Energy Codes. Connected Lighting simplified by Eaton. design and application guide
|
|
- Iris Owen
- 5 years ago
- Views:
Transcription
1 Codes Connected simplified by Eaton design and application guide
2 We make connections work* Eaton Power Connectivity Apps * Simplif ied connected lighting solutions for Buildings, Communities & omes Eaton s portfolio of connected lighting solutions leverages the realestate of the physical light fixture to increase building, business and community operating efficiency through controls and data. With connected lighting solutions, we go beyond controlling light to solve higher complexity problems enabled by sensing and communication capabilities within the light fixture itself. With innovation you can rely on, and connections you can build on; that s how Eaton makes connections work.
3 Table of Contents Codes ASI / ASRAE / IES Standard International Conservation Code (IECC) 05 4 California Title 4 4 Application code compliant sequence best practices 67 Terminology 89 WaveLinx applications & typical wiring diagrams WaveLinx overview 0 IECC 05 Classroom examples Conference room examples 34 Office corridor example 5 Private office example 6 Lobby example 7 Open office example 8 Restaurant example 9 Retail example 0 ASRAE Classroom examples Conference room examples 34 Office corridor example 5 Private office example 6 Lobby example 7 Open office example 8 Restaurant example 9 Retail example 30 DLVP applications & typical wiring diagrams DLVP overview 4 Classroom, x fixtures with integrated sensors 4 Classroom, x fixtures 43 Classroom, x4 fixtures with integrated sensors 44 Classroom, x4 fixtures 45 Conference room, x fixtures with integrated sensors 46 Conference room, x fixtures 47 Conference room, x fixtures and downlights 48 Corridor/all, x4 fixtures with integrated sensors 49 Corridor/all, x4 fixtures 50 Executive office, x fixtures 5 Open office, x4 fixtures with integrated sensors and emergency 5 Open office, x4 fixtures with integrated sensors 53 Open office, x4 fixtures 54 Open office, x4 fixtures with integrated sensors and emergency 55 Private office, x4 fixtures with integrated sensors 56 Private office, x4 fixtures 57 Private offices, x4 fixtures with integrated sensors 58 TITLE 4 06 Classroom examples 33 Conference room examples 3334 Office corridor example 35 Private office example 36 Lobby example 37 Open office example 38 Restaurant example 39 Retail example 40
4 Codes application notes ASI / ASRAE / IES Standard Standard for Buildings Except LowRise Residential Buildings (Standard 90.06) adopted as of September 06. This code significantly finetunes the design requirements for codecompliant lighting controls systems, mechanical systems, and the building envelope. This application note summarizes the new mandatory lighting control requirements and highlights where they can be used in various spaces. Please note: this document is intended to provide a general reference and design professionals should consult Standard and the authority having jurisdiction for projectspecific requirements and interpretation. Below summarizes changes from to 90.06: Reduced occupancysensor time delay from 30 to 0 minutes Requires partialoff to 50% in spaces where lights should remain O, such as corridors and stairwells Requires daylight controls in primary, secondary and top light zones Requires functional testing requirements ASRAE 90. was recognized by the U.S. Department of (DOE) as the national energy reference standard. International Conservation Code (IECC) 05 IECC 05 establishes minimum energy efficiency requirements for new and renovated buildings. This latest iteration contains dramatic changes to the prescriptive and performancebased criteria that previously defined IECCcompliant lighting and lighting control systems. ASRAE 90. is recognized by the DOE as the national reference standard, however IECC is adopted by many states. Please note: this document is intended to provide a general reference and design professionals should consult IECC 05 and the authority having jurisdiction for projectspecific requirements and interpretation. Below summarizes changes from 0 to 05: s Revamped and Redefined Continuous Dimming ow Required in Certain Daylit Spaces Reduce Exterior Lights at ight Use a Digital System to Satisfy Additional Efficiency Options ew Commissioning Documents Deadline California Title 4 California's Building Efficiency Standards are updated on an approximately threeyear cycle. The 06 Standards will continue to improve upon the 03 Standards for new construction of, and additions and alterations to, residential and nonresidential buildings. The effective date of the 06 Standards is January, 07. Below summarizes changes from 03 to 06: Mandatory controls eliminates power adjustment factors Simplify multilevel lighting controls Clarify partialo and partial requirements Clarified alterations controls requirements 4 EATO Connected Codes
5 saving lighting control strategies STRATEGY DESCRIPTIO ESTIMATED SAVIGS dimming control is one of five methods that satisfy the multilevel lighting control requirements. 00% /vacancy control turns lights Off (or partially Off) when a room is unoccupied. Lights can be turned On automatically or manually, when a person enters a room. 060% control automatically adjusts lighting levels in response to the amount of daylight available in the space. 045% O/ Auto O/ or Vacancy Mode is designed to ensure that lighting does not turn O automatically. 40%60% ighend tuning lowers the maximum light level, creating energy savings. 030% reduces light levels in response to a signal from an OpenADR device or BMS closure. 040% ly Switched O/ ly switched O/ method allows users to manually control the lighting within the space and complies with local control requirements. 00% Plug load control turns controlled receptacles On, when the space is occupied, and Off, when the space is vacant. 550% led loads UL94 ( Backup Circuit) The ability to control emergency lighting along with normal lighting while ensuring they go to full bright during normal power loss. 530% EATO Connected Codes 5
6 Application code compliant sequence best practices ASRAE IECC 05 T4 06 Atrium Banking Classroom / Training / Lecture Conference / Meeting room Local 9.4.(a)..3 (a), O (a), O 9.4.(c).. Bilevel 9.4. Side lighting 9.4.(e).3. Top lighting 9.4.(f) (g).. (c).6 Full 9.4.(h).. (c).5 Shutoff 9.4.(i).. (c) Parking Garage (a), C (a), (a), Enhanced Digital s C406.4 Required Choose one Choose one Choose one 6 EATO Connected Codes
7 Copy / Print room Corridor Courtroom Dining area Food preparation Library Office Restroom Sales area Stairwell Required Choose one Choose one Choose one EATO Connected Codes 7
