NEW AR-L AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS. Higher energy efficiency. Increased thermal comfort
|
|
- Jessie Denis Parker
- 5 years ago
- Views:
Transcription
1 NEW AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS Higher energy efficiency Increased thermal comfort Higher capacity than standard radiant ceilings Significant space savings Reduced new construction costs Virtually no maintenance costs Increased ceiling flexibility
2 PANEL FRONT PANEL BACK The and AR-C are high capacity radiant cooling linear systems based on the principles of radiant technology. By separating the linear radiant elements with a gap, the and AR-C couple the radiant cooling effects of standard radiant panels with a convective component. Chilled and AR-C ceilings create natural convection by cooling the surrounding air as it passes over the surface facing the plenum. As the denser air falls into the occupied zone, warmer air is pulled over the element, incorporating convective cooling capacity of the and AR-C with the radiant capacity of the cool surface. The approximate breakdown of heat transfer of the chilled radiant system is 30% by thermal radiation and 70% by natural convection. When used for heating the and AR-C transfer heat mainly through thermal radiation with room surfaces, where they increase the average unheated surface temperature of the room.
3 Thermal Natural ThermalConvection AR-C Thermal Natural ThermalConvection ENERGY EFFICIENCY The specific heat capacity of water is four times higher than air. Therefore, to remove a given amount of heat from a building using or AR-C radiant hydronic system Copper an Tubes requires 25% of the energy required by an all-air system. Because and AR-C are water-only systems, they can handle the sensible portion of a building s HVAC load and must be paired with a fresh air system for ventilation and latent load removal. MODELS Return to Room Return to Room Cross Brace Return to Room Panels are available in either an elliptical section or a flat surface profile. The surface profile is dependent on the application and architectural aesthetics of each unique project. Contact Steel Ceilings for more information and suggestions on which profile to use for your application.
4 Multiple profiles in assembled unit Both surface profiles are designed to allow air movement through openings between the profiles, increasing the capacity of the unit and providing an effective means of dealing with sensible cooling loads. and AR-C can be installed in a variety of applications including full or cloud ceiling areas. The visible surfaces of the aluminum extrusion and bracing are usually painted white. Optional custom colors are available which meet the emissivity requirements 0.625" O.D. (0.50" nominal) copper tubing rails Cooling fins 1" typical gap between profiles 5" typical profile width TYPICAL DESIGN The precision-extruded aluminum profiles are formed with two conduction rails to accommodate a single or twin copper tube and provide cooling fins which are rounded off at the outer end. The extruded profiles are five inches wide with lengths and the number of profiles variable to fit virtually any design. The gap between the extruded profiles is typically 1.0 inch. Variable lengths available to suit virtually any application The copper tube is press-fit into the conducting rails of the extrusion ensuring continuous contact between the copper and the aluminum along the entire length providing optimal heat transfer. Copper tubing with a
5 Cross Brace Cut Out inch O.D., (1/2 inch nominal) is used in the fabrication of the system. The connections between the modules and the distribution lines can be made via copper tubing and/or flexible metal hoses with stainless steel sheathing. After installation, the entire system must be checked for leaks The supply cold water temperature should be selected to be above the dew point of the space to avoid condensation. Dew point sensors can be employed to monitor, and if need be, adjust the water temperature. Special design options such as folding modules, sprinklers, lighting openings, air intake, etc., are available. Torsion Springs ACCESS PANEL DESIGN Panels can be designed into the and AR-C modules to allow access to the plenum area. The access panels are designed with torsion springs allowing the panel to be pulled straight down without any special tools and swung out of the way. Access panels can be placed within the ceiling system where needed.
