DC INVERTER MULTI-SYSTEM AIR CONDITIONER

Size: px
Start display at page:

Download "DC INVERTER MULTI-SYSTEM AIR CONDITIONER"

Transcription

1 TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CLM97 CLM7 CLM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CLM97 CLM7 CLM7 Product Code No CLM97 < Applicable Indoor Units > all mounted type KMS077 KMS097 KMS7 KMS87 KMS7 NOTE CLM7 For details about the combination, refer to "Unit Combination Table" in the Appendix of this manual. CLM7 IMPORTANT These air conditioners employ new refrigerant R0A. Pay special attention when servicing the unit. REFERENCE NO. SM

2 Important! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard or ARNING unsafe practice which can result in severe personal injury or death. CAUTION SPECIAL PRECAUTIONS ARNING hen iring This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage. If Necessary, Get Help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions. In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO IRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. Install a protective leakage breaker depending on the installation location (especially a damp or humid location). If a leakage breaker is not installed, electric shock can occur. hen Transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. hen Installing In a Ceiling or all Make sure the ceiling/wall is strong enough to hold the unit s weight. It may be necessary to construct a strong wood or metal frame to provide added support. In a Room Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors. In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration. In an Area with High inds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. In a Snowy Area (for Heat Pump-type Systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. hen Connecting Refrigerant Tubing Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. Check carefully for leaks before starting the test run. hen Servicing Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. Others CAUTION Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.

3 Table of Contents APPLICABLE INDOOR UNITS.... OPERATING RANGE... Page. SPECIFICATIONS -. Unit Specifications -. Major Component Specifications -. Other Component Specifications DIMENSIONAL DATA.... REFRIGERANT FLO DIAGRAM -. Refrigerant Flow Diagram.... PERFORMANCE DATA -. Temperature Charts Cooling Capacity Cooling Capacity (Low Ambient) ELECTRICAL DATA 6-. Electric iring Diagrams FUNCTIONS 7-. Explanation of Functions Protective Functions TROUBLESHOOTING 8-. Precautions before Performing Inspection or Repair Trouble Diagnosis by Error Monitop Lamps Checking the Outdoor System Trouble Diagnosis of Each Part Trouble Diagnosis of Fan Motor REFRIGERANT R0A: SPECIAL PRECAUTIONS HEN SERVICING UNIT 9-. Characteristics of New Refrigerant R0A Checklist before Servicing Tools Specifically for R0A Tubing Installation Procedures In Case of Compressor Malfunction In Case Refrigerant is Leaking Charging Additional Refrigerant Retro-Fitting Existing Systems APPENDIX A INSTALLATION INSTRUCTIONS... APPENDIX B UNIT COMBINATION TABLES A- A-

4 APPLICABLE INDOOR UNITS Multi-Outdoor Unit Indoor Unit KMS077 KMS097 KMS7 KMS87 KMS7 -Room CLM97 YES YES YES YES NO -Room CLM7 YES YES YES YES YES -Room CLM7 YES YES YES YES YES NOTE The table lists the wall-mounted type of indoor units as representative models.

5 . OPERATING RANGE Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 9 F D.B. / 7 F.B. Cooling Minimum 67 F D.B. / 7 F.B. * F D.B.: hen combined with KMS87 or KMS7 F D.B.: hen combined with KMS077, KMS097 or KMS7 F D.B. *

6 . SPECIFICATIONS -. Unit Specifications Outdoor Unit CLM97 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 0V Single-Phase 60Hz < 0V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h k BTU/h BTU/h ft /min (m /h) 9, Cooling ( 9,800 to 9,700 ) (.90 to.80 ) 6,800,900,707 (,900) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A 7.0,70 Power Factor % 98 SEER BTU/h Compressor Locked Rotor Amperes A.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi and multi-steps) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 6.7 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 8 () Refrigerant Narrow tube inch (mm) / (6.) Tube Diameter ide tube inch (mm) /8 (9.) Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling 9-/8-7/6-9/ ( ) -7/ 0-/8 6-/ (860,0 ) (6.0) (67.0) (0.6) DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CLM97 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F.B. Outdoor air temp. 9 F D.B./ 7 F.B. 6

7 Outdoor Unit CLM97 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 08V Single-Phase 60Hz < 08V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h k BTU/h BTU/h ft /min (m /h) 9, Cooling ( 9,800 to 9,700 ) (.90 to.80 ) 6,800,900,707 (,900) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A 7.7,70 Power Factor % 98 SEER BTU/h Compressor Locked Rotor Amperes A.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi and multi-steps) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 6.7 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 8 () Refrigerant Narrow tube inch (mm) / (6.) Tube Diameter ide tube inch (mm) /8 (9.) Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling 9-/8-7/6-9/ ( ) -7/ 0-/8 6-/ (860,0 ) (6.0) (67.0) (0.6) DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CLM97 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F.B. Outdoor air temp. 9 F D.B./ 7 F.B. 7

8 Outdoor Unit CLM7 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 0V Single-Phase 60Hz < 0V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h k BTU/h BTU/h ft /min (m /h), Cooling ( 9,800 to,00 ) (.90 to 7.0 ),00,000,707 (,900) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A.,60 Power Factor % 98 SEER BTU/h Compressor Locked Rotor Amperes A.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi and multi-steps) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 6.7 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 8 () Refrigerant Narrow tube inch (mm) Tube Diameter ide tube inch (mm) Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling / (6.) /8 (9.) + / (.7) 9-/8-7/6-9/ ( ) -7/ 0-/8 6-/ (860,0 ) (6.0) (67.0) (0.6) DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CLM7 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F.B. Outdoor air temp. 9 F D.B./ 7 F.B. 8

9 Outdoor Unit CLM7 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 08V Single-Phase 60Hz < 08V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h k BTU/h BTU/h ft /min (m /h), Cooling ( 9,800 to,00 ) (.90 to 7.0 ) 0,600,800,707 (,900) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A.,60 Power Factor % 98 SEER BTU/h Compressor Locked Rotor Amperes A.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi and multi-steps) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 6.7 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a 0 Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 8 () Refrigerant Narrow tube inch (mm) Tube Diameter ide tube inch (mm) Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling / (6.) /8 (9.) + / (.7) 9-/8-7/6-9/ ( ) -7/ 0-/8 6-/ (860,0 ) (6.0) (67.0) (0.6) DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CLM7 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F.B. Outdoor air temp. 9 F D.B./ 7 F.B. 9

