T7200D,E Series 2000 Commercial Microelectronic Thermostats

Size: px
Start display at page:

Download "T7200D,E Series 2000 Commercial Microelectronic Thermostats"

Transcription

1 T7200D,E Series 2000 Commercial Microelectronic Thermostats INSTALLATION INSTRUCTIONS APPLICATION The T7200D,E Thermostats provide electronic control of 24 Vac commercial single-zone heating, ventilating and air conditioning (HVAC) equipment. The T7200 is field configurable for automatic or manual changeover between heating and cooling. The system and fan selections are made by keyboard entry. All T7200 Thermostats require a common wire to supply power. RECYCLING NOTICE If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat. INSTALLATION When Installing this Product 1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After completing installation, use these instructions to check out the product operation. Location Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1. YES NO NO 5 FEET (1.5 METERS) NO M4823A Fig. 1. Typical location of thermostat. U.S. Registered Trademark Copyright 1998 Honeywell Inc. All Rights Reserved X-XX UL

2 Do not install the thermostat where it can be affected by: drafts, or dead spots behind doors and in corners. hot or cold air from ducts. radiant heat from sun or appliances. concealed pipes and chimneys. unheated (uncooled) areas such as an outside wall behind the thermostat. Mounting Wallplate The wallplate mounts horizontally on the wall or on a 2 in. x 4 in. wiring box. Position the wallplate horizontally on the wall or on a 2 in. x 4 in. wiring box. 1. Position and level the wallplate (for appearance only). The thermostat functions properly even when not level. 2. Use a pencil to mark the mounting holes. See Fig Remove the wallplate from the wall and drill two 3/16 inch (4.8 mm) holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill two 7/32 inch (5.5 mm) holes. Gently tap anchors (provided) into the drilled holes until flush with the wall. 4. Position the wallplate over the holes, pulling wires through the wiring opening. 5. Loosely insert the mounting screws into the holes. 6. Tighten mounting screws. CAUTION Electrical Shock Hazard. Power source can cause electrical shock. Disconnect power before wiring to prevent electrical shock or equipment damage. 1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 3. IMPORTANT Use 18-gauge, solid-conductor color-coded thermostat cable for proper wiring. If using 18-gauge stranded wire, do not use more than ten wires. Do not use larger than 18-gauge wire. 2. Securely tighten each terminal screw. 3. Push excess wire back into the hole. 4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat. WALL WALL ANCHORS (2) WIRES THROUGH WALL FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM). FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM). M4826 Fig. 3. Proper wiring technique. THERMOSTAT X Y1 G W1 RH RC 2 MOUNTING HOLES COMPRESSOR CONTACTOR HEATING RELAY OR VALVE COIL LEDS MOUNTING SCREWS M10237 FAN RELAY 1 L1 (HOT) L2 Fig. 2. Mounting the wallplate. WIRING WALLPLATE All wiring must comply with local electrical codes and ordinances. Follow equipment manufacturer wiring instructions when available. Refer to Fig. 4 and 5 for typical hookups. A letter code is located near each terminal for identification. 1 2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. JUMPER RC AND RH FOR SINGLE TRANSFORMER SYSTEMS. M4942A Fig. 4. Typical hookup of T7200D in single-stage heating and cooling conventional system

3 X Y G O COMPRESSOR CONTACTOR THERMOSTAT COOL CHANGEOVER VALVE R override the program temperatures, display present setting, set system and fan operation, configure Installer Setup, check Installer Test. See Fig. 7 for thermostat key information. FAN RELAY A. ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE. 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 L1 (HOT) L2 M4943A Fig. 5. Typical hookup of T7200E in single-stage heat pump system. Mounting Thermostat on Wallplate The thermostat mounts on the wallplate after it is installed. 1. Engage the tabs at the top of the thermostat and wallplate. See Fig Press the lower edge of the case to latch. B. PRESS LOWER EDGE OF CASE TO LATCH. To remove the thermostat from the wall, first pull out at the bottom of the thermostat; then remove the top. SETTINGS Using Thermostat Keys The thermostat keys are used to: set current time and day, program times and setpoints for heating and cooling, ENTER OCCUPIED PROGRAM MODE ENTER UNOCCUPIED PROGRAM MODE SET CURRENT DAY OR PROGRAM DAY M4824A Fig. 6. Mounting thermostat on wallplate. SET OCCUPIED TEMPERATURE SETPOINTS SET UNOCCUPIED TEMPERATURE SETPOINTS AND SCROLLS THROUGH INSTALLER SETUP AND SYSTEM TEST AM Room RETURNS TO NORMAL OPERATIONS Run Program Mon Occupied Heat Set Program Set Temperature Change Time/Temp Start Time Start Time Day Temp Temp Auto INCREASE TEMPERATURE OR TIME SETTING SET OVERRIDE TEMPERATURE OFFSET AND ACTIVATE TEMPORARY OVERRIDE Temporary Occupied Continuous Set Current Day/Time Clear Start Time Copy Heat/Cool Settings DECREASE TEMPERATURE OR TIME SETTING ENTER HOLD MODE SET CURRENT DAY AND TIME CLEAR PROGRAM PERIOD SELECT SYSTEM OPERATION COPY ONE PROGRAMMED DAY TO ANOTHER DAY SELECT FAN OPERATION Fig. 7. Thermostat key locations and descriptions. CHANGE BETWEEN HEATING AND COOLING SETPOINTS AND SCROLLS BACKWARDS THROUGH INSTALLER SETUP NUMBERS AND SYSTEM TEST M10233A

