1 Chapter 5 Traps, Cleanouts and Backwater Valves 5.1 SEPARATE TRAPS FOR EACH FIXTURE a. Plumbing fixtures shall be separately trapped by a water seal trap placed as close as possible to the fixture outlet. b. The vertical distance from the fixture outlet to the trap weir shall not exceed 24 inches. c. Fixtures shall not be double-trapped unless a relief vent is provided between the two traps. d. Fixture designs having integral dual traps within the fixture shall be permitted. EXCEPTIONS: (1) Fixtures that have integral traps. (2) Interceptors in Chapter 6 that provide the required trap seal. Note: Interceptors in Chapter 6 that do not provide the required trap seal shall be provided with a separate trap. (3) A combination plumbing fixture may be installed on one trap provided the waste outlets are not more than 30 inches apart. (4) One trap may be installed for a 2 or 3-compartment sink or up to three (3) lavatories that are immediately adjacent to each other in the same room, and where the trap is centrally located when three such fixtures are installed. (5) No clothes washer or laundry sink shall be discharged to a trap serving a kitchen sink. (6) As otherwise permitted by this Code. 5.2 SIZE OF FIXTURE TRAPS Fixture trap size (nominal diameter) shall be sufficient to drain the fixture rapidly and in no case less than given in Table 5.2. No trap shall be larger than the drainage pipe into which it discharges. Integral traps shall conform to appropriate standards. 5.3 GENERAL REQUIREMENTS FOR TRAPS Design of Traps Fixture traps shall be self-scouring and shall have no interior partitions except where such traps are integral with the fixture or where corrosion resistant materials of plastic or glass are used. Solid connections, slip joints, or couplings may be used on the trap inlet, trap outlet, or within the trap seal. (See Section ) 2009 National Standard Plumbing Code 79

2 Table 5.2 MINIMUM SIZE OF NON-INTEGRAL TRAPS Plumbing Fixture Trap Size in inches Bathtub (with or without overhead shower) 1-1/2 Bidet 1-1/4 Clothes washing machine standpipe 2 Combination sink and wash (laundry) sink with food waste grinder unit 1-1/2 (1) Combination kitchen sink, domestic dishwasher, and food waste grinder 1-1/2 Dental unit or cuspidor 1-1/4 Dental lavatory 1-1/4 Drinking fountain 1-1/4 Dishwasher, commercial 2 Dishwasher, domestic (non-integral trap) 1-1/2 Floor drain 2 Food waste grinder, commercial use 2 Food waste grinder, domestic use 1-1/2 Kitchen sink, domestic, with food waste grinder unit 1-1/2 Kitchen sink, domestic 1-1/2 Lavatory, common (private and public) 1-1/4 Lavatory (barber shop, beauty parlor or surgeon s) 1-1/2 Lavatory, multiple type (wash fountain or wash sink) 1-1/2 Laundry tray (1 or 2 compartments) 1-1/2 Shower stall or shower drain (single shower head) 1-1/2 Shower stall or shower drain (multiple shower heads) 2 Sink (surgeon s) 1-1/2 Sink (flushing rim type, flush valve supplied) 3 Sink (service type with floor outlet trap standard) 3 Sink (service type with P trap) 2 Sink, commercial (pot, scullery, or similar type) 2 Sink, commercial (with food grinder unit) 2 NOTES FOR TABLE 5.2 (1) Separate trap required for wash tray and separate trap required for sink compartment with food waste grinder Trap Seals Each fixture trap shall have a liquid seal of not less than two inches and not more than four inches. EXCEPTIONS: (1) Interceptors in Chapter 6 that provide the required trap seal. Note: Interceptors in Chapter 6 that do not provide the required trap seal shall be provided with a separate trap. (2) Special conditions such as accessible fixtures, a deeper seal may be required by the Authority Having Jurisdiction Trap Setting and Protection Traps shall be set level with respect to their water seals and, where necessary, shall be protected from freezing National Standard Plumbing Code

3 5.3.4 Building Traps Building traps shall not be installed except where required by the Authority Having Jurisdiction. Each building trap when installed shall be provided with a cleanout and with a relieving vent or fresh air intake on the inlet side of the trap that shall be at least one-half the diameter of the drain to which it connects. Such relieving vent or fresh air intake shall be carried above grade and terminate in a screened outlet located outside the building Prohibited Traps a. The following types of traps shall be prohibited: 1. Traps that depend upon moving parts to maintain their seal. 2. Bell traps. 3. Crown vented traps. 4. Separate fixture traps that depend on interior partitions for their seal, except if made from plastic, glass or other corrosion resistant materials. 5. S traps, of uniform internal dimension. 6. Drum traps. b. Hair interceptors, precious metal interceptors and similar appurtenances shall be permitted as required Trap Seal Maintenance a. Traps that could lose their seal due to evaporation because of infrequent use shall have accessible means to replenish the trap seal or be connected to a trap primer conforming to ASSE 1018 or ASSE b. In addition to the priming requirements of Section a, floor drains shall be permitted to be fitted with a barrier type floor drain trap seal protection device complying with ASSE DRAINAGE PIPE CLEANOUTS Cleanout Spacing a. Cleanouts in horizontal drainage lines shall be spaced at intervals not exceeding the following values: 4" pipe size or less: 75 feet 5" size and larger: 100 feet b. The distance referred to in Sections 5.4.1a shall include the developed length of the cleanout pipe Building Sewer Cleanouts, when installed on an underground building sewer, shall be extended vertically to or above the finished grade level Change of Direction a. Cleanouts shall be installed at changes of direction in drainage piping made with 60, 70 and 90 fittings. EXCEPTION: Where there are multiple changes of direction, not more than one cleanout shall be required in 40 feet of run. b. Cleanouts shall not be required where changes of direction are made with one or more 22 1/2 or 45 fittings Cleanouts for Concealed Piping Cleanouts for concealed piping shall be extended through and terminate flush with the finished wall or floor; or pits or chases may be left in the wall or floor, provided they are of sufficient size to permit removal of the cleanout plug and proper cleaning of the system National Standard Plumbing Code 81

