear results, a visual inspection of the protection anode by a technician is recommended. Should replacement of the protection anode [by a technician] be necessary, the cylinder must be drained via the drainage valve provided (to be fitted during installation - see Appendix). Malfunctioning protection anodes reduce the service life of the device! (Electrically insulated magnesium anode with selenium complying with DIN 4753 part 6) 8 Faults / troubleshooting (for the user) Work on the domestic hot water heat pump is to be performed by qualified personnel only! Observe accident prevention regulations! The heat pump will not operate! Check the following: Voltage is applied to the device the intake air or ambient temperature is 0 C The heat pump has not been switched off by the temperature controller the hot water temperature has reached (or exceeds) 60 C Condensate cannot drain properly (there is water under the device) Check the following: The seal valve in the end of the condensate hose is contaminated or clogged, and clean if necessary; the valve can be easily removed and replaced. The air supply / air outlet is significantly reduced. If the above suggestions cannot help you eliminate these faults, please contact your technician or after-sales service partner. 9 Decommissioning Tasks to be carried out: Disconnect the domestic hot water heat pump from the power supply. Completely shut off the water circuit (domestic hot water, cold water and circulation pipe) and drain the domestic hot water cylinder through the drain valve. 10 Environmental requirements During maintenance or decommissioning of the domestic hot water heat pump, all environmental requirements regarding recovery, recycling and disposal of materials and components must be observed in compliance with DIN EN378. EN FD

10 11 Device information 1 Type and order code HPWH 300 HPWH 300HE 2 Design 2.1 Defrosting yes yes 2.2 Nominal cylinder volume litre Transfer area of the internal heat exchanger m Sensor pipe ø internal for external sensors mm Installation location Outside Outside 2.6 Cylinder material Enamelled steel complying with DIN 4753 Enamelled steel complying with DIN Cylinder insulation PU with sheet metal covering PU with sheet metal covering 2.8 Nominal cylinder pressure kpa (bar) 700 (7) 700 (7) 3 Operating limits 3.1 Heat source operating limit 1 C 0 to 45 0 to Domestic hot water in heat pump operation C 60 ± 1.0 K 60 ± 1.0 K 4 Sound 4.1 Sound power level db(a) Dimension/weight and filling quantities 5.1 Dimensions height (max.) x cross-section (max.) mm 1680 x x Weight (empty) kg Refrigerant R 134a/ filling weight kg Electrical connection 6.1 Degree of protection IP 24 IP Connection voltage 1/N/PE~230 V, 50 Hz 1/N/PE~230 V, 50 Hz 6.3 Fuse max. A C16 C Heat pump power consumption cos A Supplementary electrical heating power consumption A Power consumption max. A Heat pump nominal power consumption at 60 C 2 W Supplementary electrical heating power consumption W Total power consumption max. W Hydraulic connection 7.1 Circulation pipe connection external thread R 3/4 R 3/4" 7.2 Domestic hot water outlet connection external thread R1 R1" 7.3 Cold water inlet connection external thread R1 R1" 7.4 Internal heat exchanger connection external thread - R1" 8 Performance values 8.1 Heat-up time from 15 C to 60 C 2 h Mean heat output at 45 C COP according to EN cycle XL Useful domestic hot water quantity Litres Stand-by energy consumption at 55 C / 24 h W At temperatures below 0 C ± 1 C, the heating element is automatically switched on and the heat pump module off. 2. Heating up of the nominal volume from 15 C to 60 C at an air intake temperature of 20 C and a relative humidity of 70 % 3. Heating up of the nominal volume from 15 C to 45 C at an air intake temperature of 20 C and a relative humidity of 70 % A H5 850 kpa PTR Valve must be fitted A PSL 50 Valve (500 kpa) must be fitted FD 9501 EN-9

11 EN FD

12 Appendix 1 Dimensioned drawing... A-II 2 Integration Diagram... A-III 2.1 Process circuit diagram... A-III 2.2 Legend... A-III 2.3 Hydraulic integration diagram... A-IV 2.4 Legend... A-IV 2.5 Heat Exchanger Integration Diagram for Thermal Solar Installation... A-V 3 Circuit Diagrams... A-VI 3.1 Load... A-VI 3.2 Control... A-VII 3.3 Legend... A-VIII Appendix FD 9501 A-I

13 1 Dimensioned drawing A-II FD

14 2 Integration Diagram 2.1 Process circuit diagram Appendix 2.2 Legend Compressor Evaporator Hot water cylinder with Liquifier High-pressure switch Check valve Air inlet temperature sensor (R1) Filter dryer Expansion valve Cylinder temperature sensor Heating element Safety temperature limiter for heating element Service valve Four-way valve Defrost end sensor R10 Additional heat exchanger only for HPWH 300HE FD 9501 A-III

