CHAPTER 4. HVAC DELIVERY SYSTEMS

Size: px
Start display at page:

Download "CHAPTER 4. HVAC DELIVERY SYSTEMS"

Transcription

1 CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer Cycle 4.7 Energy Recovery Systems 4.8 Controls and Automation 4.1 Introduction Complete HVAC systems are made up of sub-systems that produce heating and cooling, move heat transfer fluids, and control delivery to a space to maintain stable conditions. Equipment to produce heat transfer fluids (Primary components): Refrigeration Equipment (Cooling) Boiler (Heating) Furnaces (Heating) Equipment to move heat transfer fluids (Secondary components): Air: Air handling unit, Fan, Duct, Grill, Diffuser Water and refrigerant: pump, pipe Equipment to control flow rate of heat transfer fluids (Secondary components): Air: fan(speed), damper(on/off, flow rate) Water: pump(speed), valve(on/off, flow rate)

2 4.2 Centralized vs Individual Systems Duct and Diffuser Fan Coil Unit Duct Pipes AHU A high-rise building with centralized HVAC system Boiler Chiller Central mechanical room Refrigerant A building with central heating and individual cooling systems Radiator Hot water or steam Individual space heating Boiler

3 4.3 Heat Transfer Fluid (1) All Air System: AHU, Duct, Fan, Diffuser (2) All Water System: Pump, Pipe, Radiator, Fan Coil Unit (3) Air and Water System: (1) + (2) (4) Direct Expansion(DX) System: Package Air-Conditioning, Heat Pump 4.4 CAV versus VAV Systems Constant Air Volume (CAV) Systems In a Constant Air Volume (CAV) system, variations in the thermal requirements of a space are satisfied by varying the temperature of a constant volume of air delivered to the space. A constant fraction of outdoor air can be delivered to occupied spaces to satisfy ventilation standards. Variable Coil Temperatures ( o C) Constant Fan Speed (RPM) Constant Air Volume (m 3 /h) CAV systems are suitable for a large volume space and under ground spaces requiring high rates of ventilation. CAV systems are less energy efficient than VAV systems due to electric energy consumed by the fans. Q 0.29V t kcal/h V = constant air vol. (m 3 /h) t = variable air temp. ( o C) Variable Water Flow Rate (L/s) Variable Air Temperature

4 4.4.2 Variable Air Volume (VAV) Systems In a Variable Air Volume (VAV) ventilation system, variations in the thermal requirements of a space are satisfied by varying the volume of air that is delivered to the space at a constant temperature. Constant Coil Temperatures Variable Fan Speed Varying Duct Pressure Air Volume Control by VAV Box VAV systems reduce HVAC energy cost by 10-20% over CAV systems due to the reduced fan energy. Variable Air Volume (m 3 /h) VAV systems complicate the delivery of outdoor air. If the fraction of outdoor air is constant, the total volume of outdoor air will be reduced as the supply air volume is reduced. This would occur during partial-load conditions and cause indoor air quality problem. Q 0.29V t kcal/h V = variable air vol. (m 3 /h) t = constant air temp. ( o C) Constant Water Flow Rate (L/s) Constant Air Temperature 4.5 Common Systems for Heating and Cooling All Air Systems CAV Systems Single-Zone CAV System (4.5.1) Single-Zone CAV Reheat System (4.5.2) Multiple-Zone CAV Terminal Reheat System (4.5.3) Multiple-Zone CAV Dual-Duct System (4.5.4) CAV Multizone System (4.5.5) VAV Systems Single-Zone VAV System (4.5.6) Multiple-Zone VAV System (4.5.7) Multiple-Zone VAV Terminal Reheat System (4.5.8) Multiple-Zone VAV Dual-Duct System (4.5.9) VAV Multizone System (4.5.10) All Water Systems Fan Coil Units (FCU) (4.5.11) Radiant Panel Heating and Cooling (4.5.12) Direct Expansion(DX) Systems Package Terminal Air Conditioners (4.5.13) Heat Pumps (4.5.14)

5 4.5.1 Single-Zone CAV System Fans run continuously (constant volume) Coil temperatures are controlled by space thermostat to change flow rate of heating or cooling water. Application: Small scale commercial buildings Single-Zone CAV Reheat System This system is used when humidity control is especially important. A space humidistat is used for adjusting cooling coil temperature to condense moisture in the mixture air of OA and RA. Since the air temperature will generally be too cold to maintain a proper space temperature, a heating coil (reheat coil) is placed after the cooling coil.