6 PERFORMANCE DATA BTUH/FT Capacity Output ROOM AIR - MWT BASED ON 30% AREA VS. OPEN AREA Correction Factor PERCENT SAIL AREA/OPEN AREA BTUH/FT AR-C Capacity Output ROOM AIR - MWT BASED ON 30% AR-C AREA VS. OPEN AREA Correction Factor PERCENT SAIL AREA/OPEN AREA INSTALLATION Radiant panels are designed with crosschannels near each end of the panels with an additional two to five cross-channels (based on the length of the panel) spread out over the length of the panel. The channels are used for bracing the panel as well as hanging the panel. The radiant panels should be suspended per local building codes using such items as threaded rod or wire with additional options of carabineer etc. INSTALLATION OPTIONS Within a suspended ceiling: Ensure that the top of the panel is at least 2 from the structure above Mounted in visible sections: Panel sections should be separated by ½ -1 Concealed installation application above perforated panels: Ensure the panel is at least 2 above either the perforated panel or the overhead structure
7 RADIANT SYSTEM BENEFITS HIGHER ENERGY EFFICIENCY INCREASED THERMAL COMFORT HIGHER CAPACITY SIGNIFICANT SPACE SAVINGS The heating capacity of water is four times higher than air, providing a significant transport energy savings when compared to an all-air system. The thermal environment has a significant effect on the performance of building occupants. The high-convective component can give the and AR-C greater capacity than a standard radiant ceiling. Radiant systems significantly reduce both the volume and velocity of air transported through the building, which reduces the size of the plenum and duct work. Radiant systems only require 25% of the building volume occupied by a traditional air-conditioning system. NEW BUILDINGS Floor height can be reduced since a large plenum area is not needed resulting in a reduced overall building height and a corresponding reduction in construction costs. EXISTING BUILDINGS COSTS Increased flexibility through higher ceilings. Cooling systems can be installed in buildings which were previously impossible to fit with conventional all-air systems. Lower energy cost due to higher efficiency Virtually no maintenance costs High quality long-life product Systems can be easily reconfigured to adapt to changes in the floor plan layout Steel Ceilings Inc. 451 East Coshocton Street Johnstown, OH T: (800) F: (740) E: info@steelceilings.com
Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation
Cooling and heating systems Static cooling ceiling system SKS-/3 DS 10 E 01.010 Static cooling ceiling system SKS-/3 Main features Preliminary remarks / Applications 3 Main dimensions and materials 3 Construction
More informationMETALWORKS. Airtite Panels. Radiant Ceiling Systems
METALWORKS Airtite Panels Radiant Ceiling Systems Efficient Temperature CONTROL MetalWorks Airtite radiant ceiling systems circulate hot or cold water through concealed copper tubing providing sustainable
More informationCarat. Chilled beams. Use. Worth noting. Installation. Key figures. lindab chilled beams
22 Use Lindab's chilled beam supplies cooling with a low air velocity to the room below. It offers many possibilities and great flexibility. For example, it is possible to paint any color you want. Installation
More informationKLIMA Active Chilled Beams
KLIMA 2 600 Active Chilled Beams Index Subject Page Index 1 Introduction 2 General description 3-4 Product features 5-6 Dimensions 7 Performance data 8-11 Section example Guide specifications 13 1 Introduction
More informationStatic cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection
DS 4094 E 05.2007/1 Technical Selection Main features 2 Preliminary remarks 3 Construction design 3 Main dimensions and materials 3 Design data 3 Layout example 5 Design specifications 8 Installation instructions
More informationHydronic Heating Fan Coils Radiant ceiling systems Water Source Heat Pumps Alumline Radiant Heating and Cooling Ceiling Panels
Hydronic Heating Fan Coils Radiant ceiling systems Water Source Heat Pumps Alumline Radiant Heating and Cooling Ceiling Panels Catalog INTRODUCTION Zehnder Alumline: provides optimal comfort and energy
More informationWEAVE RADIANT TEXTILE PANEL. Credit Reimann Architecture
RADIANT TEXTILE PANEL Credit Reimann Architecture Developed in conjunction with Kvadrat Soft Cells, Weave radiant textile panels by Price provide thermal and acoustic comfort as well as infinite design
More informationModular Active. Chilled. Beams
Modular Active Chilled Beams How Twa MAC Beams Work Primary air (100% outside air) is dehumidified to between 50-57 F dew point and is used to: control the latent requirements of the space, provide fresh
More informationINTRODUCTION HOW DO RADIANT PANELS WORK? A common misconception, even among heating professionals, is that heat rises. In fact, hot air rises and cold
RADIANT PANELS TRENCH PERIMETER GRILLES ELEMENTS PIPER FARM, BROMLEY GREEN ROAD, ASHFORD, KENT. TN26 2EF TEL: 01233 733308 FAX: 01233 733883 E-MAIL: sales@feukltd.com RADIANT PANEL RANGE INTRODUCTION HOW
More informationSECTION H. Engineering Guide Radiant Products. Please refer to the Price Engineer s HVAC Handbook for more information on Radiant Heating and Cooling
SECTION H Radiant Products Please refer to the Price Engineer s HVAC Handbook for more information on Radiant Heating and Cooling Introduction To Radiant Heating and Cooling Radiant heating and cooling
More informationChilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.
