BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

Size: px
Start display at page:

Download "BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:"

Transcription

1 INSTALLATION, OPERATION AND MAINTENANCE MANUAL BHW MEDIUM STATIC PRESSURE DUCTABLE TYPE Models: Cooling capacities from 3,1 to 25 KW Heating capacities from 4,5 to 55,5 KW

2 Thank you for trust in Hitecsa Product. From our company we are offering to the market, for more than 30 years, an extended range of specialized units for air conditioning and cooling installations. Our approach is based in efficiency, flexibility, manageability and practical solutions. It has built a hallmark of our product catalogue. The versatility of our factory allows us to contribute solutions almost customitzables in each project, searching a solution for every problem that arises in design and implementation of air conditioning installations. From Hiplus Aire Acondicionado s team, once more thank you very much.

3 BHW SAFETY PRECAUTIONS... 4 OPERATING LIMITS... 4 EQUIPMENT RECEPTION... 4 RIGGING... 4 INSTALLATION LOCATION... 4 SERVICE AREA... 5 APPROXIMATE WEIGHT DISTRIBUTION (KG)... 5 UNIT SETTLEMENT... 6 ELECTRICAL CONNECTIONS... 6 WATER DRAIN... 6 AIR DUCTWORK... 6 INDOOR FAN ADJUSTMENT... 7 ELECTRIC CONNECTION FOR UNITS BHW WITH 3 SPEED... 7 DIMENSIONS... 8 BHW 174, 205, 358, BHW BHW 720, TECHNICAL DATA OPTIONALS FANS WITH EC MOTOR 3 SPEEDS VERSION MAINTENANCE BEFORE START UP START UP OPERATING INSTRUCTION FOR EC FANS SAFETY INFORMATION, ALL UNITS OPERATING CONDITIONS ECM082 MOTOR GENTEQ MOTOR... 15

4 SAFETY PRECAUTIONS Installation and maintenance of air conditioning equipment can be dangerous because system is under pressure, has high temperature of some elements and includes electrical components. Only qualified and trained service personnel should install, start up and make maintenance of the air conditioning equipment. During every visit follow the recommendations from the Installation Operation Maintenance manual, what is shown on unit s stickers and take general legal safety precautions. Follow strictly all safety codes. Use safety glasses, work gloves and some other work safety accessory. ATTENTION! Before staring installation, service or maintenance turn off system main power switch to avoid electrical shock. When repairing the unit use only original spare parts and install them properly in the same place where have been located the old parts. Do not install the unit in explosive atmosphere. OPERATING LIMITS COOLING CYCLE TEMPERATURE Indoor air inlet 27ºC, TS 19ºC, TH Water inlet 7ºC Water outlet 12ºC EQUIPMENT RECEPTION 1. Inspect equipment received for damage or missing elements. If units are damaged or shipment is incomplete, file the claim with the transport company, immediately. Max. term 48h. 2. Check if unit nameplate voltage is correct and agrees with local power supply. RIGGING 1. Before moving the unit, be sure that all unit panels are well fixed. 2. Raise and set down the equipment carefully. 3. Always transport the unit to the installation place in its original packaging. INSTALLATION LOCATION 1. Check if construction is able to support the unit s weight. 2. Check if there is enough service space around the unit. 3. Choose a place free of dust and foreign matter. 4. If necessary, install vibration absorbers through the system to avoid noise transmission.

5 SERVICE AREA APPROXIMATE WEIGHT DISTRIBUTION (Kg). BHW WEIGTH

6 UNIT SETTLEMENT Be sure unit is correctly leveled. Be sure that after settlement of the unit indoor drain is working properly. ELECTRICAL CONNECTIONS ATTENTION! Before starting any type of operations put in position off main power switch. The electrical power supply to the unit should agree with data on the nameplate. Unit star-up at incorrect voltage and resulted from it damages are not covered by Hitecsa guarantee. When making electrical connections always use the unit wiring diagram. Unit current supply should be within +-5% of Volts and Amperes indicated on the unit nameplate. Do not operate at any different current from that is shown on the unit s nameplate. The installer has to install the line protection elements according to the local laws. The interconnecting wires have to be in the protection tube or inside the groove channel. WATER DRAIN The indoor drain (of condensate water) has connection 3/4 MPT. Condensate evacuation line diameter should be equal or larger than unit drain connection depending on the lie length and general building configuration. The condensate line should be pitched a minimum 2% for proper water evacuation. When drain line is exposed to air temperatures below 0 grades is necessary to provide thermal insulation or electrical heating wire to avoid water freezing and tube damage. It is convenient to install the trap with proper dimensions. AIR DUCTWORK - Air ducts dimensions are d in function of the air flow and the available external static pressure. - A qualified technician should make the air duct design. - Use air duct of nonflammable material, which in case of fire, will not emit toxic gases. It is advisable to use metal sheet ducts with insulation. - Use flexible elements between the air duct and the unit, to avoid vibrations and noise transmissions.

