HVAC Myths and Realities Trane Engineers Newsletter Live Series
|
|
- Daniel Summers
- 5 years ago
- Views:
Transcription
1 HVAC Myths and Realities Trane Engineers Newsletter Live Series
2 AGENDA Low delta T is unavoidable 55 F supply air temperature is adequate for today s loads ASHRAE Standard 15 has to be updated before new refrigerants can be used Single-zone VAV units do not need hot gas reheat VFDs and affinity laws Small changes in pressure can have a huge impact on airflow for flat fan curves and may cause the system to surge New chilled-water systems need to be variable-primary flow System airflow issues are the fans fault Claims to energy savings
3 Myth Number 1 Low delta T is unavoidable.
4 Transport Energy is low delta T unavoidable? Tons= ( T GPM)/24 Solving for gpm GPM= (Tons 24) / T Pumping power Frictional Head Flow 2 Water HP (bhp)= (GPM head (ft))/3960 Water HP Flow 3 Delta T 3
5 Coil Delta T is low delta T unavoidable? AHRI Certified Coil Air Flow (VAV) unloading v ASHRAE Chilled-Water Coil Selection Chilled-water cooling coils shall be selected to provide a 15 F or higher temperature difference between leaving and entering water temperatures and a minimum of 57 F leaving water temperature at design conditions Engineer s Newsletter Live Coil Selection and Optimization
6 Reason 1: 3-Way Control Valves undesirable mixing in variable flow systems 50% Coil Load 1. 3-way control valves Eliminate them! Coil LVG 59 F Coil Delta T = 17 F System Delta T = 8.5 F CHWR 50.5 F Bypass 42 F CHWS 42 F CHWR = [(42 x 50) + (59 x 50)] / 100 = 50.5
7 Reason 2: Supply Air Setpoint Depression overdriving coil capacity 1. 3-way control valves 2. Control setpoint depression Avoid, limit and return 55 LAT = 16 DT 52 LAT = 11 DT 50 LAT = 8.5 DT CHW Delta T leaving air setpoint
8 Reason 3: Warmer Chilled Water Supply reduced heat transfer driving force LMTD 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water Chilled water reset only at part load CHW Delta T CHWS = 16 DT 47 CHWS = 7.5 DT 50 CHWS = 5 DT entering CHW temperature
9 Reason 4: Deficient Control Valves poor flow control at full and part loads 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water 4. Deficient control valves Control Valve Issues 1. Improperly Selected / Oversized 2. Worn-out 3. Unstable control 4. $29.95 (cheap) 5. 3-way valves
10 Reason 4: Deficient Control Valves poor flow control 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water 4. Deficient control valves Specify quality valves specific to use 8 th floor control point 20 ft pd 2 nd floor pressure 90 ft pd
11 Reason 4: Deficient Control Valves poor flow control 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water 4. Deficient control valves Pressure independent valves? (PIV) 1. Mechanical 2. Electronic Pressure independent valves Not required May be beneficial
12 Reason 5: Tertiary Pumping undesirable mixing is hard to prevent 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water 4. Deficient control valves 5. Tertiary pumping / bridge tender circuits Don t mix to the return simply pressure boost CHWS Bypass Valve DP CHWR
13 Design Delta T and Greater is Achievable 1. AHRI certified coil selections 2. AHU set point limits 3. Chilled water reset only at part load 4. Properly selected / high quality valves 5. Pressure boosting no tertiary mixing
14 Myth Number 1 Low Delta T is unavoidable.
15 Myth Number 2 55 F supply air temperature is adequate for today s loads.
16 full load OA 96 F DB, 76 F WB RA 74 F DB, 52% RH MA 80 F DB SA F DB (1,500 cfm) SA RA 80 MA full load OA humidity ratio, grains/lb of dry air dry-bulb temperature, F 110
17 full load OA 96 F DB, 76 F WB RA 74 F DB, 57% RH MA 86 F DB SA F DB (800 cfm) SA RA' RA 80 MA full load OA humidity ratio, grains/lb of dry air dry-bulb temperature, F 110
18 full load OA 96 F DB, 76 F WB RA 74 F DB, 52% RH MA 89 F DB SA F DB (630 cfm) SA' SA RA 80 MA full load OA humidity ratio, grains/lb of dry air dry-bulb temperature, F 110
19 Improving Dehumidification Cool and reheat Face-and-bypass dampers Reduce airflow Dual paths Desiccants
20 full load OA 96 F DB, 76 F WB RA 74 F DB, 52% RH MA 86 F DB SA (55) F DB (800 cfm) SA CA SA' 70 RA 80 MA full load OA humidity ratio, grains/lb of dry air dry-bulb temperature, F 110
21 Type III Series Desiccant (CDQ) C 50 F DB 97% RH 52 gr/lb CA 55 F DB 64% RH 42 gr/lb (43 F DP) SA 8-12 rph MA' MA 75 F DB 67% RH 87 gr/lb (64 F DP) 80 F DB 50% RH 77 gr/lb (60 F DP) (10,000 cfm)
22 full load OA 96 F DB, 76 F WB RA 74 F DB, 52% RH MA 81 F DB SA F DB (1,350 cfm) SA CA SA' 80 MA' MA RA full load OA humidity ratio, grains/lb of dry air dry-bulb temperature, F 110