4 Setting and (select models) The system default setting is Heat. The fan default is set so the fan operates continuously in the Occupied and Recovery modes and with the heating or cooling equipment in the mode. Use the and keys to change the settings. The system settings are: Heat: Thermostat controls the heating. Off: Both the heating and cooling are off. Cool: Thermostat controls the cooling. Auto: Thermostat automatically changes between heating and cooling operation depending on the indoor temperature. The fan settings are: On: operates continuously. Auto: Equipment controls the fan in the mode. The Intelligent operation (Installer Setup number 17) offers three choices for the fan operation in Occupied mode: fan turns on only when there is a call for heating or cooling, fan operates continuously in Occupied mode, fan is on continuously in Occupied and recovery modes. Setting Temperature Refer to Table 1 for the default temperature setpoints. See Owners Guide, form number , for complete instructions on changing the setpoints. Table 1. Default Temperature Setpoints. INSTALLER SETUP Control Heating 70 F (21 C) 55 F (13 C) Cooling 78 F (25.5 C) 90 F (32 C) For most applications, the thermostat factorysettings do not need to be changed. Review the factory-settings in Table 2 and if no changes are necessary, go to the Installer Test section. The Installer Setup is used by the installer to customize the thermostat to specific systems. Installer Setup numbers are listed in Table 2. The table includes all the configuration options available. A combination of key presses are required to use the Installer Setup feature. To enter the Installer Setup mode, press and hold the Heat/Cool Settings key while pressing both the increase and decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 8 and 9. To advance to the next Installer Setup number, press the Temp key. To return to a previous Installer Setup number, press the Heat/Cool Settings key. To change a setting, use the increase or decrease key. To exit the Installer Setup, press the Run Program key. The Installer Setup is automatically exited if no key presses are made for four minutes. Set Program Start Time Set Day/Time Temporary Setting Enrg Em Ht Sav AM Aux Ht Room Comm PM %Humid MonTueWedThuFriSatSun Heat Cool Remote UnOccupied 12 Override In Recovery LoMedHi Auto Only Duct Em Heat OffCool Auto Wait OnAuto INSTALLER SETUP NUMBER DISPLAY (COLUMN 2 OF TABLE 2) Fig. 8. LED display of all segments. FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 2) Fig. 9. Installer Setup number and setting display. Installer Setup numbers are listed in Table 2. M4916 M10238B CAUTION Possible Equipment Damage. must be running when system is operating. Configure heat pump and electric heat systems in Installer Setup 2 to prevent equipment damage caused by the system running without the fan. IMPORTANT Only configurable numbers are shown on the device. Example: If the thermostat does not have a system key, Installer Setup Number 12 will not be displayed. Review Table 2 factory settings and mark any desired changes in the Actual Setting column. When Installer Setup is complete, review the settings to confirm that they match the system

5 Installer Setup Number (Press Temp key a Number 2 must be set to 1 to extend fan operation. b Some models may not have this feature.table 2. Table 2. Thermostat Installer Setup Options. Other Choices (Press or key to change) Factory Setting Actual Select to change) Display Description Display Description Setting Not used. 1 operationa (T7200D only). Degree temperature display. Intelligent operation. Keypad lockout level (keypad lockout is enabled and disabled by dip switch 1 on thermostat back). O/B Operationb (T7200E only). Minimum offtime for the compressor. Temperature display adjustment. 2 0 Conventional applications 1 Electric heat applications where equipment controls fan operation in heat mode. where thermostat controls fan operation in heat mode Temperature is displayed in F operates continuously in Occupied and Recovery mode. operates with call for heating or cooling in mode. 1 Temperature is displayed in C. 0 or 1 0 only operates with calls for heating or cooling in Occupied and modes. 1 operates continuously in Occupied mode. operates with calls for heating or cooling in mode No lockout. 1 or 2 1 Lockout all keys on thermostat except system and fan settings, temporary setpoint; clock and day adjustments. 2 Lockout all keys except set Current Day/Time, increase and decrease keys. 3 Lockout all keys except Temporary Occupied, Set Current Day/Time (for clock, day adjustments) Energize in Cool mode minute minimum off-time for the compressor No difference in displayed temperature and actual room temperature. 1 1 Energize in Heat Mode. 0, 1, 2, 3 or 5 Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor. 1 thru 6 1 Display adjusts to 1 F (0.6 C) higher than actual room temperature. 2 Display adjusts to 2 F (1.1 C) higher than actual room temperature. 3 Display adjusts to 3 F (1.7 C) higher than actual room temperature. 4 Display adjusts to 1 F (0.6 C) lower than actual room temperature. 5 Display adjusts to 2 F (1.1 C) lower than actual room temperature. 6 Display adjusts to 3 F (1.7 C) lower than actual room temperature. (continued)

6 Run Program Temporary Occupied Continous Run Program Temporary Occupied Continous Run Program Temporary Occupied Continous Set Program Set Temperature Change Time/Temp Start Time Start Time Day Temp Temp Set Current Day/Time Clear Start Time Copy Heat/Cool Settings Set Program Set Temperature Change Time/Temp Start Time Start Time Day Temp Temp Set Current Day/Time Clear Start Time Copy Heat/Cool Settings Set Program Set Temperature Change Time/Temp Start Time Start Time Day Temp Temp Set Current Day/Time Clear Start Time Copy Heat/Cool Settings Run Program Set Program Set Temperature Change Time/Temp Start Time Start Time Day Temp Temp Temporary Set Current Clear Occupied Day/Time Start Time Continous Copy Heat/Cool Settings T7200D,E SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTATS Table 2. Thermostat Installer Setup Options (Continued). Installer Setup Number (Press Other Choices Temp key Factory Setting (Press or key to change) Actual Select to change) Display Description Display Description Setting Minimum offtimes in heating minute minimum off-time. 0, 1, 2, 3, or 5 Minimum number of minutes (0 thru 5) the heating equipment will be off between calls for heat. Installer Setup No Installer Setup 1 1 Installer Setup lockout lockout (keypad lockout is enabled and disabled by dip switch 1 on back of thermostat). lockout. activated. IMPORTANT Review the settings to confirm that they match the system. Press Run Program to exit the Installer Setup. Set the current day and time immediately. Setting Current Day and Time 1. Press Set Current Day/Time. Set Current Day/Time On initial power up or after an extended power loss, 1:00 pm flashes on the LCD until a key is pressed. Mon Set Day/Time 2. Press Day until the current day is displayed. Day PM M4951B Sun=Sunday, Mon=Monday, Tue=Tuesday, Wed=Wednesday, Thu=Thursday, Fri=Friday, Sat=Saturday. 3. Press increase or decrease until the current time is displayed. Tue Set Day/Time PM M4952B 4. Press Run Program. Run Program Mon Occupied 1 Heat INSTALLER SYSTEM TEST Auto M4954A Use the Installer Test to check the thermostat configurations and operation. Refer to Table 3 for a list of the available system tests. Table 3. Tests Available in Installer Test. Test Number Test Description 10 to 19 Heating equipment can be turned on and off 30 to 39 Cooling equipment can be turned on and off 40 to 49 equipment can be turned on and off 60 0 to Keyboard keys test to 79 Thermostat information including date code, software versions and subbase identification are displayed To start the system test: AM Room Tapping the Set Current Day/Time changes the time in one hour increments. Tue Set Day/Time PM M4953B CAUTION Possible Equipment Damage. Equipment damage can result if compressor is cycled too quickly. The minimum off-time for compressors is bypassed during the Installer Test. Press and hold the increase and decrease keys, at the same time, until 10 appears. All segments of the LCD are displayed for three seconds before 10 appears. See Fig. 10 and

