MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM
|
|
- Wesley Hugo Ball
- 5 years ago
- Views:
Transcription
1 Proceedings of ASME FEDSM 3 4 th ASME_JSME Joint Fluids Engineering Conference Honolulu, Hawaii, USA, July 6-1, 23 MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM Junjie Gu Department of Mechanical and Aerospace Engineering Carleton University, Ottawa, Ontario K1S 5B6 Canada jgu@mae.carleton.ca F E DSM Masahiro Kawaji Department of Chemical Engineering & Applied Chemistry, University of Toronto, Toronto, Ontario M5S 3E5, Canada kawaji@ecf.utoronto.ca Tracey Smith-Pollard, James Cotton Long Manufacturing Ltd., Oakville, Ontario L6K 3E4, Canada Tracey_Smith-Pollard@longmfg.com ABSTRACT This paper presents an improved on-line measurement technique developed to study two-phase flow rate distributions of refrigerants in parallel flow channels of compact heat exchangers and evaporators used in automotive air-conditioning systems. A prototype test station containing a refrigerant flow loop and a multi-channel two-phase flow measuring system, was designed and constructed based on the stratification of two-phase flow in horizontal tubes with relatively large diameters. In this work, glass tubes of 1, 1.5 and 2 diameter were tested. Upon entering the glass tube, a vapour-liquid refrigerant mixture would readily stratify and the mean velocities of vapour and liquid phases could be measured separately using a hot film anemometer and an ultrasonic flow meter, respectively. Scales taped onto the glass tubes were also used to determine the mean liquid levels, from which the flow area of each phase could be calculated. The product of the flow area, phase density and mean phase velocity would then yield the mass flow rate of each phase. Validation experiments have been performed with R-134a as the working fluid and a 3-channel evaporator test section, designed with three separate outlets and kept under an adiabatic condition. The sum of the flow rates in the glass tubes for each phase was compared with the vapour or liquid flow rate determined from the total mass flow rate measured at the evaporator inlet and a heat balance in the pre-heater section of the pump-driven refrigerant flow loop. Validation tests yielded satisfactory results for both vapor and liquid phases, indicating the soundness of the measurement system based on the stratification tubes as well as the use of an ultrasonic flow meter and hot-film anemometer probes for phase average velocity measurements. The present measurement system has been equipped with seven glass tubes and thus can be used to study liquid and vapor flow rate distributions in commercial compact heat exchangers and improve their performance in automobile air conditioning systems. Keywords: two-phase flow, evaporator, flow distribution, flow quality, measurement technique INTRODUCTION Two-phase flow rate distributions in parallel channels of a compact heat exchanger may be non-uniform depending on how the vapour-liquid mixture enters the heat exchanger. Our previous measurements of air-water flow rate distributions indicated strongly non-uniform conditions (Rong et al., 1995, 1996), however, the actual flow rate distributions of a refrigerant vapor-liquid mixture could be somewhat different due to a different density ratio between the vapour and liquid, and other fluid properties. Thus, there is a need to investigate the two-phase flow rate distributions in parallel flow channels of an evaporator for a refrigerant commonly used in car air-conditioning systems. This paper deals with the design and set-up of a prototype test station, which contains a multi-channel two-phase flow measurement system and a pumped freon flow loop. The first trial experiment has been performed with a 3-channel test evaporator, and the vapour and liquid flow rates in each channel were determined separately. MULTI-CHANNEL TWO-PHASE FLOW LOOP In order to measure the two-phase flow rate distribution in parallel channels of compact heat exchangers, a freon flow loop was constructed as shown in Figure 1, equipped with hot-film anemometer probes and an ultrasonic flow meter (Gu and Kawaji, 22). The measurement methods adopted are based on the stratification of two-phase flow in horizontal tubes with relatively large diameters (Kawaji et al., 21; Hwang, 21). 1