23 Myth Number 2 55 F supply air temperature is adequate for today s loads.
24 Myth Number 3 Single-zone VAV units do not need hot gas reheat.
25 Classroom Example basic CV system peak DB outdoor condition sensible load latent load space SHR supply airflow outdoor airflow space temp supply air temp 96 F DB, 76 F WB 29,750 Btu/h 5,250 Btu/h ,500 cfm 450 cfm 74 F 55.7 F 1,500 cfm = Jacksonville, Florida 29,750 Btu/h (74 F T supply )
26 Example: K-12 Classroom OA RA MA SA CV full load 96 F DBT 68 F DPT (450 cfm) 74 F DBT 52% RH 81 F DBT 55 F DBT (1500 cfm) (4.8 tons) CV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 67% RH 77 F DBT 63 F DBT (1500 cfm) SA 60 SA 70 RA 80 RA MA MA peak DPT OA Jacksonville, FL 180 peak DBT OA humidity ratio, grains/lb of dry air dry-bulb temperature, F 110
27 Example: K-12 Classroom OA RA MA SA CV full load 96 F DBT 68 F DPT (450 cfm) 74 F DBT 52% RH 81 F DBT 55 F DBT (1500 cfm) (4.8 tons) CV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 67% RH 77 F DBT 63 F DBT (1500 cfm) (3.7 tons) SA 60 SA MA RA RA MA peak DPT OA Jacksonville, FL 180 peak DBT OA humidity ratio, grains/lb of dry air dry-bulb temperature, F 110
28 Example: K-12 Classroom peak DPT day zone humidity, %RH 67% cooling load, tons 3.7 fan airflow, cfm 1500 mild/rainy day constant-speed fan zone humidity, %RH 73% cooling load, tons 1.6 fan airflow, cfm 1500
29 Hot Gas Reheat packaged DX units MA evaporator CA reheat coil condenser reheat valve
30 Example: K-12 Classroom constant-speed fan constant-speed fan with hot gas reheat peak DPT day zone humidity, %RH 67% cooling load, tons 3.7 fan airflow, cfm 1500 mild/rainy day zone humidity, %RH 73% cooling load, tons 1.6 fan airflow, cfm 1500 compressor energy 60% % Space humidity is maintained
31 Improved Part-Load Dehumidification EA RA 1050 cfm zone 74 F OA 450 cfm 96 F DBT 68 F DPT 1500 cfm 55 F SA
32 Example: K-12 Classroom OA RA MA SA CV full load 96 F DBT 68 F DPT (450 cfm) 74 F DBT 52% RH 81 F DBT 55 F DBT (1500 cfm) (4.8 tons) CV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 67% RH 77 F DBT 63 F DBT (1500 cfm) (3.7 tons) SZVAV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 57% RH 79 F DBT 55 F DBT (900 cfm) (4.0 tons) 50 SA 60 SA MA RA RA MA peak DPT OA Jacksonville, FL humidity ratio, grains/lb of dry air dry-bulb temperature, F 110
33 Example: K-12 Classroom peak DPT day constant-speed fan zone humidity, %RH 67% cooling load, tons 3.7 fan airflow, cfm 1500 constant-speed fan with hot gas reheat variable-speed fan 57% mild/rainy day zone humidity, %RH 73% cooling load, tons 1.6 fan airflow, cfm % % %
34 SZVAV Dehumidification Performance VAV may be enough Consider hot gas reheat for: Even lower space humidity levels Widely varying loads Oversized units
35 Example: K-12 Classroom OA RA MA SA SZVAV full load 96 F DBT 68 F DPT (450 cfm) 74 F DBT 52% RH 81 F DBT 55 F DBT (1500 cfm) SZVAV Oversized 96 F DBT 68 F DPT (450 cfm) 74 F DBT 56% RH 80 F DBT 58 F DBT (1750 cfm) SZVAV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 59% RH 78 F DBT 58 F DBT (1050 cfm) 50 SA SA 60 SA 70 RA 80 MA RA RA MA MA peak DPT OA Jacksonville, FL 180 peak DBT OA humidity ratio, grains/lb of dry air dry-bulb temperature, F 110
36 Avoid Oversizing! Oversizing supply airflow leads to: Warmer supply-air temperature Less dehumidification (in non-arid climates) Elevated indoor humidity Examples include: Auditoriums Gymnasiums Church sanctuaries Etc.
