1 Installer manual Accessory Card Accessories IHB GB - 0

2

3 Table of Contents General Component positions Shunt controlled additional heat General Pipe connections Outline diagram Electrical connection Program settings Electrical circuit diagram Step controlled additional heat General Pipe connections Outline diagram Electrical connection 0 Program settings Electrical circuit diagram Extra climate system General Pipe connections Outline diagram Electrical connection Program settings Electrical circuit diagram Hot water comfort General Pipe connections Outline diagram 0 Electrical connection Program settings Electrical circuit diagram Active cooling (-pipe) General Pipe connections Outline diagram Electrical connection Program settings Wiring diagram Connection of several heat pumps 0 General 0 Pipe connections 0 Outline diagram Electrical connection Program settings Electrical circuit diagram Table of Contents

4 L N 0 PE ON General This accessory card in is used to enable connection and control of one of the following accessory functions. Shunt controlled additional heat Step controlled additional heat Extra climate system Hot water comfort Active cooling (-pipe) Connection of several heat pumps One or more accessory functions require an AXC 0 each. Component positions AA AA-X -X -X -X 0 0 AA-X AA-F AA-X -X PE PE L N -X0 -X X LEK Electrical components X Terminal block, power supply AA Accessory card AA-X Terminal block, sensors and external blocking AA-X Terminal block, communication AA-X Terminal block, circulation pump, mixing valve and auxiliary relay AA-S DIP switch AA-F Fine wire fuse, TAH0V Designations in component locations according to standard IEC - and -. Chapter General

5 Shunt controlled additional heat General This function enables an external additional heater, e.g. an oil boiler, gas boiler or district heating exchanger to aid with heating. The indoor module controls a shunt valve and a circulation pump (GP0) via the accessory card in. If the heat pump does not manage to keep the correct supply temperature (BT), the addition starts. When the boiler temperature of (BT) has been increased to about C, the indoor module transmits a signal to the shunt (QN) to open from the addition. The shunt (QN) adjusts so the true supply temperature corresponds with the indoor module's theoretical calculated set point value. When the heating demand drops sufficiently so the additional heat is no longer required the shunt (QN) closes completely. Factory set minimum run time holding the boiler prepared is hours (can be set in menu..). Pipe connections The external circulation pump (GP0) is positioned according to the outline diagram. Shunt valve The shunt valve (QN) is located on the flow line to the climate system after the heat pump according to the outline diagram. Connect the flow line from the heat pump to the external heat source A AB via the T-pipe to port B on the shunt valve (closes at reduced signal). Connect the flow line to the climate B system from the shunt valve to the common port AB (always open) Connect the flow line from the external additional heat to the shunt valve to port A (opens at increased signal). Temperature sensor Install the boiler sensor (BT) in a suitable location in the external addition. External supply temperature sensor (BT, connected in ) must be installed on the supply line to the radiators, after the shunt valve (QN). K Install the temperature sensors with cable ties with the heat conducting paste and aluminium tape. Then insulate with supplied insulation tape. NOTE Sensor and communication cables must not be placed near power cables. Chapter Shunt controlled additional heat

6 Outline diagram Miscellaneous Explanation AA EM Shunt controlled additional heat, boiler BT AA Accessory card () BT BT Temperature sensor, boiler BT CM Expansion vessel, closed BT EM Oil/gas boiler FL0 Safety valve, heating medium side BT QN Mixing valve, addition CP0, CP EB0, EB0Heat pump system CP0 BT Temperature sensor, return CM BT Temperature sensor, condenser out FL EB0, EB0 Heat pump GP0 FL0 Safety valve QN0 GP Charge pump RN0 - RN HQ Particle filter QM Tapping valve QM - QMShut-off valve QM Shut-off valve RM Non-return valve Outline diagram and shunt controlled additional heat Outdoor sensor Temperature sensor, hot water charging Temperature sensor, hot water, top Temperature sensor, heating medium flow, External Temperature sensor, heating medium return, External Hot water heater Buffer vessel, UKV Expansion vessel, closed, brine side Safety valve Circulation pump, heating medium external Reversing valve, hot water Trim valve Designations according to standards - and -. -EM -AA-AA -CM -EM -FL0 -BT -QN -AA-BT -AA-BT -CP0 -AA-GP0 -AA -RN -RN -RN0 -RN -EB0 -EB0 -BT -FL0 -BT -QM -QM -GP -RM -HQ -QM -AA-QN0 -CP0 -AA-BT -AA-BT -CP -QM -EB0 -EB0 -BT -FL0 -BT -QM -QM -GP -RM -HQ -QM -AA -BT -QM -FL -CM Chapter Shunt controlled additional heat

7 ON Electrical connection -X AA-X Caution The relay outputs on the accessory card can have a max load of A (0 V) in total. -X -X 0 Connection of the circulation pump (GP0) Connect the circulation pump (GP0) to AA-X: (0 V), AA-X: (N) and X:PE. Externt -X PE PE L N -X0 0 -X X GP0 AA-X AA-X 0 PE NOTE All electrical connections must be carried out by an authorised electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force. must not be powered when installing accessory functions. Connection of sensors and external blocking Use cable type LiYY, EKKX or similar. Boiler sensor (BT) Connect the boiler sensor to AA-X:-. External blocking (optional) A contact (NO) can be connected to AA-X:- to block the addition. When the contact closes, the addition is blocked. Connection of the mixing valve motor (QN) Connect the mixing valve motor (QN) to AA-X: (0 V, open), AA-X: (N) and AA-X: (0 V, close). 0 Chapter Shunt controlled additional heat

8 0 0 N L PE PE Connection of the auxiliary relay for additional heating Connect the auxiliary relay for switching the addition on and off to AA-X: (0 V) and AA-X: (N). External auxiliary relay L N A A Additional Heating DIP switch The DIP switch on the accessory card must be set as follows. ON -X ON -X -X -X0 -X -X Program settings Program setting of can be performed via the start guide or directly in the menu system. Start guide The start guide appears upon first start-up after heat pump installation, but is also found in menu.. Menu system If you do not make all settings via the start guide or need to change any of the settings, this can be done in the menu system. Menu. - system settings Activating/deactivating of accessories. Select: "shunt controlled add. heat". Menu.. - shunt controlled add. heat Here you can perform the following settings: Select when the addition is to start. Minimum running time. Minimum boiler temperature at which the shunt can start control. Misc. shunt settings. Menu. - forced control Forced control of the different components in indoor module as well as in the different accessories that may be connected. EM-AA-K: Activating the relay for additional heating. EM-AA-K: Signal (close) to mixing valve (QN). EM-AA-K: Signal (open) to mixing valve (QN). EM-AA-K: Activating the circulation pump (GP0). Caution Also see the Installer manual for. Chapter Shunt controlled additional heat

9 Electrical circuit diagram Chapter Shunt controlled additional heat

10 Step controlled additional heat General This function enables an external additional heater, e.g. an electric boiler, to aid with heating. With the accessory card in a further three potential free relays can be used for addition control, which then gives max linear or binary steps. The flow through the addition is ensured either by the charge pump (GP) or the external circulation pump (GP0). Pipe connections The extra circulation pump (GP0) is positioned according to the outline diagram. Temperature sensor K Install the temperature sensors with cable ties with the heat conducting paste and aluminium tape. Then insulate with supplied insulation tape. NOTE Sensor and communication cables must not be placed near power cables. Chapter Step controlled additional heat

