RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

Size: px
Start display at page:

Download "RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana"

Transcription

1 ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum shall hereby be and become a part of the Contract Documents the same as if originally bound thereto. The following clarifications, amendments, additions, revisions, changes, and modifications change the original Contract Documents only in the amount and to the extent hereinafter specified in this Addendum. NOTE: Bidders are responsible for becoming familiar with every item of this Addendum. ITEM NO. 1: PROJECT MANUAL; NOTICE TO BIDDERS A. Change the bid due date to Friday, July 29. The place and time will remain unchanged. ITEM NO. 2: PROJECT MANUAL; SECTION BUILDING WRAP; B. PRODUCTS A. Add new item 2. As follows: 2. Moisture Barrier: Shall be either an air barrier of coated, non-woven, nonperforated, spunbonded polyolefin fabric suitable for adhering to concrete or a silylterminated polyether polymer liquid for fluid application to concrete. a. Products: 1) Tyvek Fluid Applied WB : Dupont 2) Typar MetroWrap : Fiberweb with manufacturer s recommended adhesive. ITEM NO. 3: PROJECT MANUAL; SECTION 0831 ACCESS PANELS; B. PRODUCTS; 3. ACCESS PANELS A. Add sub-item b. as follows: b. Suspended Acoustical Tile Ceiling Hatch: Shall be Model KSTE/CAD Ceiling Access Hatch, 24"x48", as manufactured by Karp Associates, Melville, NY or Architect approved equal. Locate in Files 223 centered below attic access panel as close as possible.

2 ADDENDUM NO July 1, 2016 ITEM NO. 4: PROJECT MANUAL; SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS A. Add Domestic Booster Pump BP-1" to the points list. Refer to the attached, revised points list in the replacement Section ITEM NO. 5: DRAWING SHEET M2.0 A. Revise relief air ductwork as shown on attached Supplemental Information Drawing 817M B. The floor/ceiling assembly above Mechanical 120 is UL Assembly #L528. Ducts penetrating this assembly shall have fire dampers listed for use with this assembly. Fore dampers shall be serviceable from the mechanical room. C. The attic assembly above the duct chase in UL Assembly #P522. Ducts penetrating this assembly shall have fire dampers listed for use with this assembly. Fire dampers shall be accessible for service. ITEM NO. 6: DRAWING SHEET M3.1 A. Revise relief air ductwork as shown on attached Supplemental Information Drawing 817M ITEM NO. 7: DRAWING SHEET M4.1 A. Revise Roof Cap Schedule as shown on attached Supplemental Information Drawing 817M B. All roof mounted mechanical equipment shall be painted dark bronze. Custom color to be approved by Architect. C. Louver L-1 shall be silver with clear anodized finish. ITEM NO. 8: DRAWING SHEET CE1.0; ELECTRICAL SITE PLAN A. Refer to attached Supplemental Information Drawing 817CE for raceway associated with technology. ITEM NO. 9: DRAWING SHEET E1.0 A. Lower Level Electrical Power Plan: 1. Refer to attached Supplemental Information Drawing 817E a for locations of added security devices. 2. Refer to attached Supplemental Information Drawings 817E a and 817E b for electrical revisions associated with the lower level.

3 ADDENDUM NO July 1, 2016 B. Upper Level Electrical Power Plan: 1. Refer to attached Supplemental Information Drawing 817E b for locations of added security devices. 2. Refer to attached Supplemental Information Drawing 817E c for electrical revisions associated with the upper level. ITEM NO. 10: DRAWING SHEET E5.1 A. Refer to attached Supplemental Information Drawing 817E a for security riser. ITEM NO. 11: DRAWING SHEET E5.2 A. Refer to attached Supplemental Information Drawing 817E for revisions to panel 1L1. END OF ADDENDUM NO. 2 All bidders must acknowledge receipt of this Addendum in their bid.

