Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL

Size: px
Start display at page:

Download "Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL"

Transcription

1 Indholdsfortegnelse Danvent Air Handling Units SERVICE MANUAL

2

3 Service Servicing of the Air Handling Unit Your ventilation system is equipped with a Danvent Air Handling Unit (AHU) which will contribute to creating a good indoor climate for the building for many years to come. To ensure the best possible indoor climate it is important that the performance of your AHU does not deteriorate because of neglected service and inspection. This can be the cause of running problems and reduced efficiency. Such deteriorations can have a great impact on the total running costs and safety aspects of the ventilation system. It is therefore strongly advised to service the system on a regular basis. These instructions list the few necessary service and maintenance procedures required to ensure optimal AHU running performance.! NB! Remember to switch off the main power supply The design and construction of the AHU ensures that necessary service and maintenance is reduced to an absolute minimum. Large inspection doors ensure quick and easy access to all components requiring service and inspection. The following 2 pages give a simple summary as a guide to planning the necessary service and maintenance work on the AHU. The remaining pages give a closer look at servicing and maintaining the AHU s individual components. 3

4 Service Summary The service intervals stated are intended as a guide only, and apply for operating with normal air quality for comfort ventilation. In operating conditions that are particularly dusty or humid, for example, or where the air is aggressive, shorter service intervals may be required. Inspection and check Service work to be carried out! NB! Remember to switch off the main power supply To be carried out once a year To be carried out when the recommended pressure drop is exceeded To be carried out after every 5000 running hours or at least once a year To be carried out four times a year Air Handling Unit Clean the AHU Check the seals and closing mechanisms Dampers Check the air-tightness Bag filters Replace the filter cells and check the seals at the filter cells Compact filter Replace the filter cells Rotary heat exchanger Check the condition of the rotor and that it turns easily Check the brush seals Check the Varimatic drive system Check and tighten the belt drive 4

5 Service Summary Plate heat exchanger Check the heat exchanger Check the air-tightness of the by-pass damper Clean the drip tray, drain and water trap Run-around coil heat exchangers Check the condition of the coils Vent the coils and piping system Clean the drip tray, drain and water trap (exhaust air) Check the droplet eliminator (exhaust air) Pump Heating coil Check the condition of the coil Vent the coil Check the safety thermostats (electrical coil) Cooling coil Check the condition of the coil Vent coil which use water and brine as cooling medium Clean the drip tray, drain and water trap Check the droplet eliminator Fan Check the fan impeller Check the vibration isolators and flexible connections Lubricate bearings for the large motor sizes Lubricate bearings for the large fan sizes Check and tighten the belt drive Sound attenuator Check the condition of the attenuator Clean the cleanable baffles Air distributor Check the condition of the distributor Volumeter Check the condition of the Volumeter 5

6 Air Handling Unit Air Handling Unit The unit should be cleaned once a year when operating with normal air quality for comfort ventilation with no special hygiene requirements. To clean the unit, dry it off with a dry cloth, or use water mixed with a noncorrosive cleaning medium. Any corrosion i.e. at the filters should be cleaned off immediately, and the surface treated. In special operating conditions, where the air is aggressive or very humid, for example, or where there are special hygiene requirements, the unit shall be cleaned more frequently as required. Cleaning medium and method should be adapted to the relevant conditions. Any corrosion should be cleaned off immediately, and the surface treated. Grilles, for air intake and exhaust air outlet, are to be cleaned at least once a year to prevent blockage. Closing mechanisms are to be lubricated at least once a year. Synthetic door hinges are service free. Seals around inspection doors are to be cleaned at least once a year and are to be checked for leakage. It is recommended to treat the seals with a moisture repellent agent. Connecting pieces for the unit sections, including the Disc-Lock types, are to be checked for tightness at least once a year. All seals are to be inspected at least once a year and are to be repaired if necessary. 6

7 Damper and Mixing Damper Damper and mixing damper Rubber seals between the damper blades themselves and between the damper blades and the frame are to be checked once a year. These seals are not to be lubricated or treated in any other way. Each damper blade is connected by a pivoting system. The steel rods and brass bushes do not require lubrication. The damper blades are fitted with synthetic bearings requiring no lubrication. Air-tightness of the damper, when the damper motor is in the closed position, must be visually checked once a year. The damper motor is to be adjusted if the damper does not close tightly. 7

8 Filter Filter The intervals for the replacement of the filter are very dependant on the concentration of dust in the air passing through the filter. The easiest ways to determine the time for replacing the filter cells are: A. Pressure difference manometer which shows the filter pressure drop. B. Pressure difference switch which gives an electronic signal when the filter is to be replaced. Compact filter The filter are to be replaced when the pressure drop exceeds the recommended level. The filter cells are to be taken out and replaced. The filter cell guide rails are to be cleaned before fitting the new filters. Bag filter The filter are to be replaced when the pressure drop exceeds the recommended level. Release the bagfilter cells by activating the handles and pull out the filter cells of the unit casing. The frame profiles are to be cleaned and all seals checked for damage. The handles and locking guide rails are also to be checked to ensure that they can operate unobstructed. The new filter bags should be pushed carefully into the unit in order to ensure that they are sealed properly. The various filter sizes should be placed in an order corresponding to the way in which the unit is divided up, and the filters should have vertical bags. 8