15 2.3 Hydraulic integration diagram Appendix 2.4 Legend 1 Shutoff valve 2 Pressure reducing valve 3 Test valve 4 Return flow inhibitor 5 Pressure gauge connecting stubs 6 Drain valve 7 Safety temperature pressure valve (PTR valve) There must be no shut-off device between the cylinder and the safety valve (PTR valve). The bleeding line/drain line of the valve must not be blocked 8 Circulation pump 9 Outlet * No connections for second heat generator required (i.e. no heating water flow and no heating water return flow) for hot-water heat pumps without internal heat exchanger The PTR discharge pipe is to be installed in a continuously downward direction in a frost free environment. The discharge pipe shall not be blocked. A pressure reducing valve set at 500 kpa must be fitted to the cold water inlet. A-IV FD

16 2.5 Heat Exchanger Integration Diagram for Thermal Solar Installation Appendix FD 9501 A-V

17 3 Circuit Diagrams 3.1 Last / Load Appendix A-VI FD

18 3.2 Control Appendix FD 9501 A-VII

19 3.3 Legend A2 B5 C1 C2 C5 E1 External bridge block Thermostat E1 Condenser compressor Condenser fan Suppressor capacitor Electric heater F1 Control fuse (230 V / 4 A) F2 High-pressure switch F3 Thermal contact, compressor F17 Safety temperature limiter E1 H1 Electric heater indicator lamp J1 Digital inputs / outputs (U=230 V) J3 Analogue inputs (screw terminals) K1 K2 K4 M1 M2 N1 R1 R3 R10 S1 Compressor load relay Starting relay for M1 Load relay for E1 Compressor Ventilator Control PCB Air intake temperature sensor Cylinder temperature sensor Defrost end sensor Electric heating "ON/STANDBY" switch Appendix X1 X2 X4 Y Mains plug Terminal strip 230 V Fan terminal strip Four-way valve Wired by the customer A-VIII FD

20 Appendix FD 9501 A-IX

21 Glen Dimplex Australia Pty Ltd 1/21 Lionel Road Mount Waverley, VIC ph: fax: Subject to alterations and errors.

Installation and Operating Manual

Installation and Operating Manual Installation and Operating Manual Heat Pump for Cooling of Domestic Water with Airduct Connection KWP 300 45902.67.39 FD84 TABLE OF CONTENTS. Regulations / Safety Notices 3 2. Description 4 2. Refrigeration

More information

Installation and operating instructions. DK energy storage and DK energy buffer

Installation and operating instructions. DK energy storage and DK energy buffer Installation and operating instructions DK energy storage and DK energy buffer Edition: 08-2015 1 Preliminary note With this DK energy storage / DK energy buffer you purchased a DK quality product. The

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

CD30 / CD30E DEHUMIDIFIER (FULL PRODUCT RANGE) OWNER S MANUAL

CD30 / CD30E DEHUMIDIFIER (FULL PRODUCT RANGE) OWNER S MANUAL CD30 / CD30E DEHUMIDIFIER (FULL PRODUCT RANGE) OWNER S MANUAL www.eipl.co.uk Page 1 of 16 UNPACKING Carefully remove the CD30 dehumidifier unit from its transit box and visually check for signs of transit

More information

Technical data LA 60TUR+

Technical data LA 60TUR+ Technical data LA 6TUR+ Device information LA 6TUR+ Design - Heat source Outside air - Model Universal design reversible - Regulation - Thermal energy metering Integrated - Installation location Outdoors

More information

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions Electronically controlled instantaneous water heater MCX: 27300, 27400 and 27600 models Installation instructions These appliances deliver water not exceeding 50 ºC in accordance with AS3498. 1. Overview

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

MODEL: DC10RCDH / DC12RCDH

MODEL: DC10RCDH / DC12RCDH MODEL: DC10RCDH / DC12RCDH INSTRUCTION MANUAL PORTABLE AIR CONDITIONER IMPORTANT INFORMATION Carefully read this instruction manual before you install or use your portable air conditioner. Please retain

More information

Electronically controlled instantaneous water heater. DEX: C models. Instructions for the user

Electronically controlled instantaneous water heater. DEX: C models. Instructions for the user Electronically controlled instantaneous water heater DEX: 27930-50 C models Instructions for the user For 50 ºC models, the appliance delivers water not exceeding 50 ºC in accordance with AS3498. MADE