8 Terminology IGLEVEL TERMIOLOGY Local control If the controlled space is 0,000 ft, a control device shall not control more than 500 ft If the controlled space is larger than 0,000 ft, no device shall control more than 0,000 ft The installed device shall be readily accessible and the load being controlled shall be visible when operating the control RECOMMEDED PRODUCTS* WaveLinx DLVP Room ler System Fifth Light Wallbox dimmers/sensors GDS when connected to LiteKeeper, Keeper Restricted to O Vacancy modes must be used such that lights will not turn on automatically WaveLinx DLVP Room ler System Fifth Light VSW, VW, VLW VAC Restricted to O When in occupancy mode, automatic O shall not exceed 50% of the lighting power WaveLinx DLVP Room ler System Fifth Light LiteKeeper/, Keeper Bilevel The general lighting in a space must have the following functionality: Full O, Full, and Dimming Dimming may be continuous or through step dimming If step dimming, at least one intermediate step shall be between 30% and 50% of full lighting power WaveLinx DLVP Room ler System Fifth Light LiteKeeper, Keeper OAC, OAWC with Low Voltage Switches Responsive s for Sidelighting Primary sidelighted areas with combined input power at 50W or greater shall be controlled by photocontrols Secondary sidelighted areas with combined input power at 300W or greater, the area shall be controlled by photocontrols s must also: be readily accessible for calibration, control primary and secondary sidelighted areas independently, and shall incorporate daylight dimming WaveLinx DLVP Room ler System Fifth Light Analog Photosensors with Keeper daylight responsive controls for toplighting Space within any daylight area that has combined input power for all general lighting at 50W or greater shall be controlled by photocontrols. must: Be readily accessible for calibration adjustments ave daylight response through continuous dimming or Step dimming with a point between 50% and 70%, a point between 0% and 40% (or lowest dimming level that the technology permits), and a third point at full off General lighting with overlapping toplighted and sidelighted areas shall be controlled together WaveLinx DLVP Room ler System Fifth Light Analog Photosensors with Keeper partial (full complies) Within 0 minutes of occupants leaving a space, lighting power shall automatically decrease at least 50% WaveLinx DLVP Room ler System Fifth Light Keeper * Additional product combinations may be code compliant. Please contact your Eaton s Systems representative for more information. Exceptions: more detailed information may apply, please reference your local code for more detailed information. 8 EATO Connected Codes
9 Terminology IGLEVEL TERMIOLOGY RECOMMEDED PRODUCTS* full Within 0 minutes of occupants leaving a space,lighting shall be automatically shut Each control shall not control more than 5000 ft WaveLinx DLVP Room ler System Fifth Light LiteKeeper, Keeper Wallbox and Ceiling s Shutoff When a space is scheduled to be vacant, lighting shall be automatically shut. Any override control shall revert back to the schedule within hours of the last action WaveLinx DLVP Room ler System Fifth Light LiteKeeper, Keeper ally turn off plug loads when the space is unoccupied by sensor or time schedule WaveLinx DLVP Room ler System Fifth Light LiteKeeper, Keeper Provide energy measurement data on the system collected at a minimum of every 5 minute and reported at least hourly WaveLinx (included with system) Fifth Light (included with system) PowerXpert (external measurement for all other systems) EATO Connected Codes 9
10 WaveLinx Wireless Connected System Wireless, codecompliant, and costeffective, WaveLinx Wireless Connected System offers the most outofthebox functionality on the market. It s also one of the easiest connected lighting systems to install and manage. code compliance? Yes, it s true code commissioning meets or exceeds code requirements Wireless integrated sensors ensure maximum efficiency and flexibility A simple mobile app allows building managers to easily adjust settings, even after the project has finished, with no need to go back into the wall Connected fixtures provide a platform for future scalability Wireless, codecompliant, and costeffective for today 0 EATO Connected Codes
11 IECC 05 IECC 05: Classroom example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads dimming zones of no more than eight luminaires Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy Wireless Area ler Qty Catalog # Description Wireless Area ler WSPMV00 WaveLinx Relay Switchpack with 00V dimming CWPD500 WaveLinx ceiling sensor W4SRLW WaveLinx 4ELD34UVL835CDSWPDU Encounter x4 not required for indoor spaces without windows ot required in spaces without windows or that are less than 50W s Programmable scenes Dominant button is 50% light level Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler 50 feet 00 feet to st WaveLinx device Distance between WaveLinx devices 75 feet 50 feet umber of hops from 4 hops 5 hops Wireless Area ler umber of areas per 6 6 Wireless Area ler umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation WR5 Wireless 00V CWPD500 Wireless Ceiling occupancy sensor x4 recessed light fixture with 00V dimming WSPMV00 0A Relay w/ 00V Dimming Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide
12 IECC 05 IECC 05: Classroom example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx on to 50% Optional vacancy mode Optional plug load turns on/off with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor spaces ot required in spaces without windows that are less than 50W s Programmable scenes Dominant button is 50% light level Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup Complies with Enhanced Digital section C406 PoE etwork Switch provided by others Wireless Area ler WLRLW Wireless large button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide
13 IECC 05 IECC 05: Conference room example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy / Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows or that are less than 50W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx TMSWPD WaveLinx Tilemount 3 LD4 OR LD6 Portfolio Commercial Recessed LED 4 ELD34UVL835CDSWPDU Encounter x with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup Complies with Enhanced Digital section C406 PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 TMSWPD WaveLinx Tilemount occupancy / daylighting 3A Relay with 00V ELD34UVL835CDSWPDU Encounter x with WaveLinx LD4/LD6 Portfolio Commercial Recessed LED Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide 3
14 IECC 05: Conference room example IECC 05 ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Individually addressable luminaires Out of the box 75% high end trim auto on to 50% Optional vacancy mode Optional plug load turns on/off with occupancy / Individual luminaire daylight dimming to approximately 500 lux not required for indoor space without windows ot required in spaces without windows or that are less than 50W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx TMSWPD WaveLinx Tilemount 3 LD4 OR LD6 Portfolio Commercial Recessed LED DSIWS3L35DUVAC48T8STDSWW Divide Suspended with WaveLinx s Programmable Scenes Dominant button is 50% light level Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup Complies with Enhanced Digital section C406 PoE etwork Switch provided by others Wireless Area ler DSIWS3L35DUVAC48T8STDSWW Divide Suspended 8ft with WaveLinx Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler 50 feet 00 feet to st WaveLinx device Distance between WaveLinx devices 75 feet 50 feet umber of hops from 4 hops 5 hops Wireless Area ler umber of areas per 6 6 Wireless Area ler umber of zones per area 3 6 W4SRLW Wireless 4 small button scene wallstation TMSWPD WaveLinx Tilemount occupancy / daylighting 3A Relay with 00V LD4/LD6 Portfolio Commercial Recessed LED umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide
15 IECC 05: Office corridor example IECC 05 ly Switched O/ Lumen Maintenance O/ Auto Wireless Area ler 00V lighting loads Individually addressable luminaires Out of the box 75% high end trim auto on to 50% Optional vacancy mode Optional plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor spaces without windows ot required in spaces without windows or that are less than 50W Qty Catalog # Description Wireless Area ler WLRLW WaveLinx 6 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Programmable Scenes Dominant button is 50% light level on/off Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler WLRLW Wireless large button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide 5
