Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Size: px
Start display at page:

Download "Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria"

Transcription

1 Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed using an exhaustive search method that optimized the cooling capacity of the ventilation air and the capacity of the cooling panels at the same time. With these supply air conditions, the room air conditions provide a high level of thermal comfort. Because the cooling panels transfer heat through radiation and convection, the room feels comfortable even at a higher dry bulb temperature. Table 3-Outdoor and Space Conditions Dry Bulb ( F) Humidity Ratio (gr/lbm) Dew Point ( F) (for supply air) Outdoor Air Conditions Supply Air Conditions Room Air Conditions Because the building originally had four AHUs, each serving one quadrant of the building, four new AHUs will each serve the same quadrants. The design criteria for the Pinnacle units, described in the next section, are as follows: Table-4-AHU Criteria Unit Name Pinnacle Unit Quadrant Served Airflow rate (cfm) Designation AHU-1 PVS-09 Northwest 4,000 AHU-2 PVS-09 Southwest 5,600 AHU-3 PVS-18 Northeast 9,700 AHU-4 PVS-09 Southeast 6,650 17

2 The specific size of AHU is based on air flow rate. Refer to appendix for the Pinnacle Unit Selection Table used to determine the size of each AHU. Refer to appendix for calculations of ventilation air. The amount of ventilation air is calculated using ASHRAE Standard minimum outdoor air requirement. The airflows are different from the original design because the multiple spaces equation of Standard 62 is not used in this design. Table 3 summarizes these requirements: Table 5-Ventilation Rates Space Occupancy Load Ventilation People /1000 ft 2 CFM/Person Conference room Office space 7 20 Cafeteria Seating Area Reception Area The airflow rate of AHU-3 is higher than the other units because it serves the servery/dining room. Additionally, a flat maximum occupancy of 120 people is used in the dining room in modeling the building. Pinnacle Ventilation System The SEMCO Pinnacle Ventilation System AHU (PVS) was used to replace the existing AHUs. This is because the Pinnacle System can produce low dew point space temperatures economically regardless of the temperature of the chilled water suuplied to the cooling coils. The PVS is comprised of a total energy wheel, a cooling coil, a passive 18

3 dehumidification wheel, a post-cooling coil, a supply fan, and a return fan. Because the PVS has two energy recovery wheels, it is advantageous to use in this application. The AHU components are described below, but the actual design was performed by selection software provided by SEMCO. The passive dehumidification wheel removes moisture more effectively than dessicant-based cooling or even a dual-wheel energy recovery system. Thus, it can produce the low dew point space temperature that is needed to decouple the space sensible and latent loads. Figure 5 demonstrates its dehumidification capacity as a function of wheel speed. This shows that the amount of dehumidification can be altered by controlling the speed at which the wheel rotates. Figure 5 19

4 The cooling coil, though part of the overall system, was selected using the USA Coil software. The conditioning of the air in the PVS is not dependent on the chilled water temperature. This makes it ideal for this particular application because the chilled water system serves two buildings. The controls are much simpler if the chilled water temperature is uniform throughout the system. Figure 6 displays the cooling coil selection for AHU-1. Refer to the appendix for the cooling coils of the other three AHUs. Figure 6 Normally, a sensible wheel is used to recover sensible heat from the return air to increase the supply air temperature. The supply air temperature needs to be increased because overcooling can occur if the space loads are too small. This can happen when the space is unoccupied. When a space is unoccupied, the humidity can be controlled by reheating the air after it leaves the cooling coil. However, the PVS passive 20

5 dehumidification wheel must raise the temperature of the supply air to achieve the desired humidity ratio. Consequently, the system needs a sensible cooling coil to postcool the supply air. The post-cooling coil was also selected using the USA Coil software. Figure 7 displays the coil selection for the post-cooling coil for AHU 1. Refer to the appendix for the post-cooling coils of the other three AHUs. Figure 7 Air System Modeling Cooling loads for the building are modeled using Carrier s Hourly Analysis Program (HAP). The air system is modeled as a two-pipe fan coil unit with common ventilation. The ventilation rates were those calculated in the appendix. This HAP model provided the total sensible load for each space. This information was used to design the radiant panel system discussed in the next section. The program also calculated the cooling load on the chillers in the central plant. Refer to the energy comparison section for a discussion on the reduction of cooling load on the chillers. 21

