1. Categorizing Appliances

Size: px
Start display at page:

Download "1. Categorizing Appliances"

Transcription

1 Fireplace Inspections Made Easier 1901 N. Moore St. Arlington, VA (703) Inspection 1. Categorizing Appliances 1

2 Masonry Fireplace Factory Built Fireplace 2

3 Gas Log Sets Fireplace Inserts 3

4 Free Standing Stoves Hearth Stoves 4

5 Masonry Furnaces Outdoor Categorizing By Venting Type Gas Venting Systems Conventional Vent Direct Vent Unvented 5

6 Categorizing By Venting Type Gas Conventional Vent B-Vent Chimneys Masonry or Factory-Built Liners Categorizing By Venting Type Gas Direct Vent Coaxial Co-linear PVC Hi-efficiency condensing 6

7 Categorizing By Venting Type Woodburning Venting Systems Masonry Chimneys Factory-Built Chimneys Liners HT Categorizing By Venting Type Pellet Venting Systems Type L Pellet Pellet DV Liners 7

8 Vented Gas Fireplace ANSI Z21.50, CSA 2.33 Appliances: (Not tested for efficiency) Fireplaces Fireplace inserts Freestanding stoves Requirements Safety pilot Spill switch if equipped with draft hood Restrictions No thermostat Options Listed blowers Vented Gas Fireplace Heater ANSI Z21.88, CSA 2.33 Appliances: (Tested for efficiency) Fireplaces Fireplace inserts Freestanding stoves Requirements Safety pilot Spill switch if equipped with draft hood Restrictions None Options Listed blowers Thermostats 8

9 Decorative Gas Accessory in Solid Fuel Fireplaces ANSI Z21.60, CSA 2.26 Appliances: Log Sets Requirements Safety pilot Working fireplace and chimney Permanent damper opening Fireplace screen Cleaning of venting system Restrictions No thermostat Options Listed blowers Manually Lighted, Natural Gas Appliances for Installation in Solid-fuel Burning Fireplaces ANSI Z21.84 Appliances: Log Sets Requirements Working fireplace and chimney Permanent damper opening Fireplace screen Cleaning of venting system Restrictions No thermostat 9

10 Unvented Gas Room Heater Appliances: ANSI Z a Fireplaces Fireplace inserts Freestanding stoves Requirements Safety pilot w/ods Restrictions Bedroom, Bathroom, Confined space Tight construction Maximum 40,000 Btu/hr input Options Listed blowers Thermostats Outdoor Decorative Gas Appliance ANSI Z21.97 Appliances: Fireplaces Fire Pits Fire Tables Requirements Minimum construction, performance, testing Restrictions Outdoor Use only Options Propane cylinder enclosures 10

11 Outdoor Gas Hearth Appliances: Building Codes IFGC : Listed for outdoor installation or provided with protection for environmental factors affecting operability, durability, and safety IFGC 2012: Tested to ANSI Z21.97 Outdoor Decorative Appliances Outdoor Gas Hearth Appliances: Building Codes Rain Test/Post Rain Test Electrical Test Glass Front Test Wind Test Propane Cylinder Enclosure Requirements 11

12 Solid Fuel Standards Underwriter s Laboratories (UL) Materials and construction Fire and strength tests Review of installation instructions UL 127 Factory Built Fireplaces Testing requirements for entire system Fire chamber Chimney Roof assembly Related components 12

13 UL 127 Factory Built Fireplaces Standard factory-built chimney test Sustained temperature of 1000 F Ten minute test at 1700 F Optional Type HT test Sustained temperature of 1000 F 3 - ten minute tests at 2100 F Not required for factory-built fireplaces UL 737 Fireplace Stove Open or Closed fire chamber Freestanding stoves Few appliances listed to this standard 13

14 UL 1482 Solid Fuel Room Heater Closed fire chamber Freestanding stoves Fireplace Inserts Some built-in high efficiency fireplaces Controlled combustion Regulated air intake High efficiency Extended burns Masonry Chimneys No specific standard Site-Built Materials subject to standards flue liners and mortar, etc. Construction standards in codes NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel- Burning Appliances International Residential Code 14

15 UL 103 Factory-Built Chimneys Tested to 1700 Optional Type HT High Temperature 2100 testing required not required for UL 127 fireplaces UL 1777 Chimney Liners Metallic Poured Tested to 2100 F 15

16 Combustibles Combustible: Walls with wood framing Paper-faced materials Papered sheetrock (dry wall) including fire-rated papered sheetrock Plaster on wood lath or studs Noncombustible Entirely metal Brick Tile Concrete Slate Combustibles Plaster on metal lath 16

17 Clearances Side Clearance Back Clearance Bottom Clearance Also mantle, surround, ceiling and adjacent walls Clearances Header Size Orientation Flat or on edge 17

18 Clearances Wall Protection Reducing listed clearances Approved site-built systems Listed manufactured systems Clearance reduction systems can NOT reduce clearance to less than 12" Clearances less than 12" can only be listed clearance, specific by manufacturer. Clearances Wall Protection Protection Wall Ceiling 3½" masonry wall / NO ventilation ½" noncombustible board over 1" insulation, NO ventilation Min. 24 gage sheet metal / spaced out 1" 3½" masonry wall / spaced out 1" 33% 50% 66% 66% 33% 50% ½" noncombustible wall board spaced out 1" Listed prefabricated systems 66% 50% Manufacturer instructions 18

19 House Pressure Conditions Sources that exhaust air: Kitchen range fans Clothes dryers Central vacuum Gas furnace Water heaters Recessed lighting Additional hearth appliances, -especially open fireplace Outside air Open fireplaces require cfm EPA woodstoves require cfm 4 outside air brings in about 10 cfm of air Photo compliments of CSIA House Pressure Conditions House Stack Effect Heated portion of house taller than vent termination Open window in upper portion create greater chimney effect than vent 38 19

20 Combustion Air Combustion air: (Primary Air) Dilution air: Excess air: (Secondary Air) Air provided for combustion that mixes with the gas. Air introduced into draft hood and mixed with flue gases. Moderates draft and reduces vent temperatures Air that that does not combine with fuel in the combustion process Combustion Air Air changes per hour (ACH): Percent of volume exchanged (outdoor air replacing indoor air). Example: 0.35 ACH = 35% of volume of indoor air is replaced by outdoor air every hour. Unusually tight construction: Continuous water vapor retarder Storm windows Weather-stripping Caulking/sealing of gaps 20

21 Combustion Air Confined space: Space with volume less than 50 cubic feet per 1000 Btu/hr Unconfined space: Space with volume 50 cubic feet or more per 1000 Btu/hr. Rooms communicating through openings without doors are part of unconfined space. KAIR Method: Fuel Gas Codes Combustion Air Known Air Infiltration Rate Air Exchange rate is known Must be used if.40 or less May be used if between.40 &.60 Standard Method: Air exchange rate is not known. 21

22 Fuel Gas Codes KAIR Method 60,000 Btu/hr natural draft gas fireplace in room 15' x 25' with 9' ceiling in house with 0.40 ACH Formula: 21 divided by.40 = 52.5 [60,000 divided by 1,000 = 60] 60 x 52.5 = 3,150 cubic feet Available volume in room: 15 x 25 x 9 = 3,375 Indoor air OK because volume is more than required 3,150 cubic feet Fuel Gas Codes Standard Method Minimum volume necessary: 39,000 BTU appliance cu. Ft for every 1,000 BTU s 39,000 BTU s / 1,000 = * 50 = 1950 cu. Ft 2. Divide input rating Btu/hr by 20 1,000 / 50 = 20 39,000 BTU appliance / 20 = 1950 cu. Ft Room volume 1,950 or greater is OK Room volume less than 1,950 is not OK (I.E. Room size 21x12x8=2016 cubic feet = OK) 22