9 Rotary Heat Exchanger Rotary heat exchanger Rotor The rotor is to be checked at least once a year to ensure that it can turn freely and easily. This can be done by removing the belt drive at the motor and then turning the rotor manually with a hand on the peripheral rotor casing. At the same time the brush seals are to be checked for damage. The bearings are factory lubricated and do not require any service lubrication. During operation the rotor can become dirty. The rotor can be cleaned by blowing through with compressed air. To ease inspection and service the rotor can be pulled out of the unit housing on smaller AHU sizes. Cleaning must be carried out with care so as not to damage the rotor material. Motor and belt drive The bearings are factory lubricated and do not require any service lubrication. The belt drive is to be checked four times a year for correct tightness and that it is undamaged. On smaller AHU sizes with variable speed, the rotor is fitted with an elastic belt drive and supplied with a reserve belt on the rotor. This belt drive does not require service and cannot be shortened. A new belt can be fitted using specialist tools. On all other heat exchangers the rotor has a V-belt with a belt connector. If the belt is no longer tight, it must be shortened to a length which enables the motor base frame tightening spring to hold the belt tight. If new screws are used for the belt connector, they must not have a length which exceeds the thickness of the belt and connector. Remove the excess, if any, with a file. Varimatic system A test switch is positioned behind the cover to the electronic box. The test switch is to be activated once a year in order to ensure that the system functions correctly. In the test situation the rotor must rotate slowly and gradually increase up to maximum speed.! NB! Remember to switch off the main power supply 9

10 Plate Heat Exchanger Plate heat exchanger Once a year the edges of the heat exchanger plates are to be checked for cleanliness and damage. If there is dust on the edges of the plates, remove it with a soft brush. If grease or other such substances are present, then the edges must be washed using grease dissolving detergents. The heat exchanger can be cleaned using a high pressure cleaner with a fine spray nozzle, or by blowing through with compressed air. On the opposite side of the exchanger dirt and water can be removed with a water vacuum cleaner. In order to avoid damaging the plate surfaces, washing and cleaning must be carried out with the utmost care. The surfaces must never be scraped with hard objects. When the heat exchanger is fitted into an AHU which handles air with grease particles, such as exhaust air from kitchens, the grease filter fitted before the AHU must be cleaned every day. The AHU must be stopped when the grease filter has been removed. By-pass damper The damper blades are fitted with synthetic bearings requiring no lubrication. Each damper blade is connected by a pivoting system. The steel rods and brass bushes do not require lubrication. Air-tightness of the dampers, when the damper motor is in the closed position, must be visually checked once a year. The damper motor is to be adjusted if the damper does not close tightly. Condense water drain Once a year clean the drip tray beneath the heat exchanger, as well as the drain and the water trap. 10

11 Run-around Coil Heat Exchangers Run-around coil heat exchangers A heat recovery system of this type consists of a heating coil in the supply airflow and a cooling coil in the exhaust airflow. After an extended running period (normally a few years) dust particles can accumulate on the surface of the coils. This can reduce the efficiency of the coils. The coils can be cleaned using a high pressure cleaner with a fine spray nozzle, or by blowing through with compressed air. Cleaning must be carried out with the utmost care to ensure that the coil fins are not damaged. The piping system must be vented once a year as air in the system can significantly reduce the capacity of the coils. Pump and expansion vessel The service instructions issued by the pump manufacturer must be followed. The pressure expansion system must be checked once a year. If necessary, the pressure must be increased to the correct level. Condense water drain Once a year clean the drip tray beneath the cooling coil, as well as the drain and the water trap. If a droplet eliminator has been fitted to the cooling coil, this must be checked once a year and cleaned if necessary. 11

12 Heating and Cooling Coils Heating and cooling coils! Be careful of hot heating coil and pipe surfaces. Remember to turn off the supply of hot water, steam or electricity before beginning inspection and service. After an extended running period (normally a few years) dust particles can accumulate on the surface of the coil. This can reduce the efficiency of the coil. The coil can be cleaned using a high pressure cleaner with a fine spray nozzle, or by blowing through with compressed air. Cleaning must be carried out with the utmost care to ensure that the coil fins are not damaged. The piping system must be vented once a year as air in the system can significantly reduce the capacity of the coil. Cooling coil Once a year clean the drip tray beneath the cooling coil, as well as the drain and the water trap. If a droplet eliminator has been fitted to the cooling coil, this must be checked once a year and cleaned if necessary. Electrical heating coil The coil has a built-in safety thermostat with an automatic reset function and an overheat thermostat with manually resetting. Both thermostats are positioned behind the inspection door.! NB! Remember to switch off the main power supply 12