7 If a duct temperature sensor is installed, the duct temperature is also displayed. Refer to Table 4 and Thermostat Information section for directions and results of the specific system tests. Press Run Program to exit the system test. The system test times out after four minutes if there are no additional key presses. Set Program Start Time Set Day/Time Temporary Setting Enrg Em Ht Sav AM Aux Ht Room Comm PM %Humid MonTueWedThuFriSatSun Heat Cool Remote UnOccupied 12 Override In Recovery LoMedHi Auto Only Duct Em Heat OffCool Auto Wait OnAuto TEST NUMBER Fig. 11. Test number display. M10257A Fig. 10. LCD display of all segments. M4916 Table 4. Installer Test Options. Key to Press Test Number Description Heating Equipment Test Heat/Cool Settings 10 Enter heating equipment test. 11 Heat turns on. The system fan is also energized. 10 Heat and system fan turn off. Cooling Equipment Test Heat/Cool Settings 30 Change from heating to cooling equipment test. 31 Cool and system fan turn on. 30 Cool and system fan turn off. Equipment Test Heat/Cool Settings 40 Change from cooling to fan equipment test. 41 turns on. 40 turns off. Key Operation Test Heat/Cool Settings 60 2 Change from fan to key operation test. Temp 60 0 Temp test number is displayed. Occupied Temp 60 1 Occupied Temp test number is displayed Increase test number is displayed Decrease test number is displayed. Clear Start Time 60 7 Clear Start Time test number is displayed. Day 60 8 Day test number is displayed. Copy 60 9 Copy test number is displayed. Start Start Time test number is displayed. TIme test number is displayed. (select models) (select models) test number is displayed. Set Current Day/Time Set Current Day/Time test number is displayed. Run Program Run Program test number is displayed. Temporary Occupied Temporary Occupied test number is displayed. Occupied Start Time Occupied Start Time test number is displayed. Continuous Continuous test number is displayed

8 Thermostat Information 1. Press the Heat/Cool Settings key to access the thermostat information. 5. Press the increase key again to display the EEPROM identification code. (Example: 314 = EEPROM ID 314). M4934 M4933A 2. Press the increase key to display the production date code. The first two large digits are the month and the third digit is the last digit of the year. (Example: 036 = March 1996). 6. Press the increase key again to display the wallplate identification code. (Example: HP = heat pump wallplate). M10290 M Press the increase key again to display the software identification code. (Example: 02 = software ID code 2). M4932A 4. Press the increase key again to display the software revision number. (Example: 001 = revision number 1). 7. Press Run Program to exit the system test. The system test times out after four minutes without any key presses. Setting Keypad Lockout Switch The dip switch 1 on the back of the thermostat activates the Installer Setup lockout feature. The switch must be set to the ON position (up) to activate the lockout feature. See Fig. 12. The factory setting is off (down). Remove the thermostat from the wallplate and set the switch to ON if keypad lockout is desired. The level of lockout is determined by the Installer Setup number 40. ON 1 M DIP 1 IS ON DIP 2 IS NOT USED. BACK OF THERMOSTAT M10235 Fig. 12. Set Installer Setup lockout dip switch 1 on back of thermostat

9 TROUBLESHOOTING GUIDE Symptom Possible Cause Action Display does not turn on. Temperature display is incorrect. Temperature settings will not change. (Example: Cannot set heating higher or cooling lower.) Unable to configure Installer Setup. Temperature settings change from original setting. Room temperature is out of control. Heating does not turn on. No power to thermostat. Check that C terminal is connected to the system transformer. Check for 24 Vac between C and R terminals. If missing 24 Vac: check if the circuit breaker is tripped; if so, reset the circuit breaker. check if the system fuse is blown; if so, replace the fuse. check if the power switch on the HVAC equipment is in the Off position; if so, set to the On position. check wiring between thermostat and HVAC equipment and replace any broken wires and tighten any loose connections. If 24 Vac is present, proceed with troubleshooting. Room temperature display has been reconfigured. Thermostat is configured for F or C display. Bad thermostat location. Upper or lower temperature limits were reached. Installer Setup is locked out. Heating and cooling setpoints are set too close together. There is a deadband in automatic changeover thermostat models. Example: cool setpoint = 72, deadband = 3, heat setpoint = 68, changing heat setpoint to 70 automatically changes the cool setpoint to 73. Remote temperature sensing is not working. Enter Installer Setup number 37 and reconfigure the display. Enter Installer Setup number 14 and reconfigure the display. Relocate the thermostat. Check the temperature setpoints: Heating limits are 40 F to 90 F (7 C to 31 C). Cooling limits are 45 F to 99 F (9 C to 37 C). Reset the dip switch 1 on the back of the thermostat to enable keypad. Check that the heating setpoint is lower than the cooling setpoint. Checkout all remote sensors. No power to the thermostat. Check that C terminal is connected to the system transformer. Check for 24 Vac between C and R terminals. If missing 24 Vac: check if the circuit breaker is tripped; if so, reset the circuit breaker. check if the system fuse is blown; if so, replace the fuse. check if the system switch at the equipment is in the Off position; if so, set to On position. check wiring between thermostat and HVAC equipment and replace any broken wires and tighten any loose connections. If 24 Vac is present, proceed with troubleshooting. Thermostat minimum off-time is activated and wait indicator is displayed. selection is not set to Heat. Wait up to five minutes for the system to respond. Enter Installer Setup number 38. Reconfigure minimum offtime (if required). Set system selection to Heat. (continued)

10 Troubleshooting Guide (continued). Symptom Possible Cause Action Cooling does not turn on. on indicator (flame = heat, snowflake = cool) is displayed, but no warm or cool air is coming from the registers. No power to the thermostat. Check that C terminal is connected to the system transformer Check for 24 Vac between C and R or RC and Y terminals. If missing 24 Vac: check if the circuit breaker is tripped; if so, reset the circuit breaker. check if the system fuse is blown; if so, replace the fuse. check if the system switch at the equipment is in the Off position; if so, set to the On position. check wiring between thermostat and HVAC equipment and replace any broken wires and tighten any loose connections. If 24 Vac is present, proceed with troubleshooting. Thermostat minimum off-time is activated and wait indicator is displayed. selection is not set to Cool. Conventional heating equipment turns on the fan when the furnace has warmed up to a setpoint. Heating or cooling equipment is not operating. Wait up to five minutes for the system to respond. Enter Installer Setup number 33. Reconfigure minimum offtime (if required). Set system selection to Cool. Wait one minute after the on indicator lights and then check the registers. Verify operation of heating or cooling equipment in system test