37 Humidity Control with SZVAV Avoid oversizing equipment Verify proper fan speed and discharge air temperature setpoints Equip the unit with hot gas reheat, if necessary
38 Myth Number 4 Single-zone VAV units do not need hot gas reheat
39 Myth Number 4 Slap on a VFD and you are entitled to get full advantage of the affinity laws. = Speed 3 Savings
40 The Affinity Laws dynamic compression fans/impellers Background: 1. Fans, pump impellers and other dynamic compression devices. 2. Application limited to systems with only frictional flow losses. 3. Ignoring changes in device efficiency at different conditions. If and only if the above are true then: 1. Pressure varies proportionally to the square of the impeller speed. 2. Flow produced varies proportionally to the impeller speed. 3. Power (BHP) required varies in a cubic proportion to the impeller speed.
41 The Affinity Laws Graphically dynamic compression fans/impellers Device performance in frictional pressure loss systems Pressure is proportional to the speed squared Flow is proportional to the speed Power is proportional to the speed cubed flow/pressure/power (%) pressure flow power speed (%)
42 Systems and the Affinity Laws compliant systems Systems that comply Cooling towers Single zone VAV air systems.
43 Cooling Tower Fans affinity laws 100% flow 100% pressure 100% power Cooling Tower OFF 15 kw Cooling Tower 60 HZ speed/pressure/power (%) speed pressure power 85 F 100 F P flow (%)
44 Cooling Tower Fans affinity laws For Free Discharge Fans W2 = W1 x (S2 / S1) 3 W2 = 15 kw x (30 / 60) 3 W2 = 1.88 kw Cooling Tower OFF 1.88 kw Cooling Tower 60 HZ speed/pressure/power (%) speed pressure power 85 F 92.5 F P flow (%)
45 Systems and the Affinity Laws non-compliant systems Systems that don t comply: Chilled water Hot water MultiZone VAV Condenser water HVAC cooling units HVAC heating units (HP) Non-compliant characteristics: Control valves and setpoints Fixed lift Refrigeration lift / heat exchangers / minimum flows
46 VPF Chilled Water Systems systems and the affinity laws Non-compliance factors Pump minimum speed limits speed/pressure/power (%) speed pressure power flow (%)
47 Pump Minimum Speed Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits 33% minimum speed speed/pressure/power (%) pump min speed pressure power flow (%)
48 Differential Pressure Control Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits A fixed pressure control setpoint 20 ft. setpoint 80 ft. frictional loss speed/pressure/power (%) DP pressure setpoint speed power flow (%)
49 Heat Exchanger Minimum Flow Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits A fixed pressure control setpoint Heat exchanger minimum flow limits 50% minimum flow speed/pressure/power (%) HX min flow pressure power flow (%)
50 Combined Limit Power Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits A fixed pressure control setpoint Heat exchanger minimum flow limits speed/pressure/power (%) Pump min speed HX min flow DP setpoint flow (%) affinity power
51 High HX Minimum Flow Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits A fixed pressure control setpoint Heat exchanger minimum flow limit 70% speed/pressure/power (%) HX min flow pressure power flow (%)
52 Myth Number 4 Slap on a VFD and you are entitled to get full advantage of the affinity laws. Systems that comply Cooling towers Single zone VAV HVAC systems. Systems that don t comply Chilled water Hot water Condenser water Multi-zone VAV HVAC cooling units HVAC heating units (HP)
53 Myth Number 5 Small changes in pressure can have a huge impact on airflow for flat fan curves and may cause a fan system to surge.
54 Small Changes in Pressure Static pressure inches w.g Forward Curved (FC) Fan Do not select region 1100 RPM 900 RPM 700 RPM 500 RPM 50% WOCFM 60% 70% 80% 90% peak pressure Far from peak some may select here CFM in 1000s
55 Fan Performance Test 7 blocked off 14 total static pressure (in H 2 O) restricted less restricted wide open Brake horsepower (bhp) airflow (cfm) 0
56 Pressure = f(airflow) 6 Forward Curved (FC) Fan 50% WOCFM 60% static pressure inches w.g RPM 900 RPM 700 RPM 70% 80% 90% RPM CFM in 1000s
57 Two Different Systems 6 Forward Curved (FC) Fan 50% WOCFM 60% static pressure inches w.g RPM 900 RPM 700 RPM actual system Design system 70% 80% 90% RPM CFM in 1000s
58 System Fan static pressure inches w.g. Is dependent on the Fan Is dependent on the System CFM
59 System Change: Steep Fan Curve 25-inch steep fan curve 8 45 % WO 50 % WO 7 60 % WO total static pressure (in H 2 O) RPM 1300 RPM 0.5 change RPM 700 RPM 14,500 cfm (vs. 15,000 cfm) 3.3% loss 70 % WO 80 % WO 90 % WO RPM 150 RPM 200 RPM 300 RPM 500 RPM 1750 RPM 1000 RPM 1500 RPM 2000 RPM airflow (cfm)
60 System Change: Flat Fan Curve 25-inch flat fan curve RPM 25 % WO % WO total static pressure (in H 2 O) change RPM 600 RPM 500 RPM 400 RPM 14,500 cfm (vs. 15,000 cfm) 6.7% loss 60 % WO 70 % WO 80 % WO 90 % WO RPM 500 bhp 750 bhp 1000 bhp 1500 bhp 2000 bhp airflow (cfm)
61 Myth Number 6 Small changes in pressure can have a huge impact on airflow for flat fan curves and may cause a fan system to surge.