4 5.4.5 Base of Stacks a. A cleanout shall be provided near the base of each vertical waste or soil stack and located 6 inches above the flood level rim of the lowest fixture on the lowest floor. If there are no fixtures installed on the lowest floor, the cleanout shall be installed at the base of the stack. b. For buildings with a floor slab, a crawl space of less than 18 inches, or where a stack cleanout is not accessible, the cleanout shall be installed in the building drain or building sewer, not more than five feet outside the building wall. c. Rain leaders and conductors connected to a building storm sewer shall have a cleanout installed at the base of the outside leader or inside conductor before it connects to the horizontal drain Building Drain and Building Sewer Junctions and the Property Line a. There shall be a cleanout near the junction of a building drain and building sewer either inside or outside the building wall. b. Cleanouts shall be placed in the building sanitary sewer and the building storm sewer at the property line and brought to the surface in accordance with the requirements of the Adopting Agency Direction of Flow Cleanouts shall be installed so that the cleanout opens in the direction of the flow of the drainage line or at right angles thereto Connections to Cleanouts Prohibited a. Cleanout plug openings in other than drainage pattern fittings shall not be used for the installation of new fixtures or floor drains. b. If a cleanout fitting or cleanout plug opening is removed from a drainage pattern fitting in order to extend the drain, another cleanout of equal access and capacity shall be provided in the same location Cleanout Size Cleanout size shall conform with Table Table SIZE OF CLEANOUTS Nominal Nominal Piping Size (inches) Size of Cleanout (inches) 1-1/4 1-1/4 1-1/2 1-1/ & & & 15 8 NOTES FOR TABLE (1) See Section for sizes 12" or larger for building sewers. (2) See Section for cleanout equivalents National Standard Plumbing Code

5 Manholes for Large Pipes a. Manholes shall be provided as cleanouts for building sewers 12" size and larger. Manholes shall be provided at every change of size, alignment, direction, grade, or elevation. The distance between manholes shall not exceed 300 feet. b. Manholes may be provided in lieu of cleanouts in underground building sewers, building drains, and branches thereof, 8" size and larger. c. Such manholes shall comply with the requirements of Section a. d. If manholes are installed indoors, they shall have a bolted, gas-tight cover. e. Manhole construction shall comply with the standards of the Authority Having Jurisdiction Cleanout Clearances Cleanouts on 3" or larger pipes shall be so installed that there is a clearance of not less than 18" for the purpose of rodding. Cleanouts smaller than 3 inches shall be so installed that there is a 12" clearance for rodding Cleanouts to be Kept Uncovered Cleanout plugs shall not be covered with cement, plaster, or any other permanent finishing material. Where it is necessary to conceal a cleanout plug, a covering plate or access door shall be provided that will permit access to the plug Cleanout Equivalent Where the piping is concealed, a fixture trap or a fixture with integral trap, removable without disturbing concealed roughing work, shall be accepted as a cleanout equivalent, provided the opening to be used as a cleanout opening is the size required by Table EXCEPTIONS: (1) The trap arm of a floor drain with a removable strainer. (2) Fixtures with removable traps not more than one pipe size smaller than the drain served shall be permitted Cleanouts for Floor Drains A cleanout shall be provided immediately downstream from a floor drain whose strainer is not removable. 5.5 BACKWATER VALVES Where Required a. Fixtures and/or drain inlets subject to backflow and overflow from blocked or restricted public sewers shall be protected by a backwater valve. b. Such situations include those where the flood level rim of fixtures and/or drain inlets are below the overflow level of the first upstream manhole in the public sewer that will overflow due to a blockage or flow restriction in the public sewer. c. Backwater valves shall be installed in drainage piping that receives flow only from fixtures and/or drains that are subject to backflow from public sewers. d. Other portions of the drainage system not subject to such backflow shall not drain through a backwater valve National Standard Plumbing Code 83

6 5.5.2 Material Standard and Accessibility Backwater valves shall conform to ASME A and be installed so that their internal working parts are accessible for periodic cleaning, repair or replacement Notice of the Installation of Backwater Valves When backwater valves are installed in building sanitary drainage systems, a notice shall be posted at the building water service shutoff valve(s) describing where backwater valves are located National Standard Plumbing Code

