1 NFPA 54 UPDATE Paul Cabot American Gas Association

2 PRESENTATION TOPICS Summary Listing Schedule Revisions Definitions/General Piping Appliances and Appliance Installation Venting

3 2015 Edition Revision Status ANSI Approval 8/14 Publication 9/14

4 / IFGC Identifies Code(s) Impacted by Change Presentation Slide Format Sample deleted text Sample added text. Strikethrough denotes deleted text Underlined text is what is new/added text

5 Definitions DELETED: Air Shutter Nonresidential Low-Heat Appliance Medium-Heat Appliance Low Pressure Boiler Consumption Design Certification Vent Damper Device Domestic Laundry Stove Hot Taps Leak Check Pressure Test Regulator Vent Thermostat All of Annex J Other Useful Terms REVISED: Combustible Dampers: Electrically Operated Mechanically Actuated Thermally Actuated High-Static Pressure Low-Static Pressure Noncombustible Vent

6 General Requirements NEW - Prevention of Accidental Ignition Potential Ignition Sources. Where work is being performed on piping that contains or has contained gas, the following shall apply: (1) Provisions for electrical continuity shall be made before alterations are made in a metallic piping system. (2) Smoking, open flames, lanterns, welding, or other sources of ignition shall not be permitted. (3) A metallic electrical bond shall be installed around the location of cuts in metallic gas pipes made by other than cutting torches. Where cutting torches, welding, or other sources of ignition are to be used, it shall be determined that all sources of gas or gas air mixtures have been secured and that all flammable gas or liquids have been cleared from the area. Piping shall be purged as required in Section 8.3 before welding or cutting with a torch is attempted. (4) Artificial illumination shall be restricted to listed safety-type flashlights and safety lamps. Electric switches shall not be turned on or turned off.

7 Piping System Design Calculating Maximum Demand Table moved to Annex A 5.4.2* Maximum Gas Demand * The volumetric flow rate of gas to be provided [in cubic feet (cubic meters) per hour] shall be calculated using the manufacturers input ratings the sum of the maximum input of the appliances served, adjusted for altitude. Where the input rating is not indicated, the gas supplier, appliance manufacturer, or a qualified agency shall be contacted, or the rating from Table shall be used for estimating the volumetric flow rate of gas to be supplied. Altitude adjustment to new

8 Piping System Design NEW - Annex A Sizing Guidance A Some older appliances do not have a nameplate. In this case Table A or an estimate of the appliance input should be used. The input can be based on: A rating provided by the manufacturer, The rating of similar appliances, Recommendations of the gas supplier, Recommendations of a qualified agency, A gas flow test. Measurement of the orifice size of the appliance. The requirement of that the piping system provide sufficient gas to each appliance inlet must be complied with.

9 / IFGC Piping Materials NEW- Prohibition on PVC & CPVC for fuel gas piping Polyvinyl chloride (PVC) and cholorinated polyvinyl chloride (CPVC) plastic pipe, tubing, and fittings shall not be used to supply fuel gas.

10 / IFGC Piping System Design REVISED - Fittings Metallic Pipe Fittings. Metallic fittings shall comply with the following: (1) Threaded fittings in sizes larger than 4 in. (100 mm) shall not be used unless acceptable to the authority having jurisdiction. AHJ approval dropped

11 / IFGC Piping System Design NEW Fitting Drill and Tapped (9) When pipe fittings are drilled and tapped in the field, the operation shall be in accordance with the following: (a) The operation shall be performed on systems having operating pressures of 6 psi or less. (b) The operation shall be performed by the gas supplier or their designated representative. (c) The drilling and tapping operation shall be performed in accordance with written procedures prepared by the gas supplier. (d) The fittings shall be located outdoors. (e) The tapped fitting assembly shall be in inspected and proven to be free of leaks.. Meet all of the following: - 6 psi or less - Only by gas supplier - Supplier s procedures - Outdoors - Inspected

12 / IFGC Piping Materials REVISED Throughout the Code * Copper and Brass Copper Alloy. Copper and brass copper alloy pipe shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 scf of gas (0.7 mg/100 L). Brass is now Copper Alloy

13 / IFGC Piping Materials REVISED - Acceptable Flanges All Applicable Flanges Added Flanges Flange Specifications. All flanges shall comply with Cast iron flanges shall be in accordance with ANSI/ASME B16.1, Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250, Steel flanges shall be in accordance with the following: ASME/ANSI B16.5, Pipe Flanges and Flanged Fittings: NPS ½ through NPS 24 Metric/Inch Standard, or ASME/ANSI B16.47, Large Diameter Steel Flanges: NPS 26 through NPS 60 Metric/Inch Standard Non-Ferrous Flanges shall be in accordance with: ASME/ANSI B16.24, Cast Copper Alloy Pipe Flanges and Flanged Fittings: Classes 150, 300, , 1500, and Ductile Iron Flanges shall be in accordance with: ASME/ANSI B16.42, Ductile Iron Pipe Flanges and Flanged Fittings, Classes 150 and Dissimilar Flange Connections. Raised Face flanges shall not be joined to Flat Faced Cast Iron, Ductile Iron or Non-Ferrous material flanges, ANSI/ASME B16.20, Metallic Gaskets For Pipe Flanges: Ring-Joint, Spiral-Wound and Jacketed; or MSS SP-6, Standard Finishes for Contact Faces of Pipe Flanges and Connecting-End Flanges of Valves and Fittings. The pressure-temperature ratings shall equal or exceed that required by the application.

