COMBUSTION SAFETY BASICS

Size: px
Start display at page:

Download "COMBUSTION SAFETY BASICS"

Transcription

1 COMBUSTION SAFETY BASICS Joe Konopacki Why Combustion Safety? Hydrocarbon fuels are hazardous Explosion or fire is possible Poor indoor air quality Exhaust byproducts are harmful or deadly Safe and efficient combustion Proper exhaust management Fire hazards happen thoughtlessly Combustibles set near fire Our clients want a safe & healthy home Communicate the level of risk & required action What to look for Combustion Process & CO Ambient (breathing zone) CO Gas/fuel Leaks Combustion Air CO production (on all gas appliances) CH 4 + 2O 2 2 H 2 O Exhaust Spillage signs Dryer Safety CO 2 Combustion is rarely perfect 1

2 CO Production Lack of oxygen = Incomplete combustion Inadequate combustion air High gas pressure Dirty, Misaligned burners Flame impingement Back drafting of combustion byproducts Carbon Dioxide (CO 2 ) --Nitrogen Oxide (NO) Carbon Monoxide (CO) --Sulfur Dioxide (SO 2 ) Ambient (breathing zone) CO CO Alarms ~3 yr Sensor Life! Ambient (breathing zone) CO Ambient CO Monitoring CO Alarm Young, old and ill feel effects first >5ppm can affect a fetus Position near source CO Detectors ~3 year typical sensor service life Some claim 10 year service TEST is for the battery, not the sensor Ambient (breathing zone) CO 2

3 Ambient (breathing zone) CO Ambient CO Monitoring CO Detector From time of entry BPI Ambient Limit: 35 ppm Ventilate Determine source Detecting Gas Leaks Gas/fuel Leaks Zero Out Outside or not? Adjust/Check Sensitivity Slowly move sensor around joints Check all accessible fuel pipe and joints Don t move appliances Natural gas rises -Propane falls Gas/fuel Leaks Reporting Gas Leaks Confirm with soap bubble solution? Tag it & Photo Leave a notice for homeowner Call out Pre-1973 Brass gas lines Gas Leaks Gas/fuel Leaks Most common issue Typical 1 leak per house average Not Normal Symptoms Respiratory allergic reactions Mold allergies Respiratory sensitivity 3

4 10/26/2016 Combustion Air Combustion Air Combustion Air from Inside Combustion Air from Outside 1 Total BTU to Volume of space 100, /. 2 / = 5, ft2 x 8 tall space 1 CO Production Gas Oven Testing. 1.5 / CO Production Gas Oven Testing Gas Oven CO Measurement Open window and/or turn On exhaust fan Test CO level in flue (undiluted stream) Set oven at highest setting (Broil) Monitor ambient CO during test (~2 ft away) Steady State Over 100 ppm is excessive 4

5 CO Production Gas Oven Testing CO Production Gas Oven Testing Gas Oven CO Measurement Record CO level at 10 minutes (Steady State) Report CO profile Recommend clean, tune & re-test Use exhausting range hood Typical high CO source in homes Types of Exhaust Atmospherically vented Natural Draft Uses metal exhaust pipe Inside air for combustion Hot exhaust rises due to greater buoyancy Open draft hood for dilution air Spillage possible here Types of Exhaust Induced Draft or Mechanically Assisted 5

6 Types of Exhaust Atmospherically vented Induced Draft or Mechanically Assisted Uses metal exhaust pipe Inside air for combustion Fan pulls combustion air through heat exchanger Fan does notpush exhaust up and out Measure CO Under or through draft hood Access undiluted flue gases Types of Exhaust Power Vented =1PVC pipe Inside air for combustion Cool exhaust pushed out Direct Vent= 2 PVC pipes (a.k.a. Sealed Combustion) Outside air for combustion Cool exhaust pushed out Check CO outside Types of Exhaust Power Vented =1PVC pipe Direct Vent= 2 PVC pipes 6

7 Types of Exhaust Proper Venting ¼ rise per foot min. for horizontal Min Vertical Rise (typically 3x vent diameter) With commonly vented units: Smaller Btu unit vented Above Larger Btu unit A Y-fitting assists natural upward draft Smaller unit Y s into Larger unit Improper Venting Blocked, or partially blocked, chimneys, vents or vent connectors No chimney liner for orphaned water heaters Improperly designed vent system An indirect route Negative slope T-fittings Lack of code compliance 7

