Size: px
Start display at page:

Download ""

Transcription

1 SA 1

2 INDEX Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R410A...pag. 5 Scroll compressors...pag. 6 Condenser coils...pag. 6 Brazed plates evaporators...pag. 7 Axial fans...pag. 7 Thermostatic expansion valves...pag. 8 Electronic expansion valves...pag. 8 4-way reversing valve...pag. 9 Electronic regulation...pag. 9 Hydronic circuit... pag. 10 Operating range... pag. 11 Versions and accessories... pag. 11 Technical sheets... pag. 12 Performances...pag. 36 Dimensional drawings...pag. 49 Space for unit installation...pag. 57

3 SA Air cooled water chillers and heat pumps, axial fans, hermetic scroll compressors, brazed plate evaporators, refrigerant gas R410A, condensing unit. Minimum 2 compressors for each circuit. Units designed for commercial or industrial applications. Only for outdoor installation. Cooling capacity from 50 up to 752 kw Heating capacity from 55 up to 636 kw R410A refrigerant 3

4 Available versions CHILLER: basic version with large operative range of outdoor air temperature (-15 C up to 43 C). HEAT PUMP: with large operative range of outdoor air temperature (-10 C up to 40 C in heating mode); used for hydronic circuits with 2 tubes, during winter produces hot water up to 50 C, and during summer produces cold water. ENERGY: chiller and heat pump with oversized evaporator and condenser, for maximum energy saving; very large operative range of outdoor air temperature from -15 C up to 46 C. TOP: unit with largest evaporator and condenser surfaces, for energy performances at top of the market with EER>3,1 W/W for all sizes. Large operative range of outdoor air temperature (-15 C up to 43 C). SILENT: unit equipped with soundproof compressors and fan speed decreased for limited noise levels. The unit can work during the night with reduced fan speed. CONDENSING UNITS: this units are supplied without evaporator, expansion valve and hydronic components; they are able to be connected with a remote direct expansion heat exchanger (example a cooling coil inside an air handling unit (AHU)). PARTIAL HEAT RECOVERY (desuperheater): an heat exchanger is inserted along the compressors discharge line before the condenser, it s able to desuperheat the hot gas and produces hot water up to 55 C. The amount of recovered energy is around the 30% of the cooling energy production. TOTAL HEAT RECOVERY: a water condenser is inserted on the discharge line of the compressors in parallel with the air condenser, when the recovery circuit is not satisfied, a changeover valve diverts the refrigerant hot gas in the water condenser, to transfer the total condensing energy on the hot water circuit. The amount of recovered energy is around the 135% of the cooling energy production. TWO FREECOOLING VERSIONS: STANDARD FREECOOLING: near the finned condenser there is a second finned heat exchanger with water inside (freecooling exchanger); if the external air temperature falls below than a conveniently limit, a switch valve diverts the water flow through the freecooling exchanger (freecooling and compressors work together); when outdoor air temperature falls under a second project limit, all compressors are completely stopped: - The air flow by fans cools directly the water inside the freecooling exchanger and the EER of the unit increase up to W/W. - This solution needs to use water with antifreeze for the winter period for antifreeze protection. FREECOOLING WITH SEPARATED CIRCUIT: the freecooling circuit is separate from user circuit, so the antifreeze mixture charge can be limit to it; the chiller mode has more efficiency and the user plant is in global less expensive. CLIENT: units with special equipment or devices. 4

5 Features Structure of electro-galvanized and painted steel sheet Air condensed water chiller with scroll compressors. Ecological refrigerant R410A This refrigerant R410A with zero ozone depletion potential (ODP=0) together with a very low value for the global warming effective potential, is the best choice for circuits with scroll compressors. Thanks to its characteristics of heat transfer and its heat capacity in the gas phase, allows high yields of condensers having small diameter tube, and can reduce the airflow needed for condensation. R410A 5

6 Scroll compressors two or three high-efficiency scroll compressors, on each circuit refrigerator for maximum energy efficiency at partial loads. The choice of scroll compressor allows you to have low vibration and noise emissions. Reliability is high thanks to the reduced number of moving parts and to the high capacity of the compressor to adapt to many different conditions. Scroll Compressor section Due to its construction, hermetic scroll compressors withstand at flooded start much better than the piston or screw compressors (in faulty conditions). In addition thanks to have multiple compressors on the same circuit, when only one of them is started (this happen during many hours in a year) it can work with oversized of the heat exchangers and this produce a bigger efficiency during working conditions partialized. The example is as follows: If a circuit with two compressors has a value of EER= 2.70 W/W, when on the same circuit only one compressor operates the EER value climbs to 3.74 W/W; the result of this technology is that the value of ESEER (seasonal average efficiency) increases much more than in chillers with only one compressor per circuit. Condenser coils with high-efficiency design, equipped by internally grooved copper tubes for maximize the heat exchange, with small diameter to minimize the refrigerant charge. Finned condenser The special profile of the fins allows to obtain excellent performance of heat exchange with the air, together with the use of internally grooved tubes we have low values of the condensing temperature and consequently high compressors performances. In the case of heat pumps, the fins have hydrophilic surface treatment in order to obtain high performance of water drain during defrosting of the battery. 6

7 Brazed plates evaporators specifically designed for R410A, made in stainless steel. In addition to a very high mechanical resistance, due to the use of stainless steel, they have high corrosion resistance. These evaporators work in perfect countercurrent, and allow to have very high evaporation temperature compared other kind of evaporator, for maximize EER performance. An integrated distributor guarantees a perfect equalization of the refrigerant gas flow inside each plate heat exchanger, for maximum performances. On heat pumps the evaporator commutates to condenser mode and produces hot water. Brazed plate evaporator Axial fans The chillers are normally supplied with fans equipped with AC motor, controlled by a fan speed controller (cut phase regulator) that allows the modulation of speed so as to manage the condensing pressure with the change of cooling load and outdoor air temperature. Fans are available on request with a EC motor (Electronically Commutated Motor) that enable high performance. At full load, an EC motor saves 20% energy compared to a conventional AC motor, and the difference increases up to 57% when the comparison is made at partialized conditions, with the air flow capacity equal to half of the maximum flow. The higher cost of the fans with EC motor is repaid by the energy saving after about 2 years of unit work. In addition to energy saving the low axial fans speed,facilitate limited noise levels when the unit works during the night. Fan with AC motor Fan with EC motor 7

8 Thermostatic expansion valves Standard production is equipped by thermostatic expansion valves to ensure a return of dry gas to the compressor. Electronic expansion valves on request by request the unit can be equipped with electronic expansion valves. These valves, via an electronic driver, a temperature sensor and a pressure transmitter, are able to provide a more precise value of superheating. The graph below shows the effect of switching between the operation of a chiller with a TEV (thermostatic expansion valve) to an EEV (electronic expansion valve). The lowering of the average superheat value, the stability of the value itself and the operating pressure are clearly evident. Its use is highly recommended in the case of heat pumps, where in winter operation, it allows to have a very low superheating (this allow COP increasing) and the correct function of unit also with much lower outdoor air temperatures, up to 3 C less compared to use of thermostatic valves. Carel controllers and Electronic Expansion Valve 8

9 4-way reversing valve Used for heat pump version converts the refrigerant circuit configuration from chiller to heat pump. When switched on, the unit is converted to heat pump (the chiller evaporator works at condenser mode and produces hot water - winter). When switched off the refrigerant circuit is converted to chiller mode (summer) or defrosting (winter). 4 ways reversing valve Electronic regulation by a microprocessor card for the management and control of all functional parameters The controls normally used are parametric products of Carel. For chillers up to 4 compressors the used control is μc2-se. For the other units is used μc3 with a semigraphic terminal, where available languages are English, Italian and Spanish. On request or for special units, it is possible use controllers belonging to family Carel pco or from other manufacturers. In any case, the functions controlled are: a. regulation on inlet water temperature, with the alternative possibility of adjusting the output water temperature; b. management of cooling capacity (or heating) with turning ON or OFF the compressors, depending on the request of the hydronic circuit; the control is such that the number of operating hours per year of each compressor, is the same for everyone; c. prevent high pressure - this function allows you to turn off one of the compressors on the same circuit when the condensing pressure rises too much; d. reverse cycle for hot gas defrost; e. fan speed regulation (to handle the condensing pressure as a function of load and air ambient temperature) allows to use the chiller also in very low ambient temperatures; f. management of evaporating pressure in heat pump mode - this feature allows the modulation of the fans when the outdoor air temperature is above 5-6 C to reduce noise emissions to a minimum level; g. antifreeze heaters - a set of heaters protect the parts of circuits containing water when their temperature ( caused from low outdoor air temperature) drops below the safety threshold; h. low noise mode this feature as standard on SILENT version, allows you to change the fan speed adjustment in the night hours, with limited noise emission; i. evaporator pump control; backup evaporator pump; rotation pumps (active only in the presence of double pump); μc2se μc3 semigraphic terminal 9

10 energy save mode (pump switched on only when needed) - this feature allows a considerable energy saving, trough turning ON the pump for only as long it is necessary - this function is useful when you have constant water flow on chiller side and variable water flow on the system side, by inserting a manifold by-pass between them: the maximum benefit is obtained when a buffer tank is installed; j. water flow switch; k. variable set point of water temperature depending on outdoor air temperature (sliding set temperature) or by external contact; l. start compressors by external contacts (only condensing units); m. communication with supervisory systems; n. anti freeze alarm; o. high low pressure alarms p. compressors alarm q. water flow alarm r. pump alarm Hydronic circuit The unit is normally equipped with Victaulic flexible couplings complete with clamps and solder terminals. On request the unit can be completed with the provision of pump, safety valve, water filter, buffer tank and backup pump. It is possible to choose between low pressure pump, and high pressure pump with standard performance. For special requirements is possible to install special pumps, but in this case the buffer tank is not available. The circuits are protected against freezing by heaters, down to outdoor air temperature of -15 C. On heat pumps the expansion vessel is not supplied. On freecooling version buffer tank is not available. 10

11 Operating range thank to the use of fan speed controller the operating range is very wide. operating ranges for cooling and heating modes Versions and accessories on demand N...Basic E...High Energy efficiency H...Heat pump C...Condensing unit R...Partial recovery (desuperheater) (1) R1...Total recovery (1) F...Freecooling S...Silent CLIENT Special features on specific customer needs EEV... Electronic expansion valve/s P1...Hydronic Kit with pump, safety valve, water filter P2...Hydronic Kit with double pump, safety valve, water filter P3...Hydronic Kit with high pressure pump, safety valve, water filter P4...Hydronic Kit with double high pressure pump, safety valve, water filter P1S...P1 + Buffer tank, electric heater and expansion vessel (2) P2S...P2 + Buffer tank, electric heater and expansion vessel (2) P3S...P3 + Buffer tank, electric heater and expansion vessel (2) P4S...P4 + Buffer tank, electric heater and expansion vessel (2) RIC...configuration with bypass of primary circuit integrated on unit RS485..RS 485 serial interface (MODBUS protocol) RS232..RS 232 serial interface LON...LonWorks interface KON...Konnex interface BAC1...Bacnet MS/TP interface BAC2...Bacnet Ethernet/IP interface WEB...WEB server for remote control CK...Clock board RIF...Power factor corrector ST...Low starting current device AV...Anti-vibration mountings PR...Remote control panel TP...Tropical adaptation (3) EF...Fan with EC motor SOV...2 way shut-off valve for safety valves KK...Low outdoor air temperature start device (1) SA-52, 52E, 60 only if not present buffer tank (2) For SA-..-H (heat pumps) the expansion vessel is not supplied (3) Only E version 11

12 Technical Sheets SA-N Size Cooling capacity 50,1 55,7 64,9 71,1 86,9 101,5 114,6 128,0 146,0 Power input 20,1 23,4 25,5 29,3 35,0 40,1 45,4 50,9 57,4 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 76,2 Maximum outdoor air temperature ( C) 42,0 41,0 42,0 41,0 42,5 42,5 42,3 42,0 42,0 Water flow (m3/h) 8,6 9,6 11,2 12,2 14,9 17,5 19,7 22,0 25,1 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 2,49 2,38 2,54 2,42 2,48 2,53 2,52 2,51 2,54 ESEER (kw/kw) 3,82 3,72 3,86 3,76 3,81 3,85 3,85 3,84 3,86 Sound pressure at 10m (db(a)) 47,4 47,4 47,3 49,1 51,6 52,0 51,2 51,1 52,1 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,78 0,85 1,00 1,08 1,26 1,39 1,48 2,04 2,18 Amperage of low pressure pump (A) 1,6 1,7 2,1 2,2 2,6 2,9 3,1 4,2 4,5 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 1,0 1,1 1,2 1,3 1,6 1,8 1,9 2,3 2,5 Amperage of high pressure pump (A) 2,0 2,2 2,5 2,7 3,2 3,6 3,9 4,7 5,1 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING Cooling capacity 46,1 51,2 59,7 65,4 80,0 93,3 105,5 117,7 134,3 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,6 1,6 1,8 1,8 3,4 3,4 3,4 3,4 3,4 Water flow (m3/h) 8,6 9,6 11,2 12,2 14,9 17,5 19,7 22,0 25, Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

13 Basic version ,0 186,9 225,4 259,9 290,2 328,2 380,4 440,7 501,0 569,2 671,9 752,3 63,0 75,0 91,2 98,3 121,8 125,6 151,4 181,4 204,7 227,2 272,1 309,2 83,9 97,5 117,6 131,2 153,0 164,4 190,5 231,6 248,7 283,6 343,8 378,4 42,8 41,5 41,5 43,5 40,3 43,1 42,0 41,3 41,2 41,5 41,5 40,5 27,9 32,1 38,8 44,7 49,9 56,5 65,4 75,8 86,2 97,9 115,6 129, ,57 2,49 2,47 2,64 2,38 2,61 2,51 2,43 2,45 2,51 2,47 2,43 3,88 3,82 3,80 3,94 3,72 3,92 3,83 3,76 3,78 3,83 3,80 3,77 53,6 54,0 54,1 54,8 55,6 56,6 57,9 58,1 58,2 59,4 60,7 61, ,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,26 2,31 2,73 3,31 3,70 4,70 5,45 6,32 7,18 8,16 9,10 10,78 4,7 4,8 5,6 6,8 7,6 9,7 11,3 13,0 14,8 16,8 18,8 22, ,6 2,7 4,2 4,6 5,3 6,5 7,6 8,8 10,0 11,3 12,8 15,0 5,4 5,6 8,6 9,4 11,0 13,5 15,6 18,1 20,6 23,4 26,5 30, ,0 172,0 207,4 239,1 266,9 302,0 350,0 405,5 460,9 523,7 531,9 526,6 4,8 4,9 5,6 7,4 6,9 9,8 9,8 13,7 13,1 13,1 16,5 16,4 27,9 32,1 38,8 44,7 49,9 56,5 65,4 75,8 86,2 97,9 115,6 129, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

14 Technical Sheets SA-E Size Cooling capacity 48,7 55,5 62,7 70,9 82,0 95,5 112,0 124,8 144,0 Power input 16,2 18,5 21,1 24,3 27,1 32,2 36,2 42,4 47,4 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 62,8 Maximum outdoor air temperature ( C) 46,5 46,5 45,8 46,5 46,5 46,4 46,5 45,5 46,5 Water flow (m3/h) 8,4 9,5 10,8 12,2 14,1 16,4 19,3 21,5 24,8 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 3,01 3,00 2,98 2,92 3,02 2,97 3,09 2,95 3,04 ESEER (kw/kw) 4,18 4,18 4,17 4,13 4,19 4,16 4,23 4,15 4,20 Sound pressure at 10m (db(a)) 47,3 47,4 47,4 47,3 51,2 50,8 51,2 50,4 52,0 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,70 0,78 0,86 0,94 1,30 1,44 1,56 1,61 2,40 Amperage of low pressure pump (A) 1,5 1,6 1,8 1,9 2,7 3,0 3,2 3,3 5,0 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 0,9 1,1 1,2 1,3 1,5 1,8 2,1 2,3 2,5 Amperage of high pressure pump (A) 1,9 2,2 2,4 2,7 3,1 3,8 4,3 4,6 5,1 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING Cooling capacity 40,3 45,9 51,9 58,7 67,9 79,1 92,7 103,4 119,3 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,6 1,7 1,7 2,4 3,0 3,2 3,4 3,4 4,9 Water flow (m3/h) 8,4 9,5 10,8 12,2 14,1 16,4 19,3 21,5 24, Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