16 IECC 05 IECC 05: Private office example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows or that are less than 50W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx ELD34UVL835CDSWPDU Encounter x with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup Complies with Enhanced Digital section C406 PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation ELD34UVL835CDSWPDU Encounter x with WaveLinx Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide
17 IECC 05: Lobby example IECC 05 ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy / Individual luminaire daylight dimming to approximately 500 lux not required for indoor space without windows ot required in spaces without windows or that are less than 50W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx TMSWPD WaveLinx Tilemount 6 LD4 OR LD6 Portfolio Commercial Recessed LED ELD34UVL835CDSWPDU Encounter x with WaveLinx s Dominant button half lights (sets lights to 50% or less) Programmable scenes Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup Complies with Enhanced Digital section C406 PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 TMSWPD WaveLinx Tilemount occupancy / daylighting 3A Relay with 00V ELD34UVL835CDSWPDU Encounter x with WaveLinx LD4/LD6 Portfolio Commercial Recessed LED Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide 7
18 IECC 05 IECC 05: Open office example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Optional plug load turns on/off with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor space without windows ot required in spaces without windows or that are less than 50W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SLRLW WaveLinx 4 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Raise Lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup Complies with Enhanced Digital section C406 PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide
19 IECC 05 IECC 05: Restaurant example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Individually addressable luminaires Out of the box 75% high end trim on to 50% Optional vacancy mode Optional plug load turns on/off with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor space without windows ot required in spaces without windows or that are less than 50W Wireless Area ler Qty Catalog # Description Wireless Area ler 5 W4SLRLW WaveLinx 4 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Raise Lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup Complies with Enhanced Digital section C406 PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide 9
20 IECC 05 IECC 05: Retail example ly Switched O/ Lumen Maintenance O/ Auto Linear Dimming Module WaveLinx Relay 00V 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Optional plug load turns on/off with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor space without windows ot required in spaces without windows or that are less than 50W Wireless Area ler Qty Catalog # Description Wireless Area ler 6 W4SLRLW WaveLinx 4 WSPMV00 WaveLinx Relay Switchpack with 00V dimming 4 LDCMPL07700VGR Linear Dimming Modules 3 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Raise Lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup Complies with Enhanced Digital section C406 PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls W4SRLW Wireless 4 small button scene wallstation 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 WSPMV00 0A Relay w/ 00V Dimming LDCMPL0 7700VGR Linear Dimming Module Local O O Bilevel Side Top Parking Garage Enhanced Digital IECC C EATO WaveLinx design and application guide
21 ASRAE ASRAE : Classroom example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy not required for indoor spaces without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx WSPMV00 WaveLinx Relay Switchpack with 00V dimming CWPD500 WaveLinx ceiling occupancy sensor 4ELD34UVL835CDSWPDU Encounter x4 s Programmable scenes Dominant button is 50% light level Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler 50 feet 00 feet to st WaveLinx device Distance between WaveLinx devices 75 feet 50 feet umber of hops from 4 hops 5 hops Wireless Area ler umber of areas per 6 6 Wireless Area ler umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation WR5 Wireless 00V CWPD500 Wireless Ceiling occupancy sensor x4 recessed light fixture with 00V dimming WSPMV00 0A Relay w/ 00V Dimming Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide
22 ASRAE ASRAE : Classroom example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor space without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx 4ELD34UVL835CDSWPDU Encounter x4 with Istinct s Programmable scenes Dominant button is 50% light level Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet WR5 Wireless umber of hops from Wireless Area ler 4 hops 5 hops umber of areas per Wireless Area ler 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide
23 ASRAE ASRAE : Conference room example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy / Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx TMSWPD WaveLinx Tilemount 3 LD4 OR LD6 Portfolio Commercial Recessed LED 4 ELD34UVL835CDSWPDU Encounter x with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation WR5 Wireless ELD34UVL835CDSWPDU Encounter x with WaveLinx TMSWPD WaveLinx Tilemount occupancy / daylighting 3A Relay with 00V LD4/LD6 Portfolio Commercial Recessed LED Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide 3
24 ASRAE ASRAE : Conference room example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Up to 3 dimming zones Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy / Individual luminaire daylight dimming to approximately 500 lux not required for indoor space without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx TMSWPD WaveLinx Tilemount 6 LD4 OR LD6 Portfolio Commercial Recessed LED DSIWS3L35DUVAC48T8STDSWW Divide Suspended with WaveLinx s Programmable Scenes Dominant button is 50% light level Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler DSIWS3L35DUVAC48T8STDSWW Divide Suspended 8ft with WaveLinx Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS WR5 Wireless umber of interior walls walls 3 walls Distance from Wireless Area ler 50 feet 00 feet to st WaveLinx device Distance between WaveLinx devices 75 feet 50 feet umber of hops from 4 hops 5 hops Wireless Area ler umber of areas per 6 6 Wireless Area ler umber of zones per area 3 6 W4SRLW Wireless 4 small button scene wallstation TMSWPD WaveLinx Tilemount occupancy / daylighting 3A Relay with 00V LD4/LD6 Portfolio Commercial Recessed LED umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide
25 ASRAE : Office corridor example ASRAE ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim Wireless Area ler auto on to 50% Optional vacancy mode Optional plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows or that are less than 0W Qty Catalog # Description Wireless Area ler W4SLRLW WaveLinx 6 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Programmable Scenes Dominant button is 50% light level on/off Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide 5
26 ASRAE ASRAE : Private office example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx ELD34UVL835CDSWPDU Encounter x with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation WR5 Wireless ELD34UVL835CDSWPDU Encounter x with WaveLinx Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide
27 ASRAE : Lobby example ASRAE ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy / Individual luminaire daylight dimming to approximately 500 lux not required for indoor space without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx TMSWPD WaveLinx Tilemount 6 LD4 OR LD6 Portfolio Commercial Recessed LED ELD34UVL835CDSWPDU Encounter x with WaveLinx s Dominant button half lights (sets lights to 50% or less) Programmable scenes Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler 50 feet 00 feet to st WaveLinx device Distance between WaveLinx devices 75 feet 50 feet umber of hops from 4 hops 5 hops Wireless Area ler umber of areas per 6 6 Wireless Area ler umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation WR5 Wireless ELD34UVL835CDSWPDU Encounter x with WaveLinx TMSWPD WaveLinx Tilemount occupancy / daylighting 3A Relay with 00V LD4/LD6 Portfolio Commercial Recessed LED Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide 7
28 ASRAE : Open office example ASRAE ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SLRLW WaveLinx wallstation WR5 WaveLinx 4 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Raise Lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet WR5 Wireless umber of hops from Wireless Area ler 4 hops 5 hops umber of areas per Wireless Area ler 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide
29 ASRAE ASRAE : Restaurant example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor spaces without windows ot required in spaces without windows that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler 5 W4SLRLW WaveLinx WR5 WaveLinx 4 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Raise Lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet WR5 Wireless umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide 9
30 ASRAE ASRAE : Retail example ly Switched O/ Lumen Maintenance O/ Auto Linear Dimming Module WaveLinx Relay 00V 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor spaces without windows ot required in spaces without windows that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler 6 W4SLRLW WaveLinx 4 WSPMV00 WaveLinx Relay Switchpack with 00V dimming WR5 WaveLinx 4 LDCMPL07700VGR Linear Dimming Modules 3 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Raise Lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls W4SRLW Wireless 4 small button scene wallstation 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 WR5 Wireless WSPMV00 0A Relay w/ 00V Dimming LDCMPL0 7700VGR Linear Dimming Module umber of zones per area 3 6 umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage ASRAE (a) (c) (e) (f) (g) (h) (i) EATO WaveLinx design and application guide
31 TITLE 4 06 TITLE 4 06: Classroom example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy not required for indoor spaces without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx WSPMV00 WaveLinx Relay Switchpack with 00V dimming CWPD500 WaveLinx ceiling occupancy sensor 4ELD34UVL835CDSWPDU Encounter x4 s Programmable scenes Dominant button is 50% light level Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler 50 feet 00 feet to st WaveLinx device Distance between WaveLinx devices 75 feet 50 feet umber of hops from 4 hops 5 hops Wireless Area ler umber of areas per 6 6 Wireless Area ler umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation WR5 Wireless 00V CWPD500 Wireless Ceiling occupancy sensor x4 recessed light fixture with 00V dimming WSPMV00 0A Relay w/ 00V Dimming Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) EATO WaveLinx design and application guide 3
32 TITLE 4 06 TITLE 4 06: Classroom example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Programmable scenes Dominant button is 50% light level Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet WR5 Wireless umber of hops from Wireless Area ler 4 hops 5 hops umber of areas per Wireless Area ler 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) 3 EATO WaveLinx design and application guide
33 TITLE 4 06 TITLE 4 06: Conference room example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy / Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx TMSWPD WaveLinx Tilemount 3 LD4 OR LD6 Portfolio Commercial Recessed LED 4 ELD34UVL835CDSWPDU Encounter x with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation WR5 Wireless ELD34UVL835CDSWPDU Encounter x with WaveLinx TMSWPD WaveLinx Tilemount occupancy / daylighting 3A Relay with 00V LD4/LD6 Portfolio Commercial Recessed LED Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) EATO WaveLinx design and application guide 33
34 TITLE 4 06 TITLE 4 06: Conference room example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Up to 3 dimming zones Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy / Individual luminaire daylight dimming to approximately 500 lux not required for indoor spaces without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx TMSWPD WaveLinx Tilemount 6 LD4 OR LD6 Portfolio Commercial Recessed LED DSIWS3L35DUVAC48T8STDSWW Divide Suspended with WaveLinx s Programmable Scenes Dominant button is 50% light level Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler DSIWS3L35DUVAC48T8STDSWW Divide Suspended 8ft with WaveLinx Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS WR5 Wireless umber of interior walls walls 3 walls Distance from Wireless Area ler 50 feet 00 feet to st WaveLinx device Distance between WaveLinx devices 75 feet 50 feet umber of hops from 4 hops 5 hops Wireless Area ler umber of areas per 6 6 Wireless Area ler umber of zones per area 3 6 W4SRLW Wireless 4 small button scene wallstation TMSWPD WaveLinx Tilemount occupancy / daylighting 3A Relay with 00V LD4/LD6 Portfolio Commercial Recessed LED umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) 34 EATO WaveLinx design and application guide
35 TITLE 4 06: Office corridor example TITLE 4 06 ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim Wireless Area ler auto on to 50% Optional vacancy mode Optional plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor spaces without windows ot required in spaces without windows or that are less than 0W Qty Catalog # Description Wireless Area ler WLRLW WaveLinx 6 4ELD34UVL835CDSWPDU Encounter x with WaveLinx s Programmable Scenes Dominant button is 50% light level on/off Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler WLRLW Wireless large button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) EATO WaveLinx design and application guide 35
36 TITLE 4 06 TITLE 4 06: Private office example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx ELD34UVL835CDSWPDU Encounter x with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation WR5 Wireless ELD34UVL835CDSWPDU Encounter x with WaveLinx Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) 36 EATO WaveLinx design and application guide
37 TITLE 4 06: Lobby example TITLE 4 06 ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim auto on to 50% Optional vacancy mode Plug load turns on with occupancy / Individual luminaire daylight dimming to approximately 500 lux not required for indoor spaces without windows ot required in spaces without windows or that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SRLW WaveLinx WR5 WaveLinx TMSWPD WaveLinx Tilemount 6 LD4 OR LD6 Portfolio Commercial Recessed LED ELD34UVL835CDSWPDU Encounter x with WaveLinx s Dominant button half lights (sets lights to 50% or less) Programmable scenes Scene raise Scene lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls Distance from Wireless Area ler 50 feet 00 feet to st WaveLinx device Distance between WaveLinx devices 75 feet 50 feet umber of hops from 4 hops 5 hops Wireless Area ler umber of areas per 6 6 Wireless Area ler umber of zones per area 3 6 umber of scenes per area 6 0 W4SRLW Wireless 4 small button scene wallstation WR5 Wireless ELD34UVL835CDSWPDU Encounter x with WaveLinx TMSWPD WaveLinx Tilemount occupancy / daylighting 3A Relay with 00V LD4/LD6 Portfolio Commercial Recessed LED Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) EATO WaveLinx design and application guide 37