10 Outdoor Unit CLM7 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 0V Single-Phase 60Hz < 0V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h k BTU/h BTU/h ft /min (m /h) 0, Cooling ( 9,800 to 0,600 ) (.90 to 9.00 ),800,800,9 (,00) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A.,800 Power Factor % 99 SEER BTU/h 6 Compressor Locked Rotor Amperes A 7.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi and multi-steps) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 8.8 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 00 (0.) Refrigerant Narrow tube inch (mm) Tube Diameter ide tube inch (mm) Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling / (6.) /8 (9.) + / (.7) -/ -7/6-9/ ( ) 9-/ 0-/8 6-/ (,00,0 ) (79.0) (8.0) (0.) DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CLM7 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F.B. Outdoor air temp. 9 F D.B./ 7 F.B. 0

11 Outdoor Unit CLM7 Indoor Unit KMS097 Type Number of Connectable Indoor Units Number of Operatable Indoor Units Voltage Rating -Room Multi Outdoor Unit 08V Single-Phase 60Hz < 08V > Performance Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) BTU/h k BTU/h BTU/h ft /min (m /h) 8, Cooling ( 9,800 to 8,600 ) (.90 to 8.0 ),00,00,9 (,00) Electrical Rating Available Voltage Range V 87 to Running Amperes Power Input A.6,800 Power Factor % 99 SEER BTU/h 6 Compressor Locked Rotor Amperes A 7.0 Fuse or Circuit Breaker Capacity A 0 Features (Outdoor Unit) Control Microprocessor Fan Speeds Auto (Hi and multi-steps) Compressor Refrigerant / Amount charged at shipment Ib. (g) DC Twin Rotary (Inverter) R0A / 8.8 (,800) Refrigerant Control Electric Expansion Valve Operation Sound (High) Cool db-a Refrigerant Tubing Connections Flare Type Max. allowable tubing length per unit ft. (m) 00 (0.) Refrigerant Narrow tube inch (mm) Tube Diameter ide tube inch (mm) Dimensions & eight (Outdoor Unit) Unit Dimensions Package Dimensions eight Height idth Depth Height idth Depth Shipping Volume Net Shipping inch (mm) inch (mm) Ib. (kg) Ib. (kg) cu.ft (m ) Cooling / (6.) /8 (9.) + / (.7) -/ -7/6-9/ ( ) 9-/ 0-/8 6-/ (,00,0 ) (79.0) (8.0) (0.) DATA SUBJECT TO CHANGE ITHOUT NOTICE. Remarks:. The Values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : KMS097 units Outdoor Unit : CLM7 unit. Rating conditions are: Cooling : Indoor air temp. 80 F D.B./ 67 F.B. Outdoor air temp. 9 F D.B./ 7 F.B.

12 -. Major Component Specifications --. Outdoor Unit Outdoor Unit CLM97 Control PCB Part No. Controls Control Circuit Fuse Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 68 F (0 C)) Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Operation Temp. Run Capacitor Crankcase Heater Micro F VAC CB-CLM97 Microprocessor 0V A DC Twin Rotary (Hermetic) KD0XAB /,700 FV0S....9 (900) U - V : 0.70 V - : U : 0.76 Yes Yes Yes CS-7LN Open : 9 F ( C), Close : F (00 C) - - 0V 0 Fan Type Q'ty... Dia. inch (mm) Propeller... D8-/8 (D60) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor Ohm Micro F VAC DC Motor SIC-7F-D Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube 8. Face Area ft (m ) 6.0 (0.9) External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE ITHOUT NOTICE.

13 Outdoor Unit CLM7 Control PCB Part No. Controls Control Circuit Fuse Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 68 F (0 C)) Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Operation Temp. Run Capacitor Crankcase Heater Micro F VAC CB-CLM7 Microprocessor 0V A DC Twin Rotary (Hermetic) KD0XAB /,700 FV0S....9 (900) U - V : 0.70 V - : U : 0.76 Yes Yes Yes CS-7LN Open : 9 F ( C), Close : F (00 C) - - 0V 0 Fan Type Q'ty... Dia. inch (mm) Propeller... D8-/8 (D60) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor Ohm Micro F VAC DC Motor SIC-7F-D Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube 8. Face Area ft (m ) 6.0 (0.9) External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE ITHOUT NOTICE.

14 Outdoor Unit CLM7 Control PCB Part No. Controls Control Circuit Fuse Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 68 F (0 C)) Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Operation Temp. Run Capacitor Crankcase Heater Micro F VAC CB-CLM7 Microprocessor 0V A DC Twin Rotary (Hermetic) JD0XAB /,000 FV0S.... (,00) U - V : 0. V - : 0. - U : 0. Yes Yes Yes CS-7LN Open : 9 F ( C), Close : F (00 C) - - 0V 0 Fan Type Q'ty... Dia. inch (mm) Propeller... D8-/8 (D60) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (0 C)) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor Ohm Micro F VAC DC Motor SIC-7F-D Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube 8. Face Area ft (m ) 7.7 (0.7) External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE ITHOUT NOTICE.

15 -. Other Component Specifications Sensor Name Model No. of sensor Quantity of Sensor CLM97 CLM7 CLM7 Outdoor air temp sensor TKS9B Outdoor heat exchanger sensor TKS9B A / AN sensor TKS9B / / / B / BN sensor TKS9B / / / C / CN sensor TKS9B / / / D / DN sensor TKS9B 0 / / 0 Resistance (k ohm) (-0)(-)(-0) (-) (0) () (0) () (0) Temperature F ( C) Sensor Name Model No. of sensor Quantity of Sensor CLM97 CLM7 CLM7 Compressor temp sensor TKS9B Resistance (k ohm) (0) (0) (0) (0) (0) (0) (60) (70) (80) (90) Temperature F ( C)

16 . DIMENSIONAL DATA Outdoor Unit CLM97 -/6 -/ -/8-7/ ID:/ -ID:/6 / -7/6(900) ide tube service valve dia./8" (9.) Narrow tube service valve dia./" (6.) / -9/ -7/ -/ -7/6 -/6 -/ 9-/8(70) -9/(0) -9/ -7/ -/6 -/6 -/ -/ -/6 Unit: inch(mm) 6