2 Figure 1 Schematic of a Freon Flow Loop Glass tubes of 1, 1.5 and 2 diameter were tested and initially they were placed horizontally, but that resulted in a stagnant liquid pool to remain in the glass tube under no or low flow conditions. Thus, to ensure there is no stagnant liquid in the glass tube under low flow rates, the glass tubes were slightly inclined downward at an angle of 2~5 degrees such that the elevation of the inlet was higher than that of the outlet. MEASUREMENT The two-phase flow was stratified in each glass tube, and the flow rate of each phase was measured separately using a hot-film anemometer (FMA-94-V, Omega) and an ultrasonic flow meter (DUFX2-D1-NT, Omega) at a measurement station located 1.75 m from the glass tube inlet as shown in Fig. 2. A scale was taped around the bottom of the glass tube to measure the width of the liquid stream, from which the liquid level and the cross sectional areas of both phases were determined. Validation of hot-film anemometer Different single-phase vapour flow rates could be achieved in the glass test section by boiling the refrigerant at a given mass flow rate at different power levels in the heating section (Gu et al., 21). Figure 3 shows the actual velocities of R-134a vapour and those measured using the hot-wire anemometer for different total liquid-vapor flow rates. The hot-film anemometer can be seen to successfully measure the velocities of R134a vapour. Actual, m/s Measured, m/s.5 l/min 1I/min 2 l/min Figure 3 Validation of hot-wire anemometer Validation of ultrasonic flow meter The ultrasonic flow meter uses the principle of a Doppler effect, in which the frequency of ultrasonic pulses reflected from tiny impurities (as reflectors) in a moving liquid will be altered from the frequency of the transmitted ultrasonic waves. The magnitude of frequency change is directly proportional to the velocity of the liquid. Figure 4 shows the application of a commercial ultrasonic flow meter to the measurement of the liquid R134a velocity in two-phase stratified flow in a slightly inclined tube. Figure 2 Measurement of two-phase stratified flow 2
3 From heat balace, f/s Measured, f/s.5 l/min 1 l/min 2 l/min Measured flow rate, kg/s Actual flow rate from heat balance, kg/s Figure 4 Validation of ultrasonic flow meter The data show satisfactory performance of the ultrasonic flow meter to measure the velocity of the liquid phase under stratified flow conditions. Surface waves In liquid-vapour two-phase stratified flow, surface waves often form because of the interfacial shear stress induced by the fast traveling vapour phase. The waves makes the flow measurements more difficult. To avoid waves, large diameter tubes were chosen to reduce the vapour velocity. A small downward inclination (~ 3º) of the tubes in the flow direction also helped in obtaining a smooth liquid flow. Liquid and vapour mass flow rates Figure 5 shows a comparison of the measured and actual liquid mass flow rates. The actual liquid flow rate was calculated from the total mass flow rate measured by a turbine flow meter minus the vapour mass flow rate calculated from a heat balance applied to the heating section. The measured vapour mass flow rates are compared with the actual flow rates as shown in Figure 6. The actual vapour flow rate was calculated from the total mass flow rate and electric heater power using a heat balance applied to the heating section. In both cases, the measurements are seen to be consistent with the actual liquid and vapour mass flow rates. Total mass flow rate Figure 5 Liquid mass flow rate The measured and actual total mass flow rates are compared in Figure 7. The actual total flow rate is the flow rate measured by a turbine flow meter. The sum of the liquid and vapour mass flow rates measured conform to the actual total flow rate. Vapour quality Vapor quality is the ratio of the vapor mass flow rate to the total mass flow rate. The combination of an ultrasonic flow meter and a hot-film anemometer probe could yield satisfactory flow quality measurements, as shown in Figure 8. Measured flow rate, kg/s Actual flow rate from heat balance, kg/s Figure 6 Vapour mass flow rate 3
4 Measured total flow rate, kg/s Actual total flow rate, kg/s Figure 7 Total mass flow rate.8 Measured quality, Figure 8 Quality from heat balance, - Flow quality measurements The validation tests described above have successfully demonstrated the feasibility of using an ultrasonic flow meter and a hot-film anemometer probe to measure the flow rates of vapour and liquid separately, in a refrigerant R134a two-phase flow loop. MULTIPLE-CHANNEL EVAPORATOR TEST The freon loop was modified to enable testing of multiple-channel evaporators supplied by Long Manufacturing Ltd. Liquid and vapour flow rates in up to seven separate channels need to be measured at the same time, thus an outlet manifold and a seven parallel glass-tube assembly were designed and constructed as shown in Figures 9 and 1, respectively. The outlet manifold is used to connect up to seven channels to a single inlet tube of a condenser. For each channel, the fluid temperature is measured using