INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

Size: px
Start display at page:

Download "INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL"

Transcription

1 INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES GENERAL SAFETY UNIT INSTALLATION ELECTRIC HEATER INSTALLATION Typical Installation Component Location Dimensions & Duct Connection Dimensions Physical and Electrical Data Conversion Table Electrical Data - Cooling Only (60 Hz) Electrical Data - 208/ LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES UNIT DATA MAINTENANCE WIRING DIAGRAM START UP SHEET Trap Configuration Stage Wiring Diagram Wiring Diagram & 9 Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/ Air Flow Data - 60 Hz Models Volt Air Flow Data - 60 Hz Models Volt SECTION I: GENERAL The AHX61 single piece air handler series offers the ultimate in application flexibility. These units are multi-position units and can be installed in any upflow, downflow, or horizontal airflow configuration. They may be located in closet, utility room, attic, crawl space or basement. These versatile models may be used for cooling or heat pump operation with or without electric heat. Factory installed thermal expansion valve is standard on the AHX61 series. The R410A TXV provides optimum performance and the refrigerant control required for today's high efficiency product. Electrical connections can be made from the top, left, or right. Controls are accessible from the front for easy service. A BRAND LABEL (available from Distribution) may be applied to the center of the blower access panel. SECTION II: SAFETY This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury. Understand and pay particular attention to the signal words DANGER, WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury. WARNING indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury. CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property damage. This product must be installed in strict compliance with the installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes. Johnson Controls Unitary Products Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified contractor, installer or service agency. FIRE OR ELECTRICAL HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. A fire or electrical hazard may result causing property damage, personal injury or loss of life. 1. Install this air handler only in a location and position as specified in SECTION III of these instructions. 2. Always install the air handler to operate within the air handler s intended maximum outlet air temperature. Only connect the air handler to a duct system which has an external static pressure within the allowable range, as specified on the air handler rating plate. 3. When an air handler is installed so that supply ducts carry air circulated by the air handler to areas outside the space containing the air handler, the return air shall also be handled by duct(s) sealed to the air handler casing and terminating in the space to be cooled/heated. 4. The air handler is not to be used for temporary heating of buildings or structures under construction. 5. The size of the unit should be based on an acceptable heat loss or gain calculation for the structure. ACCA, Manual J or other approved methods may be used UIM-D-0413

2 SAFETY REQUIREMENTS 1. This air handler should be installed in accordance with all national and local building/safety codes and requirements, local plumbing or wastewater codes, and other applicable codes. 2. Refer to the unit rating plate for the air handler model number, and then see the dimensions page of this instruction for supply air plenum dimensions in Figure 3. The plenum must be installed according to the instructions. 3. Provide clearances from combustible materials as listed under Clearances. 4. Provide clearances for servicing ensuring that service access is allowed for electric heaters and blower. 5. Failure to carefully read and follow all instructions in this manual can result in air handler malfunction, death, personal injury and/or property damage. 6. Check the rating plate and power supply to be sure that the electrical characteristics match. 7. Air handler shall be installed so the electrical components are protected from water. 8. Installing and servicing heating/cooling equipment can be hazardous due to the electrical components. Only trained and qualified personnel should install, repair, or service heating/cooling equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating/cooling equipment, observe precautions in the manuals and on the labels attached to the unit and other safety precautions that may apply. 9. These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-hud modular home construction practices. These instructions are required as a minimum for a safe installation. INSPECTION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. Also, before installation the unit should be checked for screws or bolts, which may have loosened in transit. There are no shipping or spacer brackets which need to be removed. Also check to be sure all accessories such as heater kits, suspension kits, and coils are available. Installation of these accessories or field conversion of the unit should be accomplished before setting the unit in place or connecting any wiring, electric heat, ducts or piping. LIMITATIONS These units must be wired and installed in accordance with all national and local safety codes. Voltage limits are as follows: Air Handler Voltage Voltage code Normal Operating Voltage Range 1 208/ Rated in accordance with ARI Standard 110, utilization range A. Airflow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units. SECTION III: UNIT INSTALLATION CLEARANCES Clearances must be taken into consideration, and provided for as follows: 1. Refrigerant piping and connections - minimum 12 (30.5 cm) recommended. 2. Maintenance and servicing access - minimum 36 (91.4 cm) from front of unit recommended for blower motor / coil replacement. 3. Condensate drain lines routed to clear filter and panel access. 4. Filter removal - minimum 36 (91.4 cm) recommended. 5. The ductwork and plenum connected to this unit are designed for zero clearance to combustible materials. 6. A combustible floor base accessory is available for downflow applications of this unit, if required by local code. 7. Unit must be installed a minimum of 18" from any ignition source. LOCATION Location is usually predetermined. Check with owner s or dealer s installation plans. If location has not been decided, consider the following in choosing a suitable location: 1. Select a location with adequate structural support, space for service access, clearance for air return and supply duct connections. 2. Using hanging brackets to wall mount this single piece air handler unit is not recommended. 3. Normal operating sound levels may be objectionable if the air handler is placed directly over some rooms such as bedrooms, study, etc. 4. Select a location that will permit installation of condensate line to an open drain or outdoors allowing condensate to drain away from structure. NOTICE The primary and secondary drain line must be trapped to allow proper drainage of condensate water. If the secondary drain line is not used, it must be capped. The coil is provided with a secondary drain. It should be piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secondary drain is not used it must be capped. 5. When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the air handler as is specified by most local building codes. 6. Proper electrical supply must be available. 7. If unit is located in an area of high humidity (i.e. an unconditioned garage or attic), nuisance sweating of casing may occur. On these installations, unit duct connections and other openings should be properly sealed, and a wrap of 2 (50.1 cm) fiberglass insulation with vinyl vapor barrier should be used. 8. For units installed in garages, warehouses, or other areas where they may be subject to mechanical damage, suitable protective barriers must be installed. Entering Air Temperature Limits Wet Bulb Temp. F Dry Bulb Temp. F Min. Max. Min. Max Johnson Controls Unitary Products

