An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters
|
|
- Rosalind Gilbert
- 5 years ago
- Views:
Transcription
1 An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters #1 Harshad D Kopurwar, #2 Pravin T Nitnaware, #3 Tapobrata Dey 1 harshvardhan1590@gmail.com #1 Mechanical Engineering, D.Y.patil college of engineering, Akurdi, pune, Savitribai phule pune university, Abstract: The study of the simple vapour compression refrigeration (VCR) cycle is much important in order to understand the overall performance of the system with parameters affecting it. The experimental study we had made on the VCR cycle with different parameters such as the capillary tube configuration, capillary tube diameter, variation in condenser fan speed and type of refrigerant. It can be concluded from the results below that capillary tube of 31 gauge (0.226 mm) and 36 gauge (0.130 mm) each with three different capillary (expansion valves) configurations i.e. helical coiled tube, straight coiled tube and serpentine coiled tube configuration. The overall performance of the system was studied with the effect of the coil configuration and capillary tube diameter on it. The refrigeration effect and heat transfer rate was found to be max for the helical coiled tube structure and was found to be least for straight coiled configuration whereas the performance was in between for serpentine type coil. Refrigerant selection and its effect on performance of VCR cycle shows that heat carrying capacity for R-134a and R-22 are much more than R-717. Also condenser fan speed has been studied and it can be noted that as condenser fan speed increases condenser performance increases but up to certain extent and then rate decreases. KEYWORDS: Capillary Tube, configuration, condenser fan, refrigerant, refrigeration system, ODP, GWP, HRR. I. INTRODUCTION A simple vapour compression refrigeration system consists of mainly five components namely compressor (Hermetically sealed), condenser, expansion device, evaporator and a filter/drier. The following study is focused towards finding out the effect of different parameters such as the capillary tube configuration, capillary tube diameter, variation in condenser fan speed and type of refrigerant on the performance of the refrigeration system. A capillary tube with small diameter tube is used for the expansion of the flowing fluid. The diameter may be 31 gauge, 36 gauge, 40 gauge. As we know that the pressure difference between the entry and exit points of the capillary tube is always equal to the pressure difference between the condenser side and the evaporator. The diameter of the capillary tube used in the refrigeration appliances varies from 0.5mm to 2.5mm. Capillaries with 3 different configurations viz. helical, straight and serpentine type of configuration are used. The performance of the capillary tube has been investigated by many of researchers in the past and interesting results were obtained. Many of the countries had banned the use of HCFC as refrigerants from I st January 2010, although it is allowed to used up to 2015 if it comes through recycling process. Therefore there is a need to have development in new working fluids which can replace the HCFC in the refrigeration plants which are now in operation. Among all the HCFC s used upto year 2010, R22 is the most widely used and has wide range of applications, especially in the air conditioning which we are comparing with HFC R-134a and R-744 having less ODP. Condenser efficiency can be checked by arranging a regulator which will change fan performance. II. OBJECTIVE a. To study the performance of system with the effect of capillary tube configuration on it. b. To investigate the performance of system with the effect of capillary tube diameter on it. c. To investigate the effect of condenser fan speed on the performance VCR cycle. d. To study the effect of different refrigerants within same range on performance of system.