7 INDOOR FAN ADJUSTMENT Verify that the consumption of the fan doesn t exceed the maximum allowed. ELECTRIC CONNECTION FOR UNITS BHW WITH 3 SPEED N L Neutral Phase 0 Neutral 1 High 2 Medium 3 Low

8 DIMENSIONS BHW 174, 205, 358, 410 CONSTRUCTIVE DETAILS 1. Plenum tubular mouthpiece 2. Plenum impulsión 3. Coil 4. Turbine 5. Motor turbine 6. Power supply input 7. Water outlet (connection 3/4 ) 8. Water inlet (connection 3/4 ) 9. Drainage 3/4 male 10. Air filter MODEL A B C D E F G H I J K L 174 mm mm mm mm

9 BHW 515 CONSTRUCTIVE DETAILS 1. Plenum impulsión 2. Turbine 3. Motor turbine 4. Water outlet (connection 1 ) 5. Water coil 6. Water inlet (connection 1 ) 7. Electrical coil 8. Air filter 9. Drainage 3/4 male BHW 720, 724 CONSTRUCTIVE DETAILS 1. Plenum impulsión 2. Motors turbines 3. Turbines 4. Water outlet (connection 1 1/4 ) 5. Water coil 6. Water inlet (connection 1 1/4 ) 7. Electrical coil 8. Air filter 9. Drainage 3/4 male

10 TECHNICAL DATA BHW CAPACITIES Speed I KW 3,1 4,4 6,0 7,9 12,2 Cooling capacity (1) Speed II KW 4,1 5,0 5,9 9,1 13,9 20,2 25,0 Speed III KW 4,5 5,3 8,4 10,8 15,3 Heating capacity (2) Speed I KW 4,5 6,4 8,6 11,1 16,1 Speed II KW 5,8 7,1 9,7 12,6 18,2 26,5 32,7 Speed III KW 6,3 7,5 11,9 14,9 19,7 Heating capacity (3) Speed I KW 7,6 10,8 14,6 18,8 27,2 Speed II KW 9,8 12,1 16,5 21,4 30,8 44,8 55,5 Speed III KW 10,7 12,7 20,1 25,2 33,5 VENTILATION Fan model 146/ / / / /236 2 X 9/9DD 2 X 9/9DD Speed I m3/h Cold air flow Speed II m3/h Speed III m3/h Speed I m3/h Hot air flow Speed II m3/h Speed III m3/h Available static pressure Speed I Pa Speed II Pa Speed III Pa Motor fan power KW 0,18 0,18 0,25 0,25 0,55 0,25 0,36 HEAT EXCHANGER Water connections Ø ( ) 3/4 3/4 3/4 3/ /4 1 1/4 Cooling and heating water flow Speed I m3/h 0,53 0,76 1,03 1,36 2,09 Speed II m3/h 0,69 0,85 1,18 1,56 2,36 Speed m3/h 0,76 0,90 1,44 1,85 2,57 III ELECTRICAL SPECIFICATIONS 3,37 4,19 Voltage V / f / Hz 230 / III / 50 Nominal power input KW 0,20 0,26 0,36 0,56 0,60 0,81 1,6 Nominal current input A 1 0,5 1,75 2,5 2,75 3,9 7,4 DIMENSIONS Width mm Length mm Height mm Weight Kg (1) Cooling capacity for water temperature of 7ºC. (2) Cooling capacity for water temperature of 50ºC and indoor temperature of 20ºC. (3) Cooling capacity for water temperature of 70ºC and indoor temperature of 20ºC.

11 OPTIONALS FANS WITH EC MOTOR 3 SPEEDS VERSION BHW CAPACITIES Speed I KW 3,1 7,9 12,2 Cooling capacity (1) Speed II KW 4,1 9,1 13,9 Speed III KW 4,5 10,8 15,3 Speed I KW 4,5 11,1 16,1 Heating capacity (2) Speed II KW 5,8 12,6 18,2 Speed III KW 6,3 14,9 19,7 Speed I KW 7,6 18,8 27,2 Heating capacity (3) Speed II KW 9,8 21,4 30,8 Speed III KW 10,7 25,2 33,5 VENTILATION Fan model EC082 EC 145 EC Speed I RPM Turning speed Speed II RPM Speed III RPM Speed I m3/h Air flow Speed II m3/h Speed III m3/h Available static pressure Speed I Pa Speed II Pa Speed III Pa Motor fan power KW 0,08 0,25 0,25 HEAT EXCHANGER Type Water coil with copper tubes and aluminium fins. Cooling and heating water flow Speed I m3/h 0,53 1,36 2,09 Speed II m3/h 0,69 1,56 2,36 Speed III m3/h 0,76 1,85 2,57 Water connections Ø( ) 3/4 3/4 1