3 I/ON O/OFF UIM-D-0413 UPFLOW DOWNFLOW HORIZONTAL RIGHT HORIZONTAL LEFT FIGURE 1: Typical Installation DOWNFLOW AND HORIZONTAL CONVERSION These air handler units are supplied ready to be installed in an upflow and right hand horizontal position. If the unit requires downflow or left hand airflow configuration, the unit must be modified. Horizontal Left Hand Conversion 1. With Air Handler in vertical position remove all access panels. 2. Remove horizontal drain pan from right hand side. Disconnect any drain connections. 3. Relocate the removed horizontal drain pan on to the left side and reconnect the drain connections. 4. "P" traps must be installed on primary and secondary drains of the horizontal drain pan. 5. Reinstall all access panels to the unit. In all cooling application an auxiliary drain pan must provided and installed by the installer under the entire unit with separate drain line properly sloped and terminated in an area visible to the occupant. NOTICE The A coil contains 150 psig of air pressure. Failure to follow this installation requirement will void the product warranty. Downflow Conversion 1. Before putting the Air Handler in the downflow position, remove lower access panels. Remove and discard horizontal drain pan. Horizontal drain pan is not required for downflow applications. 2. Remove coil with vertical drain pan from the unit. 3. Turn the air handler to the downflow position. 4. Install coil deck. In effect, coil and two lower access panels will be assembled 180 degrees from their former position. See Figure Place 3"x 16" flat insulation retainer on bottom of each coil slab against the aluminum fins as shown. This will reduce the potential for water blow-off into the air stream. 6. Install coil assembly (with drain pan attached) to the coil deck into the air handler. 7. Push coil pan assembly all the way to the rear of the air handler unit until it locks under the bracket in the rear. Install lower access panels to match the tubing and drains. 8. If the air handler has circuit breakers, they must be snapped out of the bracket and inverted to reflect "up" as the "on" position and "down" as the "off" position. FIGURE 2: Component Location TOP OF WRAPPER FILTER INSULATED WRAPPER COUNTERFLOW DECK BLOWER MOTOR ELECTRICAL COMPARTMENT Johnson Controls Unitary Products 3

4 DIMENSIONS LINE VOLTAGE 20-1/2 (52) 10-1/2 (27) 22-1/4 (57) 24-1/2 (62) LINE VOLTAGE When installing a central air return grille in or near the living space, it is advisable to design the ductwork so that the grille is not in direct line with the opening in the unit. One or two elbows and acoustical duct liner will also assure a quieter installation and system. This unit is not designed for non-ducted (freeblow) applications. All ducts should be suspended using flexible hangers and never fastened directly to the structure. Duct work should be fabricated and installed in accordance with local and/or national codes. This includes the standards of the National Fire Protection Association for Installation of Air-Conditioning and Ventilating Systems, NFPA No. 90B. They should be sized in accordance with National Environmental System Contractors Association Manual K, or whichever is applicable. AIR FILTERS A 1" filter access rack has been built into the unit. The unit ships with a disposable filter in the filter rack. A standard 1" size permanent or throw away filter may be used. See Figure 3. for filter access location. To replace filter, remove filter access cover and install proper size filter. 4 (10). 57 HORIZONTAL DRAIN STANDARD Equipment should never be operated without filters. 18-1/2 (47) 22 (56) Filter Size Piston Size Ship Weight (LBS) Skid Quantity 20 x FIGURE 3: Dimensions & Duct Connection Dimensions DUCT CONNECTIONS 21-5/8 (55) 16-5/8 (42) PRIMARY DRAIN SECONDARY DRAIN HORIZONTAL SUSPENSION For suspension of these units in horizontal applications, it is recommended to use angle steel support brackets with threaded rods, supporting the units from the bottom, at the locations shown in Figure 7. When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the air handler as is specified by most local building codes. REFRIGERANT LINE CONNECTION Route the refrigerant lines to the coil in a manner that will not obstruct service access to the coil, air handling system, or filter. Insulation on the suction line must extend into cabinet and continue as far as possible to eliminate condensation from dripping on to access door insulation. Use 1/2" screws to connect ductwork to bottom of unit. Longer screws will pierce the drain pan and cause leakage. If pilot holes are drilled, drill only though field duct and unit bottom flange. Air supply and return may be handled in one of several ways best suited to the installation. See Figure 3 for dimensions for duct inlet and outlet connections. The vast majority of problems encountered with combination heating and cooling systems can be linked to improperly designed or installed duct systems. It is therefore highly important to the success of an installation that the duct system be properly designed and installed. Use flexible duct collars to minimize the transmission of vibration/noise into the conditioned space. If electric heat is used, non-flammable material must be used. Where return air duct is short, or where sound may be a problem, sound absorbing glass fiber should be used inside the duct. Insulation of duct work is a must where it runs through an unheated space during the heating season or through an uncooled space during the cooling season. The use of a vapor barrier is recommended to prevent absorption of moisture from the surrounding air into the insulation. All main supply and return air drops should be run full size as determined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit. The supply air duct should be properly sized by use of a transition to match unit opening. Size outlet plenum or transition to discharge opening sizes shown in Figure 3. Coil is under inert gas pressure. Relieve pressure from coil by depressing schrader core. Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation. Connect lines as follows: NOTICE Route the refrigerant lines to the coil in a manner that will not obstruct service access to the coil, air handling system, or filter. 1. Suction and liquid line connections are made outside the cabinet. Leave the tubing connection panel attached to the cabinet with the tubes protruding through it. Coil access panel should be removed for brazing. The lines are swedged to receive the field line set tubes. 2. Remove the heat shield from the Customer Packet, soak in water, and install over coil tubing to prevent overheating of cabinet. 4 Johnson Controls Unitary Products