23 Fuel Gas Codes Standard Method Maximum Btu/hr rating Room15x18x8 = 2,160 cu. Ft cu. Ft for every 1,000 BTU s 2,160 cu. Ft. / 50 = 43.2 (43,200 BTU s) 2. Multiply the volume by 20 2,160 cu. Ft. * 20 = 43,200 BTU s Space OK for appliance with 43,200 Btu/hr or less Space not OK for appliance with more than 43,200 Btu/hr Fuel Gas Codes Combustion Air Bedroom/Bathroom -Unvented Confined space Not allowed Unconfined space 1 wall-mounted heater No more than 6,000 Btu/hr in bathroom No more than 10,000 Btu/hr in bedroom 2002-> Gas logs allowed with means to mount burner base to floor of solid-fuel fireplace 23

24 Fuel Gas Codes Combustion Air: Summary Indoor Adjoining room 2 Openings Indoor Different story Outdoor Direct or Vertical 2 Ducts Outdoor Horizontal Ducts 2 Openings Outdoor One Duct or Direct Opening 1 in² per 1,000 BTU s 2 in² per 1,000 BTU s 1 in² per 4,000 BTU s 1 in² per 2,000 BTU s 1 in² per 3,000 BTU s 12 of ceiling 12 of floor At least 100 in² At least 100 in² May be from ventilated attic or ventilated crawl space 12 of ceiling 12 of floor 12 of ceiling 12 of floor Not less than the sum of the areas of all vent connectors Fuel Gas Codes Combustion Air Source of Air Including adjacent spaces that cannot be closed off May now use a combination of openings to indoor spaces outdoors 24

25 Combustion Air Opening Size Calculation 60,000 Btu/hr gas fireplace 12 x 15 x 8 room 1. Determine total room volume: 12 x 15 x 8 = 1,440 cu. ft. 2. Determine required volume by standard method: 60,000/20 = 3,000 cu. ft required /3000=48% The room is able to provide 48% of the necessary air. We need to bring 52% in from outside. 4. Determine overall opening size:(1 sq. in/3,000 BTU s) 60,000/3,000 = 20 sq. In. (1 duct direct to outdoors) 5. Determine minimum outdoor air opening: 20 x 52% = 10.4 sq. In. Combustion Air Louvers and Grilles Size based on net free area Calculation Wood: 25% free area Metal: 75% free area Screens: mesh size must not be smaller than 1/2" Wood 6"x10" = 60 x.25 = 15 sq. in. Metal 10"x6" = 60 x.75 = 45 sq. in. 25

26 Combustion Air Direct Vent Combustion air requirements do NOT apply Combustion Air from Outside Combustion Products Vented to Outside Combustion Air Passive: Non-mechanical (no fan) Infiltration Gaps in building envelope Outside air kit May be required May not be reliable source due to influence of pressure conditions inside and outside house Flow reversal of air and combustion products possible in certain situations 26

27 Combustion Air Decorative Fireplaces (UL 127 or UL 737) NFPA 211 Outside air where required by AHJ Listed component installed to instructions Not from Attic Basement Garage Another interior space Combustion Air Decorative Fireplaces (UL 127 or UL 737) IRC Exterior air supply unless room mechanically ventilated/controlled to neutral or positive pressure OK from ventilated attic or crawl space Not From Garage Basement Elevation higher than firebox 27

28 Combustion Air Woodstoves UL1482 NFPA 211: Outside air is required: When building is so tight that normal air infiltration does not provide the necessary air. Woodstove UL 1482 Combustion Air IRC : Different requirements depending on tightness of construction and volume of space Unusually Tight Construction Not Unusually Tight Construction IRC 2009: in accordance with the appliance manufacturer s instructions. 28

29 Combustion Air Powered Make-up Air System Fan and ductwork to make up difference between available and needed Specifications determined by house pressure test Depressurization level from exhaust devices Hearth appliance tolerance Avoid bringing in more unheated air than needed Floor Protection Protection against heat and sparks IRC: listed to comply with UL 1618 Follow manufacturer s instructions If instructions unavailable, NFPA 211 Opening less than 6 square feet: extend 8" to each side and 16" to front of opening Opening 6 square feet or greater, extend 12" to sides and 20" in front Local codes may require more protection 29

30 Floor Protection Flame retardant rugs do NOT provide spark/ember nor thermal protection required UL 1618 listed floor protectors Confusion about listings Protectors may provide spark/ember protection, but NOT adequate thermal protection Floor Protection UL 1618 Type 1 Contiguous noncombustible surface Provide Ember Protection No thermal protection Must state on label Not for stoves that require thermal protection. 30

31 Floor Protection UL 1618 Type 2 Contiguous noncombustible surface Minimum R-value of R=1.0 Must have R-value listed on floor protector Floor protection must have R-value greater than or equal to the stove s required R-value. Mobile Home Requirements HUD Requirements Outside air attached directly to appliance Mechanically attached to floor No installation in sleeping room Listed chimney with spark arrestor UL 127 and 1482 Maintain structural integrity of home Manufacturers Instructions Some require electrical grounding to chassis 62 31

32 NFPA 211 Inspections Level Circumstance Level of Access Scope 1 Replacement with similar type, input, efficiency Readily Accessible Obstructions Deposits 2 Add/replace dissimilar Sale of property Malfunction Accessible Construction/ condition Clearances/ suitability 3 Hazard suspected Need access to concealed areas Can include removal of bldg. /chimney components Includes access to concealed areas EPA Regulations New Source Performance Standard Emissions limits Catalytic 4.1 grams/hour Non-catalytic 7.5 grams per hour Differences based on original expectations of catalyst decline 32

33 EPA Regulations New Source Performance Standard EPA/HPBA efforts focus Replace pre-epa stoves through changeouts Encourage installation and planning by qualified professionals NFI certification required for stove many changeouts Educate owners about proper fuel and operation EPA Regulations New Source Performance Standard Review and negotiation process New regulations released Feb. 2015! Compliance dates follow Changes for woodstoves Reduction in emission limits Eliminating exemptions Revising test methods Streamlining certification process 33

34 Green Building Codes International Energy Conservation Code IECC 2009 & IRC 2009 New wood-burning fireplaces shall have gasketed doors and outdoor combustion air. IECC 2012 & IRC 2012 New wood-burning fireplaces shall have tight-fitting flue damper and outdoor combustion air. Section & IRC N Fireplaces shall have gasketed doors. Appliance Standards AFUE Tested Thermostat Fireplace, Insert, Stove Z21.60 Gas Log Sets NO NO NO Z21.50 Gas Fireplaces Z21.88 Gas Fireplace Heaters NO YES NO NO YES YES YES YES YES Z Unvented Room Heater Vent switch: draft hood units ODS equipped NO YES YES NO * NO NO YES 34

35 Equipment Shutoff Valve Isolates appliance Servicing, removal, or replacement Required upstream of appliance connector Within 6 feet with exceptions for some hearth appliances Shutoff Valve Exceptions Readily accessible Permanently identified Serves no other equipment Readily accessible Having direct access without the need of removing or moving any panel, door, or similar cover Accessible Having access to but which first requires the removal of a panel, door, or similar covering 35

36 Shutoff Valve Exceptions National Fuel Gas Code Appliances installed in vented fireplaces and unvented firebox enclosures Gas log sets Fireplace inserts Unvented hearth appliances 2. Shutoff valve installed at a manifold within 50 of the appliance Vented fireplaces or free standing hearth appliances require a shutoff within 6 of the appliance Shutoff Valve Exceptions International Fuel Gas Code 2009: Vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces Vented gas hearth appliances Fireplaces Fireplace inserts Freestanding hearth appliances Vented gas log sets Unvented gas hearth appliances require shutoff within 6 of the appliance 36