12 BHW ELECTRICAL SPECIFICATIONS Voltage V / f / Hz 230 / I / 50 Speed I KW 0,06 0,13 0,14 Nominal power input Speed II KW 0,06 0,18 0,22 Speed III KW 0,06 0,21 0,32 Speed I A 0,44 0,80 0,98 Nominal current input Speed II A 0,44 0,94 1,49 Speed III A 0,45 1,19 2,13 SOUND LEVEL (4) Speed I db(a) 63 68,5 69,8 Sound power Speed II db(a) 64 69,8 71,8 Speed III db(a) 64, ,5 Speed I db(a) 43,98 48,48 49,78 Sound presure (a 2m) Speed II db(a) 43,98 49,78 51,78 Speed III db(a) 44,78 50,98 54,48 DIMENSIONS Width mm Length mm Height mm Weight Kg (1) Cooling capacity for water temperature of 7ºC. (2) Cooling capacity for water temperature of 50ºC and indoor temperature of 20ºC. (3) Cooling capacity for water temperature of 70ºC and indoor temperature of 20ºC. (4) Sound pressure level with supply and return jacks free discharge, measured 2 meters away, in free field. MAINTENANCE ATTENTION! Before performing service or maintenance operations, turn off the main power switch to avoid personal injury and put lock on power switch to avoid that any person not connected with the maintenance technical can switch on the electrical supply. It is advisable to make maintenance operation periodically according to the use and operation of the installation, as well as, on every change of the season. - Coils: At least once a year, clean condenser coils with water and detergent and dry later with air at a pressure of 600kPa. Never clean the coil with a wire brush. - Fans and motors: Verify the correct rotation of the fan to warn problems with the bearings. - Drainage system: Check if openings in the unit base for rain and defrost water evacuation is not blocked. - Water circuit: Check for leakage, noise and various system elements vibrations. Take temperature and pressure readings and record it on the maintenance form. - Electrical circuit: Make sure that all electrical cables and other elements are properly tightened. Take electricity consumption of each phase of every fan. Verify the starting current. Check the operations of all relays, contactor, etc. - Air filters: Clean air filters after 4 hours of system operation and then periodically according to the maintenance plan. Filters can be cleaned by immersion in warm water with soap, lates washed in clean water and dry.

13 BEFORE START UP - Check if all wires are well tightened. - Check if all panels are firmly secured with screws. - Verify if unit is installed on level. - Verify if there is enough space for service and maintenance. - Check if drain is not blocked. - Verify if air filters are clean and correctly mounted. - Check all grilles, air diffusers, air ducts and flexible connections. - Be sure that the electrical power source agrees with the unit nameplate rating. - Check that every fan rotates properly. START UP - Start up has to be performed by a qualified service person. - Make start-up check list and use similar check up for service and maintenance. Record chilled water inlet and outlet temperatures and pressures, outdoor air temperature, volts and amps of each fan. - Should remind that after 4 hours of system operation is necessary to clean air filters. - Observe at least, 3 cooling cycle operations. OPERATING INSTRUCTION FOR EC FANS SAFETY INFORMATION, ALL UNITS - This unit is solely intended as a built-in component as per EN and should not be operated otherwise. Sufficient protection against accidental contact according to machinery has to be safeguarded, especially for the rotating parts. Be careful in case fan-deck unit switch on. - The fans are only intended for moving air. - The fans are only to be operated within the ranges specified on the motor nameplate or in the technical specification released by Technical Dept. - The fans are supplied with external control board, in accordance to EMC guideline: EN ; EN ; EN ;EN ; EN ; EN ; EN ; EN ; EN The unit complies with the applicable standard and regulation and meet the requirements of the Low Voltage Directive 73/23/EEC and ECM guideline. - The unit meets the following standards: - EN 60529: Degree of Protection provided by enclosure ( IP code ) - EN /2+ EN /3: Electromagnetic Compatibility - EN : Safety of household and similar appliances ( see the Declaration of conformity ) - Do not open the control board if power supply is on. - Don t touch any parts if unit is running.

14 OPERATING CONDITIONS UNITS Motor model ECM082 GENTEQ Voltage supply 230V±10% 230V±15% Frequency Duty cycle Max. operating ambient temperature Input signal Output signal 50/60Hz S1, continuous operation. Intermittent duty cycle is permitted 1-10 Vdc, 0,9 Vdc motor stops 50ºC 10 Vdc 1-10 Vdc Speed rpm rpm Life expectancy hours hours Overload protection. Temperature sensor and internal fuse Locked rotor protection, via software. ECM082 MOTOR LOCKED ROTOR PROTECTION 40mm STACK ECM motor Vdc= 10V, 230V, 50Hz Test in free-air on fan deck unit type 2x146x226mm, ABS material - 15 cycles of 7 each for a total time of 100 after that motor stop, electronic control board in stand-by at minimum consumption I=45mA. re-start the motor switch off and switch on power supply. - Cycles counter reset after 30 of operation at nominal rpm, after this time in case of locked rotor control board return to count 15 cycles, before this time control board maintains in memory the cycles till now got. - In all conditions, after the motor stopped definitely due to rotor locked, to re-start occurs switch off, wait for some second, about 7, and switch on again. OVERLOAD PROTECTION Temperature sensor: via hardware through NTC In case the power stage temperature exceeds its upper limit due to overload (higher current), NTC modifies its resistance leading the motor control which it reduces the speed and power in order to return within its limit. If this does not happen then the control board stops the motor and fault signal appears. FAULTS - Motor Gate kill fault: in case of Mosfet s short circuit, they get open to avoid damage on dc bus due to critical overvoltage fault. Motor stops definitively - Dc bus overvoltage. If the voltage is greater than 270V the motor is stopped. It is restarted if the voltage goes under 270V. - Dc bus under voltage fault. If the voltage goes under 70V the board stops the motor and restarts it only when the voltage goes over 144V. - Motor over speed fault. If the speed goes over 2000 rpm the motor is stopped and restarted.