4

5

6

7

8

9

10

11

12

13

14

15 SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification sections. B. Division 23 Section "Common Work Results for HVAC". C. Division 23 Section "Facility Management Systems". 1.2 DESCRIPTION OF WORK A. Sequence of operation is hereby defined as the manner and method by which controls function. Requirements for each type of control system operation are specified in this section. B. Operating equipment, devices, and system components required for control systems are specified in Division 23 Section "Facility Management Systems". C. HVAC Systems shall be controlled with a Direct Digital Control (DDC) system, sometimes referred to as a Facility Management System (FMS), according to the point list contained at the end of this section. Additional hardware, input/output points or software programming not specifically identified in the point list but which are required to meet the following sequences of operation shall be provided. D. All electrical Controllers, Relays, Transducers, etc., required for stand-alone control shall be housed in a NEMA 1 enclosure with a lockable door. 1.3 DEFINITIONS A. FMS: Facility management system B. DAT: Discharge air temperature. C. VSD: Variable speed drive.

16 D. DX: Direct expansion. PART 2 - PRODUCTS (Not Applicable) PART 3 - EXECUTION 3.1 ALARMS A. Generate an alarm at the computer graphics when any space temperature is <50 def F for 15 minutes (adjustable) and an immediate alarm when any space temperature is <40 deg F (adjustable). B. Coordinate with the owner to identify alarms as "general" or " critical". General alarms will only be displayed at the computer graphics. Critical alarms will be displayed in the computer graphics program and dialed-out, ed, or text messaged to pre-programmed telephone numbers and address via the internet. 3.2 MONITORING SEQUENCES A. Monitor space temperature of IT Server Room and generate an alarm message at the computer graphics if space temperature falls below 50 deg F or rises above 76 deg F during occupied mode. Generate a critical alarm if space temperature falls below 40 deg F or rises above 80 deg F during occupied or unoccupied mode. B. Monitor status of electrical generator transfer switch. On a loss of utility supplied power, generate an alarm at the computer graphics stating LOSS OF UTILITY POWER. The following equipment shall be disabled by the FMS until utility power is restored: Chiller-X, P-X, AHU-X. 3.3 HVAC ZONE CONTROL SEQUENCES A. Provide software time clock and set-up schedule to place each HVAC system into occupied or unoccupied mode. Provide an override push button on each space temperature sensor to place the respective zone air handler into the occupied mode for a two hour period (adjustable) when button is pushed. When the button is pushed again prior to the override time expiring, the zone air handler will revert to the scheduled operating mode.

17 AIR HANDLING UNITS CONTROL SEQUENCES A. Safety Controls for Air Handling Units: 1. Provide a low-limit controller to prevent unit discharge air from falling below 45 deg F (adjustable). Sensor shall be located at the discharge of the unit. 2. Provide an electric low limit thermostat with a 20 foot element serpentined across the face of the leaving air side of the heating coil which will stop the supply fan, close the outside air damper (and relief dampers if applicable) and position heating control valve for full coil water flow. 3. Provide strap-on aquastat on the leaving water side of the hot water coil to, close the outside air damper (and relief dampers if applicable) and position control valve for full coil water flow if leaving water temperature drops below 40 deg F (adjustable). 4. Provide a high-limit controller to prevent unit discharge air from rising above 125 deg F (adjustable). Sensor shall be located at the discharge of the unit. B. AHU-1 & 2 (Variable Air Volume Supply Fan): 1. Occupied Mode: Supply fan shall operate continuously. Variable speed drive (VSD) shall modulate supply fan to maintain the variable air volume (VAV) terminal unit with the greatest call for cooling at least 85% open. Increase duct static pressure at a rate of 0.25 every 10 minutes (adjustable) until any VAV terminal unit exceeding 95% open, closes down to 85% open. Duct static pressure shall be determined by pressure sensors located 2/3 down the longest duct run or as shown on the drawings. A high limit discharge pressure sensor, located at the fan discharge, shall prevent the supply fan from generating a discharge pressure greater than 6.5 w.c. (adjustable). The outside air damper shall be opened to provide minimum outside air. Minimum outside air volume shall be maintained by modulating outside air damper and return air damper as required to maintain a constant differential pressure between the outside air duct (pickup point located immediately upstream of the outside air damper) and outdoors. If outside air dry bulb temperature is less than space and cooling is required, modulate outside air damper open to provide outside air economizer cooling. A mixed air temperature controller shall maintain a minimum DAT of 55 deg F.