6 The most important HAP output is the breakdown of the total cooling load into sensible and latent components. Refer to the appendix for the DOAS air system output. This shows that the air system can adequately handle the entire modeled latent load using the specified supply air conditions. There are several ways that the AHU could be modeled using the SEMCO modeling software, but because the space latent load is handled entirely by the DOAS, the air system is modeled to determine the performance data for peak space latent loads. Figure 8 shows the model of AHU-1. Refer to appendix for the models of AHU-2, AHU- 3, and AHU-4. It is clear that the PVS is capable of producing the required supply air and room conditions. Figure 8 also shows the energy savings that are achieved using the PVS. While this shows that the PVS saves energy, it compares the DOAS system to a conventional system with the same supply air and room conditions. The current system uses a supply air condition of saturated 55 F air, and a room condition of 75 F and 55% RH. Because of the difference in conditions, more accurate energy savings are predicted using HAP. Refer to the energy comparison section. 22

7 Refer to appendix for AHU-1 schematic. 23

8 Radiant Cooling Panel System Radiant cooling panels are used in every space in the building to remove sensible space loads that the DOAS cannot handle. Invensys Building System panels are selected using their Magic 6 product selection software. Because the reflected ceiling plan of the building is already set up in a 2 4 grid, 2 4 panels are selected. To maximize the panels cooling capacity, the panels are free-hanging at 8-0, or 1-6 below the original ceiling line. The radiant panel system is also designed to take up at most 50% of the total ceiling area to allow for other ceiling fixtures, such as lights, diffusers, and sprinkler heads. For each quadrant, a pump delivers water to the radiant panel control closets on each floor. In the control closets, one control valve for each zone controls the inlet temperature of the water in one of the spaces. Design The total space sensible load is calculated using the HAP model. A Microsoft Excel spreadsheet (see appendix) is used to determine how much of the space sensible load could be handled by the DOAS system. The remainder of the sensible load is met by the radiant panels. The radiant panel inlet water temperature is chosen somewhat arbitrarily, but the mean temperature difference is chosen to provide maximum capacity for each panel. Table 4 summarizes the radiant panel design choices. Refer to appendix for Magic 6 software selection outputs. 24

9 Table 6-Radiant Panel Design Criteria Room Dry Bulb Temperature ( F) 78 Panel Inlet Temperature ( F) 52 Panel Outlet Temperature ( F) 60 Mean Panel Temperature Difference ( F) 22 Total Capacity (Btu/ft 2 ) 33.6 Pressure Drop (psi) 2.8 Water Velocity (fpm) 85 The air side temperature difference ( T) is only 20 F, compared to a normal DOAS T of about 30 F. This means that the DOAS cooling capacity is relatively small, because the cooling load is directly proportional to the T of the standard air by the equation Q=1.08 scfm T. Consequently, the radiant panels have to remove more of the space latent load. The way that the building envelope is currently designed allows more sensible solar and envelope load into the space than can be handled by the DOAS system and an appropriate amount of radiant panel area (<50% of the total floor area). To overcome this problem, half of the windows in the exterior private and open offices were replaced with spandrel panels that were modeled as equal in performance with the wall construction. This exchange is discussed in the cost comparison section. This envelope alteration did not completely solve the problem in the exterior offices. In the perimeter spaces, more panel area, about 60% of the ceiling area, was able to completely handle the sensible load. In corner offices and some of the perimeter offices, the amount of air supplied to the space was increased slightly to overcome the sensible load. Refer to the appendix for the complete design of every space. To demonstrate that the radiant panel system can work in every space, figures 9 through 13 show sample radiant panel layouts for each type of space. These select spaces are on the second floor and are served by either AHU-1 or AHU-2. In each figure, the 25

10 blue 2 4 panels are the radiant panels. The radiant panels in the interior offices are able to handle the sensible load, utilizing less than 50% of the ceiling area. Figure 9 Figure 10 26

11 The percentage of ceiling area that the radiant panels cover is about 55%, but there is still adequate room for other ceiling fixtures. The ventilation air is increased to 30 cfm. Figure 11 The radiant panel area in the corner office is about 60% of the ceiling area, but there is still adequate room for other ceiling fixtures. The ventilation air in this room is increased to 60 cfm. This is a large increase, but the office is oriented to the southwest, has a large envelope area, and thus receives a higher solar load. 27

12 Figure 12 The radiant panels in the conference room are able to handle the space sensible load. The panels take up less than 50% of the ceiling area. This is very important in the conference room, because there are extra ceiling fixtures, such as dimmable lights and a projector. 28

13 Figure 13 The radiant panels in the open office area are able to handle the space sensible load, utilizing less than 50% of the ceiling area. Panel Piping For modeling purposes, the building is split into four main zones that correspond to the areas that each AHU serves. These zones are divided into mini-zones that correspond to a particular use group, such as perimeter enclosed offices with south-facing exposure. The purpose of this grouping is to separately control the radiant panel water flow to each mini-zone. Each mini-zone has its own control valve in a control closet that 29