2 III. XPERIMENTAL SETUP AND PROCEDURE: An experimental study was made in the refrigeration and air conditioning laboratory in the best possible controlled environment. Hermetically sealed compressor unit with capacity of 0.75HP the condenser is the forced air-cooled type for which condenser fan and motor has been provided. The outside diameter of condenser is 3/8. Size of condenser as per standard specification is 11 x 10 x 3 Rows. The evaporator unit was properly insulated to the best of the effort such as to minimize the heat leakage into the system from the surrounding. Overall dimension of Copper tubes (Bore x Length) = 0.36 x 5 x 1 were used for providing the supply and return lines to the flowing fluid in the system. The Capillary tube diameters with different diameter range are used. Refrigerant R134a, R22, R744 was used as the cooling fluid alternately. A filter/drier, specific for R134a, R22 and R744 was installed just after the condenser unit in order to avoid any situation which causes choking of the flow lines. The filter/drier does not allow the flow lines to form ice by absorbing all the moisture particles present in the flowing fluid. Two analogue pressure gauges are used to determine the pressure of the flowing fluid in the high pressure and the low pressure line Pressure Gauge (0 to 300 PSI.): Bourdon type pressure gauge which is used to get pressures at discharge point of compressor exit. Compound Gauge. (-30 to 150 PSI.): Bourdon type pressure gauge which shows both negative pressure (Vacuum) as well as positive pressure in the VCR system. This is used to measure pressures at suction point of compressor. The pressure gauge in the high pressure line was installed just next to the filter/drier and just before the capillary tube. Another pressure gauge was installed in the low pressure return line to measure the pressure of the fluid returning back to the compressor. The temperatures at different points in the VCR system are measured by using RTD (PT 100 Resistance Temperature Detectors) which operates on the principle of change in Resistance with change in temperature of the coil. A digital thermometer was used to determine the temperatures that were to be used in the analysis of the system. The readings of the temperature and pressure of VCR were plotted on the P-H chart and the corresponding enthalpies were noted down and from the values of the enthalpies obtained, the parameters such as refrigeration effect and the compressor work were determined. The carnot or ideal COP of the system was determined by using the temperature limits of the system and the actual COP of the VCR system was calculated by considering the ratio of the refrigeration effect and the compressor work obtained from the PH chart. Refrigerants used for the analysis of VCR system are R22, R134a and R744 alternatively. Figure 1: Schematic of simple VCR Cycle Figure 2: Photograph of simple VCR cycle Parameters to be study: 1. Capillary tube Diameter 2. Capillary tube Configuration 3. Condenser fan speed 4. Forced/Natural air cooled condenser 5. Refrigerant 1. Capillary tube Diameter: Capillary tube with diameters 31 gauge, 36 gauge, 40 gauge are used separately and its effect on performance of VCR cycle are tabulated in table and graphical form in following sections. The length of test section every time is kept constant. 2. Capillary tube Configuration: Capillary tube with different configuration such as helical tube, straight tube and serpentine type tube are used. It can be showed that the refrigeration effect was found to be max in case of helical coiled configuration and was noted least for straight coiled configuration. Also it can be found that mass flow rate is max for straight capillary and least for the helical coiled type tube.
3 3. Condenser fan speed: Condenser fan speed can be varied by arranging a regulator such that speed can be changed from 0 speed i.e. fan is off thus we can say that condition as natural cooled condenser to maximum speed which we can say that the condition is forced air cooled condenser. 4. Forced/Natural air cooled condenser: As mentioned in above point fan may be kept ON or OFF which results in either Natural air cooled or Forced air cooled condenser. Thus detailed effect of these will be studied in upcoming section. 5. Refrigerant: Out of so many refrigerant three refrigerants will be considered for the experimental study and its effect on the performance of the system will be studied. The refrigerants studied are R22, R134a and R744 alternatively. EXPERIMENTAL OBSERVATION AND RESULT 1. Capillary tube diameter and Configuration Capillary tubes of dimensions 31 gauge (0.226 mm) and 36 gauge (0.13 mm) were used as the test sections. The length of each test section was kept constant to 1.5m. For each test section, readings were taken for three alternate configurations i.e. helical coiled, straight coiled and serpentine coiled. Every set of readings consists of minimum five readings such as, two for no load condition and 600ml, 1200ml and 1800ml condition as loaded condition.