More information

Reverse Cycle Portable Air Conditioner with Dehumidifier

Reverse Cycle Portable Air Conditioner with Dehumidifier DC10RC / DC12RCBW / DC15RCBW Reverse Cycle Portable Air Conditioner with Dehumidifier INSTRUCTION MANUAL PLEASE READ THE INSTRUCTION MANUAL CAREFULLY BEFORE USING THE UNIT. www.dimplex.com.au CONTENTS

More information

USER MANUAL. Laboratory Refrigerator Range. Applicable models: LSR151 LSR288

USER MANUAL. Laboratory Refrigerator Range. Applicable models: LSR151 LSR288 USER MANUAL Laboratory Refrigerator Range Applicable models: LSR151 LSR288 1 Contents Before first use 3 Positioning of refrigerator 3 Transportation and moving of refrigerator 3 Energy saving tips 4 Important

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

Operating and installation instructions» WWK 300 AHP

Operating and installation instructions» WWK 300 AHP Operating and installation instructions DHW heat pumps» WWK 300 A» WWK 300 AP» WWK 300 AH» WWK 300 AHP Contents 1. Operating instructions for users and contractors 3 1.1 Operation and control 3 1.2 Device

More information

Owner s Manual. Installation Details Owner s Information. 80L to 400L Electric Storage Water Heaters

Owner s Manual. Installation Details Owner s Information. 80L to 400L Electric Storage Water Heaters Models: RIN80E24 RIN80E36 RIN125E24 RIN125E36 RIN160E24 RIN160E36 RIN250E36 RIN315E36 RIN400E36 Installation Details Owner s Information For advice, repairs and service, call: 1300 555 545 Carefully remove

More information

Technical data LA 9S-TU

Technical data LA 9S-TU Technical data LA 9S-TU Device information LA 9S-TU Design - Heat source Outside air - Model Universal design - Regulation - Thermal energy metering Integrated - Installation location Outdoors - Performance

More information

Owner s Manual. Installation Details Owner s Information Warranty. 25L and 50L Electric Storage Water Heater

Owner s Manual. Installation Details Owner s Information Warranty. 25L and 50L Electric Storage Water Heater Owner s Manual & Installation guide 25L and 50L Electric Storage Water Heater MODELS 25W124, 25W136, 25W124P, 50W124, 50W136, 50W124P Installation Details Owner s Information Warranty For advice, repairs

More information

USER MANUAL. Pharmacy Refrigerator Range. Applicable models: PSR353/PGR353 PSR273/PGR273 PSR151/PGR151

USER MANUAL. Pharmacy Refrigerator Range. Applicable models: PSR353/PGR353 PSR273/PGR273 PSR151/PGR151 USER MANUAL Pharmacy Refrigerator Range Applicable models: PSR353/PGR353 PSR273/PGR273 PSR151/PGR151 1 Contents Before first use 3 Positioning of refrigerator 3 Transportation and moving of refrigerator

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

Electronically controlled instantaneous water heater. MCX: 27300, and models. Instructions for the user

Electronically controlled instantaneous water heater. MCX: 27300, and models. Instructions for the user Electronically controlled instantaneous water heater MCX: 27300, 27400 and 27600 models Instructions for the user These appliances deliver water not exceeding 50 ºC in accordance with AS3498. 1. Overview

More information

Technical data LA 60TU

Technical data LA 60TU Technical data LA 6TU Device information LA 6TU Design - Heat source Outside air - Model Universal design - Regulation - Thermal energy metering Integrated - Installation location Outdoors - Performance

More information

Operating instructions

Operating instructions Operating instructions For the operator Operating instructions HOME SYSTEM GB, IE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Tel. +49 21 91 18 0 Fax +49 21 91 18 28 10 info@vaillant.de

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

Technical data LA 28TBS

Technical data LA 28TBS Technical data LA 28TBS Device information LA 28TBS Design - Heat source Outside air - Model Universal design - Regulation - Thermal energy metering Integrated - Installation location Outdoors - Performance

More information

GDDEM10 DEHUMIDIFIER

GDDEM10 DEHUMIDIFIER GDDEM10 DEHUMIDIFIER SOCIABLE REMARK When using this dehumidifier in the European countries, the following information must be followed: DISPOSAL: Do not dispose this product as unsorted municipal waste.