11

12 By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys fees, arising out of, or resulting from, any modification to the literature by you. Home and Building Control Honeywell 1985 Douglas Drive North Minneapolis, MN Home and Building Control Honeywell Limited/Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z J.S. Rev

T7300F Series 2000 Commercial Microelectronic Conventional or Heat Pump Thermostat

T7300F Series 2000 Commercial Microelectronic Conventional or Heat Pump Thermostat T7300F Series 2000 Commercial Microelectronic Conventional or Heat Pump Thermostat INSTALLATION INSTRUCTIONS APPLICATION The T7300F Thermostat provides electronic control of 24 Vac commercial single zone

More information

T8624D Chronotherm IV Deluxe Programmable Multistage Thermostats

T8624D Chronotherm IV Deluxe Programmable Multistage Thermostats T8624D Chronotherm IV Deluxe mable Multistage Thermostats INSTALLATION INSTRUCTIONS APPLICATION The T8624D Chronotherm IV Deluxe mable Multistage Thermostats provides electronic control of 24 Vac single-zone

More information

T8611M Deluxe Programmable Heat Pump Thermostats

T8611M Deluxe Programmable Heat Pump Thermostats T8611M Deluxe mable Heat Pump Thermostats INSTALLATION INSTRUCTIONS APPLICATION The T8611M Deluxe mable Heat Pump Thermostat provides electronic control of 24 Vac single-zone two compressor or two speed

More information

Deluxe Programmable Thermostats

Deluxe Programmable Thermostats Deluxe mable Thermostats T8602D INSTALLATION INSTRUCTIONS APPLICATION The T8602D IV Deluxe mable Thermostat provides electronic control of 24 Vac single-stage heating and cooling systems or 750 mv heating

More information

Deluxe Programmable Heat Pump Thermostat T8611M

Deluxe Programmable Heat Pump Thermostat T8611M APPLICATION Deluxe mable Heat Pump Thermostat T8611M INSTALLATION INSTRUCTIONS The T8611M Deluxe mable Heat Pump Thermostat provides electronic control of 24 Vac single-zone two compressor or two speed

More information

T8600D Chronotherm IV Deluxe Programmable Thermostats

T8600D Chronotherm IV Deluxe Programmable Thermostats T8600D Chronotherm IV Deluxe mable Thermostats APPLICATION INSTALLATION INSTRUCTIONS The T8600 Chronotherm IV Deluxe mable Thermostat provides electronic control of 24 Vac singlestage heating and cooling

More information

T8602C Chronotherm IV Deluxe Programmable Thermostats

T8602C Chronotherm IV Deluxe Programmable Thermostats T8602C Chronotherm IV Deluxe mable Thermostats INSTALLATION INSTRUCTIONS APPLICATION The T8602 Chronotherm IV Deluxe mable Thermostat provides electronic control of 24 Vac single-stage heating and cooling

More information

T8611G Chronotherm Deluxe Zoning Heat Pump Thermostat

T8611G Chronotherm Deluxe Zoning Heat Pump Thermostat T8611G Chronotherm Deluxe Zoning Heat Pump Thermostat INSTALLATION INSTRUCTIONS APPLICATION The T8611G Chronotherm Deluxe Zoning Heat Pump Thermostat provides electronic control of 24 Vac zoned heat pump

More information

T7100D Microelectronic Conventional Thermostat

T7100D Microelectronic Conventional Thermostat T7100D Microelectronic Conventional Thermostat INSTALLATION INSTRUCTIONS APPLICATION A. ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE. The T7100D Microelectronic Thermostat provides electronic control of

More information

T8411R Electronic Heat Pump Thermostat

T8411R Electronic Heat Pump Thermostat T84R Electronic Heat Pump Thermostat INSTALLATION INSTRUCTIONS The T84R Heat Pump Thermostat provides 24V control of two-stage heating and one-stage cooling heat pump system with manual changeover from

More information

T8524 Deluxe Electronic Thermostat

T8524 Deluxe Electronic Thermostat T8524 Deluxe Electronic Thermostat PRODUCT DATA T8524 FEATURES AND BENEFITS APPLICATION The T8524 Deluxe Electronic Thermostat provides electronic control of 18 to 30 Vac multistage heating and cooling

More information

tcu.z Commercial Programmable Thermostat Installation Instructions

tcu.z Commercial Programmable Thermostat Installation Instructions Application Mercury Notice Installation The tcu.z Commercial Programmable Thermostat controls 24-VAC commercial single-zone heating, ventilating, and air conditioning (HVAC) equipment. It consists of a

More information

T8401C Electronic Thermostats

T8401C Electronic Thermostats T8401C Electronic Thermostats INSTALLATION INSTRUCTIONS APPLICATION The T8401C Thermostat provides single-stage, nonprogrammable temperature control for 24 Vac heating cooling systems with manual changeover

More information

Commercial Touchscreen Thermostat

Commercial Touchscreen Thermostat 55,13M 1/27 Supersedes 12/25 Commercial Touchscreen Thermostat 25 Lennox Industries, Inc. Dallas, Texas, USA APPLICATION Page 1 INSTALLATION INSTRUCTIONS The Lennox Commercial Touchscreen Thermostat provides

More information

CT500 Electronic Thermostat

CT500 Electronic Thermostat CT500 Electronic Thermostat OWNER'S GUIDE MERCURY NOTICE If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of it properly.