11 Outline diagram Miscellaneous Explanation AA EB Step controlled additional heat BT AA Accessory card in () BT CM Expansion vessel, closed BT EB External electrical additional heat BT FL0 Safety valve, heating medium side QM - QMShut-off valve, heating medium side BT RN Trim valve CP0 - CP EB0, EB0Heat pump system CP0 BT Temperature sensor, return CM BT Temperature sensor, condenser out FL EB0, EB0 Heat pump GP0 FL0 Safety valve, heating medium side QN0 GP Charge pump RN0 - RN HQ Particle filter QM Tapping valve QM - QMShut-off valve QM Shut-off valve RM Non-return valve Outline diagram and step controlled additional heat -EB Outdoor sensor Temperature sensor, hot water charging Temperature, hot water top Temperature sensor, heating medium flow, External Temperature sensor, heating medium return, External Hot water heater Buffer vessel, UKV Expansion vessel, closed Safety valve Circulation pump, heating medium external Reversing valve, hot water Trim valve Designations according to standards - and -. -AA-AA -CM -EB -FL0 -QM -QM -RN -AA-BT -AA-BT -CP0 -AA-GP0 -AA -RN -RN -RN0 -RN -EB0 -AA-QN0 -CP0 -AA-BT -CP -EB0 -BT -FL0 -BT -QM -QM -GP -RM -HQ -QM -AA-BT -QM -EB0 -EB0 -BT -FL0 -BT -QM -QM -GP -RM -HQ -QM -AA -BT -QM -FL -CM Chapter Step controlled additional heat

12 ON 0 0 N L PE PE Electrical connection -X AA-X Caution The relay outputs on the accessory card can have a max load of A (0 V) in total. -X -X 0 Connection of the circulation pump (GP0) Connect the circulation pump (GP0) to AA-X: (0 V), AA-X: (N) and X:PE. Externt -X PE PE L N -X0 0 -X X GP0 AA-X AA-X 0 PE NOTE All electrical connections must be carried out by an authorised electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force. must not be powered when installing accessory functions. Connecting additional step Connect step to AA-X: and. Connect step to AA-X: and. Connect step to AA-X: and. Connection of sensors and external blocking Use cable type LiYY, EKKX or similar. External blocking (optional) A contact (NO) can be connected to AA-X:- to block the addition. When the contact closes, the addition is blocked. A A A A A A STEG STEG STEG DIP switch The DIP switch on the accessory card must be set as follows. 0 ON -X ON -X -X -X0 -X -X 0 Chapter Step controlled additional heat

13 Program settings Program setting of can be performed via the start guide or directly in the menu system. Start guide The start guide appears upon first start-up after heat pump installation, but is also found in menu.. Menu system If you do not make all settings via the start guide or need to change any of the settings, this can be done in the menu system. Menu. - system settings Activating/deactivating of accessories. Select: "step controlled add. heat". Menu.. - step controlled add. heat Here you can perform the following settings: Select when the addition is to start. Set max permitted number of additional steps. If binary stepping is to be used. Menu. - forced control Forced control of the different components in the heat pump as well as in the different accessories that may be connected. EB-AA-K: Activating additional step. EB-AA-K: Activating additional step. EB-AA-K: Activating additional step. EB-AA-K: Activating the circulation pump (GP0). Caution Also see the Installer manual for. Chapter Step controlled additional heat

14 Electrical circuit diagram Chapter Step controlled additional heat

15 Extra climate system General This accessory function is used when is installed in houses with up to four different climate systems that require different flow line temperatures, for example, in cases where the house has both a radiator system and an under floor heating system. Caution Underfloor heating systems are normally max flow line temperature set between and C. Check the max temperature for your floor with your floor supplier. Caution If the room sensor is used in a room with under floor heating it should only have an indicatory function, not control of the room temperature. Pipe connections General When connecting extra climate systems, they must be connected so that they have a lower working temperature than the climate system. Circulation pump The extra circulation pump (GP0) is positioned in the extra climate system according to the outline diagram. Shunt valve The mixing valve (QN) is located on the flow line after the heat pump/indoor module, before the first radiator in the climate system. The return line from the additional climate system must be connected to the shunt valve and to the return line from the heating system, see image and outline diagram. Connect the flow line to the climate system from the heat pump to port A on the AB shunt valve (opens at increased signal) Connect the return line from the climate B system to port B on the shunt valve via the T-pipe to (closes at reduced signal). Connect the flow line to the climate system to the common port AB on the shunt A valve (always open). Temperature sensor The flow temperature sensor (BT) is installed on the pipe between the circulation pump (GP0) and mixing valve (QN). The return line sensor (BT) is installed on the pipe from the extra climate system. K Install the temperature sensors with cable ties with the heat conducting paste and aluminium tape. Then insulate with supplied insulation tape. NOTE Sensor and communication cables must not be placed near power cables. Chapter Extra climate system

16 Outline diagram Explanation EB External additional heat CM Expansion vessel, closed EB External electrical additional heat FL0 Safety valve, heating medium side QM - QMShut-off valve, heating medium side RN Trim valve EB0, EB0Heat pump system BT Temperature sensor, return BT Temperature sensor, condenser out EB0, EB0 Heat pump FL0 Safety valve, heating medium side GP Charge pump HQ Particle filter QM Tapping valve QM - QMShut-off valve QM Shut-off valve RM Non-return valve EP Climate system AA Accessory card BT Flow temperature sensor, extra climate system Outline diagram SMO0 and up to three extra climate systems -EB BT Return line sensor, extra climate system GP0 Circulation pump, extra climate system QN Shunt valve Miscellaneous AA BT Outdoor sensor BT Temperature sensor, hot water charging BT Temperature sensor, hot water, top BT Temperature sensor, heating medium flow, External BT Temperature sensor, heating medium return, External CP0 - CP Hot water heater CP0 Buffer vessel, UKV CM Expansion vessel, closed FL Safety valve GP0 Circulation pump, heating medium external QN0 Reversing valve, hot water RN0 - RN Trim valve Designations in component locations according to standard IEC - and -. -AA-AA -CM -EB -FL0 -QM -QM -RN -AA-AA -BT -GP0 -QN -BT -AA-BT -AA-BT -CP0 -AA-GP0 -AA -RN -RN -RN0 -RN -EB0 -EB0 -BT -FL0 -BT -QM -QM -GP -RM -HQ -QM -AA-QN0 -CP0 -AA-BT -AA-BT -CP -QM -EB0 -EB0 -BT -FL0 -BT -QM -QM -GP -RM -HQ -QM -AA -BT -QM -FL -CM Chapter Extra climate system

17 ON Electrical connection -X AA-X Connection of sensors and external adjustment Use cable type LiYY, EKKX or similar. -X -X Flow temperature sensor, extra climate system (BT) 0 Connect the flow temperature sensor to AA-X:-. Return line sensor, extra climate system (BT) Connect the return line sensor to AA-X:-. 0 Room temperature sensor, extra climate system (BT0) (optional) Connect the room temperature sensor to AA- X:-0. -X PE PE L N -X0 -X External adjustment (optional) A potential free switch can be connected to AA- X:- for external adjustment of the climate system. AA-X NOTE All electrical connections must be carried out by an authorised electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force. must not be powered when installing accessory functions. 0 Caution The relay outputs on the accessory card can have a max load of A (0 V) in total. Chapter Extra climate system

18 0 0 N L PE PE Connection of the circulation pump (GP0) Connect the circulation pump (GP0) to AA-X: (0 V), AA-X: (N) and X:PE. DIP switch The DIP switch on the accessory card must be set as follows. AA-X X 0 PE Externt GP0 Connection of the mixing valve motor (QN) Connect the mixing valve motor (QN) to AA-X: (0 V, open), AA-X: (N) and AA-X: (0 V, close). AA-S -X ON -X -X Climate system ON -X0 -X -X Chapter Extra climate system