CHAPTER 10 TRAPS AND INTERCEPTORS

CHAPTER 10 TRAPS AND INTERCEPTORS CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved

More information

Read Only Document Not For Distribution

Read Only Document Not For Distribution Chapter 9 Indirect Waste Piping and Special Wastes 9.1 INDIRECT WASTES 9.1.1 General Drains from fixtures, fixture compartments, equipment, appliances, appurtenances, and other devices requiring protection

More information

STACKS AND STACK VENTS

STACKS AND STACK VENTS CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing

More information

Level I Chapter 1 Worksheet

Level I Chapter 1 Worksheet Chapter 1 Worksheet 1. For applicability requirements of the Plumbing Code, refer to: a. Building Code b. Administration and Enforcement Code c. Plumbing Code d. Residential Code 2. The provisions of the

More information

MATERIALS Traps TRAPS. No. IPC IRC Description

MATERIALS Traps TRAPS. No. IPC IRC Description MATERIALS Traps TRAPS MAX " MAX 0" No. IPC IRC Description 00. P0.6 00. P0.6 00. P0. 00. () P0.6 Exc. Vertical distance from fixture to the trap weir can not exceed ". Horizontal distance from the fixture

More information

CHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R

CHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R CHAPTER 31 VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R This page left intentionally blank. 426R 2003 INTERNATIONAL RESIDENTIAL CODE For SI: PIPE SIZE (inches) TABLE P3107.3 COMMON VENT SIZES

More information

Sanitary Drainage Systems

Sanitary Drainage Systems 11.1 MATERIALS See Section 3.1. Sanitary Drainage Systems 11.2 BUILDING SEWERS AND BUILDING DRAINS 11.2.1 Sewer or Drain in Filled Ground Chapter 11 Building sewers or building drains that are installed

More information

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Ohio Administrative Code Rule Number OPC Section IPC origin Reason for proposed 4101:3-2-01 Alternate on-site 2015 Added definition

More information

PLUMBING REQUIREMENTS

PLUMBING REQUIREMENTS PLUMBING REQUIREMENTS This handout is a compilation of the standard requirements based on the State Plumbing Code and City Ordinance for projects of this type. This information sheet does not contain all

More information

CHAPTER 9 VENTS. run undiminished in size and as directly as possible from the building drain through to the open air above the roof.

CHAPTER 9 VENTS. run undiminished in size and as directly as possible from the building drain through to the open air above the roof. CHAPTER 9 VENTS SECTION 90 GENERAL run undiminished in size and as directly as possible from the building drain through to the open air above the roof. 90. Scope. The provisions of this chapter shall govern

More information

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. ICP Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A 1 inch diameter faucet, where the inside edge of the spout opening is 2.5 inches away

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

CHaPTeR 10. TRaPS and INTeRCePTORS. Table 10-1 Horizontal lengths of Trap arms (except for water closets and similar fixtures)*

CHaPTeR 10. TRaPS and INTeRCePTORS. Table 10-1 Horizontal lengths of Trap arms (except for water closets and similar fixtures)* CHaPTeR 10 TRaPS and INTeRCePTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved

More information

CHAPTER 10 TRAPS AND INTERCEPTORS The vent pipe opening from a soil or waste No more than one (1) approved slip joint

CHAPTER 10 TRAPS AND INTERCEPTORS The vent pipe opening from a soil or waste No more than one (1) approved slip joint CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved

More information

CHAPTER 9 VENTS SECTION

CHAPTER 9 VENTS SECTION CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing

More information

CHAPTER 10 TRAPS AND INTERCEPTORS TABLE 10-1 HORIZONTAL LENGTHS OF TRAP ARMS (EXCEPT FOR WATER CLOSETS AND SIMILAR FIXTURES) 1, 2

CHAPTER 10 TRAPS AND INTERCEPTORS TABLE 10-1 HORIZONTAL LENGTHS OF TRAP ARMS (EXCEPT FOR WATER CLOSETS AND SIMILAR FIXTURES) 1, 2 CHAPTER 10 TRAPS AND INTERCEPTORS < 1001.0 Traps Required. Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.1, shall be separately trapped by an approved type

More information

Pipe Sizing Table. Hydraulic Load Served (fixture units)

Pipe Sizing Table. Hydraulic Load Served (fixture units) MODULE 1 INTRODUCTION Notes: A Pipe Type Horizontal branch Pipe Sizing Table Hydraulic Load Served (fixture units) Size (in.) Code Reference 2 + 1.5 = 3.5 2 7.4.9.1.(1) B Soil stack 13.5 + 13.5 = 27 3

More information

GIANT. Little. Guidelines for Sizing. Pump Company. Sewage Pumps & Systems. Sewage Pumps & Systems

GIANT. Little. Guidelines for Sizing. Pump Company. Sewage Pumps & Systems. Sewage Pumps & Systems Sewage Pumps & Systems GIANT Little Pump Company Guidelines for Sizing Sewage Pumps & Systems These guidelines cover the steps that need to be taken to accurately select the correct sewage pump and applicable

More information

CHAPTER VI BUILDING PLUMBING

CHAPTER VI BUILDING PLUMBING CHAPTER VI BUILDING PLUMBING 6.1. INTRODUCTION The chapter covers questions related to water demand, distribution and drainage. The basic principles for planning and installing common plumbing systems

More information

Wastewater. Guidelines for Sizing mscdirect.com. Call MSC today to learn about the latest LittleGiant products.

