Significance of the Construction Products Regulation, including for data centers WHITEPAPER

Size: px
Start display at page:

Download "Significance of the Construction Products Regulation, including for data centers WHITEPAPER"

Transcription

1 Significance of the Construction Products Regulation, WHITEPAPER

2 The aim of the Construction Products Regulation is to protect people in buildings against the consequences of a fire. The priorities in the event of a fire are: To save lives, restrict the fire and minimize resulting loss and damage. The growth of digitalization means that the density of cables in buildings is constantly increasing. In general, the quantity of flammable materials in modern buildings is increasing. As a result, the average time from the start of the fire through to the ignition of flue gases (pyrolysis gases) has reduced from approximately 15 minutes in 1950 to only some 3 minutes in This means that the time available to escape from a building has been dramatically reduced. Consequently, it is necessary to ask how it is possible to prevent the increasing quantities of cables having an excessively negative impact in the event of fire and what risks lie dormant in any existing old cabling? To answer these questions, it is necessary to examine three aspects: First of all, cables must not contribute to the propagation of the fire and, in particular, the fire must not spread from one floor to the next and no falling or dripping elements should contribute to the propagation of the fire. Second, smoke and toxic gases must be avoided in order to ensure that buildings can be evacuated safely and that the emergency services are able to intervene. And, finally, reconstruction is necessary after a fire. Here, it is necessary to remember that corrosive combustion gases combined with the water used to extinguish the fire form corrosive acids that may be dissipated far from the source of the fire and may attack all metallic objects (e.g. electronic components, construction steel, etc.) and damage or destroy these. The EU Construction Products Regulation The priorities set out above, starting with the saving of lives, together with the consequences that may arise have been incorporated in the new EU Construction Products Regulation. In 2011, the EU issued regulation 305/2011 (Construction Products Regulation) that introduced a uniform classification for improving safety in buildings. As of July 1, 2013, this Construction Products Regulation has been binding for all Member States and replaces the directive on construction products (89/106/EEC). The Construction Products Regulation makes it possible to compare the fire protection properties of products. In this Construction Products Regulation, cables and lines including data cables are also for the first time declared, at the European level, to be construction products with regard to the requirements for fire prevention. The scope of the Regulation includes cables and lines that are permanently installed in buildings and whose performance has an impact on the basic requirements placed on construction works. Author: Stefan Wiener Page 2 of 10

3 The EU Construction Products Regulation also defines the conditions for CE labelling and demands a manufacturer's declaration of performance concerning the protection-related objectives of the derived product characteristics, such as fire safety (propagation of flames, generation of heat, generation of smoke, formation of acids, burning droplets) and the absence of hazardous contents. In addition, the Construction Products Regulation defines a system that makes it possible to ensure conformity on a permanent basis. The conditions for CE labelling and the requirements placed on the reaction to fire of cables and lines are set out in, EN50575:2014 which has been in force since June 10, As of this date, it has been possible for cables and lines to be marked with a CE label as set out in the Construction Products Regulation and to be accompanied by a declaration of performance. As of July 1, 2017, this is mandatory for all manufacturers. Author: Stefan Wiener Page 3 of 10

4 The Declaration of Performance testifies to adherence to the defined fire classifications and is therefore a prerequisite for the use of the cables in the EU Member States. However, all Member States are required and obliged to define the minimum required fire protection classification for a very wide range of applications themselves. As a result, the requirements placed on products for one and the same building type may be very different in the various European countries. Consequently, planners must check local regulations carefully when entering into projects, must observe these and include them in any requests for proposals. Author: Stefan Wiener Page 4 of 10

5 Euroclass assignment of the fire reaction of cables The CPR assigns the fire reaction of cables to various Euroclasses. EN :2014 defines 7 basic Euroclasses. These range from the class A ca "nonflammable" to F ca "slightly flammable". A through F are valid for all construction products, ca stands for cable. These Euroclasses should also not be confused with the requirement that cables should be able to resist fire for a certain length of time. It seems unlikely that it will be possible to develop cables that comply with A ca. In sequence, B1, B2, C and D, simply differ in their increasingly less stringent requirements, as tested in accordance with the criteria set out in EN Class E ca cables simply fulfill the minimum requirements of EN but not the requirements relating to smoke and acid gas generation as specified in EN Euroclass F applies to flammable cables and includes many outdoor cables. Author: Stefan Wiener Page 5 of 10

6 Additional classifications In the additional classification, "s" stands for smoke/smoke generation. "d" stands for droplets or the formation of droplets and "a" for acid or the release of acid gas. Author: Stefan Wiener Page 6 of 10

7 The monitoring of compliance is defined in detail in EN Class F products are declared by the manufacturer. Class D or E products must be subjected to type testing by a notified body. Products of class A though C are subject to an additional, regular factory audit with sampling, performed by an independent institute; this represents a so-called 1+ evaluation and certification. As already mentioned, all Member States are required and obliged to define the minimum required fire protection classification for a very wide range of applications themselves. Some organizations and even international associations have since issued their own recommendations some of which go far beyond the legal minimum requirements. The highest priority is to save human lives in the event of a fire. However, buildings can differ greatly in their construction and use and the associated safety requirements differ accordingly. Thus, for example, in a free-standing detached house, there is usually more than one escape route, with the result that the top priority, "saving human lives", cannot be significantly improved through the use of high-quality safety cables. The situation is very different in buildings with very high frequentation levels, for example in department stores/retail outlets/event spaces or buildings frequented by the public. In such cases, it is necessary to create time for possible evacuation activities. The highest safety level applies to buildings that accommodate people who are not able to escape themselves due to illness or age. Ultimately, the fire protection class for buildings is specified by the responsible fire protection authority and it is essential to take account of this during planning. To improve the level of safety in buildings with very high safety requirements, in particular in the field of the emergency services, it is recommended to use fire safety cables of class B2 ca or C ca. Cables with isolation and functional integrity are not currently affected by the CPR. These will be dealt with in a future harmonized standard. Author: Stefan Wiener Page 7 of 10