15 - Motor zero speed fault. If the motor is stopped but it should be running it will be restarted. - Start fail fault. The start procedure is repeated. - Temperature sensor fault: In case of long terms overload, the control board stops the motor. - Communication fault: If a problem is detected in the communication between the Master processor and the motor processor, the motor processor will be reseted and restarted. GENTEQ MOTOR OPERATING SPEED LIMIT Operating speed limits: due to the large centrifugal forces present in the motor during high-speed operation, speed limits on present production are as follows: -1/3 hp may operate at speeds up to 1900 rpm. - All others may operate at speed up to 1500 rpm. Operation above these limits may result in permanent damage to the motor. LOCKED ROTOR PROTECTION Protection of ECM Motors: ECM motors are referred to as Impedance Protected simply because there are no thermal protectors mounted on the windings to protect motors but the protection is done by the electronic control. There is no separate class in Safety agency standards for protection using electronic control. Given the two classes namely Thermally Protected and Impedance Protected, impedance protected comes closer to electronic protection employed in ECM, therefore ECMs are referred as Impedance Protected. by safety agencies. How does the Electronic Protection work: At operating condition there are two means of limiting current into the motor. The first one called peak current regulate actually regulates the current supplied to motor by means of a resistor in the electronic control which limits current to a value that is sufficient to deliver full output. The motor thermal characteristics are such that at this full output the temperature of the windings does not exceed insulation rating for the motor (for example 130 Deg C for class B insulation system) or thermal rating of the electronic components. The second means of protection is done by current trip. This is also set by another resistor in the electronic control. When the current exceeds a pred value the electronic control automatically trips or stops energizing motor with current. At Locked rotor condition, the electronic control senses no rotation condition and shuts down. It continues to try starting motor with small amount of current but fails to do so when rotor is truly locked. It can continue trying to start the motor indefinitely but amount of current is so small that it does not result in any heating of motor windings or electronic components.

16 HIPLUS AIRE ACONDICIONADO S.L. Masia rrents, 2 Tel Fax Vilanova i la Geltrú Barcelona, España We reserve the right to make modifications without prior notice. This document is a translation from the original document.

ROOF TOP TYPE UNITS CENTRIFUGAL FANS ENGINEERING DATA MANUAL MODELS Rev. 100

ROOF TOP TYPE UNITS CENTRIFUGAL FANS ENGINEERING DATA MANUAL MODELS Rev. 100 RCCA Cooling only RCCBA Heat pump ENGINEERING DATA MANUAL MODELS 1402 1602 2002 2402 3002 04.14 207402 Rev. 100 Thank you for trust in HITECSA Product. From our company we are offering to the market, for

More information

EHW KH PF HIGH EFFICIENTY AIR CONDITONING UNITS TECHNICAL CATALOGUE

EHW KH PF HIGH EFFICIENTY AIR CONDITONING UNITS TECHNICAL CATALOGUE TECHNICAL CATALOGUE EHW KH PF HIGH EFFICIENTY AIR CONDITONING Models: 518 725 830 1036 1042 1657 Cooling Capacities: 18, 6 to 54, 4 KW Heating Capacities: 24, 1 to 71 KW 01.16 Ref. 207520 Rev. 101 INDEX

More information

CCHA / ECHA Cooling Only CCHBA / ECHBA Heat Pump

CCHA / ECHA Cooling Only CCHBA / ECHBA Heat Pump CCHA / ECHA Cooling Only CCHBA / ECHBA Heat Pump SPLIT HORIZONTAL UNITS AIR-AIR 1 CONTENTS INTRODUCTION... 3 SAFETY PRECAUTIONS... 4 RECEPTION... 5 LOCATION INSTALLATION... 8 START UP... 10 TECHNICAL DATA...

More information

TECHNICAL CATALOGUE SELF-CONTAINED VERTICAL UNITS AIR / AIR DC INVERTER

TECHNICAL CATALOGUE SELF-CONTAINED VERTICAL UNITS AIR / AIR DC INVERTER TECHNICAL CATALOGUE SELF-CONTAINED VERTICAL UNITS AIR / AIR DC INVERTER Models : 601, 741, 901 ACVIA - Cooling only (Compact) CCVIA / ECVIA - Cooling only (Split) ACVIBA - Heat Pump (Compact) CCVIBA /

More information

SELF CONTAINED HORIZONTAL AIR CONDITIONERS WATER COOLED CONDENSER (COAXIAL REFRIGERANT-WATER HEAT EXCHANGER)