18 Modulate the hot water coil control valve and stages of DX cooling as required to maintain DAT set point. Reset DAT to maximum possible temperature to satisfy zone with the greatest call for cooling. Minimum DAT shall be 42 deg F (adjustable). If any space or return duct humidistat is not satisfied, reset the DAT to minimum set point until all relative humidity s are 2% below set point. DAT shall be set to minimum level and zone VAV terminal unit shall provide reheat as required to maintain space temperature set point. 2. Unoccupied Mode: Close outside air damper, cycle unit supply fan with full hot water flow to maintain reduced set point temperature. If space humidity exceeds set point, the unit shall be placed into occupied mode until space humidity is 5% RH below set point. 3. Morning Warm-Up: Dependent on space and ambient conditions, the FMS shall determine optimum start time to return zones temperature to their occupied set points 5 to 10 minutes prior to occupied schedule. The outside air damper shall close and the return air damper shall open to its maximum position, hot water coil control valve shall modulate to maintain a maximum 125 deg F (adjustable) discharge air temperature, VAV terminals primary air valve shall open to full flow. As a zone reaches occupied heating set point, VAV terminal primary air valve and reheat valve shall modulate to prevent zone over heating. This cycle shall continue until all zones have reached their occupied heating set point temperature. 4. Morning Cool-Down: Dependent on space and ambient conditions, the FMS shall determine optimum start time to return zones temperature to their occupied cooling set points 5 to 10 minutes prior to occupied schedule. The outside air damper shall close and the return damper shall open to its maximum position with stages of DX cooling to maintain a discharge air temperature of 50 deg F, VAV terminal units shall operate as under normal occupied mode. This cycle shall continue until all zones have reached their occupied cooling set point temperature. 3.5 EXHAUST FAN CONTROL SEQUENCE A. EF-4: Continuous operation. B. EF-1 & 2: Operate during occupied cycle of AHU-1, off otherwise. C. EF-3: Operate during occupied cycle of AHU-2, off otherwise. D. EF-5: Operate with a piloted wall switch.

19 SINGLE DUCT SHUT OFF VAV TERMINAL UNIT WITH HOT WATER REHEAT A. Occupied Mode: Modulate open primary air valve with a rise in space temperature. With a fall in space temperature, modulate primary air valve towards the minimum setting. With a continued fall in space temperature below the heating set point, modulate open the hot water coil control valve, when valve is 100% open, modulate air valve increasing air flow to maintain space heating set point. If hot water is not available, close primary air valve 100% with a fall in space temperature below heating set point. If the associated occupancy sensor indicates no occupants, the VAV box is to revert to unoccupied temperature setpoints. B. Unoccupied Mode: Open primary air valve, close hot water coil control valve. If the associated occupancy sensor indicates occupants, the VAV box and associated air handler are to revert to occupied mode. C. Refer to sheet E2.0 for occupancy sensors indicated to control associated VAV boxes. D. Morning Warm-Up/Cool-Down & Night Purge: Refer to respective HVAC unit sequence of operation. During morning warm-up, provide maximum primary air with full hot water coil flow until space occupied heating set point is reached at which time reset primary air valve to heating air flow and modulate control valve to maintain set point. 3.7 PUMP CONTROL SEQUENCE A. Boiler Pump (Boiler Primary Hot Water Loop): Cycle with their respective boilers. On a failure to establish flow within 15 seconds after a call to operate, generate an alarm message reading PRIMARY HOT WATER PUMP FAILURE to be automatically displayed in computer graphics and dial out, text messaged, and to pre-programmed addresses and/or numbers. Pump shall continue to operate for a period of 30 seconds following shut down of associated boiler burner. B. P-1 & P-2 (Building Secondary Hot Water Distribution Loop): Variable volume pumping. Energize lead variable volume pump on a call for hot water. Modulate lead pump with a 4-20 ma output to the variable speed drive (VSD) to maintain a 10 PSIG (adjustable) differential pressure across the supply and return mains at location(s) shown. With a failure of the lead pump to establish flow within 15 seconds after a call to operate, start the lag pump and generate an alarm message reading "SECONDARY BUILDING HOT WATER DISTRIBUTION LOOP LEAD PUMP FAILURE" to be automatically displayed in computer graphics and dial out, text messaged, and to pre-programmed addresses and/or numbers.

20 C. HWRP-1 (Domestic Hot Water Recirculation Pump): Pump is to be controlled by an aquastat and enabled during occupied mode by the FMS. 3.8 BOILER AND HEATING WATER CONTROL SEQUENCE A. On a call for hot water the FMS shall energize the hot water distribution pump(s), and packaged controls shall be enabled to maintain the hot water loop temperature. The packaged controls shall activate and stage boilers and their associated pumps as required to maintain the loop supply temperature. The boiler controller shall sequence the boilers and modulate output such that total system efficiency is maximized. The packaged controller shall reset the supply water temperature to satisfy the zone with the greatest heating demand. The packaged controller shall have a set of dry contacts to notify the FMS of any alarm state within the boiler plant or controller.