TRACE 700 incorporates two chilled beam strategies: passive and active. Passive chilled beams consist of a fin-and-tube cooling coil, contained in a housing (or casing), suspended from the ceiling. Chilled
More informationChilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle
Chilled Beam and Radiant Cooling Basics Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle nsearle@dadanco.com Contents Radiant Ceilings & Chilled Beam Basics Energy & Space Savings First and
More informationPassive chilled beams
X X testregistrierung Passive chilled beams Type with frame, with perforated metal facing without perforated metal facing, RAL 9005, black Passive chilled beam in nominal lengths of up to 3000 mm and with
More informationTemperature Control and Zoning of UFAD Systems
Temperature Control and Zoning of UFAD Systems Presented by TROX USA Raised access flooring systems have become a very popular conduit for the delivery of power, voice and data services, as their accessibility
More informationENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory
Overview of Chilled Beam Technology Purpose Chilled beam technology is new to the United States but has been used in Europe since the 1950 s. Chilled beams can reduce energy costs, improve indoor air quality,
More informationSwegon PACIFIC. Integrated chilled beam PACIFIC CHILLED BEAM KEY FIGURES
Swegon PACIFIC Integrated chilled beam PACIFIC CHILLED BEAM The PACIFIC is a high performance chilled beam for installation in false ceilings. Built-in flexibility, designed to meet the needs of today
More informationHalton CPT Passive Chilled Beam
Passive Chilled Beam Ceiling-mounted passive chilled beam Installation above an open grid or perforated ceiling Quiet operation No moving parts Well suited for spaces with high cooling loads, low humidity
More informationNOVEMBER 2012 THE EUROPEAN EXPERIENCE
Radiant-cooling systems have progressed in the last few decades, garnering attention as a comfortable and energy- and material-efficient option. 1 Compared with air radiant-cooling hydronic systems use
More information451 East Coshocton Street Johnstown, OH (800) Fax (740)
451 East Coshocton Street Johnstown, OH 43031 (800) 848-0496 Fax (740) 967-1478 info@steelceilings.com www.steelceilings.com Image courtesy of North Carolina State University TABLE OF CONTENTS INTRODUCTION
More informationKrantz. Multifunction exposed ceiling AVACS. Cooling and heating systems
Krantz Multifunction exposed ceiling AVACS Cooling and heating systems DS 4170 E 07.16 Preliminary remarks and construction design Preliminary remarks The multifunction exposed ceiling AVACS is designed
More informationDisplacement Ventilation
Displacement Ventilation Displacement Ventilation Displacement Ventilation vs. Dilution Ventilation Characteristics Design Considerations Layout and Selection Product Overview Casino Case Study Dilution
More informationWHAT - HOW - WHY - WHERE PROTERCEILING RADIANT CHILLED CEILINGS COMFORT - EFFICIENCY - SAVINGS - AESTHETICS
WHAT - HOW - WHY - WHERE PROTERCEILING RADIANT CHILLED CEILINGS COMFORT - EFFICIENCY - SAVINGS - AESTHETICS The radiant principle - all bodies emit thermal radiation. They also absorb thermal radiation
More informationChilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2
Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 john.woollett@swegon.se, jonas.akesson@swegon.se SUMMARY The main focus of the paper will be on active beam technology regarding
More informationChilled Beams. Getting a Warmer Reception
Chilled Beams Getting a Warmer Reception Gain an understanding of how chilled-beam technology works, the difference between active/passive chilled beams and potential applications for its use. B y G r
More informationChilled Ceiling Elements
2/27/EN/2 Chilled Ceiling Elements Type WK-D-WF Convective chilled ceilings providing excellent visual results TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/202-265 Heinrich-Trox-Platz e-mail
More informationUnits for suspended ceilings
X X testregistrierung Units for suspended ceilings Type, hinged induced air grille, water connections Active chilled beam with two-way air discharge and horizontal heat exchanger, suitable for grid ceilings