SELF CONTAINED HORIZONTAL AIR CONDITIONERS WATER COOLED CONDENSER (COAXIAL REFRIGERANT-WATER HEAT EXCHANGER) SELF CONTAINED HORIZONTAL AIR CONDITIONERS WATER COOLED CONDENSER (COAXIAL REFRIGERANT-WATER HEAT EXCHANGER) SERIES: WCHZ MODELS: 201, 251, 271, 351, 401, 501, 701, 721, 751 COOLING CAPACITIES OF: 6,4

More information

ECV SP GUE ALO CAT ICAL TECHN

ECV SP GUE ALO CAT ICAL TECHN TECHNICAL CATALOGUE ECV SP TAILOR MADE FOR UNITS FITTED WITH VRF SYSTEMS Models: 1001 1502 1602 2003 2303 10.16 Ref. 207609 Rev.105 CONTENT INTRODUCTION... 3 GENERAL DESCRIPTION... 3 CABINET... 3 HEAT

More information

CATALOGUES SUMMARY - WCHBZ Pages WCHZ Pages 19-42

CATALOGUES SUMMARY - WCHBZ Pages WCHZ Pages 19-42 SELF CONTAINED HORIZONTAL UNITS WATER COOLED CONDENSER (COAXIAL REFRIGERANT-WATER HEAT EXCHANGER ) HEAT PUMP. WCHBZ COOLING ONLY. WCHZ SERIES: WCHBZ - Heat Pump MODELS: 201, 251, 271, 351, 401, 501 COOLING

More information

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ SERIES: EWCBZ - Heat pump MODELS: 70, 80, 00, 0, 60, 00, 40, 00, 50 COOLING CAPACITIES from 5,9 kw to 78,5

More information

EQEF TECHNICAL CATALOGUE AIR COOLED WATER CHILLERS AXIAL FANS WITH FREE-COOLING SYSTEM

EQEF TECHNICAL CATALOGUE AIR COOLED WATER CHILLERS AXIAL FANS WITH FREE-COOLING SYSTEM TECHNICAL CATALOGUE EQEF Water Chillers with Free Cooling System Models:60.1 60.2 70.1 70.2 90.1 90.2 120.1 120.2 135.1 150.1 190.2 200.1 200.2 240.2 270.2 300.2 Cooling capacities: 69,7 to 331 KW 02.16

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW TECHNICAL CATALOGUE EQSL Air Cooled Water Chillers Models: 300 V2 F06 1310 V2 F16 Cooling capacity: 299 to 1310 KW 02.16 ref. 207598 Rev.100 Thank you for trusting in Hitecsa Products. Our company has

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

Original instructions. Operation Manual & Cautions

Original instructions. Operation Manual & Cautions Original instructions Operation Manual & Cautions Thank you for purchasing the Mistresa from Showa Denki. This manual explains the specifications for the [Mistresa units from CRN Series]. Please read the

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

Inverter Swimming Pool Heat Pump

Inverter Swimming Pool Heat Pump P Inverter Swimming Pool Heat Pump Content I. Application... 2 II. Features... 2 III. Technical Parameter... 3 IV. Dimension... 4 V. Installation instruction... 5 VI. Operation instruction... 9 VII. Testing...

More information

General safety precautions English

General safety precautions English English 1 1 Units are marked with the following symbol: 1.1 About the documentation The original documentation is written in English. All other languages are translations. The precautions described in

More information

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 Congratulations on your purchase of a LEO Centrifugal Pump It is important that you read, fully understand and observe the following

More information

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection Ground Fault Protection GADD MKIII Ground Fault Indication System Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR

More information

General safety precautions English

General safety precautions English General safety precautions General safety precautions English 1 General safety precautions 1 General safety precautions Units are marked with the following symbol: 1.1 About the documentation The original

More information

100 FLUEBOOST

100 FLUEBOOST 100 FLUEBOOST f l u e b o o s t 1 0 0 The flueboost is a box shaped centrifugal fan unit with in line spigots for the flue connection, a pressure switch to ensure safe operation, all within a compact package.

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

General safety precautions English

General safety precautions English English 1 1 1.1 About the documentation The original documentation is written in English. All other languages are translations. The precautions described in this document cover very important topics, follow

More information

B SERIES ELECTRIC FURNACE

B SERIES ELECTRIC FURNACE MISSISSAUGA, ONTARIO L5T 1H9 TEL.: 905-670-2500 FAX: 905-795-8311 CUSTOMER SERVICE TEL.: 1-888-882-7626 B SERIES ELECTRIC FURNACE! WARNING 1. The user MUST contact a specialized contractor when a failure

More information

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS Contents Page User instructions 3-5 General 3 Fan installation 3-4 Maintenance 3 Electrical installation 5 Troubleshooting 5 Technical description 6-8 General

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - USER GUIDE DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - II CONTENTS 1. SYMBOLS AND WARNINGS... 5 2. GENERAL INFORMATION... 6 3. WARNINGS... 7 4. GENERAL DESCRIPTION... 8 5. INSTALLATION...