13 Fan About the fans in general For the smaller sized units the motor and fan are assembled on guide rails allowing easy extraction from the AHU. Dust can accumulate on the fan impeller which can cause imbalance and vibrations. The fan impeller must therefore be checked once a year and cleaned, if necessary. Vibration isolators and flexible connectors should be checked at the same time. If the vibration isolators are damaged in any way they must be replaced. Motor The motor are usually fitted with factory lubricated bearings which require no futher labrication. Larger motors can be fitted with greasing nipples and bearings which require regular lubrication. Lubricating these types of bearings must be carried out according to the manufacturer s instructions. Fan with V-belt drive Bearings Smaller fans are usually fitted with closed factory lubricated bearings which require no futher labrication. The bearings are fitted into vibration absorbing rubber bushes which should be checked for wear and tear. Larger fans are fitted with factory lubricated bearings and greasing nipples. Lubricating these types of bearings must be carried out after every 5000 running hours or at least once a year. The interval for lubrication are valid for air temperatures of up to +40 C. Reduction of the interval is necessary if the air is of a higher temperature, if the air is polluted or present a high level of humidity, or if the bearings must cope with high loads. Bearing lubrication grease must be of the highest quality and produced using a lithium soap base. Grease which contains additives must not be used. 13

14 Fan Care must be taken not to over grease the bearings. This can result in the bearings becoming overheated and eventually damaged. After lubrication of the bearings the fan should be started as follows: Start the fan and let it run for approximately 2 minutes. The fan must then be stopped and the bearings left to cool down until cold. This process is to be repeated a few times before the fan is allowed to run continuously. V-belt drive The belt drive is to be checked 4 times a year. If one or more of the belts is worn then all belts must be replaced. New and used belts must never be used together as they have different lengths. Check that the pulleys are in line and completely parallel with each other. The belts are to be tightened to a suitably tension. Over tightening can cause unnecessary wear and reduce the life expectancy of the bearings.! NB! Remember to switch off the main power supply Tightening the belts L f kg L mm f mm Profile XPZ XPA XPB Load 1,5 kg 2,7 kg 5,0 kg 14

15 Sound Attenuator and Air Distributor Sound attenuator During operation dust particles can accumulate on the surface of the baffles. Sound attenuators which are designed for dry and wet cleaning are fitted with baffles which can be extracted from the unit casing. Large inspection doors give access to the baffles which can then be easily extracted. Baffles designed for dry cleaning can be cleaned using a soft brush or they can be vacuum cleaned. Baffles designed for wet cleaning can be washed down using a soft brush and soapy water. The detergent used must be non-aggressive. After washing, the baffles must be wiped dry with a cloth. Remember to clean the inside surface of the unit casing before re-fitting the baffles. Air distributor The air distributor, which is fitted on the fan outlet, is to be checked once a year as dust particles can accumulate on the distributor during operation. The dust can be removed using a brush or a vacuum cleaner. Volumeter The measuring probe, which is fitted to the fan inlet opening, is to be checked once a year for dust accumulation. The measuring probe opening must be completely dust free. 15

16 Indholdsfortegnelse Systemair A/S Ved Milepælen 7 DK-8361 Hasselager Denmark Tel.: Fax: mail@systemair.dk GB

Air Handling Units. Danvent DV 190 and

Air Handling Units. Danvent DV 190 and Air Handling Units Danvent DV 190 and 240 www.systemair.dk arge Very large DV 190 and 240 Systemair has developed an extensive expertise within major Air Handling Units up till now usually built as individual

More information

DVU-HP. Integrated Reversible Heat Pump System

DVU-HP. Integrated Reversible Heat Pump System Fans Air Handling Units Air Distribution Products Air Conditioning Fire Safety Air Curtains and Heating Products Tunnel Fans Integrated Reversible Heat Pump System 2 Integrated Reversible Heat Pump System

More information

Air Handling Units. Quick Guide to Danvent DV

Air Handling Units. Quick Guide to Danvent DV Fans Air Handling Units Air Distribution Products Air Conditioning Fire Safety Air Curtains and Heating Products Tunnel Fans Air Handling Units Quick Guide to Danvent DV Den Blå Planet, National Aquarium

More information

lindab we simplify construction Lindab Modular air handling units Service and maintenance manual

lindab we simplify construction Lindab Modular air handling units Service and maintenance manual Lindab Modular air handling units Service and maintenance manual Service and maintenance manual General... 3 2 Warnings and Tips... 3 3 Functional sections... 3 3.1 Fan section... 3 3.2 Heater section

More information

Danvent DV. Modular Air Handling Unit

Danvent DV. Modular Air Handling Unit Fans Air Handling Units Air Distribution Products Air Conditioning Fire Safety Air Curtains and Heating Products Tunnel Fans Danvent DV Modular Air Handling Unit Bella Sky Hotel Copyright: Systemair A/S

More information

EQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4

EQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4 EQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4 ASSEMBLY AND MAINTENANCE INSTRUCTIONS Contents Page Hygienic version..... 2 Delivery...... 2 Safety precautions...... 2 Mounting on the floor......