62 Myth Number 6 A chilled water system needs to be variable primary flow to be efficient.
63 Variable Primary Flow (VPF) Savings First cost: 4-8% Annual energy: 3-8% Life-cycle cost: 3-5% Compared VPF and Primary-Secondary
64 Low Pump Power Install pump VSD Use VSD to set design flow rate Open balancing valve Employ chilled water reset If system is constant flow reduce design flow rate further
65 Design Flow ~ Minimum Flow Chilled water Ts ASHRAE GreenGuide (16-18 F T) Section Coil shall be selected to provide 15 F or higher temperature difference between leaving and entering temperatures. Chillers with limited evaporator choices
66 Design Flow ~ Minimum Flow Flow turndown = Design flow / Minimum flow Single chiller Turndown > 1.3 Two chillers Turndown > 1.5 Consider piping the chillers in series
67 Conversion from Primary-Secondary Convert to VPF If entire plant is being re-piped anyway Additional capacity is needed Install chiller where primary pumps used to be Change to Variable-Primary/ Variable-Secondary Cooling capacity is adequate Piping changes are minimal
68 Convert to Variable Primary/Variable Secondary VFDs DP ΔT = 1 or 2 ºF DP Placeholder for Manifolded P-S System picture (Beth to supply)
69 Plant Operator Doesn t understand the plant Wants to manually control VPF
70 Myth Number 7 A chilled water system needs to be variable primary flow to be efficient.
71 Myth Number 7 Fans often don t deliver the airflow they are supposed to and it s the fan s fault.
72 ANSI/ASHRAE 51 (AMCA ) Figure 12: Outlet Chamber Setup-Multiple Nozzles in Chamber Test chamber
73 System Effect: Developing a Uniform Velocity Profile fan Not enough space to fully develop uniform velocity profile
74 Free and Abrupt Discharge Hidden loss as high as 1.0 inches w.g. OA
75 AMCA Publication 201, Fans and Systems Prediction of common System Effect Factors
76 Common System Effects Open discharge, elbow, branch, turning vanes, or damper located too close to the fan outlet Elbow, turning vanes, air straightener, or other obstruction located too close to the fan inlet Pre-swirling the air prior to it entering the fan wheel Use of an inlet plenum or cabinet
77 Flex Duct Problems Good Bad flex duct
78 Low Airflow Troubleshooting Common problems: Unexpectedly high system pressures Leaks Fan installed or running backwards Close-coupled fittings From A Practical Guide to Noise and Vibration Control for HVAC Systems (M. Schaffer, 1991)
79 Fan Rotation Forward-curved Backward-tended Backward-inclined Backward-curved Airfoil
80 Low Airflow Troubleshooting Over-amping problems: Bad component (motor or bearings) Installation: Wheel-cone overlap Belt tension, belt/shaft alignment Wheel-cone overlap
81 Low Airflow Troubleshooting Uncommon problems: Wrong fan installed Cutoff issues (housed fans only) Software/catalog error Quantum mechanics & string theory Fan cutoff (split in this case)
82 Field Measurements Evaluating the right parameters: Airflow Pressure Speed Power Things to watch out for: VFD settings Damper position (systems with a return or exhaust fan) Parameter measurement error
83 Parameter Measurement Error Your duct system?
84 Parameter Measurement Error AMCA 203 Field Performance Measurement of Fan Systems
85 AMCA Fan Application Manual Publication 201 Fans and Systems Lists possible causes for low flow, including: Improper inlet duct design Improper outlet duct design Improper fan installation Unexpected system resistance characteristics Improper allowance for fan system effect Dirty filters, ducts, coils Performance determined using uncertain field measurement techniques Includes much help for system effect corrections
86 AMCA Fan Application Manual Publication 202 Troubleshooting Lists possible causes for low airflow, including: Improper fan installation or assembly Damage in handling or transit System design error Deterioration of system Faulty controls Poor fan selection Includes detailed troubleshooting checklists
87 Myth Number 8 Fans often don t deliver the airflow they are supposed to and it s the fan s fault.
88 Myth Number 8 You can save (20, 30, 40, 50 80) percent.just by doing this
89 Savings Claims 40 is the new 30!
90 50 is the New 40 improved system efficiency of up to 54%
91 And now from an online brochure
92 Percent Savings: Questions to Ask Compared to what? What is the baseline? What else changed? (particularly for retrofits).