4 primarily as "high-temperature" refrigerant for automobile air conditioning and domestic refrigeration. Fig 5 explains that the result of ratio P2/P1 on ordinate to Load condition on abscissa. It shows that ratio P2/P1 is maximum for helical coil at 1200 ml load condition but as load increases after that the ratio P2/P1is decreasing. This shows that it is efficient at 1200 ml load for helical coil, 600 ml load for straight coil and i n between for serpentine coil. Effect of refrigerant temperature on performance of VCR The effect of refrigerant on performance of VCR is shown in graphical form in graph 4. Graph 4 shows the Relation between Saturated temp and Liquid Density for R-22, R- 134a and R-717.It shows that density of R-717(NH3) is much less as compare to R-22 and R-134a which, indicates that Heat carrying capacity for R-717 is less than other. 2. Refrigerants Selection In the last decade tremendous changes were found in the choosing and utilization of refrigerants, mainly in concern with the environmental aspects such ozone layer and global warming or greenhouse effect known as ODP and GWP. Previously there was not much discussion about the scientific selection of refrigerant which is to be used, as the majority of applications could be confirmed by the well known HFC s refrigerant, R11, R22, R502 and ammonia (R717). At the time of selection of refrigerant with their chemical, physical properties and at the time of selection we have to know that condensing temperature and evaporating temperature i.e.temperature range of application. Before selection of compressor and condenser we should know about refrigerant. We had considered different refrigerant for study out of which some we will use. As the operating pressure of equipment is should be within this range. between 0.5 bar to 3 bar, the refrigerant Thus from table 7 Ammonia R717, Tetra fluro ethane R134a and Chlorodifluoromethane R22 are selected alternatively. The main advantage of R-134a is that it is a single-component refrigerant i.e. it does not have any smooth movement on the other hand has difficulty of having its relatively low capacity as compared to refrigerants liker-22. R134a is an inert gas used Effect of Condenser fan speed on performance of system It is found that at higher fan speed, convection coefficient increased thus increasing heat transfer within the evaporator and also condenser with the surroundings, thus reducing the work of the compressor to the refrigerant. VCR cycle was more efficient with fans of evaporator and condenser at highest speeds. Following graph shows the relation between condenser fan speed and COP of system. The curve is drawn on the basis of HRR (Heat Rejection Ratio). From following it can be noted that COP of Helical Coil is maximum all over graph for same input values.the curve for Serpentine type coil has results in-between helical and Straight. It can be shown from the graph 5 that increase in the slope of all coils is decreasing as condenser fan speed decreasing.
5 IV. RESULT AND DISCUSSION The above mentioned experimental study of VCR system involved a thorough observation and analysis of the readings and the values obtained. Every graph and every curve is self-explanatory in itself and points out towards a specific outcome from the study. The above shown readings, calculations, graphs and curves do point out towards some distinct conclusions and inferences which are stated below:- 1. The refrigeration effect produced in VCR system is maximum for the helical coiled capillary tubes whereas is least for straight capillary tubes for each test section. 2. It can also be shown from geometry of tubes that the mass flow rate of refrigerant is maximum in the case of straight capillary tubes and least for helical coiled capillary tubes for each test section. 3. The performance in the case of serpentine coiled capillary tubes all results are laying between to that with helical coiled capillary tube and straight coiled capillary tube. 4. As we decrease the capillary tube diameter from 31 gauge to 36, the refrigeration effect produced tends to decrease. 5. It can be shown from above discussion that Refrigerant R-717 has much less liquid density than others, which indicates that heat carrying capacity in case of R-717 is much less. 6. It can be said from above discussion that as condenser fan speed increases the performance of the system increases upto certain extent but then the slope rate is decreasing. ACKNOWLEDGMENT I highly respond to express my deep gratitude and respect to my guide Prof. Pravin T. Nitnaware for his valuable contribution, inspiring guidance, keen interest and encouragement in completing this work. I would also like to thank all the staff members of Mechanical department for their kind co-operation who made available all facilities for this work. Sathiyaseelan.G, senthil kumar.s Kannan.C (2015) REFERENCES Performance comparison on vapour compression refrigeration system by using alternate refrigerants International Journal of Engineering Research-Online. Mark O. McLinden, Andrei F. Kazakov, J. Steven Brown, Piotr A. Domanski (2014) A thermodynamic analysis of refrigerants: Possibilities and tradeoffs for Low-GWP refrigerant. international journal of refrigeration 38. Shashank shekhar pathak, Prakhar shukla, Sanjeev chauhan, A.K. Srivastava (2014) An experimental study of the Effect of capillary tube