More information

VEX250H with rotary heat exchanger and EXact control system

VEX250H with rotary heat exchanger and EXact control system 3003433-2014-04-11 VEX250_EXact VEX250H with rotary heat exchanger and EXact control system Unit supplied with (factory fitted): Compact filter FP Filter bag FB Trim damper and blowout zone,tb250 The following

More information

39 HQ Air Handling Units AiroVision

39 HQ Air Handling Units AiroVision VDI 6022 39 HQ Air Handling Units AiroVision Assembly/Installation, Commissioning, Maintenance Manual Type tested Production monitored AHU N : 08.02.251 Range: 39HQ DIN 1946-4 EN 13053 2 Code No: B.8.1.3i

More information

VEX280H with rotary heat exchanger and EXact control system

VEX280H with rotary heat exchanger and EXact control system 3003206-2014-04-15 VEX280_EXact VEX280H with rotary heat exchanger and EXact control system Unit supplied with (factory fitted): VEX280-1 VEX280-2 FP compact filter FB filter bag TB280 trim damper and

More information

Danvent DV 190 and 240

Danvent DV 190 and 240 Fans Air Handling Units Air Distribution Products Air Conditioning Fire Safety Air Curtains and Heating Products Tunnel Fans Danvent DV 190 and 240 Air Handling Units with High Capacity Danvent DV 190

More information

Air Handling Units. Geniox. Quick guide

Air Handling Units. Geniox. Quick guide Air Handling Units Geniox Quick guide Copyright: Systemair A/S, 2. edition 2018. We accept no liability for printing errors or alterations of products. The dimensions and data used in this leaflet are

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE...........

More information

Envistar Operation and Maintenance Instructions

Envistar Operation and Maintenance Instructions Air Handling Unit Envistar Instructions Project:... Air handling with the focus on LCC Address and Telephone Register for Service Supplier: IV Produkt AB Box 3103 SE-350 43 VÄXJÖ, Sweden Street address:

More information

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A CS 2 Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual Form No. 6120A TABLE OF CONTENTS Page Inspection... 2 Shipment of Units... 2 Handling... 2 Installation...

More information

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation Air handling units KLASIK Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation KLASIK air handling units Customer oriented and unique

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

VERSO Air Handling Units

VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P air handling units equipped with recuperation system

More information

COOLING / HEATING COILS

COOLING / HEATING COILS COOLING / HEATING COILS GENERAL INSTALLATION OPERATION AND MAINTENANCE COIL TYPES CHILLED WATER / GLYCOL HOT WATER / GLYCOL DIRECT EXPANSION (EVAPORATIVE COOLING) STEAM DISTRIBUTING STANDARD STEAM Type

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY...................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE..........

More information

Tuning up ventilation systems

Tuning up ventilation systems MULTI-UNIT RESIDENTIAL BUILDINGS Tune-Ups for Energy and Water Efficiency This document is a tool to help reduce energy and water costs and improve comfort in a high-rise residential building through low-cost

More information

English CNA-CNB. Centrifugal fans Installation and maintenance

English CNA-CNB. Centrifugal fans Installation and maintenance 916505-0 English CNA-CNB Centrifugal fans Installation and maintenance 916505-0 GB Centrifugal fans types CNA, CNB, CNA-M and CNB-M installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2

More information

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S USER S MANUAL Heat (Energy) Recovery Ventilator Vents Frigate HRV 120 S Vents Frigate ERV 120 S 2 Frigate HRV(ERV) 120 S CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key...

More information

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL WM150 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an

More information

Centeral Station Air Handling Unit

Centeral Station Air Handling Unit Centeral Station Air Handling Unit CA Series www.windind.com www.windind.com The product range includes double skinned Air Handling Units, double skinned Fan Coil Units, and custom designed packaged roof

More information

INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS

INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS AIRVAC INDUSTRIES & PROJECTS CORPORATE OFFICE: H-2/111, SECTOR-16, ROHINI, DELHI-110 085 PHONE: +91-11-32958731, 27298061 FAX: +91-11-27298061

More information

CxA to Answer this Section

CxA to Answer this Section EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place

More information

Installation, Operating & Maintenance Instructions. Horizontal Models: LH & HL

Installation, Operating & Maintenance Instructions. Horizontal Models: LH & HL Installation, Operating & Maintenance Instructions Horizontal Models: LH & HL Table of Contents Table of Contents... 2 Product Safety... 2 Important Information About Safety Instructions... 2 Receiving...

