SECTION FAN COIL UNITS

Size: px
Start display at page:

Download "SECTION FAN COIL UNITS"

Transcription

1 PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections: The following sections contain requirements that relate to this section: 1. Section Basic Mechanical Materials and Methods 2. Section Motors 3. Section Hangers and Supports 4. Section Vibration and Seismic Controls for HVAC Piping and Equipment 5. Section Hydronic Piping 1.2 SUMMARY A. This Section includes fan-coil units with water coils for heating and cooling. B. This Section includes fan-coil units with water cooling coils. C. This Section includes large capacity fan-coil units. 1.3 SUBMITTALS A. General: Submit each item in this Article according to the Conditions of the Contract and Specification Sections. B. Product Data for each type of product specified. C. Wiring diagrams detailing wiring for power and control systems and differentiating clearly between manufacturer-installed and field-installed wiring. D. Qualification data for firms and persons specified in the "Quality Control" Article to demonstrate their capabilities and experience. Include lists of completed projects with project names and addresses, names and addresses of architects and owners, and other information specified. E. Field test reports from a qualified independent inspecting and testing agency indicating and interpreting test results relative to compliance with performance requirements of fancoil units. 1.4 QUALITY CONTROL A. Manufacturer Qualifications: Engage a firm experienced in manufacturing fan-coil units similar to those indicated for this Project and that have a record of successful in-service performance. B. Comply with ARI 440 for testing and rating units. C. Comply with ASHRAE 33 for testing air coils. Page 1 of 5

2 D. Comply with NFPA 70 for components and installation. E. Listing and Labeling: Provide products specified in this Section that are listed and labeled. 1. The Terms "Listed" and "Labeled": As defined in the National Electrical Code, Article Listing and Labeling Agency Qualifications: A "Nationally Recognized Testing Laboratory" (NRTL) as defined in OSHA Regulation EXTRA MATERIALS A. Furnish extra materials described below that match products installed, are packaged with protective covering for storage, and are identified with labels clearly describing contents. 1. Fan-Coil Unit Filters: Furnish one spare filter for each filter installed. 2. Belts: Furnish one set of belts for belt drive units. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. United Technologies Corp; Carrier Corp. Div. 2. Trane Company (The) 3. York International Corp.; Applied Systems Div. 4. International 5. Williams 2.2 A. Provide fan coil units where shown on the Drawings. Fan coil units shall be of size, type, and capacity as scheduled; all units shall be tested and rated in accordance with ARI Standard Units shall be horizontal or vertical type with recessed, semi recessed or wall mounted cabinet as shown. Each unit shall have dimensions and design suitable for the locations shown on the Drawings. 1. NOTE: All data provided on the schedules are for units operating at medium speed. B. Units shall have a maximum sound power level of 34 db based on watts for the fourth octave band when operating at medium speed. All units shall be sound rated in accordance with ARI Standard C. Each fan coil unit shall consist of a cabinet, a fan assembly, a chilled water coil, a heating coil, a condensate drain pan, an auxiliary condensate drain pan, a filter, and a fan speed switch unless indicated otherwise. 1. Cabinets shall be constructed with 16 gauge front panels for vertical units and with 18 gauge front panels for horizontal units and with 18 gauge back panels. All panels shall be phosphorized for rust resistance and finished with baked enamel finish of color selected by the Owner. Oversized cabinets shall be Page 2 of 5