14 can easily be manually adjusted and maintained. The location of the control valves is not only advantageous to maintenance. If the control valves were located above the ceiling in the space, a leak could drip into the space. Locating the control valves in a central closet, however, reduces the risk of a leak developing above the space. Figure 14 on page 32 shows the location of the control closet for AHU-2 on the second floor. The valves are shown outside of the closet for clarity. One pump serves the control closets of each AHU, and these pumps are located in the basement. It would be optimal to place them in the same quadrant on one of the floors to be closer to the control closets, but the pumps take up floor space and have the potential to leak. While detailed controls for the piping system are out of the scope of this report, it is necessary to discuss the basic control sequence. The water for the panels comes from the chilled water system, which supplies chilled water at 44 F. A three-way valve is used to mix returning 60 F water with the chilled water supply to maintain the required 52 F inlet water temperature. One concern about locating chilled water piping in a space is what happens when the air system that normally controls condensation is turned off at night and humidity is allowed to build up. In this case, condensation would occur when 52 F water was initially pumped back into the system in the morning. To prevent this, the three-way valve can control the water temperature to ensure that is above the dew point of the space. Another control valve is placed farther down the supply line and is controlled by a temperature sensor located at the inlet of the panel system of a typical space. Condensate sensors in each room sense any condensation from the panels in the room. The 30

15 condensate sensors are located at the inlet of the piping, near the ceiling, to prevent tampering. If the condensate sensor is tripped, the control valve in the control closet for that mini-zone shuts down the flow to that mini-zone. Figure 15 on page 33 gives an example of how one mini-zone could be controlled. 31

16 Picture not available due to security reasons. Figure 14 32

17 Picture not available due to security reasons. Figure 15 33

18 Mechanical System Energy Analysis The new DOAS/Radiant system was compared to the current VAV system in terms of monthly electrical energy usage and chiller plant load. The load breakdown of each system was also compared. Table 7 summarizes the chiller plant load of each system from the Phase 2 building only. The original VAV system serves the original building. Table 7-Chiller Plant Loads System Chiller Plant Load (tons) Original VAV System 541 DOAS/Radiant Parallel System 122 Figure 16 shows the cooling load breakdown of the original VAV system. Note how small the envelope load is in comparison to the Outdoor Air Load. Figure 17 shows the cooling load breakdown of the DOAS/Radiant System. Here, the envelope load (including solar load) is a much higher percentage of the overall load because the OA load does not factor in to the cooling load estimate. This also demonstrates why eliminating one-half of the office windows contributes so strongly to the overall load on the panels. 34

19 VAV System Cooling Load Breakdown Envelope 3% Electric 32% OA Load 55% Occupant 9.74% Figure 16 DOAS/Radiant Cooling Load Breakdown Envelope 20% Occupant 13% Total Electric 67% Figure 17 35

20 Mechanical System Cost Comparison The first cost and monthly operating costs of the original VAV and DOAS system were compared. These estimates do not take into account parts of the mechanical system that did not change with the DOAS/Radiant system redesign. Because the chiller plant serves both Phase 1 and Phase 2 buildings, the central plant configuration cannot be altered. However, because the DOAS/Radiant system reduces the Phase 2 building cooling load by so much, one of the water cooled electric chillers can be downsized from 650 tons to 350 tons. This also means that one of the cooling towers can be downsized to match the condenser water flow from the smaller chiller. The main first cost savings, however, come from the reduction in ductwork. Table 8 shows a summary of the first costs of each system and the amount of savings that the DOAS/Radiant system produces. Table 8-First Cost Comparison Item Unit Cost-VAV Units-VAV VAV Unit Cost-Parallel Units-Parallel Parallel Savings 650 tonabs Chiller $321,000 1 $353,100 $321,000 1 $353,100 $0 650 ton WC Chiller $229,500 3 $757,350 $229,500 2 $504,900 $252, ton WC Chiller N/A N/A $132,000 1 $145,200 -$145, ton CT $26,796 4 $117,902 $26,796 3 $88,427 $29, ton CT N/A N/A $16,433 1 $18,076 -$18,076 Ductwork 1 $4/ft $744,000 $1/ft $186,000 $558,000 AHU-1 $77,808 1 $85,589 $24,378 1 $26,816 $58,773 AHU-2 $77,808 1 $85,589 $26,366 1 $29,003 $56,586 AHU-3 $77,808 1 $85,589 $35,903 1 $39,493 $46,096 AHU-4 $77,808 1 $85,589 $28,372 1 $31,209 $54,380 Radiant Panels 1 N/A N/A N/A $13/ft ft 2 $636,750 -$636,750 $255,733 All cost estimates are from RS Means, 2003, unless noted otherwise 1: Cost estimate from Mumma. "Ceiling Panel Cooling Systems," ASHRAE Journal: ASHRAE, November