6 4.5.3 Multiple-Zone CAV Terminal Reheat System This system is similar in principle to single-zone CAV reheat system, except that multiple zones of temperature and humidity controls can be achieved. The terminal box containing reheat coil is installed for each zone. The AHU unit is used mainly for humidity control, while the terminal unit for temperature control Multiple Zone CAV Dual-Duct System Warm and chilled air streams from AHU are sent through a pair of main trunk ducts and the two air streams are mixed in the mixing box installed for each zone or space. Effectively controls air temperature of each zone having different heating or cooling load. Mixing boxes are controlled with dampers to vary the quantity of warm and chilled air in response to the zone thermostat. The total airflow, consisting of warm and chilled air, stays fairly constant, since each damper closes as the other opens. This system waste much energy because warm and cold air are mixed.

7 Typical dual-duct terminal and its internal section CAV Multizone System This system is very similar in operation to dual-duct system. The mixing is done by dampers located at the AHU rather than at terminals located near the spaces. This system also waste energy because it mix warm and cold air. Multizones can have two sets of dampers (warm air and cold air) or three sets (warm, cold, and bypass). The latter, called triple-deck multizone, saves energy by mixing warm and bypass or cold and bypass rather than warm and cold air. A single multizone unit can serve up to approximately 12 zones. CAV multizone system (triple-zone, double-deck multizone unit)

8 The triple-deck multizone unit offers significant energy conservation by allowing return or outside air to bypass both coil, and the thermal inefficiency of mixing heated and cooled air is eliminated Single-Zone VAV System Airflow of constant temperature is increased or decreased in response to the space thermostat by adjusting dampers or the speed of the fans. This system gained popularity during the mid-1970s as an energy-efficient alternative to CAV terminal-reheat and CAV dual-duct system. No energy is wasted by reheating or mixing warm and chilled air. In addition, varying the air quantities offers energy savings in terms of operation of the fan, in comparison with CAV system. As the heating or cooling load diminishes, such as in spring and fall seasons, the airflow is reduced accordingly, and indoor air quality will also be deteriorated. Because the unit can serve just one zone, it is suitable only for small and simple buildings. Large buildings require multiples of this unit.

9 VAV Box Multiple-Zone VAV System This system uses a VAV AHU to supply chilled air into a main trunk duct feeding multiple VAV terminals for individual zones. VAV terminals are designed to provide only cooling. For buildings with heating loads, this system must be used in combination with other devices to provide heat. Interior spaces of large buildings need cooling year-round, and VAV systems often meet this need. Perimeter spaces need heating during cold weather and can be served by convectors or fan coil units (FCU)

10 Typical convector installed at the base of a perimeter wall to overcome the downdraft during cold weather Multiple VAV Interior and hot-water convector perimeter zone system Cutaway view of a hot-water convector showing the finned tube and supply pipe. Convectors may use steam or electric power and come in various designs and heights Multiple-Zone VAV Terminal Reheat System This system is equipped with electric or hot water heating coils and is similar to CAV reheat terminals except for control of the airflow. VAV reheating is generally less expensive and does not require locating equipment on the floor, so that space can be used more flexibly. OA

11 Construction of an electrical reheat coil in the ductwork. The coil may be a hot-water or an electric coil Multiple-Zone VAV Terminal Dual-Duct System VAV dual-duct terminals are arranged for operation at a variable rather than a constant air volume in order to conserve energy. Two air dampers (chilled air and warm air) in a VAV box are independently operated. In cooling mode, only chilled-air damper is open and the warm-air damper remains closed. As the cooling load diminishes, the amount of chilled air is reduced accordingly. When heating is required, the chilled air damper will be at or near closed position, and the warm-air damper will start to open and increase the flow of warm air as the heating load increases. With this mode of operation, there is minimal overuse of energy due to mixing of warm and cold air at the terminal.

12 VAV dual-duct terminal VAV Multizone System This is similar in operation to VAV dual duct system. Separate dampers are used for the warm and cold portions of the mixing section. The cold air damper is almost closed before the warm air damper is allowed to open. This prevents energy waste due to mixing.

13 Fan Coils Units A fan coil unit consists of a filter, a cooling and/or heating coil, a fan, and controls. Units can be located on the floor, above or below the ceiling, on the wall, or in the wall cabinets. Fan coil units can be designed with two or four pipes: A two-pipe unit has a set of supply and return pipes that can carry either hot or chilled water. A four-pipe unit has two sets of piping one set of supply and return for chilled water and another set for hot water. The four-pipe system is more flexible than the two-pipe system but more expensive to install. Fan coil units can be used at building perimeters in combination with VAV cooling-only systems serving interior spaces in large-scale commercial buildings. Exterior view of a FCU (vertical floor-mounted type) A close-up view of the valve assembly showing control and shutoff valves.

14 Radiant Panel Heating and Cooling Radiant heating panels can be used as perimeter heating devices in conjunction with coolingonly VAV systems, or as heating/cooling devices in conjunction with reduced-flow ventilation systems. Heating-only radiant panels can be electric or hydronic. Electric panels use heating wire or tape on the back side of the panel. Hydronic radiant ceiling panels are generally constructed of aluminum with copper tubing bonded to the back surface. Radiant heating/cooling systems are not appropriate for buildings with high ventilation needs, such as classroom buildings and laboratories.