37 Sediment Traps Installed close to appliance Intercept solid debris to prevent blockage Required by some appliance manufacturers Prevent rusting and degradation of main burner Appliance Connections International Fuel Gas Code Rigid or CSST (2006) = No length limit Semi-rigid =Maximum 6 Copper/aluminum tubing ANSI Z21.24 Listed Connectors In the same room as the appliance Length limited to 3 Extended to 6 in 2009 Protected from physical damage 37

38 Appliance Connections Additional IFGC requirements: Connectors to vented decorative appliances and room heaters can extend through walls, floors, partitions, ceilings Semi rigid tubing and listed connectors can extend through protected appliance openings Vented Gas Fireplace Installation Listed to ANSI Z21.50 Gas Fireplaces ANSI Z21.88 Gas Fireplace Heaters Floor Support and Protection: Most can be installed on combustible surface Carpet & vinyl usually not approved without metal or wood panel Appliance level and plumb, with adequate support Hearth extension may/may not be required 38

39 Gas Appliance Venting Systems Negative Pressure Category 1 (Natural draft hearth appliances) No condensate Category 2 Capable of condensate Positive Pressure Category 3 No condensate Category 4 (Mechanical draft hi-efficiency hearth appliances) Capable of condensate Conventional Vent Systems Draft Hood Allows dilution air into venting system Provides escape of flue gases in event of no draft, back draft, blockage Reduces temperatures in vent Reduces vent height affect Stronger draft brings in more dilution, not combustion air 39

40 Conventional Vent Systems Type B Vent Factory-made, double wall metal pipe Air space between walls Close clearance Help maintain draft and reduce condensation Conventional Vent Systems Type B Vent Components not interchangeable unless allowed by manufacturer Hearth products use Round B vent Oval B 2x4 Oval B 2x6 NOT Type BW unless otherwise listed 80 40

41 Conventional Vent Systems Type B Vent Horizontal Run and Rise Minimum vertical height may be specified Keep horizontal run to minimum Rise at least ¼ inch per foot for vent or connector Maximum rise to run ratio 75% of vent height for single wall connector 100% for double wall B vent connector Manufacturer may require 50% maximum (2:1) Conventional Vent Systems Type B Vent Termination with obstructions within 8 2 higher than any portion of the building within 8 41

42 Conventional Vent Systems Type B Vent Common Venting Appliances on different floors of building Only allowed for appliances in areas separate from living space Appliances on same floor Not addressed or prohibited Appliance manufacturer may prohibit AHJ may prohibit Conventional Vent Systems Type B Vent Chimney Liners Required for gas fireplace inserts and freestanding appliances using masonry or factory-built chimneys Listed liner systems Type B vent listed to UL 1777 Aluminum or stainless steel UL 1777 Rigid or flex 42

43 Conventional Vent Fireplace Insert Fireplace and chimney in good working order Some require hearth extension protection Alterations: variations by manufacturer Required removal of damper and grate Refractory, smoke shelf, baffles, screen, doors can be removed Insulation can NOT be removed Conventional Vent Fireplace Insert Surround variations Gap between fireplace face and panel may be required for air circulation and cooling Insulation along top of insert may be required for mantel clearances May allow installation without panel if minimum gap with mesh maintained Air inlet grilles on factory-built fireplaces important consideration 43

44 Conventional Vent Condensing Appliance Plastic Pipe (PVC) Recognized in Fuel Gas Codes Appliances must be listed for use High efficiency, Category IV Resists corrosion from condensation Provides adequate heat protection Can be sealed for mechanical vent positive pressure Direct Vent Follow manufacturer instructions Venting Clearances Vent system is part of appliance Appliance manufacturer provides instructions Permissible configurations are model specific 44

45 Direct Vent Fireplace Inserts Air intake terminated above damper inside chimney Listing and instructions Must be in instructions May require blocking of damper area Direct Vent Condensing Appliance Direct Vent PVC Systems Provides outside combustion air Co-linear Two separate PVC pipes Co-axial Inner pipe expelling exhaust Space between pipes providing combustion air 90 45

46 Mechanical Vent Systems Negative pressure (B-Vent or Direct Vent) Fan at flue collar or termination of vent Positive pressure (Direct Vent only) Fan before the firebox Central Fireplace Empire Comfort Systems Unvented ODS Pilot: Oxygen Depletion Shutdown Normal Operation 20.9% Oxygen Oxygen Level Dropping 19% Oxygen Safety System 18% Oxygen Pilot flame engulfs tip of thermocouple Flame begins to lift off Thermocouple begins to cool Unstable flame moves away from thermocouple Thermocouple stops generating sufficient mv to keep valve open Flow of gas stops 46

47 Unvented NFGC & IFGC Combustion air requirements Use of room restrictions IFGC Maximum input rating of 40,000 Btu/hr Not to be sole source of heating in house Garages Woodburning UL 1482 Prohibitions Areas where flammable liquid vapors may be present Enclosed spaces less than 512 cubic feet 8 x8 x8 unless listed for alcoves 47

48 Avoid elbows Woodburning Connector Pipe Use 15 0 elbows instead of 30 0 Avoid horizontal runs Minimum ¼ /foot rise for horizontal runs Woodburning Connector Pipe Materials NFPA 211 prohibits use of galvanized steel NFPA 211 requires 24 gauge or more Size and length At least appliance flue collar size Long runs can affect draft adversely and increase creosote buildup 48

49 Woodburning Connector Pipe Replacing an existing woodstove? Heat expectations Flue size Flue configuration Start up techniques Woodburning Venting Never use an unlined chimney. Two solid fuel appliances cannot share a common flue. Maximum size 3x larger than the appliance flue. 2 x if chimney is on an outside wall or in Canada. 49

50 Woodburning Masonry Chimneys Condition of flue liner Cracks, soft, mortar joints in place and tight Free of creosote Connection of other products Cannot share flue with solid fuel product Can be in same chimney on separate flue NFPA 211 requires a cleanout Woodburning Venting Height 3 feet above the highest point penetration AND at least 2 feet above anything within 10 horizontal feet 50

51 Woodburning Factory-Built Chimney Double wall or triple wall Air insulated, solid insulation, combination UL 103 HT required for woodstoves Single wall chimney connector not a chimney and should not penetrate combustibles Woodburning Firestop Spacers Blocking to prevent fire spread Correct spacing to meet clearances Provides lateral (side to side) support 51

52 Woodburning Firestop Spacers With room above: installed below joist Unoccupied attic above: installed above joist 103 Woodburning Fireplace Insert Fireplace and chimney in good working order Some require hearth extension protection Alterations: variations by manufacturer Required removal of damper and grate Refractory, smoke shelf, baffles, screen, doors can be removed Insulation can NOT be removed 52

53 Woodburning Fireplace Insert Surround Installations Gap between fireplace face and panel may be required for air circulation and cooling Insulation along top of insert may be required for mantel clearances May allow installation without panel if minimum gap with mesh maintained Air inlet grilles on factory-built fireplaces important consideration Woodburning Fireplace Insert Factory-Built Fireplaces Most fireplace manufacturer s only allow inserts specifically listed for use with specific model NFPA 211 requires Type HT chimney and insert listed for use with specific fireplace Warranty may be voided if insert not approved 12 53

54 Woodburning Fireplace Insert Direct Connect Stainless connector to first flue liner Minimum NFPA 211 requirement for installation of insert in masonry fireplace No dilution air Re-line to top Easier startup Better performance Woodburning Fireplace Insert Less frequent, expensive, difficult maintenance 54

55 Perfect Installation Balanced ventilation system in the home Outside air to firebox: Open fireplaces require cfm EPA woodstoves require cfm 4 outside air brings in about 10 cfm Photo compliments of CSIA Perfect Installation Chimney is inside the building envelope Keep flue gases warm for optimum draft Prevent cold hearth syndrome in standby and startup 55

56 Perfect Installation Chimney is insulated to prevent heat loss Perfect Installation No smaller than flue collar area Maximum Size Chimney is correct size No larger than 3 times flue collar area if inside the building envelope. (2x in Canada) No larger than 2 times flue collar area if one or more walls are exposed to the outside. Same as flue collar area best 56