More information

T874 Multistage Thermostat and Q674 Subbase

T874 Multistage Thermostat and Q674 Subbase SUPER TRADELINE T874 Multistage Thermostat and Q674 Subbase Application The T874D Thermostat and Q674E Subbase provide 4 to 30 Vac control of standard stage heating and stage cooling systems. The Y594D

More information

Q7300L Series 2000 Commercial Thermostat Subbases

Q7300L Series 2000 Commercial Thermostat Subbases Q700L Series 2000 Commercial hermostat Subbases INSALLAION INSRUCIONS APPLICAION he Q700L hermostat Subbase is used with the 700D,F hermostat to provide electronic control of commercial 24 Vac single zone

More information

T8011R Programmable Heat Pump Thermostat

T8011R Programmable Heat Pump Thermostat T8011R Programmable Heat Pump Thermostat FEATURES PRODUCT DATA APPLICATION The T8011R Heat Pump Thermostat provides 24 Vac control of a two-stage heating and one-stage cooling heat pump system with manual

More information

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase M3375 M3375 T890A/908AJ Heating or Cooling Thermostat/Wallplate; T890A/Q68B Heating/Cooling Thermostat/Subbase Installation Instructions for the Trained Service Technician. Preparation NOTE: Order Q68B

More information

Honeywell CT3611 PROGRAMMABLE THERMOSTAT. Table of Contents OWNER S GUIDE

Honeywell CT3611 PROGRAMMABLE THERMOSTAT. Table of Contents OWNER S GUIDE Honeywell CT3611 PROGRAMMABLE THERMOSTAT Seven Day Programmable Heat Pump Low Voltage (20 to 30 Vac) Thermostat and Wallplate Model CT3611 OWNER S GUIDE Para pedir estas instrucciones en español, llame

More information

Honeywell CT3550 PROGRAMMABLE THERMOSTAT. Table of Contents OWNER S GUIDE

Honeywell CT3550 PROGRAMMABLE THERMOSTAT. Table of Contents OWNER S GUIDE Weekday, Saturday and Sunday Programmable Heat and/or Cool Low Voltage (20 to 30 Vac) Thermostat and Wallplate Model CT3550 Honeywell CT3550 PROGRAMMABLE THERMOSTAT OWNER S GUIDE Para pedir estas instrucciones

More information

T7351 Commercial Programmable Thermostat FOR SINGLE- OR MULTI-STAGE CONVENTIONAL/HEAT PUMP SYSTEMS

T7351 Commercial Programmable Thermostat FOR SINGLE- OR MULTI-STAGE CONVENTIONAL/HEAT PUMP SYSTEMS T7351 Commercial Programmable Thermostat FOR SINGLE- OR MULTI-STAGE CONVENTIONAL/HEAT PUMP SYSTEMS APPLICATION The T7351 Commercial Programmable Thermostat controls 24 Vac commercial single zone heating,

More information

Honeywell CT8602 PROGRAMMABLE THERMOSTAT

Honeywell CT8602 PROGRAMMABLE THERMOSTAT Honeywell CT8602 PROGRAMMABLE THERMOSTAT Seven Day Programmable Heat and/or Cool Low Voltage (20 to 30 Vac) Thermostat and Wallplate Model CT8602 OWNER S GUIDE Para obtener un documento con las instrucciones

More information

Q7300H Series 2000 Commercial Thermostat Subbases

Q7300H Series 2000 Commercial Thermostat Subbases Q700H Series 000 Commercial hermostat Subbases INSALLAION INSRUCIONS APPLICAION he Q700H hermostat Subbases are used with 700F hermostats to provide electronic control of commercial Vac single or multistage

More information

T8112C,DElectronic ProgrammableThermostats

T8112C,DElectronic ProgrammableThermostats Honeywell T8112C,DElectronic ProgrammableThermostats APPLICATION The T8112C,D thermostats provide electronic programmable control for 24 to 30 Vac heating and cooling systems. @ RECYCLING NOTICE if this

More information

TCONT602AF22MA. Programmable Comfort Control. Installation Instructions 18-HD37D1-1

TCONT602AF22MA. Programmable Comfort Control. Installation Instructions 18-HD37D1-1 TCONT602AF22MA Programmable Comfort Control Installation Instructions 18-HD37D1-1 Product Application This Comfort Control provides electronic control of 24 VAC single-stage and multistage heating and

More information

Q7100A,C,D Thermostat Subbases

Q7100A,C,D Thermostat Subbases Q700A,C, hermostat Subbases INSALLAION INSRUCIONS APPLICAION he Q700 hermostat Subbases provide electronic control of commercial Vac single or multistage heat pump or conventional heating and cooling systems.

More information

Honeywell/36. Programmable Thermostat OWNER S GUIDE

Honeywell/36. Programmable Thermostat OWNER S GUIDE Honeywell/36 Programmable Thermostat OWNER S GUIDE Seven Day Programmable Heat and/or Cool Low Voltage (20 to 30 Vac) Thermostat and Wallplate Model CT3600 Para pedir estas instrucciones en español, llame

More information

CT2700 An Electronic Round Programmable Thermostat

CT2700 An Electronic Round Programmable Thermostat CT2700 An Electronic Round Programmable Thermostat USER S GUIDE MERCURY SWITCH TYPICAL LOCATION OF A MERCURY SWITCH IN A THERMOSTAT M064 RECYCLING THERMOSTAT If this thermostat is replacing a control that

More information

ACONT600AF11MA Programmable Comfort Control

ACONT600AF11MA Programmable Comfort Control ACONT600AF11MA Programmable Comfort Control Installation Instructions Pub. No. 11-HD02D10-4 69-1832-03 Product Application This Comfort Control provides electronic control of 24 VAC single-stage heating

More information

CAUTION: ELECTRICAL HAZARD

CAUTION: ELECTRICAL HAZARD R R Installation Guide 53DF50-HW hermostat System ypes Cool Only (single stage) Heat Pump (with electric heat) CAUION: ELECRICAL HAZARD Can cause electrical shock or equipment damage. Disconnect power

More information

PS4000 and PS5000 Touchscreen Programmable Thermostat Installation and Owners Manual Robertshaw 01/

PS4000 and PS5000 Touchscreen Programmable Thermostat Installation and Owners Manual Robertshaw 01/ PS4000 and PS5000 Touchscreen Programmable Thermostat Installation and Owners Manual www.robertshaw.com 2016 Robertshaw 01/16 352-00244-001 IMPORTANT SAFETY INFORMATION WARNING: ELECTRICAL SHOCK HAZARD

More information

Must be installed by a trained, experienced technician

Must be installed by a trained, experienced technician Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8321097: For up to 3 Heat/2 Cool heat pump or up to 2 Heat/2 Cool conventional

More information

T7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS

T7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS T7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS 63-2652 FEATURES Typically used in buildings (including: restaurants, shopping malls, office buildings and banks) under 55,000 square feet.