21 The DOAS/Radiant system also saves operating costs. An energy analysis is performed for both VAV and DOAS/Radiant systems using the HAP which shows that the DOAS/Radiant system also has a lower operating cost. Table 9 summarizes these figures, while Figure 18 compares each system visually. Table 9 also compares the energy usage for each system. Table 9-Monthly Electric Operating Costs Electric Cost Electric Usage (kwh) Month DOAS VAV Month DOAS VAV Jan $37,569 $45,143 Jan 540, ,443 Feb $36,159 $41,649 Feb 517, ,503 Mar $41,326 $49,954 Mar 609, ,669 Apr $42,668 $52,720 Apr 616, ,326 May $45,969 $56,471 May 654, ,653 Jun $52,421 $64,663 Jun 768, ,262 Jul $56,219 $68,312 Jul 839, ,718 Aug $54,478 $67,740 Aug 805, ,599 Sep $51,367 $63,633 Sep 744, ,787 Oct $44,134 $53,844 Oct 630, ,301 Nov $42,248 $51,454 Nov 599, ,471 Dec $40,651 $48,280 Dec 596, ,487 Total $545,207 $663,860 Total 7,924,132 9,127,219 Savings $118,653 Savings 1,203,087 The spandrel panels that take the pace on about one-half the windows in the office spaces could present a higher first cost. However, a comparison of costs from Means 2003 Facilities Construction Cost Data shows that the cost of an insulated spandrel panel is about the same as a tinted, doubled glazed window. 37

22 Electric Operating Cost Comparison $75,000 $70,000 $65,000 DOAS/Radiant System VAV System $60,000 $55,000 $50,000 $45,000 Dollars $40,000 $35,000 $30,000 $25,000 $20,000 $15,000 $10,000 $5,000 $0 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Figure 18 38

23 Conclusions Because the mechanical system for this building cannot adequately meet the intent of ASHRAE Standard , a DOAS system, coupled with radiant cooling panels was implemented in the building. This new system reduces the cooling load on the chiller plant, reduces first cost and reduces electric operating cost. Because of these savings, this new system should be implemented. The DOAS system provides the correct amount of fresh air to each space to meet the intent of ASHRAE Standard and provide a comfortable indoor air environment. Four SEMCO PVS AHUs are used to condition the outdoor air using the common chilled water temperature so that the central chiller plant does not have to be altered. The DOAS system is able to completely handle the space latent load and some of the space sensible load, so that the radiant ceiling panels only have to take care of the excess sensible load. Radiant panels in every space of the building take care of the excess sensible load while usually taking up less than one-half of the ceiling area, leaving the rest of the ceiling for other ceiling fixtures such as lights, diffusers, and A/V equipment. The radiant panel chilled water flow is controlled at control closets on each floor of the building in every quadrant. Each control closets contain valves for mini-zones that the closet maintains. These control closets utilize space that was formerly vertical duct space and provide a maintenance friendly area for control. Though the DOAS/Radiant system saves money in both first and operating costs, there are a few reservations with the system. First of all, in some spaces, namely the 39

24 corner offices, the radiant panels take up so much of the ceiling that the ceiling height should be lowered to the panel height of 8-0 so that the ceiling has a more uniform height. This is a workable solution, but the occupants of the corner offices may feel that their offices are smaller because of the lower ceiling height. Additionally, in these areas it may be difficult to locate a ceiling position for the sprinkler heads because the lights, diffusers, and panels take up most of the ceiling space. Integrating the fire suppression system with the radiant panel piping system may solve this problem, but that is out of the scope of this redesign. Overall, this DOAS/Radiant system provides a thermally comfortable, cost effective mechanical system. 40

Dehumidification: Energy Efficiency Comparisons

Dehumidification: Energy Efficiency Comparisons Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,

More information

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1 Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9

More information

7. MECHANICAL SYSTEM DESIGN

7. MECHANICAL SYSTEM DESIGN 7. MECHANICAL SYSTEM DESIGN The second primary topic of this thesis is to investigate the application of a dedicated outdoor air system (DOAS) to the SLCC. The stated goals for this thesis of improved

More information

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001 This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.

More information

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS) MSP WRAP-ARUND MULTIPLE SMALL PLATE DEHUMIDIFICATIN TECHNLGY VS. CNVENTINAL DEHUMIDIFICATIN IN DEDICATED UTDR AIR SYSTEMS (DAS) ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++

More information

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory Overview of Chilled Beam Technology Purpose Chilled beam technology is new to the United States but has been used in Europe since the 1950 s. Chilled beams can reduce energy costs, improve indoor air quality,

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

Benefits Offered by Passive Dehumidification Wheel Speed Control

Benefits Offered by Passive Dehumidification Wheel Speed Control Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle

More information

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Continuous Commissioning: A Valuable Partner to Retrofit Projects Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles

More information

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.