3 provided if required for making the necessary piping connections. All portions of the cabinets exposed to cold air discharge shall be provided with heavy insulation to prevent sweating. a. Type 1 cabinets shall have a fully concealed vertical wall type chassis. Units shall have top ducted discharge and front return. b. Type 2 cabinets shall have vertical floor mounted type cabinets. Units shall have top discharge and front return. c. Type 4 cabinets shall have fully recessed vertical wall type cabinets. Units shall have top ducted discharge and front return. d. Type 5 cabinets shall have surface mounted horizontal ceiling type cabinets. Units shall have front (horizontal) discharge and rear return. e. Type 7 cabinets shall have recessed horizontal ceiling type cabinets. Units shall have ducted front discharge and bottom return. f. Type 8 cabinets shall have fully concealed horizontal ceiling type cabinets. Units shall have ducted front discharge and ducted rear return. Cabinet face shall be fully accessible from below the unit. No filters will be required with this type of unit when return filter grilles are employed. 2. Fans shall be constructed of non-corrosive material and be of the forward curved single or double centrifugal type. Cabinets shall be equipped with removable fronts (bottoms) for access to the interior. Fans shall be direct drive type arranged for blow-through configuration. Motors shall be high efficiency, resilient mounted, permanently lubricated 3 speed tap wound permanent split capacitor, open type motors and shall be suitable for 115 volt 1 phase 60 hertz service. All motors shall have integral thermal overload protection. 3. Chilled water cooling coils shall be constructed of copper tubes rated for 150 (300) psig working pressure, mechanically expanded into plate type aluminum fins. Coils shall have female sweat end connections. 4. Heating coils shall be constructed of copper tubes rated for 150 (300) psig working pressure, mechanically expanded into plate type aluminum fins. Tubes shall be of minimum of 1/2-inch O.D. and shall be joined to steel headers. Coils shall be suitable for use with hot water. 5. Drain pan shall be constructed of 18 gauge galvanized steel and insulated on the under side with closed cell insulation. Auxiliary drain pan shall be insulated and have a 3/4 inch male pipe thread drain connection. 6. Filters shall be throwaway 30 percent efficiency type. 7. Each vertical unit shall be provided with a four position (off-high medium low) switch mounted inside the cabinet, which shall be easily accessible for operation from outside the cabinet. This switch shall also act as a disconnect switch. In addition, a factory mounted disconnect switch shall be provided inside the unit. 8. Each horizontal unit shall be provided with a wall mounted four position (off high medium low) switch shipped loose for field installation. In addition, a factory mounted disconnect switch shall be provided inside the unit. 9. Chilled water coils must be designed with a 16 to 18 temperature differential. D. Each unit shall be furnished with factory formed piping to suit control valves. Vertical units shall be furnished with cabinet levelers; horizontal units shall be provided with spring vibration isolators. 2.3 LARGE CAPACITY Page 3 of 5

4 A. Provide fan coil units where shown on the Drawings. Units shall be of size and capacity as scheduled. B. Each fan coil unit shall consist of a water cooling coil, a drain pan assembly, and a centrifugal fan with drive mounted in a common cabinet for independent air delivery from a single unit. Units shall be complete except for controls. 1. Casings shall be constructed of 16 gauge steel, phosphorized to assure paint adherence and finished with baked enamel. Casings shall be insulated with minimum 3/4 inch fire proof, odorless fiber glass material to prevent condensation. 2. Water coils shall be of a multiple row design with as indicated with highly efficient fins. Aluminum fins shall be mechanically bonded to 5/8 inch O.D. seamless copper tubes. All coils shall be specifically designed and circuited for water use. All coils shall be suitable for 200 psig working pressure and shall be tested at 300 psi. Sweat type coil connections shall be provided. 3. Fans shall be forward curved, centrifugal blower type fans equipped with heavy duty adjustable V belt drive. The fan shaft shall be supported by permanently lubricated bearings which shall be designed for long life. All fans shall be dynamically balanced. All units shall have a single fan. 4. Drain pans shall be integrally attached to coil casings and shall be complete with threaded pipe drain connection. All pans shall be galvanized for corrosion resistance and cover the entire coil length. C. Filters shall be supplied separately. D. Motors less than 1/2 horsepower shall be two pole single phase motors suitable for 115 volt, 1 phase, 60 hertz electrical power. All motors shall have 10% voltage utilization range and shall be wired to a unit mounted junction box. Motors shall be designed for long life and shall include internal thermal overload protection. E. Motors 1/2 horsepower and larger shall be as specified in Motors Section. Motors shall also be provided with combination starters as specified in Motors Section. F. Units shall be provided with spring vibration isolators. G. Each fan coil unit which is not provided with a combination starter shall be provided with a manual motor starter of ample capacity to disconnect unit. This starter shall be shipped loose and shall also serve as a disconnect switch. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and supports to receive fan-coil units for compliance with requirements for installation tolerances and other conditions affecting performance of fan-coil units. Do not proceed with installation until unsatisfactory conditions have been corrected. 3.2 INSTALLATION Page 4 of 5