5 3. Wrap a water soaked rag around the coil connection tubes inside the cabinet to avoid damaging the TXV bulb. 4. Remove grommets where tubes exit the cabinet to prevent burning them during brazing. 5. Purge refrigerant lines with dry nitrogen. 6. Braze the suction and liquid lines. 7. Remove the heat shield. 8. Re-attach the grommets to the lines carefully to prevent air leakage. 9. Attach the coil access panel to the cabinet. Refer to Outdoor unit Installation Manual for evacuation, leak check and charging instructions. DRAIN CONNECTION Lines should be sound isolated by using appropriate hangers or strapping. All evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder. DRAIN CONNECTIONS All drain lines should be trapped a minimum of three inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection. For trap configuration and requirements see Figure 4. Coils should be installed level or pitched slightly toward the drain end. Suggested pitch should not exceed 1/4" per foot (21mm/m) of coil. Route the drain line so that it does not interfere with accessibility to the coil, air handling system or filter and will not be exposed to freezing temperatures. VENT MUST TERMINATE BELOW TOP OF CONDENSATE PAN UNIT 2 MINIMUM UNIT 2 MINIMUM LIFT FLEXIBLE TUBING HOSE OR PIPE A POSITIVE LIQUID SEAL IS REQUIRED FIGURE 4: Trap Configuration 3 MINIMUM 3 MINIMUM WATER COLUMN Threaded drain connection should be hand-tightened, plus no more than 1/16 turn. When the coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil if specified by local building codes. When this exterior secondary drain pan is used that drain should be piped to a location that will give the occupant a visual warning that the primary drain is clogged. In all cooling applications, a secondary drain pan should be provided by the installer and placed under the entire unit with a separate drain line properly sloped and terminated in an area visible to the occupant. Failure to follow this installation requirement will void the product warranty. Use of a condensate removal pump is permitted when necessary. This condensate pump should have provision to shut-off should a blocked drain occur. The drain pan connections are designed to ASTM Standard D 2466 Schedule 40. Use 3/4" PVC or steel threaded pipe. Since the drains are not subject to any pressure it is not necessary to use Schedule 40 pipe for drain lines. It is recommended that all drain connections be sealed with teflon tape or equivalent. SECTION IV: ELECTRIC HEATER INSTALLATION If the air handler requires electric heat, install the electric heat kit according to the installation instructions included with the kit. After installing the kit, mark the air handler nameplate to designate the heater kit that was installed. If no heater is installed, mark the name plate appropriately to indicate that no heat kit is installed. Johnson Controls Unitary Products 5

6 SECTION V: UNIT DATA TABLE 1: Physical and Electrical Data Blower - Diameter x Width 12 x 9 Motor HP 1 Nominal RPM 1075 Voltage 208/230 Amps Full Load (230) 6.9/7.6 Filter 1 Type DISPOSABLE Size 20 x 20 x 1 Shipping / Operating Weight (lbs.) Field Supplied. TABLE 2: Conversion Table kw & MBH Conversions - for Total Power Input Requirement 208V 240V TABULATED kw & MBH OPERATION MULTIPLY 230V 240V BY TABLE 3: Electrical Data - Cooling Only (60 Hz) Total Motor Amps Minimum Circuit Ampacity 60 Hertz 60 Hertz Max. O.C.P. 1 Minimum Wire Amps/Type Size A.W.G. 208V 230V 208V 230V OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. TABLE 4: Electrical Data - 208/ Total Heat 1 kw Staging Heater Min. Max. Static Models* Speed Tap kw MBH W1 Only W2 Only W1 + W2 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V S1-ECL S1-ECL S1-ECL S1-ECL S1-ECL S1-ECL See conversion Table 8. * May be 0 (no breaker) or 1 (with breaker). TABLE 5: Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/ Field Wiring Heater Heater Amps Min. Circuit Ampacity Models* Max. O.C.P. 1 Amps/Type 75 C Wire Size - AWG 240V 208V 230V 208V 230V 208V 230V S1-ECL S1-ECL S1-ECL S1-ECL S1-ECL /0 S1-ECL /0 2/0 1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. * May be 0 (no breaker) or 1 (with breaker) 6 Johnson Controls Unitary Products