More informationProduct Data. Features/Benefits. 36CBAC,AE,AF,AH,AQ,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm
Product Data 36CBAC,AE,AF,AH,AQ,AN, PB,PD,PS Series Active and Passive Chilled Beams 11 to 190 cfm 36CBAC A36-449.eps Chilled beam units offer: An increase in total airflow Sensible cooling and heating
More informationUnits for suspended ceilings Type DID632
Type with hinged induced air grille water connections Active chilled beam with two-way air discharge and horizontal heat exchanger in lengths from to 0 feet Active chilled beam for heating and cooling,
More informationCooling Strip Model SPB
Cooling Strip Model SPB Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980 - 200 info@schako.de www.schako.de Contents Description...3 Advantages...
More informationIRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE
IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE Cooling System RADIANT COOLING PIPING LAYOUT Proposal for the REHAU core temperature control (CCTC) pipe size: RAUTHERM S 20x2,0mm
More informationModula Standard Performance
the future of space conditioning Modula Standard Performance heating panel Application Commercial, hospitals, hotels, schools, shops, sports halls, offices, laboratories, food industry etc. Installation
More informationHeating and cooling ceiling systems Suspended ceiling systems. Heating Cooling Fresh Air Clean Air
Heating and cooling ceiling systems Suspended ceiling systems Heating Cooling Fresh Air Clean Air The complete heating and cooling ceiling systems Customers can now order a fully suspended heating and
More informationContact, Overview, Index. Ceiling Heating/Chilled. Plexus. Professor. Pilot. Architect. Polaris I & S. Plafond. Podium. Celo. Cabinett. Capella.
Contact, Overview, Index Ceiling Heating/Chilled Plexus Professor Pilot Architect Polaris I & S Plafond Podium Celo Cabinett Capella Fasadium Atrium H & C /Loggia Regula Drypac TM Lighting TEKNOsim 0 0.00
More informationRay Magic Quad Metal panels for suspended ceiling
panels for suspended ceiling ceiling system A great investment for a better Thermal Wellbeing TM Messana Radiant Cooling ceiling systems incorporate heating and cooling in a unique solution of high-end
More informationTechnical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer
Technical Development Program PRESENTED BY: COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems Ray Chow Sales Engineer TDP Updates Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section
More informationLinear Radiant Ceiling Panels. Catalog. Cooling Fresh air Clean air
Linear Radiant Ceiling Panels Catalog Heating Cooling Fresh air Clean air Zehnder everything you need to create a comfortable, healthy and energy-efficient indoor climate Heating, cooling, fresh and clean
More informationSEMCO CHILLED BEAMS INDOOR AIR QUALITY AND ENERGY SAVINGS FANLESS FILTERLESS SPACE CONDITIONING
FANLESS FILTERLESS SPACE CONDITIONING SEMCO CHILLED BEAMS INDOOR AIR QUALITY AND ENERGY SAVINGS IQHC Active Chilled Beam An intelligently designed active chilled beam that has the highest industry cooling
More informationRADIANT PANELS COMMERCIAL BUILDINGS INNOVATIVE VENTILATION & HEATING
RADIANT PANELS COMMERCIAL BUILDINGS A guide to Radiant Panels, including our unique product range, consultancy service and accessories. INNOVATIVE VENTILATION & HEATING www.pricetwa.co.uk FLEXIBLE, INTEGRATED
More informationUnits for suspended cei lings
. X X testregistrierung Units for suspended cei lings Type, hinged induced air grille, water connections Chilled Beams No. 09.2.432 Eurovent certification HYGIENISCH GETESTET V DI 6022 Tested to VDI 6022
More informationBTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa
FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation BTBa CEILING UNIT FLUSHLINE BTBa FLUSHLINE BTBa is a complete climate system offering immense flexibility. Ideal for large areas with
More informationAPPLICATION GUIDE BEAMS
BEAMS There is an increasing need for energy efficient air conditioning systems as energy codes become more stringent. Chilled beam systems are one such alternate to traditional all air conditioning systems.