a thermocouple. The pressure is also measured in the outlet manifold so that the densities of freon vapour and liquid can be determined for each channel assuming saturated conditions. In Figure 1, the parallel glass tube assembly containing three tubes is shown connected to the outlet manifold and a three-channel evaporator. Figure 9 Outlet manifold connecting the parallel glass tubes to a condenser Figure 11 shows the hot-film anemometer probes installed in three glass tubes, along with the readout device of an ultrasonic flow meter for liquid flow measurement. The liquid level in each glass tube could be measured by visual observation and using a scale taped around each glass tube. Although the spacing between the glass tubes was tight, it was possible to observe the liquid level by viewing each glass test section from the top at a certain angle, and locating the side edge of the liquid layer on the taped scale. Figure 1 Freon two-phase flow loop with a three-channel evaporator 4
5 Figure 11 Hot-film anemometers and ultrasonic flow meter TRIAL EXPERIMENTS USING A 3-CHANNEL EVAPORATOR Following a leak test, the completed multi-channel test facility was charged with R-134a, and the first trial experiment was carried out with the three-channel evaporator as shown in Figure 12. As summarized in Table 1, these preliminary tests were performed at two different freon flow rates of 1. and 2. litre/min, corresponding to mass flow rates of 1.24 and 2.48 kg/min. For each flow rate, the heater power was set to, 1 W, and 2 W to have either single-phase liquid or a vapour-liquid mixture of different quality flowing into the three-channel evaporator. From a heat balance, the inlet mass qualities could be determined as shown in Table 1. Figure 12 Test evaporator with three outlets For each channel, the hot-film anemometer and ultrasonic flow meter readings as well as liquid levels were obtained. Surprisingly, the flow rate distribution for this top feed configuration and conventional inlet header design was relatively uniform, unlike in the previous air-water tests. The main reason for this result is suspected to be the long (about 2-m) and thin (1/4 ) copper tubing used to connect each evaporator outlet to the glass tube as shown in Figure 13. This copper tubing also had two small loops near the ends to provide enough flexibility for connection to the fragile outlet tubes of the evaporator unit. A high resistance to flow at the exit of an evaporator may have created enough back pressure for all the channels to equalize the freon flow rates. A modification is underway to shorten this connection and eliminate any loop in order to reduce the flow resistance at the evaporator outlet. Flow Rate, l/min Table 1: Experimental Data Sheet Heater Power Temperature Hot-film Ultrasonic W Channel # C (reading) (reading) Level, mm , , , , Note: The channels are numbered from the position near the evaporator inlet, and the evaporator is seated in a vertical top-feed orientation. 5
6 Kawaji, M., Hwang, D.H., Karimi, G., Dickson, T. R., Smith-Pollard, T., 21, Flow quality measurement based on stratification of flow in air-water and refrigerant two-phase flow systems. 4th International Conference on Multiphase Flow, New Orleans, Louisiana, USA. May 27 - June 1, 21. Hwang, D.H., 21. Flow quality measurements based on stratification of flow in nitrogen gas water and HFC-134a refrigerant PAG oil two-phase flow systems, M.A.Sc. Thesis, Department of Chemical Engineering & Applied Chemistry, University of Toronto. Figure 13 The long tubing from evaporator outlets to glass tubes SUMMARY An in-line two-phase flow measurement system was developed and tested in an R-134a flow loop. A hot-film anemometer and an ultrasonic flow meter were used to measure the vapour and liquid flow rates separately in a horizontal glass tube at the exit of a multiple-channel evaporator. The freon loop was also modified to enable measurements of two-phase flow rate distributions from three up to seven outlets of a commercial evaporator. The preliminary test results showed a relatively uniform flow rate distribution in all three channels in contrast to the air/water experiment results, in which the first channel received most of the liquid under the top-feed condition. This result may have been caused by the high flow resistance presented by the long and thin tubing (2.2 m long, 1/4" diameter), used to connect each evaporator outlet to the glass tube. In order to eliminate the influence of the outlet flow resistance, a further modification of the evaporator outlet connection to the glass tube is underway. REFERENCES Gu, Junjie and Kawaji, M., 22. Two-phase Flow Measurements of R134a in a Pump-driven Flow loop, a Final Report submitted to Long Manufacturing Ltd., January 22. Rong, X.Y., Kawaji, M. and Burgers, J.G., Two-phase header flow distribution in a stacked plate heat exchanger. ASME, FED - Vol. 225, pp Rong, X.Y., Kawaji, M. and Burgers, J.G., Gas-liquid and flow rate distributions in single end tank evaporator plates. A paper presented at the SAE Annual Congress, Detroit, February 26-29, 1996, SAE SP-1175, pp
COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS
COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS A. Hafner SINTEF Energy Research Refrigeration and Air Conditioning Trondheim (Norway) ABSTRACT The natural refrigerant carbon dioxide (CO 2 ) with all its
More informationPerformance of an Improved Household Refrigerator/Freezer
Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical
More informationEFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM
- 1 - EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM Shun YOSHIOKA, Hyunyoung KIM, Kazushige KASAI, Daikin Industries,
More informationInternal flow Patterns of the Horizontal Heat Mode Closed-Loop Oscillating Heat Pipe with Check Valves (HHMCLOHP/CV)
Research Journal of Applied Sciences, Engineering and Technology 5(3): 865-869, 2013 ISSN: 2040-7459; E-ISSN: 2040-7467 Maxwell Scientific Organization, 2013 Submitted: June 13, 2012 Accepted: July 09,
More information*Corresponding author;
PERFORMANCE ANALYSIS OF AUTOMOTIVE AIR CONDITIONING SYSTEM WITH AN INTERNAL HEAT EXCHANGER USING R1234YF UNDER DIFFERENT EVAPORATION AND CONDENSATION TEMPERATURES by Mehmet DIREK a *and Alper KELESOGLU
More informationAn Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 22 An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning
More informationMINIATURE HEAT TRANSPORT SYSTEMS WITH LOOP HEAT PIPES
IV Minsk International Seminar Heat Pipes, Heat Pumps, Refrigerators Minsk, Belarus, September 4-7, MINIATURE HEAT TRANSPORT SYSTEMS WITH LOOP HEAT PIPES V. Kiseev, A. Belonogov Ural State University,
More informationEnhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System
Enhancement of COP by Using Spiral and Microchannel instead of conventional of VCR System 1 P.G. Lohote, 2 Dr.K.P. Kolhe. 1 P.G. Student, 2 Professor. 1,2 Department of Mechanical Engineering, JSPM s,
More informationHEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1
HEFAT27 5 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp PERFORMANCE ANALYSIS OF AIR-COOLED CONDENSER USING MICRO-FIN TUBES P.A.Patil
More informationAn experimental study of the impact of tunnel suppression on tunnel ventilation
An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,
More informationExperimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract
Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant M. Honma, T. Tamura, Y. Yakumaru and F. Nishiwaki Matsushita Electric Industrial Co., Ltd. Living Environment
More informationStudy of R161 Refrigerant for Residential Airconditioning
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen
More informationMAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR
MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR Santhosh Kumar Student(M.Tech), Mechanical Dept Gokul group of institutions Visakhapatnam, India M Karteek Naidu ASST PROFF, Mechanical
More informationEffect of Parameters on Internal Flow Patterns of a Top Heat Mode Closed-loop Oscillating Heat Pipe with Check Valves (THMCLOHP/CV)
Australian Journal of Basic and Applied Sciences, 5(7): 638-643, 2011 ISSN 1991-8178 Effect of Parameters on Internal Flow Patterns of a Top Heat Mode Closed-loop Oscillating Heat Pipe with Check Valves
More informationOpen Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations
43rd ANZSES Conference Solar 24, Denedin (NZ), 28.11.-3.11.5, CD Abstract Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations M., W. Saman, K. Vajen* Sustainable
More informationHeat Transfer in Evacuated Tubular Solar Collectors
Heat Transfer in Evacuated Tubular Solar Collectors Graham L. Morrison, Indra Budihardjo and Masud Behnia School of Mechanical and Manufacturing Engineering University of New South Wales Sydney 2052 Australia
More informationPressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C
drop analysis of evaporator using refrigerants R-22, R-404A and R-407C #1 Pallavi Sawkar, #2 Dr. Pradeep Patil #12 Department of Mechanical Engineering, JSPM s JSCOE, Savitribai Phule Pune University,
More informationEXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE
Karthikeyan, K. et al.: Experimental Investigations on Automobile Air S515 EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE by Karthikeyan
More informationHEAT EXCHANGERS. Heat exchangers are broadly classified based on the following considerations.