15 High Energy Efficiency version ,8 181,0 211,1 248,4 285,0 317,9 374,0 414,6 480,6 573,0 613,5 53,8 60,6 66,2 84,6 94,8 113,4 127,3 142,7 168,5 198,8 214,8 71,4 80,7 87,7 112,7 125,4 150,7 168,6 189,6 224,5 264,4 286,0 46,5 46,2 46,5 45,5 46,5 45,0 46,5 45,8 45,0 45,5 45,0 27,6 31,1 36,3 42,7 49,0 54,7 64,3 71,3 82,7 98,6 105, ,99 2,98 3,19 2,93 3,00 2,80 2,94 2,91 2,85 2,88 2,86 4,17 4,17 4,28 4,14 4,18 4,06 4,14 4,12 4,09 4,11 4,09 53,3 53,2 54,8 54,9 56,0 56,6 57,9 58,6 58,1 59,4 61, ,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,40 2,30 3,27 3,36 3,63 3,80 5,06 5,61 6,51 7,76 8,30 5,0 4,7 6,8 6,9 7,5 7,8 10,5 11,6 13,4 16,0 17, ,6 2,7 4,5 4,7 5,2 5,6 7,1 7,9 9,2 11,0 11,7 5,4 5,6 9,2 9,8 10,8 11,5 14,8 16,4 19,0 22,6 24, ,1 149,9 174,8 205,7 236,0 263,2 309,7 343,3 398,0 474,5 507,9 5,1 5,6 7,6 7,1 9,8 9,6 13,0 13,0 13,1 16,5 16,4 27,6 31,1 36,3 42,7 49,0 54,7 64,3 71,3 82,7 98,6 105, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

16 Technical Sheets SA-TOP Size Cooling capacity 50,1 60,6 68,3 78,5 88,2 103,9 117,5 135,7 Power input 16,0 19,2 21,7 24,3 27,4 31,7 37,6 43,5 Maximum power input at limit conditions 20,4 24,3 27,7 30,8 34,8 40,4 48,1 55,2 Maximum outdoor air temperature ( C) 43,9 44,9 43,5 46,8 45,7 44,5 42,9 45,5 Water flow (m3/h) 8,6 10,4 11,7 13,5 15,2 17,9 20,2 23,3 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 3,13 3,16 3,14 3,22 3,22 3,28 3,12 3,12 ESEER (kw/kw) 4,25 4,26 4,25 4,29 4,29 4,32 4,25 4,24 Sound pressure at 10m (db(a)) Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) Power input of low pressure pump 0,7 0,8 0,9 1,0 1,1 1,5 1,6 1,6 Amperage of low pressure pump (A) 1,5 1,7 1,9 2,1 2,2 3,1 3,3 3,4 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 1,0 1,1 1,3 1,4 1,6 2,0 2,2 2,4 Amperage of high pressure pump (A) 2,0 2,4 2,6 3,0 3,2 4,1 4,5 4,9 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING Cooling capacity 46,1 55,7 62,8 72,2 81,1 95,6 108,1 124,9 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,8 2,5 2,6 3,6 3,7 3,6 3,7 5,5 Water flow (m3/h) 8,6 10,4 11,8 13,5 15,2 17,9 20,2 23, Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

17 Top Energy Efficiency version ,3 170,9 198,9 235,5 275,1 303,5 357,9 406,7 455,9 526,0 48,4 55,0 61,3 74,2 85,4 97,1 112,2 128,7 144,8 169,4 61,6 70,3 77,9 94,8 108,4 123,7 142,4 164,0 185,1 216,1 44,3 43,0 45,1 43,0 45,1 43,8 45,4 44,0 42,5 43,5 26,4 29,4 34,2 40,5 47,3 52,2 61,6 69,9 78,4 90, ,17 3,11 3,25 3,17 3,22 3,12 3,19 3,16 3,15 3,11 4,27 4,24 4,30 4,27 4,29 4,25 4,28 4,26 4,26 4, ,4 2,4 2,1 3,0 3,7 3,9 4,3 5,5 6,2 7,1 5,0 4,9 4,3 6,2 7,7 8,0 8,8 11,4 12,7 14, ,5 2,7 2,8 4,3 5,3 5,6 6,3 7,8 8,7 10,1 5,2 5,5 5,7 8,9 10,9 11,5 12,9 16,0 18,0 20, ,0 157,2 183,0 216,7 253,1 279,2 329,2 374,1 419,4 483,9 5,5 5,7 7,7 7,9 11,5 11,5 14,7 15,0 14,8 19,0 26,4 29,4 34,2 40,5 47,4 52,2 61,6 70,0 78,5 90, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

18 Technical Sheets SA-S Size Cooling capacity 47,6 52,9 61,7 67,5 82,6 96,4 108,9 121,6 138,7 Power input 21,4 24,9 27,2 31,3 37,2 42,6 48,3 54,2 61,2 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 76,2 Maximum outdoor air temperature ( C) 42,0 41,0 42,0 41,0 42,5 42,5 42,3 42,0 42,0 Water flow (m3/h) 8,2 9,1 10,6 11,6 14,2 16,6 18,7 20,9 23,9 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 2,22 2,13 2,27 2,16 2,22 2,26 2,25 2,24 2,27 ESEER (kw/kw) 3,57 3,47 3,61 3,51 3,57 3,61 3,60 3,59 3,61 Sound pressure at 10m (db(a)) 42,3 42,3 42,3 43,8 44,3 46,6 46,0 45,9 46,8 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,74 0,81 0,96 1,04 1,21 1,35 1,44 1,98 2,13 Amperage of low pressure pump (A) 1,5 1,7 2,0 2,1 2,5 2,8 3,0 4,1 4,4 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 0,9 1,0 1,2 1,3 1,5 1,7 1,8 2,2 2,4 Amperage of high pressure pump (A) 1,9 2,1 2,4 2,6 3,1 3,5 3,8 4,6 5,0 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING Cooling capacity 43,8 48,7 56,7 62,1 76,0 88,7 100,2 111,9 127,6 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,4 1,4 1,7 1,7 3,0 3,0 3,0 3,0 3,0 Water flow (m3/h) 8,2 9,1 10,6 11,6 14,2 16,6 18,7 20,9 23, Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

19 Silent version ,9 177,6 214,1 246,9 275,6 311,8 361,4 418,7 476,0 540,8 638,3 714,7 67,0 79,9 97,1 104,6 129,7 133,3 160,9 193,3 217,6 241,6 289,1 328,8 83,9 97,5 117,6 131,2 153,0 164,4 190,5 231,6 248,7 283,6 343,8 378,4 42,8 41,5 41,5 43,5 40,3 43,1 42,0 41,3 41,2 41,5 41,5 40,5 26,5 30,5 36,8 42,5 47,4 53,6 62,2 72,0 81,9 93,0 109,8 122, ,30 2,22 2,21 2,36 2,13 2,34 2,25 2,17 2,19 2,24 2,21 2,17 3,64 3,57 3,55 3,70 3,47 3,68 3,59 3,51 3,53 3,58 3,56 3,52 48,2 48,6 48,7 49,5 50,2 52,0 53,5 52,7 53,6 55,0 55,1 56, ,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,22 2,30 2,76 3,34 3,51 3,72 4,89 5,67 6,44 7,32 8,64 9,68 4,6 4,8 5,7 6,9 7,3 7,7 10,1 11,7 13,3 15,1 17,8 20, ,5 2,7 2,8 4,7 5,0 5,5 6,9 8,0 9,1 10,3 12,2 13,7 5,3 5,6 5,7 9,7 10,4 11,3 14,3 16,5 18,8 21,3 25,2 28, ,6 163,4 197,0 227,1 253,6 286,9 332,5 385,2 437,9 497,5 587,3 657,5 4,3 4,4 5,0 6,6 6,2 8,8 8,8 12,3 11,8 11,8 14,9 14,7 26,5 30,5 36,8 42,5 47,4 53,6 62,2 72,0 81,9 93,0 109,8 122, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

20 Technical Sheets SA-E-S Size Cooling capacity 46,3 52,7 59,6 67,3 77,9 90,8 106,4 118,6 136,8 Power input 17,2 19,7 22,4 25,7 28,8 34,2 38,5 45,1 50,4 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 62,8 Maximum outdoor air temperature ( C) 46,5 46,5 45,8 46,5 46,5 46,4 46,5 45,5 46,5 Water flow (m3/h) 8,0 9,1 10,3 11,6 13,4 15,6 18,3 20,4 23,5 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 2,69 2,68 2,66 2,62 2,71 2,66 2,76 2,63 2,72 ESEER (kw/kw) 3,98 3,97 3,95 3,92 3,99 3,95 4,03 3,93 3,99 Sound pressure at 10m (db(a)) 42,2 42,2 42,2 45,1 43,2 45,4 45,7 45,2 46,9 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,72 0,81 0,93 1,03 1,16 1,29 1,43 1,95 2,11 Amperage of low pressure pump (A) 1,5 1,7 1,9 2,1 2,4 2,7 2,9 4,0 4,4 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 0,9 1,0 1,1 1,3 1,4 1,6 1,8 2,2 2,4 Amperage of high pressure pump (A) 1,9 2,1 2,3 2,6 2,9 3,3 3,7 4,5 4,9 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING Cooling capacity 38,3 43,6 49,3 55,7 64,5 75,1 88,1 98,2 113,3 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,4 1,5 1,5 2,2 2,7 2,9 3,1 3,1 4,4 Water flow (m3/h) 8,0 9,1 10,3 11,6 13,4 15,6 18,3 20,4 23, Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

21 High Energy Efficiency - Silent version ,7 171,9 200,5 236,0 270,7 302,0 355,3 393,8 456,6 544,4 582,8 57,1 64,5 70,3 90,0 100,7 120,6 135,1 151,7 179,3 211,4 228,5 71,4 80,7 87,7 112,7 125,4 150,7 168,6 189,6 224,5 264,4 286,0 46,5 46,2 46,5 45,5 46,5 45,0 46,5 45,8 45,0 45,5 45,0 26,3 29,6 34,5 40,6 46,6 51,9 61,1 67,7 78,5 93,6 100, ,67 2,67 2,85 2,62 2,69 2,50 2,63 2,60 2,55 2,58 2,55 3,96 3,96 4,09 3,92 3,97 3,83 3,93 3,90 3,86 3,89 3,87 47,6 47,6 49,0 49,1 50,5 50,8 52,5 53,2 52,2 54,0 54, ,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,22 2,29 2,76 3,19 3,66 4,09 4,81 5,33 6,18 7,37 7,89 4,6 4,7 5,7 6,6 7,6 8,4 9,9 11,0 12,8 15,2 16, ,5 2,7 3,9 4,5 5,2 5,8 6,8 7,5 8,7 10,4 11,1 5,2 5,5 8,0 9,3 10,7 11,9 14,0 15,5 18,0 21,5 23, ,5 142,4 166,0 195,4 224,2 250,1 294,2 326,1 378,1 450,8 482,5 4,6 5,0 6,8 6,4 8,8 8,6 11,7 11,7 11,8 14,9 14,7 26,3 29,6 34,5 40,6 46,6 51,9 61,1 67,7 78,5 93,6 100, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

22 Technical Sheets SA-TOP-S Size Cooling capacity 47,6 57,5 64,9 74,6 83,8 98,7 111,6 128,9 Power input 17,0 20,3 23,1 25,8 29,1 33,7 40,0 46,1 Maximum power input at limit conditions 20,4 24,3 27,7 30,8 34,8 40,4 48,1 55,2 Maximum outdoor air temperature ( C) 43,9 44,9 43,5 46,8 45,7 44,5 42,9 45,5 Water flow (m3/h) 8,2 9,9 11,2 12,8 14,4 17,0 19,2 22,2 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 2,80 2,83 2,81 2,89 2,88 2,93 2,79 2,80 ESEER (kw/kw) 4,06 4,08 4,06 4,11 4,11 4,14 4,05 4,05 Sound pressure at 10m (db(a)) Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) Power input of low pressure pump 0,7 0,9 1,0 1,1 1,2 1,4 1,5 2,0 Amperage of low pressure pump (A) 1,5 1,8 2,1 2,3 2,5 2,8 3,0 4,2 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 0,9 1,1 1,2 1,4 1,5 1,7 1,9 2,3 Amperage of high pressure pump (A) 1,9 2,3 2,5 2,8 3,1 3,5 3,9 4,7 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING Cooling capacity 43,8 52,9 59,7 68,6 77,1 90,8 102,7 118,6 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,8 2,5 2,6 3,6 3,7 3,6 3,7 5,4 Water flow (m3/h) 8,2 9,9 11,2 12,8 14,4 17,0 19,2 22, Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

23 Top Energy Efficiency - Silent version ,6 162,3 189,0 223,7 261,4 288,3 340,0 386,3 433,1 499,7 51,3 58,4 65,0 78,8 90,5 103,0 118,9 136,6 153,6 179,8 61,6 70,3 77,9 94,8 108,4 123,7 142,4 164,0 185,1 216,1 44,3 43,0 45,1 43,0 45,1 43,8 45,4 44,0 42,5 43,5 25,0 27,9 32,5 38,5 45,0 49,6 58,5 66,4 74,5 85, ,84 2,78 2,91 2,84 2,89 2,80 2,86 2,83 2,82 2,78 4,08 4,04 4,12 4,08 4,11 4,05 4,09 4,07 4,07 4, ,2 2,3 2,3 2,7 3,5 3,9 4,6 5,2 5,9 6,8 4,5 4,7 4,8 5,6 7,3 8,1 9,5 10,8 12,1 14, ,5 2,6 2,7 4,0 5,0 5,5 6,5 7,4 8,3 9,5 5,1 5,4 5,7 8,2 10,3 11,4 13,4 15,2 17,1 19, ,0 149,3 173,8 205,8 240,5 265,2 312,8 355,4 398,5 459,7 5,4 5,6 7,6 7,7 11,3 11,3 14,6 14,8 14,6 18,8 25,1 27,9 32,5 38,5 45,0 49,6 58,5 66,5 74,6 86, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

24 Technical Sheets SA-H-N Size Cooling capacity 49,3 54,8 63,9 69,9 85,5 99,8 112,8 125,9 Power input 20,1 23,4 25,5 29,3 35,0 40,1 45,4 50,9 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 Maximum outdoor air temperature ( C) 42,0 41,0 42,0 41,0 42,5 42,5 42,3 42,0 Water flow (m3/h) 8,5 9,4 11,0 12,0 14,7 17,2 19,4 21,7 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 2,45 2,34 2,50 2,38 2,44 2,49 2,48 2,47 ESEER (kw/kw) 3,78 3,69 3,83 3,72 3,78 3,82 3,81 3,80 Heat capacity 55,7 61,9 72,2 79,0 96,6 112,8 127,5 142,3 Power input (heating mode) 19,3 22,4 24,5 28,2 33,6 38,5 43,6 48,9 Water flow (heating mode) (m3/h) 9,6 10,6 12,4 13,6 16,6 19,4 21,9 24,5 Pressure loss of hydronic circuit (kpa) Minimum operating outdoor air temperature in heating mode ( C) -10,1-9,5-9,5-8,9-11,0-10,4-9,7-9,1 COP (kw/kw) 2,88 2,76 2,94 2,80 2,88 2,93 2,92 2,91 Sound pressure at 10m (db(a)) 47,4 47,4 47,3 49,1 51,6 52,0 51,2 51,1 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,78 0,85 1,00 1,08 1,26 1,39 1,48 2,04 Amperage of low pressure pump (A) 1,6 1,7 2,1 2,2 2,6 2,9 3,1 4,2 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 1,0 1,1 1,2 1,3 1,6 1,8 1,9 2,3 Amperage of high pressure pump (A) 2,0 2,2 2,5 2,7 3,2 3,6 3,9 4,7 Available pressure with high prevalence hydronic kit (kpa) Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