57 Perfect Installation Penetrates the highest part of the house House Stack Effect Leaks, open windows in upper portion create greater chimney effect than vent Perfect Installation Chimney is tall enough 3 feet above the highest point of roof penetration 2 feet above anything within 10 horizontal feet 57

58 Perfect Installation Chimney is tall enough EPA woodstoves may need minimum 15' total venting system (connector + chimney) High altitude Manufacturer may recommend heights to be increased 2-3% per 1000 feet of elevation Extremely tall chimney can cause over drafting Damage to combustor and/or internal parts Shorter appliance life Perfect Installation Chimney is clear of obstacles 58

59 Perfect Installation Connector pipe runs straight up Avoid elbows Use 15º instead of 30º Avoid horizontal runs Minimum ¼ /foot rise Perfect Installation Home owner is informed Normal operation How to light a fire! Maintenance Ash removal Chimney Maintenance Catalytic Combustor care Break-in fires 59

60 Perfect Installation Home owner is informed Burn Wise video The Heating with Wood DVD Set Characteristics of a Perfect Installation 1. The house has a balanced ventilation system. 2. Chimney runs inside the building envelope. 3. Chimney is insulated and the correct size. 4. Chimney penetrates the highest part of the house. 5. Chimney is tall enough and is clear of obstacles. 6. Connector pipe runs straight up. 7. Homeowner is informed regarding proper operation. 60

61 Pellet Appliance Types Negative Pressure Combustion fan downstream of firebox Exhaust products drawn through fan Unwanted gaps such as worn gaskets affect combustion Pellet Appliance Types Positive Pressure Combustion fan upstream of firebox Exhaust products pushed through venting system Fly ash in the room through leaks in venting system 61

62 Pellet Control Boards Analog control boards Turn motors on or off Change to pre-set voltage/speed Digital control boards Monitor & controls motors Monitor combustion air fan speed Regulate fuel feed accordingly Monitor & maintain room and stove temperature Pellet Venting Outer galvanized wall, air space, inner stainless steel wall Different grade stainless for corn UL 641Tested sustained 570 o F, flash test to 1700 o F Factory sealed for air tightness Not to be confused with B Vent 62

63 Pellet Venting Pellet Venting NFPA 211: minimum 1 foot above roof IRC: follow manufacturer instructions Manufacturers Some require 2 63

64 Pellet Venting Pellet Venting Manufacturer may specify Minimum Maximum Horizontal runs # of elbows EVL used for positive pressure venting systems May not be used for natural draft 64

65 Pellet Venting Equivalent Vent Length 3-90 o elbows 2 horizontal 6 vertical Total: 20 = Acceptable Pellet Venting Direct Vent Bring all combustion air from outdoors Reduces concerns about tight homes Can provide preheated combustion air Avoid long horizontal runs prevent overcooling exhaust Closer minimum clearance 65

66 Safety Codes Pellet Venting Direct Vent Both NFPA and IRC recognize manufacturers instructions NFPA also offers termination clearances based on Btu/hr ratings IRC offers these terminations for gas direct vent, not pellet Safety standards Do not specifically reference pellet direct vent Code authorities Some disagreement in interpretation of direct vent in the field Pellet Venting Direct Vent NFPA Requirements Minimum distance from terminal to opening into building Appliance input 10,000 Btu/hr or less: 6 Appliance input over 10,000 to 50,000 Btu/hr: 9 Appliance input over 50,000 Btu/hr: 12 Bottom of terminal at least 12 above grade 66

67 Inspection 6. Accessory Installation Issues Vented Gas Logs For functioning fireplaces Chimney in place and proper height Adequate natural draft or mechanical listed for use with gas appliance Not for correcting draft problems 67

68 Vented Gas Logs Credentials needed varies Must have safety shutoff system Except ANSI Z Manually Lighted log sets No thermostats Use supplied damper clamp May require removal or welded open Manufacturers instructions may require damper be fully open during operation Failure to maintain opening can cause sooting and possible CO poisoning Vented Gas Logs Check flue size and chimney height Mechanical draft system may be remedy Listed for use Full interlocking to manage fuel flow Not initiated until fan establishes adequate draft Shut off in event of loss of adequate draft Sizing and installation by qualified technician 68

69 Vented Gas Logs Fireplace screen In place, closed during operation Glass doors Open during operation Log placement Important for combustion efficiency Incorrect placement Cooling of flame (impingement), soot, possible CO Media placement: Give appearance of embers and ash Usually fine sand for NG, vermiculite for NG or LP Positioned according to instructions Vented Gas Logs Chimney above roofline Firescreen on fireplace Glass doors on fireplace Damper Permanent chimney opening Specific log placement Required X X X X Not Required X X

70 Unvented Gas Logs Only in functional woodburning fireplace Logs listed for use in factory-built fireplace Fireplace listed for use with unvented log Chimney must be in place Must have adequate combustion air Fireplace screen with openings for air Unvented Gas Logs Glass doors can be present but open when log set used Outside air ducts/ash dumps permanently closed and sealed Damper closed, but not sealed Flue and firebox cleaned May be prohibited in bedroom or bathroom Approved for use by AHJ

71 Unvented Log Set: Enclosure Listed to ANSI Z21.91 Ventless Firebox Enclosures for Gas- Fired Unvented Decorative Room Heaters Decorative Shroud Cowl that covers chase Site made or manufactured Replaces listed cap Must be listed product Otherwise prohibited by NFPA 211, IRC, Can change cooling characteristics Possible ignition of combustibles at top of chimney or elsewhere

72 Special Components Wall Thimble Facing Requirements 72

73 Facing Requirements Instructions vary widely Metal face (surround) Clearances from combustibles Obstruction of air grilles Joint between fireplace and wall May/may not be required to be sealed Access door or air grille Should not be blocked Mantel Clearances 73

74 Surround Clearances Blowers Blowers and Grates Only listed for use with fireplace Follow instructions for blower and wiring No connection to cold air furnace returns Grates Some manufacturers prohibit use of grates Replacement only with manufacturer specified grate If no specifications, 2/3 hearth area or less No alterations or raising/lowering of grates 74

75 Catalytic Combustor Available for some fireplaces Original equipment or retrofit for some factory-built appliances Retrofit for masonry fireplaces May carry EPA hang tag Catalyst must be replaced every 3-5 years for proper performance 12 Glass Doors Doors standard on some fireplaces, optional on others, not allowed on some Required for fireplaces listed for installation in mobile homes ONLY doors listed and specified by the manufacturer for use with factory-built fireplaces Unauthorized doors can lead to damage and fire hazards Air grilles should not be covered 75

76 Glass Fronts & CPSC Consumer Message Fireplace glass fronts can be extremely hot when in operation or when cooling down when flame is not present. Certified barriers (screens) are recommended if there are children or other at-risk people in the home. New fireplace units will come with certified barriers (screens) which should remain in place. There are aftermarket products available for existing units. Keep fireplace remotes and switches out of reach of children. Follow the manufacturer s instruction for the safe use and maintenance of the fireplace. Glass Fronts & CPSC 76

77 Installer Qualifications NFGC calls for qualified agency Manufacturers instructions Qualified technicians Some suggest or recommend industry certification Jurisdictions Some have no requirements Some have qualifications based on broad categories of heating equipment Growing number considering specialty licenses specifically for gas hearth products installers Installer Qualifications National Fireplace Institute (NFI) Focused solely on hearth products Certification exams meet national standards for reliability, validity, legal defensibility 77

78 Maintenance Qualifications Chimney Safety Institute of America (CSIA) Inspection and cleaning or repair of chimneys and vents Certification exams 78

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

CHIMNEYS AND VENTS CHAPTER 8

CHIMNEYS AND VENTS CHAPTER 8 CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