7 TABLE 6: Air Flow Data - 60 Hz Models Volt Blower 208 Volt Motor CFM External Static Pressure - IWC Speed TAP TAP TAP TAP TAP NOTE: Air flow data shown above 1/2 w.c. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is limited to 1/2 w.c. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation. 1. Dry coil conditions only, tested without filters. Speed temp High #1 not recommended for the unit. Air handler units are UL Listed up to 0.5" w.c. external static pressure, including air filter, wet coil, and largest kw size heater, unless otherwise noted. TABLE 7: Air Flow Data - 60 Hz Models Volt Blower 230 Volt Motor CFM External Static Pressure - IWC Speed TAP TAP TAP TAP TAP NOTE: Air flow data shown above 1/2 w.c. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is limited to 1/2 w.c. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation. 1. Dry coil conditions only, tested without filters. Speed temp High #1 not recommended for the unit. Air handler units are UL Listed up to 0.5" w.c. external static pressure, including air filter, wet coil, and largest kw size heater, unless otherwise noted. SECTION VI: MAINTENANCE Filters must be cleaned or replaced when they become dirty. Inspect at least once per month. The frequency of cleaning depends upon the hours of operation and the local atmospheric conditions. Clean filters keep unit efficiency high./ COIL CLEANING If the coil needs to be cleaned or replaced, it should be washed with Calgon CalClean (mix one part CalClean to seven parts water). Allow solution to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact with painted surfaces. LUBRICATION The bearings of the blower motor are permanently lubricated. CONDENSATE DRAINS During the cooling season check the condensate drain lines to be sure that condensate is flowing from the primary drain but not from the secondary drain. If condensate ever flows from the secondary drain the unit should be promptly shut off and the condensate pan and drains cleaned to insure a free flowing primary drain. SECTION VII: WIRING DIAGRAM Y2 BLOWER TIME DELAY EVAPORATOR MOTOR x13 C G L N 24V COMMON GRN WHT L1 BLK 230V COMMON FIGURE 5: 2-Stage Wiring Diagram Johnson Controls Unitary Products 7

8 FIGURE 6: Wiring Diagram 8 Johnson Controls Unitary Products

9 FIGURE 6: Wiring Diagram Johnson Controls Unitary Products 9

10 NOTES 10 Johnson Controls Unitary Products

11 SECTION VIII: START UP SHEET Print Form Residential Air Handler with Electric Heat Start-Up Sheet Proper start-up is critical to customer comfort and equipment longevity Reset Form Start-Up Date Owner Information Name Company Name Address Start-Up Technician Daytime Phone City State or Province Zip or Postal Code Equipment Data Unit Model # Unit Serial # General Information (Check all that apply) New Construction Up flow Horizontal Left Retrofit Down flow Horizontal Right Unit Location and Connections (Check all that apply) Unit is level Duct connections are complete: Supply Return Condensate drain properly connected per the installation instructions Condensate trap has been primed with water Filters Filters installed Number of filters Filter size Electrical Connections & Inspection (Complete all that apply) 208 volts AC 230 volt AC Inspect wires and electrical connections Transformer wired properly for primary supply voltage Ground connected Line Voltage Measured (Volts AC) Thermostat wiring is complete Air Flow Setup Blower Type & Set-Up ECM X-13 PSC Low voltage value between "R" and "C" at control board (Volts AC) Thermostat cycle rate or heat anticipator adjusted to Installation Manual specifications COOL A B C D ADJUST A B C D DELAY A B C D HEAT A B C D Low Medium Low Medium Medium High High Supply static (inches of water column) Return static (inches of water column) Supply air dry bulb temperature Return air dry bulb temperature Outside air dry bulb temperature Return air wet bulb temperature Total external static pressure Temperature drop Supply air wet bulb temperature Other Jumpers (Check all that apply) HUM STAT YES NO AC/HP AC HP CONT FAN L M H Continued on next Page Johnson Controls Unitary Products 11

12 Electric Heat (Complete all that apply) Electric heat kit - Model number Serial number Rated KW Number of elements Measured Amperage Measured Voltage Heater 1 Heater 4 Heater 1 Heater 4 Heater 2 Heater 5 Heater 2 Heater 5 Heater 3 Heater 6 Heater 3 Heater 6 Heating return air dry bulb temperature Clean Up Job Site Job site has been cleaned, indoor and outdoor debris removed from job site Tools have been removed from unit All panels have been installed Heating supply air dry bulb temperature Air temperature rise Unit Operation and Cycle Test (Complete all that apply) Operate the unit through continuous fan cycles from the thermostat, noting and correcting any problems Operate the unit through cooling cycles from the thermostat, noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat, noting and correcting any problems Operate the unit through emergency heating cycles from the thermostat, noting and correcting any problems Owner Education Provide owner with the owner's manual Explain operation of system to equipment owner Explain thermostat use and programming (if applicable) to owner Explain the importance of regular filter replacement and equipment maintenance Comments and Additional Job Details Subject to change without notice. Published in U.S.A Copyright 2013 by Johnson Controls, Inc. All rights reserved. York International Corp York Drive Norman, OK UIM-D-0413 Supersedes: UIM-C-0212

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC ISO 9001 Certified Quality Management System SAFETY................................................