25 Heat Pump - Basic version ,6 159,4 183,9 221,8 255,7 285,5 323,0 374,3 433,7 489,7 562,7 57,4 63,0 75,0 91,2 98,3 121,8 125,6 151,4 181,4 206,3 243,2 76,2 83,9 97,5 117,6 131,2 153,0 164,4 190,5 231,6 265,0 305,4 42,0 42,8 41,5 41,5 43,5 40,3 43,1 42,0 41,3 41,2 40,3 24,7 27,4 31,6 38,1 44,0 49,1 55,6 64,4 74,6 84,2 96, ,50 2,53 2,45 2,43 2,60 2,34 2,57 2,47 2,39 2,37 2,31 3,83 3,85 3,78 3,77 3,91 3,69 3,88 3,80 3,73 3,71 3,66 162,3 180,1 207,8 250,6 289,0 322,6 365,0 423,0 490,1 553,3 635,9 55,1 60,5 72,0 87,5 94,3 116,9 120,5 145,4 174,1 198,1 233,5 27,9 31,0 35,7 43,1 49,7 55,5 62,8 72,8 84,3 95,2 109, ,3-9,8-9,1-8,6-9,6-8,4-9,9-9,0-9,9-9,1-8,0 2,94 2,98 2,88 2,86 3,06 2,76 3,03 2,91 2,81 2,79 2,72 52,1 53,6 54,0 54,1 54,8 55,6 56,6 57,9 58,1 57,8 58, ,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,18 2,26 2,31 2,73 3,46 3,86 4,37 5,07 5,87 6,63 7,62 4,5 4,7 4,8 5,6 7,1 8,0 9,0 10,5 12,1 13,7 15, ,5 2,6 2,7 1,4 5,1 5,7 6,4 7,5 8,6 9,7 11,2 5,1 5,4 5,6 2,9 10,5 11,7 13,3 15,4 17,8 20,1 23, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

26 Technical Sheets SA-H-E Size Cooling capacity 47,9 54,6 61,7 69,7 80,6 94,0 110,2 122,8 Power input 16,2 18,5 21,1 24,3 27,1 32,2 36,2 42,4 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 Maximum outdoor air temperature ( C) 47,0 46,0 45,8 47,3 47,5 46,4 47,1 45,5 Water flow (m3/h) 8,4 9,5 10,8 12,2 14,1 16,4 19,3 21,5 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 2,96 2,95 2,93 2,87 2,98 2,92 3,04 2,90 ESEER (kw/kw) 4,16 4,15 4,14 4,10 4,16 4,13 4,20 4,12 Heat capacity 54,2 61,7 69,8 78,8 91,1 106,2 124,5 138,8 Power input (heating mode) 15,7 18,0 20,4 23,5 26,3 31,2 35,2 41,1 Water flow (heating mode) (m3/h) 9,3 10,6 12,0 13,6 15,7 18,3 21,4 23,9 Pressure loss of hydronic circuit (kpa) Minimum operating outdoor air temperature in heating mode ( C) -10,5-10,2-9,6-10,7-10,9-10,6-10,2-9,5 COP (kw/kw) 3,45 3,44 3,41 3,35 3,47 3,40 3,54 3,38 Sound pressure at 10m (db(a)) 47,3 47,4 47,4 47,3 51,2 50,8 51,2 50,4 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,70 0,78 0,86 0,94 1,30 1,44 1,56 1,61 Amperage of low pressure pump (A) 1,5 1,6 1,8 1,9 2,7 3,0 3,2 3,3 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 0,9 1,1 1,2 1,3 1,5 1,8 2,1 2,3 Amperage of high pressure pump (A) 1,9 2,2 2,4 2,7 3,1 3,8 4,3 4,6 Available pressure with high prevalence hydronic kit (kpa) Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

27 Heat Pump - High Energy Efficiency version ,7 158,2 178,1 207,7 244,4 280,4 312,8 368,0 407,9 473,0 47,4 53,8 60,6 66,2 84,6 94,8 113,4 127,3 142,7 168,5 62,8 71,4 80,7 87,7 112,7 125,4 150,7 168,6 189,6 224,5 47,5 46,5 46,2 48,0 45,5 47,0 45,0 46,5 45,8 45,0 24,8 27,6 31,1 36,3 42,7 49,0 54,7 64,3 71,3 82, ,99 2,94 2,94 3,14 2,89 2,96 2,76 2,89 2,86 2,81 4,17 4,15 4,14 4,25 4,11 4,15 4,02 4,11 4,09 4,06 160,2 178,7 201,2 234,7 276,2 316,9 353,5 415,9 461,0 534,4 46,0 52,1 58,8 64,2 82,1 92,0 110,0 123,5 138,4 163,5 27,5 30,7 34,6 40,4 47,5 54,5 60,8 71,5 79,3 91, ,7-10,3-10,2-10,9-9,8-10,7-10,0-10,7-10,2-9,5 3,48 3,43 3,42 3,66 3,36 3,44 3,21 3,37 3,33 3,27 52,0 53,3 53,2 54,8 54,9 56,0 56,6 57,9 58,6 58, ,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,40 2,40 2,30 3,27 3,36 3,86 4,30 5,06 5,61 6,51 5,0 5,0 4,7 6,8 6,9 8,0 8,9 10,5 11,6 13, ,5 2,6 2,7 4,6 4,7 5,4 6,1 7,1 7,9 9,2 5,1 5,4 5,6 9,5 9,8 11,2 12,5 14,8 16,4 19, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

28 Technical Sheets SA-H-S Size Cooling capacity 46,9 52,0 60,7 66,4 81,2 94,8 107,2 119,6 Power input 21,5 25,0 27,3 31,4 37,3 42,8 48,5 54,4 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 Maximum outdoor air temperature ( C) 42,0 41,0 42,0 41,0 42,5 42,5 42,3 42,0 Water flow (m3/h) 8,1 9,0 10,4 11,4 14,0 16,3 18,4 20,6 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 2,18 2,08 2,22 2,12 2,18 2,22 2,21 2,20 ESEER (kw/kw) 3,53 3,43 3,57 3,46 3,52 3,57 3,56 3,55 Heat capacity 53,0 58,8 68,6 75,1 91,8 107,2 121,1 135,2 Power input (heating mode) 19,3 22,4 24,5 28,2 33,6 38,5 43,6 48,9 Water flow (heating mode) (m3/h) 9,1 10,1 11,8 12,9 15,8 18,4 20,8 23,3 Pressure loss of hydronic circuit (kpa) Minimum operating outdoor air temperature in heating mode ( C) -10,1-9,5-9,5-8,9-11,0-10,4-9,7-9,1 COP (kw/kw) 2,74 2,62 2,80 2,66 2,73 2,79 2,78 2,77 Sound pressure at 10m (db(a)) 42,2 42,2 42,2 43,2 45,9 46,1 45,7 45,6 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,68 0,74 1,03 1,11 1,30 1,43 1,53 2,26 Amperage of low pressure pump (A) 1,4 1,5 2,1 2,3 2,7 3,0 3,2 4,7 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 1,1 1,2 1,4 1,5 1,8 2,0 2,1 2,8 Amperage of high pressure pump (A) 2,3 2,5 2,9 3,1 3,6 4,1 4,4 5,9 Available pressure with high prevalence hydronic kit (kpa) Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

29 Heat Pump - Silent version ,5 151,4 174,7 210,7 242,9 271,2 306,8 355,6 412,0 465,2 534,6 61,4 67,3 80,2 97,4 105,0 130,1 133,7 161,5 194,0 219,9 259,5 76,2 83,9 97,5 117,6 131,2 153,0 164,4 190,5 231,6 265,0 305,4 42,0 42,8 41,5 41,5 43,5 40,3 43,1 42,0 41,3 41,2 40,3 23,5 26,0 30,1 36,2 41,8 46,7 52,8 61,2 70,9 80,0 92, ,22 2,25 2,18 2,16 2,31 2,08 2,29 2,20 2,12 2,12 2,06 3,57 3,60 3,53 3,51 3,66 3,43 3,64 3,55 3,47 3,46 3,40 154,2 171,1 197,4 238,1 274,5 306,5 346,7 401,8 465,6 525,7 604,1 55,1 60,5 72,0 87,5 94,3 116,9 120,5 145,4 174,1 198,1 233,5 26,5 29,4 34,0 41,0 47,2 52,7 59,6 69,1 80,1 90,4 103, ,3-9,8-9,1-8,6-9,6-8,4-9,9-9,0-9,9-9,1-8,0 2,80 2,83 2,74 2,72 2,91 2,62 2,88 2,76 2,67 2,65 2,59 46,2 47,8 48,0 48,1 49,0 49,5 51,3 52,4 52,2 52,0 52, ,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,37 2,41 2,35 3,28 3,29 3,67 4,15 4,81 5,58 6,30 7,24 4,9 5,0 4,8 6,8 6,8 7,6 8,6 9,9 11,5 13,0 14, ,1 3,2 3,4 1,2 4,6 5,2 5,9 6,8 7,9 8,9 10,2 6,3 6,7 6,9 2,4 9,6 10,7 12,1 14,0 16,3 18,4 21, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

30 Technical Sheets SA-H-E-S Size Cooling capacity 45,5 51,9 58,6 66,2 76,6 89,3 104,7 116,7 Power input 17,3 19,8 22,5 25,8 28,8 34,3 38,7 45,2 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 Maximum outdoor air temperature ( C) 47,0 46,0 45,8 47,3 47,5 46,4 47,1 45,5 Water flow (m3/h) 7,8 8,9 10,1 11,4 13,2 15,4 18,0 20,1 Pressure loss of hydronic circuit (kpa) EER (kw/kw) 2,64 2,63 2,61 2,56 2,66 2,60 2,71 2,58 ESEER (kw/kw) 3,94 3,93 3,91 3,88 3,95 3,91 3,99 3,89 Heat capacity 51,4 58,6 66,3 74,8 86,6 100,9 118,3 131,9 Power input (heating mode) 15,7 18,0 20,4 23,5 26,3 31,2 35,2 41,1 Water flow (heating mode) (m3/h) 8,8 10,1 11,4 12,9 14,9 17,4 20,3 22,7 Pressure loss of hydronic circuit (kpa) Minimum operating outdoor air temperature in heating mode ( C) -10,5-10,2-9,6-10,7-10,9-10,6-10,2-9,5 COP (kw/kw) 3,28 3,26 3,24 3,18 3,29 3,23 3,36 3,21 Sound pressure at 10m (db(a)) 42,2 42,2 42,2 45,1 45,7 45,4 45,7 45,2 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Buffer tank capacity (lt) Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,66 0,74 0,82 0,90 1,24 1,38 1,51 1,58 Amperage of low pressure pump (A) 1,4 1,5 1,7 1,9 2,6 2,9 3,1 3,3 Available pressure with low prevalence hydronic kit (kpa) Power input of high pressure pump (A) 1,1 1,2 1,3 1,5 1,7 1,9 2,1 2,2 Amperage of high pressure pump (A) 2,2 2,5 2,8 3,1 3,5 3,9 4,3 4,6 Available pressure with high prevalence hydronic kit (kpa) Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

31 Heat Pump - High Energy Efficiency - Silent version ,7 150,3 169,2 197,3 232,2 266,4 297,2 349,6 387,5 449,3 50,6 57,3 64,7 70,5 90,3 101,0 121,0 135,5 152,2 179,9 62,8 71,4 80,7 87,7 112,7 125,4 150,7 168,6 189,6 224,5 47,5 46,5 46,2 48,0 45,5 47,0 45,0 46,5 45,8 45,0 23,2 25,8 29,1 33,9 39,9 45,8 51,1 60,1 66,7 77, ,66 2,62 2,61 2,80 2,57 2,64 2,46 2,58 2,55 2,50 3,96 3,92 3,92 4,05 3,88 3,94 3,79 3,89 3,86 3,82 152,2 169,8 191,2 223,0 262,4 301,0 335,8 395,1 437,9 507,7 46,0 52,1 58,8 64,2 82,1 92,0 110,0 123,5 138,4 163,5 26,2 29,2 32,9 38,4 45,1 51,8 57,8 68,0 75,3 87, ,7-10,3-10,2-10,9-9,8-10,7-10,0-10,7-10,2-9,5 3,31 3,26 3,25 3,47 3,20 3,27 3,05 3,20 3,16 3,11 46,9 47,6 47,6 49,0 49,1 50,5 50,8 52,5 53,2 52, ,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 1,63 2,41 2,38 2,12 3,14 3,61 4,02 4,73 5,25 6,08 3,4 5,0 4,9 4,4 6,5 7,4 8,3 9,8 10,8 12, ,4 3,2 3,3 3,2 4,4 5,1 5,7 6,7 7,4 8,6 4,9 6,6 6,9 6,6 9,2 10,5 11,7 13,8 15,3 17, Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

32 Technical Sheets SA-C-N Condensing Unit - Basic version Size Cooling capacity 51,1 57,3 66,3 73,2 89,5 104,0 118,1 131,8 149,6 166,0 190,6 232,1 269,6 298,1 Power input 20,1 23,4 25,5 29,3 35,0 40,1 45,4 50,9 57,4 63,0 75,0 91,2 98,3 121,8 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 76,2 83,9 97,5 117,6 131,2 153,0 Maximum outdoor air temperature ( C) 41,2 39,8 41,2 39,8 41,3 41,5 41,1 40,8 41,0 41,8 40,7 40,3 42,0 39,2 EER (kw/kw) 2,5 2,5 2,6 2,5 2,6 2,6 2,6 2,6 2,6 2,6 2,5 2,5 2,7 2,4 ESEER (kw/kw) 3,86 3,79 3,90 3,82 3,87 3,90 3,91 3,90 3,91 3,93 3,86 3,86 4,01 3,78 Sound pressure at 10m (db(a)) 47,4 47,4 47,3 49,1 51,6 52,0 51,2 51,1 52,1 53,6 54,0 54,1 54,8 55,6 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

33 Technical Sheets SA-C-E Condensing Unit - High Energy Efficiency version Size Cooling capacity 48,9 55,8 63,2 72,6 82,8 96,3 112,8 125,8 145,8 162,8 183,2 213,7 251,5 289,2 Power input 16,2 18,5 21,1 24,3 27,1 32,2 36,2 42,4 47,4 53,8 60,6 66,2 84,6 94,8 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 62,8 71,4 80,7 87,7 112,7 125,4 Maximum outdoor air temperature ( C) 46,8 46,4 45,5 46,3 47,1 46,1 46,8 45,2 46,7 46,0 45,7 47,5 45,0 46,4 EER (kw/kw) 3,0 3,0 3,0 3,0 3,1 3,0 3,1 3,0 3,1 3,0 3,0 3,2 3,0 3,1 ESEER (kw/kw) 4,19 4,19 4,18 4,17 4,21 4,17 4,24 4,16 4,22 4,19 4,19 4,30 4,16 4,21 Sound pressure at 10m (db(a)) 47,3 47,4 47,4 47,3 51,2 50,8 51,2 50,4 52,0 53,3 53,2 54,8 54,9 56,0 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

34 Technical Sheets SA-C-S Condensing Unit - Silent version Size Cooling capacity 48,6 54,5 63,0 69,5 85,0 98,8 112,2 125,2 142,1 157,7 181,1 220,5 256,1 283,2 Power input 20,1 23,4 25,5 29,3 35,0 40,1 45,4 50,9 57,4 63,0 75,0 91,2 98,3 121,8 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 76,2 83,9 97,5 117,6 131,2 153,0 Maximum outdoor air temperature ( C) 41,2 39,8 41,2 39,8 41,3 41,5 41,1 40,8 41,0 41,8 40,7 40,3 42,0 39,2 EER (kw/kw) 2,5 2,5 2,6 2,5 2,6 2,6 2,6 2,6 2,6 2,6 2,5 2,5 2,7 2,4 ESEER (kw/kw) 3,86 3,79 3,90 3,82 3,87 3,90 3,91 3,90 3,91 3,93 3,86 3,86 4,01 3,78 Sound pressure at 10m (db(a)) 42,2 42,2 42,2 45,1 43,2 45,4 45,7 45,2 46,9 47,6 47,6 49,0 49,1 50,5 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg)

35 Technical Sheets SA-C-E-S Condensing Unit - High Energy Efficiency - Silent version Size Cooling capacity 46,5 53,0 60,0 69,0 78,6 91,4 107,2 119,5 138,6 154,6 174,1 203,0 238,9 274,8 Power input 16,2 18,5 21,1 24,3 27,1 32,2 36,2 42,4 47,4 53,8 60,6 66,2 84,6 94,8 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 62,8 71,4 80,7 87,7 112,7 125,4 Maximum outdoor air temperature ( C) 46,8 46,4 45,5 46,3 47,1 46,1 46,8 45,2 46,7 46,0 45,7 47,5 45,0 46,4 EER (kw/kw) 3,0 3,0 3,0 3,0 3,1 3,0 3,1 3,0 3,1 3,0 3,0 3,2 3,0 3,1 ESEER (kw/kw) 4,19 4,19 4,18 4,17 4,21 4,17 4,24 4,16 4,22 4,19 4,19 4,30 4,16 4,21 Sound pressure at 10m (db(a)) 47,4 47,4 47,3 49,1 51,6 52,0 51,2 51,1 52,1 53,6 54,0 54,1 54,8 55,6 Total air flow (m3/h) Number of compressors (n.) Number of circuits (n.) Rated current at nominal conditions (A) Maximum current at full load (A) Maximum starting current (A) Number of antivibrating supports Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO

36 Performances SA-N Outlet water temperature ( C) ,5 19,0 51,1 19,0 52,7 19,1 54,3 19,2 57,4 19,3 65,3 19,7 66,9 19,9 6 55,0 22,0 56,8 22,1 58,5 22,2 60,3 22,2 63,8 22,4 72,5 22,8 74,3 23,0 7 64,1 24,1 66,2 24,1 68,2 24,2 70,3 24,3 74,4 24,5 84,6 24,9 86,7 25,2 8 70,2 27,6 72,5 27,7 74,7 27,8 76,9 27,9 81,4 28,1 92,6 28,6 94,9 28, ,9 33,0 88,6 33,1 91,3 33,2 94,1 33,3 99,6 33,6 113,3 34,2 116,0 34, ,2 37,7 103,4 37,9 106,6 38,0 109,8 38,2 116,2 38,4 132,2 39,1 135,4 39, ,3 42,8 116,9 42,9 120,5 43,1 124,1 43,2 131,3 43,6 149,4 44,3 153,0 44, ,4 47,9 130,5 48,1 134,5 48,3 138,5 48,5 146,6 48,8 166,8 49,7 170,8 50, ,2 54,1 148,8 54,3 153,4 54,5 158,0 54,7 167,2 55,1 190,2 56,1 194,8 56, ,0 59,4 165,1 59,6 170,2 59,8 175,3 60,0 185,5 60,4 211,1 61,5 216,2 62, ,6 70,7 190,5 70,9 196,4 71,2 202,3 71,5 214,1 72,0 243,6 73,3 249,5 74, ,7 85,9 229,8 86,2 236,9 86,5 244,0 86,8 258,2 87,4 293,7 89,0 300,8 89, ,8 92,6 264,9 92,9 273,1 93,2 281,3 93,6 297,7 94,2 338,7 95,9 346,9 96, ,5 114,6 291,5 115,1 300,5 115,5 309,5 115,9 327,6 116,7 372,7 118,8 381,7 120, ,3 118,3 334,6 118,7 345,0 119,1 355,3 119,6 376,0 120,4 427,8 122,6 438,1 123, ,8 142,6 387,8 143,2 399,8 143,7 411,8 144,2 435,8 145,2 495,7 147,8 507,7 149, ,4 170,8 449,3 171,4 463,2 172,1 477,1 172,7 504,9 173,9 574,4 177,0 588,3 178, ,0 192,8 510,8 193,5 526,6 194,2 542,4 194,9 573,9 196,3 652,9 199,8 668,7 201, ,4 214,0 580,3 214,8 598,3 215,6 616,2 216,4 652,1 217,9 741,9 221,8 759,8 224, ,8 256,3 685,0 257,2 706,2 258,2 727,4 259,1 769,8 261,0 875,7 265,6 896,9 268, ,3 291,3 767,0 292,3 790,7 293,4 814,4 294,5 861,9 296,6 980,5 301,9 1004,2 305,0 5 47,1 20,0 48,6 20,1 50,1 20,1 51,6 20,2 54,7 20,4 62,2 20,7 63,7 20,9 6 52,3 23,2 54,0 23,3 55,7 23,4 57,3 23,4 60,7 23,6 69,0 24,0 70,7 24,3 7 61,0 25,4 63,0 25,4 64,9 25,5 66,9 25,6 70,8 25,8 80,5 26,3 82,5 26,6 8 66,8 29,1 68,9 29,2 71,1 29,3 73,2 29,5 77,5 29,7 88,1 30,2 90,3 30, ,7 34,7 84,3 34,9 86,9 35,0 89,5 35,1 94,7 35,4 107,8 36,0 110,4 36, ,4 39,8 98,4 39,9 101,5 40,1 104,5 40,2 110,6 40,5 125,8 41,2 128,8 41, ,8 45,1 111,2 45,3 114,6 45,4 118,1 45,6 125,0 45,9 142,1 46,7 145,6 47, ,3 50,5 124,1 50,7 128,0 50,9 131,8 51,1 139,5 51,4 158,7 52,4 162,5 52, ,2 57,0 141,6 57,2 146,0 57,4 150,4 57,7 159,1 58,1 181,0 59,1 185,4 59, ,2 62,6 157,1 62,8 162,0 63,0 166,8 63,2 176,5 63,7 200,8 64,8 205,7 65, ,7 74,5 181,3 74,8 186,9 75,0 192,5 75,3 203,7 75,9 231,8 77,2 237,4 78, ,9 90,5 218,6 90,9 225,4 91,2 232,1 91,5 245,7 92,2 279,5 93,8 286,2 94, ,3 97,6 252,1 97,9 259,9 98,3 267,7 98,6 283,3 99,3 322,3 101,1 330,1 102, ,8 120,8 277,4 121,3 285,9 121,7 294,5 122,2 311,7 123,0 354,6 125,2 363,2 126, ,5 124,7 318,4 125,1 328,2 125,6 338,1 126,0 357,8 126,9 407,0 129,2 416,8 130, ,6 150,3 369,0 150,9 380,4 151,4 391,8 152,0 414,6 153,1 471,7 155,8 483,1 157, ,3 180,0 427,5 180,7 440,7 181,4 454,0 182,0 480,4 183,3 546,5 186,6 559,8 188, ,9 203,2 486,0 204,0 501,0 204,7 516,0 205,5 546,1 206,9 621,2 210,6 636,3 212, ,1 225,6 552,2 226,4 569,2 227,2 586,3 228,1 620,5 229,7 705,9 233,8 722,9 236, ,6 270,1 651,8 271,1 671,9 272,1 692,1 273,1 732,4 275,0 833,2 279,9 853,4 282, ,2 307,0 729,8 308,1 752,3 309,2 774,9 310,4 820,0 312,6 932,9 318,2 955,5 321,5 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 36

37 SA-N Outlet water temperature ( C) ,7 22,0 46,2 22,2 47,6 22,4 49,0 22,5 51,9 22,9 59,0 23,8 6 49,7 25,5 51,2 25,7 52,8 25,9 54,4 26,1 57,6 26,5 65,5 27,6 7 57,9 27,9 59,8 28,1 61,6 28,4 63,5 28,6 67,2 29,0 76,4 30,1 8 63,4 32,1 65,4 32,3 67,4 32,6 69,5 32,8 73,5 33,3 83,6 34, ,5 38,3 80,0 38,6 82,5 38,9 85,0 39,2 89,9 39,8 102,3 41, ,5 43,8 93,4 44,2 96,3 44,5 99,2 44,8 104,9 45,5 119,4 47, ,3 49,7 105,5 50,0 108,8 50,4 112,1 50,8 118,6 51,6 134,9 53, ,2 55,7 117,8 56,1 121,5 56,5 125,1 57,0 132,4 57,8 150,6 60, ,2 62,8 134,4 63,3 138,5 63,8 142,7 64,3 151,0 65,3 171,8 67, ,5 68,9 149,1 69,4 153,7 70,0 158,3 70,5 167,5 71,6 190,6 74, ,7 82,1 172,0 82,7 177,4 83,3 182,7 84,0 193,3 85,3 219,9 88, ,1 99,7 207,5 100,5 213,9 101,3 220,3 102,0 233,1 103,6 265,2 107, ,8 107,5 239,2 108,3 246,6 109,1 254,0 110,0 268,8 111,7 305,8 115, ,1 133,1 263,2 134,1 271,4 135,2 279,5 136,2 295,8 138,3 336,5 143, ,8 137,3 302,1 138,4 311,5 139,4 320,8 140,5 339,5 142,7 386,2 148, ,3 165,6 350,2 166,9 361,0 168,2 371,8 169,5 393,5 172,1 447,6 178, ,2 198,3 405,7 199,9 418,3 201,4 430,8 202,9 455,9 206,1 518,7 213, ,9 223,9 461,2 225,6 475,5 227,3 489,7 229,1 518,2 232,6 589,6 241, ,8 248,5 524,0 250,4 540,2 252,3 556,4 254,3 588,8 258,2 669,9 268, ,4 297,5 618,5 299,9 637,7 302,2 656,8 304,5 695,1 309,2 790,7 321, ,1 338,2 692,5 340,8 714,0 343,4 735,4 346,1 778,2 351,4 885,3 364,8 5 43,1 23,5 44,5 23,7 45,9 23,9 47,3 24,1 50,0 24,5 6 47,9 27,3 49,4 27,5 50,9 27,7 52,5 27,9 55,5 28,4 7 55,8 29,8 57,6 30,1 59,4 30,3 61,2 30,5 64,7 31,0 8 61,1 34,3 63,1 34,6 65,0 34,8 67,0 35,1 70,9 35, ,8 40,9 77,1 41,2 79,5 41,5 81,9 41,8 86,7 42, ,3 46,8 90,0 47,2 92,8 47,6 95,6 47,9 101,2 48, ,6 53,1 101,7 53,5 104,9 53,9 108,0 54,3 114,3 55, ,1 59,5 113,6 59,9 117,1 60,4 120,6 60,9 127,6 61, ,6 67,1 129,6 67,7 133,6 68,2 137,6 68,7 145,6 69, ,3 73,6 143,8 74,2 148,2 74,8 152,6 75,4 161,5 76, ,8 87,7 165,9 88,4 171,0 89,1 176,1 89,8 186,4 91, ,9 106,6 200,0 107,4 206,2 108,2 212,4 109,0 224,8 110, ,5 114,8 230,7 115,7 237,8 116,6 244,9 117,5 259,2 119, ,9 142,2 253,8 143,3 261,6 144,5 269,5 145,6 285,2 147, ,3 146,7 291,3 147,9 300,3 149,0 309,3 150,2 327,4 152, ,2 177,0 337,6 178,4 348,1 179,7 358,5 181,1 379,4 183, ,1 211,9 391,2 213,6 403,3 215,2 415,4 216,9 439,6 220, ,9 239,2 444,7 241,1 458,4 243,0 472,2 244,8 499,7 248, ,6 265,6 505,2 267,6 520,9 269,7 536,5 271,8 567,7 275, ,9 318,0 596,4 320,5 614,8 322,9 633,3 325,4 670,2 330, ,1 361,4 667,7 364,2 688,4 367,0 709,0 369,8 750,3 375,5 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 37

38 SA-E Outlet water temperature ( C) ,1 15,2 49,7 15,3 51,2 15,4 52,7 15,4 55,8 15,5 63,5 15,8 63,1 16,0 6 54,8 17,4 56,6 17,5 58,3 17,6 60,1 17,6 63,6 17,8 72,3 18,1 71,9 18,3 7 62,0 19,8 64,0 19,9 65,9 20,0 67,9 20,1 71,9 20,2 81,8 20,6 81,2 20,8 8 70,0 22,9 72,2 22,9 74,5 23,0 76,7 23,1 81,2 23,3 92,3 23,7 91,8 23, ,0 25,5 83,6 25,6 86,1 25,7 88,7 25,8 93,9 26,0 106,8 26,5 106,1 26, ,4 30,3 97,4 30,4 100,4 30,5 103,4 30,6 109,4 30,9 124,5 31,4 123,7 31, ,6 34,1 114,2 34,3 117,7 34,4 121,2 34,5 128,3 34,8 146,0 35,4 145,0 35, ,3 39,9 127,3 40,1 131,2 40,2 135,1 40,3 143,0 40,6 162,7 41,4 161,7 41, ,3 44,7 146,9 44,8 151,4 45,0 155,9 45,2 165,0 45,5 187,7 46,3 186,5 46, ,8 50,6 163,9 50,8 169,0 51,0 174,0 51,2 184,2 51,6 209,5 52,5 208,2 53, ,8 57,1 184,5 57,3 190,2 57,5 195,9 57,8 207,3 58,2 235,9 59,2 234,4 59, ,5 62,3 215,2 62,5 221,9 62,8 228,5 63,0 241,8 63,4 275,1 64,6 273,4 65, ,4 79,7 253,2 80,0 261,1 80,3 268,9 80,6 284,6 81,2 323,7 82,6 321,7 83, ,5 89,3 290,5 89,7 299,5 90,0 308,5 90,3 326,5 91,0 371,4 92,6 369,0 93, ,1 106,8 324,1 107,2 334,1 107,6 344,1 108,0 364,2 108,8 414,3 110,7 411,7 111, ,5 119,9 381,3 120,4 393,1 120,8 404,9 121,3 428,5 122,1 487,4 124,3 484,4 125, ,6 134,4 422,6 134,9 435,7 135,4 448,8 135,9 474,9 136,8 540,3 139,3 536,9 140, ,9 158,7 490,0 159,3 505,2 159,9 520,3 160,5 550,6 161,6 626,4 164,5 622,5 166, ,1 187,2 584,2 187,9 602,3 188,6 620,3 189,3 656,5 190,7 746,8 194,0 742,1 196, ,1 202,3 625,4 203,1 644,7 203,8 664,1 204,5 702,8 206,0 799,5 209,7 794,5 211,9 5 45,8 16,1 47,2 16,1 48,7 16,2 50,2 16,2 53,1 16,4 60,4 16,7 60,0 16,8 6 52,2 18,4 53,8 18,4 55,5 18,5 57,2 18,6 60,5 18,7 68,8 19,0 68,4 19,2 7 59,0 20,9 60,9 21,0 62,7 21,1 64,6 21,1 68,4 21,3 77,8 21,7 77,3 21,9 8 66,6 24,1 68,7 24,2 70,9 24,3 73,0 24,4 77,2 24,5 87,9 25,0 87,3 25, ,0 26,9 79,5 27,0 82,0 27,1 84,4 27,2 89,3 27,4 101,6 27,9 101,0 28, ,8 31,9 92,7 32,1 95,5 32,2 98,4 32,3 104,1 32,5 118,5 33,1 117,7 33, ,3 36,0 108,6 36,1 112,0 36,2 115,4 36,4 122,1 36,6 138,9 37,3 138,0 37, ,4 42,1 121,1 42,2 124,8 42,4 128,6 42,5 136,1 42,8 154,8 43,6 153,8 44, ,4 47,1 139,7 47,3 144,0 47,4 148,4 47,6 157,0 47,9 178,6 48,8 177,5 49, ,1 53,4 155,9 53,6 160,8 53,8 165,6 54,0 175,2 54,3 199,3 55,3 198,1 55, ,1 60,2 175,6 60,4 181,0 60,6 186,4 60,9 197,3 61,3 224,4 62,4 223,0 63, ,4 65,7 204,8 65,9 211,1 66,2 217,4 66,4 230,1 66,9 261,8 68,1 260,1 68, ,5 84,0 241,0 84,3 248,4 84,6 255,9 84,9 270,8 85,6 308,0 87,1 306,1 88, ,9 94,1 276,4 94,5 285,0 94,8 293,5 95,2 310,6 95,9 353,4 97,6 351,1 98, ,8 112,6 308,4 113,0 317,9 113,4 327,4 113,8 346,5 114,6 394,2 116,7 391,7 117, ,6 126,4 362,8 126,9 374,0 127,3 385,2 127,8 407,7 128,7 463,8 131,0 460,8 132, ,7 141,7 402,1 142,2 414,6 142,7 427,0 143,2 451,9 144,2 514,1 146,8 510,8 148, ,8 167,3 466,2 167,9 480,6 168,5 495,1 169,1 523,9 170,4 596,0 173,4 592,3 175, ,7 197,3 555,8 198,1 573,0 198,8 590,2 199,5 624,6 200,9 710,6 204,5 706,1 206, ,7 213,2 595,1 214,0 613,5 214,8 631,9 215,6 668,7 217,1 760,7 221,0 755,9 223,3 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 38