8 Improper Venting 8

9 House Pressures House Pressures Stack Effect Creates negative pressure low in home Driven by temperature difference to outside Greater Stack pressure requires greater Draft pressure Wind Effect Positive pressure on Windward side induces spillage Negative pressure on Leeward side induces draft Make note of: Wind direction & speed Location of Flue Mechanical Fans Bath & kitchen fans ( cfm) Clothes Dryer ( cfm) Wood/gas burning stoves & fireplaces (300+ cfm) House Pressures Consider: Air Handler Duct Leaks Supply/Return Distribution Door Closures This is what leaky ductwork can do to your house No Leaks Supply Leaks Whole-house fan ( cfm) Return Leaks Room Imbalances 9

10 House Pressures House Pressures Exhaust Spillage Signs Depressurization Limit Negative Draft Pressure Limit is: Low for weak draft appliances High for stronger appliances Exhaust Spillage Signs Large exhaust fans Wind on chimney Room pressures Flue obstruction Negative CAZ Pressure Tug-of-War handicap Occasional Exhaust Spillage Flue geometry 10

11 Clogged flue FAU pressures Open returns Duct leaks Constant exhaust fans Tight home Exhaust Spillage Signs Consistent Exhaust Spillage Exhaust Spillage Signs Worst Case Pressure Testing The goal is to make the appliance fail. If it can be done on purpose, the homeowner may do it by accident. So how much negative pressure is too much? Exhaust Spillage Signs Worst Case Depressurization Typical Pressure Limit = -5 Exhaust Spillage Signs Spillage Test Fire appliance & check for spillage for 1 minute CDL Exceeded -FAIL- 11

12 Dryer Safety Vinyl or metalized Mylar will burn Fire hazard with gas dryers Recommend: Install metal flex or solid Clean entire line of lint No CO testing Dryer Safety Issues to Look For Dryer exhaust duct material Gas leaks Oven CO/ Range hood venting Combustion air requirements Melted grommets on water heater Corrosion near draft hood Evidence of flame roll out Benefits of CO Test Benefits of Detect Dangerous CO Malfunctioning unit Inefficient unit Cracked heat exchanger -$$ Recommend further analysis & repair Better understanding of house pressures on combustion exhaust flow Safety issues to look out for Dryer vent material Gas leaks Oven CO 12

13 QUESTIONS? 13

State of ALASKA, Weatherization Assistance Program. Technical Support Document. Combustion Safety

State of ALASKA, Weatherization Assistance Program. Technical Support Document. Combustion Safety 5.3.1A(2) Page 1 of 2 State of ALASKA, Weatherization Assistance Program Technical Support Document Combustion Safety This document is intended to support in detail the Combustion Safety Test Report. The

More information

RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO

RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO rgalenmoore1@msn.com This session will address the basics of combustion and the latest

More information

COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES*

COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* *Vented appliances refer to natural draft appliances equipped with a barometric draft regulator or Category I appliances equipped with a draft

More information

RESNET National Conference New Orleans, La. February 15, 2009 Presented by Rich Moore Invisible Energy Denver, CO

RESNET National Conference New Orleans, La. February 15, 2009 Presented by Rich Moore Invisible Energy Denver, CO RESNET National Conference New Orleans, La. February 15, 2009 Presented by Rich Moore Invisible Energy Denver, CO rgalenmoore1@msn.com Effective insulation and air sealing treatments can make a huge difference

More information

EnergyMeasure HOME DATA COLLECTION FORM

EnergyMeasure HOME DATA COLLECTION FORM EnergyMeasure HOME DATA COLLECTION FORM Section 1: General Information Customer Name: Site ID: Assessment Date: Street Address: City: State: Zip Code: Alternate Address: City: State: Zip Code: Telephone

More information

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO Combustion Safety RESNET Conference San Antonio, TX February 27, 2006 Presented by Rich Moore Lightly Treading Energy & Design Denver, CO Goals of this session Recognize the need for combustion safety

More information

Objectives. Home Performance Diagnostics with the House of Pressure (Part 1) How can Pressure effect Building Performance?