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

Industrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw

Industrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw Industrial Solid State Contactor TE10S Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw Partial load failure (PLF) detection option User Manual Copyright Eurotherm Automation

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS 036-21096-001 (0101) SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility. The

More information

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING USER S MANUAL VCU/ Series CENTRIFUGAL FAN IN SCROLL CASING 2 CONTENTS Introduction Use Delivery set Designation key Technical data Safety requirements Design and operating logic Mounting and set-up Connection

More information

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection Ground Fault Protection GADP Ground Fault Indication System Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR 737-4787

More information

50VZ/PZ 38VZ/PZ+40PZ. Vertical Air-Cooled Split-System Cooling Units and Heat Pumps. Installation, operation and maintenance instructions

50VZ/PZ 38VZ/PZ+40PZ. Vertical Air-Cooled Split-System Cooling Units and Heat Pumps. Installation, operation and maintenance instructions 50VZ/PZ 38VZ/PZ+40PZ Vertical Air-Cooled Split-System Cooling Units and Heat Pumps Installation, operation and maintenance instructions 1 CONTENTS START-UP CHECKLIST... 3 PHYSICAL DATA... 4 ELECTRICAL

More information

THERMOSTAT i-basic 3 USER MANUAL Rev.100

THERMOSTAT i-basic 3 USER MANUAL Rev.100 USER MANUAL Thank you for trusting the Hitecsa Products. Our company has been offering the market an extended range of specialized units for air conditioning and cooling installations for over 35 years.

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

General safety precautions English

General safety precautions English English 1 1 1.1 About the documentation The original documentation is written in English. All other languages are translations. The precautions described in this document cover very important topics, follow

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,

More information

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort Application guide FLATAIR - FLCK/FLHK Providing indoor climate comfort MSL60E-0701 12-2006 Congratulations you have made a wise choice and we feel sure that it will meet your expectation INDEX CONTENTS

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

MANUAL INSTALLATION. Fan Column. v200 Issue Date: 01/18/ Price Industries Limited. All rights reserved.

MANUAL INSTALLATION. Fan Column. v200 Issue Date: 01/18/ Price Industries Limited. All rights reserved. MANUAL INSTALLATION Fan Column v200 Issue Date: 01/18/17 2017 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General Safety Information...1 Safety Notices...1 Unit Description...2

More information

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307 DESCRIPTION Technical Guide CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) This 20 ton evaporator blower is designed with two distinct modules to provide maximum application

More information

38XTZ ABZ 007, 008, 016, 020 and ALZ 011 and 014. Split system air-cooled air conditioners. Models 38XTZ 016 to 024 MASTER LINK I

38XTZ ABZ 007, 008, 016, 020 and ALZ 011 and 014. Split system air-cooled air conditioners. Models 38XTZ 016 to 024 MASTER LINK I 38XTZ 007-024 40ABZ 007, 008, 016, 020 and 024 40ALZ 011 and 014 Split system -cooled conditioners MASTER LINK I Models 38XTZ 016 to 024 40ABZ/ALZ Carier is participating in the Eurovent Certification

More information

VADA - V80-H PRODUCT OVERVIEW CONSTRUCTION USAGE LIMITATIONS MOTOR WARRANTY

VADA - V80-H PRODUCT OVERVIEW CONSTRUCTION USAGE LIMITATIONS MOTOR WARRANTY PRODUCT OVERVIEW The VADA horizontal multistage centrifugal pumps combine the functional benefits of centrifugal pumps and the practical benefits of self priming pumps. They warrant high hydraulic and

More information

V80-H Multistage Pump Instruction Manual

V80-H Multistage Pump Instruction Manual V80-H Multistage Pump Instruction Manual PRODUCT OVERVIEW The VADA horizontal multistage centrifugal pumps combine the functional benefits of centrifugal pumps and the practical benefits of self priming

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

HYDRONIC SYSTEMS WHY CHOOSING BETWEEN ENERGY EFFICIENCY AND ROBUSTNESS?

HYDRONIC SYSTEMS WHY CHOOSING BETWEEN ENERGY EFFICIENCY AND ROBUSTNESS? HYDRONIC SYSTEMS WHY CHOOSING BETWEEN ENERGY EFFICIENCY AND ROBUSTNESS? New condensed air water chillers using scroll compressors and capacities from 21 to 217 kw Models 801-1501 Models 1601-6002 Models

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

INSTALLATION FB T: +44 (0) F: +44 (0) E: W:

INSTALLATION FB T: +44 (0) F: +44 (0) E: W: INSTALLATION FB 1 Contents User instructions General Fan installation Maintenance Electrical installation Troubleshooting Technical description General Classification Technical specification Manufacturer

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance DUCTABLE WATER UNIT FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

FLUEBOOST. flueboost 350 gas fire model

FLUEBOOST. flueboost 350 gas fire model 350 FLUEBOOST flueboost 350 gas fire model The flueboost is a box shaped unit with in line spigots for the flue connection, a pressure switch to ensure safe operation and plug-in electrical fittings for

More information

EQUH PF PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR INDOOR INSTALLATION

EQUH PF PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR INDOOR INSTALLATION TECHNICAL CATALOGE EQUH PF PACKAGED HEAT PUMP AIR/ WATER LIQUID CHILLER FOR INDOOR INSTALLATION Cooling capacity 19,1 to 225 kw Heating capacity 23,7 to 324 kw Thank you for trust in Hitecsa Product. From