15 Radiant cooling panels must be used in combination with ventilation air systems, which provide dehumidification and supplementary sensible cooling. Radiant heating/cooling panels is energy-efficient because of the reduced fan power for the supplementary ventilation systems. Also, the advantage of radiant heating panels is reduced transmission heat loss through building envelopes because the indoor air temperature can be maintained at a lower temperature Package Terminal Air Conditioners PTACs are window or through-wall units containing their own compressors and air-cooled condensers. PTACs are limited to room with outside exposure or suitable adjacent places to reject heat.

16 Heat Pumps The electric heat pump utilizes electrical energy to transport heat energy from the building exterior to the building interior The process is not an energy conversion process but rather a transfer process Types of Heat Pumps Air-to-Air Heat Pump Water-to-Air Heat Pump Water-to-Water Heat Pump Ground-Coupled Heat Pump

17 1) Air-to-Air Heat Pumps The most common type. Particularly suitable for factory-built unitary heat pumps. Widely used in residential and commercial applications. 2) Water-to-Air Heat Pumps Rely on water as the heat source and sink, and use air to transfer heat to, or from, the conditioned space

18 3) Water-to-Water Heat Pumps Use water as the heat source and sink for both cooling and heating. Heating-cooling changeover is usually done by switching the water circuits. 3) Ground-Coupled Heat Pumps Use the ground as a heat source and sink.

19 4.6 Economizer Cycle Economizer cycle is a AHU control method to save cooling energy by using cool outside air as a means of cooling the indoor space. When the enthalpy of the outside air is less than the enthalpy of the return air, conditioning the outside air is more energy efficient than conditioning the return air. Economizer cycle can reduce HVAC energy costs in cold and temperate climates while potentially improving IAQ, but are not appropriate in hot and humid climates. Economizer cycle can also be operated during nighttimes to cool indoor surfaces. 4.7 Energy Recovery Systems Run-Around Coil (4.7.1) Heat Pipe (4.7.2) Plate Heat Exchanger (4.7.3) Energy Transfer Wheel (4.7.4)

20 4.7.1 Run-Around Coil (sensible heat) The run-around coils are finned-tube copper coils placed in supply and exhaust airstreams. The coils of the run-around system are via piping, and a pump circulates water, glycol or other thermal fluid solution. The system utilizes the energy from the exhaust air stream to pre-condition the outdoor air. In summer, the exhaust air from the air-conditioned space cools the circulating fluid in the coil. The cooled fluid is then pre-cool the outdoor air. In winter, the process is reversed; heat is extracted from the exhaust air and then transferred to the make-up air. A high-performance, run-around energy exchanger can provide a large increase in overall HVAC system effectiveness from 50 percent to nearly 70 percent. Advantages This system does not require that the two air streams be adjacent to each other, several air streams can be used. It has relatively few moving parts - a small pump and control valve. There is no cross-contamination between air streams Heat Pipe (sensible heat) A heat pipe is a sealed self-contained, liquid evaporating and condensing system. It consists of evaporator and condenser sections. Hot air passes through the evaporator section and the cold air passes through the condenser side in a counter-flow arrangement. A typical heat pipe consists of a sealed pipe or tube made of a material with high thermal conductivity such as copper or aluminum at both hot and cold ends. A vacuum pump is used to remove all air from the empty heat pipe, and then the pipe is filled with a fraction of a percent by volume of working fluid (or coolant) chosen to match the operating temperature. Examples of such fluids include CFCs, water, ethanol, acetone, sodium, or mercury. The working fluid in HVAC system is normally Class I refrigerant (CFC). Heat is transferred from the hot incoming gas to the evaporator section of the heat pipe. The local vapor pressure of the evaporator section increases and evaporated fluid moves along the pipe to the condenser section. As the condenser section s temperature is low due to the cold air passing around it, the migrated vapor condenses and the heat is released to the cold air. The liquid then returns to the evaporator section by a combination of capillary action and gravity. Wick Copper tube

21

22 Advantages Passive Operation No energy input is required to operate the heat pipes. Long Life There is nothing in the heat pipes to wear out. The heat pipes are passive and have no moving parts. To guard against corrosion, the heat pipes can be ordered with a baked epoxy coating or other protective coating. Isolated Air Streams Dividing plates to separate the two air streams are an integral part of heat pipe heat recovery systems, assuring an excellent seal to prevent cross contamination.. Minimum Maintenance Since the Heat Pipes have no moving parts (apart from any dampers), the only maintenance recommended is periodic cleaning. A coil cleaner may be applied for this purpose just as for any cooling coil. Summer and Winter The same heat pipe can be used for both summer cooling and winter heat recovery without any changeover mechanism. The temperature difference between the air streams activates the energy recovery Plate Heat Exchanger (sensible heat) Two airstreams are separated by metal plates, which are usually augmented with fins. The heat exchange principle is simple: warm exhaust air heats a fixed plate, which, in turn, heats the incoming cool outdoor air on the other side of the plate. Two airstreams are separated by the plates to ensure no cross contamination. The effectiveness is a function of plate gaps and lengths, and air flow rate. A minimum effectiveness is 50%.