19 Program settings Program setting of can be performed via the start guide or directly in the menu system. Start guide The start guide appears upon first start-up after heat pump/indoor module installation, but is also found in menu.. Menu system If you do not make all settings via the start guide or need to change any of the settings, this can be done in the menu system. Menu.. - accessories Activating/deactivating of accessories. Select: "climate system ", "climate system " and/or "climate system " depending on how many climate systems are installed. Menu.. - max flow line temperature Setting the maximum flow temperature for each climate system. Menu.. - extra climate system Mixing valve settings for extra installed climate system. Menu. - temperature Setting the indoor temperature. Menu.. - heating curve Setting the heat curve. Menu.. - external adjustment Setting external adjustment. Menu.. - min. flow line temp. Setting the minimum flow temperature for each climate system. Menu.. - room sensor settings Activating and setting the room temperature sensor. Menu. - forced control Forced control of the different components in the heat pump as well as in the different accessories that may be connected. is climate system, EP, is climate system EP, is climate system EP. EP#-AA-K: No function. EP#-AA-K: Signal (close) to mixing valve (QN). EP#-AA-K: Signal (open) to mixing valve (QN). EP#-AA-K: Activating the circulation pump (GP0). Caution Also see the Installer manual for relevant heat pump/indoor module. Chapter Extra climate system

20 Electrical circuit diagram Chapter Extra climate system

21 Hot water comfort General This function allows temporary lux, mixing valve and hot water circulation. Temporary lux (extra hot water) If an immersion heater is installed in the tank it can be permitted to produce hot water, at the same time as the heat pump prioritises heating. Mixing valve A temperature sensor reads the temperature of the outgoing hot water to the domestic hot water and adjusts the mixing valve from the water heater until the set temperature has been reached. Hot water circulation (VVC) One pump can be controlled for the circulation of the hot water during selectable periods. Pipe connections Mixing valve The mixing valve (FQ) is located on the outgoing hot water line from the water heater according to the outline diagram. Connect the incoming cold water via the T-pipe to the port B on the B AB mixing valve (closes at signal). Connect the mixed water to the domestic hot water taps from the A mixing valve to the common port AB (always open). Connect the outgoing hot water from the water heater to the mixing valve to port A (opens on signal) Temperature sensor Temperature sensor, outgoing hot water, (BT0) installed in a suitable place after the mixing valve (FQ). K Install the temperature sensors with cable ties with the heat conducting paste and aluminium tape. Then insulate with supplied insulation tape. NOTE Sensor and communication cables must not be placed near power cables. Chapter Hot water comfort

22 Outline diagram Explanation EB External additional heat CM Expansion vessel, closed EB External electrical additional heat FL0 Safety valve, heating medium side QM - QMShut-off valve, heating medium side RN Trim valve EB0, EB0Heat pump system BT Temperature sensor, return BT Temperature sensor, condenser out EB0, EB0 Heat pump FL0 Safety valve, heating medium side GP Charge pump HQ Particle filter QM Tapping valve QM - QMShut-off valve QM Shut-off valve RM Non-return valve QZ Hot water comfort AA Accessory card Outline diagram SMO0 and hot water comfort BT0 Temperature sensor, outgoing hot water EB0 Additional water heater GP Circulation pump, domestic hot water circulation RM Non-return valve RN0 Trim valve Miscellaneous AA BT Outdoor sensor BT Temperature sensor, hot water charging BT Temperature sensor, hot water, top BT Temperature sensor, heating medium flow, External BT Temperature sensor, heating medium return, External CP0 - CP Hot water heater CP0 Buffer vessel, UKV CM Expansion vessel, closed FL Safety valve GP0 Circulation pump, heating medium external QN0 Reversing valve, hot water RN0 - RN Trim valve -EB -CM -EB -FL0 -QM -QM -RN -AA-BT -AA-BT -CP0 -AA-GP0 -AA -AA -QZ -GP -RN -RN0 -RN -RN -RN0 -RM -FQ -BT0 -AA-EB0 -EB0 -BT -FL0 -BT -QM -QM -GP -RM -HQ -QM -AA -QN0 -CP0 -AA-BT -AA-BT -CP -EB0 -QM -AA-EB0 -EB0 -BT -FL0 -BT -QM -QM -GP -RM -HQ -QM -AA -BT -QM -FL -CM 0 Chapter Hot water comfort

23 ON Electrical connection -X -X -X 0 0 -X -X0 -X PE PE L N AA-X Connection of the hot water circulation pump (GP) Connect the circulation pump (GP) to AA-X: (0 V), AA-X: (N) and X:PE. AA-X X 0 PE Externt GP AA-X NOTE All electrical connections must be carried out by an authorised electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force. must not be powered when installing accessory functions. Connecting sensors Use cable type LiYY, EKKX or similar. How water sensor, flow line (BT0) Connect hot water sensor to AA-X:-. Connection of the mixing valve (FQ) Connect the mixing valve motor (FQ) to AA-X: (0 V, open), AA-X: (N) and AA-X: (0 V, close). 0 Caution The relay outputs on the accessory card can have a max load of A (0 V) in total. Connecting auxiliary relay for temporary lux (extra hot water) Connect the auxiliary relay for switching the addition on and off to AA-X: (N) and AA-X: (0 V). External auxiliary relay Additional Hot water A A L N Chapter Hot water comfort

24 0 0 N L PE PE DIP switch The DIP switch on the accessory card must be set as follows. Program settings Program setting of can be performed via the start guide or directly in the menu system. ON -X ON -X -X -X0 -X -X Start guide The start guide appears upon first start-up after heat pump installation, but is also found in menu.. Menu system If you do not make all settings via the start guide or need to change any of the settings, this can be done in the menu system. Menu.. - accessories Activating/deactivating of accessories. Select: "hot water comfort". Menu.. - hot water recirc. Here you can make the following settings for hot water circulation for up to three periods per day: How long the hot water circulation pump must run per operating instance How long the hot water circulation pump must be stationary between operating instances. Menu.. - hot water comfort Here you can perform the following settings: If an immersion heater is installed in the tank and whether it can be permitted to charge hot water if the compressors in the heat pump prioritise heating. Whether a mixing valve for limiting the temperature of hot water from the water heater is installed. Various shunt settings and outgoing hot water temperature from the tank for the mixing valve. Menu. - forced control Forced control of the different components in the heat pump as well as in the different accessories that may be connected. QZ-AA-K: Activating the relay for extra hot water. QZ-AA-K: Signal (close) to the mixing valve (FQ). QZ-AA-K: Signal (open) to the mixing valve (FQ). QZ-AA-K: Activating the circulation pump (GP). Caution Also see the Installer manual for. Chapter Hot water comfort