14 / IFGC Piping Materials REVISED - Acceptable Gaskets Acceptable materials shall include the following: (1) Metal (plain or corrugated) (2) Composition (3) Aluminum O rings and All Applicable Gasket Materials Added (4) Sspiral-wound metal gaskets (5) Rubber-faced phenolic (6) Elastomeric Gasket Specifications When a flanged joint is opened, the gasket shall be replaced Metallic flange gaskets shall be in accordance with ANSI/ASME B16.20, Metallic Gaskets For Pipe Flanges: Ring-Joint, Spiral-Wound and Jacketed Non-metallic flange gaskets shall be in accordance with ASME/ANSI B16.21, Nonmetallic Flat Gaskets for Pipe Flanges Full-face flange gaskets shall be used with all bronze and cast-iron non-steel flanges When a flanged joint is opened, the gasket shall be replaced.

15 / IFGC Overpressure Protection REVISED Extensive rewrite 5.9 Overpressure Protection Devices General Where Required. Overpressure protection devices shall be provided to prevent the pressure in the piping system from exceeding that value that would cause unsafe operation of any connected and properly adjusted appliances. Where the serving gas supplier delivers gas at a pressure greater than 2 psi for piping systems serving appliances designed to operate at a gas pressure of 14 in. wc or less, overpressure protection devices shall be installed. Piping systems serving equipment designed to operate at inlet pressures greater than 14 in. wc shall be equipped with overpressure protection devices as required by the appliance manufacturer s installation instructions. Protection required where supply pressure is greater than 2 psi and Appliances or equipment are designed to operate at 14 inches or less.

16 / IFGC Excess Flow Valves New EFV Listing Standard 5.13 Excess Flow Valve(s). Where automatic excess flow valves are installed, they shall be ANSI Z21.93/CSA 6.30, Excess Flow Valves for Natural and LP-Gas With Pressures Up To 5 psig, and shall be sized and installed in accordance with the manufacturers' instructions.

17 / IFGC Piping Tables Table entries rounded off to 3 significant digits 4 in. Column Capacity Corrections

18 Corrosion Protection REVISED - Rewrite of requirements 7.1.3* Protection Against Corrosion Corrosion Protection of Piping. Gas piping in contact with earth or other material that could corrode the piping shall be protected against corrosion. When dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. Uncoated threaded or socket welded joints shall not be used in contact with soil or where internal or external crevice corrosion is known to occur. Steel pipe and steel tubing installed underground shall be installed in accordance with the through Coverage limited to steel pipe and tubing

19 Corrosion Protection No protection required if soils not corrosive or for other technical reasons Underground piping must be: 1. Stainless 2. Factory coated 3. Have cathodic protection Underground piping shall comply with one or more of the following unless approved technical justification is provided to demonstrate that protection is unnecessary: (A) The piping shall be made of corrosion-resistant material that is suitable for the environment in which it will be installed. (B) Pipe shall have a factory-applied, electricallyinsulating coating. Fittings and joints between sections of coated pipe shall be coated in accordance with the coating manufacturer's instructions. (C) The piping shall have a cathodic protection system installed and the system shall be maintained in accordance with or

20 Piping Installation Tracer Systems Allows Designed Systems Tracer Wire. An electrically continuous corrosion-resistant tracer wire (minimum AWG 14) or tape shall be buried with the plastic pipe to facilitate locating. One The tracer shall be one of the following: 1. A product specifically designed for that purpose 2. Insulated copper conductor not less than 14 AWG Where tracer wire is used, access shall be provided from aboveground or one end of the tracer wire or tape shall be brought aboveground at a building wall or riser.

21 / IFGC Piping Installation NEW- Bond to lightning protection system REVISED - Bond connection anywhere on system NEW- Bond length not to exceed 75 Ft. NEW- Connection in accordance with NFPA 70 and use UL device * CSST. CSST gas piping systems and gas piping systems containing one or more segments of CSST, shall be bonded to the electrical service grounding electrode system or where provided, lightning protection grounding electrode system The bonding jumper shall connect to a metallic pipe or fitting between the point of delivery and the first downstream, pipe fitting, or CSST fitting The bonding jumper shall not be smaller than 6 AWG copper wire or equivalent. Gas piping systems that contain one or more segments of CSST shall be bonded in accordance with this section The length of the jumper between the connection to the gas piping system and the grounding electrode system shall not exceed 75 ft (22 m). Any additional electrodes shall be bonded to the electrical service grounding electrode system or where provided, lightning protection grounding electrode system Bonding connections shall be in accordance with NFPA 70, National Electrical Code Devices used for the bonding connection shall be listed for the application in accordance with UL 467, Grounding and Bonding Equipment.

22 Piping Installation Bond to lightning protection system Clamp coverage delete since a listed clamp is required Provide research study reference and other equivalent bond wires allowed A The required bonding connection may be made from the piping to the electrical service equipment enclosure, to the grounded conductor at the electrical service, to the grounding electrode conductor (where of sufficient size), or directly to the grounding electrode. The bond may also be made to a lightning protection system grounding electrode (but not to down conductors) if the resulting length of the bonding conductor is shorter. Lightning protection grounding systems are bonded to the electrical service grounding electrodes in accordance with NFPA 780 using a method to minimize impedance between the systems. Listed clamps are manufactured to facilitate attachment of the bonding conductor to either a segment of rigid pipe or to a CSST brass copper alloy fitting. Clamps should be installed so as to remain accessible when building construction is complete. Clamps should be suitable for the location where they will be installed. Bonding conductors should be protected from physical damage and can be installed outdoors above grade or below grade or can be installed indoors. The maximum length of the bonding connection was established based on studies conducted by the Gas Technology Institute in Project Number 21323, Validation of Installation Methods for CSST Gas Piping to Mitigate Indirect Lightning Related Damage. The shortest practical length should always be used. State and local laws can limit who can attach the bonding connection to the building grounding system. The size of the bonding conductor, a 6 AWG copper wire, is a minimum and larger wire can be used. The requirement also permits conductors of different materials (of equivalent size) and both single wire and multi-strand.