More information

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES ISO 9001 Certified Quality Management System GENERAL.............................................. 1 SAFETY................................................

More information

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR / AHE SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR / AHE SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR / AHE SERIES ISO 9001 Certified Quality Management System GENERAL..............................................1 SAFETY................................................1

More information

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214 INSTALLATION MANUAL FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: MC FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS MODELS: FC PARTIAL-CASED UPFLOW FOR COOLING/HEAT PUMP MODELS: PC ISO

More information

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195) STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: 535.02-N2Y (795) 535.02-N2Y (1195) HEAT PUMP MODELS F1RP / F1FP018 thru 060 and COOLING MODELS F1RC / F1FC018 thru 036 035-13620

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION MODULAR AIR HANDLER MODEL: N*AH CONTENTS GENERAL... 1 INSPECTION... 2 REFERENCE... 2 LIMITATIONS... 2 LOCATION... 2 BLOWER/COIL ASSEMBLY UPFLOW AND HORIZONTAL INSTALLATIONS...

More information

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHE SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHE SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHE SERIES ISO 9001 Certified Quality Management System GENERAL..............................................1 SAFETY................................................1

More information

INSTALLATION MANUAL SINGLE PIECE, 4 POSITION AIR HANDLERS MODELS: AHR SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 4 POSITION AIR HANDLERS MODELS: AHR SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE, 4 POSITION AIR HANDLERS MODELS: AHR SERIES ISO 9001 Certified Quality Management System GENERAL..............................................1 SAFETY................................................1

More information

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY INSTALLATION MANUAL FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: MC FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS MODELS: FC PARTIAL-CASED UPFLOW FOR COOLING/HEAT PUMP MODELS: PC ISO

More information

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR SERIES ISO 9001 Certified Quality Management System GENERAL..............................................1 SAFETY................................................1

More information

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHP SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHP SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHP SERIES ISO 9001 Certified Quality Management System GENERAL..............................................1 SAFETY................................................1

More information

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: ORIFICE METERING DEVICE - G*FD024S14 - G*FD060S24 FACTORY INSTALLED TXV - G*FD024S14T - G*FD060S24T

More information

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: ORIFICE METERING DEVICE - G*FD024S14 - G*FD060S24 FACTORY INSTALLED TXV - G*FD024S14T - G*FD060S24T

More information

INSTALLATION MANUAL WARNING WARNING MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: MA LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES

INSTALLATION MANUAL WARNING WARNING MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: MA LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES INSTALLATION NUAL MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: GENERAL.............................................. 1 SAFETY................................................ 1 UNIT INSTALLATION.....................................

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION SINGLE PIECE AIR HANDLERS Supersedes: 535.02-N2V (598) 535.02-N2V (199) HEAT PUMP MODELS F+RP / F+FP018 thru 060 and COOLING MODELS F+RC / F+FC024 thru 036 035-14363 GENERAL This

More information

INSTALLATION MANUAL SINGLE PIECE VARIABLE SPEED AIR HANDLERS MODELS: AV*(C) SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE VARIABLE SPEED AIR HANDLERS MODELS: AV*(C) SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL INSTALLATION MANUAL SINGLE PIECE VARIABLE SPEED AIR HANDLERS MODELS: AV*(C) SERIES ISO 9001 Certified Quality Management System GENERAL..............................................1 SAFETY................................................1

More information

INSTALLATION MANUAL WARNING STANDARD PSC MODULAR MULTI-POSITION AIR HANDLERS MODELS: MP SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES

INSTALLATION MANUAL WARNING STANDARD PSC MODULAR MULTI-POSITION AIR HANDLERS MODELS: MP SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES INSTALLATION MANUAL STANDARD PSC MODULAR MULTI-POSITION AIR HANDLERS MODELS: MP SERIES ISO 9001 Certified Quality Management System GENERAL..............................................1 SAFETY................................................1

More information

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION SINGLE PIECE AIR HANDLERS Supersedes: 535.02-N2V (600) 535.02-N2U (900) HEAT PUMP MODELS F2RP / F2FP018 thru 060 and COOLING MODELS F2RC / F2FC024 thru 036 035-14520-000 Rev. B

More information

INSTALLATION MANUAL WARNING WARNING FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CF

INSTALLATION MANUAL WARNING WARNING FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CF INSTALLATION MANUAL FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS MODELS: CF FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CM ISO 9001 Certified Quality Management System GENERAL..............................................