More information

95-Pint Dehumidifier with Built-in Pump USER GUIDE IVALDH95PWWP

95-Pint Dehumidifier with Built-in Pump USER GUIDE IVALDH95PWWP 95-Pint Dehumidifier with Built-in Pump USER GUIDE IVALDH95PWWP Thank you for purchasing the Ivation 95-Pint Dehumidifier with Built-in Pump. This User Guide is intended to provide you with guidelines

More information

TECHNICAL PROPERTIES OF THE APPLIANCE

TECHNICAL PROPERTIES OF THE APPLIANCE TGR 30-120 SM EN Dear buyer, thank you for purchasing our product. Prior to the installation and first use of the electric water heater, please read these instructions carefully. THIS APPLIANCE IS NOT

More information

Operating instructions

Operating instructions Operating instructions Capriz 2 24c 28c GB, IE Contents Contents 1 Safety... 3 1.1 Action-related warnings... 3 1.2 Intended use... 3 1.3 General safety information... 4 2 Notes on the documentation...

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

Instructions for installation

Instructions for installation Instructions for installation Read this notice carefully before installing, maintaining or repairing this appliance! The symbol indicates important information that you must take into account to avoid

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

Operating instructions

Operating instructions The energy you need Operating instructions Betacom 3 24c -A (H-GB) 30c -A (H-GB) GB, IE Contents Contents 1 Safety... 3 1.1 Action-related warnings... 3 1.2 Intended use... 3 1.3 General safety information...

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

PORTABLE AIR CONDITIONER (LOCAL)

PORTABLE AIR CONDITIONER (LOCAL) EN PORTABLE AIR CONDITIONER (LOCAL) OPERATING INSTRUCTIONS Read the instructions carefully before operating the appliance or carrying out maintenance work. Observe all the safety instructions; failure

More information

flexotherm exclusive Installation and maintenance instructions Installation and maintenance instructions For the competent person

flexotherm exclusive Installation and maintenance instructions Installation and maintenance instructions For the competent person Installation and maintenance instructions For the competent person Installation and maintenance instructions flexotherm exclusive VWF 57/4 230 V VWF 87/4 230 V VWF 117/4 230 V GB Publisher/manufacturer

More information

30-pint Dehumidifier User Guide

30-pint Dehumidifier User Guide 30-pint Dehumidifier User Guide IVADH30PW Thank you for purchasing the Ivation 30 Pint Dehumidifier. This User Guide is intended to provide you with guidelines to ensure that operation of this product

More information

SAFETY AND OPERATING MANUAL

SAFETY AND OPERATING MANUAL SAFETY AND OPERATING MANUAL HOT WATER ELECTRIC WATER BLASTERS Read Safety & Operating Instructions Before Commencing Operation THESE INSTRUCTIONS MUST BE READ AND ADHERED TO BEFORE OPERATING THIS MACHINE.

More information

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery. PRODUCT DATA COMPACT P - SERIES BY NILAN Domestic Passive heat recovery Active heat recovery Ventilation < 300 m 3 /h Comfort heating Comfort cooling Sanitary hot water production Heating THE VENTILATION

More information

Fundamental safety warnings

Fundamental safety warnings INTRODUCTION Read these instructions carefully before using the appliance. Failure to follow these instructions may result in injuries and equipment damage. The manufacturer is not liable for damages resulting

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

INSTALLATION INSTRUCTIONS OWNERS GUIDE & WARRANTY STATEMENT

INSTALLATION INSTRUCTIONS OWNERS GUIDE & WARRANTY STATEMENT 315050B APR 2018 INSTALLATION INSTRUCTIONS OWNERS GUIDE & WARRANTY STATEMENT RHEEM ELECTRIC DAIRY HOT WATER HEATER Congratulations for choosing a Rheem Water Heater It is important that you take a few

More information

Electronically controlled instantaneous water heater CEX 9. CEX9: C models. Instructions for the user

Electronically controlled instantaneous water heater CEX 9. CEX9: C models. Instructions for the user Electronically controlled instantaneous water heater CEX 9 CEX9: 27900-50 C models Instructions for the user For 50 ºC models, the appliance delivers water not exceeding 50 ºC in accordance with AS3498.