23 Piping Installation Concealed Fittings Fittings in Concealed Locations. Fittings installed in concealed locations shall be limited to the following types: (1) Threaded elbows, tees, and couplings, caps and plugs (2) Brazed fittings (3) Welded fittings (4) Fittings listed to ANSI LC 1/CSA 6.26, Fuel Gas Piping Systems Using Corrugated Stainless Steel Tubing (CSST), or ANSI LC 4, Press-Connect Copper and Copper Alloy Fittings for Use in Fuel Gas Distribution Systems Allows caps and plugs

24 Shutoff Valves Shutoff Valves in Tubing Systems. Shutoff valves in tubing systems in concealed locations shall be rigidly and securely supported independently of the tubing. Requires Support for Valves on Tubing Systems

25 Repair Garages In accordance with NFPA 30A Repair Garages. Appliances installed in repair garages shall be installed in a detached building or room, separated from repair areas by walls or partitions, floors, or floor ceiling assemblies that are constructed so as to prohibit the transmission of vapors and that have a fire resistance rating of not less than 1 hour, and that have no openings in the wall separating the repair area within 8 ft (2.4 m) of the floor. Wall penetrations shall be firestopped. Air for combustion purposes shall be obtained from the outdoors. The heating room shall not be used for the storage of combustible materials. Exception No. 1: Overhead heaters where installed not less than 8 ft (2.4 m) above the floor shall be permitted. Exception No. 2: Heating appliances for vehicle repair areas where there is no dispensing or transferring of Class I or Class II flammable or combustible liquids or LP- Gas shall be installed in accordance with NFPA 30A, Code for Motor Fuel Dispensing Facilities and Repair Garages.

26 Z223 ONLY Existing Appliances Building Envelope Changes Weatherization * Existing Appliances. Where an existing appliance is located within the conditioned space of an existing building envelope and where a building envelope component, other than roofing material, is replaced or altered, the appliance installations shall be inspected to verify compliance with the provisions of 9.3 and Chapter 12. Where the appliance installations do not comply with 9.3 and Chapter 12, it shall be altered as necessary to be in compliance with such. Verify Combustion Air and Venting

27 Existing Appliances- Annex G Complete rewrite Applies to Most Appliances

28 Existing Appliances Annex G Procedures include: Instrumentation Safety Piping & Connections Appliances Standby & Operating Venting Combustion Air G.1 General. G.1.1 Application. G.1.2 Weatherization Programs. G.1.3 Inspection Procedure. G.1.4 Manufacturer Instructions. G.1.5 Instruments.. (1) Gas Detector: (2) CO Detector: G.2 Occupant and Inspector Safety. G.3 Gas Piping and Connection Inspections (1) Leak Checks. (2) Appliance Connector. (3) Piping Support. (4) Bonding. G.4 Inspections to be performed with the Appliance Not Operating. (1) Preparing for Inspection. (2) Vent System Size and Installation. (3) Combustion Air Supply. I (4) Flooded Appliances. (5) Flammable Vapors. (6) Clearances to Combustibles. (7) Appliance Components. (8) Placing Appliances Back in Operation. G.5 Inspections to be performed with the Appliance Operating. G.5.1 General Appliance Operation. (1) Initial Startup. (2) Flame Appearance. (3) Appliance Shutdown. G.5.2 Test for Combustion Air and Vent Drafting for Natural Draft and Category I Appliances. (1) Preparing for Inspection. (2) Placing the Appliance in Operation. (3) Spillage Test. G.6 Appliance-Specific Inspections. (1) Forced Air Furnaces: (2) Boilers: (3) Water Heaters: (4) Cooking Appliances (5) Vented Room Heaters (6) Vent-Free Heaters (7) Gas Log Sets and Gas Fireplaces (8) Gas Clothes Dryer

29 Existing Appliances - Annex G Annex G Appliance Threshold Table

30 / IFGC Combustion Air REVISED Does not apply to power burner appliances Appliances of other than natural draft design and other than, appliances not designated as Category I vented appliances, and appliances equipped with power burners shall be provided with combustion, ventilation, and dilution air in accordance with the appliance manufacturer s instructions.