38 TITLE 4 06: Open office example TITLE 4 06 ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor offices without windows ot required in spaces without windows that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler W4SLRLW WaveLinx WR5 WaveLinx 4 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Raise Lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming umber of interior walls walls 3 walls Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet WR5 Wireless umber of hops from Wireless Area ler 4 hops 5 hops umber of areas per Wireless Area ler 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) 38 EATO WaveLinx design and application guide
39 TITLE 4 06 TITLE 4 06: Restaurant example ly Switched O/ Lumen Maintenance O/ Auto 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor spaces without windows ot required in spaces without windows that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler 5 W4SLRLW WaveLinx WR5 WaveLinx 4 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Raise Lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler W4SRLW Wireless 4 small button scene wallstation Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet WR5 Wireless umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 umber of zones per area 3 6 umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) EATO WaveLinx design and application guide 39
40 TITLE 4 06 TITLE 4 06: Retail example ly Switched O/ Lumen Maintenance O/ Auto Linear Dimming Module WaveLinx Relay 00V 00V lighting loads Out of the box 75% high end trim on to 50% Optional vacancy mode Plug load turns on with occupancy Individual luminaire daylight dimming to approximately 500 lux not required for indoor spaces without windows ot required in spaces without windows that are less than 0W Wireless Area ler Qty Catalog # Description Wireless Area ler 6 W4SLRLW WaveLinx 4 WSPMV00 WaveLinx Relay Switchpack with 00V dimming WR5 WaveLinx 4 LDCMPL07700VGR Linear Dimming Modules 3 4ELD34UVL835CDSWPDU Encounter x4 with WaveLinx s Top or dominant button half lights (sets lights to 50% or less) Remaining buttons trigger scenes Raise Lower Power measurement reporting through mobile application demand response available from wireless area controller Scheduling of partial off light levels and times from wireless area controller UL94 emergency control capabilities available via luminaire battery backup PoE etwork Switch provided by others Wireless Area ler Design Consideration Best Practice Maximum Gateway/Wireless Area ler range 50 feet to 50 feet LOS 300 feet LOS umber of interior walls walls 3 walls W4SRLW Wireless 4 small button scene wallstation 4ELD34UVL835CDSWPDU Encounter x4 recessed light fixture with 00V dimming Distance from Wireless Area ler to st WaveLinx device 50 feet 00 feet Distance between WaveLinx devices 75 feet 50 feet umber of hops from Wireless Area ler umber of areas per Wireless Area ler 4 hops 5 hops 6 6 WR5 Wireless WSPMV00 0A Relay w/ 00V Dimming LDCMPL0 7700VGR Linear Dimming Module umber of zones per area 3 6 umber of scenes per area 6 0 Local O O Bilevel Side Top Parking Garage Enhanced Digital T4 06 (a) (a) (c).6 (c).5 (c) (e) (e) 40 EATO WaveLinx design and application guide
41 Distributed LowVoltage Power System The lowvoltage system that s practically plug and play. o more struggling to find qualified electrical labor for your job site. o more waiting weeks for commissioning teams. o more compliance woes. Eliminate costly project delays with our groundbreaking Distributed LowVoltage Power System, and save up to 0% on the total installed cost of your LED lighting and controls system. Designed to meet the code requirements of your project The DLVP system was designed entirely with compliance in mind, to rid you of unnecessary project snarls. Combined with Eaton s highly efficient lowvoltage LED fixtures, integrated or external sensors drive energy efficiency throughout the building. Features like scene control, receptacle control, and automatic turnoff help you customize your system to meet your area s requirements, and can achieve energy savings of up to 65%. Code compliance, outofthebox Meets or exceeds the requirements of ASRAE/ASI/IES, IECC and Title 4 energy codes. Linevoltage in. Lowvoltage out. EATO Connected Codes 4
Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE
Guides for California Title 24 & ASHRAE Code Compliance Lightcloud Makes Compliance Easy What are California Title 24 & ASHRAE? Links to Energy Codes Interior Lighting Controls Exterior Lighting Controls
More informationWaveLinx Wireless Connected System
WaveLinx Wireless Connected System WaveLinx Wireless Connected System EATON POWER LIGHTING CONNECTIVITY SOFTWARE Unparalleled knowledge of electrical power management Advanced LED fixtures Communications
More informationDistributed Low-Voltage Power System. design and application guide
Distributed LowVoltage Power System design and application guide Cut ties with complexity Table of Contents Distributed LowVoltage Power System Distributed LowVoltage Power System 4 Features and benefits
More informationASHRAE October 18, 2013
ASHRAE 90.1 2010 October 18, 2013 Energy Consumption Buildings consume 40% of the primary energy and 71% of the electrical energy in the US. Driven by economic expansion and population growth that require
More informationDissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard & 2013
WHITE PAPER Dissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard 90.1-2010 & 2013 JUNE 2016 DT213 (Rev.10.2.17) Executive Summary ASHRAE Standard 90.1 is developed with the Illuminating Engineering
More informationLighting Control Strategies. to meet code requirements save energy and improve building performance
Lighting Control Strategies to meet code requirements save energy and improve building performance 1 Lighting Control Strategies Agenda Why Lighting Control Manual Light Reduction Scheduling Occupancy
More informationVive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015
Vive Solutions Commercial Application Guide Code Compliance Lighting Controls Table of Contents IECC IECC 2015 2015 Introduction Solutions Overview... 2 Summary of Code Requirements... 4 Daylight Zone
More informationVive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2012
Vive Solutions Commercial Application Guide Code Compliance Lighting Controls Table of Contents IECC IECC 202 202 Introduction Solutions Overview... 2 Summary of Code Requirements... 4 Daylight Zone Requirements...
More informationConnected Buildings Sales positioning guide
Connected Buildings Sales positioning guide * We make connected buildings work.* Make your workspace work for you. Eaton s connected lighting systems take the guesswork out of managing your facility, seamlessly
More informationANSI/ASHRAE/IES
Vive Solutions Commercial Application Guide Code Compliance Lighting Controls ANSI/ASHRAE/IES 90. 206 Table of Contents ASHRAE ASHRAE 90.-206 90.-206 Introduction Solutions Overview... 2 Summary of Code
More informationWSA120: New Energy Codes and Lighting Controls
WSA120: New Energy Codes and Lighting Controls Member Since 2003 1.0 AIA/CES Learning Units (HSW) Partner Since 1998 Brought to you by WattStopper Today s Presenter: Joe McGrath www.wattstopper.com Learning
More informationVive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015
Vive Solutions Commercial Application Guide Code Compliance Lighting Controls Table Table of of Contents Contents Introduction Solutions Overview... 2 Summary of Code Requirements... 4 Daylight Zone Requirements...