25 Electrical circuit diagram Chapter Hot water comfort

26 Active cooling (-pipe) General Connecting this accessory makes it possible to control production of cooling. The cooling system supplies cooling from the heat pump using a circulation pump (GP) via a reversing valve (QN). For the installation to work the cooling system must flow freely permanently, for example using a volume vessel for cooling. Operating mode cooling is activated by the temperature of the outdoor sensor (BT) and any room temperature sensors (BT0), room units or separate room sensors for cooling (BT) (if two different rooms are to be heated respectively cooled at the same time for example.) When cooling is required, the cooling reversing valve (QN) and the circulation pump (GP) are activated. Cooling production is regulated according to the cooling sensor (BT) and a cooling set point value that is determined by the selected cooling curve. Cooling degree minutes are calculated in response to the value on the external temperature sensor (BT) for cooling out and the cooling set point value. As an accessory, cooling reversing valve is required, e.g. VCC/VCC. Pipe connections General Pipes and other cold surfaces must be insulated with diffusion-proof material to prevent condensation. Where the cooling demand is high, fan convectors with drip trays and drain connection are needed. Reversing valve, cooling/heating The reversing valve (QN) is located in the system on the supply line from the heat pump ahead of another reversing valve according to the outline diagram. B AB A Temperature sensor Temperature sensor (BT) is mounted on the supply line to the cooling system at the T-pipe connection to the volume vessel (CP). K Install the temperature sensors with cable ties with the heat conducting paste and aluminium tape. Then insulate with supplied insulation tape. NOTE Sensor and communication cables must not be placed near power cables. Chapter Active cooling (-pipe)

27 Outline diagram Explanation EQ Cooling system AA-AAAccessory card in BT Temperature sensor, flow line cooling CP Accumulator tank, cooling GP Cooling circulation pump EB0 Heat pump system BT Temperature sensor, return BT Temperature sensor, condenser supply Outline diagram SMO0 and active cooling (-pipe) -AA-AA -CP -EQ -AA GP Charge pump EB0 Heat pump FL0 Safety valve, heating medium side HQ Particle filter QM Tapping valve QM- Shut-off valve QM QM Shut-off valve RM Trim valve Designations in component locations according to standard IEC - and -. -AA-QN0 - -GP -BT -BT -BT0 -EQ-QN -EB0 -EB0 -BT -FL -QM -BT -QM -GP -HQ -QM -QM Chapter Active cooling (-pipe)

28 ON 0 0 N L PE PE L N 0 PE Electrical connection -X -X -X AA-S Connection of sensors and external blocking Use cable type LiYY, EKKX or similar. Temperature sensor (BT) Connect the sensor to AA-X: AA-X Room temperature sensor for cooling operating mode (BT) An extra temperature sensor (room sensor for cooling) can be connected to in order to better determine when it is time to switch between heating and cooling operation. Connect the temperature sensor to one of the AUX inputs which are behind the front hatch in. The actual AUX input is selected in menu.. Use a core cable of at least 0. mm cable area. AA -X PE PE L N -X0 -X -X ON -X -X -X AA-X0 AA-X -X0 -X NOTE All electrical connections must be carried out by an authorised electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force. must not be powered when installing accessory functions. Place the temperature sensor in a neutral position in the room where the set temperature is required. It is important that the sensor is not obstructed from measuring the correct room temperature by being located, for example, in a recess, between shelves, behind a curtain, above or close to a heat source, in a draft from an external door or in direct sunlight. Closed radiator thermostats can also cause problems. LEK Room sensor (BT0) To connect the room sensor (BT0), see the Installation manual for. Chapter Active cooling (-pipe)

29 External blocking (optional) A contact can be connected to AA-X:- to block cooling operation. When the contact closes, cooling operation is blocked. Connection of the reversing valve motor (QN) Connect the motor (QN) to AA-X: (signal), AA- X: (N) and AA-X0: (0 V). Externt Extern blockering BT AA-X -X0 Svart Blå Brun QN 0 Caution AA-X The relay outputs on the accessory card can have a max load of A (0 V) in total. Connection of the cooling circulation pump (GP) Connect the circulation pump (GP) to AA-X: (0 V), AA-X: (N) and X:PE. Externt GP AA-X0 DIP switch The DIP switch on the accessory card must be set as follows. ON AA-S AA-X 0 PE X Connecting the charge pump (GP) Do not connect charge pump GP to the accessory card. See Installation manual to connect charge pump GP. Chapter Active cooling (-pipe)

30 Program settings Program setting of can be performed via the start guide or directly in the menu system. Caution Also see the Operating manual for. Start guide The start guide appears upon first start-up after heat pump installation, but is also found in menu.. Menu system If you do not make all settings via the start guide or need to change any of the settings, this can be done in the menu system. Menu.. - accessories Activating/deactivating of accessories. Select: "active cooling pipe". Menu. - temperature Setting indoor temperature (room temperature sensor is required). Menu.. - cooling settings Here you can perform the following settings: Lowest flow line temperature when cooling. Desired flow temperature at an outdoor air temperature of +0 and +0 C. Time between cooling and heating operation and vice versa. Selection of room sensor can control cooling. How much the room temperature may decrease or increase compared to the desired temperature before switching to heating respectively cooling (requires room sensor). Degree minute levels for cooling. Misc. shunt settings. Menu.. - auto mode setting When heat pump operating mode is set to "auto it selects when start and stop of additional heat, heat production and cooling is permitted, dependent on the average outdoor temperature. Select the average outdoor temperatures in this menu. You can also set the time over which (filtering time) the average temperature is calculated. If you select 0, the present outdoor temperature is used. Menu. - forced control Forced control of the different components in the heat pump as well as in the different accessories that may be connected. EQ-AA-K: Signal to three way valve (QN). EQ-AA-K: Signal (close) to mixing valve (QN). EQ-AA-K: Signal (open) to shunt (QN) EQ-AA-K: Activating the circulation pump (GP0). EQ-AA-K: Signal (close) to mixing valve (QN). EQ-AA-K: Signal (open) to mixing valve (QN). Chapter Active cooling (-pipe)

31 Wiring diagram Chapter Active cooling (-pipe)

32 Connection of several heat pumps General This function allows control of up to two extra charge pumps GP. The accessory is required for charge pump for slave - EB0X with address or greater. Up to eight slaves can be combined in one system. The control module controls the charge pumps together with the relevant slave during operation. Type CPD charge pump is recommended to use speed control which ensures correct delta-t in the different operating modes during the year. The accessory also enables external blocking of each corresponding slave. Pipe connections The charge pump (GP) is positioned in the relevant charge circuit before joining with other charge circuits or branching off different sub systems via reversing valve. 0 Chapter Connection of several heat pumps

33 Outline diagram QM - Shut-off valve QM Explanation QM Shut-off valve EB0- Heat pump system QN0 Reversing valve, heating/hot water EB0 RM Non-return valve BT Temperature sensor Miscellaneous BT Temperature sensor AA Accessory card () EB00- Heat pump BT Temperature sensor EB0 CM Expansion vessel, closed FL0 Safety valve FL Safety valve GP Charge pump Designations in component locations according to HQ Particle filter standard IEC - and -. Outline diagram SMO0 and connecting several heat pumps -EB0 -EB0 -BT -FL0 -BT -QM -QM -GP -HQ -RM -QM -QM -EB0 -EB0 -BT -QM -AA-AA -RM -AA -FL0 -BT -QM -GP -HQ -QM -QM -EB0 -EB0 -BT -QM -RM -FL0 -BT -QM -GP -HQ -QM -QM -EB0 -EB0 -BT -FL0 -BT -QM -QM -GP -HQ -RM -QM -AA -BT -QM -FL -CM Chapter Connection of several heat pumps