More information

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT MASSAGE TO INSTALLER: "The United States Environmental Protection Agency ("EPA") has issued various regulations regarding the

More information

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER ASPEN MANUFACTURING 373 ATASCOCITA RD. HUMBLE, TX 77396 TEL (281) 441-6500 FAX (281) 441-6510 > INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT: "The

More information

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY INSTALLATION MANUAL MC SERIES MULTI-POSITION, FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL FOR COOLING/HEAT PUMPS Flex Coils for Field Installed TXV- Factory Installed R-22 TXV - Coils MC***3XH MC***2AH

More information

INSTALLATION MANUAL LIST OF SECTIONS. 1 General 1 3 Louvered Door Frame Assembly Installation 3 2 Safety 2 4 Coil Cabinet Installation 5

INSTALLATION MANUAL LIST OF SECTIONS. 1 General 1 3 Louvered Door Frame Assembly Installation 3 2 Safety 2 4 Coil Cabinet Installation 5 INSTALLATION MANUAL DOWNFLOW / HORIZONTAL COIL CABINET DOWNFLOW LOUVERED DOOR ASSEMBLY MODELS: 97-F SERIES LIST OF SECTIONS 1 General 1 3 Louvered Door Frame Assembly Installation 3 2 Safety 2 4 Coil Cabinet

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

GAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT)

GAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT) GAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT) MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should be retained and

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Installation Instructions

Installation Instructions CNPHP Cased N s Horizontal Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION...

More information

Installation Instructions

Installation Instructions CNPHP Cased N Coils Horizontal Heating --- Cooling NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FCP2400D FCP3000D FCP3600D FCP4200D FCP4800D FCP6000D FCP2400C FCX2400C FCP3000C FCP3600C FCX3600C FCP4200C FCP4800C FCX4800C FCP6000C FCX6000C Require AMF001NHA Accessory No

More information

TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36

TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36 TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36 Due to continuous product improvement, specifications are

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Models MB08B1500A2 MB12F1900A2 MB16J2200A2 MB20N2600A2 Contents 115 Volt General Information / Installation... 2 Installations... 3 Horizontal Installations... 3 Ductwork Connections...

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS INTRODUCTION Please note that HUD Manufactured Home Construction and Safety Standard Section 3280.714, paragraph (a) and subparagraph

More information

Installation Instructions

Installation Instructions Installation Instructions Indoor Air Handlers for Systems These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of heating and/or air conditioning

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. VARIABLE SPEED ELECTRIC FURNACE INSTALLATION INSTRUCTIONS VARIABLE SPEED ELECTRIC FURNACE SAFETY...1 INSTALLATION REQUIREMENTS...2 Tools and Parts...2 Location Requirements...2 Installation Configurations...3

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Models FCV3600A FCV4800A FCV6000A Require AMF001NHA Accessory No Heat Kit Contents Use ONL factory listed electric heaters. General Information / Installation... 2 Upflow Installations...

More information

INSTALLATION MANUAL SINGLE PIECE AIR HANDLERS MODELS: F6FP018** - 060** TABLE OF CONTENTS LIST OF FIGURES LIST OF TABLES SAFETY UIM-B-0409

INSTALLATION MANUAL SINGLE PIECE AIR HANDLERS MODELS: F6FP018** - 060** TABLE OF CONTENTS LIST OF FIGURES LIST OF TABLES SAFETY UIM-B-0409 INSTALLATION MANUAL SINGLE PIEE AIR HANDLERS MODELS: F6FP018** - 060** ISO 9001 ertified Quality Management System SAFETY................................................ 1 SPEIFI SAFETY RULES AND PREAUTIONS...............

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

TECHNICAL GUIDE VARIABLE SPEED AIR HANDLERS DESCRIPTION FEATURES Rev. A (0105)

TECHNICAL GUIDE VARIABLE SPEED AIR HANDLERS DESCRIPTION FEATURES Rev. A (0105) TECHNICAL GUIDE VARIALE SPEED AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: N1VS 600-2000 CFM LOWERS 2-5 TON COILS OPTIONAL 1 & 3 φ ELECTRIC HEATERS ISO 9001 Certified Quality Management

More information

INSTALLATION MANUAL SINGLE PIECE AIR HANDLERS MODELS: F*FP LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SAFETY UIM-B-0209

INSTALLATION MANUAL SINGLE PIECE AIR HANDLERS MODELS: F*FP LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SAFETY UIM-B-0209 INSTALLATION MANUAL SINGLE PIEE AIR HANDLERS MODELS: F*FP ISO 9001 ertified Quality Management System SAFETY................................................1 SPEIFI SAFETY RULES AND PREAUTIONS...............2

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Models EBP EBX EBXX(R -410A) CAUTION Use ONLY factory listed electric heaters. Safety Labeling and Signal Words Danger, Warning and Caution The signal words DANGER, WARNING and

More information

AHG**-0B Series Hydronic Air Handling Units

AHG**-0B Series Hydronic Air Handling Units HEAT CONTROLLER, INC. Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual AHG**-0B Series Hydronic Air Handling Units HEAT CONTROLLER, INC. 1900 Wellworth Ave.,