Objectives. Home Performance Diagnostics with the House of Pressure (Part 1) How can Pressure effect Building Performance? Home Performance Diagnostics with the House of Pressure (Part 1) Objectives Learn the basic rules of air flow and differences Begin to be able to recognize building problems related to airflow and differences

More information

Home Performance Science

Home Performance Science Home Performance Science Symptoms of a Sick House Too hot/too cold rooms Respiratory problems Headaches/nausea Smoky fireplace Foggy windows Stuffy air and lingering odors Peeling paint Constant dust problems

More information

Whole House Combustion Appliance Safety Test Procedure for Pacific Gas and Electric Company (PG&E) Advanced Home Upgrade 2019

Whole House Combustion Appliance Safety Test Procedure for Pacific Gas and Electric Company (PG&E) Advanced Home Upgrade 2019 Whole House Combustion Appliance Safety Test Procedure for Pacific Gas and Electric Company (PG&E) Advanced Home Upgrade 2019 Note: This procedure is subject to revision or modification by PG&E at any

More information

Indiana WX Oil Furnace Inspection Guide

Indiana WX Oil Furnace Inspection Guide Indiana WX Oil Furnace Inspection Guide Client: Job # : Address: Phone: Client Interview: Oil Dealer: Date of last service: Comments/Billing information: Standard Inspection / Clean and Tune Follow-up:

More information

Spray Polyurethane Foam and Open-Combustion Appliances

Spray Polyurethane Foam and Open-Combustion Appliances Spray Polyurethane Foam and Open-Combustion Appliances Before applying SPF (spray foam polyurethane) insulation in an attic or crawl space it is important to determine if there are any appliances present,

More information

Green Building Practice Summary 3/10/2011

Green Building Practice Summary 3/10/2011 Green Building Practice Summary 3/10/2011 Sector: Residential Category/Practice: IEQ / Safer Combustion Appliances: New Construction Proposed GB Practice Description Most natural draft combustion appliances

More information

Combustion Appliance Safety Testing Guidelines

Combustion Appliance Safety Testing Guidelines Combustion Appliance Safety Testing Guidelines This guide is intended to assist home performance contractors complete all combustion safety tests adequately and safely according to the Building Performance

More information

Combustion gases in your home: What you should know about combustion spillage

Combustion gases in your home: What you should know about combustion spillage Combustion gases in your home: What you should know about combustion spillage Are combustion gases spilling into your home? Does your home have any of these combustion appliances? gas-fired furnace, boiler

More information

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06 page 1 of 6 VENTING CLEARANCES The vents should not be obstructed and all joints properly fitted. Floors, ceilings and walls must be cut or framed to provide necessary clearance to vents. Metal strippings

More information

BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST

BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST 1. Pre-Inspection Homeowner Interview (3 minutes) A. Turn on & zero CO Meters. Determine ambient CO : B. Record Outside Temperature: C. Homeowner interview:

More information

BUILDING PERFORMANCE INSTITUTE TECHNICAL STANDARDS

BUILDING PERFORMANCE INSTITUTE TECHNICAL STANDARDS BUILDING PERFORMANCE INSTITUTE TECHNICAL STANDARDS FOR THE BUILDING ANALYST PROFESSIONAL Health and Safety All technicians performing diagnostic tests, inspections, or installations, must have access to

More information

Combustion Sources of Carbon Monoxide. Carbon Monoxide Repairs. Topics Addressed in Session. Why CO can be Harmful Inhalation Time and Symptoms

Combustion Sources of Carbon Monoxide. Carbon Monoxide Repairs. Topics Addressed in Session. Why CO can be Harmful Inhalation Time and Symptoms Affordable Comfort Conference 2002 Saturday, April 20, 8:00 12:00 Rick Karg R.J. Karg Associates www.karg.com April 2002 2002 R.J. Karg Associates Topics Addressed in Session Combustion sources of CO.

More information

Overview of Gas Range Types

Overview of Gas Range Types Residential Gas Ranges Overview of Types How Carbon Monoxide is Emitted How They Operate Overview of Gas Range Types Rick Karg R.J. Karg Associates www.karg.com November 2001 2001 R.J. Karg Associates

More information

SnuggPro DATA COLLECTION FORM

SnuggPro DATA COLLECTION FORM SnuggPro DATA COLLECTION FORM Section 1: General Information Trade Ally: Trade Ally Telephone: Trade Ally Email: Auditor Name: Auditor Telephone: Auditor Email: Home Owner Name: Home Owner Telephone: Home

More information

MBPA Home Performance FIELD DATA COLLECTION FORM

MBPA Home Performance FIELD DATA COLLECTION FORM MBPA Home Performance FIELD DATA COLLECTION FORM Customer Information Test Date: Name Address City State Zip Phone: ( ) Email: Electric Provider Heating Fuel Provider Account Number Account Number Customer

More information

Introductions HERS Industry HERS Ratings ACCA Standard 12 Resources

Introductions HERS Industry HERS Ratings ACCA Standard 12 Resources Abe Kruger 2013 RESNET Conference abe@krugersustainabilitygroup.com 215/385-6891 Introductions HERS Industry HERS Ratings ACCA Standard 12 Resources www.krugersustainabilitygroup.com 1 HERS Rater & Trainer/QAD