34 ON Electrical connection -X -X -X 0 0 AA-S AA-X Connection of sensors and external blocking Use cable type LiYY, EKKX or similar. External blocking (optional) A contact can be connected to AA-X:- to block slave EB0. When the contact closes, EB0 is blocked, however, anti-freeze via GP is ensured. A further contact can be connected to AA-X:- to block slave EB0. When the contact closes, EB0 is blocked, however, anti-freeze via GP is ensured. A contact can be connected to AA-X:- to block cooling the accessory function. When the contact closes, the entire accessory function is blocked. Caution When the entire accessory function is blocked, there is no anti-freeze for connected slaves! -X PE PE L N -X -X0 AA-X0 AA-X Extern blockering EB0-GP EB0-GP NOTE All electrical connections must be carried out by an authorised electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force. must not be powered when installing accessory functions. 0 AA-X Caution The relay outputs on the accessory card can have a max load of A (0 V) in total. Chapter Connection of several heat pumps

35 Connection of the circulation pump (GP) Connect the circulation pump (EB0-GP) to AA- X: (0 V), AA-X: (N) and X:PE. Connect the circulation pump (EB0-GP) to AA- X: (0 V), AA-X: (N) and X:PE. Externt PMW GND PMW GND AA-X AA-X 0 PE EB0-GP EB0-GP X DIP switch The DIP switch on the accessory card must be set as follows. ON AA-S Chapter Connection of several heat pumps

36 Program settings Program setting of multi-installation during operation of several heat pumps can be performed via the start guide or directly in the menu system. Start guide The start guide appears upon first start-up after heat pump installation, but is also found in menu.. Menu system If you do not make all settings via the start guide or need to change any of the settings, this can be done in the menu system. Menu.. - installed slaves Activating/deactivating slaves Menu.. - docking Enter how your system is docked regarding pipes, for example to pool heating, hot water heating and heating the building. TIP Examples of docking alternatives can be found at This menu has a docking memory which means that the control system remembers how a particular reversing valve is docked and automatically enters the correct docking the next time you use the same reversing valve. Master/slave: Select which heat pump the docking setting is to be made for (if the heat pump is alone in the system only master is displayed). Compressor: Select if your compressor in the heat pump is blocked (factory setting), externally controlled via soft input or standard (docked for example to pool heating, hot water charging and heating the building). Marking frame: Move around the marking frame using the control knob. Use the OK button to select what you want to change and to confirm setting in the options box that appears to the right. Workspace for docking: The system docking is drawn here. Symbol Description Pool Heating (heating the building, includes any extra climate system) Menu.. - EB0 Make settings for the installed slaves here. Menu. - forced control Forced control of the different components in the heat pump as well as in the different accessories that may be connected. Compressor speed EB0 - GP - AA-K Charge pump speed Compressor speed EB0 - GP - AA-K Charge pump speed Caution Also see the Installer manual for. Symbol Description Compressor (blocked) Compressor (externally controlled) Compressor (standard) Reversing valves for hot water control. The designations above the reversing valve indicate where it is electrically connected (EB0 = Slave, CL = Pool etc.). Pool Chapter Connection of several heat pumps

37 Electrical circuit diagram Chapter Connection of several heat pumps

38 Chapter

39

40 NIBE AB Sweden Hannabadsvägen Box SE- Markaryd 0

Installer manual AXC 30

Installer manual AXC 30 LEK Installer manual AXC 0 Accessories IHB GB - Table of Contents General Contents Component positions Common electrical connection Connecting communication Connecting the supply Shunt controlled additional

More information

Installer manual AXC 40. Accessories IHB GB LEK

Installer manual AXC 40. Accessories IHB GB LEK EK Installer manual AXC 0 Accessories IHB GB 0-0 Table of Contents General Contents Component positions Common electrical connection Connecting the supply Connecting communication Shunt controlled additional

More information

Outline principle. Application Buildings with water-borne heating systems. Alternative

Outline principle. Application Buildings with water-borne heating systems. Alternative Outline principle Application Buildings with water-borne heating systems. Alternative Additional heating before QN10 Accessories NOTE! This is an outline diagram. Actual installation must be engineered

More information

Installer manual SMO 40

Installer manual SMO 40 Installer manual Control module IHB EN 76-5 23760 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button

More information

Outline principle. Application Houses with water-borne heating systems. Maximal recommended heating output 13.5 kw. Alternative

Outline principle. Application Houses with water-borne heating systems. Maximal recommended heating output 13.5 kw. Alternative Outline principle Application Houses with water-borne heating systems. Maximal recommended heating output 13.5 kw. Alternative NOTE! This is an outline diagram. Actual installation must be project planned

More information

Outline principle. Application Houses with water-borne heating systems. Alternative Select the desired configuration by highlighting the boxes below.

Outline principle. Application Houses with water-borne heating systems. Alternative Select the desired configuration by highlighting the boxes below. Outline principle Application Houses with water-borne heating systems. Alternative Select the desired configuration by highlighting the boxes below. NOTE! This is an outline diagram. Actual installation

More information

Outline principle. Application Buildings with water-borne heating systems. Alternative

Outline principle. Application Buildings with water-borne heating systems. Alternative Outline principle Application Buildings with water-borne heating systems. Alternative F1145/1245/1345 Master/Slave with additional heat, accessories and hot water heater (floating condensing). Heat pump

More information

Installer manual SMO 40

Installer manual SMO 40 Installer manual UK Control module IHB GB 1546-3 231764 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

Installer manual ELK 213 Immersion heater

Installer manual ELK 213 Immersion heater Installer manual ELK 213 LEK IHB GB 1535-3 031403 Table of Contents 1 English, IHB - ELK 213 General Component positions Pipe connections 2 2 3 5 Disturbances in comfort Accessories Technical data Electrical

More information

Installer manual NIBE VVM 310

Installer manual NIBE VVM 310 Installer manual EMK Indoor module APH IHB EN 1750-8 231175 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of

More information

Installer manual NIBE VVM 500

Installer manual NIBE VVM 500 Installer manual Indoor module APH IHB EN 1751-9 031991 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

Installer manual SMO 20

Installer manual SMO 20 Installer manual UK Control module IHB GB 546-5 23762 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button

More information

SOLAR 42 IHB LEK

SOLAR 42 IHB LEK EK SE G DE FI Installatörshandbok SOR för NIE F/F Installer manual SOR for NIE F/F Installateurhandbuch SOR für NIE F/F sentajan käsikirja SOR NIE F/F SOR IH - 0 G English, Installer manual - SOR General

More information

Installer manual SMO 40

Installer manual SMO 40 Installer manual Control module IHB GB 1624-4 231760 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button

More information

Installer manual SMO 40. Control module IHB GB LEK

Installer manual SMO 40. Control module IHB GB LEK Installer manual Control module IHB GB 1436-2 231760 A detailed explanation of the button functions can be found on page 29. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE VVM 320

Installer manual NIBE VVM 320 Installer manual UK 1x230V Indoor module APH IHB GB 1613-6 231342 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

NIBE F1355. A +++ The system's efficiency class for heating. Speed-controlled ground source heat pump for large buildings. Ground source heat pump

NIBE F1355. A +++ The system's efficiency class for heating. Speed-controlled ground source heat pump for large buildings. Ground source heat pump NIBE F1355 Ground source heat pump Speed-controlled ground source heat pump for large buildings Optimal annual coefficient of performance and minimal operating costs thanks to the inverter controlled compressor.