8 Special considerations Connecting cables (patchcords, trunk cables) As mentioned above, the EU Construction Products Regulation applies to cables and lines that are permanently installed in structures or parts thereof. This also includes communication cables and lines that are installed in buildings, even if they are installed under render or in ducts. Cables that are not permanently installed in data centers, for example, and that are used flexibly as connecting cables between devices and connection panels and that can be removed do not fall within the definition set out in the Construction Products Regulation. By contrast, cables that are temporarily installed for an undefined period do fall within the scope of the CPR (cables that are assembled at one or both ends and are fixed). One special feature here, however, is that pre-assembled cables may not be identified with the CE label and associated CPR label promoted in the CPR because the connectors are not subject to EN However, this does not release the parties involved from the responsibility for using the CPR-authorized cables specified in the project. Author: Stefan Wiener Page 8 of 10

9 Recommendation on the fire protection class to be used in data centers / server rooms Data centers generally contain a high density (in terms of investment) of devices and hardware relative to the volume of the room. Even if there is no threat to human life, a fire almost inevitably represents a catastrophe for the data center. Consequently, it is necessary to take the utmost care to ensure that no fires occur and employ intelligent early fire detection and fire prevention mechanisms, i.e. take measures to ensure that no fire can break out, for example by means of fire detection through the early recognition of thermolysis gases that are released even before the fire itself starts. However, should such a fire break out then it will be extinguished immediately either by means of, for example, inert gas extinguishing equipment (extinguishing without leaving deposits) or, more generally, through oxygen reduction involving the lowest possible level of material damage. In the light of this fact, the use of very high-quality and very expensive fire protection cables is not absolutely essential and, in the light of cost-benefit considerations, we therefore recommend the use of class D ca cables. Author: Stefan Wiener Page 9 of 10

10 About Rosenberger OSI: Since 1991, Rosenberger Optical Solutions & Infrastructure (Rosenberger OSI) has been an expert in innovative fiber optic cabling infrastructure and service solutions for Datacom, Telecom and Industrial. The products and services can be found wherever largest amounts of data have to be transferred quickly and securely. In addition to the development and production of a broad portfolio of fiber optic and copper cabling systems, Rosenberger OSI also offers a variety of services such as planning, installation and maintenance of cabling infrastructure. Rosenberger OSI employs about 600 people in Europe and has been a part of the globally operating Rosenberger Group since 1998, a worldwide leading provider of high-frequency-, high-voltage-, and fiberoptic-connection solutions headquartered in Germany. For further information, please visit: Rosenberger-OSI GmbH & Co. OHG Optical Solutions & Infrastructure Endorferstr Augsburg GERMANY Phone: info-osi@rosenberger.com Rosenberger is a registered trademark of Rosenberger Hochfrequenztechnik GmbH & Co. KG. All rights reserved. Rosenberger 2017 Transfer to third party only by authority of Rosenberger-OSI GmbH & Co. OHG- All rights reserved Created: Valid sincet:

DID YOU GET USED TO THE NEW CPR? HERE S A QUICK REVIEW!

DID YOU GET USED TO THE NEW CPR? HERE S A QUICK REVIEW! June 2018 DID YOU GET USED TO THE NEW CPR? HERE S A QUICK REVIEW! How to recognize compliant cables? The new CPR defines the rules and the requirements of construction products to be manufactured, distributed

More information

Belcom Cable excellence engineered through quality. CPR Construction Products Regulation

Belcom Cable excellence engineered through quality. CPR Construction Products Regulation CPR Construction Products Regulation Index Construction Products Regulation... 3 What is the Construction Products Regulation (CPR)... 4 What is the objective of the CPR... 4 Who does the application of

More information

CONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE

CONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE CONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE Carol Harris, EMEA Product Manager WHITE PAPER Molex Connected Enterprise Solutions EXECUTIVE SUMMARY Combustible construction materials

More information

Üntel is ready for CPR

Üntel is ready for CPR 2016 Üntel is ready for CPR Hakan Kubas Marketing Manager 01.11.2016 Construction Products Regulation What is the CPR? The Construction Products Regulation (CPR) lays down conditions for the placing or

More information

Construction Products Regulation (CPR) and BS 6701

Construction Products Regulation (CPR) and BS 6701 Construction Products Regulation (CPR) and BS 6701 What you need to know Nancy De Clerck Product Manager Nexans Cabling Solutions Construction Products Regulation (CPR) Scope Performance classifications

More information

Europacable FAQ on CPR Status: 26/01/17

Europacable FAQ on CPR Status: 26/01/17 Europacable FAQ on CPR Status: 26/01/17 DISCLAIMER This FAQ document reflects the best knowledge of industry experts across Europe and the state of the art at the time of writing (July 2016). It represents

More information

YOUR GUIDE TO UNDERSTANDING CPR

YOUR GUIDE TO UNDERSTANDING CPR YOUR GUIDE TO UNDERSTANDING CPR WITH EXCEL NETWORKING SOLUTIONS ISSUE 2 UPDATED JANUARY 2018 WWW.EXCEL-NETWORKING.COM CONTENTS What is CPR? When will this happen? Why the update? Which products are affected?