21 Control Relay Solenoid Pneumatic Transducer Electrical Transducer 4-20 ma or 0-10 VDC Pressure Switch Flow Switch Contact Closure Auxiliary Contact KW Meter Contact Temperature Relative Humidity Set Point Adjustment Psig, Psia, Psid, IN H20 Flow Electrical Current Flow Position Trending Equipment Status Maintenance High Limit Low Limit (Temperature) Run Time Scheduled On/Off Optimum Start/Stop Demand Limiting Totalization Day/Night Setback Economizer Ventilation/recirculation Direct Digital Temp Control Enthalpy Heating or (Global) Cooling HARDWARE SOFTWARE Reset Boiler Optimization OA Reset Chiller Optimization Chilled Water Reset VAV Control Variable Speed Pumping Ice Storage Control Lead/Lag Control Lighting Control Color Graphics Item Outside Air X X X X AHU-1, 2 (VAV) X SUPPLY FAN X X X X X HW VALVES X X X X VAV BOXES X X X SPACE SERVED X X X X HW VALVE X X X X Customer: INPUT/OUTPUT SUMMARY TABLE Location: OUTPUT (O) INPUT (T, D, V, C) ALARMS DGT ANALG DIGITAL ANALOG DGT ANALG EMCS FUNCTIONS Point Description MIXED & SUPPLY AIR X X RETURN AIR X X OA & RA DAMPERS X X X X X SUPPLY DUCT X X X

22 PRIMARY AIR DAMPER X X X X DISCHARGE AIR X X EXHAUST FAN- 1, 2, 3 X X X X I.T. SERVER ROOM X X X Control Relay Solenoid Pneumatic Transducer Electrical Transducer 4-20 ma or 0-10 VDC Pressure Switch Flow Switch Contact Closure Auxiliary Contact KW Meter Contact Temperature Relative Humidity Set Point Adjustment Psig, Psia, Psid, IN H20 Flow Electrical Current Flow Position Trending Equipment Status Maintenance High Limit Low Limit (Temperature) Run Time Scheduled On/Off Optimum Start/Stop Demand Limiting Totalization Day/Night Setback Economizer Ventilation/recirculation Direct Digital Temp Control Enthalpy Heating or (Global) Cooling HARDWARE SOFTWARE P-1, 2 X X X X HWRP-1 X X X Reset Boiler Optimization OA Reset Chiller Optimization Chilled Water Reset VAV Control Variable Speed Pumping Ice Storage Control Lead/Lag Control Lighting Control Color Graphics Item Customer: INPUT/OUTPUT SUMMARY TABLE Location: OUTPUT (O) INPUT (T, D, V, C) ALARMS DGT ANALG DIGITAL ANALOG DGT ANALG EMCS FUNCTIONS Point Description

23 BOILER B-1, 2 X X X X X X X HWS X X X HWR X X FIRE ALARM PANEL X X DIFFERENTIAL PRESSURE X X X EXTERIOR LIGHTING X (2 CONTACTORS) Domestic Booster X X X Pump BP-1 END OF SECTION 23093

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT February 29, 2012 RFP NO: 17 PROJECT: Josephine County Justice Center HVAC Upgrades BID CLOSING DATE: NO CHANGE: March 8, 2012 / NOT LATER

More information

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

November 11, City of Sparks 215 S. 21 st St. Sparks, NV November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of

More information

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of

More information

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...