5 A. Install fan-coil units as indicated, to comply with manufacturer's written instructions and NFPA 90A. B. Connect fan-coil units and components to wiring systems and to ground as indicated and instructed by manufacturer. Tighten connectors and terminals, including screws and bolts, according to equipment manufacturer's published torque-tightening values for equipment connectors. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals according to tightening requirements specified in UL 486A. C. Connect fan-coil units to hydronic piping according to Section "Hydronic Piping." Provide shutoff valve and union or flange at each connection. D. Fan coil units installed above the ceiling grid level shall have all returns ducted to ceiling grid level with filters installed at ceiling grid. 3.3 FIELD QUALITY CONTROL A. Testing: After installing fan-coil units and after electrical circuitry has been energized, demonstrate product capability and compliance with requirements. B. Remove and replace malfunctioning units with new units, and retest. 3.4 CLEANING A. Replace filters in each fan-coil unit. 3.5 START UP SERVICE A. Startup Services: Engage a factory-authorized service representative to provide startup service. B. Operate fan motor to verify proper rotation. C. Operate electric heating elements through each stage to verify proper operation and electrical connections. D. Test and adjust controls and safeties. Replace damaged or malfunctioning controls and equipment. END OF SECTION Page 5 of 5

SECTION (15767) - UNIT HEATERS

SECTION (15767) - UNIT HEATERS SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

C. Samples for Initial Selection: For units with factory-applied color finishes.

C. Samples for Initial Selection: For units with factory-applied color finishes. SECTION 238126- SPLIT-SYSTEM AIR-CONDITIONERS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services Page 238216-1 Copyright 2003 and 2005 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION CONVECTION HEATING AND COOLING UNITS

SECTION CONVECTION HEATING AND COOLING UNITS PART 1 GENERAL 1.01 SECTION INCLUDES A. Baseboard radiation. B. Finned tube radiation. C. Convectors. D. Unit heaters. E. Cabinet unit heaters. F. Fan-coil units. G. Unit ventilators. H. Blower-coil units.

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

DARTMOUTH COLLEGE DESIGN March 15, 2003 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN March 15, 2003 & CONSTRUCTION GUIDELINES SECTION 15830 HEATING & COOLING TERMINAL UNITS PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. All fan coil units shall be sized to meet design load while operating at medium speed. In extreme noise sensitive

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

Product Specifications. Vertical Floor Consoles By First Co.

Product Specifications. Vertical Floor Consoles By First Co. NOW WITH 18 GAUGE CABINET AND FACTORY INSTALLED SERVICE SWITCH Product Specifications VFB Series VSB Series VCB Series Vertical Console Fan Coils 300-00 CFM Vertical Floor Consoles By First Co. VFB Series

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork. SECTION 15855 AIR HANDLING UNITS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.02 REFERENCES A. Air Moving

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

SECTION CONVECTION HEATING AND COOLING UNITS

SECTION CONVECTION HEATING AND COOLING UNITS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 82 00 CONVECTION HEATING AND COOLING UNITS SPEC WRITER NOTES: 1. Delete between//----// if not applicable to project. Also delete any other item or paragraph

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

A. This Section includes air-handling units with coils for indoor installations.

A. This Section includes air-handling units with coils for indoor installations. SECTION 237313 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes air-handling units with coils for indoor installations. 1.2 SUBMITTALS A. Product Data: For each type of indoor air-handling unit

More information

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT SECTION 23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes packaged roof top unit, unit controls, remote panel, roof mounting curb and base, maintenance service,

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems. 15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution

More information

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals. SECTION 23 21 23 - HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

EHH SERIES DRAW THROUGH FAN COILS CFM

EHH SERIES DRAW THROUGH FAN COILS CFM EHH SERIES DRAW THROUGH FAN COILS 400-5000 CFM TABLE OF CONTENTS TABLE OF CONTENTS 2 INTRODUCTION 3 GUIDE SPECIFICATIONS 4 UNIT OVERVIEW 6 TECHNICAL DATA 8 DIMENSIONS 10 COMPUTER SELECTION 11 GEMCOOL PROFILE

More information

SECTION ROOFTOP REPLACEMENT AIR UNITS

SECTION ROOFTOP REPLACEMENT AIR UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

Large Capacity Fan Coil Units Belt and Direct Drive Cabinet and Hideaway

Large Capacity Fan Coil Units Belt and Direct Drive Cabinet and Hideaway Catalog C: 735-7 Large Capacity Fan Coil Units Belt and Direct Drive Cabinet and Hideaway Direct Drive CUL Listed McQuay Large Capacity Fan Coil Units Page 2 / Catalog 735 Direct drive hideaway unit The