diameter and configuration on the performance of a simple vapour compression refrigeration system. IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE). Dr. A. G. Matani, Mukesh K. Agrawal (2013) Effect of capillary diameter on the power consumption of VCRS using different refrigerants. International Journal of Application or Innovation in Engineering & Management (IJAIEM). R S Mishra (2013) Thermodynamic Performance Evaluation of Multi-Evaporators Single Compressor and Single Expansion Valve and Liquid Vapour Heat Exchanger in Vapour Compression Refrigeration Systems using Thirteen Ecofriendly Refrigerants for Reducing Global Warming and Ozone Depletion International Journal of Advance Research and Innovation. Samira Benhadid-Dib, Ahmed Benzaoui (2011) Refrigerants and their impact in the environment. Use of the solar energy as the source of energy. MEDGREEN LB. Asst. Lecturer. Haider ali hussen (2013) Numerical Analysis Of Refrigerant Flow In Different Types Of Capillary Tubes Used R1270 Journal of Engineering and Development, Vol. 17, No.6, December 2013, ISSN
An experimental study of the effect of evaporator temperature on the compressor work of a simple vapour compression refrigeration system
ISSN (ONLINE): 2321-3051 INTERNATIONAL JOURNAL OF RESEARCH IN AERONAUTICAL AND MECHANICAL ENGINEERING An experimental study of the effect of evaporator temperature on the of a simple vapour compression
More informationPerformance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers
e-issn 2455 1392 Volume 2 Issue 5, May 2016 pp. 108-116 Scientific Journal Impact Factor : 3.468 http://www.ijcter.com Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl
More informationEXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)
EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) Abstract- With the recent government regulations, of banning the ozone depleting substances and Kyoto protocol
More informationPERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL
PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL K.Thejeswarudu 1, R. Meenakshi Reddy 2 and E. Siva Reddy 2 1 PG Student, Department of Mechanical Engineering, G. Pulla Reddy College
More informationImproving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a
ISSN (e): 0 00 Vol, 0 Issue, 8 August 0 International Journal of Computational Engineering Research (IJCER) Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants
More informationWaghmare Tushar Ramrao, D.S.Nakate
International Engineering Research Journal Performance analysisof vapor compression system by using capillary tube suction line heat exchanger and helical condenser for R134a Waghmare Tushar Ramrao, D.S.Nakate
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical
More informationEffect of capillary diameter on the power consumption of VCRS using different refrigerants
Effect of capillary diameter on the power consumption of VCRS using different refrigerants Dr. A. G. Matani 1, Mukesh K. Agrawal 2 1 Asso. Professor, Mechanical Engineering Department, Govt. College of
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,
More informationExperimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures
Experimental Study on Performance Parameters for Refrigerants, R41a and R44a at Various Air Outlet Temperatures P. Nagaraju P. G. Student Sanketika Institute of Technology and Management Ch. Kiran Kumar
More informationRole of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview
International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationNUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A
ISSN: 2250-0138 (Online) NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A RANENDRA ROY a1, MADHU SRUTHI EMANI b AND BIJAN KUMAR MANDAL c abc Department
More informationEvaluation of Vapour Compression Refrigeration System Using Different Refrigerants
Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Mukesh K. Agrawal, Dr. Ashok G. Matani Abstract- The performance of heat transfer is one of the most important research
More informationNUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A
NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A [1] Ranendra Roy, [2] Madhu Sruthi Emani, [3] Bijan Kumar Mandal [1], [2],[3] Department of Mechanical
More informationPERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS
Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK
More informationEnhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System
Enhancement of COP by Using Spiral and Microchannel instead of conventional of VCR System 1 P.G. Lohote, 2 Dr.K.P. Kolhe. 1 P.G. Student, 2 Professor. 1,2 Department of Mechanical Engineering, JSPM s,
More informationSubscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid
Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance
More informationStudy of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants
International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Study
More informationEXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM
EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM 1 RONANKI SURESH, 2 Dr. K. KALYANI RADHA 1 M.Tech, Mechanical Engineering, JNTUA College of Engineering
More informationEXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM
EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Prof. S.V.Rao 1, Hitesh Sharma 2, Pankaj Kumar Gound 3, Tukaram Walgude 4, Shekhar Gavas 5 1 Prof.