23 4.7.4 Energy Transfer Wheel (sensible heat and/or latent heat) Energy transfer wheel is a heat transfer device with a rotating wheel, which allows the sensible and/or latent heat transfer between the incoming outdoor air and exhaust air in an HVAC system. The air duct connections are arranged so that each of the airstreams flow axially through approximately one half of the wheel in a counter-flow pattern. Energy Transfer Wheel SENSIBLE WHEEL - This wheel is not coated with a desiccant and therefore transfers only sensible heat. The wheel can be constructed of almost any material (paper, metal or plastic) and transfers energy between two air streams as the mass of the material gains or loses heat to the opposite air stream. The wheel rotates at a speed of 25 to 50 revolutions per minute. ENTHALPY WHEEL - It is similar to the sensible wheel except that a desiccant material such as silica gel is coated to the wheel s surface. As the wheel rotates, it can transfer latent heat (moisture) as well as sensible heat simultaneously. This wheel also rotates at 25 to 50 revolutions per minute. The range of heat recovery effectiveness is 70% to 80%. Cross leakage through the energy recovery wheels ranges from 2% to 5% between the supply and exhaust air streams

24 Pre- heating and humidification of OA in winter Warm & Humidified RA From Room Warm & Humidified SA To Room Air Filter Energy Transfer Wheel Cooled & Dry EA Cold & Dry OA Hot Water From Boiler Air Filter OA Damper RA: Return Air SA: Supply Air EA: Exhaust Air OA: Outdoor Air Pre- cooling and dehumidification of OA in summer Air Filter Energy Transfer Wheel Cool & Dry RA From Room Cool & Dehumidified SA To Room Warm & Humid EA Hot& Humid OA Chilled Water From Chiller Air Filter OA Damper RA: Return Air SA: Supply Air EA: Exhaust Air OA: Outdoor Air

25 4.8 Controls and Automation Overview (4.8.1) Basic Control Systems and Devices (4.8.2) Building Energy Management, BMS (4.8.3) Overview Heating and cooling loads vary with time; therefore, the amount of heating or cooling supplied to a space must vary to keep the temperature and humidity within certain limit (comfort range). Controls and automation provide the intelligence of mechanical and electrical systems. Automation is the function of having equipment react, without any intervention of an operator, to satisfy preset conditions. Control occurs when a signal to the equipment cause the movement or adjustment of a component to produce the desired result.

26 4.8.2 Basic Control Systems and Devices The control systems in HVAC systems are designed to control the following properties of the energy transporting medium, such as air and water, and the related equipment. Temperature: with sensors set for an operating temperature, a differential, or temperature limits. Pressure: with sensors set for an operating pressure, a differential, or pressure limits. Flow rate: with sensors set for an operating rate, a differential, or flow rate limits. Humidity: with sensors set for an operating level, a differential, or humidity limits. Speed: with sensors to control the equipment so that it is either on or off or has variable or multiple speed Time: with a clock or a program to control the duration of operation of the equipment. 1) Basic Control Systems Control systems may be electric, electronic, pneumatic, direct digital, or a combination of these. Electric controls: Use line voltage (110 or 220V) or low voltage (12 to 24 V) to perform the basic function. A low-voltage control system is more sensitive and is preferred. Pneumatic controls: Use 5- to 30-psi (approximately 35 to 210 kpa) compressed air and receiver controllers with force-balance (usually springs) mechanism. Electronic controls: Use a similar form of controller, except that the signals are electronic rather than pneumatic. DDC controls: DDC system controllers contain microprocessors that are programmed to interpret the input signal, process the data in resident programs, and intelligently decide on the appropriate response.

27 2) Basic Control Devices The basic control devices include sensors, controllers, and actuators. Sensors: Measure the monitored or controlled variable. The signal from the sensors is input to a controller for processing and decision making. Controllers: Determine if a signal be sent to a monitoring station or to an actuator. The Controllers determine if the input or output signal is two-position or proportional, or direct- or reverse-acting. Actuators: Manipulate the equipment to meet the desired set point or the controlled variable.