More information

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,

More information

PURCHASING DEPARTMENT LOUISVILLE, KENTUCKY

PURCHASING DEPARTMENT LOUISVILLE, KENTUCKY PURCHASING DEPARTMENT LOUISVILLE, KENTUCKY Date: June 14, 2017 Invitation No: IB-096-17 Title: Student Activity Center Renovation and Addition, Bid Package V Addendum No. Three (3) The following shall

More information

Power and Energy Management Solutions

Power and Energy Management Solutions Selection Guide Power and Energy Management Solutions Heating, Ventilating and Air Conditioning (Bulletin 1414) Selection Guide 2 HVAC Selection Guide Instrumentation Selection Checklist Use the following

More information

AHU Air Handling Unit Fundamentals. j.ilangumaran

AHU Air Handling Unit Fundamentals. j.ilangumaran AHU Air Handling Unit Fundamentals j.ilangumaran Objectives Review primary components of an AHU Understand the basic progression and advantages of advanced AHU control Understand the basic control sequences

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas

More information

4. OVERVIEW OF MECHANICAL SYSTEM

4. OVERVIEW OF MECHANICAL SYSTEM 4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in

More information

HEAT TROL ELITE SERIES HWE-Single Stage, HWE-MOV, HWE-Mulit Stage Hot Water Reset Control for Light Commercial and Residential Applications Provides q

HEAT TROL ELITE SERIES HWE-Single Stage, HWE-MOV, HWE-Mulit Stage Hot Water Reset Control for Light Commercial and Residential Applications Provides q SIGNAL REPEATER RC2100 WI-CON Wireless Heating Control for Steam and Hot Water Boilers No sensor wiring required Intelligent sensing algorithm saves energy Low limit control and alarm alert operator of

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL SECTION 15100 PART 1 GENERAL THIS IS A DESIGN GUIDE NOT A SPECIFICATION Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL HVAC SYSTEMS APPLICATIONS 1.1 SCOPE: The intent of this

More information

Florida Department of Transportation

Florida Department of Transportation Page 1 of 7 RICK SCOTT GOVERNOR Florida Department of Transportation 1109 S. Marion Avenue Lake City, Florida 32025 ANANTH PRASAD SECRETARY September 27, 2011 To: Proposal Holders Addendum No: 1, E2Q23,

More information

1. Please see the attached document as it applies to North Central high School Classroom Addition Project. End of Addendum No. 15

1. Please see the attached document as it applies to North Central high School Classroom Addition Project. End of Addendum No. 15 Purchasing Department 8 East Garland Avenue Spokane, WA 9907-889 phone (09) -77 fax (09) -78 www.spokaneschools.org September, 0 GC/CM for North Central High School Classroom Addition ADDENDUM NO.. Please

More information

DIVISION 15 MECHANICAL

DIVISION 15 MECHANICAL DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

Feature Summary. I. System

Feature Summary. I. System I. System A. Supports up to 60 VAV HVAC Units 1. Each HVAC Unit Can Support up to 59 VAV Boxes 2. Constant Volume Units Can Be Integrated With VAV Units 3. System Can Support Over 3000 Controllers B. Fill-in

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Technical Assignment 3 11/15/04. Executive Summary

Technical Assignment 3 11/15/04. Executive Summary Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria

More information

Civil Engineering Building

Civil Engineering Building Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Technical Report #3 Mechanical Systems Existing Conditions Evaluation Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front

More information

SECTION ENERGY MANAGEMENT SYSTEM (EMS)

SECTION ENERGY MANAGEMENT SYSTEM (EMS) SECTION 13810 ENERGY MANAGEMENT SYSTEM (EMS) PART 1 GENERAL 1.01 SUMMARY A. Section Includes: The energy management system (EMS) including the following major subsystems: HVAC temperature controls, HVAC

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information Charles M. LeMaistre PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and

More information

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort

More information

Selected Laboratory Energy Efficiency Measures

Selected Laboratory Energy Efficiency Measures Selected Laboratory Energy Efficiency Measures These are some of the most effective energy efficiency measures for laboratories 1. Reduce (optimize) air changes per hour in lab space 2. Design to the proper

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

Building Automation System

Building Automation System University of New Hampshire University of New Hampshire Scholars' Repository Division 25 Integrated Automation Chapter 5 Technical Construction and Renovation Standards 8-1-2014 250000 - Building Automation

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC PART 1 GENERAL 1.01 RELATED REQUIREMENTS SECTION 23 0913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC A. Section 26 2717 - Equipment Wiring: Electrical characteristics and wiring connections. 1.02 ADMINISTRATIVE

More information

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals control sequences Table 47: QST / EST Analog Electronic Control Strategies Control Package Number QST EST FS-A-5000 FSE-A-5000 FS-A-5001 FSE-A-5001 FS-A-5002 FSE-A-5002 FS-A-5003 FSE-A-5003 FS-A-5004 FSE-A-5004

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

HVAC Mandatory Provisions Part II, Page 1

HVAC Mandatory Provisions Part II, Page 1 HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57295/Page 1/July 21, 2017 HVAC SYSTEMS NARRATIVE REPORT The following is the HVAC system narrative, which defines the scope of work and capacities of the HVAC system as well as the Basis of Design.