More information

SOME NOTIONS ON HUMIDITY

SOME NOTIONS ON HUMIDITY SOME NOTIONS ON HUMIDITY Air always contains a certain amount of water in the form of vapour. This determines the level of humidity in an atmosphere. The capacity of the air to hold water vapour increases

More information

VADA - Rain2Main Automatic Rainwater Controller

VADA - Rain2Main Automatic Rainwater Controller PRODUCT OVERVIEW / APPLICATION The Vada Rain2Main is designed to select between stored rainwater (when available) and mains supply water, and send this water to your toilet cistern, washing machine, garden

More information

PORTABLE AIR CONDITIONER (LOCAL)

PORTABLE AIR CONDITIONER (LOCAL) EN PORTABLE AIR CONDITIONER (LOCAL) OPERATING INSTRUCTIONS Read the instructions carefully before operating the appliance or carrying out maintenance work. Observe all the safety instructions; failure

More information

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS User Manual INDEX IMPORTANT SAFETY INSTRUCTIONS... 1 FEATURES... 2 SPECIFICATIONS...2 PRODUCT DESCRIPTION... 3 THE CONTROL PANEL... 4 UNIT SETUP... 5 TO OPERATE SAFELY... 5 OPERATING INSTRUCTIONS... 6-10

More information

Zen Boiling Tap Range

Zen Boiling Tap Range Product Instruction Manual Zen Boiling Tap Range Zen Solo, Zen Spa, Zen Life Tap Range v16.10/3 Version 3.2 Jan 2015 Overview The Zen Boiling Tap Range delivers elegant practical solutions for your domestic

More information

O Pro electric storage water heater

O Pro electric storage water heater O Pro electric storage water heater PREMIUM SERIES MAINS PRESSURE ELECTRIC STORAGE WATER HEATERS DOCUMENTATION FOR INSTALLATION AND OPERATION New Zealand INDOOR INSTALLATION ONLY MODEL 272014 MODEL 282029

More information

USER MANUAL. Danfoss Heat Pump DHP-R VUIFK102

USER MANUAL. Danfoss Heat Pump DHP-R VUIFK102 USER MANUAL Danfoss Heat Pump DHP-R VUIFK102 Table of contents 1 Important information........................................................... 4 1.1 Safety precautions...4 1.2 Protection...4 2 About

More information

User Instruction &)+ 4: CFH110QB

User Instruction &)+ 4: CFH110QB User Instruction &)+ 4: CFH110QB 10 Safety Information In the interest of your safety and to ensure the correct use, before installing and first using the appliance, read this user manual carefully, including

More information

CA-707. Manual. Read these instructions carefully before you start using the dehumidifier and keep the manual for later usage.

CA-707. Manual. Read these instructions carefully before you start using the dehumidifier and keep the manual for later usage. Dehumidifier 2in1: Dehumidifying & air purifying CA-707 Manual Read these instructions carefully before you start using the dehumidifier and keep the manual for later usage. Copyright : Clean Air Optima

More information

Owner s Manual. Installation Details Owner s Information Warranty. Electric Storage Water Heaters

Owner s Manual. Installation Details Owner s Information Warranty. Electric Storage Water Heaters Owner s Manual Electric Storage Water Heaters Standard Models: 80T118, 80T124, 80T136, 125T118, 125T136, 160T124, 160T136, 250T136, 315T136, 315T236, 315T248 400T136, 400T236 An H at the end of the model

More information

DIRTY WATER SUBMERSIBLE PUMP

DIRTY WATER SUBMERSIBLE PUMP WHAT S IN THE BOX DIRTY WATER SUBMERSIBLE PUMP 780W INSTRUCTION MANUAL SPECIFICATIONS Motor: 780W Max. Flow Rate: 15,700l/h Max. Head 8m Max. Immersion: 7m Min. Suction Depth 50mm Max Particle Size: Ø35mm

More information

For Models FF2310APS, FF2310APW, FF2310APB 55cm FREESTANDING FRIDGE FREEZER. Instruction Manual

For Models FF2310APS, FF2310APW, FF2310APB 55cm FREESTANDING FRIDGE FREEZER. Instruction Manual For Models FF2310APS, FF2310APW, FF2310APB 55cm FREESTANDING FRIDGE FREEZER Instruction Manual Please read these instructions carefully before use and retain for future reference. Before switching on your

More information

DIGITAL MODULATING BOILERS

DIGITAL MODULATING BOILERS DIGITAL MODULATING BOILERS FOR HEATING AND SANITARY HOT WATER CMX15 CMX18 CM15 CM18 INSTALLATI INSTRUCTIS AND USER GUIDE Please read these instructions before installing or using this appliance for the

More information

PORTABLE AIR CONDITIONER (LOCAL)

PORTABLE AIR CONDITIONER (LOCAL) EN PORTABLE AIR CONDITIONER (LOCAL) OPERATING INSTRUCTIONS Read the instructions carefully before operating the appliance or carrying out maintenance work. Observe all the safety instructions; failure