28 Commonly used HVAC sensors: Thermostats: Sense and respond to temperature. Humidistats: sense and respond to humidity (either relative or absolute). Pressure sensors: sense and respond to pressure. Current sensors: sense and respond to electric current. Gas sensors: sense concentrations of CO and CO 2, and refrigerant Flow sensors: sense and respond to rates of flow Pneumatic Actuators

29 Electric Solenoid Actuators (on/off control) A typical electric solenoid consists of a coil, armature, spring, and stem. The coil is connected to an external current supply. The spring rests on the armature to force it downward. The armature moves vertically inside the coil and transmits its motion through the stem to the valve. When current flows through the coil, a magnetic field forms around the coil. The magnetic field attracts the armature toward the center of the coil. As the armature moves upward, the spring collapses and the valve opens. When the electric current stops, the magnetic field disappears. This allows the spring to expand and shut the valve. Electric Motorized Actuators (proportional control with position sensor)

30 Signals Two-position signals Input signals from sensors: indicate the operating status of the equipment (on/off, normal/alarm, open/close) Output signals from controllers: start/stop or open/close the controlled equipment. Proportional signals Monitor and control temperature or pressure, or flow. Provide multiple levels of control and alarm Building Energy Management System (BEMS) Building energy management is typically a function of the microprocessor-based DDC controllers. Automation and controls play a major role in managing a building s energy costs. In order to manage energy usage effectively, the controllers of the energy management system must be able to speak to one another. Addition of a local area network for dedicated communication among all controllers is the most common arrangement. The most basic option for managing energy is to shut down unnecessary equipment. Operating equipment at optimum conditions is another way to save energy. An excellent example is operating multiples of a single type of equipment. Energy can also be saved through monitoring demand and shutting down equipment to prevent consumption from exceeding a preset limit. Another method of energy management is to record equipment trend. By tracking the energy usage of the equipment, it is possible to identify when operations are outside the normal range, and then to perform the required maintenance.

31 Occupancy Sensor Systems Occupancy sensor system can be used to determine on/off control of HVAC operation to save unnecessary energy consumption. Configuration of a hierarchical control system

32 Intelligent Building System (IBS)

Heat pump and energy recovery systems

Heat pump and energy recovery systems SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air

More information

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort

More information

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return Single Zone System One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return Multi Zone System Used in small to medium sized buildings

More information

HVAC DISTRIBUTION and DELIVERY SYSTEMS

HVAC DISTRIBUTION and DELIVERY SYSTEMS HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 1) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 REMINDER HVAC = Heating, Ventilating, Air-Conditioning The AC part of HVAC implies a system that

More information

HVAC Mandatory Provisions Part II, Page 1

HVAC Mandatory Provisions Part II, Page 1 HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012 HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic VAV Systems One of the Systems Series July 2012 TRG-TRC014-EN VAV Systems One of the Systems Series A publication of Trane Preface VAV Systems A Trane Air Conditioning Clinic Figure

More information

Heat Recovery Units. Heat Recovery 1

Heat Recovery Units. Heat Recovery 1 Heat Recovery Units Heat Recovery 1 Heat Recovery Unit Why? A heat recovery unit (HRU) can help make mechanical ventilation more cost effective by reclaiming energy from exhaust airflows. HRUs use air-to-air

More information

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 2) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Contextual Reminder All-air systems Single zone Terminal reheat Multi-zone Dual-duct VAV Combinations

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

HVAC 101. H V A C S y s t e m s

HVAC 101. H V A C S y s t e m s H V A C 1 0 1 S y s t e m s Introduction & Overview Should you care? Mechanical System Types Components & operation Popular Application Key Issues and Design Considerations System Comparisons First Cost

More information

AHU Air Handling Unit Fundamentals. j.ilangumaran

AHU Air Handling Unit Fundamentals. j.ilangumaran AHU Air Handling Unit Fundamentals j.ilangumaran Objectives Review primary components of an AHU Understand the basic progression and advantages of advanced AHU control Understand the basic control sequences

More information

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline ME 414/514 HVAC Systems Overview Equipment Outline 2-1 The Complete System 2-2 The Air-Conditioning and Distribution System 2-3 Mechanical Equipment Air-handling Equipment Heating Equipment Boilers Furnaces

More information

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XIN INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning HVAC 101 The Basics of Heating, Ventilation and Air Conditioning HVAC Heating, Ventilation and Air Conditioning Provides comfort for people Allows humans to exist under adverse conditions. Comfort Comfort

More information

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled

More information

COMcheck Software Version Review Mechanical Compliance Certificate

COMcheck Software Version Review Mechanical Compliance Certificate COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Benefits Offered by Passive Dehumidification Wheel Speed Control

Benefits Offered by Passive Dehumidification Wheel Speed Control Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle

More information

Pharmaceutical Facility Design

Pharmaceutical Facility Design PhEn-602 Pharmaceutical Facility Design J. Manfredi Notes 9A PhEn-602 J. Manfredi 1 Primary & Secondary HVAC units Primary Primary air handling unit arrangement: One unit is responsible for all of the

More information

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling DES CHAMPS PRODUCTS Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling DES CHAMPS PRODUCTS Packaged Heat Recovery Systems Micro-Z