More informationUse. Worth noting. Key figures. Installation. linx industries chilled beams. the beam is mounted on a standard T-support.
63 Use Lindab's supply air beam has a large cooling capacity and can therefore be used to advantage in rooms with substantial cooling requirements. In terms of appearance, looks similar to Professor. Polaris/Professor
More informationRadiant Heating & Cooling for Commercial Buildings
Radiant Heating & Cooling for Commercial Buildings Kaveesh Padiachy, PEng, PMP, LEED AP Business Development Manager Central Canada kaveesh.padiachy@uponor.com www.uponorpro.com/engineering Radiant Heating
More informationUnderfloor Air Systems. How It s Different: Overhead vs. Underfloor Air Systems
Underfloor Air Fresher Design Developers, building owners and architects face a complex challenge: build buildings that are not only pleasing aesthetically, but also are efficient, flexible and smart.
More information1.1 This section applies to air handling units for HVAC Systems.
AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling
More informationEnergy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for
More informationEverything you need to know about Radiant Heating but didn t dare ask
Decorative radiators Comfortable indoor ventilation Heating and cooling ceiling systems Clean air solutions Everything you need to know about Radiant Heating but didn t dare ask Introduction Radiant heating
More informationRADIANT PANELS COMMERCIAL BUILDINGS INNOVATIVE VENTILATION & HEATING
RADIANT PANELS COMMERCIAL BUILDINGS A guide to Radiant Panels, including our unique product range, consultancy service and accessories. INNOVATIVE VENTILATION & HEATING www.pricetwa.co.uk FLEXIBLE, INTEGRATED
More informationLinear Floor Heaters
Linear Floor Heaters The Price Linear Floor Heater family provides ultimate flexibility in terms of style, performance, and ease of installation. Using room-side heat virtually eliminates the requirement
More informationLOW STATIC HYDRONIC DUCTED UNIT
LOW STATIC HYDRONIC DUCTED UNIT PDWA-~AC SERIES PDWA(4R)-~-V-MEDC PDWA(4R)-~-V-MEEU PDWA(R)-~-V PDWA(R+1)-~-P Model cooling capacity( KW) at Medium Speed cooling capacity (KW) at Medium Speed cooling capacity
More informationlindab ventilation Lindab Comfort Waterborne indoor climate solutions Product overview
lindab ventilation Lindab Comfort Product overview Products within the Lindab Waterborne solutions, e.g. chilled beams, facade systems, radiant heating and cooling panels, uses water to regulate the room
More informationCHAPTER 4. HVAC DELIVERY SYSTEMS
CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer
More informationADRIATIC VF. Active chilled beam with cooling, heating and ventilation QUICK FACTS
Active chilled beam with cooling, heating and ventilation QUICK FACTS The ADRIATIC VF is a chilled beam with integrated recirculated air opening in the face plate. Air is discharged into the room along
More informationHow to ensure Thermal Comfort in buildings with CFD
How to ensure Thermal Comfort in buildings with CFD Using CFD Simulations to analyze and improve HVAC Systems Simulation in your browser How to Ensure Thermal Comfort in Buildings with CFD How to use CFD
More informationUFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas
UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully
More informationEHH SERIES DRAW THROUGH FAN COILS CFM