Inspection Checklist Mechanical Final

Inspection Checklist Mechanical Final Property Owner Name: Property Address: Property Parcel Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans, and

More information

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717) City of York Qdot Engineering 101 S. George St 116 E Gas Ave York, PA 17405 York, PA 17405 (717) 849-2329 (717) 744-8315 INSPECTION CHECKLIST Residential Mechanical 2009 Codes This checklist is intended

More information

Inspection Checklist Mechanical Rough in

Inspection Checklist Mechanical Rough in Property Owner Name: Property Address: Permit Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans are on site and

More information

4.3 Installing Appliances and Interior Vapor Distribution Systems Performance-Based Skills Assessment 2016

4.3 Installing Appliances and Interior Vapor Distribution Systems Performance-Based Skills Assessment 2016 4.3 Installing Appliances and Interior Vapor Distribution Systems Performance-Based Skills Assessment 2016 Section One Task 1 Task 2 Task 3 Task 4 Task 5 Section Two Task 1 Task 2 Task 3 Task 4 Task 5

More information

2012 INTERNATIONAL FUEL GAS CODE VENTS

2012 INTERNATIONAL FUEL GAS CODE VENTS 2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with

More information

2015 MECHANICAL CODE REQUIREMENTS

2015 MECHANICAL CODE REQUIREMENTS 2015 MECHANICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Mechanical requirements for residential buildings per

More information

St. Croix Greenfield Installation Manual

St. Croix Greenfield Installation Manual St. Croix Greenfield Installation Manual Table of Contents General Information... 1 Installation Check List... 2 Approved Installations... 3 Exhaust Venting... 4 Venting - Approved Materials... 4 Venting-Typical

More information

CHIMNEY INSTALLATION. Technical Bulletin #1

CHIMNEY INSTALLATION. Technical Bulletin #1 Technical Bulletin #1 CHIMNEY INSTALLATION A chimney performs two functions: it removes smoke and flue gases from the stove/furnace, and it provides draft for the fire. Draft is the term used to describe

More information

C O D E S & A M M E N D M E N T S

C O D E S & A M M E N D M E N T S SEVIER COUNTY UTILITY DISTRICT SEPTEMBER 2, 2014 Sevier County Utility District has adopted the 2009 International Fuel Gas Code for gas inspections. The following pages contain frequently used codes and

More information

HVAC Equipment Access Equipment Location

HVAC Equipment Access Equipment Location City of Lancaster- Building Department 121 East Chestnut Street, Suite 102, Lancaster, Ohio 43130-3825 (740) 687-6649, Fax (740) 681-5030 Web site: www.ci.lancaster.oh.us/dept/building HVAC Heating, Ventilating,

More information

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL LO HI OFF Pilot UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL Remote-Ready and Variable Manually-Controlled Models Also Design-Certified As Vented Decorative Appliances

More information

Inspection Checklist Residential Mechanical Rough In July 2016

Inspection Checklist Residential Mechanical Rough In July 2016 Inspection Checklist Residential Mechanical Rough In July 2016 This Inspection Checklist reflects code requirements of the 2015 International Residential Code (IRC), the 2015 Uniform Plumbing Code (UPC),

More information

qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system.

qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system. 8. qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system. How Chimneys Work An effective chimney is an important part of any successful wood-burning system. Many of

More information

Mechanical Appliance and Equipment Inspection Checklist

Mechanical Appliance and Equipment Inspection Checklist 34 2015 IRC Performing Residential Mechanical s Mechanical Appliance and Equipment Checklist Inspect Mechanical Appliance and Equipment Comments / I. Identify possible mechanical appliance and equipment

More information

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL Remote-Ready Models VUL18/24/30/36(N,P)R Thermostatically-Controlled Models VUL18/24/30/36(N,P)T Remote-Ready Models Also Design-Certified

More information

UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER

UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL FLAME-MAX Vintage Oak Log Design FLAME-MAX Golden Oak Log Design FLAME-MAX Birch Log Design 18" and 24" Variable

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ELIMINATOR 36 Wood Burning Fireplace Models: 36E Non-Circulating (Smooth Face) I36E Non-Circulating (Smooth Face) Fully Insulated INSTALLATION INSTRUCTIONS SAVE THIS BOOK This book is valuable. In addition

More information

Comfort UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL

Comfort UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL Comfort by Flame TM FMI PRODUCTS, LLC UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL PFS US Remote-Ready Models CRB3624(N,P)RA Thermostatically-Controlled Models CSG3924(N,P)TB

More information

UNVENTED (VENT-FREE) GAS LOG HEATER

UNVENTED (VENT-FREE) GAS LOG HEATER LO UNVENTED (VENT-FREE) GAS LOG HEATER TM OWNER S OPERATION AND INSTALLATION MANUAL ("A" Models) 18", 24", and 30" Remote-Ready ( C Models) 18", 24", and 30" Variable Manually-Controlled PILOT OFF HI (

More information

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL LO PILOT OFF HI UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL ("R" Models) 18", 24", 30" and 36" Remote-Ready ( V Models) 18", 24", 30" and 36" Variable Manually- Controlled

More information

Venting of Gas Fired Equipment RV

Venting of Gas Fired Equipment RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

DESA INTERNATIONAL UNVENTED (VENT-FREE) PROPANE GAS LOG HEATER

DESA INTERNATIONAL UNVENTED (VENT-FREE) PROPANE GAS LOG HEATER DESA INTERNATIONAL UNVENTED (VENT-FREE) PROPANE GAS LOG HEATER Manually Control Models Also Designed Certified as Vented Decorative Appliance) This appliance may be installed in an aftermarket* manufactured

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 42" WOODBURNING FIREBOX Model C42EC2 Circulating (Louvered) INSTALLATION INSTRUCTIONS SAVE THIS BOOK This book is valuable. In addition to instructing you on how to install and maintain your appliance,

More information

UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER VARIABLE MANUALLY-CONTROLLED MODELS ALSO DESIGN-CERTIFIED AS VENTED DECORATIVE APPLIANCES

UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER VARIABLE MANUALLY-CONTROLLED MODELS ALSO DESIGN-CERTIFIED AS VENTED DECORATIVE APPLIANCES LO HI OFF Pilot UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER VARIABLE MANUALLY-CONTROLLED MODELS ALSO DESIGN-CERTIFIED AS VENTED DECORATIVE APPLIANCES OWNER S OPERATION AND INSTALLATION MANUAL FLAME-MAX

More information

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO Combustion Safety RESNET Conference San Antonio, TX February 27, 2006 Presented by Rich Moore Lightly Treading Energy & Design Denver, CO Goals of this session Recognize the need for combustion safety

More information

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06 page 1 of 6 VENTING CLEARANCES The vents should not be obstructed and all joints properly fitted. Floors, ceilings and walls must be cut or framed to provide necessary clearance to vents. Metal strippings

More information

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL PFS US REMOTE CONTROL READY BURNER SYSTEM MODELS EWPO2430NV AND EWPO2430PV FOR USE WITH EWPO18R, EWPO24R, AND EWPO30R LOG SETS

More information

Woodburning Zero clearance

Woodburning Zero clearance Woodburning Zero clearance Z 42 CD (cast doors) w/black grills Windom w/oval pattern doors & black grills Z 42 Series Z 42 Specifications...2 #231 ZC & #241 ZC Series #231 ZC & #241 ZC Specifications...5

More information

State of ALASKA, Weatherization Assistance Program. Technical Support Document. Combustion Safety

State of ALASKA, Weatherization Assistance Program. Technical Support Document. Combustion Safety 5.3.1A(2) Page 1 of 2 State of ALASKA, Weatherization Assistance Program Technical Support Document Combustion Safety This document is intended to support in detail the Combustion Safety Test Report. The

More information

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL PFS US REMOTE-READY BURNER SYSTEM MODELS BG18NR, BG18PR, BG2436NR, BG2436PR, BGE18NR, BGE18PR, BGE2436NR AND BGE2436PR BG MODELS