31 Connecting Appliances Connecting Appliances and Equipment. Appliances and equipment shall be connected to the building piping in compliance with through by one of the following: (1) (2) (3) (4) (5) (6)... Clarify that these sections also apply Relocated as new standalone sections & (7) In (2), (3), (4), (5), and (6), the connector or tubing shall be installed so as to be protected against physical and thermal damage. Aluminum alloy tubing and connectors shall be coated to protect against external corrosion where they are in contact with masonry, plaster, or insulation or are subject to repeated wettings by such liquids as water (except rain water), detergents, or sewage. Materials addressed in (2), (3), (4), (5), and (6) shall not be installed through an opening in an appliance housing, cabinet, or casing, unless the tubing or connector is protected against damage. (8) Unlisted gas hose connectors for use in laboratories and educational facilities in accordance with New coverage for UNLISTED gas hoses in labs

32 Connecting Appliances Injection (Bunsen) burners used in laboratories and educational facilities shall be permitted to be connected to the gas supply by an unlisted hose. Permits UNLISTED gas hoses in labs

33 Specific Appliances Clearances around Cooking Tops Combustible Material Adjacent to Cooking Top. Any portion of combustible material adjacent to a cooking top section of a food service range, even though listed for close-to-wall installation, that is not shielded from the wall by a high shelf, warming closet, and so on, shall be protected as specified in for a distance of at least Listed and unlisted food service ranges shall be installed to provide clearance to combustible material of not less than 18 in. (460 mm) horizontally for a distance up to 2 ft (0.6 m) above the surface of the cooking top where the combustible material is not completely shielded by high shelving, warming closet, or other system. Reduced combustible material clearances are permitted where protected in accordance with Table Existing coverage is rewritten to clarify.

34 Specific Appliances Hot Plates & Laundry Stoves Hot Plates and Laundry Stoves Listed domestic hot plates and laundry stoves installed on combustible surfaces shall be set on their own legs or bases. They shall be installed with minimum horizontal clearances of 6 in. (150 mm) from combustible material Unlisted domestic hot plates and laundry stoves shall be installed with horizontal clearances to combustible material of not less than 12 in. (300 mm). Combustible surfaces under unlisted domestic hot plates and laundry stoves shall be protected in an approved manner The vertical distance between tops of all domestic hot plates and laundry stoves and combustible material shall be at least 30 in. (760 mm). New appliances no longer available.

35 Specific Appliances Household Cooking Appliances Floor-Mounted Units Installation. Listed floor-mounted and built-in household cooking appliances shall be installed in accordance with the manufacture s installation instructions Clearance from Combustible Material Clearances. The clearances specified as follows shall not interfere with combustion air, accessibility for operation, and servicing: (1) Listed floor-mounted household cooking appliances, where installed on combustible floors, shall be set on their own bases or legs and shall be installed in accordance with the manufacturer's installation instructions. (2) Listed household cooking appliances with listed gas room heater sections shall be installed so that the warm air discharge side shall have a minimum clearance of 18 in. (460 mm) from adjacent combustible material. A minimum clearance of 36 in. (910 mm) shall be provided between the top of the heater section and the bottom of cabinets. (3) Listed household cooking appliances that include a solid or liquid fuel burning section shall be spaced from combustible material and otherwise installed in accordance with the manufacturer's installation instructions for the supplementary fuel section of the appliance. Outdated appliance deleted (4) (3) Unlisted floor-mounted household cooking appliances shall be installed with at least a 6 in. (150 mm) clearance at the back and sides to combustible material. Combustible floors under unlisted appliances shall be protected in an approved manner. (4) Unlisted built-in household cooking appliances shall not be installed in, or adjacent to, unprotected combustible material. Floor-mounted and built-in units combined.

36 Specific Appliances Household Cooking Appliances New Annex A figure added * Vertical Clearance Above Cooking Top. Household cooking appliances shall have a vertical clearance above the cooking top of not less than 30 in. (760 mm) to combustible material or metal cabinets. A minimum clearance of 24 in. (610 mm) is permitted when one of the following is installed: (1) The underside of the combustible material or metal cabinet above the cooking top is protected with not less than 1 4 in. (6 mm) insulating millboard covered with sheet metal not less than in. (0.3 mm) thick. (2) A metal ventilating hood of sheet metal not less than in. (0.3 mm) thick is installed above the cooking top with a clearance of not less than 1 4 in. (6 mm) between the hood and the underside of the combustible material or metal cabinet, and the hood is at least as wide as the appliance and is centered over the appliance. (3) A listed cooking appliance or microwave oven is installed over a listed cooking appliance and conforms to the terms of the upper appliance s manufacturer s installation instructions Level Installation. Cooking appliances shall be installed so that the cooking top, broiler pan, or oven racks are level. Floor-mounted and built-in units combined.

37 Specific Appliances Household Cooking Appliances Figure A

38 / IFGC Venting Plastic pipe used in venting systems Plastic Piping. Plastic Where plastic piping is used for venting appliances listed for to vent an appliance, the appliance shall be listed for use with such venting materials shall be approved and the appliance manufacturer's installation instructions shall identify the specific plastic piping material. Instructions must ID specific plastic AHJ approval is removed

39 / IFGC Venting Sizing of Category II, III & IV Vents Category II, Category III, and Category IV Appliances. The sizing of gas vents for Category II, Category III, and Category IV appliances shall be in accordance with the appliance manufacturer's instructions. The sizing of plastic pipe specified by the appliance manufacturer as a venting material for Category II, III and IV appliances shall be in accordance with the appliance manufacturers' instructions. Added since the vent definition does not cover plastic vents

40 2018 Edition Revision Status Open for Public Input Due Date: July 6th 2018 Use NFPA Online Proposal System

41 Questions Paul Cabot American Gas Association

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. PIPING Various Brass REVISED

More information

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND ADMINISTRATION ADMINISTRATION 301.1.2 LP-Gas installations. Whenever there is a conflict between this code and NFPA 54 and B+NFOA 58 as adopted by the Nevada LP-Gas

More information

CSST Installation Requirements in the Fuel Gas Codes

CSST Installation Requirements in the Fuel Gas Codes CSST Installation Requirements in the Fuel Gas Codes Paul Cabot American Gas Association Course Description Correct gas pipe sizing, installation, and appliance connections are vital steps that help ensure

More information

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. 1.1.1.1 (B), (C), & (D)

More information

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev This fact sheet provides an overview of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. These revisions are published

More information

Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition

Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition Reference: Various Errata Z223.1-2015-1 Issue Date: 3/10/16 National Fuel Gas Code user: The American Gas Association (AGA) notes the following errors

More information

The following preprint is based on the First Revision Draft of the 2018 edition of NFPA 54/Z223.1.