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

10L Dehumidifier. Model Number: LDH V AC 50/60Hz 290W

10L Dehumidifier. Model Number: LDH V AC 50/60Hz 290W 10L Dehumidifier Model Number: LDH1001 220-240V AC 50/60Hz 290W For Customer Services & Spare Parts please call 0345 209 7461 Opening times: Monday - Friday 8am 8pm & Saturday 9am 1pm Or visit us at www.productcare.co.uk

More information

Portable Air-conditioner

Portable Air-conditioner Use and Care Manual Portable Air-conditioner Thank you very much for selecting this new model of Portable Air Conditioner, please read this Use and Care Manual carefully before installing and using this

More information

Progress plus Instruction manual

Progress plus Instruction manual GB Progress plus Instruction manual Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 10 Please read this user s manual carefully to ensure proper use, maintenance and installation.

More information

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW TECHNICAL INSTRUCTIONS PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER to KW PHRT PHRT PHRT PHRT For terminal units and boiler overhaul applications Heating Cooling PHRT.00 kw -. kw PHRT.0 kw /.0 kw

More information

installation & operating instructions

installation & operating instructions installation & operating instructions RGE 410 RA/RM-2D 822706106 MO-M 0740 INTRODUCTION We are pleased that you have chosen this refrigerator and hope you will derive much satisfaction from using it.

More information

Bar Fridge USER MANUAL MB46W

Bar Fridge USER MANUAL MB46W Bar Fridge USER MANUAL MB46W CONTENTS Safety information... 2-3 Identifying parts of the fridge... 4 Transporting... 5 Installation... 5 Reversing the door... 6 Operating instructions... 7 Cleaning &

More information

RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www.eipl.co.uk Page 1 of 12 INTRODUCTION Designed for a wide range of applications, the RM85 is a rugged, industrial unit, which utilizes an energy-efficient

More information

Trotec PAC FT 2600 Portable air conditioner

Trotec PAC FT 2600 Portable air conditioner Trotec PAC FT 2600 Portable air conditioner The PAC FT 2600 portable room air conditioner comes with an infrared remote control and an air outlet hose with a flat nozzle.the unit s primary function is

More information

Instantaneous water heater - Operation and installation instructions

Instantaneous water heater - Operation and installation instructions DHC 6 XG / 8 XG English Instantaneous water heater - Operation and installation instructions This water heater must be installed (water and electrical installation), commissioned and serviced by approved

More information

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300 USER S MANUAL Heat Recovery Ventilator Vents Brig HRV 200 Vents Brig HRV 300 2 Brig HRV 200 (300) CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key... 4 Basic unit dimensions...

More information

GLASS DOOR BAR FRIDGE

GLASS DOOR BAR FRIDGE GLASS DOOR BAR FRIDGE GMF118D, GMF228D & GMF338D 338 Litre 228 Litre FEATURES Compressor refrigerator Low noise operation Adjustable thermostat 118 Litre Magnetic Door Seal Stainless Steel Finish Double

More information

User Manual. Chest Freezer ZFC26500WA

User Manual. Chest Freezer ZFC26500WA EN User Manual Chest Freezer ZFC26500WA Contents Safety information 2 Safety instructions 3 Operation 5 Before first use 5 Daily use 5 Hints and tips 6 Care and cleaning 7 Troubleshooting 8 Installation

More information

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or INTRODUCTION Thank you for choosing this De Longhi product. Please take a few minutes to read these instructions. This will prevent running any risks or damaging the appliance. Symbols used in these instructions

More information

Instructions manual DEHUMID HP50

Instructions manual DEHUMID HP50 Instructions manual DEHUMID HP50 Table of contents 1. Unpacking 3 2. Intended use 3 3. Disposal 3 4. Safety instructions 3 5. Functional principle 4 6. Automatic defrosting system 4 7. Set up and transportation

More information

LS Condensate Removal Pump INSTRUCTION MANUAL REVISION A

LS Condensate Removal Pump INSTRUCTION MANUAL REVISION A LS Condensate Removal Pump INSTRUCTION MANUAL 6-71-075-115 REVISION A CAUTION: Combustible liquids may not be pumped! The condensate pump may not be run dry, as this can destroy the bearings in a very

More information

INSTRUCTION MANUAL. Model Number : CF-300K, CHEST FREEZER BEFORE USE, PLEASE READ AND FOLLOW ALL SAFETY RULES AND OPERATING INSTRUCTIONS.