More information

Direct Vent System Required

Direct Vent System Required CB-200A Cottage Base Installation Instructions IMPORTANT: Read all instructions carefully before beginning the installation. This base must be installed by a qualified installing agency and in accordance

More information

Energy Design Conference 2016 Test Protocols & Results: Airport Sound Program and Building America Field Tests

Energy Design Conference 2016 Test Protocols & Results: Airport Sound Program and Building America Field Tests Energy Design Conference 2016 Test Protocols & Results: Airport Sound Program and Building America Field Tests Dave Bohac, PE Center for Energy and Environment MSP Airport Sound Program Weatherization

More information

Natural Gas Appliance Testing Action Guidelines (Non ESA/Low Income 5 )

Natural Gas Appliance Testing Action Guidelines (Non ESA/Low Income 5 ) Natural Gas Appliance Testing Action Guidelines (n ESA/Low Income 5 ) The purpose of these Action Guidelines is to describe the actions participating contractors and/or inspectors should take in the event

More information

Whole House Action Guidelines

Whole House Action Guidelines for Pacific Gas and Electric Company's (PG&E) Whole House Rebate Progam 12/23/2011 The purpose of these Action Guidelines is to describe the actions participating contractors and/or inspectors should take

More information

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems about your house CE 28 k Assessing the Comfort and Safety of Your Home s Mechanical Systems The heating, ventilating and air conditioning (HVAC) systems are a vital part of every home. These mechanical

More information

Retrofit Installer-Mechanical

Retrofit Installer-Mechanical Retrofit Installer-Mechanical Lesson Plan Section 1: Gas FurnaceFundamentals Learning Objectives By attending this session, participants will: Know the components of a gas furnace Understand the basic

More information

Seriously how do you know your CO monitor is Working!

Seriously how do you know your CO monitor is Working! Seriously how do you know your CO monitor is Working! SHHHHHHHHHHHHHHHH, the deadly gas maybe coming to get you in your home. Difficult to detect and treat once the damage is done, carbon monoxide is known

More information

Combustion Safety Testing: What we learn from Standards and Research. Objectives. Objectives 2/24/2016

Combustion Safety Testing: What we learn from Standards and Research. Objectives. Objectives 2/24/2016 Combustion Safety Testing: What we learn from Standards and Research Better Buildings Better Business Conference March 2016 Experience. Innovation. Results. Confiden al 2015 Objectives Identify differences

More information

BEST DRAFT CONTROL: MANUAL DAMPERS IN MULTIPLE BOILER SYSTEMS

BEST DRAFT CONTROL: MANUAL DAMPERS IN MULTIPLE BOILER SYSTEMS BEST DRAFT CONTROL: MANUAL DAMPERS IN MULTIPLE BOILER SYSTEMS WHITEPAPER Decades of evolving codes have led to much confusion over how dampers can and cannot be used. Contrary to popular belief, manual

More information

QUALITY CONTROL INSPECTION GUIDELINES V6.0

QUALITY CONTROL INSPECTION GUIDELINES V6.0 SOUTHERN CALIFORNIA EDISON AND SOCALGAS ENERGY UPGRADE CALIFORNIA HOME UPGRADE SOCALGAS ENERGY UPGRADE CALIFORNIA HOME UPGRADE QUALITY CONTROL INSPECTION GUIDELINES V6.0 This page was intentionally left

More information

Prepared by: (415) Indoo. Prepared for: Final Report. Contributors: Rob. dekiefferr Tom. Me!

Prepared by: (415) Indoo. Prepared for: Final Report. Contributors: Rob. dekiefferr Tom. Me! Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-24800 Arizona Public Service Indoo or Air Quality Study Prepared for: Arizona Public Service Final Report December 3, 1997 Contributors:

More information

The evil that men do lives after them; the good is oft interred with their bones.

The evil that men do lives after them; the good is oft interred with their bones. Did I do that?? The evil that men do lives after them; the good is oft interred with their bones. William Shakespeare 1 Windows sweat Mold starts to grow Coil freezes up on A/C Utility bills not as low

More information

Carbon monoxide (CO) is a colorless, odorless gas that is the product of incomplete combustion of carbon-based fuels.