17 Outdoor Unit CLM7 -/6 -/ -/8-7/ ID:/ -ID:/6 / -9/(0) -9/ -7/ -7/6(900) -/6 ide tube service valve dia./8" (9.) Narrow tube service valve dia./" (6.) / 9-/8(70) -9/ -7/ -/ -/ ide tube service valve dia./" (.70) -/6 -/ -/ -7/6 -/6 -/ -/ -/6 -/ Unit: inch(mm) 7

18 Outdoor Unit CLM7 -/6 -/ -/8-7/ ID:/ -ID:/6 / -7/6(900) ide tube service valve dia./8" (9.) Narrow tube service valve dia./" (6.) ide tube service valve dia./" (.70) / -9/ -7/8 -/ -/ -7/6 -/6 -/ -/ -9/(0) -9/ -7/ -/(890) -/6 -/6 -/ -/ -/6 -/ Unit: inch(mm) 8

19 . REFRIGERANT FLO DIAGRAM -. Refrigerant Flow Diagram Outdoor Unit CLM97 Indoor unit Outdoor unit ide tube O.D./8" O.D./8" O.D./8" Service valve on wide tube C B A Header Sub accumulator Main accumulator High pressure switch H.P. Compressor Narrow tube O.D./" O.D./" O.D./" Service valve on narrow tube CN BN AN Strainer Electric expansion valve M M M Header Heat exchanger Cooling cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min./6"(8 mm). Thickness: Min./6"(8 mm) Insulation Thickness: Min./6"(8 mm) CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. ide tube Narrow tube 9

20 Outdoor Unit CLM7 Indoor unit Outdoor unit ide tube O.D./8" O.D./8" O.D./8" O.D./" Service valve on wide tube D C B A Header Sub accumulator Main accumulator High pressure switch H.P. Compressor Narrow tube O.D./" O.D./" O.D./" O.D./" Service valve on narrow tube DN CN BN AN Strainer Electric expansion valve M M M M Header Heat exchanger Cooling cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min./6"(8 mm). Thickness: Min./6"(8 mm) Insulation Thickness: Min./6"(8 mm) CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. ide tube Narrow tube 0

21 Outdoor Unit CLM7 Indoor unit Outdoor unit ide tube O.D./8" O.D./8" O.D./" O.D./" Service valve on wide tube D C B A Header Sub accumulator Main accumulator High pressure switch H.P. Compressor Narrow tube O.D./" O.D./" O.D./" O.D./" Service valve on narrow tube DN CN BN AN Strainer Electric expansion valve M M M M Header Heat exchanger Cooling cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min./6"(8 mm). Thickness: Min./6"(8 mm) Insulation Thickness: Min./6"(8 mm) CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. ide tube Narrow tube

22 . PERFORMANCE DATA -. Temperature Charts --. Temperature Charts (CLM97) Outdoor Unit CLM97 Indoor Unit KMS077 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 88 (.) 7 (.) 60 (.) 6 (.0) 77 () Lo fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) () Operating current performance chart 0 (0) Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) () Indoor discharge air performance chart 0 (0) Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6t (7.m). If the tubing length is different, the performance chart will vary.

23 Outdoor Unit CLM97 Indoor Unit KMS097 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 88 (.) 7 (.) 60 (.) Lo fan Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) HH fan 6 (.0) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 6 Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Hi fan Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) HH fan 0 (0)

24 Outdoor Unit CLM97 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) (0.9) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) () Operating current performance chart 6 Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () HH fan 0 (0)

25 Outdoor Unit CLM97 Indoor Unit KMS87 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) Lo fan Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) HH fan (0.9) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 8 Lo fan Hi fan HH fan Operating current (A) 7 6 Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary.

26 --. Temperature Charts (CLM7) Outdoor Unit CLM7 Indoor Unit KMS077 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 88 (.) 7 (.) 60 (.) 6 (.0) 77 () Lo fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) () Operating current performance chart 0 (0) Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) () Indoor discharge air performance chart 0 (0) Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6t (7.m). If the tubing length is different, the performance chart will vary. 6

27 Outdoor Unit CLM7 Indoor Unit KMS097 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 88 (.) 7 (.) 60 (.) 6 (.0) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) () Operating current performance chart 6 Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. 7 Hi fan Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) HH fan 0 (0)

28 Outdoor Unit CLM7 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) (0.9) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) () Operating current performance chart 6 Lo fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. 8 Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () HH fan 0 (0)

29 Outdoor Unit CLM7 Indoor Unit KMS87 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) Lo fan Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) HH fan (0.9) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 8 Lo fan Hi fan HH fan Operating current (A) 7 6 Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) HH fan 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. 9

30 Outdoor Unit CLM7 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 60 (.) 6 (.0) Lo fan Hi fan HH fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) (0.9) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart Operating current (A) 9 Lo fan 8 7 HH fan Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 6 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. 0 Hi fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () HH fan 0 (0)

31 --. Temperature Charts (CLM7) Outdoor Unit CLM7 Indoor Unit KMS077 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) 90 (0.6) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) 0 (0) () Operating current performance chart Lo fan Hi fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) 0 (0)

32 Outdoor Unit CLM7 Indoor Unit KMS097 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) 90 (0.6) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart Lo fan Hi fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary.

33 Outdoor Unit CLM7 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) Lo fan Hi fan Hi fan HH fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 90 (0.6) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 6 Lo fan Hi fan Hi fan HH fan Operating current (A) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) () Indoor discharge air performance chart 0 (0) Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () Lo fan Hi fan Hi fan HH fan 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) 0 (0)

34 Outdoor Unit CLM7 Indoor Unit KMS87 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) Lo fan Hi fan 90 (0.6) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Operating current performance chart 9 Lo fan Hi fan Operating current (A) F (7 C) Indoor air temp. 86 F (0 C) 7 F ( C) 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () 86 (0) Lo fan Indoor air temp. 86 F (0 C) 9 () Outdoor air temperature F ( C) 80 F (7 C) 7 F ( C) Hi fan 0 (0) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary.