HEAT EXCHANGERS INTRODUCTION The devices that are used to facilitate heat transfer between two or more fluids at different temperatures are known as heat exchangers. Different types and sizes of heat exchangers
More informationHeat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a
2011 International Conference on Advanced Materials Engineering IPCSIT vol.15 (2011) (2011) IACSIT Press, Singapore Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a Eed Abdel-Hafez
More informationFeasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System
Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System Kwanghee Seo 1) and Taewan Kim 2)* 1) KEPCO Engineering & Construction Company. INC., 269 Hyeoksin-ro,
More informationSustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a
Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a Gaurav 1 and Raj Kumar 2 1,2Department of Mechanical Engineering, YMCA University of Science & Technology,
More informationPerformance investigation of Air-conditioning system using ejector as expansion device
International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Performance
More informationPerformance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant
International Journal of Scientific and Research Publications, Volume 4, Issue 7, July 2014 1 Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170
More informationOperation of a Two-Phase Reverse Loop Thermosyphon
Journal of Applied Science and Engineering, Vol. 18, No. 3, pp. 259 264 (2015) DOI: 10.6180/jase.2015.18.3.06 Operation of a Two-Phase Reverse Loop Thermosyphon Meng-Chang Tsai 1, Shung-Wen Kang 2 *, Heng-Yi
More informationExperimental Research On Gas Injection High Temperature Heat Pump With An Economizer
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Research On Gas Injection High Temperature Heat Pump With
More informationEXPERIMENT NO. III AIR ENTRAINMENT INTO AN IRS DEVICE
Objective EXPERIMENT NO. III AIR ENTRAINMENT INTO AN IRS DEVICE To investigate air entrainment into a louvered infrared suppression (IRS) device experimentally on a laboratory scale set up both with cold
More informationNOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS
- 1 - NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS S.J. Metcalf, Z. Tamainot-Telto (1) and R.E. Critoph School of Engineering, University of Warwick, Coventry CV4 7AL, UK Abstract: A new
More informationCHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way
1 CHAPTER I INTRODUCTION In the modern life, electronic equipments have made their way in to practically every part, which is from electronic gadgets to high power computers. Electronic components have
More informationExperimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant
International Journal of Refrigeration 28 (2005) 1302 1307 www.elsevier.com/locate/ijrefrig Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant Tomoichiro
More informationNumerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length
Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University
More informationGlobal Journal of Engineering Science and Research Management
EXPERIMENTAL AND THEORETICAL STUDY OF MINIATURE VAPOR COMPRESSION CYCLE USING MICROCHANNEL CONDENSER Issam M. Ali Aljubury*, Ahmed Q. Mohammed, Marwa S. Neama * Mechanical Eng. Dept. College of Engineering,
More information2. HEAT EXCHANGERS MESA
1. INTRODUCTION Multiport minichannel and microchannel aluminium tubes are becoming more popular as components in heat exchangers. These heat exchangers are used in various industrial applications and
More informationSTUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE
Numbers of Abstract/Session (given by NOC) - 1 - STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE Seok Ho Yoon, Kong Hoon Lee, Chan Ho Song, and Ook Joong Kim Environment and Energy
More informationEFFECT OF CENTRAL PILE IN INCREASING THE BEARING CAPACITY OF BORED PILE GROUPS
EFFECT OF CENTRAL PILE IN INCREASING THE BEARING CAPACITY OF BORED PILE GROUPS Mohamed M. Shahin Department of Civil Engineering, 7 th October University, Misurata,, Libya, E-mail: Mohamed_zubi@yahoo.com
More information0Effect of Fin on the Performance Characteristics of Close and Open Loop Pulsating Heat Pipe
Effect of Fin on the Performance Characteristics of Close and Open Loop Pulsating Heat Pipe Brig Gen Md. Lutfor Rahman, Sumaiya Nawrin, Rasel A Sultan Department of Mechanical Engineering, Military Institute
More informationEffects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance
Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance Jong Min Choi, W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building
More informationNumerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger
International Journal of ChemTech Research CODEN( USA) IJCRGG ISSN 0974-4290 Vol.5, No.2, pp 925-934, April-June 2013 ICGSEE-2013[14th 16th March 2013] International Conference on Global Scenario in Environment
More informationEffect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators
Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators Yong-Ju Hong, Seong-Je Park Korea Institute of Machinery & Materials Daejeon, 35-6, Korea Young-Don Choi Department
More informationNUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A
NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A [1] Ranendra Roy, [2] Madhu Sruthi Emani, [3] Bijan Kumar Mandal [1], [2],[3] Department of Mechanical
More informationThermal Performance of a Loop Thermosyphon
Tamkang Journal of Science and Engineering, Vol. 13, No. 3, pp. 281 288 (2010) 281 Thermal Performance of a Loop Thermosyphon Shung-Wen Kang*, Meng-Chang Tsai, Chih-Sheng Hsieh and Jian-You Chen Department
More informationEFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES
International Journal of Mechanical and Materials Engineering (IJMME), Vol. 2 (2007), No. 2, 109--117. EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES M. Hasanuzzaman
More informationExperimental Study on Waste Heat Recovery from the Pyrolysis Stack using Heat Pipe
2011 International Conference on Communication Engineering and Networks IPCSIT vol.19 (2011) (2011) IACSIT Press, Singapore Experimental Study on Waste Heat Recovery from the Pyrolysis Stack using Heat
More informationPerformance of Shell and Tube Heat Exchanger under Varied Operating Conditions
Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions N. Prabhu Kishore 1, N. Alekhya 2, J. Ugandhar 3 Asst. Professor, Department of Mechanical Engineering, MLR Institute of Technology,
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical
More informationDevelopment of the Micro Capillary Pumped Loop for Electronic Cooling
Development of the Micro Capillary Pumped Loop for Electronic Cooling Seok-Hwan Moon, Gunn Hwang Microsystem Team, Electronic and Telecommunications Research Institute, 161 Kajeong-Dong, Yusong-Gu, Daejeon
More informationFalling Film Heat Exchangers for Solar Water Heaters
Y.C., G.L. Morrison and M. Behnia School of Mechanical and Manufacturing Engineering University of New South Wales Sydney 2052 AUSTRALIA E-mail: yens@student.unsw.edu.au Abstract The characteristics of
More informationExperimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 12, Issue 2 Ver. V (Mar - Apr. 2015), PP 63-67 www.iosrjournals.org Experimental Investigation on
More informationExperimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance
Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule
More informationExperimental Investigation of a Hybrid Evacuated Tube Solar Collector
International Conference on Mechanical, Industrial and Materials Engineering 2015 (ICMIME2015) 11-13 December, 2015, RUET, Rajshahi, Bangladesh Paper ID: ET-46 Experimental Investigation of a Hybrid Evacuated
More informationTWO-PHASE MICRO-CHANNEL HEAT SINK FOR SPACE CRAFT THERMAL CONTROL
TWO-PHASE MICRO-CHANNEL HEAT SINK FOR SPACE CRAFT THERMAL CONTROL Vance K. Hashimoto Department of Mechanical Engineering University of Hawai i at Mānoa Honolulu, HI 96822 ABSTRACT The increasing requirements
More informationAvailable online at ScienceDirect. Energy Procedia 91 (2016 ) 35 41
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 91 (216 ) 35 41 SHC 215, International Conference on Solar Heating and Cooling for Buildings and Industry Butane heat pipes for stagnation
More informationHomework Chapter2. Homework Chapter3
Homework Chapter2 2/1 A storage tank holds methane at 120 K, with a quality of 25 %, and it warms up by 5 C per hour due to a failure in the refrigeration system. How long time will it take before the
More informationPool boiling heat transfer enhancement on porous surface tube
Nuclear Science and Techniques 22 (2011) 122 128 Pool boiling heat transfer enhancement on porous surface tube LI Yong * YAN Changqi SUN Zhongning SUN Licheng College of Nuclear Science and Technology,
More informationPerformance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 Performance Comparisons Of A Unitary Split System Using Microchannel and
More informationAir-Cooled Thermosyphon for Press-Pack Stack of Semiconductors
Journal of Physics: Conference Series PAPER OPEN ACCESS Air-Cooled Thermosyphon for Press-Pack Stack of Semiconductors To cite this article: M. Habert and B. Agostini 2016 J. Phys.: Conf. Ser. 745 032110
More informationMeasurement of internal pressure and thermal performance in a closed-loop oscillating heat-pipe with check valves (CLOHP/CV)
Indian Journal of Pure & Applied Physics Vol. 52, August 2014, pp. 531-540 Measurement of internal pressure and thermal performance in a closed-loop oscillating heat-pipe with check valves (CLOHP/CV) S