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories for each type of product indicated.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories for each type of product indicated. PART 1 - GENERAL 1.1 SUMMARY A. This Section includes 1. Hydronic baseboard radiators. 2. Hydronic finned-tube radiators. 3. Hydronic convectors. 1.2 SUBMITTALS A. Product Data: Include rated capacities,

More information

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 SECTION FLOOR MOUNTED FAN COIL UNITS (UN-DUCTED)

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 SECTION FLOOR MOUNTED FAN COIL UNITS (UN-DUCTED) P00000000 0000 DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A Publication No. WT-CSX-0616A Central Station Air Handling Units Complete HVAC Capability Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013 SECTION 15800 - AIR HANDLING EQUIPMENT 1.1 GENERAL A. All air handlers installed shall conform to the University of Rochester specification Guideline for Semi-Custom and Pre-Engineered Air Handling Units.

More information

SeasonMaker ThinLine Fan-coil Units

SeasonMaker ThinLine Fan-coil Units Catalog C: 720-12 SeasonMaker ThinLine Fan-coil Units Type TSH & TSC Horizontal Design TSS, TPF, TSF & TSB Vertical Design C L I S T E D Ratings Certified by the Air Conditioning & Refrigeration Institute

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

SeasonMaker ThinLine Fan-coil Units

SeasonMaker ThinLine Fan-coil Units Catalog C: 720-12 SeasonMaker ThinLine Fan-coil Units Type TSH & TSC Horizontal Design TSS, TPF, TSF & TSB Vertical Design C L I S T E D Ratings Certified by the Air Conditioning & Refrigeration Institute

More information

CB18/CBS18 Bulletin # September 1994 Supersedes August 1986

CB18/CBS18 Bulletin # September 1994 Supersedes August 1986 ENGINEERING DATA CB18 SERIES UP-FLOW CBS18 SERIES HORIZONTAL 2 To 5 Ton (7 To 18 kw) Nominal Cooling Capacity 7200 To 102 400 Btuh (2.1 To 30.0 kw) Optional Electrical Heat ENGINEERING DATA COILS MATCHED

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 82 16 AIR COILS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL

SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL SO TOUGH, WE GUARANTEE IT. SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL SSL SBS www.superiorrex.com SSL / SBS Series: BIG ON FEATURES; SMALL IN SIZE Contractors All SSL/SBS model blower-coil

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES Page 226119-1 SECTION 226119 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

AIR HANDLER SPECIFICATION

AIR HANDLER SPECIFICATION AIR HANDLER SPECIFICATION Air Handlers AH-1 through 5 The following air handlers will be supplied: AH-1 FX15-4842 Series 5700 CFM AH-2 FX15-4236 Series 3990 CFM AH-3 FX15-3633 Series 2570 CFM AH-4 FX15-3330

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw) Indoor Single Package Vertical, Air-Cooled Heat Pump Unit RetroAire Model Number: Capacity Range: VPRH 9,000 to 36,000 Btuh (2.6 to 10.5 kw) Part 1 General 1.01 UNIT DESCRIPTION A. Indoor, single package

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 08:50:16 AM Job Name: EarthWise Modular Climate Changer Full Spec Location: Any Town, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SUBMITTALS Submittals

More information

SECTION AIR-SOURCE UNITARY HEAT PUMPS

SECTION AIR-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 81 43 AIR-SOURCE UNITARY HEAT PUMPS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION WATER-TUBE BOILERS

SECTION WATER-TUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more. Page 237323-1 SECTION 237323 - For large systems, 50,000 cfm or more. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH MHCCW-10-05 Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH Rev. 1.21 HVAC Guide Specifications Chilled Water Fan Coil with Electric Heat 2-Pipe Nominal Size:

More information

Catalog C: McQuay Horizontal Concealed Fan Coil Unit

Catalog C: McQuay Horizontal Concealed Fan Coil Unit Catalog C: 700-1 McQuay Horizontal Concealed Fan Coil Unit Model THC Sizes 200 Through 1200 CFM McQuay THC Horizontal Concealed Fan Coil Nomenclature F THC 1 H02 Fan-coil Type of Unit THC = Horizontal

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH MHCCW-06-00 Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH Rev. 1.21 HVAC Guide Specifications Chilled or Hot Water Fan Coil 2-Pipe Nominal Size: 18,000 BTUH

More information

engineering guide FH Fan-Coil Units Low-Profile, Horizontal

engineering guide FH Fan-Coil Units Low-Profile, Horizontal engineering guide FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908) Table of contents FH Fan-Coil Units Low-Profile, Horizontal Features and Benefits... Construction Features... Standard

More information

Large Capacity Fan Coil Units Catalog Belt-Drive and Direct-Drive Cabinet and Hideaway Models

Large Capacity Fan Coil Units Catalog Belt-Drive and Direct-Drive Cabinet and Hideaway Models Large Capacity Fan Coil Units Catalog 735-12 Belt-Drive and Direct-Drive Cabinet and Hideaway Models Table of Contents Agency Listing and Nomenclature... 3 Overview....................................