More information

OSU Alumni Center Phase I Implementation Review. Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon

OSU Alumni Center Phase I Implementation Review. Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon OSU Alumni Center Phase I Implementation Review Prepared for Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon 97331 October 31, 2011 Job No. 02.11.00113 Introduction: Glumac was engaged by

More information

DACC - NMDA BUILDINGS

DACC - NMDA BUILDINGS A PROJECT FOR: LAS CRUCES, NEW MEXICO PROJECT LOCATION LOCATION MAP INDEX OF DRAWINGS: CV001 - COVER SHEET M101 - OVERALL CAMPUS STEAM UTILITY PLAN M102 - DACC DAMA 341 PLAN M103 - DACC LRC & CLASSROOM

More information

OPTIMUM APPLIED SYSTEMS,

OPTIMUM APPLIED SYSTEMS, OPTIMUM APPLIED SYSTEMS, INC. HEAT COMPUTER 3500 DSL TECHNICAL SPECIFICATIONS HC 3500 GENERAL SYSTEM DESCRIPTION The Heat Computer is a computerized building heating control system that utilizes sensors

More information

DIGI-VAV APPLICATIONS

DIGI-VAV APPLICATIONS DIGI-VAV DIGI-VAV APPLICATIONS Digi-VAV: An optimization kit for Variable Air Volume Air Handling Units (VAV AHU) that ensures individual zone indoor air quality (IAQ), and minimizes system energy consumption.

More information

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3 Existing System Evaluation Executive Summary The MBNA Career Services Center is a 44,000 square foot, 4-story office type building at Penn State University, University Park Campus. The building is located

More information

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 2 OCCUPIED MODE: When the program control source calls for

More information

Summary Comparison of Simulation Program Features

Summary Comparison of Simulation Program Features Summary Comparison of Simulation Program Features FEATURE DOE2.2 equest TRACE 700 HAP Public/Proprietary Public Domain Proprietary Proprietary Proprietary Simulation Method 8760 hours 8760 hours 8760 hours

More information

iworx Air Side Application Wiring Guide

iworx Air Side Application Wiring Guide iworx Side Application Wiring uide Pages ASM2 Sequence of peration & ypical Wiring 1 ALM2 Sequence of peration & ypical Wiring 2 U2 Sequence of peration, Flow iagram & ypical Wiring 3 - U3 Sequence of

More information

COMcheck Software Version Review Mechanical Compliance Certificate

COMcheck Software Version Review Mechanical Compliance Certificate COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project

More information

Computing Services Center

Computing Services Center Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Application of Direct Digital Temperature Control Systems for Maximum System Efficiency on VAV Systems

Application of Direct Digital Temperature Control Systems for Maximum System Efficiency on VAV Systems Application of Direct Digital Temperature Control Systems for Maximum System Efficiency on VAV Systems Frank W. Mayhew, EC/TC Consulting The acceptance of direct digital temperature control technology

More information

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

SECTION INTEGRATED AUTOMATION COMMISSIONING

SECTION INTEGRATED AUTOMATION COMMISSIONING SECTION 25 08 00 INTEGRATED AUTOMATION COMMISSIONING PART 1. GENERAL 1.01 SECTION INCLUDES: A. BAS and equipment testing and start-up B. Validation of proper and thorough installation of BAS and equipment

More information

2006 Washington State Nonresidential Energy Code Compliance Form Washington State Nonresidential Energy Code Compliance Forms Revised July 2007

2006 Washington State Nonresidential Energy Code Compliance Form Washington State Nonresidential Energy Code Compliance Forms Revised July 2007 Mechanical Summary 2006 Washington State nresidential Energy Code Compliance Form MECH-SUM 2006 Washington State nresidential Energy Code Compliance Forms Revised July 2007 Project Info Project Address

More information

Hydronic & HVAC Control Systems

Hydronic & HVAC Control Systems tekmar 218 Full Line Catalog Hydronic & HVAC Control Systems HVAC Multi-Staging Alternative Energy Zoning Snow Melting Setpoint tekmarcontrols.com tekmarcontrols.com Better Design, Better Control, Better

More information

FUNCTIONAL DESIGN SPECIFICATION

FUNCTIONAL DESIGN SPECIFICATION Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised

More information

Better Design, Better Control, Better Systems.