More information

White paper. Construction Product Regulations* by Multimedia Connect. Which cables are concerned by these new regulations?

White paper. Construction Product Regulations* by Multimedia Connect. Which cables are concerned by these new regulations? White paper by Multimedia Connect Construction Product Regulations* We are all concerned by the safety of persons and property. In 2010, 8 million fires were recorded: they are estimated to have caused

More information

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Metal faced sandwich panels with plastic foam cores - a challenge to fire safety by Gordon Cooke Confusion, misleading

More information

COMMISSION DELEGATED REGULATION (EU) /... of

COMMISSION DELEGATED REGULATION (EU) /... of EUROPEAN COMMISSION Brussels, 1.7.2015 C(2015) 4394 final COMMISSION DELEGATED REGULATION (EU) /... of 1.7.2015 on the classification of the reaction to fire performance of construction products pursuant

More information

Improving electrical cable safety in Europe

Improving electrical cable safety in Europe Improving electrical cable safety in Europe The European Association of Wire and Cable Manufacturers and National Associations Presentation to the European Fire Safety Alliance Thomas Neesen, Secretary

More information

Construction Products Regulation (CPR) and cables. British Cables Association Guidance to Specifiers

Construction Products Regulation (CPR) and cables. British Cables Association Guidance to Specifiers Construction Products Regulation (CPR) and cables British Cables Association Guidance to Specifiers 1 Outline In January 2017 BCA issued its Guidance to Specifiers. A key consideration at the time was

More information

UK Direction BS7671 BS 8492 BS /01/2018

UK Direction BS7671 BS 8492 BS /01/2018 UK Direction BS7671 BS 8492 BS6701 23/01/2018 BS7671:2015 The 17 th Edition Revision 3 details the requirements for an improved fire rating on all cables within a fire route. 422.2.1 In conditions BD2

More information

Construction Products Regulation (CPR)

Construction Products Regulation (CPR) www.excel-networking.com S2 Construction Products Regulation (CPR) Section 2 In this Section: Pages What is CPR? 21 When will this happen? 21 Why the update? 21 Which products are affected? 21 Who is affected?

More information

DUST EXPLOSION CODES AND STANDARDS: Ensuring Regional Compliance and Global Consistency

DUST EXPLOSION CODES AND STANDARDS: Ensuring Regional Compliance and Global Consistency DUST EXPLOSION CODES AND STANDARDS: Ensuring Regional Compliance and Global Consistency TABLE OF CONTENTS Introduction Why are dust threats so serious? Key Points: NFPA 652 Key Points: ATEX What do you

More information

BUSINESS PLAN CEN/TC 239 RESCUE SYSTEMS EXECUTIVE SUMMARY

BUSINESS PLAN CEN/TC 239 RESCUE SYSTEMS EXECUTIVE SUMMARY Page: 1 BUSINESS PLAN CEN/TC 239 RESCUE SYSTEMS EXECUTIVE SUMMARY Business Environment CEN/TC 239 is engaged in the standardization of ambulances as emergency medical vehicles and/or crafts and their associated

More information

BUSINESS PLAN CEN/TC 305 POTENTIALLY EXPLOSIVE ATMOSPHERES EXPLOSION PREVENTION AND PROTECTION EXECUTIVE SUMMARY

BUSINESS PLAN CEN/TC 305 POTENTIALLY EXPLOSIVE ATMOSPHERES EXPLOSION PREVENTION AND PROTECTION EXECUTIVE SUMMARY BUSINESS PLAN CEN/TC 305 POTENTIALLY EXPLOSIVE ATMOSPHERES EXPLOSION PREVENTION AND PROTECTION CEN/TC 305 Business Plan Page: 1 Business environment, benefits and priorities EXECUTIVE SUMMARY CEN/TC 305

More information

Responsible Care Product Stewardship for Refrigerants

Responsible Care Product Stewardship for Refrigerants 1 ABSTRACT Responsible Care Product Stewardship for Refrigerants Christoph Meurer; Ewald Preisegger Solvay Fluor und Derivate GmbH Hans-Böckler-Allee 20 30161 Hannover Germany Product stewardship summarizes

More information

Seat Ventilation offers an extensive range of ATEX certified products and is undertaking great efforts to extend this range even further.

Seat Ventilation offers an extensive range of ATEX certified products and is undertaking great efforts to extend this range even further. ATEX SOLUTIONS In order to apply a single level for health and safety requirements and to overcome barriers of trade within Europe, national regulations for explosion prevention were harmonized in 1975

More information

Fire protection for emergency power supply

Fire protection for emergency power supply Fire protection for emergency power supply Protection of IT infrastructure, data and business continuity For data centers emergency power supply (e.g. generators or battery/ups rooms) is mission critical

More information

TFI Report Classification

TFI Report Classification TFI Report Classification of the Reaction to Fire according to EN 13501-1:2010 Customer Stuttgarter Straße 75 74321 Bietigheim-Bissingen GERMANY Product resilient floor covering Product 1: Scala 55 Connect