The following preprint is based on the First Revision Draft of the 2018 edition of NFPA 54/Z223.1. Copyright 2016 by American Gas Association and the National Fire Protection Association, All Rights Reserved BSR Z223.1 20xx NFPA 54 20xx National Fuel Gas Code 2018 Edition NOTE: This preprint of the

More information

ASC Z223 SECOND PUBLIC REVIEW DRAFT

ASC Z223 SECOND PUBLIC REVIEW DRAFT Copyright 2016 by American Gas Association and the National Fire Protection Association, All Rights Reserved BSR Z223.1 20xx NFPA 54 20xx National Fuel Gas Code 2018 Edition ASC Z223 SECOND PUBLIC REVIEW

More information

Mechanical Appliance and Equipment Inspection Checklist

Mechanical Appliance and Equipment Inspection Checklist 34 2015 IRC Performing Residential Mechanical s Mechanical Appliance and Equipment Checklist Inspect Mechanical Appliance and Equipment Comments / I. Identify possible mechanical appliance and equipment

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

2012 INTERNATIONAL FUEL GAS CODE VENTS

2012 INTERNATIONAL FUEL GAS CODE VENTS 2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with

More information

C O D E S & A M M E N D M E N T S

C O D E S & A M M E N D M E N T S SEVIER COUNTY UTILITY DISTRICT SEPTEMBER 2, 2014 Sevier County Utility District has adopted the 2009 International Fuel Gas Code for gas inspections. The following pages contain frequently used codes and

More information

First Revision No. 82-NFPA [ Detail ] Submitter Information Verification Submitter Full Name: Organization:

First Revision No. 82-NFPA [ Detail ] Submitter Information Verification Submitter Full Name: Organization: of 176 1/25/2016 3:32 PM First Revision No. 82-NFPA 54-2015 [ Detail ] Title of 7.1: Installation of Underground Piping. Underground Title of 7.2: Installation of Aboveground Piping. Submittal Date: Thu

More information

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Changes to the Florida Building Code, Fuel-Gas This Analysis of Changes for the 5 th Edition (2014) of the Florida Codes is intended

More information

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS. Part I Administrative... 1 Part I Administrative............................ 1 CHAPTER 1 Deleted Part II Definitions.............................. 3 CHAPTER 2 DEFINITIONS.................... 3 R201 General..................................

More information

NATURAL GAS PIPING

NATURAL GAS PIPING SECTION 15496 - NATURAL GAS PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FUEL GAS CODE 2009 EDITION.

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FUEL GAS CODE 2009 EDITION. CHAPTER 23.110 LOCAL AMENDMENTS TO THE INTERNATIONAL FUEL GAS CODE 2009 EDITION. 23.110.100 Local amendments to the International Fuel Gas Code, 2009 Edition. 23.110.101.2 Scope. 23.110.103 23.110.110.

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

Inspection Checklist Mechanical Rough in

Inspection Checklist Mechanical Rough in Property Owner Name: Property Address: Permit Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans are on site and

More information

CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL

CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL 101.1 Title. These regulations shall be known as the North Carolina Fuel Gas Code as adopted by the North Carolina Building Code Council on March 11,

More information

2012 International Fuel Gas Code Design, Installation and Inspection Principles

2012 International Fuel Gas Code Design, Installation and Inspection Principles Overview 2012 International Fuel Gas Code Design, Installation and Inspection Principles Based on the 2012 International Fuel Gas Code Administration Definitions General regulations Gas piping installations

More information

4.3 Installing Appliances and Interior Vapor Distribution Systems Performance-Based Skills Assessment 2016

4.3 Installing Appliances and Interior Vapor Distribution Systems Performance-Based Skills Assessment 2016 4.3 Installing Appliances and Interior Vapor Distribution Systems Performance-Based Skills Assessment 2016 Section One Task 1 Task 2 Task 3 Task 4 Task 5 Section Two Task 1 Task 2 Task 3 Task 4 Task 5

More information

VENTING GAS APPLIANCES NFPA 54 CODE

VENTING GAS APPLIANCES NFPA 54 CODE VENTING GAS APPLIANCES NFPA 54 CODE Better Buildings: Better Business Robert Parkhurst March 3, 2017 Objectives Standardize terminology Examine gas piping size and safety Simplify design rules Selection

More information

CHAPTER 5: EXHAUST SYSTEMS

CHAPTER 5: EXHAUST SYSTEMS MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such

More information

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Ohio Administrative Code Rule Number OMC Section IMC origin Reason for proposed 4101:2-2-01 Air, Makeup 2015 Modified definition Air,

More information

Chapter FUEL GAS CODE*

Chapter FUEL GAS CODE* Chapter 19.09 FUEL GAS CODE* * Editors Note: Serial No. 2004-31, 1, adopted Oct. 11, 2004 amended Title 19 in its entirety to read as herein set out. See the editor's note at Tit. 19 and also the Code