39 SA-E Outlet water temperature ( C) ,9 18,9 43,2 19,1 44,6 19,2 45,9 19,4 48,6 19,7 55,3 20,4 54,9 20,9 6 47,7 21,6 49,3 21,8 50,8 22,0 52,3 22,1 55,3 22,5 63,0 23,3 62,6 23,9 7 54,0 24,6 55,7 24,8 57,4 25,0 59,1 25,2 62,6 25,6 71,2 26,6 70,7 27,1 8 60,9 28,4 62,9 28,6 64,8 28,8 66,8 29,0 70,7 29,5 80,4 30,6 79,9 31, ,5 31,7 72,7 31,9 75,0 32,2 77,2 32,4 81,7 32,9 93,0 34,2 92,4 34, ,2 37,6 84,8 37,9 87,4 38,2 90,0 38,5 95,3 39,1 108,4 40,6 107,7 41, ,3 42,4 99,4 42,7 102,5 43,0 105,6 43,4 111,7 44,0 127,1 45,7 126,3 46, ,4 49,5 110,8 49,9 114,2 50,3 117,7 50,7 124,5 51,5 141,6 53,4 140,8 54, ,9 55,4 127,8 55,9 131,8 56,3 135,8 56,7 143,7 57,6 163,4 59,8 162,4 61, ,3 62,8 142,7 63,3 147,1 63,8 151,5 64,3 160,3 65,3 182,4 67,8 181,2 69, ,7 70,9 160,6 71,4 165,6 72,0 170,6 72,5 180,5 73,6 205,3 76,5 204,1 78, ,6 77,3 187,4 77,9 193,1 78,5 198,9 79,1 210,5 80,3 239,5 83,4 238,0 85, ,7 98,9 220,5 99,7 227,3 100,5 234,1 101,2 247,8 102,8 281,8 106,7 280,1 109, ,1 110,8 252,9 111,7 260,7 112,5 268,6 113,4 284,2 115,2 323,3 119,6 321,3 122, ,4 132,5 282,1 133,5 290,9 134,6 299,6 135,6 317,0 137,7 360,7 143,0 358,4 146, ,7 148,8 331,9 150,0 342,2 151,1 352,5 152,3 373,0 154,6 424,3 160,5 421,7 164, ,6 166,7 367,9 168,0 379,3 169,3 390,7 170,6 413,5 173,3 470,4 179,9 467,4 183, ,4 196,9 426,6 198,5 439,8 200,0 453,0 201,6 479,4 204,6 545,3 212,5 541,9 217, ,9 232,3 508,6 234,1 524,3 235,9 540,1 237,7 571,5 241,4 650,2 250,6 646,1 256, ,6 251,0 544,5 253,0 561,3 254,9 578,2 256,9 611,8 260,8 696,0 270,8 691,7 276,9 5 38,0 22,1 39,2 22,3 40,4 22,4 41,6 22,6 44,1 23,0 6 43,3 25,3 44,7 25,5 46,1 25,7 47,4 25,9 50,2 26,3 7 48,9 28,8 50,5 29,0 52,1 29,2 53,6 29,4 56,8 29,9 8 55,3 33,1 57,0 33,4 58,8 33,7 60,6 33,9 64,1 34, ,9 37,0 66,0 37,3 68,0 37,6 70,1 37,9 74,1 38, ,5 43,9 76,9 44,3 79,3 44,6 81,7 45,0 86,4 45, ,4 49,5 90,2 49,9 93,0 50,3 95,7 50,6 101,3 51, ,4 57,9 100,5 58,3 103,6 58,8 106,7 59,2 112,9 60, ,4 64,8 116,0 65,3 119,6 65,8 123,1 66,3 130,3 67, ,4 73,4 129,4 74,0 133,4 74,5 137,4 75,1 145,4 76, ,2 82,8 145,7 83,4 150,2 84,1 154,7 84,7 163,7 86, ,7 90,3 169,9 91,0 175,2 91,7 180,5 92,4 191,0 93, ,8 115,6 200,0 116,5 206,2 117,4 212,4 118,3 224,7 120, ,3 129,5 229,4 130,5 236,5 131,5 243,6 132,5 257,8 134, ,0 154,8 255,9 156,0 263,8 157,2 271,8 158,4 287,6 160, ,8 173,9 301,1 175,2 310,4 176,6 319,7 177,9 338,4 180, ,4 194,8 333,8 196,3 344,1 197,8 354,4 199,4 375,1 202, ,0 230,1 387,0 231,9 398,9 233,7 410,9 235,5 434,8 239, ,1 271,4 461,4 273,5 475,6 275,6 489,9 277,8 518,4 282, ,6 293,3 493,9 295,6 509,2 297,8 524,4 300,1 555,0 304,7 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 39

40 SA-TOP Outlet water temperature ( C) ,5 15,1 51,1 14,2 52,7 15,2 54,3 15,2 57,4 15,3 65,3 15,6 66,9 15,8 6 59,8 18,0 61,7 18,1 63,6 18,2 65,5 18,2 69,4 18,4 78,9 18,7 80,8 18,9 7 67,4 20,5 69,6 20,6 71,7 20,6 73,9 20,7 78,2 20,9 89,0 21,2 91,1 21,4 8 77,6 22,9 80,0 23,0 82,5 23,1 85,0 23,2 89,9 23,4 102,3 23,8 104,8 24, ,1 25,8 89,9 25,9 92,7 26,0 95,5 26,1 101,0 26,3 114,9 26,8 117,7 27, ,6 29,9 105,9 30,0 109,2 30,1 112,4 30,2 119,0 30,4 135,4 31,0 138,6 31, ,2 35,1 119,9 35,2 123,6 35,4 127,3 33,6 134,7 34,1 153,3 35,4 157,0 36, ,1 40,9 138,4 41,1 142,6 41,2 146,9 39,2 155,5 39,8 176,9 41,3 181,2 42, ,4 45,6 156,3 45,7 161,1 45,9 165,9 43,6 175,6 44,3 199,8 45,9 204,6 47, ,8 51,8 174,2 52,0 179,6 52,2 185,0 49,6 195,7 50,3 222,7 52,3 228,1 53, ,5 57,7 202,8 57,9 209,0 58,1 215,3 55,2 227,9 56,1 259,2 58,2 265,5 59, ,7 69,9 240,1 70,2 247,5 70,4 254,9 66,9 269,8 67,9 306,9 70,5 314,3 72, ,8 80,5 280,5 80,8 289,2 81,0 297,8 77,0 315,2 78,2 358,6 81,2 367,2 83, ,8 91,5 309,4 91,8 319,0 92,2 328,5 87,5 347,7 88,9 395,5 92,3 405,1 94, ,6 105,7 364,8 106,0 376,1 100,3 387,4 101,1 410,0 102,6 466,4 106,6 477,7 108, ,1 121,5 412,8 121,9 425,6 115,3 438,4 116,2 463,9 118,0 527,8 122,5 540,5 125, ,2 137,3 461,5 137,8 475,7 130,3 490,0 131,3 518,6 133,3 589,9 138,4 604,2 141, ,6 159,5 536,2 160,1 552,8 151,5 569,4 152,6 602,5 155,0 685,5 160,9 702,0 164,5 5 47,1 15,9 48,6 15,9 50,1 16,0 51,6 16,1 54,6 16,2 62,1 16,5 63,6 16,6 6 56,9 19,0 58,7 19,1 60,6 19,2 62,4 19,2 66,0 19,4 75,1 19,7 76,9 19,9 7 64,2 21,6 66,2 21,7 68,3 21,7 70,3 21,8 74,4 22,0 84,6 22,4 86,7 22,6 8 73,8 24,2 76,1 24,3 78,5 24,3 80,9 24,4 85,6 24,6 97,3 25,1 99,7 25, ,9 27,2 85,6 27,3 88,2 27,4 90,8 27,5 96,1 27,7 109,4 28,2 112,0 28, ,6 31,5 100,8 31,6 103,9 31,7 107,0 31,8 113,2 32,1 128,8 32,6 131,9 33, ,6 37,0 114,1 37,1 117,6 37,3 121,1 37,6 128,2 38,1 145,8 39,6 149,4 40, ,6 43,1 131,7 43,3 135,7 43,5 139,8 43,8 147,9 44,5 168,3 46,2 172,4 47, ,1 48,0 148,7 48,2 153,3 48,4 157,9 48,7 167,1 49,5 190,1 51,4 194,7 52, ,6 54,6 165,7 54,8 170,9 55,0 176,0 55,4 186,2 56,3 211,9 58,4 217,0 59, ,0 60,8 192,9 61,1 198,9 61,3 204,9 61,8 216,8 62,7 246,6 65,1 252,6 66, ,4 73,7 228,4 73,9 235,5 74,2 242,6 74,8 256,7 75,9 292,0 78,8 299,1 80, ,6 84,8 266,9 85,1 275,1 85,4 283,4 86,1 299,9 87,4 341,2 90,7 349,4 92, ,3 96,4 294,4 96,8 303,5 97,1 312,6 97,9 330,8 99,4 376,3 103,2 385,4 105, ,4 111,4 347,1 111,8 357,9 112,2 368,6 113,0 390,1 114,8 443,8 119,2 454,5 121, ,7 128,0 392,8 128,5 405,0 129,0 417,1 130,0 441,4 132,0 502,2 137,0 514,3 140, ,5 144,7 439,1 145,2 452,7 145,7 466,2 146,8 493,4 149,1 561,3 154,8 574,9 158, ,4 168,1 510,2 168,7 526,0 169,4 541,7 170,7 573,3 173,3 652,2 179,9 668,0 183,9 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 40

41 SA-TOP Outlet water temperature ( C) ,7 17,5 46,1 17,6 47,6 16,8 49,0 16,9 51,8 17,0 59,0 17,3 6 54,0 21,0 55,7 20,1 57,5 20,1 59,2 20,2 62,6 20,3 71,3 20,7 7 60,9 23,8 62,8 22,8 64,8 22,8 66,7 22,9 70,6 23,1 80,3 23,5 8 70,0 26,6 72,3 25,5 74,5 25,6 76,7 25,7 81,2 25,9 92,4 26, ,7 30,0 81,2 28,7 83,7 28,8 86,2 28,9 91,2 29,1 103,8 29, ,7 34,7 95,6 33,2 98,6 33,3 101,5 33,4 107,4 33,7 122,2 34, ,9 40,8 108,3 39,0 111,6 39,2 115,0 41,7 121,7 42,3 138,4 44, ,1 47,5 124,9 45,5 128,8 45,7 132,7 48,6 140,4 49,4 159,7 51, ,7 52,9 141,1 50,6 145,5 50,8 149,8 54,1 158,6 55,0 180,4 57, ,4 60,2 157,3 57,6 162,1 57,8 167,0 61,6 176,7 62,5 201,1 64, ,4 67,0 183,1 64,1 188,8 64,4 194,4 68,6 205,7 69,6 234,1 72, ,1 81,1 216,8 77,7 223,5 78,0 230,2 83,0 243,6 84,3 277,1 87, ,4 93,4 253,3 89,4 261,1 89,7 268,9 95,6 284,6 97,1 323,8 100, ,7 106,2 279,4 101,7 288,0 102,0 296,6 108,7 313,9 110,4 357,1 114, ,3 122,7 329,4 117,4 339,6 124,6 349,8 125,5 370,2 127,5 421,1 132, ,3 141,0 372,8 135,0 384,3 143,2 395,8 144,3 418,9 146,5 476,5 152, ,8 159,3 416,7 152,5 429,6 161,8 442,5 163,1 468,2 165,6 532,7 171, ,2 185,2 484,2 177,3 499,1 188,1 514,1 189,5 544,1 192,4 618,9 199,8 5 43,1 18,7 44,5 18,8 45,9 17,3 47,2 17,4 50,0 17,5 6 52,1 22,4 53,7 20,7 55,4 20,8 57,1 20,8 60,4 21,0 7 58,7 25,4 60,6 23,5 62,5 23,6 64,3 23,7 68,1 23,8 8 67,5 28,5 69,7 26,3 71,8 26,4 74,0 26,5 78,3 26, ,9 32,1 78,3 29,6 80,7 29,7 83,1 29,8 88,0 30, ,3 37,1 92,2 34,2 95,0 34,4 97,9 37,9 103,6 34, ,2 43,6 104,4 40,2 107,6 40,4 110,8 44,6 117,3 45, ,7 50,8 120,5 46,9 124,2 47,1 127,9 52,0 135,4 52, ,8 56,5 136,1 52,2 140,3 52,4 144,5 57,8 152,9 58, ,0 64,3 151,6 59,4 156,3 59,6 161,0 65,8 170,4 66, ,1 71,6 176,5 66,2 182,0 66,4 187,4 73,3 198,4 74, ,6 86,7 209,0 80,1 215,5 80,4 222,0 88,8 234,9 90, ,6 99,8 244,2 92,3 251,7 92,6 259,3 102,2 274,4 103, ,0 113,5 269,4 104,9 277,7 105,3 286,0 116,2 302,7 118, ,8 131,1 317,6 121,2 327,5 133,1 337,3 134,2 356,9 136, ,3 150,7 359,4 139,3 370,5 153,1 381,7 154,3 403,9 156, ,3 170,3 401,8 157,4 414,2 172,9 426,6 174,3 451,5 177, ,4 197,9 466,8 182,9 481,3 201,0 495,7 202,5 524,6 205,7 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 41

42 SA-H-N Outlet water temperature ( C) Outlet water temperature ( C) Hc Hc Hc ,7 19,0 51,9 19,1 56,5 19,3 33,2 15,5 6 54,1 22,0 57,6 22,2 62,8 22,4 36,9 18,0 7 63,1 24,1 67,1 24,2 73,2 24,5 43,0 19,7 8 69,1 27,6 73,5 27,8 80,1 28,1 47,1 22, ,5 33,0 89,9 33,2 98,0 33,6 57,6 27, ,6 37,7 104,9 38,0 114,4 38,4 67,3 30, ,4 42,8 118,6 43,1 129,2 43,6 76,0 35, ,4 47,9 132,4 48,3 144,3 48,8 84,8 39, ,9 54,1 151,0 54,5 164,6 55,1 96,8 44, ,5 59,4 167,5 59,8 182,6 60, ,4 48, ,7 70,7 193,3 71,2 210,7 72,0 123,9 57, ,1 85,9 233,1 86,5 254,1 87,4 149,4 70, ,6 92,6 268,8 93,2 293,0 94,2 172,3 75, ,0 114,6 295,7 115,5 322,3 116,7 189,6 93, ,1 118,3 339,4 119,1 370,0 120,4 218,9 99, ,8 142,6 393,4 143,7 428,8 145,2 251,3 117, ,5 170,8 455,8 172,1 496,8 173,9 292,2 139, ,8 192,8 514,7 194,2 561,0 196,3 329,9 159, ,0 214,0 591,4 215,6 644,7 217,9 379,1 187,5 5 46,4 20,0 49,3 20,1 53,8 20,4 35,0 15,5 34,4 18,2 6 51,5 23,2 54,8 23,4 59,7 23,6 38,9 18,0 38,1 21,1 7 60,0 25,4 63,9 25,5 69,6 25,8 45,3 19,7 44,5 23,0 8 65,7 29,1 69,9 29,3 76,2 29,7 49,6 22,6 48,7 26, ,4 34,7 85,5 35,0 93,2 35,4 60,7 27,0 59,5 31, ,8 39,8 99,8 40,1 108,8 40,5 70,9 30,9 69,5 36, ,0 45,1 112,8 45,4 123,0 45,9 80,1 35,0 78,5 40, ,4 50,5 125,9 50,9 137,3 51,4 89,4 39,2 87,7 45, ,0 57,0 143,6 57,4 156,6 58,1 102,0 44,3 100,0 51, ,8 62,6 159,4 63,0 173,7 63, ,1 48,6 111,0 56, ,9 74,5 183,9 75,0 200,5 75,9 130,5 57,8 128,1 67, ,5 90,5 221,8 91,2 241,7 92,2 157,4 70,3 154,4 82, ,4 97,6 255,7 98,3 278,7 99,3 181,5 75,7 178,1 88, ,5 120,8 281,4 121,7 306,7 123,0 199,7 93,8 195,9 109, ,6 124,7 323,0 125,6 352,0 126,9 230,7 99,7 226,3 116, ,8 150,3 374,3 151,4 408,0 153,1 264,8 117,3 259,7 137, ,7 180,0 433,7 181,4 472,7 183,3 307,8 139,8 302,0 163, ,3 203,2 489,7 204,7 533,8 206,9 347,6 159,0 341,0 186, ,0 225,6 562,7 227,2 613,4 229,7 399,5 187,5 391,8 219,3 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 42