EHH SERIES DRAW THROUGH FAN COILS 400-5000 CFM TABLE OF CONTENTS TABLE OF CONTENTS 2 INTRODUCTION 3 GUIDE SPECIFICATIONS 4 UNIT OVERVIEW 6 TECHNICAL DATA 8 DIMENSIONS 10 COMPUTER SELECTION 11 GEMCOOL PROFILE
More informationraymagic quad Installation, Operation & Maintenance Manual
Installation, Operation & Maintenance Manual The service panels 3 Features 4 Type of Finish 5 Assembly Instructions 5 Hydraulic connections 7 Pipe Repair Instructions 3 Thermal Performance 4 Head Loss
More informationZIP Radiant Heating and Cooling Ceiling Panels. Catalog
ZIP Radiant Heating and Cooling Ceiling Panels Catalog Heating Cooling Fresh Air Clean Air Zehnder everything you need to create a comfortable, healthy and energy-efficient indoor climate Heating, cooling,
More informationRadiant Snap-In Formed Metal Panels
Radiant Snap-In Formed Metal Panels Energy Efficient Comfortable Clean Quiet 395 West 1100 North North Salt Lake, Utah 84054 T EL (801) 292-0493 FAX (801) 292-9908 WATER PRESSURE DROP HEATING PERFORMANCE
More informationPolaris-I-60. active chilled beam. the future of space conditioning
the future of space conditioning Polaris-I-60 active chilled beam Function Cooling and supply air with two-way air distribution Available with heating and integrated controls Application Offices, hotels,
More informationHalton Rex for Vario R6O - Variable air volume chilled beam
Halton Rex for Vario R6O - Variable air volume chilled beam Halton Rex for Vario chilled beam is: Combined cooling, heating, and supply air unit for flush installation within a suspended ceiling Well suited
More informationIDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions
IDL20e (2 way discharge) IDS60e ( way discharge) Frequently Asked Questions UDI (vertical discharge) Inffusers INFFUSER FREQUENTLY ASKED QUESTIONS The following are frequently asked questions (FAQ s) on
More informationActive Chilled Beams
T 2.4/12/US/7 Active Chilled Beams DID61 and DID62 series TROX USA, Inc. 405 Settingdown Circle www.troxusa.com Cumming, GA 0028 e-mail trox@troxusa.com Telephone 770.569.14 Facsimile 770.569.14 Contents
More informationUse. Worth noting. Key figures. Installation. linx industries chilled beams
71 Use Lindab's supply air beam has a large cooling capacity, uses one-way air injection and can therefore be used to advantage in rooms with small spaces and substantial cooling requirements. In terms
More informationDARTMOUTH COLLEGE DESIGN March 15, 2003 & CONSTRUCTION GUIDELINES
SECTION 15830 HEATING & COOLING TERMINAL UNITS PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. All fan coil units shall be sized to meet design load while operating at medium speed. In extreme noise sensitive
More informationEnriching Environments
Enriching Environments 2 Enriching Environments We understand the difference an improved internal environment can make 3 Contents 4 5 6 7 8 9 10 11 About us Heating and cooling coils Fan convectors Trench
More informationHood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL
The Kitchen Cool by Hood Depot is a conditioned make up air unit design with flexibility, form and function kept in mind. Our unit offers a variety of configurations that allow the customer to customize
More informationPRODUCTS TAO TAO PRODUCT: ADVANCING THE SCIENCE OF AIR DISTRIBUTION. temperature ambient optimizer. Redefine your comfort zone.