More information

T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS

T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS Contents T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS OWNER S GUIDE Features... 2 Settings... 3 Programming... 5 63-2638 FEATURES Typically used in buildings (including: restaurants,

More information

CT2800 Programmable Thermostat

CT2800 Programmable Thermostat CT2800 Programmable Thermostat INSTALLATION AND PROGRAMMING INSTRUCTIONS Welcome to the world of comfort and energy savings with your new Honeywell Programmable Thermostat. Your new thermostat will automatically

More information

heat (2 heat/1 cool).

heat (2 heat/1 cool). Product Application This thermostat provides electronic control of 24 VAC heat pump systems with auxiliary heat (2 heat/1 cool). Power Type * Battery power, ColTIll3On wire " CoITI1TIon wire with battery

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8800 Universal Communicating Thermostat Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Installation Installation location recommendations... 2 Thermostat mounting...

More information

EWT-3102/EWT-3103 Touchscreen Programmable Thermostat

EWT-3102/EWT-3103 Touchscreen Programmable Thermostat EWT-3102/EWT-3103 Touchscreen Programmable Thermostat WED Room PM Running As SCHED SYSTEM AUTO HEAT FAN AUTO MORE SCHED HOLD CLOCK SCREEN EWC Controls, Inc. 385 HWY 33, Englishtown, NJ 07726 Ph: 732-446-3110

More information

T6984F,G Electronic Floating Control Thermostats

T6984F,G Electronic Floating Control Thermostats T6984F,G Electronic Floating Control Thermostats FEATURES PRODUCT DATA P+I control action provides accurate, stable room temperature control. Used with ML644 Series 60 Direct Coupled Damper Actuators.

More information

T8011F Flush Mount Programmable Heat PumpThermostat OWNER S GUIDE

T8011F Flush Mount Programmable Heat PumpThermostat OWNER S GUIDE T8011F Flush Mount Programmable Heat PumpThermostat OWNER S GUIDE 1 69-1557 Welcome to the world of comfort and energy savings with your new Honeywell programmable thermostat. Your new programmable thermostat

More information

Q7100A,C Thermostat Subbases

Q7100A,C Thermostat Subbases Q700A,C hermostat Subbases INSALLAION INSRUCIONS APPLICAION he Q700 hermostat Subbases provide electronic control of commercial 4 Vac single or multistage heat pump or conventional heating and cooling

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8476 Thermostat with Event-Based Air Cleaning Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Installation Installation location recommendations... 3 Outdoor

More information

Safety & Installation Instructions

Safety & Installation Instructions 8400 Series Thermostats Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS 61000652C 8400 Tstat Install.indd 1 10/13/09 11:08:56 AM Table of contents Installation Installation location

More information

This thermostat provides electronic control of 24 VAC single-stage and multi-stage

This thermostat provides electronic control of 24 VAC single-stage and multi-stage Product Application This thermostat provides electronic control of 24 VAC single-stage and multi-stage heating and cooling systems, or 750 mv heating systems. System Types (up to 2 heat/2 cool) (ats, oil,

More information

VisionPRO 8000 with Wi-Fi

VisionPRO 8000 with Wi-Fi VisionPRO 8000 with Wi-Fi FEATURES PRODUCT DATA Thermostat acquires weather data through either a wired sensor or an Internet connection, making for a truly universal installation. U1 Terminals One set

More information

CT1001/CT1002 Touchscreen Programmable Thermostat

CT1001/CT1002 Touchscreen Programmable Thermostat CT1001/CT1002 Touchscreen Programmable Thermostat WED Room PM Running As SCHED SYSTEM HEAT AUTO FAN AUTO MORE SCHED HOLD CLOCK SCREEN Contents CT1001/CT1002 Touchscreen Programmable Thermostat Application/Features...2

More information

INSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page. INSTALLATION MANUAL This manual covers the following models: T755 Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

MagicStat CT3300 Programmable Thermostat

MagicStat CT3300 Programmable Thermostat MagicStat CT3300 Programmable Thermostat Installation and Programming Instructions Weekday/Weekend (5-day/2-day) Programmable Heat and/or Cool Low Voltage (20 to 30 Vac) Thermostat and Mounting Plate Model

More information

T7984 A,B,C Electronic Modulating Control Thermostats

T7984 A,B,C Electronic Modulating Control Thermostats T7984 A,B,C Electronic Modulating Control Thermostats FEATURES PRODUCT DATA APPLICATION These microprocessor-based thermostats provide proportional - integral (PI) individual room temperature control in

More information

T8000C Programmable Thermostat

T8000C Programmable Thermostat T8000C Programmable Thermostat APPLICATIN The T8000C Thermostat provides single-stage, programmable temperature control for 24 Vac heating-cooling systems with manual changeover from heat to cool. Heating

More information

T834C Heating-Cooling Thermostat

T834C Heating-Cooling Thermostat M3375 M3375 TRADELINE T834C Heating-Cooling Thermostat Application T834C Thermostats control 4 to 30 Vac single-stage heating-cooling systems. See Table for specific models and applications. An spdt mercury

More information

Safety & Installation Instructions

Safety & Installation Instructions 8400 Series Thermostats Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS 61000652A 8400 Tstat Install.indd 1 7/23/09 2:20:45 PM Table of contents Installation Installation location recommendations...

More information

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page. INSTALLATION MANUAL This manual covers TopTech models: TT-N-851 Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

T8400C Universal Electronic Thermostats

T8400C Universal Electronic Thermostats T8400C Universal Electronic Thermostats INSTALLATIN INSTUCTINS APPLICATIN The T8400C Universal Thermostat provides single-stage, non-programmable temperature control for 24 Vac heating-cooling systems

More information

Parts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins

Parts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins Table of Contents Parts Diagram........................................................... 1 Icon Descriptions......................................................... 2 Specifications...........................................................

More information

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control Document Number 13I00-5 November, 1997 CONTENTS

More information

ELECTRONIC COMMUNICATING THERMOSTAT

ELECTRONIC COMMUNICATING THERMOSTAT O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-81 Single Stage Heat/Cool Real Time Pricing System Document Number 13I00-2 January, 1997 Copyright 1997 Home Automation, Inc.

More information

INSTALLATION MANUAL. Need Help? This manual covers the following models: T915. Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T915. Power Type. Thermostat Applications Guide. Page. INSTALLATION MANUAL This manual covers the following models: T915 Thermostat Applications Guide Des cription Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux.

More information

INSTALLATION MANUAL. This manual covers TopTech models: TT-S-755H. Need Help? Thermostat Applications Guide. Power Type. Table of Contents.