Carbon monoxide (CO) is a colorless, odorless gas that is the product of incomplete combustion of carbon-based fuels. Construction Concerns: Carbon Monoxide November 20, 2017 By Gregory Havel Carbon monoxide (CO) is a colorless, odorless gas that is the product of incomplete combustion of carbon-based fuels. The chemical

More information

Carbon Monoxide Alarm

Carbon Monoxide Alarm Carbon Monoxide Alarm Benefits of the Carrier Carbon Monoxide Alarm INTRODUCTION A very serious and often ignored issue in the home is the possible presence of carbon monoxide (CO) gas. Carbon monoxide

More information

New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011

New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011 New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011 Customer: Street: City: Zip: Phone: (Home): ( ) - Phone: (Work): ( ) - Owner: Yes No/ Name: Phone: ( )

More information

qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system.

qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system. 8. qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system. How Chimneys Work An effective chimney is an important part of any successful wood-burning system. Many of

More information

Temperature Relative Humidity

Temperature Relative Humidity Prepared For: John Smith 1234 Any Street Portland, OR 97219 (503) 416-0000 Conducted By: AirAdvice 503-416-7859 Test Period: 4/18/10 4/24/10 Monitor ID: #11922 Report ID: #164139 This report offers recommendations

More information

Southern California Edison and SoCalGas Energy Upgrade California Home Upgrade. SoCalGas

Southern California Edison and SoCalGas Energy Upgrade California Home Upgrade. SoCalGas Southern California Edison and SoCalGas Energy Upgrade California Home Upgrade SoCalGas Energy Upgrade California Home Upgrade Quality Control Inspection Guidelines V6.0 March 2016 ii Table of Contents

More information

CHIMNEY INSTALLATION. Technical Bulletin #1

CHIMNEY INSTALLATION. Technical Bulletin #1 Technical Bulletin #1 CHIMNEY INSTALLATION A chimney performs two functions: it removes smoke and flue gases from the stove/furnace, and it provides draft for the fire. Draft is the term used to describe

More information

VF/VG700 Jumbo. Construction Heater. Installation and Maintenance Manual

VF/VG700 Jumbo. Construction Heater. Installation and Maintenance Manual 342 N. Co. Rd. 400 East Valparaiso, IN 46383 888-432-8924 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. VF/VG700 Jumbo Construction

More information

WARNING FIRE OR EXPLOSION HAZARD.

WARNING FIRE OR EXPLOSION HAZARD. 2017 Lennox Industries Inc. Dallas, Texas, USA 506897-01 04/2017 Supersedes 10/2015 EL280DF SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property damage,

More information

bout your house WHY THE CONCERN?

bout your house WHY THE CONCERN? A bout your house CE2 COMBUSTION GASES IN YOUR HOME THINGS YOU SHOULD KNOW ABOUT COMBUSTION SPILLAGE ARE COMBUSTION GASES SPILLING INTO YOUR HOME? Does your home have any of these appliances? gas-fired

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW & DOWNFLOW/HORIZONTAL CONDENSING GAS FURNACES SAFETY Recognize this symbol as an indication of Important Safety Information If not installed, operated and maintained in

More information

Manhattan Fire Protection District

Manhattan Fire Protection District Section: RESCUE OPERATIONS Page 1 of 5 PURPOSE: This procedure is established to ensure proper detection and mitigation of carbon monoxide alarms and emergencies, and to provide a standard of response

More information

WAP Pressure Diagnostics Procedure. Page 1

WAP Pressure Diagnostics Procedure. Page 1 WAP Pressure Diagnostics Procedure Page 1 This document is meant to describe an overall procedure that will allow a WAP Energy Assessor to conduct a thorough blower door / manometer guided diagnostic assessment

More information

Carbon Monoxide. Carbon Monoxide in the Home. Part II Sources of CO in the home. Part I Health effects of CO

Carbon Monoxide. Carbon Monoxide in the Home. Part II Sources of CO in the home. Part I Health effects of CO Carbon Monoxide in the Home A Community Workshop Presented by William W. Hill, Ph.D. Department of Urban Planning Ball State University Sponsored by the Community Outreach Partnership Center and East Central

More information

HEALTH. Particles. Chemicals

HEALTH. Particles. Chemicals AirAdvice for Your Home Monitor: 32212 Report ID: 227907 02/23/16 10:00 AM Action Recommended Particles 25.4 ug/m3 This report displays our findings about the air quality in your home, and offers recommendations

More information

Energy Saver 101: Home Energy Audits

Energy Saver 101: Home Energy Audits Energy Saver 101: Home Energy Audits Take the first step to improving your home s energy efficiency: get a home energy audit. What is a home energy audit? A home energy audit helps you pinpoint where your