A I R D I S T R I B U T I O N PRODUCTS PRODUCT: TAO TAO temperature ambient optimizer F O C U S 04 ADVANCING THE SCIENCE OF AIR DISTRIBUTION Redefine your comfort zone. www.titus-hvac.com Rethink what
More informationActive & Passive Beams
Active & Passive Beams www.price-hvac.com Active & Passive Beams Introduction Beam systems are an alternative to traditional all-air conditioning systems. Beams use water to move energy through a building
More informationModule 1: Introduction to Radiant Cooling. Pierre Jaboyedoff
Module 1: Introduction to Radiant Cooling Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Heat Transfer Basics Human Body Heat Exchange Radiant Cooling Basics Radiant Cooling Suitability? Radiant
More informationA. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.
Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationAir magic NTD500 Neutral Temperature Dehumidifier Air magic HRV500 Heat Recovery Ventilation. designed for radiant cooling systems.
Air magic NTD500 Neutral Temperature Dehumidifier Air magic HRV500 Heat Recovery Ventilation designed for radiant cooling systems User s Manual CONTENTS 2 Chapter 1 GENERAL INFORMATION page 4 Chapter 2
More informationLindabCapella. Supply air beam
lindab we simplify construction Lindab Supply air beam 0.06 0.06 Lindab Ventilation Lindab Ventilation. A/S. All forms All forms of reproduction of reproduction without without written written permission
More informationThe swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.
Halton CSW Swirl comfort unit for ceiling installation The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply. A combined cooling, heating, and supply-air unit for flush
More informationRadiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems
Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems CBE Timothy Moore CENTER FOR THE BUILT ENVIRONMENT SimBuild
More informationMHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH
MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH 318 MHNCCX NOMENCLATURE BREAKDOWN 4-Pipe Heat/Cool Ceiling Concealed Fan Coil MHNCCW- XX - XX Ceiling Concealed
More informationspc-hvac.co.uk THERMATILE PLUS HEATING & COOLING RADIANT CEILING PANELS INNOVATION WITH STYLE Active
spc-hvac.co.uk THERMATILE PLUS HEATING & COOLING Active RADIANT CEILING PANELS INNOVATION WITH STYLE ABOUT SPC ABOUT SPC THE COMPANY S & P Coil Products Limited is a UK based specialist manufacturer and
More informationRittling Element. Catalog
Hydronic Heating Fan Coils Radiant ceiling systems Rittling Catalog Water Source Heat Pumps Zehnder decorative radiators Heating and cooling ceiling systems Comfortable indoor ventilation Clean air solutions
More informationRaised Access Floor - (AE Breadth Area)
Raised Access Floor - (AE Breadth Area) Currently, the Plaza has a raised access flooring system on both the 7 th and 8 th floors. The 8 th floor is designed with an independent HVAC system utilizing an
More informationEngineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.
VAV Diffusers lease refer to the rice Engineer s HVAC Handbook for more information on VAV Diffusers. Diffuser Types Ceiling Diffusers Conventional air distribution systems typically group several rooms
More informationAIR HANDLER SPECIFICATION
AIR HANDLER SPECIFICATION Air Handlers AH-1 through 5 The following air handlers will be supplied: AH-1 FX15-4842 Series 5700 CFM AH-2 FX15-4236 Series 3990 CFM AH-3 FX15-3633 Series 2570 CFM AH-4 FX15-3330
More informationGuide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:
Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT
More informationMechanical System Redesign. Dedicated Outdoor Air System. Design Criteria
Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed
More information7. MECHANICAL SYSTEM DESIGN
7. MECHANICAL SYSTEM DESIGN The second primary topic of this thesis is to investigate the application of a dedicated outdoor air system (DOAS) to the SLCC. The stated goals for this thesis of improved
More informationRosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS
10 Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS 2 INDEX Page Description - Introduction -Application - Data... 2 Typical Installation... 3 Sound performance... 3-6 Dimensional
More informationRadiant Lay-In Formed Metal Panels
Energy Efficient Comfortable Clean Quiet 395 West 1100 North North Salt Lake, Utah 84054 TEL (801) 292-0493 FAX (801) 292-9908 WATER PRESSURE DROP HEATING PERFORMANCE Head Loss in Head Loss in Feet of
More informationElegance and design for your residential comfort
Elegance and design for your residential comfort between elegance, comfort and energy savings Conceived to make every kind of residential environment more comfortable, the new i-life Slim fan coil integrates
More informationJim Aswegan Chief Engineer
Displacement Ventilation Jim Aswegan Chief Engineer Displacement Ventilation Systems Comfort & Contaminate Control DV Concepts & System Benefits Outlet Types and Air Patterns Example l Space Layouts Displacement
More informationIf a peak space temperature to about 28ºC is acceptable to the occupants then a naturally ventilated solution is a viable option.