INSTALLATION MANUAL. This manual covers TopTech models: TT-S-755H. Need Help? Thermostat Applications Guide. Power Type. Table of Contents. INSTALLATION MANUAL This manual covers TopTech models: TT-S-755H Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

T8400C and T8401C Electronic Thermostats

T8400C and T8401C Electronic Thermostats T8400 and T840 Electronic Thermostats INSTALLATION INSTUTIONS The T8400 and T840 Thermostats provide singlestage, non-programmable temperature control for 4V heating-cooling systems with manual changeover

More information

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION Your new White-Rodgers Digital Thermostat

More information

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT CONTENTS Installation Instructions for Heating & Air Conditioning 1F79 n-programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information

Installer Guide. WARNING Important Safety Information. 1 Specifications

Installer Guide. WARNING Important Safety Information. 1 Specifications 1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Heat Pump or 2 Heat / 2 Cool Conventional Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE

More information

T6984 A,D,E Electronic Floating Control Thermostats

T6984 A,D,E Electronic Floating Control Thermostats T6984 A,D,E Electronic Floating Control Thermostats FEATURES PRODUCT DATA PI (proportional and integral) control action provides accurate, stable room temperature control. T6984 models are used with Series

More information

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help? INSTALLATION MANUAL This manual covers the following models: T955W Master Thermostat Base Module Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump (No Aux. or Emergency

More information

EL-TSTAT-8820 Safety & Installation Instructions

EL-TSTAT-8820 Safety & Installation Instructions EL-TSTAT-8820 Safety & Installation Instructions TABLE OF CONTENTS WI-FI SETUP Wi-Fi Setup 2 INSTALLATION Installation location recommendations 3 Outdoor temperature sensor (included) 3 Remote temperature

More information

Oil-Fired Furnace Single Stage Heat Pumps No- Auxiliary Heat. Electric Air Conditioning

Oil-Fired Furnace Single Stage Heat Pumps No- Auxiliary Heat. Electric Air Conditioning ES100 ROUND DIGITAL NON-PROGRAMMABLE BATTERY OPERATED THERMOSTAT The ES100 Digital Thermostat is designed to work on the following 24V systems. This Thermostat will not control multistage heat pumps or

More information

IF79 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning

IF79 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning CONTENTS Installation Instructions for Heating & Air Conditioning IF79 n- Programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL

More information

SMART 5000 Wi-Fi Touchscreen Programmable Thermostat Owners Manual

SMART 5000 Wi-Fi Touchscreen Programmable Thermostat Owners Manual by Uni-Line SMART 5000 Wi-Fi Touchscreen Programmable Thermostat Owners Manual www.robertshaw.com 2016 Robertshaw 4/16 352-00243-001 IMPORTANT SAFETY INFORMATION WARNING: ELECTRICAL SHOCK HAZARD Turn off

More information

RC-101 Heat Pump Real Time Pricing System 2 Stage Heat / 1 Stage Cool

RC-101 Heat Pump Real Time Pricing System 2 Stage Heat / 1 Stage Cool O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-101 Heat Pump Real Time Pricing System 2 Stage Heat / 1 Stage Cool Document Number 13I00-4 January, 1997 Copyright 1997 Home Automation,

More information

INSTALLATION MANUAL. Need Help? This manual covers TopTech models: TT-N-721 and T721. Power Type. Thermostat Applications Guide.

INSTALLATION MANUAL. Need Help? This manual covers TopTech models: TT-N-721 and T721. Power Type. Thermostat Applications Guide. INSTALLATION MANUAL This manual covers TopTech models: TT-N-721 and T721 Thermostat Applications Guide Description Gas or Oil Heat Electric Furnace Heat Pump ( Aux. or Emergency Heat) Heat Pump (with Aux.

More information

1 PREPARATION 2 THERMOSTAT MOUNTING DIMENSIONS. CT70A Heat Pump Thermostat. Your Honeywell Thermostat. Recycling Notice. Do-It-Yourself Models

1 PREPARATION 2 THERMOSTAT MOUNTING DIMENSIONS. CT70A Heat Pump Thermostat. Your Honeywell Thermostat. Recycling Notice. Do-It-Yourself Models M75 M75 Installation Instructions Thermometer Scale Range: 45 o F to 85 o F [7 o C to 29 o C]. Electrical Ratings: 24 to 27 Vac. CT70A Heat Pump Thermostat Do-It-Yourself Models Your Honeywell Thermostat

More information

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions DESCRIPTION The RC-90 is a precision digital thermostat designed for 24 VAC single stage heating and

More information

SC Installation, Operation & Application Guide

SC Installation, Operation & Application Guide SC 5211 2-Stage Heat Pump Auto Changeover Hardwire Programmable Electronic Thermostat 7-Day, 5-2-Day or 5-1-1-Day Programmable Configurable 2-Stage Heat Pump Systems Large Display With Backlight Selectable

More information

Smart Temp. Model

Smart Temp. Model Smart Temp Model 42-160 SINGLE STAGE PROGRAMMABLE THERMOSTAT 1 Heat / 1 Cool Single Stage Thermostat. 5+2 Programmable, Compatible with Gas Heat & Heat Pump System Installation and Operation Manual SPECIFICATIONS:--------------------------------------------------------------------------------

More information

Home and Building Control Home and Building Control Helping You Control Your World

Home and Building Control Home and Building Control Helping You Control Your World M3375 Home and Building Control Home and Building Control Helping You Control Your World Honeywell Inc. Honeywell Limited/Honeywell Limitée 1985 Douglas Drive No. 740 Ellesmere Road Golden Valley, MN 55422

More information

Installer Guide. WARNING Important Safety Information. 1 Specifications

Installer Guide. WARNING Important Safety Information. 1 Specifications 1 Specifications cont. Premier Series Universal Auto Changeover Up to 3 Heat / 2 Cool Conventional and Heat Pump Thermostat Installer Guide Before Installing, Programming or Operating, PLEASE READ ALL

More information

1F98EZ-1421, Easy Install

1F98EZ-1421, Easy Install 1F98EZ-1421, -1441 Easy Install For up to 4 Stages and 2 Stages Cool INSTALLATION INSTRUCTIONS APPLICATIONS Configuration Options Single Stage Multi Stage Pump Pump with Dual Fuel FAILURE TO READ AND FOLLOW

More information

Emerson Blue Easy Set 1H/1C

Emerson Blue Easy Set 1H/1C Emerson Blue Easy Set 1H/1C Model: 1F86EZ-0251 Non-Programmable Thermostat with 3 Temperature Pre-Sets Home, Sleep and Away Installation Instructions and User Guide Message to Homeowner Congratulations

More information

PRO Installation. Thermostat Wi-Fi

PRO Installation. Thermostat Wi-Fi PRO Installation Thermostat Wi-Fi 1 Designed by the pros for the pros There are a lot of choices when it comes to buying a thermostat, but only one combines 125 years of experience and the latest connected