More informationANSI/ASHRAE/IES
Vive Solutions Commercial Application Guide Code Compliance Lighting Controls ANSI/ASHRAE/IES 90. 200 Table of Contents ASHRAE ASHRAE 90.-200 90.-200 Introduction Solutions Overview... 2 Summary of Code
More informationTITLE 24 ICONOGRAPHY. Iconography System
TITLE 24 ICONOGRAPHY Iconography System The icons symbolize specific language found in the code requirements. They represent product and space characteristics. Icons not only represent the requirements
More informationA. The wireless lighting control system shall be capable of providing all of the following functions for all lighting:
SECTION 260943.13 DIGITAL NETWORK LIGHTING CONTROLS WAVELINX WIRELESS LIGHTING CONTROL SYSTEM This specification was updated August 14, 2018 and supersedes all previous WaveLinx specifications. This section
More informationConnected Buildings Sales positioning guide
Connected Buildings Sales positioning guide * We make connected buildings work.* Make your workspace work for you. Eaton s connected lighting systems take the guesswork out of managing your facility, seamlessly
More informationCode Review TITLE PRESENTED BY POURIA NIKNAM
Code Review TITLE 24-2016 PRESENTED BY POURIA NIKNAM 2 Important Topics Partial-On as per Title 24 Definition and criteria for Daylight Responsive Control Controlled Receptacles Automatic Demand Response
More informationIECC. nlight Applications Guide.
IECC nlight Applications Guide www.acuitycontrols.com 2 Intro ACUITY CONTROLS It s not just smarter. It s easier. Acuity Controls is advanced lighting controls technology, service and support from a single
More informationMANDATORY MEASURES MANDATORY LIGHTING CONTROLS (a) Area Controls: Manual controls that control lighting in each area separately
MANDATORY MEASURES INDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130.1) MANDATORY LIGHTING CONTROLS 1. 130.1 (a) Area Controls: Manual controls that control lighting in each area separately
More informationMANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)
MANDATORY MEASURES INDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130.1) MANDATORY LIGHTING CONTROLS 1. Area Controls: Manual controls that control lighting in each area separately 2. Multi-level
More informationCalifornia s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings
California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings A Title 24 Code Review for Electrical Professionals By: Brian Friedel LEED AP brian.friedel@wattstopper.com
More informationINSPECTION REQUIREMENTS: ENERGY CODE LIGHTING & ELECTRICAL NON-RESIDENTIAL
Energy Code Lighting & Electrical Non-Residential Page 1 of 14 Revision Date: 2/12/2018 INSPECTION REQUIREMENTS: ENERGY CODE LIGHTING & ELECTRICAL NON-RESIDENTIAL INSPECTION CODE: N/A SCOPE: NON-RESIDENTIAL,
More informationA Guide for Applicants and Lighting Designers
Sustainable Office Design Program: A Guide for Applicants and Lighting Designers Inside this Guide: Introduction... 2 Organize Your Space... 3 Select Lighting Solutions... 4 Select Controls... 5 Open Offices...
More informationMini Product Guide.
Mini Product Guide www.acuitybrands.com/sensorswitch Better Performance Through Advanced Technology 100% Digital Passive Infrared (PIR) Detection Dual Technology Detection utilizing Microphonics Contractor
More informationvisual environment technologies etcconnect.com
visual environment technologies etcconnect.com About ETC ETC is a global leader in the manufacture of award-winning lighting-control systems, backed by our renowned /7/65 support. ETC offers complete solutions
More informationMANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)
MANDATORY MEASURES INDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130.1) MANDATORY LIGHTING CONTROLS 1. 130.1 (a) Area Controls: Manual controls that control lighting in each area separately
More informationHospitality Title Solutions
Hospitality Solutions Design Guide Crestron Electronics, Inc. Contents About 1 Design Guide Information 1 Code Standards 2 Guest Room 4 Zūm... 4 Guest Room Suite 5 Zūm... 5 Lobby 6 Zūm... 6 GLPP... 7 GLPAC
More information1. Section [ Lighting Control Panel Boards:] Lighting panels (switching) controlled by ControlKeeper
SECTION 260923 EATON DISTRIBUTED LOW-VOLTAGE POWER SYSTEM This specification was updated June 1, 2017 and supersedes all previous DLVP specifications. This section includes editing notes. These notes are
More informationRestaurants IECC 2015 Solutions
Restaurants IECC 2015 Solutions Design Guide Crestron Electronics, Inc. Contents About IECC 2015 1 Design Guide Information 1 IECC 2015 Code Standards 2 Dining Room 4 Zūm... 4 GLPAC... 5 Kitchen 6 Zūm...
More informationvisual environment technologies etcconnect.com
visual environment technologies etcconnect.com About ETC ETC is a global leader in the manufacture of award-winning lighting-control systems, backed by our renowned /7/65 support. ETC offers complete solutions
More informationdesign and application guide LumaWatt Pro powered by Enlighted
design and application guide LumaWatt Pro powered by Enlighted Connected Lighting simplified by Eaton Table of Contents Wireless Connected Lighting System LumaWatt Pro Connected Lighting System Connected
More informationCodes and Controls Commercial Building Energy Code Requirements for Light Control. Michael Jouaneh, CEM, LEED AP September 20, 2012
Commercial Building Energy Code Requirements for Light Control Michael Jouaneh, CEM, LEED AP September 20, 2012 Table of Contents What Code/Standard Does Your State Use?... 3 Mandatory Lighting Control
More informationEducation Title Solutions
Education Solutions Design Guide Crestron Electronics, Inc. Contents About 1 Design Guide Information 1 Code Standards 2 Classroom 4 Zūm... 4 GLPP... 5 Higher Education Classroom 6 Zūm... 6 GLPAC... 7
More informationNote: A summary of the applicable code sections is shown in the CEC _Table100A.
CALIFORNIA ENERGY COMMISSION 2016 Building Energy Efficiency Standards California Code of Regulations, Title 24, Part 6 Non-Residential Lighting Requirements Summary 3/27/2018 Scope: The California Title
More informationLumaWatt Pro Wireless Connected Lighting System powered by Enlighted
LumaWatt Pro Wireless Connected Lighting System powered by Enlighted LumaWatt Pro powered by Enlighted EATON POWER LIGHTING CONNECTIVITY SOFTWARE Unparalleled knowledge of electrical power management
More informationHealthcare Title Solutions
Healthcare Solutions Design Guide Crestron Electronics, Inc. Contents About 1 Design Guide Information 1 Code Standards 2 Operating Room 4 GLDALI... 4 GLPAC... 5 Patient Room / Exam Room 6 GLDALI... 6
More informationWaveLinx Outdoor Wireless Connected Lighting System
WaveLinx Outdoor Wireless Connected Lighting System WaveLinx Wireless Connected Lighting System EATON POWER LIGHTING CONNECTIVITY APPS / SOFTWARE Unparalleled knowledge of electrical power management Advanced
More informationLighting Application Guide for K-12 Classrooms
Lighting Application Guide for K-12 Classrooms Lighting Controls for Today's Classroom Commercial building energy codes contain detailed mandatory lighting control requirements related to buildings such
More informationRestaurants ASHRAE Solutions
Restaurants ASHRAE 90.1-2016 Solutions Design Guide Crestron Electronics, Inc. Contents About ASHRAE 90.1-2016 1 Design Guide Information 1 ASHRAE 90.1-2016 Code Standards 2 Dining Room 4 Zūm... 4 GLPAC...