More informationEnhancement of COP in Vapour Compression Refrigeration System
Enhancement of COP in Vapour Compression Refrigeration System M. Krishna Prasanna #1 M.E student, Heat Transfer studies in Energy Systems Department of Mechanical Engg., Andhra University Visakhapatnam-530003,
More informationU.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India
DESIGN OF HYBRID AIR COOLER USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Vimalkirti Shende 1, Sushil Borkar 2, Touseef Iqbal Qureshi 3 Asst. Prof. Nikhil Bhende 1 1,2,3 U.G. Student, Department of Mechanical
More informationEffects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling
ISSN 2395-1621 Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling #1 Mr. Sachin Das, #2 Prof. M. V. Khot #1 Student, Mechanical
More informationijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12
EXPERIMENTAL ANALYSIS OF THE EFFECT OF FIN GEOMETRY ON HEAT TRANSFER RATE THROUGH THE REFRIGERATOR CONDENSER ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12
More informationEXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER
EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional
More informationDEEPAK PALIWAL, S.P.S.RAJPUT
International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-15 623 EXPERIMENTAL ANALYSIS OF HYDROCARBON MIXTURES AS THE NEW REFRIGERANT IN DOMESTIC REFRIGERATION SYSTEM DEEPAK PALIWAL,
More informationInternational Journal of Informative & Futuristic Research ISSN (Online):
Reviewed Paper Volume 2 Issue 9 May 2015 International Journal of Informative & Futuristic Research ISSN (Online): 2347-1697 Performance Comparison of R22 and R290 Refrigerants Using Smaller Paper ID IJIFR/
More informationIJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December
Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser
More informationExperimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator
Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Dr. R. A. Kathar 1, S. D. Surushe 2 1 Associate Professor, Mechanical
More informationA Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes
ISSN 2395-1621 A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes #1 N. Dhekale, #2 Dr. P. A. Patil 1 amardhekale@gmail.com #12 Research Laboratory, Department
More informationEVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22
EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC
More informationInternational Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72
International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015
Page77 Page78 COMPARATIVE ANALYSIS OF PERFORMANCE OF OZONE-FRIENDLY AND LOW GWP HFC REFRIGERANT IN A VAPOUR COMPRESSION REFRIGERATION CYCLE Kashid Hari T. 1,Khatpe Akshay R 1,Khile Parshuram N 1,Ligade
More informationComparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants
[VOLUME 5 I ISSUE 3 I JULY SEPT 2018] e ISSN 2348 1269, Print ISSN 2349-5138 http://ijrar.com/ Cosmos Impact Factor 5.75 Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a
More information[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor
GLOBAL JOURNAL OF ENGINEERING SCIENCE AND RESEARCHES PERFORMANCE ANALYSIS OF VCR SYSTEM WITH TWISTED TAPE CONDENSER BY USING R134a REFRIGERANT Chidige Jhansi* 1 & Dr.Smt.G.Prasanthi 2 *1 PG Research Scholar
More information(Refer Slide Time: 00:00:40 min)
Refrigeration and Air Conditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 10 Vapour Compression Refrigeration Systems (Refer Slide
More informationAdsorption refrigeration system using waste heat
Adsorption refrigeration system using waste heat 1 RISHI SREEKUMAR, 2 SANJEEV SINGH, 3 HIMANSHU SHEKHAR, 4 RAUSHAN KUMAR, 5 Dr. R. S. BINDU 1,2,3,4 BE Students, 5 Professor Mechanical Engineering Department
More informationII. OBJECTIVE OF RESEARCH
Enhancement of Coefficient of Performance of Vapor Compression Refrigeration System Using Diffuser at let of Condenser Mr. Nurul Seraj 1, Dr. S. C. Roy 2 1 Student, 2 Head of Department, Department of
More informationPerformance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant
Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant Bukke Bhagyalathamma 1, Dr.Smt.G.Prasanthi 2 Department 1,2,Department of Mechanical Engineering,PG Scholor
More informationPerformance Optimization of the Evaporative Condenser Design
Performance Optimization of the Evaporative Condenser Design Mit. C. Patel P.G.Student, Mech. Engg.Dept. Institute of Technology, Nirma University, Ahmadabad, Prof. B. A. Shah Mechanical Engineering Department
More informationVolume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation
Thermodynamic Comparison Using HFO-1234yf and HFO-1234ze in the Refrigeration s and in Applications R. S. Mishra Department of Mechanical Engineering, Delhi Technological University, Delhi, India Article
More informationExperimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 14, Issue 1 Ver. V (Jan. - Feb. 2017), PP 75-82 www.iosrjournals.org Experimental Evaluation of
More informationDepartment of MCE, Islamic University of Technology 2. Abstract
Paper ID: TE-85 Study of power consumption characteristics of LPG and R134a in a vapor compression refrigeration system Md. Abu Shaid Sujon 1, Rakibul Hossain Ahmed 2, Dr. A.K.M. Sadrul Islam 3, Sk. Suzauddin
More informationExperimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant
Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant Shubham Rangari 1, Shubham Mahakalkar 2, Shubham Tiple 3, Praharsh Marathe 4, Sameer Bansod 5, Sunnyraj Katam 6, Suraj Nagrare
More informationDesign & Fabrication of Hybrid Cooler
IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 11 April 2016 ISSN (online): 2349-6010 Design & Fabrication of Hybrid Cooler Shashank Chauragade Mukul Kshirsagar
More informationAir Conditioning System with Modified Condenser Ducts and Evaporative Cooling
Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling Dr. Akash Langde 1, Zeeshan Jamal 2, Shahrukh Jamal 3, Mohammad Shumoil Ansari 4 1Professor, Department of Mechanical Engineering,
More informationA Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant
International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article A Review
More informationPerformance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile
Available online at www.pelagiaresearchlibrary.com Advances in Applied Science Research, 2013, 4(5):232-237 ISSN: 0976-8610 CODEN (USA): AASRFC Performance analysis of ejector refrigeration system with
More informationA Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration
ANALELE UNIVERSITĂłII EFTIMIE MURGU REŞIłA ANUL XXI, NR. 1, 2014, ISSN 1453-7397 Feiza Memet A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration
More informationPerformance Enhancement of Mini Refrigerator with Phase Change Materials
Performance Enhancement of Mini Refrigerator with Phase Change Materials Souptik Acharya 1, Manu Jose 2 and Risikesh Choudhury 3 Souptik Achraya,student at St. Martin s Engineering College Manu Jose T,
More informationNumerical Study on Improvement of COP of Vapour Compression Refrigeration System
Numerical Study on Improvement of COP of Vapour Compression Refrigeration System Sanath Kumar K H 1, Arun Kumara K S 2, Nissar Ahmed 3 Assistant Professor, Department of Mechanical Engineering, VVIT, Bangalore,
More informationPerformance investigation of Air-conditioning system using ejector as expansion device
International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Performance
More informationSarthak Thakar, 2 R.P.Prajapati 1
PERFORMANCE ANALYSIS OF A DOMESTIC REFRIGERATOR USING VARIOUS ALTERNATIVEREFFRIGERANT 1 Sarthak Thakar, 2 R.P.Prajapati 1 PG Student, 2 Assitant Professor 1,2 Thermal Engineering Department, Sal Institute
More informationWaste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System
Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System 1 Avnish Chandra Pandey, 2 M. Akash Rao, 3 Sabyasachi Sahoo, 4 Narendra Kumar Students, Department of Mechanical
More informationInternational Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:
Comparison of Second Law Efficiency and Exergy Analysis of Refrigerants R-12, R-22, R-407C Influenced by Evaporator Temperature for Vapour Compression Refrigeration System Md Ozair Arshad Guest Faculty,
More informationFABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE
FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE PRESENTED BY J.SARAVANA PERUMAL 1 Saravananjsp005@gmail.com D.SATHEESH 2 Satheeshd123@gmail.com Contact no: 9789080381 DEPARTMENT
More informationExperimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering
IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Experimental performance evaluation of heat pump by using CO 2 as a refrigerant To cite this article: V K Venkatesh et al 2016
More informationAnalysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant
Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET
More informationExperimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators
IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 11 April 2017 ISSN (online): 2349-6010 Experimental Investigations of Different Types of Condensers on the Performance
More informationAN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS
AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore
More informationVolume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation
Methods for Improving Thermodynamic Energy and Exergy Performance of Vapour Compression Refrigeration Systems using Thirteen Ecofriendly Refrigerants in Primary Circuit and TIO 2 Nano Particles Mixed with
More informationInternational Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015
International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015 ISSN: 2289-4152 Performance Evaluation of Vapour Compression Refrigeration System Using Double Effect Condensing
More informationInternational Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5
International Journal of Research in Engineering and Innovation Vol-3, Issue- (9), -5 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com ISSN
More informationStudy of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator
Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator Mr. Subodh S. Deshpande Department of Mechanical Engineering M.G.M.s College of Engineering
More informationExperimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant
Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant Satish parmar 1, Ravindra Randa 2 1M.TECH. Scholar, Department Of Mechanical
More informationAnalysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine
IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 11 April 2015 ISSN (online): 2349-6010 Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling
More informationCHAPTER 1 INTRODUCTION
1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,
More informationPERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL
International Journal of Technical Innovation in Modern Engineering & Science (IJTIMES) Impact Factor: 3.45 (SJIF-2015), e-issn: 2455-2585 Volume 3, Issue 10, October-2017 PERFORMANCE ANALYSIS OF VAPOUR
More informationVolume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation
Use of Hydrocarbons in Low Temperature Circuit in Terms of First Law and Second Law of Four Stage Cascade Refrigeration of Semen Preservation R.S. Mishra Department of Mechanical Engineering, Delhi Technological
More informationExperimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System
216 IJSRSET Volume 2 Issue 4 Print ISSN : 2395-199 Online ISSN : 2394-499 Themed Section: Engineering and Technology Experimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System
More informationThermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23
Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23 A. D. Parekh, P. R. Tailor Abstract The Montreal protocol and Kyoto protocol underlined the need of substitution
More informationThermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate
International Journal of Research in Engineering and Innovation (IJREI) Vol-1, Issue-2, (2017), 49-53 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationINTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY
INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK EXPERIMENTAL INVESTIGATION OF HELICAL COIL AND STRAIGHT TUBE HEAT EXCHANGER 1.
More informationPage 116
Evaluation of Coefficient of Performance of a Vapour Compression Refrigeration System with Change in Length of Condenser Saragadam Vinay Kumar 1, Karteek Naidu Mariserla 2 #1Student of M.Tech in Mechanical
More informationA study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion
A study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion Prepared for the Public Commenting Meeting of Ph.D program February 28,
More informationUse of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion
International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018), 201-208 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationIJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Experimental Study on Performance of Condenser of Two Different Types Used in Window Air Conditioner Madhu Jhariya *1, P.K. Jhinge
More informationNumerical Simulation of Window Air Conditioner
Numerical Simulation of Window Air Conditioner Mathewlal T 1, Kalpesh Patil 2, Gauri Thorat 3, Anisha Ankush 4, Ambarish Pote 5, Kartik Doshi 6 ( 1 Associate ProfessorMechanical Engineering Department,
More informationJJMIE Jordan Journal of Mechanical and Industrial Engineering
JJMIE Jordan Journal of Mechanical and Industrial Engineering Volume 9 Number 4, August.21 ISSN 199-666 Pages 289-296 Thermodynamic Analysis of R12a and Dimethylether Refrigerant Mixtures in Refrigeration
More informationEnhancement of COP using Nanoadditives in Domestic Refrigerator