More information

2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments

2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments 2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments Based on the International Residential Code (IRC ) GR PPN 1208 Course Approval # 12085 Description This seminar reviews and

More information

2012 International Mechanical Code Significant Changes. About the Significant Changes

2012 International Mechanical Code Significant Changes. About the Significant Changes Significant Changes to the International Mechanical Code and the International Fuel Gas Code With Louisiana Amendments Copyright Materials This presentation is protected by US and International Copyright

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment

More information

GE Monogram. Installation. Instructions. Component Cooktop System. Models ZEW145V ZGW124EN3 ZGW125EN3 ZEW155N ZEW166Y ZEW176Y

GE Monogram. Installation. Instructions. Component Cooktop System. Models ZEW145V ZGW124EN3 ZGW125EN3 ZEW155N ZEW166Y ZEW176Y GE Monogram Installation Instructions Component Cooktop System Models ZEW145V ZGW124EN3 ZGW125EN3 ZEW155N ZEW166Y ZEW176Y Before you begin Read these instructions completely and carefully. IMPORTANT: Save

More information

TABLE OF CONTENTS Board of Appeals General Limitations of Authority... 6 Table Mechanical Permit Fees...

TABLE OF CONTENTS Board of Appeals General Limitations of Authority... 6 Table Mechanical Permit Fees... TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION............. 1 101.0 General....................... 1 101.1 Title.......................... 1 101.2 Scope........................ 1 101.3 Purpose......................

More information

Completed Projects / Projets terminés

Completed Projects / Projets terminés Completed Projects / Projets terminés New Standards New Editions Special Publications Gas Technician Training 2 Module 10, 3rd edition Piping and Tubing Systems for Industrial and Commercial Applications...

More information

Vent Supplement Ultra-80, -105, -155, -230 & -310

Vent Supplement Ultra-80, -105, -155, -230 & -310 Gas-fired water boiler Vent Supplement Ultra-80, -105, -155, -230 & -310 Installation of: Vent piping Air piping with This document must only be used by a qualified heating installer/service technician.

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GBI 201-5 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

UNIFORM MECHANICAL CODE

UNIFORM MECHANICAL CODE INDEX Note: Content and section numbers will be updated before publishing. 2009 International Association of Plumbing and Mechanical Officials. All rights reserved. The copyright in this index is separate

More information

Land Use and Environmental Services Code Enforcement. Table of Contents

Land Use and Environmental Services Code Enforcement. Table of Contents 3rd Quarter 2013 Code Answers in blue (Jul Sep) 2013 Code Answers in red (Oct Dec) Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Chimneys & Vents Chapter 7 Gaseous Hydrogen S. POLICY

More information

Standard for tests for flammability of plastic materials for parts in devices and appliances

Standard for tests for flammability of plastic materials for parts in devices and appliances IAS Accreditation Number TL-212 Company Name Address 3933 U.S. Route 11 Cortland, NY 13045 Contact Name Terence J. O'Beirne, Quality Manager Telephone (607)758-6316 Effective Date of Scope September 25,

More information

Inspection Checklist Mechanical Final

Inspection Checklist Mechanical Final Property Owner Name: Property Address: Property Parcel Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans, and

More information

TABLE OF CONTENTS. Part I Administrative

TABLE OF CONTENTS. Part I Administrative Part I Administrative.......................... 1-1 CHAPTER 1 SCOPE AND ADMINISTRATION. 1-1 R101 General............................. 1-1 R102 Applicability......................... 1-2 R103 (Not adopted)........................

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

Installation Instructions

Installation Instructions Instructions for Dryers Original Instructions Keep These Instructions for Future Reference. (If this machine changes ownership, this manual must accompany machine.) Part No. 514446ENR2 February 2015 Front

More information

ASX7-4-IOM-6 J

ASX7-4-IOM-6 J INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

Electrical Protection of CSST Gas Piping Systems. Bob Torbin, PE Omega Flex, Inc.

Electrical Protection of CSST Gas Piping Systems. Bob Torbin, PE Omega Flex, Inc. Electrical Protection of CSST Gas Piping Systems Bob Torbin, PE Omega Flex, Inc. Standard Yellow Arc-Resistant Black CSST Product Standard National Standard ANSI LC-1 Performance-based standard Listed

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment

More information

Alliant Energy - Gas Service Manual Appendix

Alliant Energy - Gas Service Manual Appendix Gas Service Manual Appendix Page 1 of 12 Alliant Energy - Gas Service Manual Appendix Issued: 2018 Supersedes: 2015 APPROXIMATE GAS INPUT FOR TYPICAL APPLIANCES Appliance Input /hr (Approx.) Space Heating

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO. GBI 210 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

esfr dry pendent sprinkler Vk501 (k14.0)

esfr dry pendent sprinkler Vk501 (k14.0) September 13, 2012 Sprinkler 122a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK501 is a fast response fusible element type sprinkler designed for use in storage

More information

HVAC Equipment Access Equipment Location

HVAC Equipment Access Equipment Location City of Lancaster- Building Department 121 East Chestnut Street, Suite 102, Lancaster, Ohio 43130-3825 (740) 687-6649, Fax (740) 681-5030 Web site: www.ci.lancaster.oh.us/dept/building HVAC Heating, Ventilating,