More information

Centexbel. General certification regulations. Construction products

Centexbel. General certification regulations. Construction products Centexbel Scientific and Technical centre of the Belgian Textile Industry General certification regulations Construction products 22/03/17 blz. 1 / 8 Contents 1 Introduction 3 2 Object 3 3 Definitions

More information

Erik Leider Project Engineer Hazardous Locations, Gas & Oil Underwriters Laboratories

Erik Leider Project Engineer Hazardous Locations, Gas & Oil Underwriters Laboratories Hazardous Locations: Understanding the Basics of Global Compliance Requirements Erik Leider Project Engineer Hazardous Locations, Gas & Oil Underwriters Laboratories DISCLAIMER/ TERMS OF USE: THE INFORMATION

More information

BUSINESS PLAN CEN/TC 79 RESPIRATORY PROTECTIVE DEVICES EXECUTIVE SUMMARY

BUSINESS PLAN CEN/TC 79 RESPIRATORY PROTECTIVE DEVICES EXECUTIVE SUMMARY CEN/TC 79 Business Plan Page: 1 BUSINESS PLAN CEN/TC 79 RESPIRATORY PROTECTIVE DEVICES EXECUTIVE SUMMARY Scope To prepare European Standards for respiratory protective devices (RPD) for work and rescue

More information

The PPE Directive and the PPE Regulation

The PPE Directive and the PPE Regulation PPE Regulation (EU) 2016/425 The PPE Directive and the PPE Regulation The history and future of PPE Certification A whitepaper The current PPE Directive at a glance The PPE Directive was one of the first

More information

Your Key to achieving C.E Marking Compliance

Your Key to achieving C.E Marking Compliance Your Key to achieving C.E Marking Compliance As of the 1 st July 2013 The Construction Products Regulation 2011 contains clauses relating to C E marking of products. This will therefore mean that a CE

More information

NON-FLAMMABLE WALL COVERING SYSTEM FOR INNOVATIVE FIRE PROTECTION

NON-FLAMMABLE WALL COVERING SYSTEM FOR INNOVATIVE FIRE PROTECTION SYSTEX X ACTIVE FIREPROTECT NON-FLAMMABLE WALL COVERING SYSTEM FOR INNOVATIVE FIRE PROTECTION THE INNOVATIVE GLASS FABRIC FOR WALLS AND CEILINGS 2 SPREADS LIKE WILDFIRE EVERY SECOND COUNTS Of course, we

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

White Paper. Keeping up with compliance: Escape doors standards. The global leader in door opening solutions

White Paper. Keeping up with compliance: Escape doors standards. The global leader in door opening solutions White Paper Keeping up with compliance: Escape doors standards The global leader in door opening solutions Introduction When it comes to access control, there is no greater responsibility than specifying

More information

Frequently Asked Questions on the Construction Products Regulation (CPR) - Enterprise and Industry

Frequently Asked Questions on the Construction Products Regulation (CPR) - Enterprise and Industry 1. Must a construction product bear the CE marking after 30/06/2013? After 30/06/2013, in order to sell a construction product in the European Union (EU) the manufacturer has the obligation to issue a

More information

Harmonisation and equivalence of reaction-to-fire performance classification in Europe: a small-scale desk-based study

Harmonisation and equivalence of reaction-to-fire performance classification in Europe: a small-scale desk-based study Harmonisation equivalence of reaction-to-fire performance classification in Europe: a small-scale desk-based study Prepared for: ADCAS 2 Waltham Court, Milley Lane, Hare Hatch, Reading, Berkshire RG10

More information

CE MARKING OF WOOD-BASED PANELS

CE MARKING OF WOOD-BASED PANELS 28 Market Place Grantham Lincolnshire NG31 6LR Tel: 00 44 (0) 1476 563707 Fax: 0044 (0) 1476 579314 e-mail: wpif.panelboards@virgin.net WOOD PANEL INDUSTRIES FEDERATION CE MARKING OF WOOD-BASED PANELS

More information

TFI Report Classification

TFI Report Classification TFI Report Classification of the Reaction to Fire according to EN 13501-1:2010 Customer Unilin bvba, Division Flooring Ooigemstraat 3 8710 Wielsbeke BELGIUM Product wall covering Wall covering This report

More information

Council Directive 93/68/EEC of 22 July 1993 amending Directives

Council Directive 93/68/EEC of 22 July 1993 amending Directives Council Directive 93/68/EEC of 22 July 1993 amending Directives 87/404/EEC (simple pressure vessels), 88/378/EEC (safety of toys), 89/106/EEC (construction products), 89/336/EEC (electromagnetic compatibility),

More information

9 Standards, Regulations and Authorities

9 Standards, Regulations and Authorities 9 9.1 Summary...283 9.2 Basics...284 9.3 Standards and how to Secure Adherence to Standards...285 9.3.1 Types of Standards...285 9.3.2 Hierarchy of Standards...285 9.3.3 Proof...286 9.3.4 Overview of the

More information

ETICS and the EU Internal Market The European framework. G. Katsarakis European Commission, DG GROWTH Unit C-1: Clean technologies and products

ETICS and the EU Internal Market The European framework. G. Katsarakis European Commission, DG GROWTH Unit C-1: Clean technologies and products ETICS and the EU Internal Market The European framework G. Katsarakis European Commission, DG GROWTH Unit C-1: Clean technologies and products 1 THE EU CONSTRUCTION SECTOR The importance of the construction