More information

T874A-F Multistage Thermostats; Q674A-G Subbases by Honeywell

T874A-F Multistage Thermostats; Q674A-G Subbases by Honeywell M3375 M3375 T874A-F Multistage Thermostats; Q674A- Subbases by Honeywell Installation Instructions for the Trained Service Technician Application The T874A-F Thermostats provide 4 to 30 Vac control for

More information

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT CONTENTS Installation Instructions for Heating & Air Conditioning 1F72 5/2 Day Programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information

INSTALLATION MANUAL. Need Help? This manual covers the following models: T725. Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T725. Power Type. Thermostat Applications Guide. Page. INSTALLATION MANUAL This manual covers the following models: T725 Thermostat Applications Guide Des cription Gas or Oil Heat Electric Furnace Heat Pump ( Aux. or Emergency Heat) Heat Pump (with Aux. or

More information

ATP21W02 CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS REMOVING OLD THERMOSTAT 2 THERMOSTAT DETAILS

ATP21W02 CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS REMOVING OLD THERMOSTAT 2 THERMOSTAT DETAILS CONTENTS Installation Instructions for 97B0082N07 Heating & Air Conditioning 5/2 Day Programmable Heat Pump Thermostat Preparations...1 Thermostat Details...1 Removing Old Thermostat... 1-2 Mounting and

More information

PRO Installation. Touch Wi-Fi Thermostat

PRO Installation. Touch Wi-Fi Thermostat PRO Installation Touch Wi-Fi Thermostat 1 Designed by the pros for the pros There are a lot of choices when it comes to buying a thermostat, but only one combines 125 years of experience and the latest

More information

PerFormance Pro t4900 school series InstallatIon GUIDe

PerFormance Pro t4900 school series InstallatIon GUIDe T4900 PerFormance Pro t4900 school series InstallatIon GUIDe the Peco PerFormance Pro t4900 school series thermostat Thank you for choosing the PECO Performance PRO T4900 School Series thermostat. The

More information

T7300F Multistage Conventional or Heat Pump Programmable Commercial Thermostat

T7300F Multistage Conventional or Heat Pump Programmable Commercial Thermostat T7300F Multistage Conventional or Heat Pump Programmable Commercial Thermostat 1.0 GENERAL 1.1 Overview GUIDE SPECIFICATION The contractor shall furnish, install, and place in operating condition an HVAC

More information

T8090A/Q682B Heating, Cooling, and Heating-Cooling Thermostat, Wallplate and Subbase

T8090A/Q682B Heating, Cooling, and Heating-Cooling Thermostat, Wallplate and Subbase M75 M75 T8090A/Q68B Heating, ooling, and Heating-ooling Thermostat, allplate and Subbase SUPER TRADELINE Installation Instructions for the Trained Service Technician. Preparation heck thermostat and subbase

More information

VisionPRO IAQ Total Home Comfort System

VisionPRO IAQ Total Home Comfort System VisionPRO IAQ Total Home Comfort System PRODUCT DATA FEATURES APPLICATION Large, clear display with backlight shows the current and set temperature and time even in the dark. Touchscreen interaction Real-time

More information

CT1500, CT1501, CT1502, CT1503

CT1500, CT1501, CT1502, CT1503 Timer Thermostat Fuel Saver Heating-Only Thermostat and Wallplate or Heating/Cooling Thermostat and Subbase Models CT1500, CT1501, CT1502, CT1503 Heat Only CT1500 Heat/Cool CT1501 Central Electric Heat/Cool

More information

SC Installation, Operation & Application Guide

SC Installation, Operation & Application Guide SC 3006 Auto Changeover 7-Day Programmable Hardwired Programmable Electronic Thermostat 7-Day Programmable Single Stage Heat Pump/Non-Heat Pump Systems Backlit Display Single Stage Heat/Cool Systems Field

More information

Safety & Installation Instructions

Safety & Installation Instructions Premium Programmable Thermostat Safety & Installation Instructions Model 8570 READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS PAGE SPECIFICATIONS............................. 1 WIRE REQUIREMENTS.........................

More information

PRO Installation. Touch Wi-Fi Thermostat

PRO Installation. Touch Wi-Fi Thermostat PRO Installation Touch Wi-Fi Thermostat 1 Designed by the pros for the pros There are a lot of choices when it comes to buying a thermostat, but only one combines 125 years of experience and the latest

More information

PerFormance Pro t12000 series InstallatIon GUIDe

PerFormance Pro t12000 series InstallatIon GUIDe PerFormance Pro t12000 series InstallatIon GUIDe the Peco PerFormance Pro thermostat Thank you for choosing a PCO Performance PRO thermostat. The Performance PRO T12000 Series is intended for use in residential

More information

COMFORT CONTROL - 4 HEAT (GAS, OIL*, OR ELECTRIC)/3 COOL/HEAT PUMP COMMUNICATING PROGRAMMABLE 3 WIRE HOOKUP

COMFORT CONTROL - 4 HEAT (GAS, OIL*, OR ELECTRIC)/3 COOL/HEAT PUMP COMMUNICATING PROGRAMMABLE 3 WIRE HOOKUP COMFORT CONTROL - 4 HEAT (GAS, OIL*, OR ELECTRIC)/3 COOL/HEAT PUMP COMMUNICATING PROGRAMMABLE 3 WIRE HOOKUP ALL phases of this installation must comply with NATIONAL, STATE, AND LOCAL CODES INSTALLER S

More information

T4398A,B High Performance Electric Heat Thermostats

T4398A,B High Performance Electric Heat Thermostats T498A,B High Performance Electric Heat Thermostats FEATURES PRODUCT DATA Controls both fan-forced and baseboard electric heaters. Temperature-responsive, vapor-filled dual diaphragm sensing element provides

More information

VisionPRO IAQ Total Home Comfort System

VisionPRO IAQ Total Home Comfort System VisionPRO IAQ Total Home Comfort System PRODUCT DATA FEATURES APPLICATION The VisionPRO IAQ Total Home Comfort System features an effortless, 7-Day programmable touchscreen thermostat that provides control

More information

CR Series Command Relays

CR Series Command Relays CR Series Command Relays FEATURES INSTALLATION INSTRUCTIONS Patented 35mm Din-rail mounting flange (US Patent 7,416,421) SPDT Form 1C Relay contacts Pilot duty rated LED status indication Stackable for

More information