More information

INSTALLATION INSTRUCTIONS SAVE THIS BOOK

INSTALLATION INSTRUCTIONS SAVE THIS BOOK 36 Open Corner Circulating (louvered) Wood Burning Fireplace Models: 36 LM Left Side Opening / 36RM Right Side Opening Includes: Manual Variable Control Fan System, Combustion Air Kit and Bi-Fold Doors

More information

ROYAL ENGLISH OAK AND WINCHESTER OAK UNVENTED (VENT-FREE) GAS LOG HEATER

ROYAL ENGLISH OAK AND WINCHESTER OAK UNVENTED (VENT-FREE) GAS LOG HEATER TM ROYAL ENGLISH OAK AND WINCHESTER OAK UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND MANUAL 18" and 24" Variable Manually- Controlled Models CGS2718P, CGS2718N CGS3124P, CGS3124N CLD3018PA,

More information

INSTALLATION OPERATION AND SERVICE MANUAL

INSTALLATION OPERATION AND SERVICE MANUAL INSTALLATION OPERATION AND SERVICE MANUAL THE OLD SALEM COLLECTION VENT FREE REGENCY COAL BASKET complies with ANSI Z21.11.2 THIS ONLINE MANUAL IS FOR PLANNING PUPOSES ONLY. CAREFULLY READ BEFORE PURCHASING.

More information

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE PFS APPROVED FOR NATURAL GAS OR PROPANE GAS Z21.50-2014 If your plans do not allow for the venting system as outlined previously in the installing chimney/vent

More information

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL PFS US REMOTE CONTROL READY BURNER SYSTEM MODELS VD1824NR AND VD1824PR FOR USE WITH LVD18-GO, LVD24-GO, LVD18-PP, LVD24-PP,

More information

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL PFS US VARIABLE MANUALLY CONTROLLED BURNER SYSTEM MODELS EWPO2430NM AND EWPO2430PM, FOR USE WITH EWPO18R, EWPO24R AND EWPO30R,

More information

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL Echo Valley Oak Log Design Meadowbrook Oak Log Design 24" Variable Manually- Controlled Models LSL3124N and LSL3124P 24" Variable

More information

MOUNTAIN OAK, PREMIUM AGED SPLIT OAK, AND SMOKY MOUNTAIN OAK UNVENTED (VENT-FREE) NATURAL GAS LOG HEATERS

MOUNTAIN OAK, PREMIUM AGED SPLIT OAK, AND SMOKY MOUNTAIN OAK UNVENTED (VENT-FREE) NATURAL GAS LOG HEATERS MOUNTAIN OAK, PREMIUM AGED SPLIT OAK, AND SMOKY MOUNTAIN OAK UNVENTED (VENT-FREE) NATURAL GAS LOG HEATERS VARIABLE MANUALLY-CONTROLLED MODELS ALSO DESIGN-CERTIFIED AS VENTED DECORATIVE APPLIANCES OWNER

More information

Installation and Operation Instructions

Installation and Operation Instructions Installation and Operation Instructions Superior Unvented (Vent-Free) Gas Log Heater P/N 126827-01 Rev. A 01/2014 Models BGE18NV BGE18PV BGE2436NV BGE2436PV P126827-01 INSTALLER: Leave this manual with

More information

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL. BGe18NM, BGe18PM, BGe2436NM and BGe2436PM

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL. BGe18NM, BGe18PM, BGe2436NM and BGe2436PM UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL PFS US Variable Manual BURNER SYSTEM MODELS BG18NM, BG18PM, BG2436NM, BG2436PM, BGe18NM, BGe18PM, BGe2436NM and BGe2436PM FOr

More information

Installation and Operation Instructions

Installation and Operation Instructions Installation and Operation Instructions Superior Unvented (Vent-Free) Gas Log Heater P/N 126842-01 Rev. A 01/2014 Models VS1824NM VS1824PM P126842-01 INSTALLER: Leave this manual with the appliance. CONSUMER:

More information

BDM Direct Vent systems are for use with direct vent gas fired appliances.

BDM Direct Vent systems are for use with direct vent gas fired appliances. INSTALLATION INSTRUCTIONS Pro-Form DIRECT VENT SYSTEM Tested to ANSI Z21.88-2009 /CSA 2.33-2009 REPORT # 369-P-02b-6.5 Read through all venting and appliance instructions before beginning your installation.

More information

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL Models EZ18N, EZ18P, EZ24N and EZ24P 18" and 24" Variable Manually-Controlled Design-Certified As Vented Decorative Appliances

More information

ASX7-5-IOM-3 J

ASX7-5-IOM-3 J INSTALLATION INSTRUCTIONS 5" CONCENTRIC VENT TERMINAL KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 90,000 to 120,000 BTU/HR

More information

UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER

UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER OWNER S OPERATION AND MANUAL 18", 24", and 30" Variable Manually-Controlled Models CGD3018P CCL3924P CGD3924P CRL2718P CGD3930P CRL3124P CCL3018P 18", 24",

More information

2012 International Fuel Gas Code Design, Installation and Inspection Principles

2012 International Fuel Gas Code Design, Installation and Inspection Principles Overview 2012 International Fuel Gas Code Design, Installation and Inspection Principles Based on the 2012 International Fuel Gas Code Administration Definitions General regulations Gas piping installations

More information

ROYAL ENGLISH OAK, BILTMORE SPLIT OAK, AND WINCHESTER OAK UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER

ROYAL ENGLISH OAK, BILTMORE SPLIT OAK, AND WINCHESTER OAK UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER ROYAL ENGLISH OAK, BILTMORE SPLIT OAK, AND WINCHESTER OAK UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER VARIABLE MANUALLY-CONTROLLED MODELS ALSO DESIGN-CERTIFIED AS VENTED DECORATIVE APPLIANCES OWNER S OPERATION

More information

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified Thank you for purchasing our fully-automatic gas-fired tankless water heater. Please completely read this Manual

More information

BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS

BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by

More information

UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER ALSO DESIGN-CERTIFIED AS A VENTED DECORATIVE APPLIANCE

UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER ALSO DESIGN-CERTIFIED AS A VENTED DECORATIVE APPLIANCE LO PILOT OFF HI UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER ALSO DESIGN-CERTIFIED AS A VENTED DECORATIVE APPLIANCE OWNER S OPERATION AND INSTALLATION MANUAL VFN18MV, VFN24MV VFN30MV Variable Manually-

More information

HYBRID-FYRE FLUSH WOOD INSERTS

HYBRID-FYRE FLUSH WOOD INSERTS HYBRID-FYRE FLUSH WOOD INSERTS CLEANEST BURNING WOOD INSERTS IN THE WORLD Large Flush Wood Hybrid-Fyre Insert The Avalon Large Flush Wood Hybrid-Fyre Insert is one of the cleanest and most efficient wood

More information

INSTALLATION AND SERVICE MANUAL

INSTALLATION AND SERVICE MANUAL INSTALLATION AND SERVICE MANUAL HORIZONTAL COMBUSTION AIR INLET KITS CATEGORY III VENTING FOR SEPARATED COMBUSTION TUBULAR GAS FIRED UNIT HEATERS USE 5 INCH KIT FOR UNITS WITH CAPACITIES 100,000 TO 250,000

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

Uniform Dwelling Code 2017 Updates SPS 323

Uniform Dwelling Code 2017 Updates SPS 323 Uniform Dwelling Code 2017 Updates SPS 323 Lenny Kanter UDC Engineering Consultant Department of Safety and Professional Services 608 261 6541 voice 608 267 9723 fax robert.kanter@wi.gov Plan Review and