More information

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation Air handling units KLASIK Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation KLASIK air handling units Customer oriented and unique

More information

Climaster ZerAx. Eco-designkrav. Climaster ZerAx type ZCN-M guide GB

Climaster ZerAx. Eco-designkrav. Climaster ZerAx type ZCN-M guide GB Climaster ZerAx Climaster ZerAx type ZCN-M guide 924784-0 GB Eco-designkrav Important This document is made available as it is. Novenco reserves the right to make changes without prior notice due to further

More information

VERSO Air Handling Units

VERSO Air Handling Units VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO Air Handling Units VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P

More information

AIR HANDLING UNITS MANDÍK

AIR HANDLING UNITS MANDÍK AIR HANDLING UNITS MANDÍK 2 CONTENTS MANDÍK, a. s. The Company... 3 Photo Gallery... 4 Unit Description... 6 Air handling unit parameters according to Eurovent... 7 Product Range of the Air Handling Units...

More information

DANVENT CATALOGUE 1999

DANVENT CATALOGUE 1999 DANVENT CATALOGUE 1999 CONTENTS Contents TC 7-10 Combi-unit 11-15 Combination examples with dimensions and weights 16 Transportation & installation 17-18 Roof unit 19-26 Damper sections 27-30 Filter sections

More information

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT 90% EFFICIENCY HIGHEST EFFICIENCY AIR HANDLING UNIT Packaged energy recovery solutions for Green Buildings Integrated Accumulator, controls and DX Cooling System CLEAN AIR SINCE 1963 Euroclima is a company

More information

Installation, Operating & Maintenance Instructions. Air Handler Models: AH & AV

Installation, Operating & Maintenance Instructions. Air Handler Models: AH & AV Installation, Operating & Maintenance Instructions Air Handler Models: AH & AV Table of Contents Table of Contents... 2 Product Safety... 2 Important Information About Safety Instructions... 2 Receiving...

More information

USER S INFORMATION MANUAL (2,4)SG13B

USER S INFORMATION MANUAL (2,4)SG13B USER S INFORMATION MANUAL (2,4)SG13B Series Gas Heating/Electric Cooling Package Unit Congratulations......your outdoor heating/cooling package unit is a valuable piece of equipment, designed and manufactured

More information

CMHC HOME MAINTENANCE CHECKLIST

CMHC HOME MAINTENANCE CHECKLIST Make sure air vents indoors and outdoors (intake, exhaust and forced air) are not blocked by snow or debris. Check and clean range hood filters on a monthly basis. Test ground fault circuit interrupter(s)

More information

Drying Tumblers Pound Capacity

Drying Tumblers Pound Capacity Drying Tumblers 25-170 Pound Capacity Preventative Maintenance Please refer to your operating manual for detailed maintenance procedures. www.comlaundry.com Part No. 70323301R6 December 2009 Table of

More information

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300 USER S MANUAL Heat Recovery Ventilator Vents Brig HRV 200 Vents Brig HRV 300 2 Brig HRV 200 (300) CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key... 4 Basic unit dimensions...

More information

Preventative Maintenance Tables

Preventative Maintenance Tables Preventative Maintenance Tables Table of Contents I. Table : Gas Fired Domestic Hot Water Heater II. III. IV. Table : Circulating Pump Table : Convectors Table 4: Grille and Diffusors V. Table 5: Unit

More information

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual DOMEKT ReGO 400VE(W)-B Series Air Handling Units EN Content Safety Requirements...3 Transportation...3 Brief Description of the Unit...5 Installation...6 Maintenance...11 Technical Information......13

More information

INSTRUCTION MANUAL Model: SU3022

INSTRUCTION MANUAL Model: SU3022 INSTRUCTION MANUAL Model: SU3022 GUARANTEE This product is guaranteed for 2 years from the date of original purchase. If any defect arises due to faulty materials or workmanship, the unit will, either

More information

Ball Float Controlled. Thermo Dynamic(TD) Trap Safety Valve Condensate Pump Flash Vessel Moisture Separators Deaerator Head Steam Injector Sight Glass

Ball Float Controlled. Thermo Dynamic(TD) Trap Safety Valve Condensate Pump Flash Vessel Moisture Separators Deaerator Head Steam Injector Sight Glass Product of Quality Best Performance Ball Float Controlled Steam Traps Auto Drain Traps Float Valve Air Vent Valves Feed Control Valve Drain Control Valve Thermo Dynamic(TD) Trap Safety Valve Condensate

More information

Fans Air Handling Units Air Distribution Products Fire Safety Air Conditioning Air Curtains and Heating Products Tunnel Fans. Geniox.