Wastewater. Guidelines for Sizing mscdirect.com. Call MSC today to learn about the latest LittleGiant products. Wastewater Guidelines for Sizing Features These guidelines cover the steps which need to be taken to accurately select the correct sewage pump and applicable systems to use in sewage ejectors. Work through

More information

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. The minimum air gap for a fixture with an effective open of 1/2", located away from a

More information

CHAPTER 10 TRAPS AND INTERCEPTORS

CHAPTER 10 TRAPS AND INTERCEPTORS CAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved

More information

TABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General...

TABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General... TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION................1 101.0 Title, Scope, and General...........1 101.1 Title............................1 101.2 Purpose.........................1 101.3 Plans Required...................1

More information

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X X

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X X CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 10 - TRAPS AND INTERCEPTORS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority

More information

2016 Plumbing Supplemental Plan Review List

2016 Plumbing Supplemental Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for

More information

PLUMBING FIXTURES CHAPTER 27

PLUMBING FIXTURES CHAPTER 27 CHAPTER 27 PLUMBING FIXTURES SECTION P2701 FIXTURES, FAUCETS AND FIXTURE FITTINGS P2701.1 Quality of fixtures. Plumbing fixtures, faucets and fixture fittings shall be constructed of approved materials,

More information

PLUMBING INSTALLATIONS

PLUMBING INSTALLATIONS PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT PLUMBING INSTALLATIONS A homeowner guide to plumbing requirements for single-family dwellings November 2017 contents Permit Requirements... 3 Inspection Requirements...

More information

1 Exam Prep Plumber s Handbook Tabs and Highlights

1 Exam Prep Plumber s Handbook Tabs and Highlights 1 Exam Prep Plumber s Handbook Tabs and Highlights These 1 Exam Prep Tabs are based on the Plumber s Handbook Revised 2006. Each Tabs sheet has five rows of tabs. Start with the first tab at the first

More information

2015 UPC CODE - CHAPTER 8 INDIRECT WASTES

2015 UPC CODE - CHAPTER 8 INDIRECT WASTES 801.0 General. 2015 UPC CODE - CHAPTER 8 INDIRECT WASTES 801.1 Applicability. This chapter shall govern the materials, design, and installation of indirect waste piping, receptors, and connections; and

More information

APPENDIX L ALTERNATE PLUMBING SYSTEMS

APPENDIX L ALTERNATE PLUMBING SYSTEMS ALTERNATE PLUMBING SYSTEMS L 1.0 General. L 1.1 Applicability. The intent of this appendix is to provide clarification of procedures for the design and approval of engineered plumbing systems, alternate

More information

2015 UPC Chapter 8 Indirect Wastes RV

2015 UPC Chapter 8 Indirect Wastes RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

Special Requirements For Health Care Facilities

Special Requirements For Health Care Facilities Chapter 14 Special Requirements For Health Care Facilities 14.1 GENERAL This Chapter applies to special fixtures and systems that occur in health care facilities and to the special plumbing requirements

More information

PLUMBING FIXTURES Reserved

PLUMBING FIXTURES Reserved CHAPTER 27 PLUMBING FIXTURES Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 395R This page left intentionally blank. 396R 2003 INTERNATIONAL RESIDENTIAL CODE SECTION P2708 SHOWERS P2708.1 General. Shower

More information

Matrix of changes for the National Standard Plumbing Code July 2013

Matrix of changes for the National Standard Plumbing Code July 2013 Matrix of changes for the National Standard Plumbing Code July 2013 Item # Section Number Person Submitting Change Committee Action 10-77 10.20.8 and Table 3.1.3 XI Certification 10-82 12.16 Size and Lengths

More information

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A vent stack handling 25 dfu s with a developed length of 35 feet shall be inches minimum

More information

Pro Vent TM. Provent Systems Inc Capital Circle Lawrenceville Georgia

Pro Vent TM. Provent Systems Inc Capital Circle Lawrenceville Georgia Pro Vent TM Guide to Design and Usage Provent Single System Handling Installation Corrosion Ease Simplicity Resistance IPMO Copyright (c) 2014, Pro Vent Systems Inc., plus *2016 Revisions ll Rights Reserved

More information

Drain and Vent Systems 6 CE Hours

Drain and Vent Systems 6 CE Hours Drain and Vent Systems 6 CE Hours Wisconsin Contractors Institute N27 W23953 Paul Road, Suite 203 Pewaukee, WI 53072 www.wicontractorsinstitute.com 262-409-4282 What is the purpose of this course? The

More information

Read Only Document Not For Distribution

Read Only Document Not For Distribution Chapter 14 Special Requirements For Health Care Facilities 14.1 GENERAL This Chapter applies to special fixtures and systems that occur in health care facilities and to the special plumbing requirements

More information

Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC

Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC People Helping People Build a Safer World Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC Installation, Flexibility and Opportunity for Savings Lee Clifton, Senior Director of PMG Resources,

More information

Read Only Copy Not For Distribution. Chapter 10. Water Supply and Distribution 10.1 QUALITY OF WATER SUPPLY 10.2 RESERVED 10.