More information

National Institutes of Health Building 37 Modernization Bethesda, Maryland MECHANICAL DEPTH EXISTING MECHANICAL SYSTEM

National Institutes of Health Building 37 Modernization Bethesda, Maryland MECHANICAL DEPTH EXISTING MECHANICAL SYSTEM MECHANICAL DEPTH EXISTING MECHANICAL SYSTEM The need to maintain occupancy during the renovation and the strict NIH Design Guidelines were the main driving forces behind the design. The mechanical engineering

More information

The School District of Philadelphia Administration Headquarters Shell and Core Renovations 440 North Broad Street Philadelphia, PA

The School District of Philadelphia Administration Headquarters Shell and Core Renovations 440 North Broad Street Philadelphia, PA 2.0 Depth Work - Alternative Mechanical Designs 2.1 Objectives The goal of designing alternative systems is to compare energy usage, system costs, emissions, lost rentable space, and constructability.

More information

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

NOVEMBER 2012 THE EUROPEAN EXPERIENCE Radiant-cooling systems have progressed in the last few decades, garnering attention as a comfortable and energy- and material-efficient option. 1 Compared with air radiant-cooling hydronic systems use

More information

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae APPENDIX C Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 12:56PM Air System Information Air System Name Equipment Class Air System Type Lobby System CW AHU SZCAV Number

More information

Executive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed

Executive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed Observations, ref ASHRAE May 2013 Journal article Vol. 55, NO 5, pg. 18 VAV Reheat vs. Active Chilled Beams & DOAS. Also published at: http://escholarship.org/uc/item/1jh193x3 Prepared by: S. A. Mumma,

More information

Appendices. Included in this section are

Appendices. Included in this section are Appendices Included in this section are Appendix A Building Overview Appendix B Alternative Mechanical Designs Appendix C Integration of Structural System and Constructability 68 Appendix A Building Overview

More information

The Ed Roberts Campus Berkeley, CA

The Ed Roberts Campus Berkeley, CA The Ed Roberts Campus Berkeley, CA Anderson Clemenceau Mechanical Option Penn State A.E. Senior Thesis April 14, 2015 Leddy Maytum Stacy Architects, Photo by Tim Griffith ASHRAE Climate Zone 3C 99.6% Heating

More information

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection. Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using

More information

DADANCO Technical Paper

DADANCO Technical Paper DADANCO Technical Paper 260 North Elm Street Westfield, MA 01085 Phone: (413) 564-5657 Fax: (413) 568-2969 March 2013 CLASSROOM SOLUTION USING ACTIVE CHILLED BEAMS (Note: This technical paper assumes the

More information

Dehumidifying with Dedicated Outdoor Air

Dehumidifying with Dedicated Outdoor Air Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,

More information

Mechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013

Mechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013 Mechanical Redesign, Proposal Elizabeth C. Mechanical Option September 18, 2013 State Institute of Rehabilitation T e c h n i c a l R e p o r t I 1 Mechanical Redesign, Proposal... 0 Executive Summary...

More information

Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation

Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation Author:John Vavrin, PE Presenter: Dale Herron US Army Corps of Engineers Engineer Research

More information

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 john.woollett@swegon.se, jonas.akesson@swegon.se SUMMARY The main focus of the paper will be on active beam technology regarding

More information

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I. Air System Sizing Summary for AHU/CU-1 AHU/CU-1 Floor Area 1678.0 ft² Central Cooling Coil Total coil load 4.8 Tons Total coil load 57.8 MBH Sensible coil load 41.8 MBH Coil CFM at Jul 1500 1909 CFM Max

More information

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION ENERGY EFFICIENT DEHUMIDIFICATION PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM Provides a very high degree of latent cooling using only a minimal amount of conventional cooling input Substantial energy

More information

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. M&V Real Results of High Performance Design Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. Overview Measurement & Verification (M&V) Plan for New

More information

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)

More information

Auburn University Basketball Arena:

Auburn University Basketball Arena: Auburn University Basketball Arena: How Building Data Analytics Achieved Energy and O&M Savings While Improving Comfort and Sustainability Eric Moore, PE, CEM, Auburn University Hadas Webb, CEM, Cimetrics

More information

Modular Active. Chilled. Beams

Modular Active. Chilled. Beams Modular Active Chilled Beams How Twa MAC Beams Work Primary air (100% outside air) is dehumidified to between 50-57 F dew point and is used to: control the latent requirements of the space, provide fresh

More information

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80 NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80 Carrier Software Systems Carrier Corporation Syracuse, New York rev October 10, 2013 Copyright 2013 Carrier Corporation, All Rights Reserved Page

More information

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes In Humid Climates BY DAVID A. JOHN, P.E., MEMBER ASHRAE; DREW ELSBERRY, MEMBER ASHRAE Designing g a building s HVAC system requires designers