35 Outdoor Unit CLM7 Indoor Unit KMS7 Cooling Characteristics (RH : 6%, Indoor fan speed : High fan) (0V, 60Hz) () Low pressure performance chart Low pressure at wide tube service valve psig (MPaG) 7 (.) 6 (.0) 8 (0.8) 90 (0.6) 77 () 86 (0) Lo fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) 9 () Outdoor air temperature F ( C) Hi fan 0 (0) () Operating current performance chart Operating current (A) 0 9 Lo fan Indoor air temp. 86 F (0 C) 80 F (7 C) 7 F ( C) Hi fan 8 77 () 86 (0) 9 () Outdoor air temperature F ( C) 0 (0) () Indoor discharge air performance chart Indoor discharge air temperature F ( C) 68.0(0) 6.(8) 60.8(6) 7.().6() 0.0(0) 6.( 8) 77 () 86 (0) Outdoor air temperature F ( C) NOTE This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) The performance is for a tubing length of.6ft (7.m). If the tubing length is different, the performance chart will vary. Lo fan Indoor air temp. 86 F (0 C) 9 () 80 F (7 C) 7 F ( C) Hi fan 0 (0)

36 -. Cooling Capacity Outdoor Unit : CLM97 Indoor Unit : KMS097 Power Supply : 0V Single Phase 60Hz < Cooling Capacity > RATING CAPACITY: 9,700 BTU/h AIR FLO RATE: 88 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C).B. D.B (8.) (.9) (9.) (.0) (0.6) (6.) TC 9,800 9,00 8,0 7,770 6,890,90 7 (.) SHC 7,70 7,0 6,790 6,60 6,70, (.) SHC 9,800 9,00 8,0 7,770 6,890,90 (.0) 80 (6.7) SHC 9,800 9,00 8,0 7,770 6,890,90 8 (8.9) SHC 9,800 9,00 8,0 7,770 6,890,90 88 (.) SHC 9,800 9,00 8,0 7,770 6,890,90 TC 0,790 0,060 9,90 8,70 7,800 6,80 7 (.) SHC,0,870,0,60,00, (.) SHC 7,0 6,960 6,60 6,70,90,90 (7.) 80 (6.7) SHC 0,90 0,00 9,90 8,70 7,800 6,80 8 (8.9) SHC 0,790 0,060 9,90 8,70 7,800 6,80 88 (.) SHC 0,790 0,060 9,90 8,70 7,800 6,80 TC,790,00 0,0 # 9,700 8,70 7,70 7 (.) SHC 0,960 0,60 0,70 0,00 9,760 9, (.) SHC,870,700,60,90,80,0 (9.) 80 (6.7) SHC 6,960 6,790 6,0 6,70,90,90 8 (8.9) SHC 0,00 9,700 9,60 9,90 8,70 7,70 88 (.) SHC,790,00 0,0 9,700 8,70 7,70 TC,800,00,0 0,700 9,70 8,70 7 (.) SHC 7,60 7,90 6,80 6,670 6,0, (.) SHC 0,0 0,00 9,90 9,760 9,0 8,900 (.7) 80 (6.7) SHC,0,90,00,80,00,990 8 (8.9) SHC 6,0 6,70,90,760,0, (.) SHC 9,0 9,90 9,00 8,80 8,00 7,990 TC,690,90,080,600 0,90 8, (.) SHC 7,00 6,80 6,00 6,0 6,60,60 (.9) 80 (6.7) SHC 0,00 9,90 9,90 9,0 9,0 8,70 8 (8.9) SHC,90,80,670,00,60,60 88 (.) SHC 6,00,90,90,0,070,70 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) NOTE. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 F (6.7 C) D.B. / 67 F (9. C).B. : Outdoor Ambient Temp. 9 F ( C) D.B.. Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.. Above data represents the value when the operation frequency of a compressor is fixed. 6

37 Outdoor Unit : CLM7 Indoor Unit : KMS097 Power Supply : 0V Single Phase 60Hz < Cooling Capacity > RATING CAPACITY:,00 BTU/h AIR FLO RATE: 88 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C).B. D.B (8.) (.9) (9.) (.0) (0.6) (6.) TC,690,800,80,90,00 7,90 7 (.) SHC 0,0 9,870 9,60 9,00 8,00 6, (.) SHC,0,790,70,00,0 7,90 (.0) 80 (6.7) SHC,690,800,80,90,00 7,90 8 (8.9) SHC,690,800,80,90,00 7,90 88 (.) SHC,690,800,80,90,00 7,90 TC 6,80,900,90,90,0 7,700 7 (.) SHC 6,790 6,0,90,760,0, (.) SHC 9,700 9,60 9,00 8,670 8,60,90 (7.) 80 (6.7) SHC,960,0,00,760,0 7,700 8 (8.9) SHC,870,0,90,90,0 7, (.) SHC 6,80,900,90,90,0 7,700 TC 7,90 6,980,970 #,00,80 8,070 7 (.) SHC,60,00,00,0,80 9, (.) SHC 6,70,90,90,0,900,00 (9.) 80 (6.7) SHC 9,60 9,00 8,670 8,0 7,990,90 8 (8.9) SHC,0,00,90,0 0,900 8, (.) SHC,60,00,670,0,80 8,070 TC 8,980 8,00 6,990 6,00,00 8,80 7 (.) SHC 9,90 9,0 8,900 8,70 8,0, (.) SHC,670,0,80,60,0 8,900 (.7) 80 (6.7) SHC,760,0,070,70,0,990 8 (8.9) SHC 8,670 8,0 7,990 7,80 7,00, (.) SHC,90,0 0,900 0,70 0,0 7,990 TC 9,880 8,90 7,870 7,60,0 8, (.) SHC 9,070 8,70 8,90 8,0 7,0,70 (.9) 80 (6.7) SHC,60,80,70,00 0,60 8,60 8 (8.9) SHC,070,70,90,90,700,60 88 (.) SHC 8,60 7,80 7,70 7,00 6,60,60 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) NOTE. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 F (6.7 C) D.B. / 67 F (9. C).B. : Outdoor Ambient Temp. 9 F ( C) D.B.. Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.. Above data represents the value when the operation frequency of a compressor is fixed. 7