Air handling units Aesthetic Not to add significantly to the existing ambient noise levels. Functional requirements If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally
More informationLine Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas
HVAC Guideline Specifications WHISPER-JET: SET SERIES Two Stage Positive Pressure Gas-Fired Infrared Radiant Tube Type Heater Commercial/Industrial Applications Technical Summary Input Range: 80,000/60,000
More informationC. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.
SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers
More informationCOMFORT APPLICATION HYDRONIC TERMINALS ELEGANCE AND DESIGN FOR YOUR RESIDENTIAL COMFORT
COMFORT APPLICATION HYDRONIC TERMINALS ELEGANCE AND DESIGN FOR YOUR RESIDENTIAL COMFORT climaveneta.com COMFORT APPLICATION HYDRONIC TERMINALS between elegance, comfort and energy savings Conceived to
More informationA TRUE GAME CHANGER - The Vortex Heat Recovery Center CONDENSING EFFICIENCIES FOR TRADITIONAL BOILERS & HEATERS
A TRUE GAME CHANGER - The Vortex Heat Recovery Center CONDENSING EFFICIENCIES FOR TRADITIONAL BOILERS & HEATERS Flexibility and Performance - Unlike any other Heat Recovery System FEATURES Exceptional
More informationInffusers. idl20 (2 WAY) ids60 (4 WAY)
Inffusers idl20 (2 WAY) ids60 (4 WAY) built on innovation what is an inffuser? DADANCO s INFFUSERS are quite simply an induction diffuser that uses special nozzles located in the underside of the air plenum
More informationiq Star LYRA II chilled beam cassette
iq Star LYRA II chilled beam cassette Key features Ventilation Heating and cooling Compact chilled beam Adjustable induction Flow Pattern Control Integrated control In option: Demand Controlled Ventilation,
More informationExperimental Verification of Cooling Load Calculations for Spaces with Non-Uniform Temperature Radiant Surfaces
Experimental Verification of Cooling Load Calculations for Spaces with Non-Uniform Temperature Radiant Surfaces ASHRAE 1729-TRP Project Prepared by Dr. Atila Novoselac Principle Investigator Dr. Stephen
More informationBALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT
BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT Ashak Nathwani AM Adjunct Senior Lecturer ashak.nathwani@sydney.edu.au PRESENTATION THREE SESSIONS This presentation will be in three parts addressing
More informationC o o l i n g a n d h e a t i n g s y s t e m s
2 C o o l i n g a n d h e a t i n g s y s t e m s Cooling ceiling system description Preliminary remarks Cooling ceilings Cooling ceilings are room cooling systems for placement in the ceiling zone. Their
More informationGAS-FIRED HIGH AND LOW INTENSITY INFRARED HEATERS
GAS-FIRED HIGH AND LOW INTENSITY INFRARED HEATERS MODEL IHR MODEL OHP MODEL IPT 9-123.2 SEPTEMBER, 2016 9-123.2 FEATURES AND BENEFITS - MODEL IHR Figure 4.1 - Construction Features - Model IHR Features
More informationiq Star LYRA II chilled beam cassette
Key features The LYRA II cassette is an active chilled beam for ventilation, cooling and heating. This diffusion system offers high flexibility thanks to the combination of Flow Pattern Control, Coanda
More information