More information

Chilled Ceilings / Beams Working Principles & Applications

Chilled Ceilings / Beams Working Principles & Applications 5 th International Conference on Energy Sustainable Energy Polices and Technologies 15-17 October 2014 Chilled Ceilings / Beams Working Principles & Applications Francis W H Yik ATAL Building Services

More information

F.W. Olin Physical Science Laboratory

F.W. Olin Physical Science Laboratory Mechanical Systems Existing Conditions Evaluation Presented on Page 1 of 16 Table of Contents Executive Summary Depth p.3 Executive Summary Breadth p.4 Introduction & Background p.5 Alternatives p.7 Breadth

More information

Designing Energy Efficient Outdoor Air Systems

Designing Energy Efficient Outdoor Air Systems Designing Energy Efficient Outdoor Air Systems Joseph Thorndal Applied Products Sales Manager Greenheck, Schofield, Wisconsin 1 Joseph Thorndal BS Industrial Engineering North Dakota State University Work

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to

More information

Underfloor Air Distribution:

Underfloor Air Distribution: Underfloor Air Distribution: An underfloor air distribution system utilizes a plenum space between the structural slab and the underside of a raised floor to distribute the conditioned air to the room.

More information

HVAC: The Next. Variable-air-volume systems. Outside-the-box thinking suggests the integration of dedicated

HVAC: The Next. Variable-air-volume systems. Outside-the-box thinking suggests the integration of dedicated cse0301doas.qxd 1/31/2003 9:09 AM Page 38 HVAC: The Next Outside-the-box thinking suggests the integration of dedicated By STANLEY A. MUMMA, Ph.D., P.E., ASHRAE Fellow Professor of Architectural Engineering

More information

Time-Based Scheduling of Residential Ventilation

Time-Based Scheduling of Residential Ventilation Time-Based Scheduling of Residential Ventilation by Armin Rudd USDOE Building America Program for EEBA Conference 2000 Building for Peak Performance Denver, Colorado 26 October 2000 Climate Specific Design

More information

Do All DOAS Configurations Provide the Same Benefits?

Do All DOAS Configurations Provide the Same Benefits? TECHNIL FTURE This article was published in ASHE Journal, July 2014. Copyright 2014 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Challenges and Methods of Estimating a Conceptual HVAC Design

Challenges and Methods of Estimating a Conceptual HVAC Design Challenges and Methods of Estimating a Conceptual HVAC Design ABSTRACT In any conceptual HVAC design, estimators are faced with the challenge of trying to capture all of the pieces that complete a system.

More information

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency Application Note 24 AHRI 920 Performance Rating and Comparisons I NTRODUCTION In 2015, the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) introduced a performance rating for dedicated outside

More information

Redesign of Bennett Hall HVAC System

Redesign of Bennett Hall HVAC System MEE 488 April 18, 2006 Redesign of Bennett Hall HVAC System Greg Andreasen Michael Chicoine Florent Hohxa Jason Jacobe Mechanical Engineering, University of Maine, Orono ME 04473, USA ABSTRACT Our task

More information

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully

More information

Chilled Ceiling Condensation Control Experience In A Movable Sash Building

Chilled Ceiling Condensation Control Experience In A Movable Sash Building Chilled Ceiling Condensation Control Experience In A Movable Sash Building Introduction: A dedicated outdoor air system (DOAS) with a parallel sensible cooling chilled ceiling, or ceiling radiant cooling

More information

Technical Assignment 3

Technical Assignment 3 0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Technical Assignment 3 Mechanical Systems and Existing Conditions Report David H. Koch Institute for Integrative

More information

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation Mechanical Technical Report 1 Standard 62.1 Ventilation Compliance Evaluation Lutheran Theological Seminary at Philadelphia The New Learning Center Prepared For: William P. Bahnfleth, Ph.D., P.E. Department

More information

APPLICATION GUIDE BEAMS

APPLICATION GUIDE BEAMS BEAMS There is an increasing need for energy efficient air conditioning systems as energy codes become more stringent. Chilled beam systems are one such alternate to traditional all air conditioning systems.

More information

Integrated Building Environmental Design Case Study: Beijing Parkview Green

Integrated Building Environmental Design Case Study: Beijing Parkview Green Integrated Building Environmental Design Case Study: Beijing Parkview Green The 7th International Energy Agency Annex 44 Forum 24 October 2007 Dr Raymond Yau Director Ove Arup & Partners Hong Kong Ltd.