More information

Installer manual NIBE F1145

Installer manual NIBE F1145 Installer manual UK 1x230V Ground source heat pump LEK IHB GB 1643-2 331510 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed

More information

Installer manual NIBE F1245. Ground source heat pump. UK 1x230V

Installer manual NIBE F1245. Ground source heat pump. UK 1x230V Installer manual UK 1x230V Ground source heat pump LEK IHB GB 1343-2 231995 A detailed explanation of the button functions can be found on page 32. How to scroll through menus and make different settings

More information

Installer manual SMO 20. Control module IHB GB LEK

Installer manual SMO 20. Control module IHB GB LEK Installer manual Control module IHB GB 1436-4 231758 A detailed explanation of the button functions can be found on page 24. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE F1145. Ground source heat pump. UK 1x230V IHB GB LEK

Installer manual NIBE F1145. Ground source heat pump. UK 1x230V IHB GB LEK Installer manual UK 1x230V Ground source heat pump LEK IHB GB 1251-2 431074 A detailed explanation of the button functions can be found on page 28. How to scroll through menus and make different settings

More information

NIBE SPLIT ACVM 270 Air/water heat pump

NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 Air/water heat pump NIBE SPLIT ACVM 270 system with complete indoor module NIBE SPLIT ACVM 270 is a complete modern heat pump system that offers effective technical energy saving and

More information

Installer manual NIBE F1245. Ground source heat pump. UK 1x230V IHB GB

Installer manual NIBE F1245. Ground source heat pump. UK 1x230V IHB GB Installer manual UK 1x230V Ground source heat pump LEK IHB GB 1335-1 231613 A detailed explanation of the button functions can be found on page 29. How to scroll through menus and make different settings

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS AMB AMB 30 LEK

INSTALLATION AND MAINTENANCE INSTRUCTIONS AMB AMB 30 LEK MOS GB 1044-1 INSTALLATION AND MAINTENANCE INSTRUCTIONS 031533 Table of Contents For the User General System description Principle of operation 3 Outdoor air operation 3 Hybrid operation 3 The control

More information

NIBE VVM 500 FLEXIBLE INDOOR MODULE INTELLIGENT HOT WATER NIBE VVM 500. Flexible all-in-one indoor module for heating and hot water.

NIBE VVM 500 FLEXIBLE INDOOR MODULE INTELLIGENT HOT WATER NIBE VVM 500. Flexible all-in-one indoor module for heating and hot water. NIBE VVM 500 FXIB INDOOR MODU INTELLIGENT HOT WATER Flexible all-in-one indoor module for heating and hot water. For upgrading existing heating systems or new buildings with requirements for high performance

More information

Installer manual NIBE F1245

Installer manual NIBE F1245 Installer manual Ground source heat pump LEK IHB GB 16432 331488 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

Installer manual NIBE VVM 310. Indoor module IHB GB

Installer manual NIBE VVM 310. Indoor module IHB GB Installer manual Indoor module APH IHB GB 1428-4 231175 A detailed explanation of the button functions can be found on page 33. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE VVM 320. Indoor module IHB GB

Installer manual NIBE VVM 320. Indoor module IHB GB Installer manual Indoor module APH IHB GB 1336-1 231357 A detailed explanation of the button functions can be found on page 32. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE VVM 320. Indoor module IHB GB

Installer manual NIBE VVM 320. Indoor module IHB GB Installer manual Indoor module APH IHB GB 1452-3 231357 A detailed explanation of the button functions can be found on page 33. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE VVM 500. Indoor module APH

Installer manual NIBE VVM 500. Indoor module APH Installer manual Indoor module APH IHB GB 1428-5 031991 A detailed explanation of the button functions can be found on page 30. How to scroll through menus and make different settings is described on page

More information

Installer manual NIBE VVM 310

Installer manual NIBE VVM 310 Installer manual EMK Indoor module APH IHB GB 1524-5 231175 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of

More information

Installer manual NIBE VVM 500

Installer manual NIBE VVM 500 Installer manual Indoor module APH IHB GB 1705-8 031991 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

Installer manual NIBE VVM 310. Indoor module IHB GB

Installer manual NIBE VVM 310. Indoor module IHB GB Installer manual Indoor module APH IHB GB 1338-3 231175 A detailed explanation of the button functions can be found on page 33. How to scroll through menus and make different settings is described on page

More information

NIBE F2026 air/water heat pump. fresh air s free. NIBE F2026. Efficient scroll compressor that operates at temperatures down to -20 C.

NIBE F2026 air/water heat pump. fresh air s free. NIBE F2026. Efficient scroll compressor that operates at temperatures down to -20 C. NIBE F2026 air/water heat pump fresh air s free. Efficient scroll compressor that operates at temperatures down to -20 C. Automatic 2-step capacity regulator for the fan (not 6kW). Manufactured in three

More information

ELK 26 INSTALLATION AND MAINTENANCE INSTRUCTIONS ELK 26

ELK 26 INSTALLATION AND MAINTENANCE INSTRUCTIONS ELK 26 MOS GB 38-2 INSTALLATION AND MAINTENANCE INSTRUCTIONS 2352 LEK Table of Contents For Home Owners General System description Principle of operation 3 Components 3 System diagram 3 Operation and maintenance

More information

Installer manual NIBE F730

Installer manual NIBE F730 Installer manual Exhaust air heat pump IHB EN 1803-1 431700 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of

More information

NIBE F1245 GROUND SOURCE HEAT PUMP. Heat pump with rock, ground or lake as heat source. NIBE F1245

NIBE F1245 GROUND SOURCE HEAT PUMP. Heat pump with rock, ground or lake as heat source. NIBE F1245 NIBE F1245 GROUND SOURCE HEAT PUMP Heat pump with rock, ground or lake as heat source. New display unit with easy-to-read colour screen. Indoor sensor included See status and make settings via SMS with

More information

Installer manual NIBE VVM 500. Indoor module APH

Installer manual NIBE VVM 500. Indoor module APH Installer manual Indoor module APH IHB GB 1216-2 031991 A detailed explanation of the button functions can be found on page 27. How to scroll through menus and make different settings is described on page

More information

NIBE SPLIT HBS 05 Air/water heat pump

NIBE SPLIT HBS 05 Air/water heat pump NIBE SPLIT HBS 05 Air/water heat pump NIBE SPLIT HBS 05 with several possibilities Can be docked with NIBE SMO and NIBE VVM. Customer adapted and cost effective split system. Possible to combine up to

More information

Installer manual NIBE F470

Installer manual NIBE F470 Installer manual Exhaust air heat pump LEK IHB EN 1751-1 431679 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

Installer manual NIBE FLM. Exhaust air module IHB GB LEK

Installer manual NIBE FLM. Exhaust air module IHB GB LEK Installer manual Exhaust air module IHB GB 1414-4 031375 Table of Contents 1 Important information 2 Connections 14 Safety information 2 6 Commissioning and adjusting 19 2 Delivery and handling Transport

More information

Installer manual AHP/AHPS

Installer manual AHP/AHPS Installer manual Accumulator tank IHB GB 1415-2 231351 Table of Contents 1 Important information Safety information 2 2 AHP and AHPS Installation alternative 10 11 2 Delivery and handling Transport 5

More information

Installer manual ELK 213 Immersion heater

Installer manual ELK 213 Immersion heater Installer manual ELK 213 LEK IHB GB 1548-5 031403 Table of Contents 1 Important information Safety information 2 General 4 4 6 Output Time relay Sensors Connection of the circulation pump (GP10) 16 16

More information

Installer manual SAM 40. Supply air module IHB GB LEK

Installer manual SAM 40. Supply air module IHB GB LEK LEK Installer manual Supply air module IHB GB 1231-2 031934 LEK LEK Table of Contents 1 Important information 2 Safety information 2 2 Delivery and handling 5 Transport 5 Assembly 5 Removing the covers

More information

Installer manual NIBE F1245. Ground source heat pump IHB GB

Installer manual NIBE F1245. Ground source heat pump IHB GB Installer manual Ground source heat pump LEK IHB GB 1343-2 231611 A detailed explanation of the button functions can be found on page 34. How to scroll through menus and make different settings is described