Read Only Copy Not For Distribution. Chapter 10. Water Supply and Distribution 10.1 QUALITY OF WATER SUPPLY 10.2 RESERVED 10. Water Supply and Distribution 10.1 QUALITY OF WATER SUPPLY a. Only potable water shall be supplied to plumbing fixtures used for drinking, bathing, culinary use or the processing of food, medical or pharmaceutical

More information

Building Utilities 1 Plumbing and Sanitary Systems

Building Utilities 1 Plumbing and Sanitary Systems Building Utilities 1 Plumbing and Sanitary Systems Taken from UST Architecture exams by Arch. Rafael Alli Recommended review material for UST Preboard Exam Prepared by: arkireviewph.multiply.com Types

More information

STUDENT NOTES Plan, size and layout sanitary pipe work and fixtures

STUDENT NOTES Plan, size and layout sanitary pipe work and fixtures 4. SANITARY PLUMBING FULLY VENTED SYSTEM On completion of this module, the student should be able to: Design, install and develop bills of quantities for a fully vented modified system for commercial and

More information

Is Sewer Gas Giving Your Customers the Wrong Impression?

Is Sewer Gas Giving Your Customers the Wrong Impression? Is Sewer Gas Giving Your Customers the Wrong Impression? Prepared by Dialectic INTRODUCTION We ve all been there. You walk into a public restroom and you immediately wonder if one of the toilets is overflowing.

More information

INSPECTION OF COMMERCIAL KITCHEN PLUMBING

INSPECTION OF COMMERCIAL KITCHEN PLUMBING INSPECTION OF COMMERCIAL KITCHEN PLUMBING 801.1 SCOPE Food-handling establishments 2 - by John Williams, Jr. Plumbing Control Supervisor Onondaga County Water Environment Protection Commercial Kitchens

More information

TABLE OF CONTENTS Limitations of Authority...6 Table Plumbing Permit Fees...7

TABLE OF CONTENTS Limitations of Authority...6 Table Plumbing Permit Fees...7 TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION.............1 101.0 General.......................1 101.1 Title..........................1 101.2 Scope........................1 101.3 Purpose......................1

More information

1 Exam Prep Plumbing State Contractors Practice Exam 2

1 Exam Prep Plumbing State Contractors Practice Exam 2 1 Exam Prep Plumbing State Contractors Practice Exam 2 1 According to Chapter 64E-6, when sizing a grease interceptor used in a restaurant, the correct formula is. A. (S) x (EW 12) x (LF) B. (S) x (GS)

More information

APPENDIX J ILLUSTRATIONS

APPENDIX J ILLUSTRATIONS The following figures have been included in the 1994 edition of the Standard Plumbing Code to aid in interpreting this code. The figures are not to be construed as superseding the written text, but merely

More information

TABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General...

TABLE OF CONTENTS. CHAPTER 2 DEFINITIONS General Applicability Definition of Terms General... TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION..............1 101.0 General.......................1 101.1 Title..........................1 101.2 Scope........................1 101.3 Purpose......................1

More information

Plumbing. Definitions. Background Factors. Air Chambers. Air Gap (Drainage System) Air Gap (Water Distribution System) Air Lock.

Plumbing. Definitions. Background Factors. Air Chambers. Air Gap (Drainage System) Air Gap (Water Distribution System) Air Lock. Plumbing Plumbing may be defined as practice, materials, and fixtures used in the installation, maintenance, and alteration of all piping, fixtures, appliances, and appurtenances in connection with sanitary

More information

Land Use and Environmental Service Agency (Code Enforcement) Plumbing 2010

Land Use and Environmental Service Agency (Code Enforcement) Plumbing 2010 General: 1) (Q) Who enforces the cutting and notching requirements found in the plumbing code? (A) The plumbing inspector would question the contractor initially. A building inspector would either take

More information

WATER HAMMER ARRESTORS & MISC. SPECIALTIES

WATER HAMMER ARRESTORS & MISC. SPECIALTIES TABLE OF CONTENTS Pictorial Index Water Hammer Arrestors Certification Sizing & Placement Backwater Valves Typical Installations Trap Seal Primers Compliance Pressure & Flow Characteristics Typical Installations

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#58619/Page 1/November 1, 2017 PLUMBING Executive Summary: Presently, the Plumbing Systems serving the building are cold water, hot water, sanitary, waste and vent system, storm drain piping, and natural

More information

plumbing for greywater

plumbing for greywater plumbing for greywater october 2015 christina bertea ~union trained journeywoman plumber (1978) ~plumbing contractor (1996) ~greywater action singingwater@jps.net plumbing for greywater basic parts of

More information

2006 Thermaco, Inc. All rights reserved Patented/Patents Pending Specifications subject to change without notice

2006 Thermaco, Inc. All rights reserved Patented/Patents Pending Specifications subject to change without notice One to Three Compartment Sink When planning a multiple fixture discharge into a single Big Dipper, establish the size unit required by following the method outlined in the sizing section of this manual.