More information2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG-1-A
2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) LTG-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR
More informationWireless Lighting Control Made Easy
Wireless Lighting Control Made Easy Wireless Lighting Control Made Easy David Orband Crestron Electronics This session is eligible for 1 Contact Hour. For these hours to appear on your certificate, you
More informationMetalux SWLED LED. Type. Catalog # Project. Date. Comments. Prepared by
DESCRIPTION is a versatile LED surface or wall mount luminaire which can be used in a broad range of commercial and industrial applications. This series provides customers with a high quality luminaire
More informationLighting Controls An Introduction and Review
Lighting Controls An Introduction and Review Prepared by Dialectic Controls Beyond Timeclocks and Contactors When designing the lighting for a space, there is always a debate concerning what lighting control
More informationOffice Title Solutions
Office Title 24-2016 Solutions Design Guide Crestron Electronics, Inc. Contents About Title 24-2016 1 Design Guide Information 1 Title 24-2016 Code Standards 2 Private Office Space / Huddle Space 4 Zūm...
More information1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.
Energy Conservation Code Commercial Electric CHAPTER 5 WORKSHEET 1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is. a.
More informationIndoor Controls. SpaceWise SWZG2. Wireless technology
Project: Indoor Controls SpaceWise SWZG2 Location: Cat. No: Type: Lamps: Notes: Qty: Philips luminaires with SpaceWise wireless technology SWZG2 are stand alone LED lighting systems with integrated occupancy
More informationAre LED s ready for Prime Time?
Tracy Beattie, LC, CLMC has been in the lighting industry since 1988. He was Lighting Certified by NCQLP in December 2013. He worked for a lighting distributor in the LA market until 2010 when he partnered
More information2015 IECC. Design Guide for Smart Lighting Control and Energy Solutions
205 IECC Design Guide for Smart Lighting Control and Energy Solutions Intellect Intelligent Fixture Control System out-of-the-box energy code and DLC compliant wireless plug-and-play system Provolt Room
More informationMANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130)
MANDATORY MEASURES INDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130) MANDATORY LIGHTING CONTROLS 1. Area Controls: Manual controls that control lighting in each area separately 2. Multi-level
More informationCalifornia Title Design Guide for Smart Lighting Control and Energy Solutions
California Title 24 206 Design Guide for Smart Lighting Control and Energy Solutions Leviton Excellence for Title 24 Standards California Title 24 206 provides the minimum requirements for energy-efficient
More informationCode Compliance Commercial Application Guide
Code Compliance Commercial Application Guide ASHRAE 90.1-2010 IECC 2012 Title 24-2013 Summary of code requirements for lighting control In the following pages, we ve provided examples of how Lutron solutions
More informationReduce lighting energy costs with controls
Reduce lighting energy costs with controls Reduce energy costs. Support sustainability Get control of your lighting. Upgrading lighting systems to next-generation lighting technologies can deliver energy
More informationLIGHTING CONTROLS
260923 LIGHTING CONTROLS PART 1: GENERAL 1.01 SUMMARY COMMENTS A. CU has developed this lighting control guideline to direct design professionals toward standard solutions that meet the University s performance
More informationilumin Plus design and application guide
ilumin Plus design and application guide Table of Contents Wired Connected Lighting System Solutions overview 4 Built-in energy saving lighting control strategies 5 ilumin Plus system and integration 6-7
More informationHere we see the list of auto shutoff controls we will cover in the next few slides
Here we see the list of auto shutoff controls we will cover in the next few slides 22 All installed indoor lighting: Shall be controlled with an occupant sensing control, automatic time switch control,
More informationHubbell Controls Application Guide to ASHRAE 90.1 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING CONTROL
Hubbell Controls Application Guide to ASHRAE 90.1 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING Hubbell Lighting s Commitment to the ASHRAE 90.1 Challenge Hubbell Lighting understands the challenge
More information1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.
2018 NC Energy Conservation Code Commercial Electrical Module 5 CHAPTER 4 [CE] WORKSHEET 1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the
More informationAesthetic, energyefficient. control solutions for hospitality facilities QUICK GUIDE TO LIGHTING CONTROL FOR HOTELS
Aesthetic, energyefficient lighting control solutions for hospitality facilities QUICK GUIDE TO LIGHTING CONTROL FOR HOTELS Table of Contents Introduction 3 Guest room 4-5 Guest bathroom 6-7 Public areas
More informationPower. Eaton is a registered trademark. All other trademarks are property of their respective owners.
Lighting Product Lines Commercial Portfolio Iris RSA Corelite Neo-Ray Fail-Safe MWS Ametrix Shaper io Lumark McGraw-Edison Invue Ephesus Lumière Streetworks AtLite Sure-Lites Get connected. Controls Product
More informationApplication Guide to CA Title 24
Application Guide to CA Title 24 A S U P P L E M E N TA L G U I D E TO C O D E R E V I S I O N S I M PAC T I N G L I G H T I N G C O N T R O L Hubbell Lighting s Commitment to the CA Title 24 Challenge
More informationWireless Indoor Lighting Control System
enabled by Lutron Wireless Indoor Lighting Control System Lutron the image company TM enabled by Lutron simple to specify simple to install simple to use 2 AirLink Simple to specify The flexibility you
More informationApplied Lighting Controls
Better Buildings By Design 2010 Applied Lighting Controls Steven Mesh, LC, IESNA Senior Lighting Program Coordinator Pacific Energy Center (Pacific Gas & Electric) 851 Howard Street, San Francisco, CA
More informationLighting Control Solutions for Parking Facilities
Lighting Control Solutions for Parking Facilities Control Safety, Connect Strategies, and Commission Zones Parking Lighting Strategies for Optimal Performance Historically, parking garage lighting was
More informationDecoding 2016 Title 24, Part 6
Decoding 2016 Title 24, Part 6 Let s Talk About Nonresidential Lighting Gina Rodda Gabel Associates, LLC gina@gabelenergy.com Nicole Graeber California Lighting Technology Center (CLTC) negraeber@ucdavis.edu
More informationRetrofitting Billingsley Company office spaces in Dallas, TX
Retrofitting Billingsley Company office spaces in Dallas, TX silvair.com Introduction To showcase the capabilities of Bluetooth mesh lighting networks in different types of office spaces, Silvair together
More informationFROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR
FROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR INNOVATION AND RELIABILITY THAT SPANS OVER 120 YEARS.