43 SA-H-N Outlet water temperature ( C) Outlet water temperature ( C) Hc Hc Hc ,7 22,0 47,6 22,4 51,9 22,9 38,0 15,5 37,3 18,2 36,5 20,8 6 49,7 25,5 52,8 25,9 57,6 26,5 42,2 18,0 41,4 21,1 40,6 24,1 7 57,9 27,9 61,6 28,4 67,2 29,0 49,2 19,7 48,3 23,0 47,3 26,4 8 63,4 32,1 67,4 32,6 73,5 33,3 53,9 22,6 52,8 26,5 51,8 30, ,5 38,3 82,5 38,9 89,9 39,8 65,9 27,0 64,6 31,5 63,3 36, ,5 43,8 96,3 44,5 104,9 45,5 76,9 30,9 75,4 36,1 73,9 41, ,3 49,7 108,8 50,4 118,6 51,6 86,9 35,0 85,2 40,9 83,6 46, ,2 55,7 121,5 56,5 132,4 57,8 97,0 39,2 95,1 45,9 93,3 52, ,2 62,8 138,5 63,8 151,0 65,3 110,6 44,3 108,5 51,8 106,4 59, ,5 68,9 153,7 70,0 167,5 71, ,7 48,6 120,4 56,8 118,0 65, ,7 82,1 177,4 83,3 193,3 85,3 141,6 57,8 138,9 67,7 136,2 77, ,1 99,7 213,9 101,3 233,1 103,6 170,8 70,3 167,5 82,2 164,3 94, ,8 107,5 246,6 109,1 268,8 111,7 196,9 75,7 193,2 88,6 189,4 101, ,1 133,1 271,4 135,2 295,8 138,3 216,7 93,8 212,5 109,7 208,4 125, ,8 137,3 311,5 139,4 339,5 142,7 250,2 99,7 245,4 116,6 240,7 133, ,3 165,6 361,0 168,2 393,5 172,1 287,2 117,3 281,8 137,1 276,3 157, ,2 198,3 418,3 201,4 455,9 206,1 334,0 139,8 327,6 163,5 321,2 187, ,9 223,9 475,5 227,3 518,2 232,6 377,1 159,0 369,9 186,0 362,7 212, ,8 248,5 540,2 252,3 588,8 258,2 433,3 187,5 425,1 219,3 416,8 251,1 5 43,1 23,5 45,9 23,9 50,0 24,5 56,8 16,5 55,7 19,3 54,7 22,1 6 47,9 27,3 50,9 27,7 55,5 28,4 63,1 19,2 61,9 22,4 60,7 25,7 7 55,8 29,8 59,4 30,3 64,7 31,0 73,6 21,0 72,2 24,5 70,8 28,1 8 61,1 34,3 65,0 34,8 70,9 35,6 80,6 24,1 79,0 28,2 77,5 32, ,8 40,9 79,5 41,5 86,7 42,5 98,5 28,7 96,6 33,6 94,8 38, ,3 46,8 92,8 47,6 101,2 48,7 115,0 32,9 112,8 38,5 110,6 44, ,6 53,1 104,9 53,9 114,3 55,1 129,9 37,3 127,5 43,6 125,0 49, ,1 59,5 117,1 60,4 127,6 61,8 145,1 41,8 142,3 48,9 139,5 55, ,6 67,1 133,6 68,2 145,6 69,8 165,5 47,2 162,3 55,1 159,2 63, ,3 73,6 148,2 74,8 161,5 76, ,6 51,7 180,1 60,5 176,6 69, ,8 87,7 171,0 89,1 186,4 91,1 211,9 61,6 207,8 72,0 203,8 82, ,9 106,6 206,2 108,2 224,8 110,7 255,5 74,8 250,6 87,5 245,8 100, ,5 114,8 237,8 116,6 259,2 119,3 294,6 80,7 289,0 94,3 283,4 108, ,9 142,2 261,6 144,5 285,2 147,8 324,1 99,9 318,0 116,8 311,8 133, ,3 146,7 300,3 149,0 327,4 152,5 374,3 106,2 367,2 124,2 360,1 142, ,2 177,0 348,1 179,7 379,4 183,9 429,7 124,9 421,5 146,1 413,3 167, ,1 211,9 403,3 215,2 439,6 220,2 499,6 148,9 490,1 174,1 480,6 199, ,9 239,2 458,4 243,0 499,7 248,6 564,1 169,3 553,3 198,1 542,6 226, ,6 265,6 520,9 269,7 567,7 275,9 648,2 199,7 635,9 233,5 623,6 267,4 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 43

44 SA-H-E Outlet water temperature ( C) Outlet water temperature ( C) Hc Hc Hc ,3 15,3 50,4 14,5 54,9 15,5 31,1 12,6 6 53,9 17,4 57,4 17,5 62,6 17,7 35,5 14,4 7 61,0 19,9 64,9 20,1 70,7 20,3 40,1 16,5 8 68,9 22,9 73,3 23,0 79,9 23,3 45,3 18, ,7 25,5 84,8 25,7 92,4 26,0 52,4 21, ,9 30,3 98,8 30,5 107,7 30,9 61,1 25, ,9 34,1 115,8 34,4 126,3 34,8 71,6 28, ,4 39,9 129,1 40,2 140,7 40,6 79,8 33, ,0 44,7 149,0 45,0 162,4 45,5 92,1 36, ,3 50,7 166,3 51,1 181,2 51,6 102,8 41, ,9 57,1 187,2 57,5 204,0 58,2 115,7 47, ,2 62,3 218,3 62,8 238,0 63,4 134,9 51, ,5 80,0 256,9 80,6 280,0 81,4 158,8 66, ,0 89,3 294,7 90,0 321,2 91,0 182,2 73, ,0 106,8 328,8 107,6 358,3 103,8 203,2 88, ,1 121,1 377,7 122,0 411,7 117,7 233,5 100, ,7 135,1 427,3 136,1 465,8 131,3 264,1 111, ,5 158,7 493,1 159,9 537,5 154,2 304,8 131,2 5 45,0 16,1 47,9 16,2 52,2 16,4 34,0 12,6 33,4 14,7 6 51,3 18,3 54,6 18,5 59,5 18,7 38,8 14,4 38,0 16,8 7 58,0 21,0 61,7 21,1 67,3 21,4 43,8 16,5 43,0 19,3 8 65,5 24,1 69,7 24,3 76,0 24,5 49,5 18,9 48,6 22, ,8 26,9 80,6 27,1 87,9 27,4 57,2 21,1 56,2 24, ,4 31,9 94,0 32,2 102,5 32,5 66,7 25,1 65,5 29, ,6 36,0 110,2 36,2 120,1 36,6 78,2 28,2 76,7 33, ,5 42,1 122,8 42,4 133,9 42,8 87,2 33,0 85,5 38, ,2 47,1 141,7 47,4 154,5 47,9 100,6 36,9 98,7 43, ,7 53,5 158,2 53,8 172,4 54,4 112,3 41,9 110,1 49, ,4 60,2 178,1 60,6 194,1 61,3 126,4 47,2 124,0 55, ,2 65,7 207,7 66,2 226,4 66,9 147,4 51,5 144,6 60, ,8 84,3 244,4 84,9 266,4 85,8 173,5 66,1 170,2 77, ,6 94,1 280,4 94,8 305,6 95,9 199,0 73,9 195,3 86, ,0 112,6 312,8 113,4 341,0 116,0 222,0 88,3 217,8 103, ,8 127,7 359,4 128,6 391,7 131,6 255,1 100,1 250,3 117, ,2 142,4 406,6 143,4 443,2 146,8 288,6 111,7 283,1 130, ,1 167,3 469,2 168,5 511,4 172,4 333,1 131,2 326,7 153,5 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 44

45 SA-H-E Outlet water temperature ( C) Outlet water temperature ( C) Hc Hc Hc ,2 18,9 43,9 19,2 47,8 17,7 36,9 12,6 36,2 14,7 35,5 16,9 6 47,0 21,6 50,0 20,0 54,5 20,2 42,0 14,4 41,2 16,8 40,4 19,3 7 53,1 24,7 56,5 22,9 61,6 23,2 47,5 16,5 46,6 19,3 45,7 22,0 8 60,0 28,4 63,8 26,3 69,5 26,6 53,7 18,9 52,7 22,1 51,6 25, ,4 31,7 73,8 29,4 80,4 29,7 62,1 21,1 60,9 24,7 59,7 28, ,9 37,6 86,0 34,9 93,8 35,2 72,4 25,1 71,0 29,3 69,6 33, ,8 42,4 100,8 39,3 109,9 39,7 84,9 28,2 83,2 33,0 81,6 37, ,7 49,5 112,4 45,9 122,5 46,4 94,6 33,0 92,8 38,6 91,0 44, ,9 55,4 129,7 51,4 141,4 52,0 109,1 36,9 107,1 43,2 105,0 49, ,1 62,9 144,7 58,4 157,8 59,0 121,8 41,9 119,5 49,0 117,2 56, ,2 70,9 163,0 65,7 177,6 66,4 137,1 47,2 134,5 55,2 131,9 63, ,7 77,3 190,1 71,7 207,2 72,5 159,9 51,5 156,9 60,3 153,9 69, ,2 99,2 223,7 92,1 243,8 93,0 188,2 66,1 184,6 77,4 181,1 88, ,2 110,8 256,6 102,8 279,7 103,9 215,9 73,9 211,8 86,4 207,7 98, ,0 132,5 286,2 122,9 312,0 137,7 240,9 88,3 236,3 103,3 231,7 118, ,1 150,3 328,9 139,4 358,4 156,2 276,7 100,1 271,5 117,1 266,2 134, ,7 167,6 372,0 155,5 405,5 174,2 313,1 111,7 307,1 130,7 301,1 149, ,6 196,9 429,3 182,7 468,0 204,6 361,3 131,2 354,4 153,5 347,5 175,7 5 37,4 22,1 39,8 22,5 43,4 19,1 55,2 13,4 54,2 15,7 53,1 18,0 6 42,6 25,2 45,3 21,5 49,4 21,8 62,9 15,3 61,7 17,9 60,5 20,5 7 48,2 28,9 51,2 24,7 55,8 24,9 71,1 17,5 69,8 20,5 68,4 23,5 8 54,4 33,1 57,9 28,3 63,1 28,6 80,3 20,1 78,8 23,5 77,3 27, ,9 37,0 66,9 31,6 73,0 31,9 92,9 22,5 91,1 26,3 89,4 30, ,3 43,9 78,0 37,5 85,0 37,9 108,3 26,7 106,2 31,2 104,2 35, ,0 49,5 91,5 42,3 99,7 42,7 127,0 30,1 124,5 35,2 122,1 40, ,8 57,9 102,0 49,4 111,1 50,0 141,5 35,1 138,8 41,1 136,1 47, ,6 64,8 117,6 55,3 128,2 55,9 163,3 39,3 160,2 46,0 157,1 52, ,4 73,5 131,3 62,8 143,1 63,5 182,2 44,7 178,7 52,2 175,3 59, ,9 82,8 147,8 70,7 161,1 71,5 205,1 50,3 201,2 58,8 197,3 67, ,1 90,3 172,4 77,2 187,9 78,0 239,3 54,9 234,7 64,2 230,2 73, ,7 116,0 202,9 99,0 221,1 100,1 281,6 70,4 276,2 82,4 270,9 94, ,8 129,5 232,7 110,6 253,7 111,8 323,0 78,6 316,9 92,0 310,7 105, ,0 154,8 259,6 132,3 283,0 160,9 360,3 94,0 353,5 110,0 346,6 125, ,4 175,6 298,3 150,0 325,1 182,4 414,0 106,7 406,1 124,7 398,2 142, ,2 195,9 337,4 167,3 367,8 203,5 468,3 119,0 459,4 139,1 450,5 159, ,1 230,1 389,4 196,5 424,5 239,1 540,5 139,8 530,2 163,5 519,9 187,2 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 45

46 SA-C-N Evaporating temperature ( C) , ,8 18,8 49,0 17,7 50,6 19,0 53,0 19,1 55,3 19,2 58,5 19,3 61,7 19,5 6 53,6 21,0 57,3 21,1 59,2 21,2 62,0 21,3 64,8 21,4 68,5 21,6 72,2 21,7 7 59,1 23,9 63,2 24,1 65,2 24,2 68,3 24,3 71,4 24,5 75,5 24,6 79,6 24, ,7 27,4 70,3 27,6 72,6 27,7 76,0 27,8 79,4 28,0 84,0 28,2 88,5 28, ,4 32,7 86,0 32,9 88,8 33,0 92,9 33,2 97,1 33,4 102,7 33,6 108,3 33, ,4 37,4 99,9 37,7 103,1 37,8 108,0 35,8 112,8 36,2 119,3 36,8 125,8 37, ,0 42,4 113,4 42,7 117,1 42,9 122,6 40,6 128,1 41,1 135,5 41,7 142,8 42, ,4 47,5 126,6 47,8 130,7 48,0 136,9 45,5 143,0 46,0 151,2 46,7 159,4 47, ,9 53,4 144,2 53,8 148,9 54,0 155,9 51,2 162,9 51,8 172,3 52,6 181,6 53, ,4 57,5 163,0 57,9 168,3 58,1 176,2 55,1 184,2 55,7 194,7 56,6 205,3 57, ,7 69,4 183,7 69,9 189,6 70,1 198,5 66,5 207,5 67,2 219,4 68,3 231,3 69, ,5 85,1 222,9 85,7 230,2 86,0 241,0 81,5 251,9 82,5 266,3 83,7 280,8 85, ,2 92,1 259,0 92,7 267,4 93,1 280,0 88,2 292,6 89,2 309,4 90,6 326,2 92, ,9 111,0 291,8 111,8 301,3 112,3 315,5 106,4 329,7 107,6 348,6 109,3 367,5 110,9 5 43,6 19,8 46,6 19,7 48,1 20,0 50,4 20,1 52,7 20,2 55,7 20,4 58,7 20,5 6 51,0 22,1 54,5 22,3 56,3 22,3 59,0 22,5 61,6 22,6 65,2 22,8 68,7 22,9 7 56,2 25,2 60,1 25,4 62,1 25,5 65,0 25,6 67,9 25,8 71,8 26,0 75,7 26, ,6 28,9 66,9 29,1 69,1 29,2 72,3 29,3 75,6 29,5 79,9 29,7 84,3 29, ,5 34,4 81,8 34,7 84,5 34,8 88,4 35,0 92,4 35,2 97,7 35,4 103,0 35, ,9 39,4 95,0 39,7 98,1 39,9 102,7 40,1 107,3 40,5 113,5 41,2 119,7 41, ,9 44,7 107,9 45,0 111,4 45,2 116,6 45,4 121,9 45,9 128,9 46,6 135,9 47, ,6 50,1 120,5 50,4 124,4 50,6 130,2 50,9 136,1 51,5 143,9 52,3 151,7 53, ,3 56,3 137,2 56,7 141,7 56,9 148,4 57,2 155,0 57,9 163,9 58,8 172,8 59, ,0 60,6 155,1 61,0 160,1 61,3 167,7 61,6 175,2 62,3 185,3 63,3 195,3 64, ,4 73,1 174,7 73,6 180,4 73,9 188,9 74,3 197,4 75,2 208,7 76,3 220,1 77, ,4 89,7 212,1 90,4 219,0 90,7 229,3 91,2 239,7 92,2 253,4 93,6 267,2 95, ,4 97,0 246,4 97,7 254,4 98,1 266,4 98,6 278,4 99,8 294,4 101,3 310,3 102, ,6 117,0 277,7 117,9 286,7 118,3 300,2 119,0 313,7 120,3 331,7 122,2 349,7 124,0 5 39,9 23,1 42,7 23,4 44,0 21,7 46,1 21,8 48,2 21,9 51,0 22,1 6 46,7 25,7 49,9 24,1 51,5 24,2 54,0 24,4 56,4 24,5 59,6 24,7 7 51,4 29,4 55,0 27,5 56,8 27,6 59,5 27,8 62,1 27,9 65,7 28, ,2 33,6 61,2 31,5 63,2 31,6 66,2 31,8 69,1 32,0 73,1 32, ,0 40,1 74,8 37,6 77,3 37,7 80,9 41,5 84,6 42,0 89,4 42, ,3 45,9 86,9 43,0 89,8 43,2 94,0 47,6 98,2 48,1 103,9 48, ,3 52,1 98,7 48,8 101,9 49,0 106,7 53,9 111,5 54,5 117,9 55, ,1 58,3 110,2 54,7 113,8 54,9 119,2 60,4 124,5 61,1 131,7 62, ,4 65,6 125,6 61,5 129,6 61,7 135,7 67,9 141,9 68,7 150,0 69, ,7 70,6 141,9 66,2 146,5 66,4 153,4 73,1 160,3 73,9 169,5 75, ,5 85,2 159,9 79,8 165,1 80,1 172,8 88,2 180,6 89,2 191,0 90, ,5 104,5 194,1 97,9 200,4 98,3 209,8 108,2 219,3 109,5 231,9 111, ,8 113,0 225,5 106,0 232,8 106,3 243,7 117,1 254,7 118,4 269,3 120, ,6 136,3 254,1 127,8 262,3 128,2 274,6 141,2 287,0 142,8 303,5 145,0 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; 46 heating main value