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Faucets for lavatories, bathtubs, bathtub/showers, showers and sinks. 2. Flushometers. 3. Toilet

More information

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT PLUMBING. Test Code: 5924 Version: 01

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT PLUMBING. Test Code: 5924 Version: 01 CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT PLUMBING Test Code: 5924 Version: 01 Specific competencies and skills tested in this assessment: Safety Follow rules for fire safety Follow rules for housekeeping

More information

c. Direct or indirect?

c. Direct or indirect? ~ \ 1.) GENERAL a. Definitions: Chapter B Code References (1) Air-break Comm 81.01 (5) (2) Air-gap, drain system Comm 81.01 (6) (3) Flood level rim Comm 81.01(102) (4) sink Comm 81.01(105) (5) Indirect

More information

APPENDIX A. A 3.2 Determine the elevation of the highest. A 3.3 Subtract the sum of loss in static pressure

APPENDIX A. A 3.2 Determine the elevation of the highest. A 3.3 Subtract the sum of loss in static pressure APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes

More information

Schedule of Fees Schedule B

Schedule of Fees Schedule B Schedule of Fees Schedule B BUILDING DEPARTMENT 2. Building Permit* $65.00 for value or valuation up to $1,000. After $1,000 of value $8.00 per $1,000. After $1,000,000 of value $6 per $1,000 3. Demolition

More information

FIXTURES, FAUCETS AND FIXTURE FITTINGS

FIXTURES, FAUCETS AND FIXTURE FITTINGS CHAPTER 4 FIXTURES, FAUCETS AND FIXTURE FITTINGS SECTION 401 GENERAL 401.1 Scope. This chapter shall govern the materials, design and installation of plumbing fixtures, faucets and fixture fittings in

More information

2012 Virginia Plumbing Code & VRC (Plumbing) Update Training

2012 Virginia Plumbing Code & VRC (Plumbing) Update Training 2012 Virginia Plumbing Code & VRC (Plumbing) Update Training ----------------------------- Henrico County Department of Building Construction and Inspections Introduction This presentation was prepared

More information

1. You are required to use a 20 foot ladder placed up against a building that is 40 high. At what

1. You are required to use a 20 foot ladder placed up against a building that is 40 high. At what This practice exam will require you to have a calculator, pencil, scrap paper, a copy of the 2005 National Plumbing Code and will contain many similar questions as the current Plumbing Red Seal trade certification.

More information

I. Best Management Practices (BMPs) to Prevent Blockages in the Sanitary Sewer System

I. Best Management Practices (BMPs) to Prevent Blockages in the Sanitary Sewer System BMP Train kitchen staff and other employees about how they can help ensure BMPs are implemented. Post "No Grease" signs above sinks and on the front of dishwashers. I. Best Management Practices (BMPs)

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.

More information

CHAPTER 2 DEFINITIONS

CHAPTER 2 DEFINITIONS CHAPTER 2 DEFINITIONS 201 GENERAL 201.1 Scope For the purpose of this code, certain abbreviations, terms, phrases, words and their derivatives shall be construed as set forth in this chapter or the chapter

More information

ENERGY MARKETING SERVICES

ENERGY MARKETING SERVICES 1 IMPORTANT STUFF This manual has been designed as a supplemental aid for students preparing to take the Plumbing Exam based on the international codes. It is not intended to replace any manuals or material

More information

2009 IPC ,IMC Q &A ANDIFGC

2009 IPC ,IMC Q &A ANDIFGC 2009 IPC,IMC ANDIFGC Q &A TABLE OF CONTENTS PREFACE.... ix ABOUT THE INTERNATIONAL CODE COUNCIL...x IPC CHAPTER 1 SCOPE AND ADMINISTRATION...1 Section 101 General... 1 Section 102 Applicability... 1 Section

More information

2. Sanitary Plumbing General Installation Requirements

2. Sanitary Plumbing General Installation Requirements 2. Sanitary Plumbing General Installation Requirements On completion of this section, students should be able to: Identify and describe sanitary plumbing installations requirements in accordance with the

More information

CONTINUING EDUCATION UPC Definitions Code Course. 4 hours Course # ID09143 (CODE) PO Box Spokane, WA

CONTINUING EDUCATION UPC Definitions Code Course. 4 hours Course # ID09143 (CODE) PO Box Spokane, WA AMERICAN PLUMBING INSTITUTE 2015 33 CONTINUING EDUCATION PO Box 31131 Spokane, WA 99223-3018 www.apiceu.com 2009 UPC Definitions Code Course 4 hours Course # ID09143 (CODE) DISCLAIMER NOTE: This course

More information

ASME STANDARDS IN MODEL CODES

ASME STANDARDS IN MODEL CODES STANDARDS IN MODEL CODES ASME Name Model Code With Year of Referenced IPC IRC UPC 2009 NSPC A112.1.2 Air Gaps in Plumbing 2004 2004 2004 2004 A112.1.3 Air Gap Fittings For Use With Plumbing, Appliances