Fans Air Handling Units Air Distribution Products Fire Safety Air Conditioning Air Curtains and Heating Products Tunnel Fans. Geniox. Fans Air Handling Units Air Distribution Products Fire Safety Air Conditioning Air Curtains and Heating Products Tunnel Fans Geniox Quick guide Copyright: Systemair A/S, 1. edition 2017. We accept no liability

More information

Ecodesign in SystemairCAD

Ecodesign in SystemairCAD Fans Air Handling Units Air Distribution Products Air Conditioning Fire Safety Air Curtains and Heating Products Tunnel Fans in SystemairCAD A quick guide to ErP ErP 2016 2018 i SystemairCAD To reduce

More information

OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QW*S Series

OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QW*S Series OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: 90-007 QWSERV 90-08 QWSERV with Intelligent Defrost For Use With Bard Through 5 Ton QW*S Series Bard Manufacturing Company, Inc. Bryan,

More information

Novenco Air Handling Units

Novenco Air Handling Units Novenco Air Handling Units Climaster ZCF Guide 919432-0 GB Important This document is provided As is and is subject to change without notice. Novenco reserves this right due to continuous product development.

More information

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS AIR COMFORT AIR TREATMENT 9933 GB 2016.05.25 PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN» INSTALLATION AND MAINTENANCE INSTRUCTIONS contents Page Installation options...... 2 Checks to be

More information

CLIMACIAT AIRTOP. Air handling units. Very short delivery time Double wall with 50 mm insulation. Complete range meeting all the tertiary requirements

CLIMACIAT AIRTOP. Air handling units. Very short delivery time Double wall with 50 mm insulation. Complete range meeting all the tertiary requirements Excellent quality / price ratio Very short delivery time Double wall 50 mm insulation Complete range meeting all the tertiary requirements Air flow : 000 to 7 000 m 3 /h DESCRIPTION Casing Double wall

More information

Maintenance instructions for Duco's Ventilation systems

Maintenance instructions for Duco's Ventilation systems L8000013 Maintenance instructions for Duco's Ventilation systems Table of contents A. Maintenance summary...2 B. Window ventilators...3 B.1 Maintenance frequency...3 B.2 How to clean...4 Window ventilators

More information

How about Savings in Time, Money, Energy and Longer Life?

How about Savings in Time, Money, Energy and Longer Life? Chapter 17: The Value of Maintaining Evaporative Cooling Equipment 97 The Value 17 of Maintaining Evaporative Cooling Equipment 1. Cooling Tower Maintenance and Upgrades... What s in it for You? How about

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

Quality Products AHU Repair, Refurbishment and Replacement

Quality Products AHU Repair, Refurbishment and Replacement Quality Products AHU Repair, Refurbishment and Replacement We are engineers specialising in the repair, refurbishment and replacement of ventilation systems. We have considerable experience in solving

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

FAMSUN SDZB3000 Zoned Belt Dryer. Quick Manual

FAMSUN SDZB3000 Zoned Belt Dryer. Quick Manual FAMSUN SDZB3000 Zoned Belt Dryer Quick Manual For operation and maintenance Has no legal effect Please refer to the product instruction for more information Catalog: 1.Maintenance of the air duct system

More information

TopMaster Air Handling unit. Installation instructions

TopMaster Air Handling unit. Installation instructions Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,

More information

Plastic plate heat exchanger

Plastic plate heat exchanger 2014US - 7.3.1 PWT-plastic Plastic plate heat exchanger Applications POLYBLOC is the right choice for highly corrosive pollutants. Plate heat exchangers in exhaust systems for brine baths, electroplating

More information

CADDY 5 UL OPERATOR S MANUAL

CADDY 5 UL OPERATOR S MANUAL CADDY 5 UL CADDY ENGLISH 10 UL OPERATOR S MANUAL CADDY 1 TECHNICAL CHARACTERISTICS Read electrical ratings written on the data plate under the individual units. The serial number of the unit is preceded

More information

If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally ventilated solution is a viable option.

If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally ventilated solution is a viable option. Air handling units Aesthetic Not to add significantly to the existing ambient noise levels. Functional requirements If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com UNPACKING

More information

Table of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5

Table of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5 Introduction The Scotsman Compact Refrigerator is a unique product, capable of being built into a cabinet because of its front vented, forced-air cooling system. It s also designed to be a companion to

More information

V-VTP Maintenance Manual

V-VTP Maintenance Manual V-VTP Maintenance Manual PO Box 501 Denver, NC 28037 ph: 704-483-9316 / fx: 704-483-4538 sales@leonardautomatics.com - http://leonardautomatics.com Maintenance Guide Proper maintenance of the tunnel finisher

More information

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 700 Thimble Shoals Boulevard Newport News VA 23606-2575 Telephone (757) 873-6800 Fax (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information

57" Fiberglass Exhaust Fan with Cone

57 Fiberglass Exhaust Fan with Cone OPERATORS MANUAL Fiberglass Exhaust Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate or service the product described. Failure

More information

Lo-Carbon Quadra Centrifugal Fan

Lo-Carbon Quadra Centrifugal Fan Lo-Carbon Quadra Centrifugal Fan Installation and Wiring Instructions Stock Ref. N Quadra TP Quadra TM Quadra HTP 439251A 439253A 439181A 220-240V~50Hz IPX4 PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH

More information

User s Manual MATRIX A MATRIX S MATRIX A. Filtro de aspiración Movil Matrix Tel.