More information

Installer manual NIBE F370. Exhaust air heat pump IHB GB LEK

Installer manual NIBE F370. Exhaust air heat pump IHB GB LEK Installer manual Exhaust air heat pump LEK IHB GB 1035-2 031546 A detailed explanation of the button functions can be found on page 33. How to scroll through menus and make different settings is described

More information

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 MOS GB 1236-6 SMO 10 511882 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 Contents General System diagram 3 Principle of operation 3 Abbreviations 3 Front panel Display 4 Switch 5 Offset heating

More information

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 MOS GB 0707-3 SMO 10 511262 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 Contents User guide System diagram 3 Principle of operation 3 Abbreviations 3 Front panel Display 4 Switch 5 Offset heating

More information

Installer manual AHP/AHPS

Installer manual AHP/AHPS Installer manual Accumulator tank IHB GB 1544-4 231351 Table of Contents 1 Important information 3 Installation alternative 13 Safety information 3 5 Electrical installation 15 2 Delivery and handling

More information

NIBE SPLIT ACVM , AMS 10

NIBE SPLIT ACVM , AMS 10 MOS GB 1252-4 INSTALLATION AND MAINTENANCE INSTRUCTIONS 431156 ACVM 10-270, AMS 10 LEK LEK LEK 2 LEK LEK LEK LEK 1 7 5 3 6 LEK LEK LEK 4 $06 K LE LE K LE K LEK LEK $06 Table of Contents For Home Owners

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS ELK ELK 15 LEK

INSTALLATION AND MAINTENANCE INSTRUCTIONS ELK ELK 15 LEK MOS GB 1011-3 INSTALLATION AND MAINTENANCE INSTRUCTIONS 031179 LEK Table of Contents For Home Owners General System description Principle of operation 3 Abbreviations 3 System diagram 3 Operation and

More information

Installer manual AG-WL10

Installer manual AG-WL10 LEK LED CLEAN TIMER OPERATION Installer manual Indoor unit air/air heat pump IHB GB 1637-1 331827 Table of Contents 1 Important information Safety information Read before starting the installation Electrical

More information

Installer manual NIBE F1245PC. Ground source heat pump IHB GB

Installer manual NIBE F1245PC. Ground source heat pump IHB GB Installer manual Ground source heat pump LEK IHB GB 1506-3 231810 A detailed explanation of the button functions can be found on page 34. How to scroll through menus and make different settings is described

More information

Installer manual SAM 40

Installer manual SAM 40 Installer manual Supply air module LEK IHB GB 1549-4 031934 LEK LEK Table of Contents 1 Important information 4 5 Electrical connections 17 Safety information 4 General 17 2 Delivery and handling Transport

More information

Installer manual NIBE ERS

Installer manual NIBE ERS Installer manual Ventilation heat exchanger LEK IHB GB 1622-1 331802 Table of Contents 1 Important information 4 10 Accessories 18 Safety information Serial number 4 4 11 Technical data 19 Recovery Country

More information

Installer manual NIBE F750. Exhaust air heat pump IHB GB LEK

Installer manual NIBE F750. Exhaust air heat pump IHB GB LEK Installer manual Exhaust air heat pump IHB GB 1437-1 231917 A detailed explanation of the button functions can be found on page 30. How to scroll through menus and make different settings is described

More information

NIBE SPLIT ACVM 270, AMS 10

NIBE SPLIT ACVM 270, AMS 10 MOS GB 1452-1 INSTALLATION AND MAINTENANCE INSTRUCTIONS 331183 ACVM 270, AMS 10 LEK LEK LEK 2 LEK LEK LEK LEK 1 7 5 3 6 LEK LEK LEK 4 AMS 10-8 K LE LE K LE K LEK LEK AMS 10-12 Table of Contents For Home

More information

NIBE SPLIT ACVM 270, AMS 10

NIBE SPLIT ACVM 270, AMS 10 MOS GB 0923-1 INSTALLATION AND MAINTENANCE INSTRUCTIONS 031211 ACVM 270, AMS 10 LEK LEK LEK 2 1 LEK LEK LEK LEK 5 3 6 4 LEK LEK 7 LEK LEK LEK Table of Contents For Home Owners General 3 Installation data

More information

Air/water heat pump NIBE F2120 8, 12, 16, 20

Air/water heat pump NIBE F2120 8, 12, 16, 20 IHB EN 1817-4 331385 INSTALLER MANUAL Air/water heat pump 8, 12, 16, 20 Table of Contents 1 Important information 4 Connecting accessories 32 Safety information Symbols Marking Serial number Recovery

More information

Installer manual NIBE ERS

Installer manual NIBE ERS Installer manual Ventilation heat exchanger LEK IHB EN 1726-3 331802 Table of Contents 1 Important information 4 10 Accessories 19 Safety information Serial number 4 4 11 Technical data 20 Recovery Country

More information

Installer manual NIBE VVM 325. Indoor module IHB GB APH

Installer manual NIBE VVM 325. Indoor module IHB GB APH Installer manual Indoor module APH IHB GB 1442-1 331115 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

NIBE F2120 Air/water heat pump

NIBE F2120 Air/water heat pump NIBE Air/water heat pump A breakthrough in efficiency NIBE is an air/water heat pump that has made a real breakthrough with a market leading SCOP. utilises the heat from the outdoor air which places big

More information

Operating manual NIBE F1345

Operating manual NIBE F1345 Operating manual Ground source heat pump LEK OHB GB 1702-2 331035 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10

MOS GB SMO INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 MOS GB 0735-3 SMO 10 511882 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE SMO 10 Contents General System diagram 3 Principle of operation 3 Abbreviations 3 Front panel Display 4 Switch 5 Offset heating

More information

User manual NIBE F370

User manual NIBE F370 User manual Exhaust air heat pump LEK UHB GB 1722-3 231437 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the

More information

NIBE F470 A + Complete heat pump unit that provides heating, hot water, ventilation, heated supply air and heat recovery. Exhaust air heat pump

NIBE F470 A + Complete heat pump unit that provides heating, hot water, ventilation, heated supply air and heat recovery. Exhaust air heat pump NIBE F470 Exhaust air heat pump Complete heat pump unit that provides heating, hot water, ventilation, heated supply air and heat recovery Display unit with easytoread colour screen. It also gives you

More information

NIBE VVM 300. Intelligent hot water NIBE VVM 300. VVM 300 is designed for connection and communication

NIBE VVM 300. Intelligent hot water NIBE VVM 300. VVM 300 is designed for connection and communication NIBE VVM 300 all in one indoor unit Intelligent hot water VVM 300 is designed for connection and communication with outdoor heat pump F20XX of 6 kw, 8 kw and 10 kw. Water volume 280 litres, of which 155

More information

Installer manual NIBE ERS

Installer manual NIBE ERS Installer manual Ventilation heat exchanger LEK IHB EN 1743-4 331812 Table of Contents 1 Important information 4 9 Service 18 Safety information 4 Water seal for condensation water 18 Serial number 4

More information

air/water heat pump. NIBE F2040 provides

air/water heat pump. NIBE F2040 provides NIBE.EU Air/water heat pump NIBE F2040 NIBE F2040 is an intelligent and compact invertercontrolled air/water heat pump. NIBE F2040 provides optimum savings since the heat pump automatically adapts to your

More information

Diplomat Inverter/Diplomat Duo Inverter

Diplomat Inverter/Diplomat Duo Inverter www.thermia.com The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC) Copyright Thermia Värmepumpar Table of