93 Percent Savings: Questions to Ask Compared to what? What is the baseline? What else changed? (particularly for retrofits). Is the comparison valid for Your building? Your application and load profile? Your climate?
94 78.5 Percent Claim Indirect evaporative cooling Compared to compressor cooling Dry climate Water is available Does the solution meet my customers needs?
95 Myth Number 8 You can save (20, 30, 40, 50 80) percent.just by doing this Make sure the baseline and comparison are valid for the specific project Perform an analysis on energy savings, energy cost savings, and ROI Help the client determine if the solution is in both their short-term and long-term interests
96 Myth Number 9 Anti-freeze doesn t have much affect on chilled water systems.
97 Example Fluid Properties and Impacts Fluid Property Compared to Water Impact Result Viscosity Increases Pressure drop increases Pump power increases Film heat transfer coefficient Drops Heat transfer worsens More flow required Specific heat Drops More flow required Pressure drop and pump power increase Specific gravity Rises Less flow required Pressure drop and pump power increase
98 Fluid Properties at 60 F Property Water 25% EG 25% PG Viscosity (lb/hr-ft) Thermal conductivity (Btu/ hr-ft- F) Specific heat (Btu/lb- F) Specific gravity
99 ASHRAE, (2016) ASHRAE Handbook HVAC Systems and Equipment.
100 Antifreeze Affect on the Coil heat transfer capability can change by 40% or more when antifreeze solutions are used consult the manufacturer s rating data in glycol systems.
101 Antifreeze Affect on the Chiller 17% Reduction ASHRAE, (2016) ASHRAE Handbook HVAC Systems and Equipment.
102 Required Flow Tons= 500 gpm T cp /12,000 ( ῤ/ ῤw ɤ ) Tons(water)= gpm T /24 Tons(25% EG)= gpm T /25.5 Tons(25% PG)= gpm T /25
103 Antifreeze Affect Water: 25% EG: 25% PG: gpm = 24 x tons x ΔT gpm = 25.5 x tons x ΔT gpm = 25 x tons x ΔT More flow is required
104 Affect of Antifreeze on Flow ΔP (Flow2 / Flow1) 2 Δ Pump Power (Flow2 / Flow1) 3 Antifreeze Flow increase (%) Pressure drop increase (%) Pump power increase (%) 25% EG % PG
105 Affect of Antifreeze Viscosity Pressure drop increase 25% EG: 9% 25% PG: 17% ASHRAE, (2016) ASHRAE Handbook HVAC Systems and Equipment.
106 Reality: Affects of Antifreeze Capacity Coil Chiller Pump Flow Pressure Power It s all bad except the system doesn t freeze
107 Guidance use the smallest possible concentration to produce the desired antifreeze properties. ASHRAE, (2016) ASHRAE Handbook HVAC Systems and Equipment.
108 Freeze and Burst Protection Burst protection Keep pipes from bursting Crystal formation is ok Use when equipment is not going to run in winter Freeze protection Solution must remain 100% liquid Necessary when equipment operates in freezing conditions
109 Freeze and Burst Protection Ethylene Glycol % Propylene Glycol % Temperature ( F) Freeze Burst Freeze Burst
110 Myth Number 10 Anti-freeze doesn t have much affect on chilled water systems.
Trane Engineers Newsletter Live
Trane Engineers Newsletter Live HVAC Myths and Realities Presenters: Systems and Applications Engineers Lee Cline, Dustin Meredith and Mick Schwedler with Jeanne Harshaw (host) Trane program number: APP-CMC062-EN
More informationFan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10
Fan Laws Keith Miller Samuel Tepp Associates Paul Cenci, P. E.-Principal Brian England-Principal Basic Terms CFM - Cubic Feet per Minute, volume (amount) of air being moved SP - Static Pressure, resistance
More informationEarthWise System Seminar
EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States
More informationIntroduction to Fans. The Basics of Fan Principles and Terminology
Introduction to Fans The Basics of Fan Principles and Terminology Airflow Principles A fan is a rotating device that creates pressure differential that results in air movement Pressure rise in a fan Downstream
More informationFan Selection. and Energy Savings
Fan Selection and Energy Savings Reducing power consumption by minimizing system pressure loss and choosing the right equipment HBy BRIAN MLEZIVA Greenheck Fan Corp. Schofield, Wis. Power Consumption HVAC
More informationSystem Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.