More information

INSTALLATION AND SERVICE MANUAL

INSTALLATION AND SERVICE MANUAL INSTALLATION AND SERVICE MANUAL VERTICAL COMBUSTION AIR INLET KITS CATEGORY III VENTING FOR SEPARATED COMBUSTION TUBULAR GAS FIRED UNIT HEATERS USE 5 INCH KIT FOR UNITS WITH CAPACITIES 100,000 TO 250,000

More information

Pellet Stove. Flex Pipe. Appliance Connector

Pellet Stove. Flex Pipe. Appliance Connector Installation Instructions & Owners Maintenance Guide DT-M Direct-Temp for Multi Fuel L-Vent / Vent System for Pellet, Corn and other Bio-Fuel Burning Appliances Introduction Direct-Temp for Multi-Fuel

More information

Heat-N-Glo Fireplace. Installers Guide. Model: AT-GRAND

Heat-N-Glo Fireplace. Installers Guide. Model: AT-GRAND Heat-N-Glo Fireplace Model: AT-GRAND Installers Guide Patents Pending Underwriters Laboratories Listed WARNING: IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY

More information

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL PFS US 24" REMOTE CONTROL READY MODELS CF2436NR(-M) AND CF2436PR(-M) Also Design-Certified As Vented Decorative Appliances

More information

Do not use this vent pipe or fittings for venting incinerators of any kind.

Do not use this vent pipe or fittings for venting incinerators of any kind. ! CAUTION! Do not use this vent pipe or fittings for venting incinerators of any kind. C.S.A. Certified For Natural Gas Or Propane Tested For 100 LBS. ASME Working Pressure For correct installation of

More information

Biltmore TM Unvented (Vent-Free) Gas Log Heaters

Biltmore TM Unvented (Vent-Free) Gas Log Heaters REMOTE OFF HI ON PILOT Installation and Operation Instructions TM WELCOME HOME TO WARMTH Biltmore TM Unvented (Vent-Free) Gas Log Heaters P/N 900555-00 Rev. NC 12/2015 Models P900555-00 PFS US Report No.

More information

Can I install my stove using an existing masonry chimney?

Can I install my stove using an existing masonry chimney? FAQ: Wood Stoves Can I install a wood stove in my mobile home? Yes, you can install a wood stove in a mobile home. However, the stove you install must have been specifically approved for mobile home applications.

More information

UNVENTED (VENT-FREE) GAS FIREPLACE INSERT OWNER S OPERATION AND INSTALLATION MANUAL VI33NRB AND VI33PRB REMOTE READY GAS FIREPLACE INSERT

UNVENTED (VENT-FREE) GAS FIREPLACE INSERT OWNER S OPERATION AND INSTALLATION MANUAL VI33NRB AND VI33PRB REMOTE READY GAS FIREPLACE INSERT Vantage Hearth TM by FMI PRODUCTS, LLC UNVENTED (VENT-FREE) GAS FIREPLACE INSERT OWNER S OPERATION AND INSTALLATION MANUAL PFS US Shown with GB38 Surround Kit and Brick Liner Accessory VI33NRB AND VI33PRB

More information

Peninsula woodburning fireplace. Models (V)PN36-A

Peninsula woodburning fireplace. Models (V)PN36-A Peninsula woodburning fireplace OWNER S OPERATION AND INSTALLATION MANUAL ICC-ES #ESR-2542 Models (V)PN36-A SAVE THIS BOOK This book is valuable. In addition to instructing you on how to install and maintain

More information

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL LO HI PILOT OFF Patent Pending Variable Manually- Controlled Models HDVF3018P AND HDVF3018N Also Design-Certified As Vented

More information

HOME INSPECTOR EDUCATION EXPO 2016

HOME INSPECTOR EDUCATION EXPO 2016 An Education in Hot Water HOME INSPECTOR EDUCATION EXPO 2016 Residential Water Heater Inspection Course Objective Course Objective Completing this course should enable an inspector to identify components

More information

the perfect match Between Wood Fireplaces and Venting Products new

the perfect match Between Wood Fireplaces and Venting Products new the perfect match Between Wood Fireplaces and Venting Products new ZERO CLEARANCE FIREPLACES CLEAN COMBUSTION DECORATIVE FIREPLACES SUPERIOR QUALITY MANUFACTURING www.occanada.com ME150 FACEPLATE INCLUDED

More information

STORM COLLAR 3/4" AIR SPACE BACK AND SIDES 31 5 / / /16 LOUVERS ON MODEL 3601 ONLY AIR KIT K/O GAS LINE K/O OUTSIDE AIR (LEFT SIDE ONLY)

STORM COLLAR 3/4 AIR SPACE BACK AND SIDES 31 5 / / /16 LOUVERS ON MODEL 3601 ONLY AIR KIT K/O GAS LINE K/O OUTSIDE AIR (LEFT SIDE ONLY) INSTALLATION INSTRUCTIONS BARON WOODBURNING FIREBOX V3600 Non-Circulating V3601 Circulating SAVE THIS BOOK This book is valuable. In addition to instructing you on how to install and maintain your appliance,

More information

Boston OWNERS MANUAL. Model: 1200-C & 1700C Free Standing WARRANTY REGISTRATION

Boston OWNERS MANUAL. Model: 1200-C & 1700C Free Standing WARRANTY REGISTRATION WARRANTY REGISTRATION IS QUICK AND EASY ONLINE: enviro.com Boston Model: 1200-C & 1700C Free Standing OWNERS MANUAL SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED

More information

ASX7-4-IOM-6 J

ASX7-4-IOM-6 J INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT

More information

Woodburning. Z 42 Series. #231 ZC & #241 ZC Series. #231 ZC & #241 ZC Specifications...6 Woodburning Accessories...8. Z 42 Specifications...

Woodburning. Z 42 Series. #231 ZC & #241 ZC Series. #231 ZC & #241 ZC Specifications...6 Woodburning Accessories...8. Z 42 Specifications... CELEBRATING 35 YEARS OF BEING KOZY Z 42 w/prairie design screen doors & black grills Z 42 Series Z 42 Specifications...2 Windom w/oval pattern doors & black grills #231 ZC & #241 ZC Series #231 ZC & #241

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION SECTIONS 23.20.100 Local Amendments To The International Mechanical Code, 2000 Edition 23.20.202 Definitions 23.20.301.14

More information

PFS. Installation and Operation Instructions. Superior Unvented (Vent-Free) Gas Log Heater

PFS. Installation and Operation Instructions. Superior Unvented (Vent-Free) Gas Log Heater Installation and Operation Instructions Superior Unvented (Vent-Free) Gas Log Heater P/N 126857-01 Rev. A 02/2014 Models PFS US VF18NBTB VF18PBTB VF24NBTB VF24PBTB P126857-01 INSTALLER: Leave this manual

More information

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. O-TL REPORT # 258-L-04-5 UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL Models SBJ18VNA, SBJ18VPA SBJ24VNA and SBJ24VPA Models SMA18VNA, SMA18VPA SMA24VNA and SMA24VPA Vent-free

More information

Biltmore TM Unvented (Vent-Free) Gas Log Heaters

Biltmore TM Unvented (Vent-Free) Gas Log Heaters REMOTE HI Installation and Operation Instructions TM WELCOME HOME TO WARMTH Biltmore TM Unvented (Vent-Free) Gas Log Heaters P/N 900556-00 Rev. NC 12/2015 Models P900556-00 PFS US Report No. F09-126 Biltmore24LMN

More information

POWER VENTER. Model: PVE Series

POWER VENTER. Model: PVE Series POWER VENTER Model: PVE Series CONTENTS Typical Venting System Components... System Operation... Power Venter Sizing... Installation Safety Instructions... Installation of Power Venter... Connecting Power

More information

ROYAL ENGLISH OAK UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL

ROYAL ENGLISH OAK UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL ROYAL ENGLISH OAK UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL Patent Pending 24" Thermostatically-Controlled Models CLD3924PTC and CLD3924NTC WARNING: If the information