More information

BUSINESS PLAN CEN/TC 164 WATER SUPPLY EXECUTIVE SUMMARY

BUSINESS PLAN CEN/TC 164 WATER SUPPLY EXECUTIVE SUMMARY Page: 1 BUSINESS PLAN CEN/TC 164 WATER SUPPLY EXECUTIVE SUMMARY Business Environment Nearly almost 100% of the 450 M European people are supplied with drinking water (DW) Europe represents approximately

More information

Sinorix Silent Extinguishing Technology protecting the quiet way

Sinorix Silent Extinguishing Technology protecting the quiet way Sinorix Silent Extinguishing Technology protecting the quiet way An intelligent offering for safe and quiet extinguishing in data centers and server rooms. Answers for infrastructure and cities. Data centers

More information

CEN standardization work on refrigerating systems, especially standard EN 378

CEN standardization work on refrigerating systems, especially standard EN 378 CEN standardization work on refrigerating systems, especially standard EN 378 Carsten Hoch Head of Refrigeration TÜV SÜD Industrie Service GmbH Ridlerstrasse 65, 80339 Munich carsten.hoch@tuev-sued.de

More information

Ex Products Highest level of safety under the most difficult conditions

Ex Products Highest level of safety under the most difficult conditions Ex Products Highest level of safety under the most difficult conditions Fire protection for potentially explosive areas The Ex Products Nuclear power Logical: The avoidance of flammable materials still

More information

Abrasion Resistance of Fluoropolymer and polyester Coatings

Abrasion Resistance of Fluoropolymer and polyester Coatings Abrasion Resistance of Fluoropolymer and polyester Coatings British Standards British Standard 476 refers to fire tests on building materials and structures. The parts of this standard that are of most

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60079-29-2 Edition 2.0 2015-03 Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen INTERNATIONAL

More information

Achieve Success with European Medical Device Commercialization. By Russ King

Achieve Success with European Medical Device Commercialization. By Russ King Achieve Success with European Medical Device Commercialization By Russ King Achieve Success with European Medical Device Commercialization Given the complexity of the FDA s regulatory pathway, many medical

More information

Grow your business: Get ready for flammable refrigerants!

Grow your business: Get ready for flammable refrigerants! Grow your business: Get ready for flammable refrigerants! WHY SHOULD YOU READ THIS LEAFLET? In a nutshell: 1 2 3 Because many of the lower GWP refrigerants are flammable and because using flammable refrigerants

More information

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - TF N 530 Rev.2 2012-04-13 CONSTRUCTION SECTOR STANDARDIZATION GUIDANCE DOCUMENT Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - 1 Drafting

More information

Fire Safety PPT-SM-FIRESFTY V.A.0.0

Fire Safety PPT-SM-FIRESFTY V.A.0.0 Fire Safety 1 Fire Theory Definition of fire Rapid, persistent chemical change that releases heat and light Accompanied by flame Produces rapid oxidation 2 Fire Tetrahedron A fire needs four main elements

More information

The New Generationn of Firedoors

The New Generationn of Firedoors The New Generationn of Firedoors Product Standard EN 16034 Introduction A modern company, while operating in mature sectors, is actually part of an ncreasingly technocratic world, influenced by technical,

More information

Guidance from the Group of Notified Bodies for the Construction Products Regulation 305/2011/EU

Guidance from the Group of Notified Bodies for the Construction Products Regulation 305/2011/EU GNB-CPR AG Guidance from the Group of Notified Bodies for the Construction Products Regulation 305/2011/EU NB-CPR/AG/03/002r3 Issued: 24 May 2013 APPROVED GUIDANCE GNB-CPR AG position paper Guidance to

More information

EtherCAT Box Modules (EPxxxx-xxxx)

EtherCAT Box Modules (EPxxxx-xxxx) Notes about operation of EtherCAT Box Modules (EPxxxx-xxxx) in potentially explosive areas (ATEX) Version: 1.1.0 Date: 2011-06-10 Table of Contents Table of Contents 1 Foreword 1 1.1 Notes on the documentation

More information

Fire Safety. Version 1.0

Fire Safety. Version 1.0 This document is intended to provide basic safety guidelines for the Physical Plant Department at Community College of Allegheny County. The information provided in this guide may vary by site. Version

More information

Instruction Manual. CAT 100 & CAT 200 Continuous Analyzer Transmitter Addendum for Hazardous Area Applications. 3 rd Edition 05/2007

Instruction Manual. CAT 100 & CAT 200 Continuous Analyzer Transmitter Addendum for Hazardous Area Applications. 3 rd Edition 05/2007 CAT 100 & CAT 200 Continuous Analyzer Transmitter Addendum for Hazardous Area Applications 3 rd Edition www.emersonprocess.com CAT 100 & CAT 200 Addendum for Hazardous Area Applications ESSENTIAL INSTRUCTIONS

More information

Managing technical risks

Managing technical risks Aon Global Risk Consulting Managing technical risks Choosing the right protection for your investments. Our offer at a glance Introduction...3 Fire Protection...5 Fire protection advice and planning Design

More information

What extinguishes fires without pressure peaks?

What extinguishes fires without pressure peaks? What extinguishes fires without pressure peaks? Intelligent extinguishing solutions from Siemens. Sinorix CDT innovative, sustainable, and safe. Answers for infrastructure. Innovative technology the intelligent

More information

English.