System Components with ` Emphasis on Packaged Rooftop Application and Installation Jerry Cohen President Jacco & Assoc. Agenda Define and relate in practical terms the following components: System Effect
More informationAC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT
AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT Central Chiller Plant (with Cooling Tower and Chilled Water distribution) The other AC configuration is called a Chilled Water or Larger Cooler system. It
More informationDesigning Energy Efficient Outdoor Air Systems
Designing Energy Efficient Outdoor Air Systems Joseph Thorndal Applied Products Sales Manager Greenheck, Schofield, Wisconsin 1 Joseph Thorndal BS Industrial Engineering North Dakota State University Work
More informationAgenda and Objectives
Agenda and Objectives Trane Engineers Newsletter Live Series Variable-Speed Drives (VSDs) and Their Effect On HVAC System Components Variable-speed drives (VSDs) can save energy, but the savings may not
More informationTechnical Development Program
Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7
More informationINTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings
INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,
More informationChiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off
Application Guide AG 31-003-1 Chiller Plant Design 51.5F Return Water To Chiller Two 400 Ton Chillers Each At 300 Tons (Balanced Load) 51.5F 480 gpm Flow Through Decoupler 44F 54F Building Load 600 Tons
More informationIntroduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN
Introduction to HVAC Agenda Psychrometrics Human Comfort Heat Transfer Refrigeration Cycle HVAC Terminology HVAC Systems Introduction to HVAC Psychrometrics 2000 TRG-TRC002-EN Properties of Air Dry-bulb
More informationAdding More Fan Power Can Be a Good Thing
This article was published in ASHE Journal, May 14. Copyright 14 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of
More informationSummary Comparison of Simulation Program Features
Summary Comparison of Simulation Program Features FEATURE DOE2.2 equest TRACE 700 HAP Public/Proprietary Public Domain Proprietary Proprietary Proprietary Simulation Method 8760 hours 8760 hours 8760 hours
More informationAPPLICATION GUIDE BEAMS
BEAMS There is an increasing need for energy efficient air conditioning systems as energy codes become more stringent. Chilled beam systems are one such alternate to traditional all air conditioning systems.
More informationUNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationEnergy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE
This article was published in ASHRAE Journal, March 20145 Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationMethod to test HVAC equipment at part load conditions
IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking
More informationAgenda and Objectives
Agenda and Objectives Trane Engineers Newsletter Live Series Air-Handling Systems, Energy, and IAQ Air-handling systems are key elements for building comfort and air quality, but they use energy. How much
More informationPharmaceutical Facility Design
PhEn-602 Pharmaceutical Facility Design J. Manfredi Notes 9A PhEn-602 J. Manfredi 1 Primary & Secondary HVAC units Primary Primary air handling unit arrangement: One unit is responsible for all of the
More informationASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee
ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique CTTC
More informationTechnical Development Program
Technical Development Program PRESENTED BY: James Parker Insert your logo here AIR HANDLERS Coils: Direct Expansion Chilled Water and Heating Menu Section 1 Introduction Section 2 Typical Coil Applications
More informationHVAC Mandatory Provisions Part II, Page 1
HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency
More informationRT-OA TM Rooftop Outdoor-Air (DOAS)
RT-OA TM Rooftop Outdoor-Air (DOAS) A/C s & HEAT PUMPS (DX - Air Source Data) Dedicated Outside-Air System (DOAS) Solutions Office Buildings, Schools, Hospitals, Restaurants, Gyms & Fitness Centers, Hotels,
More informationTrane CDQ Desiccant Dehumidification
Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features
More informationAppendices. Included in this section are
Appendices Included in this section are Appendix A Building Overview Appendix B Alternative Mechanical Designs Appendix C Integration of Structural System and Constructability 68 Appendix A Building Overview
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationTo Keep Docs Cool, Dry and Happy
To Keep Docs Cool, Dry and Happy David N. Schurk DES., CEM., LEED-AP., CDSM., SFP., CWEP. Director of Healthcare Accounts for Heat Transfer Solutions in Houston, TX. Learning Objectives 1. Understand the
More informationHVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS
HVAC Systems What the Rater Needs to Know in the Field This presentation used CASE* studies from the following *CASE Copy And Steal Everything HVAC Systems - What the Rater Needs to Know in the Field This
More informationAHRI 920 & ASHRAE 90.1
AHRI 920 & ASHRAE 90.1 Optimizing Solutions through Superior Dehumidification Technology SM 1 About the Presenter Paul Stewart Education: BSGE University of Illinois Work History: Johnson Controls Inc.
More informationRedesign of Bennett Hall HVAC System
MEE 488 April 18, 2006 Redesign of Bennett Hall HVAC System Greg Andreasen Michael Chicoine Florent Hohxa Jason Jacobe Mechanical Engineering, University of Maine, Orono ME 04473, USA ABSTRACT Our task
More informationPresented By: John Dolan, P.E.
Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience jdolan@thermohvac.com
More informationH3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog
H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...
More informationRT-OA TM Rooftop Outdoor-Air (DOAS)
RT-OA TM Rooftop Outdoor-Air (DOAS) A/C s & HEAT PUMPS Dedicated Outside-Air System (DOAS) Solutions Office Buildings, Schools, Hospitals, Restaurants, Gyms & Fitness Centers, Hotels, Retail Stores...!