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS C7BA & C7BH Series Split System Indoor Cased Coils INSTALLATION INSTRUCTIONS IMPORTANT It is your responsibility to know this product better than your customer. This includes being able to install the

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C7BA Series Split System Indoor Cased Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

INSTALLATION INSTRUCTIONS TXV Coils EBD, EBA

INSTALLATION INSTRUCTIONS TXV Coils EBD, EBA TXV Coils EBD, EBA These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system to operate

More information

INSTALLATION INSTRUCTIONS TXV Coils EBU, EBA

INSTALLATION INSTRUCTIONS TXV Coils EBU, EBA TXV s EBU, EBA These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system to operate

More information

INSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA

INSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA TXV Coils EDM, EDD, EDA These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system to

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS 036-21096-001 (0101) SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility. The

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2017 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE WARNING This product contains a chemical known to the State of California to cause cancer,

More information

CBX32MV (HFC-410A) SERIES UNITS

CBX32MV (HFC-410A) SERIES UNITS Service Literature Corp. 005-L2 Revised November 5, 202 (HFC-40A) SERIES UNITS (icomfort-enabled) NOTICE A thermostat is not included and must be ordered separately. The Lennox icomfort thermostat must

More information

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

Cased Aluminum Coils Dedicated Upflow / Downflow Convertible to horizontal with separately purchased kit 18-AD32D1-3 Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit Upflow models: 4PXCAU24BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA

More information

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA 18- AH39D1-4 Cased Aluminum "Convertible" Coils 2/4TXCA018BC3HCA 2/4TXCA024BC3HCA 2/4TXCB025BC3HCA 2/4TXCB031BC3HCA 4TXCB032BC3HCA 2/4TXCB036BC3HCA ALL phases of this installation must comply with NATIONAL,

More information

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH AVS Air Handlers Installation Manual for Classic SC, SD, and SDH AVS-NCL-IM (12/15) Copyright 2015 Earthlinked Technologies, Inc. Table of Contents Model Nomenclature... 4 Safety... 5 Equipment Manuals...

More information

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307 DESCRIPTION Technical Guide CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) This 20 ton evaporator blower is designed with two distinct modules to provide maximum application

More information

TECHNICAL GUIDE MODELS: MV MODULAR VARIABLE SPEED AIR HANDLERS FOR USE WITH SPLIT SYSTEM COOLING & HEAT PUMP DESCRIPTION FEATURES

TECHNICAL GUIDE MODELS: MV MODULAR VARIABLE SPEED AIR HANDLERS FOR USE WITH SPLIT SYSTEM COOLING & HEAT PUMP DESCRIPTION FEATURES TP TECH GUIDE TECHNICAL GUIDE MODELS: MV MODULAR VARIABLE SPEED AIR HANDLERS FOR USE WITH SPLIT SYSTEM COOLING & HEAT PUMP 1200-2000 CFM BLOWERS 3-5 TON COILS OPTIONAL ELECTRIC HEATERS ISO 9001 Certified

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2016 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE WARNING This product contains a chemical known to the State of California to cause cancer,

More information

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH AVS-ACL-IM (08/15) Copyright 2015 Earthlinked Technologies, Inc. Table of Contents Model Nomenclature... 4

More information

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500 SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing 550.23-N4C-0500 MODEL L*BC240 035-16603 GENERAL This 20 ton evaporator blower is designed with two distinct modules

More information

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES R-410A MODELS: 7.5-20 Ton, 60 Hertz NH-07 thru -20, 2-Pipe NJ-10 thru -20, 4-Pipe General.......................................... 2 Safety Considerations............................... 2 Reference......................................

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS* TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling

More information

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

Cased Aluminum Convertible Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC** 18- AH44D1-4 Cased Aluminum "Convertible" Coils 4TXCB003CC3HC 4TXCB004CC3HC 4TXCC005CC3HC 4TXCC006CC3HC 4TXCC007CC3HC 4TXCC008CC3HC 4TXCD009CC3HC 4TXCD010CC3HC May be "A" or "B" ALL phases of this installation

More information

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

Installation Instructions

Installation Instructions Evaporator Coil A Coil --- Cased Multipoise NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

PL Series Premier Indoor Plenum Coils

PL Series Premier Indoor Plenum Coils IM-PLC-0667392-04 April 2016 PL Series Premier Indoor Plenum Coils Installation Instructions GENERAL ADP evaporator coils are designed for use with condensing units or heat pump units. These instructions

More information

EarthLinked AFN Series Air Handlers Installation Manual

EarthLinked AFN Series Air Handlers Installation Manual EarthLinked AFN Series Air Handlers Installation Manual AFN-410-IM (07/15) Copyright 2015 Earthlinked Technologies, Inc. Table of Contents Model Nomenclature... 4 Safety... 5 Equipment Manuals... 5 Installation...