More information

2009 IECC Commercial Mechanical Requirements

2009 IECC Commercial Mechanical Requirements BUILDING ENERGY CODES UNIVERSITY 2009 IECC Commercial Mechanical Requirements Ken Baker PNNL-SA-66171 Learning(Objec-ves(( ( 1. Find(minimum(equipment(efficiency(requirements( and(recite(at(least(3(common(terms(for(measuring(

More information

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks DEHUMIDIFICATION: Ice Arena Application & Product Guide Design, construct and operate to control indoor humidity in ice rinks Munters is the world leader in dehumidification Munters is the largest manufacturer

More information

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS CARROLL COUNTY PUBLIC SCHOOLS LIFE CYCLE COST ANALYSIS SUMMARY DGS PROCEDURES FOR THE IMPLEMENTATION OF LIFE CYCLE COST ANALYSIS AND ENERGY CONSERVATION OCTOBER, 2010 G.A.I.#09090 GIPE ASSOCIATES, INC.

More information

August 15, 2013 Page 1 of 19

August 15, 2013 Page 1 of 19 Section C401 Application Compliance with C402, C403, C404 and C405 AND (either C406.2, C406.3 or C406.4) Compliance with C402, C403, C404 or C405 Section C402 Building Envelope (Climate Zone 5A) Space-Conditioning

More information

7. MECHANICAL SYSTEM DESIGN

7. MECHANICAL SYSTEM DESIGN 7. MECHANICAL SYSTEM DESIGN The second primary topic of this thesis is to investigate the application of a dedicated outdoor air system (DOAS) to the SLCC. The stated goals for this thesis of improved

More information

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview As in residential buildings the purpose of mechanical conditioning and ventilation is to maintain air quality and thermal comfort in buildings, with

More information

Summary Comparison of Simulation Program Features

Summary Comparison of Simulation Program Features Summary Comparison of Simulation Program Features FEATURE DOE2.2 equest TRACE 700 HAP Public/Proprietary Public Domain Proprietary Proprietary Proprietary Simulation Method 8760 hours 8760 hours 8760 hours

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Dehumidifying with Dedicated Outdoor Air

Dehumidifying with Dedicated Outdoor Air Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,

More information

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device DIVISION 23800 APPENDIX A ASHTABULA CAMPUS: 1. Air Handling Equipment And Appurtenances 2. Exhaust Fans 3. Fume Hood Exhaust Fans 4. Fume Hood monitoring devices and annual certification of face velocity

More information

Designing Energy Efficient Outdoor Air Systems

Designing Energy Efficient Outdoor Air Systems Designing Energy Efficient Outdoor Air Systems Joseph Thorndal Applied Products Sales Manager Greenheck, Schofield, Wisconsin 1 Joseph Thorndal BS Industrial Engineering North Dakota State University Work

More information

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

EADQUARTERS. Technical Report One. Stephanie Kunkel   Mechanical Option EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option

More information

2. CURRICULUM. Sl. No.

2. CURRICULUM. Sl. No. . CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration

More information

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION ENERGY EFFICIENT DEHUMIDIFICATION PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM Provides a very high degree of latent cooling using only a minimal amount of conventional cooling input Substantial energy

More information

College of Technological Studies Department of Power & Refrigeration Technology. Course Contents

College of Technological Studies Department of Power & Refrigeration Technology. Course Contents College of Technological Studies Department of Power & Refrigeration Technology Course Contents Course Designation: Air Conditioning Control systems Course No. : 272 0463 Credit Hrs.: 3 Lecture Hrs.: 2

More information

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Temperature. In the HVAC area, we talk about two kinds of temperatures. HEATING and COOLING HEATING and COOLING PSYCHROMETRIC CHART Temperature In the HVAC area, we talk about two kinds of temperatures. One is called dry bulb (DB) temperature, a fancy name for the reading

More information

COMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume

COMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume COMMERCIAL HVAC PACKAGED EQUIPMENT Rooftop Units Level 1: Constant Volume Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application

More information

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are

More information

ENGINEERING. Edition No. 13 October 2002

ENGINEERING. Edition No. 13 October 2002 Edition No. 13 October 2002 ENGINEERING S Y S T E M S O L U T I O N S W e at McQuay are very proud of our tradition of producing industry leading water source heat pumps. Our heritage stretches back more

More information

Technical Development Program

Technical Development Program Technical Development Program PRESENTED BY: James Parker Insert your logo here AIR HANDLERS Coils: Direct Expansion Chilled Water and Heating Menu Section 1 Introduction Section 2 Typical Coil Applications

More information

COMMERCIAL HVAC EQUIPMENT Coils: Direct Expansion, Chilled Water, and Heating

COMMERCIAL HVAC EQUIPMENT Coils: Direct Expansion, Chilled Water, and Heating COMMERCIAL HVAC EQUIPMENT Coils: Direct Expansion, Chilled Water, and Heating Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