More information

XB-EFA-8L-BK & XB-EFA-8R-BK

XB-EFA-8L-BK & XB-EFA-8R-BK Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU The information contained in this document provides details of installation, operation

More information

SELF-PRIMING JET PUMPS

SELF-PRIMING JET PUMPS SS Anti-Rust SS Shaft Copper & Cold-rolled SELF-PRIMING JET PUMPS CONTENTS 1. Applications.... Model Description.... Technical Data... 4. Implementation Standards... 5. Safety Precautions... 6. Product

More information

Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE

Vertical Concealed Fan Coil. FCVC Series MANUAL INSTALLATION, OPERATION, & MAINTENANCE MANUAL INSTALLATION, OPERATION, & MAINTENANCE Vertical Concealed Fan Coil FCVC Series v100 Issue Date: 12/21/15 2015 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Safety

More information

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS 550.23-TG5Y (893) CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L2EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility.

More information

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS TSEK VENCO Havalandırma ve Makina San.ve Tic. A.Ş. 2004. Cad. No:5 45400 OSB Turgutlu MANISA / TURKİYE Tel: +90 (236) 332

More information

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS TC SERIES OPTIONS TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15,, 5 AIR COOLED PACKAGED WATER CHILLERS CONTENTS EQUIPMENT AND COMPONENT DETAILS PERFORMANCE AND TECHNICAL DATA SCHEMATIC FLOW & SYSTEM

More information

Duct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater.

Duct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater. Duct Heaters Synheat duct heaters come in various sizes and dimensions to fit any compartment. There are three types of duct heaters available: open coil, tubular element or finned tubular heating elements

More information

TQ Series. Electronic Control Pump Instruction Manual. 50Hz. ISO 9001 Certified Walrus Pump Co., Ltd.

TQ Series. Electronic Control Pump Instruction Manual. 50Hz. ISO 9001 Certified Walrus Pump Co., Ltd. TQ Series Electronic Control Pump Instruction Manual 50Hz ISO 9001 Certified Walrus Pump Co., Ltd. EC Declaration of Conformity Manufacturer: Walrus Pump Co., Ltd. Address: No. 83-14, Dapiantou, Sanjhih

More information

CONDENSING UNITS AIR COOLED CONDENSER. COOLING ONLY

CONDENSING UNITS AIR COOLED CONDENSER. COOLING ONLY CONDENSING UNITS. AIR COOLED CONDENSER. CONDENSING UNITS AIR COOLED CONDENSER. COOLING ONLY SERIES: DXCZ MODELS: 171, 201, 221, 251, 271, 351 371, 401, 451, 501, 701 and 721 COOLING CAPACITIES OF: 4,7

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

38LB/38LF AIR COOLED CONDENSING UNIT

38LB/38LF AIR COOLED CONDENSING UNIT WORLD LEADER IN AIR CONDITIONING AND HEATING TECHNOLOGY INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38LB/38LF AIR COOLED CONDENSING UNIT CONTENTS PAGE PHYSICAL DATA 2 PHYSICAL DATA 2 DIMENSION DATA

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

SAFETY AND OPERATING MANUAL. Original Instructions 5.0

SAFETY AND OPERATING MANUAL. Original Instructions 5.0 SAFETY AND OPERATING MANUAL Original Instructions 5.0 Read all safety warnings and all instructions before use. Failure to follow the warnings and instructions may result in electric shock, fire and/or

More information

50AZ/UZ Packaged Rooftop Cooling Only Units and Heat Pumps

50AZ/UZ Packaged Rooftop Cooling Only Units and Heat Pumps 50AZ/UZ Packaged Rooftop Cooling Only Units and Heat Pumps Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. Installation,

More information

FX5 Series Explosion-Proof Electric Air Heaters

FX5 Series Explosion-Proof Electric Air Heaters FX5 Series Explosion-Proof Electric Air Heaters Ruffneck FX5 heaters are C UL US certified for use in hazardous locations. They are designed for the harshest environments such as: dry indoor industrial

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RFEC/U/2017-1 (EN) (valid since 18.08.2017) ROOF FANS RF/EC...-... / RFV/EC...-... Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the

More information

ELECTRIC FIRE PUMP CONTROLLER

ELECTRIC FIRE PUMP CONTROLLER ELECTRIC FIRE PUMP CONTROLLER INSTRUCTION MANUAL CONTENTS 1. INTRODUCTION 1.1 Safety 1.2 Warranty 1.3 Safety Precautions 1.4 Product Overview 1.5 AS2941-2008 Requirements 2. FEATURES 3. FUNCTIONS AND OPERATIONS

More information

MOSAIC OCTOPLUS. EWCIBA - Models: 16-i 20-i 25-i. Installation, Operation & Maintenance Manual HORIZONTAL INVERTER MULTIZONE CLIMATIZATION SYSTEM