More information

C7 Series Split System Uncased Indoor Coils

C7 Series Split System Uncased Indoor Coils Installation Instructions C7 Series Split System Uncased Indoor Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

USERS INFORMATION MANUAL

USERS INFORMATION MANUAL MODULAR DX OR CHILLED WATER COOLING WITH ELECTRIC OR HOT WATER HEATING MODELS: US, UM SERIES USERS INFORMATION MANUAL For Installation In: 1. Modular Homes & Buildings 2. Residential Homes LIST OF SECTIONS

More information

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor IM-BAH-0662402-18 August 2018 Installation Instructions B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor TABLE OF CONTENTS

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2011 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation

More information

Installation Instructions

Installation Instructions Installation Instructions Cased Horizontal Furnace Coil CK3B A96318 Fig. 1 Model CK3B Furnace Coil NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper

More information

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. Installation NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION... 2 Inspect Equipment... 2 Select

More information

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED (491) SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU, K3EU & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ,t_2007 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR 505,264M (65484504) 10/07 Supersedes 09/06 COILS n _putech blications ical Litho U.S.A. RETAIN THESE

More information

EarthLinked AVN Series Air Handlers Installation Manual

EarthLinked AVN Series Air Handlers Installation Manual EarthLinked AVN Series Air Handlers Installation Manual AVN-410-IM (03/14) Copyright 2014 Earthlinked Technologies, Inc. Table of Contents Model Nomenclature... 4 Safety... 5 Equipment Manuals... 5 Installation...

More information

INSTALLATION & OPERATING INSTRUCTIONS AAC & AEC SERIES CEILING MOUNT AIR HANDLER (ELECTRIC HEAT)

INSTALLATION & OPERATING INSTRUCTIONS AAC & AEC SERIES CEILING MOUNT AIR HANDLER (ELECTRIC HEAT) INSTALLATION & OPERATING INSTRUCTIONS AAC & AEC SERIES CEILING MOUNT AIR HANDLER (ELECTRIC HEAT) MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should be retained

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE INSTALLATION INSTRUCTIONS ACBX32CM Units WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C8DA Series Split System Uncased Indoor Coils - Downturn IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes

More information

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2 Service Literature Corp. 0527 L10 Revised May 2011 CB26UH and CBX26UH Series Table of Contents CB26UH CBX26UH Model Number Information................... 2 Specifications / Electrical Data................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR COILS 505,264M (65484504) 05/08 Supersedes 10/07 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE

More information

HIGH EFFICIENCY AIR HANDLER

HIGH EFFICIENCY AIR HANDLER FORM NO. HFJ- Supersedes Form No. PTZ-789 HIGH EFFICIENCY AIR HANDLER Features FH***TTS feature a Constant Torque motor (ECM) which provides enhanced SEER performance with most Rheem outdoor units. Versatile

More information

WH1T SERIES Constant Torque Motor (ECM) Efficiencies up to 14 SEER. FORM NO. H REV. 1 Supersedes Form No. G Rev. 3

WH1T SERIES Constant Torque Motor (ECM) Efficiencies up to 14 SEER. FORM NO. H REV. 1 Supersedes Form No. G Rev. 3 FORM NO. H66- REV. 1 Supersedes Form No. G66-6 Rev. WH1T SERIES Constant Torque (ECM) Efficiencies up to 1 SEER HIGH EFFICIENCY AIR HANDLER Features WH1T feature a Constant Torque motor (ECM) which provides

More information

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS 550.23-TG5Y (893) CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L2EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility.

More information

USERS INFORMATION MANUAL

USERS INFORMATION MANUAL USERS INFORMATION MANUAL DOWNFLOW For Installation In: SINGLE AND TWO STAGE 1. Manufactured (Mobile) Home 2. Recreational Vehicle ELECTRIC FURNACE 3. Modular Homes & Buildings 4. Residential Homes MODELS:

More information

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION INSTALLATION INSTRUCTION CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS Supersedes: 550.44-N1Y (1194) 550.44-N1Y (495) MODELS H*DE018 THRU H*DE060 035-11029 WARNINGS are given to alert the installer

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Series Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life,

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

MERIT Series R-410A - Upflow / Horizontal

MERIT Series R-410A - Upflow / Horizontal PRODUCT SPECIFICATIONS AIR HANDLERS CBX5UH (-0) MERIT Series R-0A - Upflow / Horizontal Bulletin No. 060 March 05 Supersedes November 0 Nominal Capacity -.5 to 5 Tons Optional Electric Heat -.5 to 0 kw

More information

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE GENERAL..............................................1 SAFETY................................................1

More information

MODELS K2EU060A, K4EU090A, & K3EU120A

MODELS K2EU060A, K4EU090A, & K3EU120A AIR COOLED SPLIT-SYSTEM AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: 550.23-N2Y (589) 550.23-N2Y (399) MODELS K2EU060A, K4EU090A, & K3EU120A 035-16672 GENERAL These completely assembled 5, 7-1/2

More information

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature Service Literature Corp. 0804 L2 Revised 05 05 2008 G71MPP G71MPP SERIES UNITS G71MPP series units are high efficiency multi position (upflow, downflow, horizontal right and left) gas furnaces equipped

More information

R-410A AFFINITY SERIES DEX DEY Ton

R-410A AFFINITY SERIES DEX DEY Ton R-410A AFFINITY SERIES 024-048 DEY060 2-5 Ton ISO 9001 Certified Quality Management System General.......................................... 1 Installation........................................ 3 Limitations......................................

More information