Flexible & Innovative. Cooling Solutions

Flexible & Innovative. Cooling Solutions Flexible & Innovative Cooling Solutions Flexible & Innovative Compu-Aire Inc. offers a variety of high performance precision cooling systems that can adapt to your application needs. With today s rapidly

More information

Comfort and health-indoor air quality

Comfort and health-indoor air quality Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental

More information

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 3.8.2 Mechanical Compliance Certificate 90.1 (2007) Standard Section 1: Project Information Project Type: New Construction Project Title : Rudy's Star Motors Construction Site:

More information

INDEX. ADDITIONS AND ALTERATIONS Defined Requirements ADMINISTRATION AND ENFORCEMENT... Chapter 1 AIR ECONOMIZERS

INDEX. ADDITIONS AND ALTERATIONS Defined Requirements ADMINISTRATION AND ENFORCEMENT... Chapter 1 AIR ECONOMIZERS A ADDITIONS AND ALTERATIONS Requirements........................ 101.4.3 ADMINISTRATION AND ENFORCEMENT..................... Chapter 1 AIR ECONOMIZERS Defined.................................202 Requirements........

More information

Relative Humidity in Schools Jim Cummings and Chuck Withers

Relative Humidity in Schools Jim Cummings and Chuck Withers to Co n tr o l Relative Humidity in Schools Jim Cummings and Chuck Withers SEEC Southern Energy-Efficiency Center Energy Efficient Strategies to Control Relative Humidity in Schools James Cummings and

More information

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM 551B 581B DuraPac Plus Series Sizes 036-150 3to12 1 / 2 Tons Cancels: New PAD 551B.36.2 10/1/04 CONTENTS Page INTRODUCTION.................................

More information

EP SERIES PACKAGED ENERGY RECOVERY SYSTEM ENERGY EFFICIENT AIR COMFORT

EP SERIES PACKAGED ENERGY RECOVERY SYSTEM ENERGY EFFICIENT AIR COMFORT ENERGY EFFICIENT AIR COMFORT EP SERIES PACKAGED ENERGY RECOVERY SYSTEM Certified total energy recovery performance (sensible and latent) up to 90% efficient. Double-wall panel construction eliminates exposed

More information

Energy Recovery with Cooling and Heating Model ERCH

Energy Recovery with Cooling and Heating Model ERCH Energy Recovery with Cooling and Heating Model ERCH 100% Outdoor Air System Dedicated Outdoor Air System 1,000-10,000 cfm 1.75 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating,

More information

H O B O K E N R E S I D E N T I A L

H O B O K E N R E S I D E N T I A L Proposal 1: Open Loop Geothermal for Water Source Packaged Terminal Heat Pumps and Heat Recovery Ventilation and Humidifier Heating and Cooling System Schematic Ventilation Schematic Proposal 1 System

More information

Trane CDQ Desiccant Dehumidification

Trane CDQ Desiccant Dehumidification Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features

More information

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs Lesson 1 - Basic Heat Pump Theory (Part 1) Describe the basic operation of a heat pump. Explain the function of various heat pump controls. Interpret the wiring diagrams and performance data provided by

More information

Appendix A. Glossary of Common Terms

Appendix A. Glossary of Common Terms Glossary of Common Terms Glossary of Common Terms Absorption chiller A refrigeration machine using heat as the power input to generate chilled water. Adjustable speed drive A means of changing the speed

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series. RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities

More information

Design Options For HVAC Distribution System. Course Content

Design Options For HVAC Distribution System. Course Content Design Options For HVAC Distribution System Course Content CENTRAL HVAC SYSTEM AN OVERVIEW The objective of an HVAC (heating, ventilating, and air-conditioning) system is to control the temperature, humidity,

More information

Power and Energy Management Solutions

Power and Energy Management Solutions Selection Guide Power and Energy Management Solutions Heating, Ventilating and Air Conditioning (Bulletin 1414) Selection Guide 2 HVAC Selection Guide Instrumentation Selection Checklist Use the following

More information

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.

More information

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated

More information

The ultimate fresh air solution.

The ultimate fresh air solution. Fresh Access The ultimate fresh air solution. Introducing Fresh Access TM. Expertly designed, our innovative energy recovery ventilator (ERV) unit, split dedicated outside air system (DOAS), and packaged

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Vapor-Compression Refrigeration

Vapor-Compression Refrigeration Vapor-Compression Refrigeration condenser D C expansion device compressor A B evaporator Types of Heat Pumps water-source heat pumps water-to-water heat pump air-source heat pumps Cooling Heating

More information

SESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members:

SESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members: SESSION 1-2015 Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE (90.1.2013) ASHRAE Detroit Members: AM Session is eligible for (X) Professional Development

More information

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,

More information

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating Rooftop Ventilator with Packaged Cooling & Heating Models RV and RVE Institutional Commercial Industrial 800-1,500 cfm.0 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating Packaged

More information

MECHANICAL SERVICES 101. Ian White

MECHANICAL SERVICES 101. Ian White MECHANICAL SERVICES 101 Ian White Contents 1. Ventilation 2. Heat Gains & Losses 3. Heating Ventilation Air Conditioning (HVAC) Systems What are Building Services Building Services incorporate all aspects

More information

APPLICATION GUIDE BEAMS

APPLICATION GUIDE BEAMS BEAMS There is an increasing need for energy efficient air conditioning systems as energy codes become more stringent. Chilled beam systems are one such alternate to traditional all air conditioning systems.