More information

TASKS REGARDING COMBUSTION AIR

TASKS REGARDING COMBUSTION AIR TASKS REGARDING COMBUSTION AIR DETERMINE IF THERE IS ENOUGH COMBUSTION AIR FOR THE TYPES OF APPLIANCES IN THE CAZ Use one of two methods, depending on appliance type and whether or not you have a blower

More information

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified Thank you for purchasing our fully-automatic gas-fired tankless water heater. Please completely read this Manual

More information

about your house Before You Start an Energy-Efficient Retrofit Mechanical Systems

about your house Before You Start an Energy-Efficient Retrofit Mechanical Systems about your house CE 28i Before You Start an Energy-Efficient Retrofit Mechanical Systems One of the best ways to make your home more comfortable, healthier and less expensive to operate is to upgrade the

More information

Installing an exhaust system with a capacity Wood Heat

Installing an exhaust system with a capacity Wood Heat HOME COMBUSTION & ENERGY GUIDE TECHNIQUES TACTICS & TIPS Outside combustion air supplies for furnaces, water heaters, wood stoves and fireplaces How to test for combustion air The difference between makeup

More information

The Heating System and Ventilation and Combustion Air

The Heating System and Ventilation and Combustion Air The Heating System and Ventilation and Combustion Air Introduction Both you and your furnace need some fresh air coming into the house, but most Canadian homes have too much. In fact, 25 percent or more

More information

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION DL Bohac * Center for Energy and Environment, Minneapolis, MN USA ABSTRACT Extensive

More information

SERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA

SERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA SERVICE FACTS Gas Furnaces Upflow & Downflow Induced Draft Stage Heat Models: M80P00AU2AA M80P060AU2AA M80P060AU36AA M80P080BU36AA M80P080BU8AA M80P00BU36AA M80P00CU8AA M80P00CU60AA M80PDU60AA M80P0DU60AA

More information

Heating and Hot Water

Heating and Hot Water Heating and Hot Water Funding Funding for this class was provided by the Alaska Housing Finance Corporation (AHFC). This course is designed to empower homeowners with the knowledge to live in and maintain

More information

INSTALLATION AND SERVICE MANUAL

INSTALLATION AND SERVICE MANUAL INSTALLATION AND SERVICE MANUAL VERTICAL COMBUSTION AIR INLET KITS CATEGORY III VENTING FOR SEPARATED COMBUSTION TUBULAR GAS FIRED UNIT HEATERS USE 5 INCH KIT FOR UNITS WITH CAPACITIES 100,000 TO 250,000

More information

Home Heating MORE THAN JUST STAYING WARM

Home Heating MORE THAN JUST STAYING WARM Home Heating MORE THAN JUST STAYING WARM Types of Home Heating Fuel Sources Propane (LP) Natural Gas Fuel Oil Wood Coal Kerosene Pellets Outdoor wood boilers Electric Combustion CH4 + O2 CO2 + H2O Less

More information

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce. Ventilation ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce /NDCommerce /NDCommerce /NDCommerce /NDCommerce WHATS NEW IN ASHRAE 62.2 2016 Controls (Override) Shutoff for maintenance

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

Response to Carbon Monoxide Incidents. W.J. Streett Jr Training Section Chief

Response to Carbon Monoxide Incidents. W.J. Streett Jr Training Section Chief Response to Carbon Monoxide Incidents W.J. Streett Jr Training Section Chief The Secret to Success Joe Loving and his faithful hunting companion bag another big buck Overview Introduction Carbon Monoxide

More information

INSTALLER'S GUIDE MASONRY CHIMNEY VENT KIT WARNING: BAYVENT800B 18- CH23D2-05

INSTALLER'S GUIDE MASONRY CHIMNEY VENT KIT WARNING: BAYVENT800B 18- CH23D2-05 INSTALLER'S GUIDE IMPORTANT This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work. Model: BAYVENT800B For use with Category

More information

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments: Second Revision No. 3-NFPA 31-2015 [ Section No. 10.5.1 ] 10.5.1* Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the

More information

INSTALLATION AND SERVICE MANUAL

INSTALLATION AND SERVICE MANUAL INSTALLATION AND SERVICE MANUAL HORIZONTAL COMBUSTION AIR INLET KITS CATEGORY III VENTING FOR SEPARATED COMBUSTION TUBULAR GAS FIRED UNIT HEATERS USE 5 INCH KIT FOR UNITS WITH CAPACITIES 100,000 TO 250,000