MOSAIC OCTOPLUS. EWCIBA - Models: 16-i 20-i 25-i. Installation, Operation & Maintenance Manual HORIZONTAL INVERTER MULTIZONE CLIMATIZATION SYSTEM MOSAIC OCTOPLUS HORIZONTAL INVERTER MULTIZONE CLIMATIZATION SYSTEM EWCIBA - Models: 16-i 20-i 25-i Cooling Capacities: from 15.8 kw to 24.3 kw Heating Capacities: from 18.1 kw to 27.9 kw Installation,

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL CENTRIFUGAL FAN IN SCROLL CASING Helix S-Vent EN OPERATION MANUAL Helix / S-Vent www.blaubergventilatoren.de CONTENTS CONTENTS 3 Introduction 3 Use 3 Delivery set 4 Technical data 10 Safety requirements

More information

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3) www.dometic.com Freightliner Refrigerator Troubleshooting Guide For Before initiating troubleshooting, the following equipment is recommended: Multimeter, 20 gauge (min) wires to use as jumpers, and 12Vdc

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT:. TRIAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.102. 0.8180.611.02 09/2012 IMPORTANT! Please read before installation This air conditioning

More information

CAUTION - READ THESE INSTRUCTIONS BEFORE USING THE MACHINE

CAUTION - READ THESE INSTRUCTIONS BEFORE USING THE MACHINE User instructions Model X46 Escalator and Travelator cleaner CAUTION - READ THESE INSTRUCTIONS BEFORE USING THE MACHINE 03-7845-0000 Iss.1 07/04 Fig 1 Fig 2 2 Contents Page 1 Product information... 4 1.1

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual 238 Series Industrial/Commercial Electric Unit Heater Owner s Manual This manual covers installation, operation and maintenance. Read carefully before attempting to install, operate or service the 238

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

> ENGLISH VERSION. Instructions HERU 50 HERU / utg 2

> ENGLISH VERSION. Instructions HERU 50 HERU / utg 2 > ENGLISH VERSION Instructions HERU 50 HERU 75 1270100/ utg 2 EC declaration of conformity (as defined by the Machinery Directive 98/37/EEC, appendix 2A) We hereby confirm that HERU 50 and HERU 75 comply

More information

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL BC(E) SERIES INDOOR / OUTDOOR MANUFACTURED BY GENERAL INFORMATION PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: TELEPHONE: INSTALLATION

More information

BATHROOM EXTRACT FANS SILENT-100 Series

BATHROOM EXTRACT FANS SILENT-100 Series SILENT-1 Series Range of axial extractors with airflow rates of 95 m 3 /h, for connection to 1 mm diameter circular ducting. Motor mounted on silent-elastic-blocks which absorb the vibrations and allow

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

E U R O V E N T CERTIFIED PERFORMANCE

E U R O V E N T CERTIFIED PERFORMANCE Compact Horizontal Air-Air Heat Pump Model RTH-7K to 3K Ref.: Y-R719 7 Technical information E U R O V E N T CERTIFIED PERFORMANCE I S O 9 1 ER-8/1991 Clima Roca York S.L. is participating in the EUROVENT

More information

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts Standard Construction Control Options HEATREX offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

Technical instructions

Technical instructions Énergie Transfert Thermique Technical instructions A different climate Environmental control solutions Version IMPORTANT The warranty of ETT units depends on the respect of these technical instructions

More information

Directions for use. CPS/XPS - Condensor / Dry cooler

Directions for use. CPS/XPS - Condensor / Dry cooler 61221 Directions for use 1 2 Declaration by the Manufacturer, Annex II B As defined by the EC Machinery Directive (MD) 98/37/EC, the Low Voltage Directive (LVD) 2006/95/EC and the EMC Directive 2004/108/EC.

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS GENERAL INDEECO Industrial Control Panels are designed to provide years of trouble free operation if properly

More information

40KMC KMQ

40KMC KMQ 40KMC------301 40KMQ------301 OWNER S MANUAL Split system Global cassette indoor unit IR Remote Control Room Controller Zone Manager The unit can be used with infrared Remote Control, with the Carrier

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...

More information

High Heat COP. High/Low Stage

High Heat COP. High/Low Stage SOUND REFRIGERANT ENVIRONMENTALLY PHN5 Product Specifications 15 SEER, 8.0 HSPF, PACKAGE HEAT PUMP, 2-5 TONS Single Phase, 208/230V, Hz. REFRIGERATION CIRCUIT R--410A refrigerant Copper tube/aluminum fin

More information

USER MANUAL. Frigate HRV 120 SR Frigate ERV 120 SR. Heat (energy) recovery ventilation unit

USER MANUAL. Frigate HRV 120 SR Frigate ERV 120 SR. Heat (energy) recovery ventilation unit USER MANUAL Frigate HRV 120 SR Frigate ERV 120 SR Heat (energy) recovery ventilation unit 2 CONTENTS Safety requirements... 3 Introduction... 5 Use... 5 Included in the box... 5 Designation key... 5 Technical

More information

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products 1 821 1821P01 Frost sensors for use on the air side Active capillary tube sensor for measuring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10 V Use On

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2 MARKING This product marked conforms to the essential

More information