More information

Practical and Effective Approaches to Residential Ventilation for Production Builders

Practical and Effective Approaches to Residential Ventilation for Production Builders Practical and Effective Approaches to Residential Ventilation for Production Builders by Armin Rudd USDOE Building America Program for Affordable Comfort Conference 2002 Cincinnati, Ohio 18 April 2002

More information

EarthWise System Seminar

EarthWise System Seminar EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States

More information

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report East Liberty Presbyterian Church 14 009 For: By: East Liberty Presbyterian Church Jeffery Ison, James Construction Date: October

More information

Energy Efficient Measures That Add Little or no. Program Lights & Appliances: How To Benefit from the Low-Hanging Fruit

Energy Efficient Measures That Add Little or no. Program Lights & Appliances: How To Benefit from the Low-Hanging Fruit Energy Efficient Measures That Add Little or no FirstEnergy Cost Energy to Construction Efficient New Homes Program Lights & Appliances: How To Benefit from the Low-Hanging Fruit 1 2 Optimizing Savings

More information

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL SECTION 15100 PART 1 GENERAL THIS IS A DESIGN GUIDE NOT A SPECIFICATION Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL HVAC SYSTEMS APPLICATIONS 1.1 SCOPE: The intent of this

More information

Adding More Fan Power Can Be a Good Thing

Adding More Fan Power Can Be a Good Thing This article was published in ASHE Journal, May 14. Copyright 14 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

Achieving Dry Outside Air in an Energy-Efficient Manner

Achieving Dry Outside Air in an Energy-Efficient Manner AT-01-7-2 Achieving Dry Outside Air in an Energy-Efficient Manner Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE Kurt M. Shank Student Member ASHRAE ABSTRACT The central thrust of this paper is to develop

More information

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning HVAC 101 The Basics of Heating, Ventilation and Air Conditioning HVAC Heating, Ventilation and Air Conditioning Provides comfort for people Allows humans to exist under adverse conditions. Comfort Comfort

More information

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING Danny Hall, National Sales Manager, Desert Aire Corp., Milwaukee, WI USA Traditionally, a heat pump has relied on a reversing valve system

More information

HVAC 101. H V A C S y s t e m s

HVAC 101. H V A C S y s t e m s H V A C 1 0 1 S y s t e m s Introduction & Overview Should you care? Mechanical System Types Components & operation Popular Application Key Issues and Design Considerations System Comparisons First Cost

More information

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS CARROLL COUNTY PUBLIC SCHOOLS LIFE CYCLE COST ANALYSIS SUMMARY DGS PROCEDURES FOR THE IMPLEMENTATION OF LIFE CYCLE COST ANALYSIS AND ENERGY CONSERVATION OCTOBER, 2010 G.A.I.#09090 GIPE ASSOCIATES, INC.

More information

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

HONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING

HONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING ASHRAE s BEST This article was published in ASHRAE Journal, November 2010. Copyright 2010 American Society of Heating, Refrigerating and -Conditioning Engineers, Inc. Reprinted here by permission from

More information

Radiant Heating & Cooling for Commercial Buildings

Radiant Heating & Cooling for Commercial Buildings Radiant Heating & Cooling for Commercial Buildings Kaveesh Padiachy, PEng, PMP, LEED AP Business Development Manager Central Canada kaveesh.padiachy@uponor.com www.uponorpro.com/engineering Radiant Heating

More information

Technical Assignment 3 11/15/04. Executive Summary

Technical Assignment 3 11/15/04. Executive Summary Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria

More information

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

EADQUARTERS. Technical Report One. Stephanie Kunkel   Mechanical Option EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

Standards and Guidelines. Presented by: Aric Murray December 12, 2014 TDSHS Ventilation Standards and Guidelines Presented by: Aric Murray December 12, 2014 Agenda 1. What are the TDSHS ventilation 1. What are the TDSHS ventilation requirements? 2. Pressure relationships.

More information

Civil Engineering Building

Civil Engineering Building Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

MBNA Career Services Center The Pennsylvania State University University Park Campus

MBNA Career Services Center The Pennsylvania State University University Park Campus University Park Campus Variable Air Volume System and Dedicated Outdoor Air System with Fan Coil Units Comparison AE Senior Thesis Primary Consultant Spring 2003 Dr. Bahnfleth Table of Contents Executive

More information

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013 TDSHS Air Change Requirements and the Basics of Psychrometrics Presented by: Aric Murray December 06, 2013 Agenda 1. What are the air change requirements and how do you calculate them? 2. Why are air change

More information

Annual environmental performance evaluation of light and heat in daylight harvesting systems using Radiance and NewHASP

Annual environmental performance evaluation of light and heat in daylight harvesting systems using Radiance and NewHASP Annual environmental performance evaluation of light and heat in daylight harvesting systems using Radiance and NewHASP 2017 International Radiance Workshop August 22 24 Portland, Oregon Chikako Ohki and

More information

Trane CDQ Desiccant Dehumidification

Trane CDQ Desiccant Dehumidification Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features