INSTRUCTION MANUAL. Model Number : CF-300K, CHEST FREEZER BEFORE USE, PLEASE READ AND FOLLOW ALL SAFETY RULES AND OPERATING INSTRUCTIONS. INSTRUCTION MANUAL Model Number : CF-300K, CHEST FREEZER BEFORE USE, PLEASE READ AND FOLLOW ALL SAFETY RULES AND OPERATING INSTRUCTIONS. 1 CF-300K Dear customers, Thank you for purchasing our product.

More information

COMPRESSOR TYPE DEHUMIDIFIER DÉSHUMIDIFICATEUR D AIR LUFTENTFEUCHTER LUCHTONTVOCHTIGER TD-C100

COMPRESSOR TYPE DEHUMIDIFIER DÉSHUMIDIFICATEUR D AIR LUFTENTFEUCHTER LUCHTONTVOCHTIGER TD-C100 COMPRESSOR TYPE DEHUMIDIFIER DÉSHUMIDIFICATEUR D AIR LUFTENTFEUCHTER LUCHTONTVOCHTIGER TD-C100 OPERATING MANUAL ENGLISH P. 1 MANUAL D UTILISATION FRANÇAIS P. 5 BEDIENUNGSANLEITUNG DEUTSCH P. 9 GEBRUIKSAANWIJZING

More information

INSTRUCTION MANUAL PORTABLE FRIDGE/FREEZER. Models: RVX-35 / RVX-45 / RVX-50 RVX-55 / RVX-65 / RVX-75

INSTRUCTION MANUAL PORTABLE FRIDGE/FREEZER. Models: RVX-35 / RVX-45 / RVX-50 RVX-55 / RVX-65 / RVX-75 INSTRUCTION MANUAL PORTABLE FRIDGE/FREEZER Models: RVX-35 / RVX-45 / RVX-50 RVX-55 / RVX-65 / RVX-75 PLEASE READ THIS INSTRUCTION MANUAL CAREFULLY BEFORE CONNECTING AND OPERATING THE APPLIANCE. SAVE IT

More information

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2 MARKING This product marked conforms to the essential

More information

IMPORTANT SAFETY INFORMATION:

IMPORTANT SAFETY INFORMATION: 08/53542/0 (AU/NZ) Issue 1 Owner s Manual Model BLF5051-AU/ PRISM 50" EN IMPORTANT SAFETY INFORMATION: Always read this manual first before attempting to install or use this fireplace. For your safety,

More information

Unvented Electric Water Heater 10/15 litre Undersink

Unvented Electric Water Heater 10/15 litre Undersink Unvented Electric Water Heater 10/15 litre Undersink Fitting Instructions and User Guide 1 CONTENTS SECTION PAGE 1.0 INTRODUCTION 2 2.0 TECHNICAL SPECIFICATION 3 3.0 INSTALLATION 4 4.0 COMMISSIONING 9

More information

Combi 2 E / 4 E CP plus (Australia) Operating instructions Page 2. To be kept in the vehicle!

Combi 2 E / 4 E CP plus (Australia) Operating instructions Page 2. To be kept in the vehicle! Combi 2 E / 4 E CP plus (Australia) Operating instructions Page 2 To be kept in the vehicle! Combi 2 E / 4 E CP plus (Australia) 4 5 1 2 6 10 13 15 16 12 8 10 14 6 1 Control panel (digital) 2 Room temperature

More information

Instruction Manual. Refrigerator. Model: HS-65L

Instruction Manual. Refrigerator. Model: HS-65L Instruction Manual Refrigerator Model: HS-65L General This refrigerator is widely used in places such as hotels,offices, student dormitories and houses. It is small size, lightweight, low electric consumption

More information

SCHWAN INSTALLATION GUIDE

SCHWAN INSTALLATION GUIDE SCHWAN INSTALLATION GUIDE For Schwan Versatap SC52E Instant Hot Cold Filtered Water FOR SERVICE OR ASSISTANCE CALL MERQUIP ON 0800 636 0 636. Schwan recommends that a qualified tradesperson installs your

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017 24 1 2 23 3 4 5 20 6 I 19 7 18 8 9 15 14 11 13 12 i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book i 24 OFF MAX E STATUS BURNER RESET MIN PRE MIN MAX HEAT PREHEAT

More information

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 HG 675 X 60 HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 1 2 1. : 93/68: 90/396: 2006/95/CE: 2004/108/CE: - 1935/2004:. 2002/95/CE: RoHS 2.,.,,,,...,. (,..)..,,.,. ( ),,, ;,,.,.....,.,,,,,,...,. (..),,.,..,.,,,,