More information

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH MHNCCW-04-01 (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH Rev. 1.2 HVAC Guide Specifications Chilled and Hot Water Fan Coil 4-Pipe Nominal Size: 12,000

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 37,800* Design CFM: 1,200 Seasonal

More information

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup. SECTION 23 70 00- CENTRAL HVAC EQUIPMENT PART 1: GENERAL 1.1 PURPOSE: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

AIR COOLED PACKAGED CHILLER

AIR COOLED PACKAGED CHILLER AIR COOLED PACKAGED CHILLER UNIC sal is equipped to produce a wide range of COOLER Air conditioning and Refrigeration units, conforming to the international standards and works continually to improve its

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Placement within a mechanical room is required for all major mechanical equipment. Only small units may be roof-mounted, and shall be made as inconspicuous

More information

FCC Fan-Coil Units High-Performance, Vertical

FCC Fan-Coil Units High-Performance, Vertical FCC Fan-Coil s High-Performance, Vertical Model FCC construction features Piping and supply-duct connections are from top of unit, eliminating the need for side or back access Right or left-hand configurations

More information

SECTION AXIAL FANS

SECTION AXIAL FANS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

A. General: Refer to paragraph entitled SUBMITTAL in Section Include the following data: SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016 SECTION 23 21 23 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section.

More information

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make.

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make. All outdoor units are designed to perform satisfactorily at 52 C, with the option of either top discharge condensing units, with Copeland reciprocating scroll compressors. All top discharge condensing

More information

SSL & SBS Engineering Guide

SSL & SBS Engineering Guide REDUCED-FOOTPRINT VERTICAL BLOWER COIL UNITS SSL & SBS Engineering Guide SO TOUGH, WE GUARANTEE IT. SSL SBS Table of Contents Features and Benefits... 3 Construction Features... 4 Features and Options...

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 3300 - ELECTRIC, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements. SECTION 15855 AIR HANDLING UNITS WITH COILS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Central Station Air Handling Units. B. Related Sections: 1.02 REFERENCES 1. Section 15010 - Basic Mechanical

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

PROJ. NO SECTION REFRIGERANT PIPING

PROJ. NO SECTION REFRIGERANT PIPING SECTION 23 23 00 REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13 Tag Data - Split System Air Conditioning Units (Large) (Qty: 6) Item Tag(s) Qty Description Model Number A1 20 ton vfd 6 6-25 Ton Unitary Split Systems ( SSC2 TTA24004H00-TWE240E404A TTA Air Condensing

More information

Horizontal and Vertical DIRECT DRIVE BLOWER COIL UNITS. Rating and selection at

Horizontal and Vertical DIRECT DRIVE BLOWER COIL UNITS. Rating and selection at Horizontal and Vertical DIRECT DRIVE BER COIL UNITS Rating and selection at www.enviro-tec.com CDH/CDV TABLE OF CONTENTS Construction Features...3 Fan Assembly...4 Optional Construction...5 Electric Heat...6

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING SECTION 221123 - DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1.

More information

Cabinet Unit Heaters Steam / Hot Water

Cabinet Unit Heaters Steam / Hot Water 11-160.4 February, 2005 Cabinet Unit Heaters Steam / Hot Water Model C MODEL IDENTIFICATION Table of Contents I. Model Identification... 3 Page Il. IIl. III. IV. Design Benefits A. Features and Benefits...

More information

catalog CDV Fan-Coil Units High-Performance, Vertical

catalog CDV Fan-Coil Units High-Performance, Vertical catalog CDV Fan-Coil Units High-Performance, Vertical Catalog: ET115.26-EG8 (415) TABLE OF CONTENTS CDV Fan-Coil Units High-Performance, Vertical Features and Benefits... 3 Construction Features... 4 Standard

More information