More information

Efficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden

Efficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden Efficient energy recovery in AHU DOHA, Qatar 11.04.2010 Timo Schreck Enventus AB, Sweden Main principles for cooling and dehumidification process in AHU 1. With cooling coil and reheater 2. Energy recovery

More information

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active. TRACE 700 incorporates two chilled beam strategies: passive and active. Passive chilled beams consist of a fin-and-tube cooling coil, contained in a housing (or casing), suspended from the ceiling. Chilled

More information

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx Case Study: Furman University Charles H. Townes Center for Science Michael K. Mantai, PE, CCP President System WorCx AIA Quality Assurance Learning Objectives 1. Case study example of Chilled Beam technology

More information

Technical Assignment 1

Technical Assignment 1 0 Technical Assignment 1 ASHRAE Standard 62.1 Ventilation and Standard 90.1 Energy Design Evaluations Compliance Analysis David H. Koch Institute for Integrative Cancer Research Massachusetts Institute

More information

Munters Heat Exchangers

Munters Heat Exchangers Munters Heat Exchangers Brad Perdew Applications Engineer 8/27/12 DOAS Configurations Cheryl Hughes Regional Sales Manager October 11, 2016 cheryl.hughes@munters.com Munters DOAS Configurations Presentation

More information

Mold/Moisture Control Case Study

Mold/Moisture Control Case Study Mold/Moisture Control Case Study Presented by Boggarm S. Setty, P.E., FASHRAE Setty & Associates, Ltd. www.clima2005.ch Clima 2005 Lausanne Solothurnstrasse 13 CH-3322 Schönbühl Switzerland th 8 REHVA

More information

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012 HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

2 Existing Mechanical System

2 Existing Mechanical System 2 Existing Mechanical System 2.1 Design Objectives and Requirements The Gossett Field House project consists of a 25,000 sqft addition and a 40,000 sqft renovation of the existing facility for the University

More information

4.0 Mechanical Redesign

4.0 Mechanical Redesign 4.0 Mechanical Redesign As my depth area of research, I have performed a detailed analysis of the existing air handling units and the existing conditions of the FIT Science Lab. After one semester of breaking

More information

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems CBE Timothy Moore CENTER FOR THE BUILT ENVIRONMENT SimBuild

More information

Chilled Beams. Getting a Warmer Reception

Chilled Beams. Getting a Warmer Reception Chilled Beams Getting a Warmer Reception Gain an understanding of how chilled-beam technology works, the difference between active/passive chilled beams and potential applications for its use. B y G r

More information

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget VanceFox.com 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal Vol. 49, Jan. 2006. For personal use only. Additional reproduction,

More information

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 2) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Contextual Reminder All-air systems Single zone Terminal reheat Multi-zone Dual-duct VAV Combinations

More information

Direct Digital Temperature, Humidity, and Condensate Control for a Dedicated Outdoor Air-Ceiling Radiant Cooling Panel System

Direct Digital Temperature, Humidity, and Condensate Control for a Dedicated Outdoor Air-Ceiling Radiant Cooling Panel System OR-05-3-3 Direct Digital Temperature, Humidity, and Condensate Control for a Dedicated Outdoor Air-Ceiling Radiant Cooling Panel System Stanley A. Mumma, PhD, PE Fellow ASHRAE Jae-Weon Jeong, PhD Associate

More information

A New Approach to Museum HVAC Design ASHRAE TECHNOLOGY AWARD CASE STUDIES

A New Approach to Museum HVAC Design ASHRAE TECHNOLOGY AWARD CASE STUDIES A New Approach to Museum HVAC Design PHOTO CREDIT JON MCNEAL, SNØHETTA.JPG The San Francisco Museum of Modern Art (SFMOMA) consists of a 10-story addition and a renovated existing five-story building.

More information

High-Performance VAV Systems

High-Performance VAV Systems This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER A. Bolher 1, E. Fleury 1, J.R. Millet 1, D. Marchio 2 and P. Stabat 2. 1 Centre Scientifique et Technique du bâtiment, 84, avenue

More information

SECTION I: EXISITNG SYSTEM AND PROPOSED SYSTEMS

SECTION I: EXISITNG SYSTEM AND PROPOSED SYSTEMS SECTION I: EXISITNG SYSTEM AND PROPOSED SYSTEMS Original Design: Traditional Central Heating and Cooling Heating and Cooling System Schematic Original Design Ventilation Schematic: Existing system summary:

More information

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XIN INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

Passive building in Hot and Humid Climates

Passive building in Hot and Humid Climates 9 th Annual North American Passive House Conference Passive building in Hot and Humid Climates Lisa White 1 Overview 1. Thermal Comfort 2. Drivers of sensible and latent cooling loads 3. Passive cooling

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information