More informationTHE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE
Proceedings of the Asian Conference on Thermal Sciences 2017, 1st ACTS March 26-30, 2017, Jeju Island, Korea ACTS-P00385 THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK
More informationCHECK VALVES INSTALLATION
CHECK VALVES 35 CHECK VALVES APPLICATIONS The check valves illustrated herein are designed for use with refrigerant fluids CFC, HCFC and HFC. Castel check valves can be used on any section of a refrigerating
More informationQuantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel
More informationEnhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance
More informationHeat pump supplemental heating system for motor vehicles
1 Heat pump supplemental heating system for motor vehicles D Antonijevic and R Heckt Visteon Automotive Systems, Visteon Deutschland GmbH, Kerpen, Germany Abstract: The paper deals with the importance
More informationSubscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid
Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance
More informationAnalysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance
Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance P Vamshi Krishna 1, Hemasunder Banka 2, S.Rama 3, Ch. Jeevan Reddy 4, G.Venkanna 5 1,2,3,4,5,
More informationExperimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental and Numerical Study on the Performance of R410A Liquid Recirculation
More informationInternational Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72
International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationDesign of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible
More informationMechanical Engineering Department Sheet (1)
Benha University Heat and Mass Transfer Faculty of Engineering at Shoubra 3 rd Year (Power) Mechanical Engineering Department Sheet (1) (1) What is heat exchanger? Mention with brief description and sketches
More informationScientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University
Scientific Principals and Analytical Model Charcoal Cooler Lisa Crofoot MECH 425, Queens University 1.0 Scientific Principles Evaporative cooling is based on the principle that water requires heat energy
More informationThe Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 The Development Of High Efficiency Air Conditioner With Two Compressors
More informationNoise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 004 Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow
More informationAN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS
AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore
More informationExperimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection
RESEARCH ARTICLE OPEN ACCESS Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection Tanuj Kumar Sahu 1, Vishal Gupta 2, Ajay Kumar Singh 3
More informationHot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump
Available online at www.sciencedirect.com Procedia Engineering 8 (2011) 165 170 2 nd International Science, Social-Science, Engineering and Energy Conference 2010: Engineering Science and Management Hot
More informationA Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant
International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article A Review
More informationEXPLORING POSSIBILITIES WITH THE DEVELOPMENT OF THE LOOP HEAT PIPE TECHNOLOGY. Roger R. Riehl
EXPLORING POSSIBILITIES WITH THE DEVELOPMENT OF THE LOOP HEAT PIPE TECHNOLOGY Roger R. Riehl National Institute for Space Research INPE Space Mechanics and Control Division-DMC Av dos Astronautas 1758,
More informationEffect of Inclination Angle on Performance Limit of a Closed-End Oscillating Heat Pipe
American J. of Engineering and Applied Sciences 1 (3): 174-180, 2008 ISSN 1941-7020 2008 Science Publications Effect of Inclination Angle on Performance Limit of a Closed-End Oscillating Heat Pipe. Hudakorn,
More informationICONE DRAFT Proceedings of the 16th International Conference on Nuclear Engineering ICONE16 May 11-15, 2008, Orlando, Florida, USA
DRAFT Proceedings of the 16th International Conference on Nuclear Engineering ICONE16 May 11-15, 2008, Orlando, Florida, USA ICONE16-48187 THERMAL CYCLE EVALUATION FOR FEEDWATER HEATER OUT OF SERVICE CONDITION
More informationEXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM
EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM 1 RONANKI SURESH, 2 Dr. K. KALYANI RADHA 1 M.Tech, Mechanical Engineering, JNTUA College of Engineering
More informationExperimental study on mass transfer comparison of two liquid desiccants aqueous solutions
International Conference on Renewable Energies and Power Quality (ICREPQ ) Cordoba (Spain), th to th April, 0 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 1-03 X, No., April 0 Experimental