47 SA-C-E Evaporating temperature ( C) , ,9 15,1 47,0 14,2 48,5 15,3 50,8 15,4 53,1 15,4 56,1 15,6 59,2 15,7 6 50,1 17,2 53,5 17,4 55,3 17,4 57,9 17,5 60,5 17,6 64,0 17,7 67,4 17,9 7 56,7 19,7 60,7 19,9 62,7 19,9 65,6 20,1 68,6 20,2 72,5 20,3 76,4 20, ,2 22,7 69,7 22,8 72,0 22,9 75,4 23,0 78,8 23,2 83,3 23,3 87,8 23, ,3 25,3 79,5 25,5 82,1 25,6 85,9 25,7 89,8 25,9 94,9 26,0 100,1 26, ,4 30,0 92,4 30,2 95,4 30,4 99,9 30,5 104,4 30,7 110,4 30,9 116,4 31, ,3 33,8 108,3 34,1 111,9 34,2 117,1 34,4 122,4 34,6 129,4 34,8 136,4 35, ,9 39,5 120,8 39,8 124,7 40,0 130,6 37,9 136,4 38,3 144,3 38,9 152,1 39, ,0 44,3 140,0 44,6 144,6 44,8 151,4 42,4 158,2 42,9 167,3 43,6 176,4 44, ,1 50,3 156,3 50,6 161,4 50,8 169,0 48,2 176,6 48,7 186,7 49,5 196,8 50, ,5 56,6 175,9 57,0 181,7 57,2 190,2 54,2 198,8 54,9 210,2 55,7 221,6 56, ,9 61,7 205,2 62,2 211,9 62,4 221,9 59,2 231,8 59,8 245,1 60,8 258,5 61, ,8 79,3 241,5 79,8 249,3 80,1 261,1 75,9 272,8 76,8 288,5 78,0 304,2 79, ,7 88,5 277,7 89,2 286,7 89,5 300,2 84,8 313,8 85,8 331,8 87,1 349,8 88,4 5 41,8 15,9 44,7 15,9 46,2 16,1 48,3 16,2 50,5 16,3 53,4 16,4 56,3 16,5 6 47,6 18,2 50,9 18,3 52,6 18,4 55,1 18,5 57,6 18,6 60,9 18,7 64,2 18,8 7 54,0 20,8 57,7 20,9 59,6 21,0 62,4 21,1 65,2 21,3 69,0 21,4 72,7 21, ,1 23,9 66,4 24,1 68,5 24,1 71,7 24,3 75,0 24,4 79,3 24,6 83,6 24, ,7 26,7 75,6 26,9 78,1 27,0 81,8 27,1 85,4 27,2 90,3 27,4 95,2 27, ,2 31,6 87,9 31,9 90,8 32,0 95,1 32,2 99,3 32,3 105,0 32,6 110,7 32, ,4 35,7 103,1 35,9 106,4 36,1 111,4 36,2 116,5 36,7 123,1 37,2 129,8 37, ,4 41,7 114,9 42,0 118,6 42,1 124,2 42,4 129,8 42,9 137,3 43,5 144,7 44, ,6 46,7 133,2 47,0 137,6 47,2 144,0 47,4 150,5 48,0 159,2 48,7 167,8 49, ,1 53,0 148,7 53,4 153,5 53,6 160,8 53,8 168,0 54,5 177,6 55,3 187,3 56, ,6 59,6 167,4 60,1 172,8 60,3 181,0 60,6 189,1 61,3 200,0 62,3 210,8 63, ,6 65,1 195,3 65,6 201,6 65,8 211,1 66,2 220,6 66,9 233,3 67,9 245,9 69, ,9 83,5 229,8 84,2 237,2 84,5 248,4 84,9 259,6 85,9 274,5 87,2 289,4 88, ,1 93,3 264,3 94,0 272,8 94,3 285,7 94,8 298,5 95,9 315,7 97,4 332,8 98,9 5 38,3 18,6 40,9 18,9 42,2 17,5 44,2 17,6 46,2 17,6 48,9 17,8 6 43,6 21,2 46,6 19,8 48,1 19,9 50,4 20,0 52,7 20,1 55,7 20,3 7 49,4 24,2 52,8 22,7 54,5 22,8 57,1 22,9 59,7 23,0 63,1 23, ,8 27,8 60,7 26,1 62,7 26,2 65,6 26,3 68,6 26,5 72,5 26, ,7 31,1 69,2 29,1 71,4 29,2 74,8 29,4 78,2 29,5 82,7 29, ,2 36,9 80,5 34,6 83,1 34,7 87,0 38,2 90,9 35,1 96,1 35, ,2 41,5 94,3 38,9 97,4 39,1 102,0 43,0 106,6 43,5 112,7 44, ,3 48,6 105,1 45,5 108,5 45,7 113,7 50,3 118,8 50,9 125,6 51, ,0 54,4 121,9 50,9 125,9 51,1 131,8 56,3 137,7 56,9 145,6 57, ,2 61,7 136,1 57,8 140,5 58,0 147,1 63,9 153,7 64,6 162,5 65, ,2 69,5 153,2 65,1 158,1 65,4 165,6 72,0 173,1 72,8 183,0 73, ,1 75,8 178,7 71,1 184,5 71,3 193,1 78,5 201,8 79,4 213,4 80, ,6 97,3 210,2 91,2 217,1 91,6 227,3 100,8 237,5 102,0 251,2 103, ,1 108,7 241,8 101,9 249,6 102,2 261,4 112,5 273,2 113,8 288,8 115,6 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 47

48 Correction factors for ethylene glycol content Weight percentage of glycol % Freezing point ( C) 0-3,6-8,8-15,7-24,86-37,13 Minimum outlet water temperature allowed ( C) 5,5 1,9-3,3-10,2-19,4-31,6 Cooling capacity correction factor (dt=5 C) 1,000 0,993 0,985 0,978 0,970 0,963 Correction factors for differential water temperature IN-OUT Differential water temperature (Inlet - Outlet) C Cooling capacity correction factor 0,970 0,985 1,000 1,008 1,016 1,024 1,032 1,040 The technical data in this document are not binding. Rigel Impianti S.r.l. keeps rights to make any technical modifications at any time without notice due to its improvement process. 48

49 DIMENSIONAL DRAWINGS Unit SA sizes 5, 5-E 6, 6-E 7, 7-E, 8 5 TOP 49

50 Unit SA sizes 8-E, 10, 10-E, 11, 11-E, 12, 12-E, 13, 13-E, 15 6-TOP, 7-TOP, 8-TOP, 10-TOP, 11-TOP, 12-TOP 50

51 Unit SA sizes 15- E, 18, 18-E, TOP, 15-TOP, 18-TOP 51

52 Unit SA sizes 20-E, 23 52

53 Unit SA sizes 23-E, 27, 27-E, TOP, 23-TOP 53

54 Unit SA sizes 30-E, 36, 36-E, TOP, 30-TOP 54

55 Unit SA sizes 41-E, 46, 46-E, 52, 52-E, TOP, 41-TOP, 46-TOP 55

56 Unit SA sizes 60-E 52-TOP 56

57 SPACE FOR UNIT INSTALLATION 57

58 Notes

59 Cold Innovation Zona Industriale Padule , Gubbio (PG) - Italy Tel Fax info@coldinnovation.it

60 VENERUCCI 0214

1

1 ST www.coldinnovation.it 1 INDEX Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R410A...pag. 5 Scroll compressors...pag. 6 Condenser

More information

H4T R410A. refrigerant

H4T R410A. refrigerant H4T INDEX Polyvalent unit working modes...pag. 4 Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R410A...pag. 5 Scroll compressors...pag.

More information

ARS. 1

ARS.   1 ARS www.rigelimpianti.it 1 INDEX Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R410A...pag. 5 Scroll compressors...pag. 6 Brazed plates

More information

ARV.

ARV. ARV www.coldinnovation.it 1 INDEX Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R134a...pag. 5 Semi-hermetic screw compressor...pag.

More information

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS RAH 602 Ka + CF + GP 62 Above picture is only indicative and is not binding.

More information

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw COMFORT CHILLERS AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw climaveneta.com COMFORT CHILLERS PERFECT COMFORT AND MAXIMUM EFFICIENCY Air-cooled liquid chiller for outside installation

More information

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N E S A RE F R E IG RA N T G TECHNICAL MANUAL -FRIEND Y CONDENSING UNITS FOR OUTDOOR INSTALLATION O L CMA C 2 The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual,

More information

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw COMFORT HEAT PUMPS AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw climaveneta.com COMFORT HEAT PUMPS PERFECT COMFORT AND MAXIMUM EFFICIENCY Air to water heat pump for outdoor installation,

More information

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES COOLING CAPACITY FROM 76 TO 612 Kw 1 AND 2 COOLING CIRCUITS RAE 1702 F Kc + P2 28 Above picture is only indicative

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1 UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS GPE 802 Kc + CF + GP + MV + P1 130 Above picture is only indicative and is not binding. AIR R-410A

More information

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS Energy saving thanks to a total recovery p Cooling Heating/DHW h Galletti multi-purpose heat pumps are total recovery units used for a simultaneous hot and

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 1402 C O K AIR R-407C Series RAE... C K Cooling capacity from 81 to 250 kw - 2 circuits The air cooled chillers of RAE C K series, with centrifugal fans, are designed for indoor installation and are

More information

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB R407C EASY_R Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans 5,2 41,5 kw T_ESY_R_0508_GB EASY_R R407C INDEX WORKING LIMITS... 3 SERIES IDENTIFICATION... 4 MODEL

More information

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS RAE 1352 F.K + MV AIR R-407C FC Series RAE... F.K Cooling capacity from 77 to 289 kw - 2 circuits The air cooled chillers of RAE... F.K series, are designed for outdoor installation and are particularly

More information

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw PROCESS CHILLERS AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw climaveneta.com PROCESS CHILLERS MAXIMUM EFFICIENCY IN EVERY TYPE OF PROCESS APPLICATION Air cooled liquid chiller for outdoor

More information

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw Multifunction chillers for indoor installation. Cooling Capacity: 22 222 Heating Capacity: 25 236 Scroll compressors EC Plug Fans Plate type heat exchangers EER up to 3,12 COP up to 3,84 ESEER up to 4,01

More information

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories > HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION Available range Unit type IP Reversible heat pump (reversible on the refrigerant side) ECO-FRIENDLY REFRIGERANT GAS Versions (heat recovery) VB Base

More information

HYDRONIC RESIDENTIAL

HYDRONIC RESIDENTIAL HYDRONIC RESIDENTIAL Chillers, reversible heat pumps and modular units for small and medium applications. Climaveneta. brand of Mitsubishi Electric Hydronics & IT Cooling Systems, presents the mini chiller

More information

PRODUCT GUIDE

PRODUCT GUIDE PRODUCT GUIDE 01.2017 Cooling Heating CHAPTER 1 AIRCOOLED LIQUID CHILLERS AND HEAT PUMPS FOR RESIDENTIAL & LIGHT COMMERCIAL APPLICATION Power (kw) Page IACAK/II/WP 101.5 106 0 58 115 A CLASS energy efficiency

More information

Aquaflair TRAC-TRAF-TRAH

Aquaflair TRAC-TRAF-TRAH Aquaflair TRAC-TRAF-TRAH 110 400 kw Air-cooled chillers, free-cooling chillers and heat pumps for mission critical applications Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 201 C K RAE 482 C K AIR R-407C Series RAE... C K from 19 to 83 kw - 1 and 2 circuits The air cooled chillers of RAE... C K series, with centrifugal fans, are designed for indoor installation and are

More information

Modular Air-cooled Chillers

Modular Air-cooled Chillers Modular Air-cooled Chillers High Seasonal Efficiency (HSE) version Cooling capacity 48-232 kw Trane Flex Series Modular air/water chillers with axial EC fans, inverter driven scroll compressors and microchannel

More information

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING

More information

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS Total heat recovery multi-purpose units LCP Outdoor monobloc air-water unit LCP - kw Heating, cooling, domestic hot water one single system to meet all kinds of needs. Total heat recovery multi-purpose

More information

Air cooled industrial chillers

Air cooled industrial chillers Air cooled industrial chillers Main features R410A refrigerant Cooling capacity 5 175 kw Air cooled industrial chillers Models Versions HE High Efficiency Finned coil evaporators submerged in the storage

More information

Blue Box Epsilon Echos +

Blue Box Epsilon Echos + Blue Box Epsilon Echos + 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Packaged version in 5 sizes Nominal cooling capacity (A35;W7): 6 26 kw Nominal heating

More information

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 46 Above picture is only indicative and is not binding AIR FC The packaged air cooled chillers of RAS Kp series are suitable

More information

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10 Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW Compressors Scroll Serie: Series: Emissione: Issue: SCAEY Catalogo: Leaflet: Sostituisce: Supersedes: DE 88 04/11 12/10 Index

More information

New CGAF Air Cooled Scroll Chiller. New Air-Cooled Scroll Chiller CGAF

New CGAF Air Cooled Scroll Chiller. New Air-Cooled Scroll Chiller CGAF New CGAF New Air-Cooled Scroll Chiller CGAF New CGAF CGAF Air cooled Scroll Chiller 170 700 kw Cooling Only CXAF 150 700 kw Heat pump Coming soon 2 New addition to the Sintesis Family: Multiple technologies,

More information

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw Multi-pipe Units with Scroll Compressors Model CMAA Cooling capacity 45-485 kw Heating capacity 50-670 kw CMAA multi-pipe units Simultaneous heating and cooling with one product Standard versions Acoustic

More information

pyxis hp "u" pyxis hp "u" IDEA NEW rcgroupairconditioning

pyxis hp u pyxis hp u IDEA NEW rcgroupairconditioning Comfort PYXIS HP U : ir / water reversible heat pumps for outdoor installation, equipped with scroll compressors and axial fans Cooling Capacity: 42,3 195,0 Heating Capacity: 47,1 222,0 NEW IDE R410 rcgroupairconditioning

More information

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98 Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw Scroll Compressors Series: SCAEY-FC Leaflet: DE 98 Issue: 01/16 Supersedes: 12/13 Identification code Index Index... pag. 2 Identification code...»

More information

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017 Zeta Rev LN HP 10.2 Configured unit accessories 1PS - One user-side pump with tank LN - Low noise RG - Condensation control with fan speed regulator CSP - Set point compensation depending on external air

More information

INVERTER SCROLL. LG Electronics Distributed by. Copyright 2017 LG Electronics. All rights reserved.

INVERTER SCROLL. LG Electronics     Distributed by. Copyright 2017 LG Electronics. All rights reserved. LG Electronics http://www.lg.com http://partner.lge.com Distributed by Copyright 2017 LG Electronics. All rights reserved. FEATURES & BENEFITS High Efficient Inverter Technologies EER 2.65 / COP 3.2 /

More information

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION ECO-FRIENDLY REFRIGERANT GAS INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years

More information

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB Packaged air cooled liquid chillers for outdoor installation 42 574 kw technicalcatalogue T_EGL_1012_GB INDEX EUROVENT CERTIFICATION... 3 GENERAL CHARACTERISTICS... 3 SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION...

More information

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz EN Technical Catalogue Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: 321-1308 kw 50 Hz EKV/BS business Air cooled water chillers for outdoor installation. Flexibility in the

More information

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Type of Compressors Compressor Rotary Scroll Reciprocating Screw Centrifugal Air Cooled Chiller 77 ~ 329TR (270 ~ 1156 kw) ACDX Series 100 ~ 520TR

More information

Advance Split

Advance Split Engineering Data Manual Aqu@Scop Advance Split Air-to-Water DC Inverter Split Heat Pumps Models 005, 008, 012 & 014 2 to 16 kw Strength Points Most efficient heating technology with variable speed compressor.