38 Outdoor Unit : CLM7 Indoor Unit : KMS097 Power Supply : 0V Single Phase 60Hz < Cooling Capacity > RATING CAPACITY: 0,600 BTU/h AIR FLO RATE:,77 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C).B. D.B (8.) (.9) (9.) (.0) (0.6) (6.) TC,70 0,000 8,70 8,00,960 6,690 7 (.) SHC,80,900,0,980,700 6, (.) SHC 9,70 9,00 8,0 8,00,960 6,690 (.0) 80 (6.7) SHC,70 0,000 8,70 8,00,960 6,690 8 (8.9) SHC,70 0,000 8,70 8,00,960 6, (.) SHC,70 0,000 8,70 8,00,960 6,690 TC,90,80 9,960 9,0,00 6,970 7 (.) SHC,00 0,0 9,870 9,60 7,0, (.) SHC,900,0,980,0,0 6,970 (7.) 80 (6.7) SHC 9,00 8,0 8,00 7,60,00 6,970 8 (8.9) SHC,90,80 9,960 9,0,00 6, (.) SHC,90,80 9,960 9,0,00 6,970 TC,790,0,70 # 0,600,770 7,00 7 (.) SHC 6,0,980,90,070,0 0, (.) SHC 0,0 9,870 9,0 9,80 6,670,0 (9.) 80 (6.7) SHC,0,980,0,00 0,780 7,00 8 (8.9) SHC 8,0 8,00 7,0 7,80,770 7,00 88 (.) SHC,0,980,70 0,600,770 7,00 TC,00,70,0,860,00 7,0 7 (.) SHC,0 0,90 0,90 0,90 7,70, (.) SHC,0,070,60,80,60 9,80 (.7) 80 (6.7) SHC 9,60 9,80 8,70 8,00,980,690 8 (8.9) SHC,0,070,60,60 9,870 7,0 88 (.) SHC 7,60 7,80 6,70 6,00,70 7,0 TC 6,00,70,70,90,0 7, (.) SHC 0,70 0,70 9,80 9,80 7,070,0 (.9) 80 (6.7) SHC,80,60,0,90,80 9,0 8 (8.9) SHC 8,90 8,00 8,00 7,80,90,0 88 (.) SHC,80,80,90,90 9,80 7,0 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) NOTE. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 F (6.7 C) D.B. / 67 F (9. C).B. : Outdoor Ambient Temp. 9 F ( C) D.B.. Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.. Above data represents the value when the operation frequency of a compressor is fixed. 8

39 -. Cooling Capacity (Low Ambient) Outdoor Unit : CLM97 Indoor Unit : KMS097 Power Supply : 0V Single Phase 60Hz < Cooling Capacity (Low Ambient) > RATING CAPACITY: 9,700 BTU/h AIR FLO RATE: 88 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C).B. D.B. 0 (-6.7) (-.9) (.7) (7.) (.8) TC 0,000 9,990 9,980 0,080 9,90 7 (.) SHC 7,60 7,60 7,60 7,60 7, (.) SHC 0,000 9,990 9,980 0,080 9,90 (.0) 80 (6.7) SHC 0,000 9,990 9,980 0,080 9,90 8 (8.9) SHC 0,000 9,990 9,980 0,080 9,90 88 (.) SHC 0,000 9,990 9,980 0,080 9,90 TC 0,0 0,60 0,0 0,70 0,60 7 (.) SHC,00,00,00,0, (.) SHC 7,0 7,0 7,0 7,0 7,0 (7.) 80 (6.7) SHC 0,0 0,0 0,0 0,0 0,0 8 (8.9) SHC 0,0 0,60 0,0 0,70 0,60 88 (.) SHC 0,0 0,60 0,0 0,70 0,60 TC 0,760 0,80,00,0,0 7 (.) SHC 0,60 0,60 0,60 0,790 0, (.) SHC,0,0,0,700,700 (9.) 80 (6.7) SHC 6,60 6,60 6,790 6,790 6,790 8 (8.9) SHC 9,0 9,700 9,700 9,870 9, (.) SHC 0,760 0,80,00,0,0 TC 0,90,080,00,890,960 7 (.) SHC 6,80 6,80 7,00 7,90 7, (.) SHC 9,760 9,760 9,90 0,00 0,00 (.7) 80 (6.7) SHC,80,00,00,90,90 8 (8.9) SHC,90,90 6,00 6,70 6,70 88 (.) SHC 8,80 8,80 9,00 9,90 9,90 TC 0,90,0,60,70, (.) SHC 6,60 6,0 6,0 6,670 6,670 (.9) 80 (6.7) SHC 9,0 9,0 9,90 9,760 9,760 8 (8.9) SHC,0,0,00,670, (.) SHC,0,0,0,90,760 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h). NOTE Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.. Above data represents the value when the operation frequency of a compressor is fixed. 9

40 Outdoor Unit : CLM7 Indoor Unit : KMS097 Power Supply : 0V Single Phase 60Hz < Cooling Capacity (Low Ambient) > RATING CAPACITY:,00 BTU/h AIR FLO RATE: 88 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C).B. D.B. 0 (-6.7) (-.9) (.7) (7.) (.8) TC,60,70,0,70,60 7 (.) SHC 0,00 0,0 0,0 0,0 0, (.) SHC,0,0,0,00,0 (.0) 80 (6.7) SHC,60,70,0,70,60 8 (8.9) SHC,60,70,0,70,60 88 (.) SHC,60,70,0,70,60 TC,690,760,960 6,0 6,0 7 (.) SHC 6,70 6,70 6,0 6,60 6, (.) SHC 9,60 9,60 9,60 9,0 9,0 (7.) 80 (6.7) SHC,0,0,0,60,60 8 (8.9) SHC,60,60,0,700, (.) SHC,690,760,960 6,0 6,0 TC,70,870 6,0 6,80 6,960 7 (.) SHC,00,00,670,80, (.) SHC,0,0,90,90,90 (9.) 80 (6.7) SHC 8,00 8,670 8,670 9,00 9,00 8 (8.9) SHC,90,90,760,90,90 88 (.) SHC,00,00,670,00,00 TC,80,70 6,0 7,0 7,0 7 (.) SHC 8,90 8,90 8,70 8,900 9, (.) SHC,00,70,60,990,990 (.7) 80 (6.7) SHC,90,60,70,070,070 8 (8.9) SHC 7,70 7,70 7,60 7,990 8,60 88 (.) SHC 0,90 0,60 0,70,070,070 TC,970,0 6,60 7,80 7, (.) SHC 7,60 7,0 7,870 8,0 8,90 (.9) 80 (6.7) SHC 0,60 0,60 0,960,00,70 8 (8.9) SHC,0,700,870,0,90 88 (.) SHC 6,0 6,60 6,960 7,00 7,00 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h). NOTE Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.. Above data represents the value when the operation frequency of a compressor is fixed. 0