More information

BPI 1200 and ASHRAE Standards

BPI 1200 and ASHRAE Standards BPI 1200 and ASHRAE Standards For the HPwES Program in 2016 December 16, 2015 Audio Connection To connect to audio: 1. Click the Call Using Computer button to use this setting. a. To confirm connection,

More information

ML180UH SERIES GAS FURNACE WARNING WARNING

ML180UH SERIES GAS FURNACE WARNING WARNING 2017 Lennox Industries Inc. Dallas, Texas, USA 506525-01 04/2017 Supersedes 10/2015 ML180UH SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property damage,

More information

Ventilation and Indoor Air Quality

Ventilation and Indoor Air Quality Ventilation and Indoor Air Quality Funding Funding for this class was provided by the Alaska Housing Finance Corporation (AHFC). This course is designed to empower homeowners with the knowledge to live

More information

EL195UHE SERIES GAS FURNACE WARNING WARNING

EL195UHE SERIES GAS FURNACE WARNING WARNING 2012 Lennox Industries Inc. Dallas, Texas, USA 506737-01 12/2012 Supersedes 06/2011 EL195UHE SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property

More information

EL296UHV SERIES GAS FURNACE WARNING WARNING

EL296UHV SERIES GAS FURNACE WARNING WARNING 2011 Lennox Industries Inc. Dallas, Texas, USA 506769 01 08/2012 Supersedes 10/2011 EL296UHV SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property

More information

EL195DFE SERIES GAS FURNACE WARNING

EL195DFE SERIES GAS FURNACE WARNING 2011 Lennox Industries Inc. Dallas, Texas, USA 506739 01 06/2011 EL195DFE SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in serious injury,

More information

VENTING GAS APPLIANCES NFPA 54 CODE

VENTING GAS APPLIANCES NFPA 54 CODE VENTING GAS APPLIANCES NFPA 54 CODE Better Buildings: Better Business Robert Parkhurst March 3, 2017 Objectives Standardize terminology Examine gas piping size and safety Simplify design rules Selection

More information

Good Ideas For Propane Safety

Good Ideas For Propane Safety Good Ideas For Propane Safety What You Don't Know CAN Hurt You Safety...It's Up to You Propane is a safe, reliable fuel. Like many other fuels, however, it is flammable. That means it can be dangerous

More information

CARBON MONOXIDE DETECTOR, i4h-co-m330

CARBON MONOXIDE DETECTOR, i4h-co-m330 CARBON MONOXIDE DETECTOR, i4h-co-m330 Alarm LED Power LED Fault LED Air Vents Test/Mute Button Press the latch and push the cover downward to open the battery compartment INTRODUCTION The i4h-co-m330 electrochemical

More information

WARNING FIRE OR EXPLOSION HAZARD.

WARNING FIRE OR EXPLOSION HAZARD. 2017 Lennox Industries Inc. Dallas, Texas, USA 506698-01 04/2017 Supersedes 10/2015 SL280DFV SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property

More information

Venting of Gas Fired Equipment RV

Venting of Gas Fired Equipment RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this

More information

2012 INTERNATIONAL FUEL GAS CODE VENTS

2012 INTERNATIONAL FUEL GAS CODE VENTS 2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with

More information

FGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP)

FGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP) FGR Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM FGR-8 through FGR-22 (25 HP to 1000 HP) Gas, Light Oil or Combination MANUFACTURED BY JOHN ZINK COMPANY, LLC

More information

RECOMMENDED PROCEDURES FOR THIRD-PARTY PREVENTATIVE MAINTENANCE PROVIDERS

RECOMMENDED PROCEDURES FOR THIRD-PARTY PREVENTATIVE MAINTENANCE PROVIDERS RECOMMENDED PROCEDURES FOR THIRD-PARTY PREVENTATIVE MAINTENANCE PROVIDERS 1 Contents Introduction... 3 Portfolio Energy Goals... 3 Purpose of This Document... 3 Gas Furnaces... 4 Electric Furnaces... 7

More information

EL195UH SERIES GAS FURNACE WARNING

EL195UH SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506597 01 11/2010 EL195UH SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in serious injury,

More information

Temperature Relative Humidity

Temperature Relative Humidity Prepared For: John Smith 1234 Any Street Portland, OR 97219 (503) 416-0000 Conducted By: AirAdvice 503-416-7859 Test Period: 4/18/10 4/24/10 Monitor ID: #11922 Report ID: #164139 This report offers recommendations

More information

PVE SERIES POWER VENTER SYSTEM MANUAL

PVE SERIES POWER VENTER SYSTEM MANUAL PVE SERIES POWER VENTER SYSTEM MANUAL Contents Page I. Typical Venting System Components 2 II. System Operation 3 III. Power Venter Sizing 3,4 IV. Installation Safety Instructions 5,6 V. Installation of