English. www.atex100.com English For more than 25 years Detection Venting Suppression Isolation 2 ATEX Who isn t aware of the ATEX Directive EG ATEX 2014/34/EU? Ahead of his time, engineer Dr. Franz Alfert was

More information

1. Terms defined in the Construction Products Regulation (CPR)

1. Terms defined in the Construction Products Regulation (CPR) CEN/TC 351 Glossary of relevant terms related to the CPR The following list of terms provides definitions of terms related to the CPR (EU/305/2011) which are relevant for the work of CEN/TC 351 Construction

More information

Approved Sound Proofed Systems

Approved Sound Proofed Systems Approved Sound Proofed Systems Building owners, consultants and contractors who want to know if the considered Soundproof System fulfill the requirements of the DIN4109 should ask the piping system supplier

More information

New Requirements for Placing of Medical Devices on the Market: Conformity Assessment to the Technical Regulations

New Requirements for Placing of Medical Devices on the Market: Conformity Assessment to the Technical Regulations New Requirements for Placing of Medical Devices on the Market: Conformity Assessment to the Technical Regulations September 2015 This summer the medical device circulation reform became one of the most

More information

BUSINESS PLAN CEN-CLC/TC 3 QUALITY MANAGEMENT AND CORRESPONDING GENERAL ASPECTS FOR MEDICAL DEVICES EXECUTIVE SUMMARY

BUSINESS PLAN CEN-CLC/TC 3 QUALITY MANAGEMENT AND CORRESPONDING GENERAL ASPECTS FOR MEDICAL DEVICES EXECUTIVE SUMMARY Page: 1 BUSINESS PLAN CEN-CLC/TC 3 QUALITY MANAGEMENT AND CORRESPONDING GENERAL ASPECTS FOR MEDICAL DEVICES EXECUTIVE SUMMARY Business Environment The area of responsibility of CEN-CLC/TC 3 Quality management

More information

Shipboard incinerators with capacities up to 4000 kw

Shipboard incinerators with capacities up to 4000 kw STANDARD FOR CERTIFICATION No. 2.9 Approval Programmes Type Approval Programmes for Marine Equipment Directive (MED) No. 431.90 - MED A.1/2.7 Shipboard incinerators with capacities up to 4000 kw JANUARY

More information

speed pipe indoor system. Secure indoor networks.

speed pipe indoor system. Secure indoor networks. speed pipe indoor system. Secure indoor networks. www.gabocom.com gabo Systemtechnik 2 3 Networks of the future. Safety obliges. Fiber-optic more and more approaches the end-user also inside buildings

More information

TECHNICAL WHITE PAPER AUTOMATIC WARNING DEVICES FOR LIGHT LIQUID SEPARATORS

TECHNICAL WHITE PAPER AUTOMATIC WARNING DEVICES FOR LIGHT LIQUID SEPARATORS PROCESS AUTOMATION TECHNICAL WHITE PAPER AUTOMATIC WARNING DEVICES FOR LIGHT LIQUID SEPARATORS Recommendations for the Installation and Operation of Light Liquid Separators This White Paper presents European

More information

FAÇADE FIRE TESTS Towards a new European standard method

FAÇADE FIRE TESTS Towards a new European standard method FAÇADE FIRE TESTS Towards a new European standard method Lars Boström November 22, 2017 RISE Research Institutes of Sweden Safety Content Current state in Europe regarding façade fire tests History on

More information

Technical Bulletin CE marking: from 1st July 2013

Technical Bulletin CE marking: from 1st July 2013 Technical Bulletin CE marking: from 1st July 2013 New regulation New obligations Same CE mark We are facing the most significant change for a decade in the way that construction products are manufactured

More information

Regulation 574_2014: Annex III CPR. and. Regulation 568_2014: Annex V CPR

Regulation 574_2014: Annex III CPR. and. Regulation 568_2014: Annex V CPR TF N 635 Regulation 574_2014: Annex III CPR and Regulation 568_2014: Annex V CPR 30-05-2014 28.5.2014 L 159/41 REGULATIONS COMMISSION DELEGATED REGULATION (EU) No 574/2014 of 21 February 2014 amending

More information

HazLoc Essential Guides:

HazLoc Essential Guides: HazLoc Essential Guides: Intertek Deeside Lane, Chester, CH1 6DD UK hazloc@intertek.com 01244 882590 www.intertek-hazloc.com Introduction This white paper aims to clarify ATEX Technical Files. As a Notified

More information

BT Cables Technical Seminar CIBSE South Wales Region. Nov 17

BT Cables Technical Seminar CIBSE South Wales Region. Nov 17 BT Cables Technical Seminar CIBSE South Wales Region Nov 17 Agenda Introductions and BT Cables overview Construction Products Regulation Cables for BMS: A Technical Overview Q&A s Toby Collins Mark Froggatt

More information

September Safety Subject

September Safety Subject September Safety Subject Portable Fire Extinguishers If a fire is detected, sound the alarm and evacuate the building or have someone else pull the alarm so that help can be on the way. Do not attempt

More information

The Danish Energy Authority to carry out inspections in June and July 2012

The Danish Energy Authority to carry out inspections in June and July 2012 The Danish Energy Authority to carry out inspections in June and July 2012 We check the CE marking of the insulation products of expanded polystyrene (EPS) you sell or use. And we check if you have declared

More information

How can you minimize consequential damages in case of a fire?