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS1872 + C1872 + CL1872 KS2472 + C2472 + CL2472 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS1872 KS2472 Product

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: GRF188R5TAA GRF228R5TAA GRF228R7TAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. GRF188R5TAA 38.7107.083 GRF228R5TAA 38.7107.084 GRF228R7TAA 38.7107.085

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE726SCL AE752SCL AE71SCL3 AE735SCL AE752SCL3 AE100SCL3 AE764SCL3 AE125SCL3 SPLIT SYSTEM AIR CONDITIONER Model No. AE726SCL AE735SCL AE752SCL AE752SCL3 AE764SCL3

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT:. TRIAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.102. 0.8180.611.02 09/2012 IMPORTANT! Please read before installation This air conditioning

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AE22AH 387031006 AE28AH 387031007 AE38AH 387031008

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: DUAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.098 38.7107.103 38.7107.106 0.8180.597.03 09/2012 IMPORTANT! Please read before installation

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XHS1271 & PNR-XS1872 + CH1271 XHS1872 & PNR-XS1872 + CH1872 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS1271

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW22AL 387030005 AW28AL 387030006 AW38AL 387030007 AW42AL 387030094 0.8180.467.0

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XS171 & PNRXS187 + C171 XS171 & PNRXS187 + CL171 XS187 & PNRXS187 + CH187 XS187 & PNRXS187 + CL187 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL XH7R / CH7R, C7R XH7R / CH7R, C7R XH7R / CH7R, C7R TH7R / CH7R, C7R TH7R / CH7R, C7R TH7R / CH7R, C7R THH7R / CH7R THH7R / CH7R FILE NO. KH7R / CH7R, C7R KH07R / CH07R,

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF97R5IAA CAF98MR5IAA CAF127R5IAA CAF128MR5IAA CAF187R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. CAF97R5IAA CAF127R5IAA CAF187R5IAA CAF98MR5IAA CAF128MR5IAA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KE30NKU + CU-KE30NKU CS-KE36NKU + CU-KE36NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KE30NKU CS-KE36NKU Product Code No. 1 852 360 88

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL KHS308 + CH308 KHS368 + CH368 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KHS308 KHS368 Product Code No. 85 354 8 85 354 9 Outdoor

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513 TECHNICAL & SERVICE MANUAL SA 123A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-123A 1 851 006 95 Australia SA 123A REFERENCE NO. SM700513 IMPORTANT! Please Read Before

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No. 852 360 86

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XHS7 & PNRXS87 + CH7 XHS87 & PNRXS87 + CH87 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS7 (PNRXS87) XHS87 (PNRXS87)

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS0971 + C0971 + CL0971 KS1271 + C1271 + CL1271 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS0971 KS1271 Product

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A TECHNICAL & SERVICE MANUAL SA 183A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. SA-183A 1 851 006 96 Destination Australia SA 183A REFERENCE NO. SM700514 IMPORTANT! Please Read Before

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338 TECHNICAL & SERVICE MANUAL SA 128S5 FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-128S5-A 1 851 004 09 General (50Hz) & Europe SA 128S5 REFERENCE NO. SM700338 IMPORTANT!

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS - Wall-mount indoor unit - OPERATING LIMITS Cooling Maximum conditions Heating Maximum conditions Outdoor temperature : 122 F (50 C) D.B. Outdoor temperature : 75 F (24 C) D.B.

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF94R5IAA + GRF97R5I MCAF124R5IAA + GRF127R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF94R5IAA

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510 TECHNICAL & SERVICE MANUAL SA 93AH FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-93AH 1 851 006 97 Australia SA 93AH REFERENCE NO. SM700510 IMPORTANT! Please Read Before

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: ASR609CL ASR612CL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. ASR609CL 387006970 ASR612CL 387006971 0.8180.250.0 05/2002 IMPORTANT! Please read

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : KMS0772 FILE NO. KMS0972 KMS1272 KMS1872 KMS2472 Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF94R5 CAF124R5 SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. CAF94R5 387106979 CAF124R5 387106980 0.8180.361.0 07/2005 IMPORTANT! Please read before

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF88R5I + GRF86R5I MCAF48R5I + GRF46R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF88R5I MCAF88R5IAA

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : SAP-CMRVEH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 0.0kW Outdoor Model No. SAP-CMRVEH-F Product Code No. 8 8 SAP-CMRVEH

More information

TECHNICAL & SERVICE MANUAL SAP K181A + SAP C181A

TECHNICAL & SERVICE MANUAL SAP K181A + SAP C181A TECHNICAL & SERVICE MANUAL SAP K181A SAP K241A + SAP C181A + SAP C241A FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K181A S 1 852 068 06 SAP K241A

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE9NB4U & CZ-18BT1U CS-MKE12NB4U & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 9,000BTU / h 11,900BTU / h 17,500BTU

More information

TECHNICAL DATA & SERVICE MANUAL MULTI-SPLIT SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL MULTI-SPLIT SYSTEM AIR CONDITIONER TECHNICAL DATA & SERVICE MANUAL Outdoor Unit GR54M2C Indoor Unit MCA27MC (X2) MULTI-SPLIT SYSTEM AIR CONDITIONER Indoor Unit Outdoor Unit MCA27MC GR54M2C 0.8180.195.0 04/2001 IMPORTANT! Please Read Before

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU / h 11,900BTU / h 17,500BTU / h 24,200BTU / h

DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU / h 11,900BTU / h 17,500BTU / h 24,200BTU / h AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKS7NKU CS-MKS9NKU CS-MKS12NKU CS-MKS18NKU CS-MKS24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL AWR222CLE - AER222SC AWR222CLE - AER222SC3 SPLIT SYSTEM AIR CONDITIONER 0.8180.076.0 03/00 Important! Please Read Before Starting This air conditioning system meets strict safety

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP K303A + SAP C303A FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K303A A 1 852 098 83 Outdoor Model No.