More information2009 IECC Commercial Mechanical Requirements
BUILDING ENERGY CODES UNIVERSITY 2009 IECC Commercial Mechanical Requirements Ken Baker PNNL-SA-66171 Learning(Objec-ves(( ( 1. Find(minimum(equipment(efficiency(requirements( and(recite(at(least(3(common(terms(for(measuring(
More informationEnergy Recovery with Cooling and Heating Model ERCH
Energy Recovery with Cooling and Heating Model ERCH 100% Outdoor Air System Dedicated Outdoor Air System 1,000-10,000 cfm 1.75 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating,
More informationFans: Features and Analysis
Technical Development Program COMMERCIAL HVAC EQUIPMENT Fans: Features and Analysis PRESENTED BY: Michael Ho Version 1.2 Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Section
More informationLGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
Service Literature The LGH/LCH high and standard efficiency 5, 0, 5 and 50 ton (, 0.7, 58. and 75.9 kw) units, are configure to order units (CTO) with a wide selection of factory installed options. The
More informationEnergy Recovery with Cooling and Heating
Energy Recovery with Cooling and Heating VersiVent - Model VER Commercial Institutional 2,000-10,000 cfm 3.0 in. wg external static pressure Configurable September 2008 Page The VersiVent Header Model
More informationBest Practices for Applied Rooftop ` Systems, Applications and. Jerry Cohen President Jacco & Assoc. Installation
Best Practices for Applied Rooftop ` Systems, Applications and Jerry Cohen President Jacco & Assoc. Installation Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Focused on the Engineered Environment
More informationTrane Engineers Newsletter Live
Trane Engineers Newsletter Live Presenters: John Murphy, Dustin Meredith and Jeanne Harshaw (host) Trane program number: APP-CMC059-EN Agenda Trane Engineers Newsletter Live Series Abstract The Air Movement
More informationAir System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae
APPENDIX C Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 12:56PM Air System Information Air System Name Equipment Class Air System Type Lobby System CW AHU SZCAV Number
More informationDehumidifying with Dedicated Outdoor Air
Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,
More informationUNIVERSITY OF MISSOURI Central Station Air-Handling Units March
GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,
More informationState of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney
Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled
More informationMechanical Systems Design
Mechanical Systems Design After much deliberation and a long process of brainstorming ideas for potential mechanical system designs for the, it was finally decided to design a central chilled water plant
More informationCTI Sponsored Educational Program
Presented By: Kent Martens SPX Cooling Technologies, Inc. Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for
More informationCARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.
Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using
More informationSession: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island
Session: HVAC 101 HVAC 101 Steve Sain Sain Engineering Associates, Inc. August 9, 2016 Rhode Island Convention Center Providence, Rhode Island Why? 2 Acknowledgements 3 Disclaimer I m gonna shoot down
More informationASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering
ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.
More informationPINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION
ENERGY EFFICIENT DEHUMIDIFICATION PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM Provides a very high degree of latent cooling using only a minimal amount of conventional cooling input Substantial energy
More informationPartial Load Performance Of Refrigeration System
Chapter 11 Partial Load Performance Of Refrigeration System Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Hot Gas Bypass & Liquid Injection: When the compressor is under surge condition,
More informationBRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application
1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights
More informationBest Practices for Condensing Boilers
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cleaverbrooks.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For
More informationAHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency
Application Note 24 AHRI 920 Performance Rating and Comparisons I NTRODUCTION In 2015, the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) introduced a performance rating for dedicated outside
More informationD-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency
Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)
More informationDucted Propeller. Airflow Volume
Total Pressure Radial-Blade Centrifugal Tubeaxial Backward-inclined Airfoil Centrifugal Forward-curved Centrifugal Ducted Propeller Airflow Volume Figure 2: Forward-Curved Centrifugal Fan
More informationAndrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3
Existing System Evaluation Executive Summary The MBNA Career Services Center is a 44,000 square foot, 4-story office type building at Penn State University, University Park Campus. The building is located
More informationDesign Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationDescription of All Alternatives Considered-
Description of All Alternatives Considered- Energy efficiency is an area where the Tubman design can be improved. The design heating load is 1807.8 MBH and the design cooling load is 1702.2 MBH or 142
More informationAir Conditioning Clinic
Air Conditioning Clinic Psychrometry One of the Fundamental Series D C B A C B D A July 2012 TRG-TRC001-EN Psychrometry One of the Fundamental Series A publication of Trane Preface Psychrometry A Trane
More informationCHAPTER 4. HVAC DELIVERY SYSTEMS
CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer
More informationThe Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and
More informationCivil Engineering Building
Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationFAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney
FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1
More informationterminal units only provide sensible cooling, a separate dehumidification system is usually needed.
providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 23 0594 - TESTING, ADJUSTING, AND BALANCING (TAB) PART 1 - GENERAL 1.1 SUMMARY A. This Section includes testing, adjusting and balancing HVAC systems to provide design conditions as indicated by
More informationMath. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.
HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +
More informationTechnical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler
Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System
More informationBuilding Systems: HVAC
Building Systems: HVAC Committee on Microbiomes of the Built Environment June 21, 2016 Washington DC Dennis Stanke (dstanke47@gmail.com) Retired rane (IR) Outline Ventilation Systems Moisture sources Low
More informationAir System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.
Air System Sizing Summary for AHU/CU-1 AHU/CU-1 Floor Area 1678.0 ft² Central Cooling Coil Total coil load 4.8 Tons Total coil load 57.8 MBH Sensible coil load 41.8 MBH Coil CFM at Jul 1500 1909 CFM Max
More informationBest Practices for Applied Rooftop ` Systems - Application and. Jerry Cohen President Jacco & Assoc. Installation
Best Practices for Applied Rooftop ` Systems - Application and Jerry Cohen President Jacco & Assoc. Installation Who is Jacco Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Systems Knowledgeable
More informationSelecting the Correct Fan
Selecting the Correct Fan Ryan B. Johnson Air Purification Company Sales Engineer Member, ASHRAE Pikes Peak Chapter rjohnson@airpurificationcompany.com 1 Your Speaker circa 1998 Fan Types Applications
More informationASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes
ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes In Humid Climates BY DAVID A. JOHN, P.E., MEMBER ASHRAE; DREW ELSBERRY, MEMBER ASHRAE Designing g a building s HVAC system requires designers
More informationSYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC
VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things
More informationUpdate Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South
3/5/2018 1 Update Dedicated Heat Recovery Chiller Technology Don Frye Gulf South Good design is an intentional act Begin with the end in mind Basic Bldg Tenants IAQ (low VOC & CO 2 ) Controlled Temp &
More informationService Step by Step Trouble-Shooting Check-List
WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:
More informationA/C Cooling Load calculation and measurement
Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying
More informationCity of Duluth Festival Center 04/25
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationPerformance Rating of Computer and Data Processing Room Air Conditioners
ANSI/AHRI Standard 1360 (I-P) with Addendum 1 2013 Standard for Performance Rating of Computer and Data Processing Room Air Conditioners Approved by ANSI on November 8, 2013 WITH ADDENDUM 1, PERFORMANCE
More informationMechanical Engineering Laboratory
Mechanical Engineering Laboratory MEE 416 Professor H. Ezzat Khalifa Syracuse University http://lcs.syr.edu/faculty/khalifa/mee416/ MEE416 1 A. Experiment 1 Air-Conditioning: Air-side Experiment 0031 Link
More informationHAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001
This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.
More informationStandards and Guidelines. Presented by: Aric Murray December 12, 2014
TDSHS Ventilation Standards and Guidelines Presented by: Aric Murray December 12, 2014 Agenda 1. What are the TDSHS ventilation 1. What are the TDSHS ventilation requirements? 2. Pressure relationships.
More informationENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory
Overview of Chilled Beam Technology Purpose Chilled beam technology is new to the United States but has been used in Europe since the 1950 s. Chilled beams can reduce energy costs, improve indoor air quality,
More informationASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES
INTRODUCTION ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES Tom Brooke MBA, PE, CEM May 25, 212 On April 19, 212, ASHRAE conducted a webcast to publicize the concept of Dedicated
More informationTechnical Assignment 3 11/15/04. Executive Summary
Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria
More informationTHE ULTIMATE ROOFTOP SOLUTION
Configured Packaged Rooftop Solutions Specializing in Dedicated Outdoor Air Systems (DOAS) Capacities from 6 to 90 Tons Available in 208, 230, 460 and 575 Volts THE ULTIMATE ROOFTOP SOLUTION Service Friendly
More informationMECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE
MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE 18422 Bear Valley Road Victorville, CA 92395 Date 25 September 2012 dha Job No. 12155 TABLE OF CONTENTS I. Purpose.... Page 1 II. Existing
More informationMulti-Path RTU-TYPE 2
ALDI # CITY, STATE SUPERMARKET MultiPath RTUTYPE 2 (RTU1) CESMPU025RHVAV2 Date: February 17, 201 2013 Consolidated Energy Solutions, Inc. UNIT FEATURES CES TYPE VAV2 Unit features include: 25 Ton MultiPath
More informationVertiCool Aurora Engineering Guide
Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8
More informationAgenda and Objectives
Agenda and Objectives Trane Engineers Newsletter Live Series Rooftop variable-air-volume (VAV) systems are used to provide comfort in a wide range of building types and climates. This ENL discusses HVAC
More informationC13-Series Engineering Guide
Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................
More information100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION
100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest
More informationA. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.
SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate
More informationCommercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark
Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office
More information2. CURRICULUM. Sl. No.
. CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration
More informationR7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units
TECHNICAL SPECIFICATIONS R7DA Series 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units 5.4 ISMRE Commercial System 81% Steady State Efficiency Standard Features Fits Pre-Existing Curbs High-Efficiency Low
More information