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

Installer manual NIBE F470

Installer manual NIBE F470 Installer manual Exhaust air heat pump LEK IHB GB 1549-2 231450 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

Ground source heat pump NIBE F1255

Ground source heat pump NIBE F1255 NIBE.EU Ground source heat pump NIBE F1255 NIBE F1255 is an intelligent, inverter-controlled ground source heat pump with integrated water heater. NIBE F1255 provides optimum savings since the heat pump

More information

Operating manual NIBE F1355

Operating manual NIBE F1355 Operating manual Ground source heat pump LEK OHB GB 1716-2 431340 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

Installer manual NIBE F370

Installer manual NIBE F370 Installer manual Exhaust air heat pump LEK IHB GB 1536-2 231470 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

Heating when you need it Cooling when you don t

Heating when you need it Cooling when you don t when you need it Cooling when you don t NIBE SPLIT air/water heat pump NIBE SPLIT is a system for heating, cooling and producing hot water for variety of house sizes It gives you an optimal annual heating

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS F F2025

INSTALLATION AND MAINTENANCE INSTRUCTIONS F F2025 MOS GB 0840-3 INSTALLATION AND MAINTENANCE INSTRUCTIONS 031185 LEK Table of Contents For Home Owners General System description Principle of operation 3 Maintenance routines General 4 For the Installer

More information

User manual NIBE F370 1x230 V

User manual NIBE F370 1x230 V User manual 1x230 V Exhaust air heat pump LEK UHB GB 1722-3 231435 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

User and Installer manual NIBE UKV 20

User and Installer manual NIBE UKV 20 User and Installer manual 20-500, 20-750, 20-1000 Accumulator tank CHB EN 1743-1 431416 Table of Contents 1 Important information 2 For the User 3 For the Installer 4 Technical data Contact information

More information

Indoor module NIBE VVM 500

Indoor module NIBE VVM 500 UHB EN 1834-7 431240 Indoor module USER MANUAL Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button functions

More information

Installer manual NIBE F370

Installer manual NIBE F370 Installer manual Exhaust air heat pump LEK IHB GB 1608-4 231436 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation

More information

Installer manual NIBE F1155PC

Installer manual NIBE F1155PC Installer manual Ground source heat pump LEK IHB GB 1644-5 331168 Quick guide Navigati Ok butt (cfirm/select) Back butt (back/undo/exit) Ctrol knob (move/increase/reduce) A detailed explanati of the butt

More information

Installer manual NIBE F , 12, 16 kw UK 1x230V Air/water heat pump IHB GB LEK LEK LEK

Installer manual NIBE F , 12, 16 kw UK 1x230V Air/water heat pump IHB GB LEK LEK LEK Installer manual 8, 12, 16 kw UK 1x230V Air/water heat pump IHB GB 1512-3 231846 Table of Contents 1 Important information Safety information 2 Delivery and handling 2 2 5 Compressor heater Start-up and

More information

User manual NIBE SMO 05

User manual NIBE SMO 05 LEK User manual Accessories LEK AHB GB 1020-1 031523 A detailed explanation of the button functions can be found on page 10. How to scroll through menus and make different settings is described on page

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS MOS GB NIBE VVM 300 UK NIBE VVM 300 UK 230 V VVM 300 LEK

INSTALLATION AND MAINTENANCE INSTRUCTIONS MOS GB NIBE VVM 300 UK NIBE VVM 300 UK 230 V VVM 300 LEK A B I II III A B I II I II A B -2 0 +2 MOS GB 1027-6 NIBE VVM 300 UK 031142 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE VVM 300 UK 230 V VVM 300 2 1 5 4 3 Contents User guide General Principle of operation

More information

Planning guide. Atec.

Planning guide. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

Installer manual NIBE F135

Installer manual NIBE F135 Installer manual Exhaust air module IHB GB 1622-4 331432 Table of Contents 1 Important information 4 Index 34 Safety information 4 2 Delivery and handling 7 Transport 7 Assembly 7 Supplied components

More information

User manual NIBE VVM 320

User manual NIBE VVM 320 User manual Indoor module APH UHB EN 1751-5 231358 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button

More information

NIBE F750 A +++ Flexible, high-performance exhaust air heat pump. Exhaust air heat pump

NIBE F750 A +++ Flexible, high-performance exhaust air heat pump. Exhaust air heat pump NIBE F750 Exhaust air heat pump Flexible, highperformance exhaust air heat pump Energy and power efficient exhaust air heat pump with inverter controlled compressor. Display unit with easytoread colour

More information

User manual NIBE SMO 05. Accessories UHB GB LEK

User manual NIBE SMO 05. Accessories UHB GB LEK LEK User manual Accessories LEK UHB GB 1339-2 431198 A detailed explanation of the button functions can be found on page 10. How to scroll through menus and make different settings is described on page

More information

User manual AG-WT10. Indoor unit air/air heat pump UHB GB

User manual AG-WT10. Indoor unit air/air heat pump UHB GB User manual Indoor unit air/air heat pump UHB GB 1516-1 331557 Table of Contents 1 Important information Installation data Safety information Serial number an excellent choice Safety instructions Recovery

More information

Operating manual NIBE F1345. Ground source heat pump OHB GB LEK

Operating manual NIBE F1345. Ground source heat pump OHB GB LEK Operating manual Ground source heat pump LEK OHB GB 1210-2 031838 A detailed explanation of the button functions can be found on page 6. How to scroll through menus and make different settings is described

More information

Planning guide. (2010/09) en

Planning guide. (2010/09) en Planning guide (2010/09) en 1 Planning guide for Greenline HE E 21, 28 and HE D 36, 43 Page Contents 3 Documentation and VPW2100 4 Technical data of heatpump 5 Dimensioning of DHW systems 6 Symbol explanations

More information

User manual NIBE F1145PC

User manual NIBE F1145PC User manual Ground source heat pump LEK UHB GB 1644-4 231789 Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of

More information

Installer manual NIBE F2120

Installer manual NIBE F2120 Installer manual 8, 12, 16, 20 Air/water heat pump LEK IHB GB 1718-1 431357 Table of Contents 1 Important information 4 9 Alarm list 42 Safety information 2 Delivery and handling Transport and storage

More information

MAKING MODERN LIVING POSSIBLE. Wiring Diagram. DHP-iQ.

MAKING MODERN LIVING POSSIBLE. Wiring Diagram. DHP-iQ. MAKING MODERN LIVING POSSIBLE Wiring Diagram www.heating.danfoss.com Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English

More information

MOS GB NIBE VVM INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE VVM 300 VVM 300 LEK

MOS GB NIBE VVM INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE VVM 300 VVM 300 LEK A B I II III A B I II I II A B -2 0 +2 MOS GB 0821-4 NIBE VVM 300 511806 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE VVM 300 VVM 300 LEK 2 1 LEK LEK 5 4 3 LEK LEK Contents User guide General Principle

More information

Installer manual NIBE F1255

Installer manual NIBE F1255 Installer manual Ground source heat pump LEK IHB EN 17455 331296 Quick guide Navigati Ok butt (cfirm/select) Back butt (back/undo/exit) Ctrol knob (move/increase/reduce) A detailed explanati of the butt

More information

User manual NIBE F110

User manual NIBE F110 User manual Hot water heat pump LEK UHB GB 1434-1 231975 A detailed explanation of the button functions can be found on page 10. How to scroll through menus and make different settings is described on

More information

Installation Guide. Twin Kit 086L1370

Installation Guide. Twin Kit 086L1370 086L1370 Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions. Other languages

More information