More informationIn the name of God. Jami Institute of Jami - Mehdi Rasti
In the name of God 1 Heat Transfer Jami Institute of Technology Heat Exchangers part 2 Mehdi Rasti 2 The Counter-Flow Heat Exchanger In contrast to the parallel-flow exchanger, this configuration provides
More informationImproving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Improving Heating Performance of a MPS Heat Pump System With Consideration
More informationCOOLING SYSTEMS FOR CONTINOUS GALVANIZING LINE Miroslav Raudensky a, Milan Hnizdil a, Jaroslav Horsky a, FrédéricMarmonier b
COOLING SYSTEMS FOR CONTINOUS GALVANIZING LINE Miroslav Raudensky a, Milan Hnizdil a, Jaroslav Horsky a, FrédéricMarmonier b a Heat Transfer and Fluid Flow Laboratory, Brno University of Technology, Technicka
More informationDeveloping Two-Phase Flow Distribution in Horizontal Headers With Downward Minichannel-Branches
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering Developing Two-Phase Flow Distribution in Horizontal Headers With Downward Minichannel-Branches
More informationAnalysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant
Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET
More informationPerformance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for
More informationAmerican International Journal of Research in Science, Technology, Engineering & Mathematics
American International Journal of Research in Science, Technology, Engineering & Mathematics Available online at http://www.iasir.net ISSN (Print): 2328-3491, ISSN (Online): 2328-358, ISSN (CD-ROM): 2328-3629
More informationTranscritical CO2 Bottle Cooler Development
Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains
More informationExperimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant
Proceedings of the World Congress on Momentum, Heat and Mass Transfer (MHMT 16) Prague, Czech Republic April 4 5, 216 Paper No. ENFHT 111 DOI: 1.11159/enfht16.111 Experimental Investigation of a Multi
More informationLab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems
Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems OBJECTIVES Warning: though the experiment has educational objectives (to learn about boiling heat transfer, etc.), these should not
More informationA STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS
A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS V. BHOGESWARA RAO Research Scholar Email:pallivayala@gmail.com Dr. S. CHAKRADHAR GOUD Principal, Sri Sarada Institute of Science and Technology
More informationImproving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a
ISSN (e): 0 00 Vol, 0 Issue, 8 August 0 International Journal of Computational Engineering Research (IJCER) Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants
More informationHot Reservoir Stainless-Methanol Variable Conductance Heat Pipes for Constant Evaporator Temperature in Varying Ambient Conditions
Joint 18th IHPC and 12th IHPS, Jeju, Korea, June 12-16, 2016 Hot Reservoir Stainless-Methanol Variable Conductance Heat Pipes for Constant Evaporator Temperature in Varying Ambient Conditions Jens Weyant
More informationME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3
ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes
More informationDae-Hyun Jin. 8/2018-Present Assistant Professor of Mechanical Engineering, Taylor University, USA
Dae-Hyun Jin Education 9/2003-8/2006 University of Maryland at College Park, USA PhD, Department of Mechanical Engineering Center for Environmental Energy Engineering (CEEE) Dissertation Topic: Investigation
More informationEfficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station
Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station Normuminov J.A. Assistant, Dean of Heat Power Engineering, Tashkent State Technical University,
More informationExperimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential
More informationNatural Convection Heat Transfer Augmentation from Heat Sinks using Perforated Fins: A Review
(JMSME) Print ISSN : 2339-9095; Online ISSN : 2393-9109; Volume 2, Number 6; April June, 2015 pp 80 84 Krishi Sanskriti Publications http://www.krishisanskriti.org/jmsme.html Natural Convection Heat Transfer
More informationAn Experimental Study on Evacuated Tube Solar Collector for Heating of Air in India Avadhesh Yadav, V.K. Bajpai
Vol:5, No:7, 211 An Experimental Study on Evacuated Tube Solar Collector for Heating of Air in India Avadhesh Yadav, V.K. Bajpai International Science Index, Mechanical and Mechatronics Engineering Vol:5,
More informationA study of Transient Performance of A Cascade Heat Pump System
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 79 (2015 ) 131 136 2015 International Conference on Alternative Energy in Developing Countries and Emerging Economies A study of
More information