More information

INSTALLATION AND SERVICE MANUAL

INSTALLATION AND SERVICE MANUAL INSTALLATION AND SERVICE MANUAL VERTICAL COMBUSTION AIR INLET KITS CATEGORY III VENTING FOR SEPARATED COMBUSTION TUBULAR GAS FIRED UNIT HEATERS USE 5 INCH KIT FOR UNITS WITH CAPACITIES 100,000 TO 250,000

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

CHIMNEYS AND VENTS CHAPTER 8

CHIMNEYS AND VENTS CHAPTER 8 CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

esfr dry pendent sprinkler Vk502 (k14.0)

esfr dry pendent sprinkler Vk502 (k14.0) Page 1 of 11 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION Sections 23.20.100 Local amendments to the International Mechanical Code, 2012 Edition.... 2 23.20.101.2 Scope.... 2 23.20.103-110

More information

Building Department Informational Handout

Building Department Informational Handout City of Sonoma Building Department Informational Handout Residential Water Heaters Handout No: 15 Revised: 4/26/18 A water heater is an appliance designed to supply hot water and is equipped with automatic

More information

INSTALLATION AND SERVICE MANUAL

INSTALLATION AND SERVICE MANUAL INSTALLATION AND SERVICE MANUAL HORIZONTAL COMBUSTION AIR INLET KITS CATEGORY III VENTING FOR SEPARATED COMBUSTION TUBULAR GAS FIRED UNIT HEATERS USE 5 INCH KIT FOR UNITS WITH CAPACITIES 100,000 TO 250,000

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION 601 (IFGC) GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and

More information

TANKLESS WATER HEATING

TANKLESS WATER HEATING TANKLESS WATER HEATING With any gas appliance, it is essential that the gas supply system be properly sized to support the BTU load of the system. Tankless water heaters can be a great solution to provide

More information

of 2 http://submittals.nfpa.org/terraviewweb/contentfetcher?contentid=54-... 5/6/2014 11:37 AM NFPA STANDARDS DEVELOPMENT SITE SECOND DRAFT REPORT Closing Date: January 03, 2014 NFPA 54, ANSI Z223.1 2012

More information

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2007

Land Use and Environmental Service Agency (Code Enforcement) Mechanical Q&A 2007 General: 1) (Q) May the gas be turned on temporarily to the gas piping system without the installation of the appliance? (A) NO! 2) (Q) Are traps required on all condensate drains from equipment? (A) Only

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

INSTALLATION GUIDE Dual Fuel Ranges

INSTALLATION GUIDE Dual Fuel Ranges INSTALLATION GUIDE Dual Fuel Ranges Contents Wolf Dual Fuel Ranges......................... 3 Safety Instructions............................ 4 Dual Fuel Range Specifications.................. 5 Dual Fuel

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS. Part I Administrative... 1 Part I Administrative............................ 1 CHAPTER 1 ADMINISTRATION............... 1 R101 Title, Scope and Purpose.................... 1 R102 Applicability.............................. 1 R103

More information

X Article/Section 902.0(D) X X X X X X X X X X X

X Article/Section 902.0(D) X X X X X X X X X X X CALIFORNIA MECHANICAL CODE MATRIX ADOPTION TABLE CHAPTER 9 INSTALLATION OF SPECIFIC APPLIANCES Adopting Agency BSC SFM HCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 Adopt Entire Chapter X X X X X Adopt Entire

More information

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS Page 1 of 6 CENTRAL STATE HOSPITAL PLAN SUBJECT: SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS ANNUAL REVIEW MONTH: RESPONSIBLE FOR REVIEW: APRIL CSH SAFETY DIRECTOR LAST REVISION

More information

ASX7-5-IOM-3 J

ASX7-5-IOM-3 J INSTALLATION INSTRUCTIONS 5" CONCENTRIC VENT TERMINAL KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 90,000 to 120,000 BTU/HR

More information

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

Installation Instructions

Installation Instructions Installation Instructions for Dryers Inside... Dimensions... Before You Start... 4 Installing the Dryer... 5 Installer Checklist... Back Cover Date Purchased Model Number Serial Number Keep these instructions

More information

Installation Instructions

Installation Instructions Instructions for Stacked Dryers Original Instructions Keep These Instructions for Future Reference. (If this machine changes ownership, this manual must accompany machine.) www.speedqueen.com Part No.

More information

Installation Instructions

Installation Instructions Instructions for Dryers Original Instructions Keep These Instructions for Future Reference. CAUTION: Read the instructions before using the machine. (If this machine changes ownership, this manual must

More information

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.

More information

APPUZO RANGE HOOD INSTALLATION

APPUZO RANGE HOOD INSTALLATION IMPORTANT SAFETY INFORMATION TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR PERSONAL INJURY, PLEASE READ THE FOLLOWING: Use the range hood only in the manner intended by the manufacturer. If you have questions,

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

SPRINKLERS TABLE OF CONTENTS

SPRINKLERS TABLE OF CONTENTS SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717) City of York Qdot Engineering 101 S. George St 116 E Gas Ave York, PA 17405 York, PA 17405 (717) 849-2329 (717) 744-8315 INSPECTION CHECKLIST Residential Mechanical 2009 Codes This checklist is intended

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

CHAPTER 17 STANDARDS STANDARDS Broadway, New York, NY 10018,

CHAPTER 17 STANDARDS STANDARDS Broadway, New York, NY 10018, STANDARDS Chapter 17, Part II CHAPTER 17 STANDARDS 1701.0 Scope Part I of this chapter covers standards that are hereby declared to be part of this code. Part II of this chapter lists standards which relate