ISSN 2395-1621 Enhancement of COP using Nanoadditives in Domestic Refrigerator #1 Mr.Sajjan Kawade, #2 Prof P.T.Kharat 1 sajjankawade@gmail.com 2 pradip5872@gmail.com #1 P.G. Student, Mechanical Engineering
More informationPerformance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS
Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS Lalit Narayan, Abhishek Arya 2,2 M. Tech. Scholar, Associate Professor,,2 Scope College of Engineering, Bhopal, India Abstract: The
More informationRefrigeration Cycle Demonstration Unit R633
Refrigeration Cycle Demonstration Unit R633 Figure 1: R633 Unit Ozone friendly, low pressure, non-toxic working fluid allows evaporation and condensation to be seen in glass cylinders. A Bench top unit
More information[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY PERFORMANCE ANALYSIS OF VCR SYSTEM WITH VARYING THE DIAMETERS OF HELICAL CONDENSER COIL BY USING R-134A REFRIGERANT R.Hussain
More informationEXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE
Karthikeyan, K. et al.: Experimental Investigations on Automobile Air S515 EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE by Karthikeyan
More informationOptimum Length of a Condenser for Domestic Vapor Compression refrigeration System
Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System T. Mahaboob Basha 1, H.Ranganna 2,G. Maruthi Prasad Yadav 3 1.PG Student, Mechanical Engineering Dept, St Johns College
More informationEnergy Use in Refrigeration Systems
2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is
More informationReheating Refrigeration System
Vol.2, Issue.1, Jan-Feb 2012 pp-271-275 ISSN: 2249-6645 Reheating Refrigeration System Meemo Prasad Assistant Engineer, SEPCO1 Abstract The title Reheating Refrigeration System has the objective to utilize
More informationPerformance Assessment of Water Cooled Condenser Refrigeration System
Energy and Power 2017, 7(3): 70-74 DOI: 10.5923/j.ep.20170703.03 Performance Assessment of Water Cooled Condenser Refrigeration System Sheetal Narayan Shetty *, Prashanth Kamath Department of Mechanical
More informationPerformance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a
International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 Volume 4 Issue 6 ǁ June. 2016 ǁ PP. 52-57 Performance analysis of a vapour compression
More informationAnalysis of Coefficient of Performance & Heat Transfer Coefficient on Sterling Cycle Refrigeration system.
RESEARCH ARTICLE OPEN ACCESS Analysis of Coefficient of Performance & Heat Transfer Coefficient on Sterling Cycle Refrigeration system. * Narendra.N.Wadaskar 1, Dr S.K.Choudhary 2, Dr R.D.Askhedkar 3 Ph.D.
More informationPressure Enthalpy Charts
Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance
More informationExperimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance
Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule
More informationPerformance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants
Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants CHENNUCHETTY CHINNARAJ * Associate Professor in Mechanical Engineering, Government College of
More informationENHANCEMENT OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING NANOFLUIDS
International Research Journal of Engineering and Technology (IRJET) e-issn: 9-006 Volume: 04 Issue: 04 Apr -017 www.irjet.net p-issn: 9-007 ENHANCEMENT OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING
More informationDesign of LPG Refrigeration System
Design of LPG Refrigeration System Sethu Sathayan 1, Gopakumar M G 2, Jaya Krishnan S 3, Nanda Gopan 4, Nithin S 6 Assistant Professor, Department of Mechanical Engineering, SNIT Adoor, Kerala, India 1
More informationME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3
ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes
More informationExperimental investigation on the performance of air conditioner using R32 Refrigerant
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 12, Issue 4 Ver. V (Jul. - Aug. 2015), PP 139-144 www.iosrjournals.org Experimental investigation
More informationAn Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 An Investigation Into The Influence Of Improved Refrigeration Cycle And
More informationVCR SYSTEM USING R-600a/ POE OIL/MINERAL OIL/NANO-SiO 2 AS WORKING FLUID: AN EXPERIMENTAL INVESTIGATION
VCR SYSTEM USING R-600a/ POE OIL/MINERAL OIL/NANO-SiO 2 AS WORKING FLUID: AN EXPERIMENTAL INVESTIGATION M.S.Bandgar 1, R. N. Kare 2 1,2 Assistant Professor, JSPM s Imperial College of Engineering & Research,
More informationCHAPTER 1 INTRODUCTION
CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties
More information