More information

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line) ERAH MC Ka AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line) Range 394-1220 kw Liquid chillers air condensing unit Package external installation Screw compressors

More information

Air Cooled Chillers & Heat Pumps WinPACK HE-A

Air Cooled Chillers & Heat Pumps WinPACK HE-A Air Cooled Chillers & Heat Pumps WinPACK HE-A TCAEY-THAEY 2110-4340 1 Air Cooled Chillers & Heat Pumps WinPACK HE-A TCAEY-THAEY 2110-4340 Cooling capacity: 91,6-345 kw Heating capacity: 110,5-357 kw Class

More information

INVERTER SCROLL INVERTER SCROLL INVERTER SCROLL. LG Electronics Distributed by

INVERTER SCROLL INVERTER SCROLL INVERTER SCROLL. LG Electronics     Distributed by 4mm 이상 ~ 15mm 미만 (음화형 규정) LG Electronics http://www.lg.com http://partner.lge.com Copyright 2017 LG Electronics. All rights reserved. Distributed by FEATURES & BENEFITS High Efficient Inverter Technologies

More information

NRP MULTIPURPOSE HEAT PUMPS 2 AND 4-PIPE SYSTEMS PLUS PRODUCTION OF DOMESTIC HOT WATER

NRP MULTIPURPOSE HEAT PUMPS 2 AND 4-PIPE SYSTEMS PLUS PRODUCTION OF DOMESTIC HOT WATER NRP MULTIPURPOSE HEAT PUMPS AND 4-PIPE SYSTEMS PLUS PRODUCTION OF DOMESTIC HOT WATER Multipurpose air cooled units with axial fans. For external installation. High efficiency version. NRP MULTIPURPOSE

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata EKS/HE Refrigerant R410A GWP=2.088 Scroll Compressor Shell & Tube exchanger Axial fan Brazed plate heat exchanger MultiScroll Air-cooled liquid chillers High efficiency Solution B - Base I - Integrata

More information

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw AIR-COOLED LIQUID CHILLER REVERSIBLE AIR-TO-WATER HEAT PUMP PRO-DIALOG PLUS 30RB/RQ 039S-60S Refrigerant HFC-40A Nominal cooling capacity 40-58 kw Nominal heating capacity 4-59 kw The new generation of

More information

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98 Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw Scroll Compressors Series: SCAEY-FC Leaflet: DE 98 Issue: 04/11 Supersedes: 12/10 Identification code Index Index... pag. 2 Identification code...»

More information

Galletti Water chillers and heat pumps catalogue

Galletti   Water chillers and heat pumps catalogue Galletti www.galletti.it Water chillers and heat pumps catalogue Table of Contents/SMALL SYSTEMS MPI DC Water chillers and heat pumps with inverter compressor 6 models page 6 MCE MPE Air condensed water

More information

MPI DC 8-29 kw. Outdoor monobloc unit with BLDC compressor. Air chillers and heat pumps MPI DC PLUS

MPI DC 8-29 kw. Outdoor monobloc unit with BLDC compressor. Air chillers and heat pumps MPI DC PLUS Air chillers and heat pumps MPI DC Outdoor monobloc unit with BLDC compressor MPI DC - 9 kw Large operating range and energy efficiency under every condition BLDC scroll compressor PLUS BLDC rotary compressor

More information

RTA TECHNICAL MANUAL AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION O L S E A F RA N

RTA TECHNICAL MANUAL AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION O L S E A F RA N A RE F S E -FRIEND Y R E IG RA N T G AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION O L RTA C TECHNICAL MANUAL 1 2 SUMMARY THIS MANUAL IS DIVIDED INTO SECTIONS. THEIR NAMES APPEAR IN THE HEADING

More information

Construction details: Structure and base in hot dip galvanised sheet steel with epoxy pain finish (RAL 9002)

Construction details: Structure and base in hot dip galvanised sheet steel with epoxy pain finish (RAL 9002) Water cooled internal chiller and heat pump units with scroll compressors Cooling capacity from 106 kw to 385 kw NXW Heating capacity from 119 kw to 419 kw R410A Aermec participates in the EUROVENTProgram:

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

Modular Air Cooled Scroll Chillers

Modular Air Cooled Scroll Chillers Modular Air Cooled Scroll Chillers 65 80 130 Find out more at www.greeonline.com 160 249 High Efficiency Shell and Tube Heat Exchanger The Gree D Series Chillers utilise high efficiency shell and tube

More information

Flex Series Heat Pumps

Flex Series Heat Pumps Flex Series Heat Pumps Air/water heat pumps with axial or centrifugal fans; plate or shell and tube exchangers. 08/0/06 Page of 5 FLEX SERIES The patented series of modular packaged chiller and heat pump

More information

Conditioning your ambient, maximising your comfort.

Conditioning your ambient, maximising your comfort. High efficiency water cooled chillers, heat pumps and evaporating units with screw compressors and R134a refrigerant gas. Cooling capacity 378 1554 kw Heating capacity 425 1744 kw Cooling capacity evaporating

More information

HIWARM COMPACT kw

HIWARM COMPACT kw Total heat recovery multi-purpose s HIWRM COMPCT Outdoor monobloc air-water with BLDC compressor HIWRM COMPCT - kw Total recovery and energy efficiency in every condition Total heat recovery multi-purpose

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

O L R E RGA ST RA N AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION TECHNICAL MANUAL

O L R E RGA ST RA N AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION TECHNICAL MANUAL -FRIEND A R E IG RA N T G RGA ST RE F S Y E O L C AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION TECHNICAL MANUAL 1 2 SUMMARY THIS MANUAL IS DIVIDED INTO SECTIONS. THEIR NAMES APPEAR IN THE

More information

GHE GHE. Dehumidifiers for radiant cooling systems with heat recovery VERSIONS ACCESSORIES

GHE GHE. Dehumidifiers for radiant cooling systems with heat recovery VERSIONS ACCESSORIES Dehumidifiers for radiant cooling systems with heat recovery The dehumidifiers with heat recovery of high efficiency series were designed to provide dehumidification and fresh air in a residential area

More information

50A KP 70A KP 90A KP 120A KP 150A KP 210A

50A KP 70A KP 90A KP 120A KP 150A KP 210A DC inverter all in one Model KP 5A KP 7A KP 9A KP 12A KP 15A KP 21A Power supply V/Hz/Ph 23/5/1 23/5/1 23/5/1 23/5/1 38/5/3 38/5/3 Nominal heating capacity kw 5 7 9 12 15 21 Nominal cooling capacity kw

More information

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation Air-Cooled Liquid Chillers www.eurovent-certification.com www.certiflash.com Quality Management Systems 0RB 008-05 Nominal cooling capacity 8- The new generation of Aquasnap liquid chillers was designed

More information

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW TECHNICAL CATALOGUE EQSL Air Cooled Water Chillers Models: 300 V2 F06 1310 V2 F16 Cooling capacity: 299 to 1310 KW 02.16 ref. 207598 Rev.100 Thank you for trusting in Hitecsa Products. Our company has

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

MPE 4-76 kw. Outdoor monobloc unit. Air chillers and heat pumps MPE PLUS. Efficiency under all operating conditions. 152 galletti.

MPE 4-76 kw. Outdoor monobloc unit. Air chillers and heat pumps MPE PLUS. Efficiency under all operating conditions. 152 galletti. Air chillers and heat pumps MPE Outdoor monobloc unit MPE - kw Efficiency under all operating conditions Rotary compressor PLUS Scroll compressor R-0A R-0A refrigerant Cooling only Cooling / Heating Monobloc

More information

SyScroll 40 to 75 Air NEW

SyScroll 40 to 75 Air NEW Chiller Close Control Water terminals SyScroll 40 to 75 Air NEW Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual 40.0 to 76.0 kw 40.0 to 77.0 kw SyScroll 40-75 Air 3 Key points

More information

FHE FHE. Dehumidifiers for radiant cooling systems with heat recovery. Versions

FHE FHE. Dehumidifiers for radiant cooling systems with heat recovery. Versions Dehumidifiers for radiant cooling systems with heat recovery 50 The dehumidifiers with heat recovery of high efficiency series were designed to provide dehumidification and fresh air in a residential area

More information

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES LS ir cooled water chillers with axial fans + LS The LS water chiller range has been designed for small and medium residential and commercial applications. They are suitable for generating chilled water

More information

HIWARM kw. Air-water system with external and internal BLDC unit. Total heat recovery multi-purpose units HIWARM PLUS

HIWARM kw. Air-water system with external and internal BLDC unit. Total heat recovery multi-purpose units HIWARM PLUS Total heat recovery multi-purpose units HIWARM Air-water system with external and internal BLDC unit HIWARM - kw The perfect combination between multi-purpose, inverter technology and style Multi-purpose

More information

AIR TO WATER UNITS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS (PLUG FAN), FOR INDOOR INSTALLATION kw

AIR TO WATER UNITS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS (PLUG FAN), FOR INDOOR INSTALLATION kw PROCESS CHILLERS HEAT PUMPS AIR TO WATER UNITS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS (PLUG FAN), FOR INDOOR INSTALLATION 17-290 kw climaveneta.com PROCESS CHILLERS HEAT PUMPS A TRULY UNIQUE SOLUTION

More information

Be sustainable while protecting your business

Be sustainable while protecting your business Be sustainable while protecting your business Aquaflair 50Hz Air-cooled chillers and free-cooling chillers with double screw compressors and HFO R1234ze refrigerant (400V/3ph/50Hz) 300-1000 kw Aquaflair

More information

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning : Packaged air cooled liquid chillers with free-cooling system for outdoor installation, equipped with screw compressors and axial fans Cooling Capacity: 314 1343 Free-Cooling Capacity: 308 938 GLYCOL

More information

CRIMSON & CRIMSON MAX

CRIMSON & CRIMSON MAX High efficiency water/water and geothermal heat pumps 5 114 General High efficiency water/water and geothermal heat pumps. Ideal for heating, cooling and production of domestic hotwater with total or partial

More information

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient PRODUCT SELECTION DATA Easy and fast installation Compact, reliable and efficient Class A variable speed circulator available Air-Cooled Liquid Chillers 0RB 008-015 CARRIER participates in the ECP programme

More information

NEOSYS. AIR TO WATER LIQUID CHILLER kw. AIR TO WATER HEAT PUMP kw. lennoxemea.com

NEOSYS. AIR TO WATER LIQUID CHILLER kw. AIR TO WATER HEAT PUMP kw. lennoxemea.com NEOSYS AIR TO WATER LIQUID CHILLER 200-1000 kw AIR TO WATER HEAT PUMP 200-500 kw lennoxemea.com NEOSYS, winning ENERGY PERFORMANCE The NEOSYS delivers energy efficiency at full and partial load by the

More information

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running Climaveneta Technical Bulletin BRH_0011_0121_201211_EN BRH r HFC R-410A 0011-0121 5,5-35,1 kw Water-cooled liquid chillers (The photo of the unit is indicative and may change depending on the model) Versatile

More information

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual u Air-to-Water Reverse Cycle Heat Pumps AQH 40 to 130 40 to 131 kw 45 to 141 kw Engineering Data Manual EDM AQH-W.3GB Date : November 2007 Supersedes : TM AQH-W.2GB/03.04 Specifications The Aqu@Logic air-to-water

More information

Conditioning your ambient, maximising your comfort.

Conditioning your ambient, maximising your comfort. Air cooled water chillers and condensing units with hermetic scroll compressors and R410A refrigerant gas. Cooling capacity 72,5 154 kw Cooling capacity condensing units 76,4 164,6 kw Conditioning your

More information

pyxis u pyxis ua NEW rcgroupairconditioning

pyxis u pyxis ua NEW rcgroupairconditioning Industrial : Packaged air cooled liquid chillers for outdoor installation equipped with scroll compressors and microchannel condensing coils Cooling capacity: 44,9 200,0 rcgroupairconditioning R410 C PLTE

More information

Chillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to kw

Chillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to kw Chillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to 1.99 kw Centrifugal compressor with magnetic levitation This is a miniaturized, highly innovative

More information

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw Air cooled chillers with brushless oil-free compressors R-134a RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw External installation with very low sound level Cooling circuit with

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS Indoor motor-driven evaporating units LER 0-0 kw Compact and silent machines with remote dissipation into the air Scroll compressor PLUS R-0A R-0A refrigerant Cooling only Split version Electronic expansion

More information

44,9 202,0 kw. technicalcatalogue

44,9 202,0 kw. technicalcatalogue Packaged air cooled liquid chillers for outdoor installation equipped with scroll compressor and microchannel condensing coils 44,9 202,0 kw technicalcatalogue T_PYXU_0413_GB INDEX EUROVENT CERTIFICATION...

More information

Neosys Product catalogue

Neosys Product catalogue 00/0 Neosys Product catalogue Providing indoor climate comfort NEOSYS 00 0 kw Air cooled chiller/heat pump YEAR WARRANTY* Quality makes the difference* Introduction to the range NEOSYS is providing chilled

More information

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps.

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps. Air/water cooled chillers and heat pumps 41 303 kw General BETA ECHOS is a range of chillers and ductable air-water heat pumps. Configurations HP: Reversible heat pump LE: For connection to remote evaporator

More information

GHE Dehumidifiers for radiant cooling systems with heat recovery

GHE Dehumidifiers for radiant cooling systems with heat recovery Dehumidifiers for radiant cooling systems with heat recovery The dehumidifiers with heat recovery of high efficiency series were designed to provide dehumidification and fresh air in a residential area

More information

Air-to-water scroll chillers

Air-to-water scroll chillers Air-to-water scroll chillers Model CGA 040 to 115 Cooling capacity: 14-40 kw CG-PRC031B-GB Table of Contents Technical specifications...4 Standard configuration... 4 Hydraulic version... 4 Casing... 4

More information

RMA AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

RMA AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL RMA ECO-FRIENDLY REFRIGERANT GAS AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the

More information

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED EQV R-407C WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED Size Cooling Heating [kw] [kw] 5 1,9 2,2 7 2,4 2,5 9 2,6 2,5 15 3,3 3,2 17 3,7 3,7 REPLACE: BT02E008GB-01 The Versatemp EQV units

More information

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: 40-158 kw Nominal heating capacity: 41-159 kw Carrier China Carrier Corporation is a subsidiary of the United Technologies

More information

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB Next P 6 112 kw COOLING 5 93 kw HEATING Heat pump air conditioners with upflow air delivery technicalcatalogue T_NXTP_0411_GB INDEX GENERAL CHARACTERISTICS... 3 SERIES IDENTIFICATION... 4 MODEL IDENTIFICATION...

More information

DOMINO. Line Heavy Commercial & Industrial. Air/water chillers with axial or centrifugal fans; plate or shell and tube exchangers.

DOMINO. Line Heavy Commercial & Industrial. Air/water chillers with axial or centrifugal fans; plate or shell and tube exchangers. DOMINO Line Heavy Commercial & Industrial Air/water chillers with axial or centrifugal fans; plate or shell and tube exchangers. The pictures in the catalogues are not binding, accessories represented

More information

Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

Большая библиотека технической документации   каталоги, инструкции, сервисные мануалы, схемы. Большая библиотека технической документации http://splitoff.ru/tehn-doc.html каталоги, инструкции, сервисные мануалы, схемы. AIR BLUE AIR BLUE air conditioning Homes Easy to install and use, quiet, attractive,

More information

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation AIR-TO-WATER HEAT PUMPS 30RQV 017-021 NEW Nominal cooling capacity 15-18 kw Nominal heating capacity 17-21 kw greenspeed Easy and fast installation Hydronic module available Inverter technology compressor

More information

kw. technicalcatalogue

kw. technicalcatalogue Packaged air cooled liquid chillers in A class energy efficiency for outdoor installation equipped with scroll compressor and microchannel condensing coils 108 876 kw technicalcatalogue T_PYXCLA_0413_GB

More information

TCHVZ TCEVZ

TCHVZ TCEVZ K20310EN ed. 3 TCHVZ 1200 31630 TCEVZ 1200 31630 Serie Z-Flow Macrosystem 171,9 1.629,2 kw TCHVZ - Water cooled water chillers with R134a ecological refrigerant. Semi-hermetic screw compressor range. TCEVZ

More information

2017 HYDRONIC SYSTEMS MINI CHILLER FULL DC INVERTER. AIR-TO-WATER HEAT PUMP cooling - heating

2017 HYDRONIC SYSTEMS MINI CHILLER FULL DC INVERTER. AIR-TO-WATER HEAT PUMP cooling - heating 2017 HYDRONIC SYSTEMS MINI CHILLER FULL DC INVERTER AIR-TO-WATER HEAT PUMP cooling - heating MINI CHILLER Highly efficient heat pump for summer and winter air conditioning. Ideal for residential and commercial

More information