More information

SPLIT SYSTEM AIR CONDITIONER

SPLIT SYSTEM AIR CONDITIONER TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MRAF99R5IAA MRAF129R5IAA MPAF99R5IAA MPAF129R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MRAF99R5IAA 38.7104.065 MRAF129R5IAA 38.7104.062 MPAF99R5IAA

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Solenoid Valve Kit For 3WAY VRF System CZ-PXXXHR3 () IMPORTANT! Please Read Before Starting This solenoid Valve kit must be installed by the sales dealer or installer. This information

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL HEAT PUMP MODELS INDOOR UNIT: MPAF188R5TAA MPAF228R5TAA COOLING MODELS MPAF188C5TAA MPAF228C5TAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MPAF188R5TAA 38.7104.033

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K301AH + SAP C301AH FILE NO. SAP K301AH SAP C301AH REFERENCE NO.

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K301AH + SAP C301AH FILE NO. SAP K301AH SAP C301AH REFERENCE NO. TECHNICAL & SERVICE MANUAL SAP K301AH + SAP C301AH FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K301AH S 1 852 071 34 Outdoor Model No. Product Code

More information

TEST RUN SERVICE MANUAL

TEST RUN SERVICE MANUAL TEST RUN SERVICE MANUAL Model No. Outdoor Unit ME Class Model Name HP U-MEE 0HP U-0MEE HP U-MEE HP U-MEE HP U-MEE HP U-MEE 0HP U-0MEE U-MEEE U-0MEEE U-MEEE U-MEEE U-MEEE U-MEEE U-0MEEE Indoor Unit Class

More information

AUTO COOL DRY FAN SPEED AIR SWING OFF ON TIMER TIMER OFF/ON FAN SPEED MODE TEMP AIR SWING TIMER ON SET OFF CANCEL AC RC SET CHECK CLOCK RESET

AUTO COOL DRY FAN SPEED AIR SWING OFF ON TIMER TIMER OFF/ON FAN SPEED MODE TEMP AIR SWING TIMER ON SET OFF CANCEL AC RC SET CHECK CLOCK RESET AUTO COOL DRY MODE TIMER ON OFF TIMER OFF/ON TEMP ON TIMER FAN SPEED AIR SWING SET 1 2 3 FAN SPEED AIR SWING OFF CANCEL AC RC SET CHECK CLOCK RESET Order No: PAPAMY1611008CE Indoor Unit CS-MPS9SKH CS-MPS12SKH

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : MCAF78MR5I MCAF98MR5I MCAF128MR5I MCAF188R5I MCAF248R5I FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG18KLCA ASYG24KLCA OUTDOOR AOYG18KLTA AOYG24KLTA DR_AS069EF_01 2018.03.16 Notices: Product specifications and design are subject to

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications

More information

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A.

More information

MULTI-SPLIT SYSTEM AIR CONDITIONER

MULTI-SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP KM97AHA ( 2) + SAP CM1827AHA FILE NO. Destination: Australia MULTI-SPLIT SYSTEM AIR CDITIER Indoor Model No Product Code No. Outdoor Model No. Product Code No. SAP KM97AHA

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH Revision D: Capacity corrections have been corrected [7-1. 2), 3)]. OBH684 REVISED EDITION-C is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH684 REVISED EDITION-D Models MUZ-FH06NA MUZ-FH09NA

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.2 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 05-355 KMS0772_indoor 3/16/06 5:27 PM Page a INSTALLATION INSTRUCTIONS Inverter Split System Air Conditioner COOL/ DRY Model This air conditioner uses the new refrigerant R410A. For Indoor Unit Contents

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA 0.8180.472.0 07/2005 Page 1. SPECIFICATIONS 3 1-1 Unit Specifications 3 1-2 Major Component Specifications 4 2. DIMENSIONAL DATA 6 2-1 Unit Dimensions 6 3. ELECTRICAL

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

Destination Europe WARNING

Destination Europe WARNING Order No: PAPAMY1406071CE Indoor Unit CS-E12QD3EAW Outdoor Unit CU-E12QD3EA Destination Europe Please file and use this manual together with the service manual for Model No. CU-2E15PBE CU-2E18PBE CU-3E18PBE

More information

TECHNICAL & SERVICE MANUAL WIRED REMOTE CONTROLLER STK-RCS-7TWSUA FILE NO. Product Code No Model No. STK-RCS-7TWSUA

TECHNICAL & SERVICE MANUAL WIRED REMOTE CONTROLLER STK-RCS-7TWSUA FILE NO. Product Code No Model No. STK-RCS-7TWSUA TECHNICAL & SERVICE MANUAL STK-RCS-7TWSUA FILE NO. Destination: North America WIRED REMOTE CONTROLLER Model No. STK-RCS-7TWSUA Product Code No. 1 852 353 85 REFERENCE NO. SM700799 Important! Please Read

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

Wall Mounted Split Systems

Wall Mounted Split Systems MWM - 2005 Wall Mounted Split Systems Models: MWM 007F/FR MWM 010F/FR MWM 015F/FR MWM 020F/FR MWM 025F/FR MWM 030F/FR Contents Features... 1 Nomenclature... 2 Specifications... 3 Performance Table... 11

More information

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8.

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8. Submittal Data: CROWN09HP230V1B Superior Performance in Extreme Temperature 9,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule

More information

YC ON-OFF SERIES. Service Manual

YC ON-OFF SERIES. Service Manual YC ON-OFF SERIES Service Manual CONTENTS 1. Precaution... 3 1.1 Safety Precaution... 3 1.2 Warning... 3 2. Model Lists... 6 3. Dimension... 7 3.1 Indoor Unit... 7 3.2 Outdoor Unit... 11 4. Refrigerant

More information

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH MHNCCW-04-01 (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH Rev. 1.2 HVAC Guide Specifications Chilled and Hot Water Fan Coil 4-Pipe Nominal Size: 12,000