User s Manual MATRIX A MATRIX S MATRIX A. Filtro de aspiración Movil Matrix Tel. Filtro de aspiración Movil Matrix 1000 User s Manual Filtering unit Tel. 976 359 352 MATRIX-1000-1-S MATRIX-1000-1-A MATRIX-1000-2-S MATRIX-1000-2-A email. albis@albis.net www.aspiraciondehumos.com KLIMAWENT

More information

User Manual HEAT RECOVERY VENTILATORS 1000 HE HE HE HE HE HE COMPACT 5585 COMPACT READ AND SAVE THESE INSTRUCTIONS.

User Manual HEAT RECOVERY VENTILATORS 1000 HE HE HE HE HE HE COMPACT 5585 COMPACT READ AND SAVE THESE INSTRUCTIONS. User Manual HEAT RECOVERY VENTILATORS MODELS: 1000 HE HE 1.3 2000 HE HE 1.8 3000 HE HE 2.6 3055 COMPACT 5585 COMPACT VB0021 READ AND SAVE THESE INSTRUCTIONS. VVI, 550 Lemire Blvd., Drummondville, QC, Canada

More information

Air Conditioner. Instruction Manual. For Models WA-1010E, WA-1010H, WA-1010M WA-1230E, WA-1230H P O R T A B L E

Air Conditioner. Instruction Manual. For Models WA-1010E, WA-1010H, WA-1010M WA-1230E, WA-1230H P O R T A B L E R Instruction Manual For Models WA-1010E, WA-1010H, WA-1010M WA-1230E, WA-1230H P O R T A B L E Air Conditioner It is important that you read these instructions before using your new purchase and we strongly

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

Fans Air handling units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Air Humidifiers For DV Air Handling Units

Fans Air handling units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Air Humidifiers For DV Air Handling Units Fans Air handling units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Air Humidifiers For DV Air Handling Units 2 Air Humidifiers Air Humidifier DVX For DV Air Handling

More information

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER RV Products Division INSTALLATION INSTRUCTIONS FOR 46413 SERIES PACKAGE AIR CONDITIONER 1. WARNINGS IMPORTANT NOTICE These instructions are for the use of qualified individuals specially trained and experienced

More information

OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QW*S Series

OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QW*S Series OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: 90-09 QWSERV with Occupied Air Capabilities For Use With Bard Through Ton QW*S Series Bard Manufacturing Company, Inc. Bryan, Ohio

More information

HANDLING INSTRUCTIONS for DISPENSA VVS-x

HANDLING INSTRUCTIONS for DISPENSA VVS-x 02/2012 Top runner (with stop point) Top damper Stop point Support frame Trays or baskets Pull-out components: Top runner Support frame Trays or baskets Front panel connector Bottom runner Top damper (optional)

More information

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components: Pumps DOE-HDBK-1018/1-93 CENTRIFUGAL PUMPS CENTRIFUGAL PUMPS Centrifugal pumps are the most common type of pumps found in DOE facilities. Centrifugal pumps enjoy widespread application partly due to their

More information

Technical instructions

Technical instructions Énergie Transfert Thermique Technical instructions A different climate Environmental control solutions Version IMPORTANT The warranty of ETT units depends on the respect of these technical instructions

More information

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN EQLK, DIRECT-DRIVEN INSTALLATION AND MAINTENANCE INSTRUCTIONS Contents Page Installation options...... 2 Checks to be made prior to commissioning...2 Electrical connections.....2 Measures before starting.....

More information

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW)

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW) Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW) The contents of this publication are based on the latest information available and the materials that are used at the time of printing.

More information

Proper maintenance of tunnel finisher will prolong its life and enable the equipment to produce the best possible quality.

Proper maintenance of tunnel finisher will prolong its life and enable the equipment to produce the best possible quality. Maintenance Guide Proper maintenance of tunnel finisher will prolong its life and enable the equipment to produce the best possible quality. Daily Maintenance CAUTION: Lock out main panel disconnect according

More information

Double Skin Air Handling Units

Double Skin Air Handling Units Double Skin Air Handling Units With Screwless Cabinets Engineered to Deliver High Indoor Air Quality Double Skin Air Handling Units from the Experts Blue Star has over six decades of experience in offering

More information

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features. Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause

More information

-DUCTED SYSTEM- OPERATING INSTRUCTIONS

-DUCTED SYSTEM- OPERATING INSTRUCTIONS HOMEDEAL AIR CONDITIONING (QLD) PTY LTD Heating & Cooling Specialists Sales, Service and Maintenance (07) 3397 8900 www.homedealairconditioning.com.au Contractors Licence No.897403 -DUCTED SYSTEM- OPERATING