How can you minimize consequential damages in case of a fire? How can you minimize consequential damages in case of a fire? With intelligent extinguishing solutions from Siemens. Sinorix 227 fast, effective, and reliable. Answers for infrastructure. Reliability the

More information

Type 5 Certifications:

Type 5 Certifications: : What are they and how do you use them for compliance? Intertek Cleeve Road, Leatherhead, Surrey KT22 7SB UK info.uk@intertek.com 01372 370900 www.intertek.com Contents Contents... 1 Introduction... 1

More information

COMMISSION DELEGATED REGULATION (EU) /... of

COMMISSION DELEGATED REGULATION (EU) /... of EUROPEAN COMMISSION Brussels, 20.3.2017 C(2017) 1703 final COMMISSION DELEGATED REGULATION (EU) /... of 20.3.2017 on the conditions for classification, without testing, of external renders and internal

More information

BUSINESS PLAN. CEN/TC 336 BITUMINOUS BINDERS Version 2018 EXECUTIVE SUMMARY

BUSINESS PLAN. CEN/TC 336 BITUMINOUS BINDERS Version 2018 EXECUTIVE SUMMARY Page: 1 BUSINESS PLAN CEN/TC 336 BITUMINOUS BINDERS Version 2018 EXECUTIVE SUMMARY BUSINESS ENVIRONMENT The parties interested in the bituminous binder market are the following industries: - the bituminous

More information

AUTOMATIC FIREFIGHTING SYSTEMS IN HOSPITALS

AUTOMATIC FIREFIGHTING SYSTEMS IN HOSPITALS SPECIAL HAZARDS PROTECTION AUTOMATIC FIREFIGHTING SYSTEMS IN HOSPITALS Protection for all areas Our goal: safety Possible solutions require a detailed study of the actual conditions and taking stronger

More information

WKE Spelsberg. The name in maintaining electrical integrity.

WKE Spelsberg. The name in maintaining electrical integrity. WKE Spelsberg. The name in maintaining electrical integrity. Reference object: Central train station, Berlin Modern architecture places strictly demand the reliability of electrical systems. That is especially

More information

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D-PL-11035-03-00 according to DIN EN ISO/IEC 17025:2005 Period of validity: 25.10.2017 to 24.10.2022 Holder of certificate: DMT

More information

White Paper. Effective and Energy Efficient Access Control in Commercial Buildings. The global leader in door opening solutions

White Paper. Effective and Energy Efficient Access Control in Commercial Buildings. The global leader in door opening solutions White Paper Effective and Energy Efficient Access Control in Commercial Buildings The global leader in door opening solutions Introduction Security expert Abloy UK is promoting a green security message,

More information

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE - 249 - SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE Urs Welte Amstein + Walthert AG, Switzerland ABSTRACT The paper aims at a detailed analysis of the current know-how in the construction of tunnel cabling

More information

PRICELESS PROTECTION INERGEN Clean Agent Fire Suppression Systems

PRICELESS PROTECTION INERGEN Clean Agent Fire Suppression Systems PRICELESS PROTECTION INERGEN Clean Agent Fire Suppression Systems DETECT-SUPPRESS-PROTECT THE INERGEN CLEAN AGENT SYSTEM FROM ANSUL INERGEN IS BETTER FOR YOUR PROPERTY Upon discharge, INERGEN instantly

More information

Pressed pyrotechnical powder.

Pressed pyrotechnical powder. 1. Product and Company Information Type of Product: Comet Smoke Signal, Art.-No. 9181700 Pains Wessex Buoysmoke MK9, Art.-No. 9538350 Area of Usage: Sea distress signal Manufacturer s Name and Address:

More information

HazLoc Essential Guides:

HazLoc Essential Guides: HazLoc Essential Guides: Intertek Deeside Lane, Chester, CH1 6DD UK hazloc@intertek.com +44 1244 882590 www.intertek-hazloc.com Contents Contents... 1 Introduction... 1 Introduction to Ex... 1 ATEX Overview...

More information

BUSINESS PLAN CEN/TC 124 TIMBER STRUCTURES EXECUTIVE SUMMARY

BUSINESS PLAN CEN/TC 124 TIMBER STRUCTURES EXECUTIVE SUMMARY Page: 1 BUSINESS PLAN CEN/TC 124 TIMBER STRUCTURES EXECUTIVE SUMMARY Business environment The wood and wood products industry is faced with cyclic demands from other industrial activities, such as construction,

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Sponsor Prepared by P.O. Box 70 NL-5750 AB DEURNE Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280 CB

More information

Tampa, FL Fire Cause Classification Task Group Tue, 14 April 2011

Tampa, FL Fire Cause Classification Task Group Tue, 14 April 2011 Fire Cause Classification Tampa, FL Tue, 12 April 2011 Proposals: CP2 - Chapter 19 (New 19 is a portion of old 19) CP3 - Chapter 20 (New 20 is the remainder of old 19) CP4-2 definitions in Chapter 3, as

More information

S12 Fire Safety Risk Assessment H&SFS01-1 / 9

S12 Fire Safety Risk Assessment H&SFS01-1 / 9 S12 Fire Safety Risk Assessment H&SFS01 Risk ratings The following risk ratings are based on two factors: The overall fire risk rating for the site The risk rating for the individual recommendations /control

More information

Regulation (EU) No 305/2011 laying down harmonised conditions for the marketing of construction products (EU CPR)