More information

Code verification sign-off

Code verification sign-off Code verification sign-off Following is a list of the most common manufactured home code non-compliant items found in used or altered manufactured homes. These are only the most commonly found items and

More information

INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG FIRE PIT SERIES ONLY

INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG FIRE PIT SERIES ONLY INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG FIRE PIT SERIES ONLY Installation and service must be provided by a qualified installer, service agency or gas supplier Grand Canyon Gas Logs,

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

Installation Instructions

Installation Instructions Instructions for Dryers Original Instructions Keep These Instructions for Future Reference. (If this machine changes ownership, this manual must accompany machine.) www.alliancelaundry.com Part No. D5486ENR

More information

Installation Instructions

Installation Instructions Instructions for Dryers Original Instructions Keep These Instructions for Future Reference. (If this machine changes ownership, this manual must accompany machine.) www.speedqueen.com Part No. 5439R October

More information

TABLE OF CONTENTS Limitations of Authority...6 Table Swimming Pool, Spa, and Hot Tub Permit Fees...7

TABLE OF CONTENTS Limitations of Authority...6 Table Swimming Pool, Spa, and Hot Tub Permit Fees...7 TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION..............1 101.0 General.......................1 101.1 Title..........................1 101.2 Scope........................1 101.3 Purpose......................1

More information

Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended (amended sections listed below)

Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended (amended sections listed below) CALIFORNIA MECANICAL CODE MATRIX ADOPTION TABLE CAPTER CIMNEY AND VENTS Adopting Agency BSC SFM CD DSA OSPD 1 1/AC AC SS SS/CC 1 4 Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS Ul611-0l SECTION 211316- DRY-PIPE SPRINKLER SYSTEMS PARTl-GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification

More information

TRIAD Boiler Systems, Inc Atlantic Drive, Unit 2 West Chicago, IL

TRIAD Boiler Systems, Inc Atlantic Drive, Unit 2 West Chicago, IL TRIIUMPH SERIIES AIIR SUPPLY AND VENTIING GUIIDE C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam & Hot Water Boilers ASME Code Section IV C.S.A Design-Certified Complies

More information

Installation & Operation Manual Models: 502, 752, 1002, 1302, 1501, 1701, and 2001 Up To 5:1 Turndown

Installation & Operation Manual Models: 502, 752, 1002, 1302, 1501, 1701, and 2001 Up To 5:1 Turndown PBX-PFX-I-O_100161632_2000016130_Rev M Installation & Operation Manual Models: 502, 752, 1002, 1302, 1501, 1701, and 2001 Up To 5:1 Turndown WARNING: This manual supplies information for the installation,

More information

CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003

CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003 CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES 2000 to 2003 The following pages contain comments regarding the changes to the 2000 edition of the UNIFORM MECHANICAL CODE (UMC ) that were made to

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION SECTIONS 23.20.100 Local Amendments To The International Mechanical Code, 2000 Edition 23.20.202 Definitions 23.20.301.14

More information

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8 City of Ottawa Project No. CR006230 Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire

More information

Suggested Specifications Prestige Excellence 110

Suggested Specifications Prestige Excellence 110 Suggested Specifications Prestige Excellence 110 General Requirements A. Furnish and install (qty) completely assembled, modulating, sealed combustion, high efficiency, combination gas-fired boiler(s)

More information

SIZING HANDBOOK & APPLICATION GUIDE

SIZING HANDBOOK & APPLICATION GUIDE SIZING HANDBOOK SIZING HANDBOOK & APPLICATION GUIDE Chimney & Gas Vent For Capacities to 100 Million B.T.U. The primary aim of this Sizing Handbook is to provide more detailed guidance on appliance venting

More information

Installation & Operation Manual Models: Up To 4:1 Turndown

Installation & Operation Manual Models: Up To 4:1 Turndown VFS-I-O_100161775_2000019057_Rev D Installation & Operation Manual Models: 500-2000 Up To 4:1 Turndown WARNING: This manual supplies information for the installation, operation, and servicing of the appliance.

More information

D UAL F UEL R ANGES INSTALLATION INSTRUCTIONS

D UAL F UEL R ANGES INSTALLATION INSTRUCTIONS D UAL F UEL R ANGES INSTALLATION INSTRUCTIONS As you follow these instructions, you will notice WARNING and CAUTION symbols. This blocked information is important for the safe and efficient installation

More information

Installation Instructions

Installation Instructions Instructions for Dryers Original Instructions Keep These Instructions for Future Reference. (If this machine changes ownership, this manual must accompany machine.) www.speedqueen.com Part No. D5439R2

More information

INSTALLATION INSTRUCTIONS MANUAL STEEL GAS STAR COOKTOPS 30" MODELS: SGS304, SGSX304 36" MODELS: SGS365, SGSX365 45" MODELS: SGS456, SGSX456

INSTALLATION INSTRUCTIONS MANUAL STEEL GAS STAR COOKTOPS 30 MODELS: SGS304, SGSX304 36 MODELS: SGS365, SGSX365 45 MODELS: SGS456, SGSX456 INSTALLATION INSTRUCTIONS MANUAL STEEL GAS STAR COOKTOPS 30" MODELS: SGS304, SGSX304 36" MODELS: SGS365, SGSX365 45" MODELS: SGS456, SGSX456 PLEASE READ INSTRUCTION BEFORE PROCEEDING IMPORTANT: INSTALLER:

More information