More information

DOMESTIC WATER PACKAGED BOOSTER PUMPS

DOMESTIC WATER PACKAGED BOOSTER PUMPS DIVISION 22 PLUMBING 22 11 16 DOMESTIC WATER PIPING 22 11 19 DOMESTIC WATER PIPING SPECIALTIES 1. To facilitate landscape and other maintenance operations, exterior hose bibs shall be provided at 150 foot

More information

CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM 1 2 1/AC AC SS SS/CC

CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM 1 2 1/AC AC SS SS/CC CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Adopting Agency BSC SFM HCD DSA OSHPD CSA DPH AGR DWR CA 1 2 1/AC AC SS SS/CC 1 2 3 4 Adopt

More information

DEFINITIONS CHAPTER 2

DEFINITIONS CHAPTER 2 CHAPTER 2 DEFINITIONS SECTION 201 GENERAL 201.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the purposes of this code, have the meanings shown in this chapter. 201.2

More information

Test Code: 8117 / Version 1

Test Code: 8117 / Version 1 Pennsylvania Customized Assessment Blueprint Plumbing Technology/Plumber PA Test Code: 8117 / Version 1 Copyright 2012. All Rights Reserved. General Assessment Information Plumbing Technology/Plumber PA

More information

Chapter 4: Fixtures, Faucets & Fittings:

Chapter 4: Fixtures, Faucets & Fittings: Table of Contents Chapter 1 Administration 0 Chapter 2 Definitions 0 Chapter 3 General Regulations 0 Chapter 4 Fixtures, Fau & Fit. 12 Chapter 5 Water Heaters 14 Chapter 6 Water Supply & Dist. 10 Chapter

More information

DEFINITIONS CHAPTER 2

DEFINITIONS CHAPTER 2 CHAPTER 2 DEFINITIONS SECTION PC 201 GENERAL 201.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the purposes of this code, have the meanings shown in this chapter.

More information

2015 MPC, MMC and IFGC Significant Changes

2015 MPC, MMC and IFGC Significant Changes 2015 MPC, MMC and IFGC Significant Changes Based on the 2015 Michigan Plumbing Code, (MPC), the 2015 Michigan Mechanical Code (MMC) and the 2015 International Fuel GaS Code (IFGC) Purpose This program

More information

BACKFLOW PREVENTION GUIDE FOR COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL DEVELOPMENTS

BACKFLOW PREVENTION GUIDE FOR COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL DEVELOPMENTS AG AVB PVB DCVA PA 1 Abattoir (slaughter house) 2 Air compressor oil cooler 3 Agricultural chemicals (sprayers 4 Animal watering 5 Apartment building (within the scope of Part 3 of the Ontario Building

More information

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE 1. BUILDING FEES: 1 AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE ESTABLISHMENT OF FEES PURSUANT TO N.J.A.C.

More information

DEFINITIONS CHAPTER 2

DEFINITIONS CHAPTER 2 CHAPTER 2 DEFINITIONS SECTION 201 GENERAL 201.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the purposes of this code, have the meanings shown in this chapter. 201.2

More information

The following test is Continuing Education for: Master Plumbers, Journeyman Plumbers, UDC Plumbing Inspectors, and Commercial Plumbing Inspectors.

The following test is Continuing Education for: Master Plumbers, Journeyman Plumbers, UDC Plumbing Inspectors, and Commercial Plumbing Inspectors. The following test is Continuing Education for: Master Plumbers, Journeyman Plumbers, UDC Plumbing Inspectors, and Commercial Plumbing Inspectors. You can complete the test by printing a hard copy, or

More information

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D20 PLUMBING 02/18

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D20 PLUMBING 02/18 NAVFAC PTS-D20 (February 2018) ------------------------------ Preparing Activity: NAVFAC SUPERSEDING PTS-D20 (September 2016) PERFORMANCE TECHNICAL SPECIFICATION SECTION D20 PLUMBING 02/18 NOTE: This section

More information

SAFETY PLUMBING PACKAGES. Quality Products & Value Packages SUSTAINABILITY. Residential Solutions ANTI-SCALE SYSTEMS FIRE PROTECTION

SAFETY PLUMBING PACKAGES. Quality Products & Value Packages SUSTAINABILITY. Residential Solutions ANTI-SCALE SYSTEMS FIRE PROTECTION Quality Products & Value Packages Residential Solutions FIRE PROTECTION COMFORTSUSTAINABILITYCONTROL PRESSURE REGULATORS TRENCH DRAINSHVAC SYSTEMS SAFETY ANTI-SCALE SYSTEMS HEATING & COOLING CONTROLS PLUMBING

More information

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS City of Redwood City Community Development Department Building and Inspection Department 1017 Middlefield Road Redwood City, CA 94063 Phone (650) 780-7350 2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY

More information

TRUMAN STATE UNIVERSITY PRESIDENT S RESIDENCE RENOVATION

TRUMAN STATE UNIVERSITY PRESIDENT S RESIDENCE RENOVATION SECTION 224100 - RESIDENTIAL PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

DUKE UNIVERSITY CONSTRUCTION STANDARDS

DUKE UNIVERSITY CONSTRUCTION STANDARDS 1 22 40 00 Plumbing Fixtures 1. General A. Definitions 1. Section includes a. Water closets and urinals b. Lavatories, sinks, and service sinks c. Electric water coolers, drinking fountains, d. Showers