Better Design, Better Control, Better Systems. Product Catalog Better Design, Better Control, Better Systems. At tekmar Control Systems, we believe the indoor comfort of a building depends on the performance of its heating, ventilating & air conditioning

More information

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks Improving Performance with a Building Tune-Up Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks How much is too much? Most buildings can cut total energy use by 5-30% while

More information

Electric Coils. Blower Coils. Product Information

Electric Coils. Blower Coils. Product Information Product Information General Information Electric heat coils are an available accessory for use with Price blower coil units. The electric heating coils have been specific ally designed to suit Price blower

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

BAS Point Trend Data Guidance

BAS Point Trend Data Guidance BAS Point Trend Data Guidance Rev. 3, January 2018 Introduction The Building Automation System (BAS also, referred to as a DDC system, or a Direct Digital Control system) at your building has been set-up

More information

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012) Madeira City Schools Madeira, Ohio HVAC Assessment December 2011 (Revised February 2012) Prepared by: CMTA Engineering Consultants, Inc. 10411 Meeting Street Prospect, KY 40059 www.cmtaegrs.com (502) 326-3085

More information

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated

More information

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements ADDENDUM 1 CLIENT: PROJECT: TO: FROM: Guilford County Schools (GCS) Southeast High School Auditorium & Gymnasium HVAC Improvements All Prospective Bidders Derrick Giles, SAMR, PLLC. DATE: 6/6/2018 The

More information

IAQ: Re-tuning Commercial Buildings

IAQ: Re-tuning Commercial Buildings IAQ: Re-tuning Commercial Buildings A low-cost path to improved air quality and energy efficiency. B y S c o t t G o r d o n, C M All images courtesy of Johnson Controls Service. 10 RSES Journal FEBRUARY

More information

Zoning Solutions. Thermostats & Wiring Centers Designed to Maximize Indoor Comfort. A Watts Water Technologies Company

Zoning Solutions. Thermostats & Wiring Centers Designed to Maximize Indoor Comfort. A Watts Water Technologies Company Zoning Solutions Thermostats & Wiring Centers Designed to Maximize Indoor Comfort HVAC Systems Multi-Staging Alternative Energy Zoning Snow Melting Setpoint A Watts Water Technologies Company Zoning in

More information

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates Prescriptions for Critical Healthcare Cx John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. Medical Industry Changes and how they impact Design, Construction,

More information

Single zone RTU, controlled by a programmable thermostat. Single zone RTU, generic description, with power exhauster

Single zone RTU, controlled by a programmable thermostat. Single zone RTU, generic description, with power exhauster Rooftop Units CV Reheat RTU Reheat Reheat system RTU, serving electric reheat coils, w/dehumidification cycle & RA CO2 override of OAD CV Single Zone RTU SZ (from PC) RTU SZ Generic RTU SZ Multiple Units

More information

2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems

2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems 2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems Dieter Bartel, Manitoba Hydro September 17 th, 2014 Outline Scope and compliance Prescriptive path

More information

Product Data. Features/Benefits. 33CS Carrier Comfort System Variable Volume and Temperature (VVT )

Product Data. Features/Benefits. 33CS Carrier Comfort System Variable Volume and Temperature (VVT ) Product Data 33CS Carrier Comfort System Variable Volume and Temperature (VVT ) The VVT Comfort System provides the following features and benefits: 365-day scheduling, daylight savings compensation, and

More information

Integrated Automation

Integrated Automation Revision 04/27/2017 Purpose: The Architect and/or Engineer shall incorporate the Rice specific requirements indicated in this standard s section into their design. The Architect and/or Engineer shall further

More information

- Data Brochure Universal Reset Module 423

- Data Brochure Universal Reset Module 423 - Data Brochure Universal Reset Module 423 D 423 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012 HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

EarthWise System Seminar

EarthWise System Seminar EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States

More information

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN 20-131.001 Page 1 Copyright 2017 Unico Inc. TABLE OF CONTENTS APPLICATIONS... 3 CABINET CONSTRUCTION... 3 FEATURES AND CONTROLS... 3 DIMENSIONAL

More information