More information

Instructions for operation and maintenance

Instructions for operation and maintenance KOJA oy KOJAmarine KOJAcool oy Air handling unit Future Instructions for operation and maintenance www.koja.fi 2 Index 1. General...4 2. Commissioning and maintenance...5 Damper section FPTP... 6 Mixing

More information

G-7s. Instruction Manual. G-Series Cooler COUNTERTOP COOLER. Part No.11IPA

G-7s. Instruction Manual. G-Series Cooler COUNTERTOP COOLER. Part No.11IPA G-Series Cooler COUNTERTOP COOLER Part No.11IPA-061000 Instruction Manual FOR YOUR FUTURE REFERENCE This easy-to-use manual will guide you in getting the best use of your cooler. Remember to record the

More information

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL KOMPACT OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the Kompact is a rugged, industrial unit, which utilizes

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

Agilent Dissolution Seminar Series

Agilent Dissolution Seminar Series Agilent Dissolution Seminar Series The Dissolution Apparatus Drive unit Paddle shaft Locking rings Touch screen Water bath Vessel plate Lift mechanism DISSOLUTION APPARATUS Support plate Water heater/circulator

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013 SECTION 15800 - AIR HANDLING EQUIPMENT 1.1 GENERAL A. All air handlers installed shall conform to the University of Rochester specification Guideline for Semi-Custom and Pre-Engineered Air Handling Units.

More information

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU) AIR HANDLERS Central Station (CS3) (Modular AL Frame AHU) Roof Mounted (RT) CONTENTS 1. CS3 Modular Aluminium Frame AHU : Unit Types 2. Casing Structure 3. Blowers and Drives 4. Coils 5. Options and Accessory

More information

Assessment Schedule - TS8

Assessment Schedule - TS8 The Assessor shall determine the business s commitment and support to good and safe working practices; also that it has a positive culture in all aspects of its work. In particular, the assessor shall

More information

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual 238 Series Industrial/Commercial Electric Unit Heater Owner s Manual This manual covers installation, operation and maintenance. Read carefully before attempting to install, operate or service the 238

More information

Pocket Hardmount. Preventative Maintenance.

Pocket Hardmount. Preventative Maintenance. Pocket Hardmount Preventative Maintenance www.comlaundry.com Part No. 7-04-49 November 2005 Table of Contents Daily...2 Beginning of the Day...2 End of the Day...4 Weekly...6 Monthly...7 Quarterly...11

More information

The ultimate in air handling units: directly and indirectly fired

The ultimate in air handling units: directly and indirectly fired AHU The ultimate in air handling units: directly and indirectly fired Mark has developed a range of air handling units with several options for a wide variety of applications. From a simple air intake

More information

SAVE VTR 250/B. User Manual. Document in original language A001

SAVE VTR 250/B. User Manual. Document in original language A001 SAVE VTR 250/B User Manual Document in original language 211474 A001 GB Copyright Systemair UAB All rights reserved E&OE Systemair UAB reserves the rights to change their products without notice. This

More information

Vallox INSTRUCTIONS FOR USE AND MAINTENANCE. Compact. Supply and extract air ventilation with heat recovery

Vallox INSTRUCTIONS FOR USE AND MAINTENANCE. Compact. Supply and extract air ventilation with heat recovery Vallox 1.09.349E 19.5.2009 VALLOX INSTRUCTIONS FOR USE AND MAINTENANCE 70 Compact CODE 3475 Supply and extract air ventilation with heat recovery For blocks of flats, terraced houses and detached houses.

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1. Table of contents 1. Table of contents... 2 2. EC Declaration of Conformity... 5 3. General information... 6 4. Safety precautions... 7 5. AmberAir range

More information

ANLAGENBAU HEAT EXCHANGER w w w. a nla g enba u-b oehm er. d e Version 05/2015

ANLAGENBAU HEAT EXCHANGER w w w. a nla g enba u-b oehm er. d e Version 05/2015 ANLAGENBAU HEAT EXCHANGER Table of Contents 1.0 General Information 1.2 User Instructions 1.3 Proper Use 1.4 General Safety Rules 2.0 Design and Function 3.0 Installation 3.1 Setting up the Plate Heat

More information

EQUIPMENT CARE AND CLEANING

EQUIPMENT CARE AND CLEANING EQUIPMENT CARE AND CLEANING 205 206 NOTES EQUIPMENT CARE AND CLEANING Preventative Maintenance Please read these instructions. Failure to follow maintenance guidelines may cause a non-warranted cabinet

More information

INSTALLATION AND OPERATION MANUAL FOR HUUM DROP ELECTRIC SAUNA HEATER

INSTALLATION AND OPERATION MANUAL FOR HUUM DROP ELECTRIC SAUNA HEATER INSTALLATION AND OPERATION MANUAL FOR HUUM DROP ELECTRIC SAUNA HEATER 2 Table of Contents 1. THINGS TO CHECK BEFORE INSTALLATION... 2 2. INSTALLATION... 2 3. CONTROLLING THE HEATER... 5 4. GUARD RAILS...

More information