More information

VILLA VISTA. Traditional. Fireplace Design Collection EPA WOOD BURNING FIREPLACES

VILLA VISTA. Traditional. Fireplace Design Collection EPA WOOD BURNING FIREPLACES VILLA VISTA EPA WOOD BURNING FIREPLACES Traditional Fireplace Design Collection SHOW YOURSELF Create a room that begs you to stick around, sit down and relax. IN FEATURED Villa Vista with Del Sol Decorative

More information

Installation Instructions

Installation Instructions Installation Instructions Type B Gas Vent Model E/R 3" 8" ECCO TYPE B GAS VENT AND ACCESSORIES ARE FOR USE ONLY WITH LISTED CATEGORY 1 GAS-FIRED APPLIANCES OR APPLIANCES LISTED FOR USE WITH TYPE B GAS

More information

CAUTION - FOR YOUR SAFETY

CAUTION - FOR YOUR SAFETY WARNING: This appliance is equipped for (Natural and Propane) gas. Field conversion is not permitted other than between natural or propane gases. Vent-Free Gas Log Heater MODEL: PCD8T PCD24TD PCD24M Español

More information

OWNERS MANUAL LIBERATOR ROCKET HEATER Model: RMH-1

OWNERS MANUAL LIBERATOR ROCKET HEATER Model: RMH-1 OWNERS MANUAL LIBERATOR ROCKET HEATER Model: RMH-1 SAVE THIS MANUAL FOR FUTURE REFERENCE LIBERATOR STOVE, LLC ST. LOUIS, MO. (314)-770-1043 Thank you for your purchase of the Liberator Rocket Heater. This

More information

Vent Supplement Ultra-80, -105, -155, -230 & -310

Vent Supplement Ultra-80, -105, -155, -230 & -310 Gas-fired water boiler Vent Supplement Ultra-80, -105, -155, -230 & -310 Installation of: Vent piping Air piping with This document must only be used by a qualified heating installer/service technician.

More information

PFS. Installation and Operation Instructions Unvented (Vent-Free) Gas Fireplace Insert. Models VCI3032ZMN VCI3032ZMP

PFS. Installation and Operation Instructions Unvented (Vent-Free) Gas Fireplace Insert. Models VCI3032ZMN VCI3032ZMP Installation and Operation Instructions Unvented (Vent-Free) Gas Fireplace Insert P/N 127119-01 Rev B 12/2016 P127119 01 PFS US REPORT NO. F09-121 Models VCI3032ZMN VCI3032ZMP INSTALLER: Leave this manual

More information

Introduction Service Pipe Application Important Terms Air Requirements... Appliance Location... Venting... Calculations...

Introduction Service Pipe Application Important Terms Air Requirements... Appliance Location... Venting... Calculations... Construction Guide Table of Contents Page Introduction... 2 Service Pipe Application... 4 Important Terms... 5 Air Requirements... Appliance Location... Venting... Calculations... 37 Gas Distribution System...

More information

UNVENTED (VENT-FREE) GAS FIREPLACE INSERT OWNER S OPERATION AND INSTALLATION MANUAL For more information, visit

UNVENTED (VENT-FREE) GAS FIREPLACE INSERT OWNER S OPERATION AND INSTALLATION MANUAL For more information, visit UNVENTED (VENT-FREE) GAS FIREPLACE INSERT OWNER S OPERATION AND INSTALLATION MANUAL VI33NR VI33PR REMOTE READY GAS FIREPLACE INSERT Shown with GS38 Surround Kit and G8010 Brick Liner Accessories WARNING:

More information

SWB400I DELUXE RADIANT WOOD BURNING FIREPLACE INSTALLATION, OPERATION AND MAINTENANCE MANUAL

SWB400I DELUXE RADIANT WOOD BURNING FIREPLACE INSTALLATION, OPERATION AND MAINTENANCE MANUAL SWB4I DELUXE RADIANT WOOD BURNING FIREPLACE INSTALLATION, OPERATION AND MAINTENANCE MANUAL The SWB4I fireplace is an insulated radiant wood burning fireplace with a 6-inch wide front opening. It comes

More information

Fire Chief Wood/Coal Burning Furnaces

Fire Chief Wood/Coal Burning Furnaces Distributed by: BEST MATERIALS LLC Ph: 800-474-7570, 602-272-8128 Fax: 602-272-8014 www.bestmaterials.com Email: Sales@BestMaterials.com Fire Chief Wood/Coal Burning Furnaces Indoor FC300F FC450 FC500E

More information

Installation and Operation Instructions

Installation and Operation Instructions Installation and Operation Instructions Superior Unvented (Vent-Free) Gas Log Heater P/N 126817-01 Rev. A 01/2014 Models TF18NV TF18PV TF2430NV TF2430PV P126817-01 INSTALLER: Leave this manual with the

More information

INSTALLATION AND SERVICE MANUAL. Hot Water Heating Boilers Domestic Hot Water Supply Boilers 399, ,000 Btu/hr Models

INSTALLATION AND SERVICE MANUAL. Hot Water Heating Boilers Domestic Hot Water Supply Boilers 399, ,000 Btu/hr Models INSTALLATION AND SERVICE MANUAL CF/CH(P)i&S-02 Hot Water Heating Boilers Domestic Hot Water Supply Boilers 399,999 750,000 Btu/hr Models Installation and service must be performed by a qualified service

More information

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL

UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL UNVENTED (VENT-FREE) GAS LOG HEATER OWNER S OPERATION AND INSTALLATION MANUAL VF-18N-PDG, VF-18P-PDG VF-24N-PDG, VF-24P-PDG VF-18N-BTB, VF-18P-BTB VF-24N-BTB, VF-24P-bTB PFS US WARNING: If the information

More information

M MMG Insurance Company Presents A Guide for Woodburning Safety

M MMG Insurance Company Presents A Guide for Woodburning Safety MMG Insurance Company Presents A Guide for Woodburning Safety CONTENTS Burning Wood Safely...5 Chimney and Stovepipe Cleaning...8 Chimneys for Wood Stoves...1 Cleaning System...8 Clearances...5 Creosote...8

More information

Models BGE18NV BGE18PV BGE2436NV BGE2436PV. For use with log sets

Models BGE18NV BGE18PV BGE2436NV BGE2436PV. For use with log sets Installation and Operation Instructions Unvented (Vent-Free) Gas Log Heater P/N 126827-01 REV. B 04/2018 Models PFS US BGE18NV BGE18PV BGE2436NV BGE2436PV P126827-01 Report No. F09-100 For use with log

More information

RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO

RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO rgalenmoore1@msn.com This session will address the basics of combustion and the latest

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

OWNERS MANUAL MODEL DO110 & DO180 IS CERTIFIED TO: Unit Serial # Purchased From Company Address

OWNERS MANUAL MODEL DO110 & DO180 IS CERTIFIED TO: Unit Serial # Purchased From Company Address OWNERS MANUAL MODEL DO110 & DO180 IS CERTIFIED TO: UL 391 CAN/CSA B366.1 Unit Serial # Purchased From Company Address Name of Installer Installer Telephone # Date Installed IMPORTANT This manual must be

More information

Installation and Operation Instructions

Installation and Operation Instructions Installation and Operation Instructions Superior Unvented (Vent-Free) Gas Log Heater P/N126818-01 Rev. A 01/2014 Models TF18NE TF18PE TF2430NE TF2430PE P126818-01 INSTALLER: Leave this manual with the

More information

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

LADERA. Traditional. Fireplace Design Collection EPA WOOD BURNING FIREPLACES

LADERA. Traditional. Fireplace Design Collection EPA WOOD BURNING FIREPLACES LADERA EPA WOOD BURNING FIREPLACES Traditional Fireplace Design Collection SHOW YOURSELF Create a room that begs you to stick around, sit down and relax. IN FEATURED Ladera fireplace with White Stacked

More information