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

DX Units. Ranging from 15 to 750 tons and 1,000 to 300,000+ CFM

DX Units. Ranging from 15 to 750 tons and 1,000 to 300,000+ CFM D Units Ranging from 15 to 750 tons and 1,000 to 300,000+ CFM INDUSTRY-LEADING HVAC MANUFACTURER Nortek Air Solutions is the largest custom HVAC manufacturer in North America, with a combined total of

More information

b.) Technical Information:

b.) Technical Information: Section VI- Strategies a.) Summary: It is important for new construction designers to consider the heating, ventilation, and air conditioning needs within a building. There are many different systems,

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Buda, Texas 2a New Construction Construction

More information

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...

More information

General Notes. See V sheets for scope of work details on thermostats, terminal units, air handling units and exhaust fans. Abbreviations: T.C.C. = Temperature Controls Contractor, M.C. = Mechanical Contractor.

More information

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks Ventilation Heat Recovery PoolPak International Maintaining Your Climate for Indoor Pools and Waterparks Complete Ventilation, Heat Recovery and Dehumidification Packaged System by PoolPak International

More information

100% Outdoor Air Dehumidification Methods

100% Outdoor Air Dehumidification Methods Technical Bulletin 16 100% Outdoor Air ehumidification Methods I NTROUCTION As consulting engineers and end users implement the ASHRAE 6 ventilation code, they are faced with selecting an appropriate method

More information

Control Systems. Design & Manufacturing. Eco-Friendly. High Performance

Control Systems. Design & Manufacturing. Eco-Friendly. High Performance Temperature & Humidity Control Systems Design & Manufacturing DX Air / Water / Glycol Cooled Air and Water Side Economizer Chilled Water Systems Eco-Friendly High Performance OPTIMAL COOLING SOLUTIONS

More information

Are uncontrollable humidity problems costing you a bundle?

Are uncontrollable humidity problems costing you a bundle? HOT GAS REHEAT OPTION Are uncontrollable humidity problems costing you a bundle? Why put up with humidity problems when you can have true climate control with the installation of an FHP water source heat

More information

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN Introduction to HVAC Agenda Psychrometrics Human Comfort Heat Transfer Refrigeration Cycle HVAC Terminology HVAC Systems Introduction to HVAC Psychrometrics 2000 TRG-TRC002-EN Properties of Air Dry-bulb

More information

Technical Assignment 3 11/15/04. Executive Summary

Technical Assignment 3 11/15/04. Executive Summary Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria

More information

AHRI Certification Program Scopes - COOLING

AHRI Certification Program Scopes - COOLING Air-to-Air Energy Recovery Ventilators (AHRI Std. 1060) Automatic Commercial Ice-Cube Machines and Ice Storage Bins (AHRI Stds. 810 & 820) Central Station Air-Handling Units (AHRI Std. 430) Commercial

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Air-Cooling Evaporators

Air-Cooling Evaporators Air-Cooling Evaporators Types of construction Circuit Configurations Methods of Refrigerant Feed Methods of Air Circulation Methods of Defrost Type of Construction Bare tube Finned Tube Plate-surface Bare

More information

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the

More information

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1 Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things

More information

Custom Air Handler Solutions Custom Units to Meet Your Unique Design Needs

Custom Air Handler Solutions Custom Units to Meet Your Unique Design Needs Custom Units to Meet Your Unique Design Needs Engineered for flexibility and performance Contents Horizontal Configuration....1 Horizontal with Standard Economizer Configuration...2 Stacked Configuration...3

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

Liquid Desiccant Air Conditioning Systems

Liquid Desiccant Air Conditioning Systems Liquid Desiccant Air Conditioning Systems High-Efficiency Industrial Dehumidification High-Efficiency External Air Dehumidification Energy-Efficient Heat Pump Drying For Industries Use Only www.ascsciences.com

More information

DES CHAMPS PRODUCTS 85% 4,400 CFM

DES CHAMPS PRODUCTS 85% 4,400 CFM DES CHAMPS PRODUCTS Saves up to 85% of the heat from exhaust airstream Removes pollutants before they accumulate Transfers heat energy in winter/cool energy in summer Low cost Capacities up to 4,400 CFM

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information