More information

SERVICE MANUAL CLASSIC 10 SERIAL NUMBER FROM FEBRUARY 2011 (0211) TO PRESENT. DocID: 00G00089E

SERVICE MANUAL CLASSIC 10 SERIAL NUMBER FROM FEBRUARY 2011 (0211) TO PRESENT. DocID: 00G00089E SERVICE MANUAL CLASSIC 10 SERIAL NUMBER FROM FEBRUARY 2011 (0211) TO PRESENT DocID: 00G00089E 2012 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL TECHNICAL & SERVICE MANUAL INDOOR UNIT: MCAF94MR5IAA MCAF124MR5IAA MCAF184MR5IAA MCAF244MR5IAA NOV.2003 Destination: General area (50Hz) Europe (50Hz) Australia (50Hz) General area (60Hz) DC INVERTER MULTI-SYSTEM

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System Submittal Data: Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES

More information

INVERTER SPLIT SYSTEM AIR CONDITIONER

INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV91EH + SAP-CRV91EH FILE NO. INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. Outdoor Model No. Product Code No. Destination SAP-KRV91EH 1 852 065

More information

2-WAY ECO-i MULTI SYSTEM

2-WAY ECO-i MULTI SYSTEM SERVICE MANUAL 2-WAY ECO-i MULTI SYSTEM CHDX07263 CHDXR07263* CHDX09663 CHDXR09663* Outdoor Units Class 72 96 C ECO-i W-2WAY CHDX07263 CHDX09663 CHDXR07263* CHDXR09663* Refrigerant R410A is used in the

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

SUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP

SUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP VEP075N432G Job Name: Location: Schedule No.: System Designation: Engineer: Architect: Date: For: Reference Approval Review Construction FEATURES Two-pipe heat pump Access to electrical box for ease of

More information

INSTALLATION INSTRUCTIONS R 410A

INSTALLATION INSTRUCTIONS R 410A R 410A Ductless Split System Air Conditioner and Heat Pump MODELS: DLC4(A/H) Outdoor, DLF4(A/H) SIZES: 9K, 12K, 18K, 24K, 30K, and 36K NOTE: Read the entire instruction manual before starting the installation.

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To Submittal Data: Innovative Ductless solutions 12,000 BTU/H (208/230V) Wall Mounted Heat Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES

More information

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System Submittal Data: Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES -Compact and Quiet Design -High Efficiency DC Inverter Technology -Wireless Remote

More information

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To Submittal Data: Innovative Ductless solutions 24,000 BTU/H (208/230V) Wall Mounted Heat Pump System Job Name Location Date Purchaser Engineer Submitted To For Unit Designation Schedule No. GENERAL FEATURES

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2 INVERTER MULTI AIR CONDITIONER CASSETTE type Models Indoor unit AUY12LBAB AUY14LBAB Outdoor unit AOY18LMAK2 CONTENTS SPECIFICATIONS..................... 1 OUTLINE AND DIMENSIONS........... 2 REFRIGERANT

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA-

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA- TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA- SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. MCAF72R5TA- 387104015 MCAF92R5TA- 387104016 MCAF122R5TA- 387104017

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LMCA AS G09LMCA AS G12LMCA AS G14LMCA OUTDOOR AO G07LMCA AO G09LMCA AO G12LMCA AO G14LMCA 1. INDOOR UNIT : AS G07LMCA AS G09LMCA

More information

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E Revision E: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH629 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-E Models

More information

7/8 NO NO NO PROPELLER DIRECT / /230/1/ SPINE FIN /8 8 LBS., 0 OZ. YES 7/8 3/8

7/8 NO NO NO PROPELLER DIRECT / /230/1/ SPINE FIN /8 8 LBS., 0 OZ. YES 7/8 3/8 Service Facts Split System Cooling 4TTR3060D1000A CAUTION IMPORTANT This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC Revision F: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH590 REVISED EDITION-E. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED EDITION-F

More information

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

TABLE OF CONTENTS. Air Conditioner

TABLE OF CONTENTS. Air Conditioner Order No. MAC0804027A2 Air Conditioner CS-E9GFEW-2 CU-E9GFE-2 CS-E12GFEW-2 CU-E12GFE-2 CS-E18GFEW-2 CU-E18GFE-2 CU-2E15GBE CU-3E18EBE CU-3E23CBPG CU-4E27CBPG Please file and use this manual together with

More information

208/230/1/ CLIMATUFF /230/1/ YES NO NO PROPELLER 23-1 DIRECT / /230/1/ SPINE FIN

208/230/1/ CLIMATUFF /230/1/ YES NO NO PROPELLER 23-1 DIRECT / /230/1/ SPINE FIN Service Facts Split System Cooling 4TTB3030D1000A IMPORTANT This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit. Please

More information

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH MHCCW-10-05 Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH Rev. 1.21 HVAC Guide Specifications Chilled Water Fan Coil with Electric Heat 2-Pipe Nominal Size:

More information

HEAT PUMP INSTALLATION MANUAL

HEAT PUMP INSTALLATION MANUAL DUCTLESS INVERTER HEAT PUMP INSTALLATION MANUAL Models: TERRA09HP230V1A TERRA12HP230V1A TERRA18HP230V1B TERRA24HP230V1B Thank you for choosing a Gree Terra Ductless Heat Pump for your customer. Please

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS

More information

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH MHCCW-06-00 Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH Rev. 1.21 HVAC Guide Specifications Chilled or Hot Water Fan Coil 2-Pipe Nominal Size: 18,000 BTUH

More information

Air Conditioner CONTENTS

Air Conditioner CONTENTS ORDER NO. MAC0509068C2 Air Conditioner CS-F24DD1E5 CU-B24DBE5 CS-F28DD1E5 CU-B28DBE5 CS-F28DD1E5 CU-B28DBE8 CS-F34DD1E5 CU-B34DBE5 CS-F34DD1E5 CU-B34DBE8 CS-F43DD1E5 CU-B43DBE8 CS-F50DD1E5 CU-B50DBE8 CONTENTS

More information

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA ARGO 245C / 3SC Cooling only model ARGO 235H / 3HP Heat pump model 0.8180.405.2 09/2006 Table of contents Page A SPECIFICATIONS 1) Unit specifications 3

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR ASU9RL2 ASU12RL2 OUTDOOR AOU9RL2 AOU12RL2 1.INDOOR UNIT : ASU9RL2 ASU12RL2 DTR_AS072E_01 2012.11.02 1. INDOOR UNIT CONTENTS 1. FEATURE...

More information