More information

CHIMNEYS AND VENTS CHAPTER 8

CHIMNEYS AND VENTS CHAPTER 8 CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

RS Chimney Fan for Solid Fuel Applications

RS Chimney Fan for Solid Fuel Applications Installation & Operating Manual RS Chimney Fan for Solid Fuel Applications USA CAN Product Information... Chapter 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up

More information

REFERENCE GUIDE TO SUCCESSFUL BPI EXAMS

REFERENCE GUIDE TO SUCCESSFUL BPI EXAMS REFERENCE GUIDE TO SUCCESSFUL BPI EXAMS compiled to assist you by A. Tamasin Sterner President and Chief Coach December 2014 Major Standards of Reference BPI Exams Note - All BPI exams are based on a mixture

More information

Bosch 80% AFUE Gas Furnace BGS80 Model

Bosch 80% AFUE Gas Furnace BGS80 Model Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace User's Information Manual 3124627 2 Bosch 80% AFUE Gas Furnace User's Information Manual Data subject to change 06.2018

More information

RS Chimney Fan for Solid Fuel Applications

RS Chimney Fan for Solid Fuel Applications Installation & Operating Manual RS Chimney Fan for Solid Fuel Applications USA CAN Product Information... Chapters 1 + 2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start

More information

ASX7-4-IOM-6 J

ASX7-4-IOM-6 J INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT

More information

FURNACE OPERATION OVERVIEW

FURNACE OPERATION OVERVIEW You ve had a fun day but now it s getting chilly, so you decide to fire up the RV furnace. You flip the thermostat on, set the temperature and wait expectantly, but no heat comes from the outlets. It s

More information

OWNER S MANUAL PG9YAA HIGH EFFICIENCY GAS FURNACE ! WARNING SAFETY CONSIDERATIONS

OWNER S MANUAL PG9YAA HIGH EFFICIENCY GAS FURNACE ! WARNING SAFETY CONSIDERATIONS HIGH EFFICIENCY GAS FURNACE OWNER S MANUAL NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. USER: Please read all instructions in the manual and retain all manuals for future reference.

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW/HORIZONTAL & DOWNFLOW TWO STAGE INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this manual is not

More information

G61MPV SERIES GAS FURNACE WARNING

G61MPV SERIES GAS FURNACE WARNING 2003 Lennox Industries Inc. Dallas, Texas, USA 504,809M 03/2009 Supersedes 06/2003 G61MPV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result

More information

GAS BOILERS USER'S INFORMATION MANUAL SG-135-E TO SG-495-E AAA-480 TO AAA-3000

GAS BOILERS USER'S INFORMATION MANUAL SG-135-E TO SG-495-E AAA-480 TO AAA-3000 USER'S INFORMATION MANUAL GAS BOILERS FOR MODELS: MG-50-E TO MG-150-E SG-135-E TO SG-495-E AAA-480 TO AAA-3000 WARNING: If the information in this manual is not followed exactly, a fire or explosion may

More information

MANUAL WARNING FIRE OR EXPLOSION HAZARD. SL280UHNV SERIES WHAT TO DO IF YOU SMELL GAS:

MANUAL WARNING FIRE OR EXPLOSION HAZARD. SL280UHNV SERIES WHAT TO DO IF YOU SMELL GAS: U S E R S I N F O R M AT I O N MANUAL 2017 Lennox Industries Inc. Dallas, Texas, USA SL280UHNV SERIES 507650-01 10/2017 Improper installation, adjustment, alteration, service or maintenance can cause property

More information

Gas Safety. Syllabus. For. Gas Appliance Service. Certificate of Qualification Examination. (Formerly Class C)

Gas Safety. Syllabus. For. Gas Appliance Service. Certificate of Qualification Examination. (Formerly Class C) Gas Safety Syllabus For Gas Appliance Service Certificate of Qualification Examination (Formerly Class C) 1. Prerequisites to obtain a gas appliance service certificate of qualification An applicant for

More information

Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs

Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs Rebecca Olson Neighborhood Energy Connection Duluth Energy Design Conference February 26 th, 2013 Duluth, MN Learning Objectives

More information

Supplement A- Improving Forced Air Heating Systems

Supplement A- Improving Forced Air Heating Systems Supplement A Improving Forced Air Heating Systems The Challenge Recent research and testing of new homes in the Pacific Northwest and across the United States shows the importance of a properly installed

More information