More information

FEATURES. Other Fed-Flush Arrangements

FEATURES. Other Fed-Flush Arrangements Brochure # 0710 TYPE TYPE... VSAF SEWAGE EJECTOR SYSTEM Flows to 600 gpm, Heads to 120, 1 thru 40 HP. Discharge size 4, 1750 and 1150 RPM, strainer in discharge pipe. HIGHLIGHTS Installations where rags

More information

Definitions UPC Code - Chapter 2 Definitions A-I

Definitions UPC Code - Chapter 2 Definitions A-I 2015 UPC Code - Chapter 2 Definitions A-I Definitions 201.1 Applicability. For the purpose of this code, the following terms have the meanings indicated in this chapter. 202.0 Definition of Terms. 202.1

More information

CHAPTER 5 Water, Plumbing, and Waste

CHAPTER 5 Water, Plumbing, and Waste CHAPTER 5 Water, Plumbing, and Waste Parts 5-1 Water 5-2 Plumbing System 5-3 Mobile Water Tank 5-4 Sewage, Other Liquid Waste, and Rainwater 5-5 Refuse, Recyclables, and Returnables 5-1 Water 5-101 Source

More information

CONNECTICUT. Downloaded

CONNECTICUT. Downloaded Housekeeping/Laundry/Maintenance J. Laundry. CONNECTICUT Downloaded 01.15.11 (1) This service, if provided, shall be used exclusively for laundry and shall be remote from resident and food service areas,

More information

Plumbing Guidelines 2012 IBC/ANSI A

Plumbing Guidelines 2012 IBC/ANSI A Plumbing Guidelines 2012 IBC/ANSI A117.1-2009 This document provides basic and fundamental information for accessible plumbing fixtures, toilet rooms and bathing facilities. It is not intended to replace

More information

4. Committee Member presentation of New Items for consideration by the committee (Written ideas with discussion, maximum 5 minutes each.

4. Committee Member presentation of New Items for consideration by the committee (Written ideas with discussion, maximum 5 minutes each. AGENDA for PMG CODE ACTION COMMITTEE TELECONFERENCE CALL MEETING ON TUESDAY 13 MAY 2014 Starting at 11am CDT (12pm EDT, 10am MDT, 9am PDT) Scheduled Length of Meeting: 2 hours The Dial-in Number is 1-800-910-8278

More information

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Suppression Systems; and Chapter 34-National Electric

More information

House Drainage System. Building Utility & Services

House Drainage System. Building Utility & Services House Drainage System Building Utility & Services Syllabus House Drainage: principles of house drainage, pipes and traps, Classification of traps: nahni trap, interception trap, grease-trap, sanitary fittings,

More information

Master in Architecture. (Services in High Rise Buildings)

Master in Architecture. (Services in High Rise Buildings) Master in () 1. Details of Module and its Structure Module Detail Subject Name Paper Name - Module Name/Title Water Supply to High Rise Buildings - 1 Objectives To explain the need and the capacity of

More information

Summary of Substantive Changes between the 2012 and 2018 editions of ASME A /CSA B125.1 Plumbing Supply Fittings

Summary of Substantive Changes between the 2012 and 2018 editions of ASME A /CSA B125.1 Plumbing Supply Fittings Summary of Substantive Changes between the 2012 and 2018 editions of ASME A112.18.1/CSA B125.1 Plumbing Supply Fittings Presented to the IAPMO Standards Review Committee on May 6, 2013 General: The changes

More information

CHAPTER 2 DEFINITIONS. Back-Siphonage The flowing back of used, Backwater Valve A device installed in a drainage. bathtub.

CHAPTER 2 DEFINITIONS. Back-Siphonage The flowing back of used, Backwater Valve A device installed in a drainage. bathtub. CHAPTER 2 DEFINITIONS 201.0 General. For the purpose of this code, the following terms have the meanings indicated in this chapter. No attempt is made to define ordinary words which are used in accordance

More information

SUBCOURSE EDITION EN US ARMY ENGINEER SCHOOL PLUMBING FIXTURES (PLUMBING IV)

SUBCOURSE EDITION EN US ARMY ENGINEER SCHOOL PLUMBING FIXTURES (PLUMBING IV) SUBCOURSE EDITION EN5113 5 US ARMY ENGINEER SCHOOL PLUMBING FIXTURES (PLUMBING IV) US ARMY PLUMBER MOS 51K SKILL LEVELS 1 AND 2 COURSE PLUMBING FIXTURES (PLUMBING IV) SUBCOURSE NO. EN5113 US Army Engineer

More information

Gulfport, Mississippi 21 May 2007

Gulfport, Mississippi 21 May 2007 G PLUMBING GENERAL REQUIREMENTS The D-BC shall design the plumbing system to comply with this criteria and the Plumbing Code. Piping shall be shown on the same plan as the fixtures being served. Pipe size

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties:

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties: SECTION 221319 - SANITARY WASTE PIPING SPECIALTIES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following sanitary drainage piping specialties: 1. Backwater valves. 2. Cleanouts. 3. Floor

More information