Regulation (EU) No 305/2011 laying down harmonised conditions for the marketing of construction products (EU CPR) November 2013 Last updated: June 2015 Regulation (EU) No 305/2011 laying down harmonised conditions for the marketing of construction products (EU CPR) Frequently Asked Questions Part IV Preliminary remarks

More information

NON ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS

NON ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS NON ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS The ATEX Directive consists of two EU Directives, ATEX Directive 2014/34/EU and ATEX Directive 99/92/EC. ATEX Directive 2014/34/EU embodies the European minimum

More information

If there are more than ten people working other than on the ground floor,

If there are more than ten people working other than on the ground floor, Fire safety information sheet Introduction This information sheet is designed to give our safety representatives a basic understanding of fire safety and fire risk assessments under the current law. This

More information

best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to

best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to BS EN 16034: 2014 Permission to reproduce extracts from BS EN 16034 : 2014 is granted by BSI. DHF BEST PRACTICE

More information

BUSINESS PLAN CEN/TC 142 WOODWORKING MACHINES SAFETY EXECUTIVE SUMMARY

BUSINESS PLAN CEN/TC 142 WOODWORKING MACHINES SAFETY EXECUTIVE SUMMARY Page: 1 BUSINESS PLAN CEN/TC 142 WOODWORKING MACHINES SAFETY EXECUTIVE SUMMARY Business environment largest in the world, covering more than 50% of the world market. CEN TC 142 activity deals with standardization

More information

fire resistant cables

fire resistant cables Building Technology fire resistant cables Special electrical and optical cables www.tecnikabel.com Special electrical and optical cables 2 INTRODUCTION Structured cabling solutions. Tecnikabel can provide

More information

The Machinery Directive 2006/42/EC

The Machinery Directive 2006/42/EC The Machinery Directive 2006/42/EC Aims of the Machinery Directive To ensure the free movement of machinery on the EU market whether manufactured in the EU or imported To ensure a high level of protection

More information

+ = FIRE LABORATORY INTRODUCTION. APPLUS+ LGAI - Our company history. High Technology Knowledge. Customer Confidence. Branding

+ = FIRE LABORATORY INTRODUCTION. APPLUS+ LGAI - Our company history. High Technology Knowledge. Customer Confidence. Branding INTRODUCTION APPLUS+ LGAI - Our company history As a brief resume of our history LGAI - Laboratori General d'assaigs i Investigacions (whose commercial name was LGAI Technological Center) was fully owned

More information

Development of a European approach to assess the fire performance of facades

Development of a European approach to assess the fire performance of facades Development of a European approach to assess the fire performance of facades This presentation was made in Brussels on December 8, 2017, for EC, AGF and stakeholders Lars Boström, Roman Chiva, Anja Hofmann-Böllinghaus,

More information

Guideline Construction Products Regulation (EU) 305/20122

Guideline Construction Products Regulation (EU) 305/20122 Guideline Construction Products Regulation (EU) 305/20122 Guideline: CPR 1 Table of contents Common Abbreviations... 4 Executive Summary... 5 Purpose of this guidance document... 5 Summary Requirements

More information

S I M P L Y C E INTRODUCTION TO CE NORMS AND STANDARDS FOR DOORS AND GATES TWO THOUSAND EIGHTEEN

S I M P L Y C E INTRODUCTION TO CE NORMS AND STANDARDS FOR DOORS AND GATES TWO THOUSAND EIGHTEEN S I M P L Y C E INTRODUCTION TO CE NORMS AND STANDARDS FOR DOORS AND GATES TWO THOUSAND EIGHTEEN CONTENT INTRODUCTION MAIN REQUIREMENTS CE CE FOR DOOR PRODUCING COMPANY CE FOR INSTALLER END USER FLEXIFORCE

More information

Fire Safety Risk Assessment for Treowen, Wonastow, Monmouth, NP25 4DL

Fire Safety Risk Assessment for Treowen, Wonastow, Monmouth, NP25 4DL Fire Safety Risk Assessment for Treowen, Wonastow, Monmouth, NP25 4DL Record of significant findings Scope of Risk Assessment This fire safety risk assessment covers the use of Treowen as a venue for Civil

More information

Reaction to fire classification report No C-rev.1

Reaction to fire classification report No C-rev.1 Reaction to fire classification report. 17241C-rev.1 Owner of the classification report Distributor: Vescom bv Churchilllaan 10 Sint Jozefstraat 20 5705 BK Helmond 5750 AB Deurne The Netherlands The Netherlands

More information

AS AS Australian Standard. Industrial fuel-fired appliances. This is a free 9 page sample. Access the full version online.

AS AS Australian Standard. Industrial fuel-fired appliances. This is a free 9 page sample. Access the full version online. AS 1375 2013 AS 1375 2013 Australian Standard Industrial fuel-fired appliances This Australian Standard was prepared by Committee AG-011, Industrial and Commercial Gas Fired Appliances. It was approved

More information

Guidance from the Group of Notified Bodies for the Construction Products Directive 89/106/EEC

Guidance from the Group of Notified Bodies for the Construction Products Directive 89/106/EEC CEN/TC 88 N 2873 GNB-CPD SG19 Guidance from the Group of Notified Bodies for the Construction Products Directive 89/106/EEC NB-CPD/SG19/11/085 Issued: 19 October 2011 APPROVED - GUIDANCE GNB-CPD position

More information

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - TF N 687rev1 2015-06-02 CONSTRUCTION SECTOR STANDARDIZATION GUIDANCE DOCUMENT Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - 1 I - Drafting

More information