More information

DD12E DEHUMIDIFIER USER'S MANUAL CONTENTS. VOLTAGE: V~50Hz

DD12E DEHUMIDIFIER USER'S MANUAL CONTENTS. VOLTAGE: V~50Hz DD12E DEHUMIDIFIER CONTENTS WARNING/CAUTION 1 DESCRIPTION OF COMPONENTS FUNCTION EXPLANATION 2 OPERATION INSTRUCTIONS 3 CONTINUOUS DRAINAGE 4 CAUTIONS 5 MAINTENANCE/EMERGENCY 6 SPECIFICATION LAST PAGE

More information

EH0533 Indoor Climate Control

EH0533 Indoor Climate Control EH0533 Indoor Climate Control 2.8 kw of cooling, 2.9 kw of heating Air Conditioning Efficient heating (air-source heat-pump) Cooling Remote control Suitable for low-wall installation No external unit required

More information

ECO85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

ECO85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL ECO85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www.eipl.co.uk Page 1 of 12 INTRODUCTION Designed for a wide range of applications, the ECO85 dehumidifier is a rugged, industrial unit which utilizes an energy-efficient

More information

EBAC MODEL PD120 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL PD120 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL PD120 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www.eipl.co.uk UNPACKING Carefully remove the PD120 dehumidifier unit from its transit box and visually check for signs of transit damage. If there

More information

air conditioner/dehumidifier 9000btu/hr

air conditioner/dehumidifier 9000btu/hr instructions for air conditioner/dehumidifier 9000btu/hr model no: SAC9001 Thank you for purchasing a Sealey product. Manufactured to a high standard, this product will, if used according to these instructions,

More information

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE:

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE: TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE: 560955 CE Directive 2006/95/CEE British Standard EN 60335-1 (C 73800) 1 CONTENTS Page 1) INTRODUCTION 1.1) Description 3 1.2) Dimensions & connections

More information

ACTIVA SERIES ROOF TOP Air Conditioners 017/040

ACTIVA SERIES ROOF TOP Air Conditioners 017/040 ACTIVA SERIES ROOF TOP Air Conditioners 017/040 Installation manual Ref.: N-40388_EN 0112 Index Index 1 Installation manual...1 1.1 Safety instructions...2 1.2 Icons used in this document...2 1.3 Instructions

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

Manual is for the following models: G-26 GCG-26 GCG-26-C31N* G-26-C31N* GCG-26-C231N* GCG-26-CA31N* *G,I,M,7,J plug. Instruction Manual.

Manual is for the following models: G-26 GCG-26 GCG-26-C31N* G-26-C31N* GCG-26-C231N* GCG-26-CA31N* *G,I,M,7,J plug. Instruction Manual. G-Series Cooler G-26c/GCG-26c UPRIGHT COOLER Manual is for the following models: G-26 GCG-26 GCG-26-C31N* G-26-C31N* GCG-26-C231N* GCG-26-CA31N* *G,I,M,7,J plug Instruction Manual Manual is for the following

More information

INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15

INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15 INSTALLATION INSTRUCTIONS POINT OF USE WATER HEATERS EPU - US10 EPU - US15 01 CONTENTS Special information 2 General information 3 Safety 5 Appliance description, cleaning, care & maintenance 7 Appliance

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Table of Content

Table of Content Table of Content 43402001 1. User manual... 2 2. Legal regulations... 2 3. Safety instructions... 3 4. Technical information... 4 5. Functional principle... 5 6. Technical data... 6 7. Mounting... 7 8.

More information

DIRTY WATER SUBMERSIBLE PUMP KIT

DIRTY WATER SUBMERSIBLE PUMP KIT WHAT S IN THE BOX DIRTY WATER SUBMERSIBLE PUMP KIT 1000W INSTRUCTION MANUAL SPECIFICATIONS Motor: 1000W Max. Flow Rate: 18,000l/h Max. Head 9m Max. Immersion: 7m Min. Suction Depth 50mm Max Particle Size:

More information

Instructions for installation and use English. More documents on: H B /09

Instructions for installation and use English. More documents on:  H B /09 TM Instructions for installation and use English EN More documents on: www.zodiac-poolcare.com H0538700.B - 2015/09 Read this manual carefully before installing, maintaining or repairing this appliance!

More information

PORTABLE AIR CONDITIONER

PORTABLE AIR CONDITIONER PORTABLE AIR CONDITIONER Model: PEL00460 1 CONTENTS Page No. Details 2 Important Safety Information 3 Product Overview 3 Positioning & Installation 4 Installation Errors 4 Control Panel 5 Screen IMPORTANT

More information