More informationMANDATORY MEASURES. There are two major steps for exterior spaces to comply with Title 24:
MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130.2) HOW TO COMPLY? There are two major steps for exterior spaces to comply with Title 24: 1. Meet all mandatory requirements
More informationPRESCRIPTIVE APPROACH
PRESCRIPTIVE APPROACH 1. Actual and Allowed LPD 2. Complete Building Method 3. Area Category Method 4. Tailored Method This section contains exercises for lighting power adjustments, Complete Building
More informationLighting Controls. Energy-Saving Solutions For Efficient Buildings
Lighting Controls Energy-Saving Solutions For Efficient Buildings Honeywell Lighting Controls Deliver Light When You Need It And Energy Savings When You Don t Businesses, schools and government facilities
More informationWireless Plug Load Control
General Specification Wireless Plug Load Control Model No.: PL20R & PLBPC Description:Enerlites Wireless Plug Load Controller is designed with simplicity, and helps to make plug load control requirements
More informationCA TITLE 24 QUICK SOLUTIONS GUIDE FOR
QUICK SOLUTIONS GUIDE FOR C TITLE 24 This guide is not intended to replace the code itself. It is meant to use as a quick solutions tool when complying with the new California Title 24 lighting requirements,
More informationVersatile wall switch sensors maximize payback and simplify code compliance
Versatile wall switch sensors maximize payback and simplify code compliance Commercial Wall Switch Occupancy Sensors MANUAL-ON MULTI-WAY NIGHTLIGHT Achieve the best energy savings for every wall switch
More informationRetrofit Solutions NEW. Energy-saving products for single rooms. Lutron energy-saving products. Patient Rooms. Office Spaces. Affordable Solutions
Lutron energy-saving products NEW Patient Rooms Office Spaces Educational Facilities Affordable Solutions New Wireless Products Energy Savings Government & Military Retrofit Solutions Energy-saving products
More informationLIVMODERN LIVMODERN RPT. Elegant linear LED fixture PART NUMBER BUILDER 10VDIM 0-10VDIMMABLE 3000K 4000K 24IN 36IN 48IN 1800LM* 3000LM** 3500LM***
LIVMODERN Elegant linear LED fixture Our most versatile and stylish linear fixture can be ceiling or wall mounted. The curved lens is secured to the fixture base using the stylish end-caps so that it cannot
More informationCeiling PIR HS presence detector. Product Guide. Overview. Features
Product Guide 796-2047 Ceiling PIR HS presence detector Overview The 796-2047 (passive infrared) presence detector provides automatic control of lighting loads with optional manual control. This is a high
More informationFCSENS0R Occupancy Sensor. Long Description. Manufacturer Information. Taxonomies, Classifications, and Categories
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 Catalog Number Manufacturer Description Weight per unit Product Category Descriptions Description Long Description Product
More informationDual Technology Wall Switch Occupancy Sensor. Manual & Specification
Dual Technology Wall Switch Occupancy Sensor Manual & Specification PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL ELECTRICAL CODES Douglas Lighting Controls Page 1 November 19, 2014 1. INTRODUCTION
More informationUBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical
More informationENERGY EFFICIENCY EXPERTS
ENERGY EFFICIENCY EXPERTS Sensors maximize energy savings by ensuring that lights are turned off or to a lower level when spaces are unoccupied or adequate daylight exists. WattStopper s sensors provide
More informationTable of Contents. Fast Fact. Sensor Models 2 Advantages of Sensors 3 FAQs 4-5
Sensor Buying Guide Table of Contents Sensor Models 2 Advantages of Sensors 3 FAQs 4-5 Occupancy and Vacancy Sensors, which provide automatic switching of lighting and motor loads, are fast becoming a
More informationUNIVERSAL LIGHTING OFFERS BREAKTHROUGHS FOR BOTH ANALOG AND DIGITAL DIMMING APPLICATIONS
UNIVERSAL LIGHTING OFFERS BREAKTHROUGHS FOR BOTH ANALOG AND DIGITAL DIMMING APPLICATIONS SuperDim and AddressPro provide dimming versatility and time-saving convenience SuperDim Analog Dimming Ballasts
More informationFixture Controller. Applications. Features. Specifications. Certifications & Affiliations. Catalog #: ALC/ALCE Part #: /
Project name Prepared by Date INDOOR AIRLINK LUTRON Catalog #: ALC/ALCE Part #: 624087/634480 The ALC/ALCE wireless fixture controller is a radio-frequency (RF) device that controls the 0 10V or Lutron
More informationSavings, control, and comfort without complexity
Controls Indoor SpaceWise DT Savings, control, and comfort without complexity Philips SpaceWise wireless technology DT, featuring dwell time functionality, is a flexible intuitive controls solution for
More informationDesign and Commissioning of Lighting Control Systems. Rick Miller, PE, LC, LEED AP RNM Engineering, Inc. October 18, 2012
Design and Commissioning of Lighting Control Systems Rick Miller, PE, LC, LEED AP RNM Engineering, Inc. October 18, 2012 Objectives Review the Cx process as it relates to lighting control. Emphasize the
More informationVESICA LINEAR SUSPENDED VES L
PROJECT INFORMATION Project Name Catalog # VESICA LINEAR SUSPENDED APPLICATIONS Office Spaces Conference Rooms Municipal Facilities Medical Facilities Type Date Financial Institutions Retail Spaces Hospitality
More informationArrow Hart. Universal Dimmers and Sensors. Eaton s Arrow Hart. Reliable lighting control for commercial installations
Eaton s Arrow Hart Commercial lighting controls Eaton s Arrow Hart Universal Dimmers and Sensors Reliable lighting control for commercial installations Arrow Hart Eaton s s and dimmers are cost -effective
More informationFrom the Originator and Leader in Integrated Motion Sensor Controls
From the Originator and Leader in Integrated Motion Sensor Controls DESIGNED BUILT BACKED IN THE USA Occu-smart allows for maximum energy savings. Energy use is as little as 3 watts in standby mode when
More information4SNLEDLD548SLUNV 4snledld548slunvl840cd1u
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 4SNLEDLD548SLUNV 4snledld548slunvl840cd1u Catalog Number Manufacturer Description Weight per unit Product Category Features
More informationF series. Complete Room Controller. echoflex Powered by ETC. Product Overview ERDRC-FC
echoflex Powered by ETC Complete Room Controller F series ERDRC-FC This guide covers the F series of the Complete Room Controller, model number ERDRC-FCU equipped with a 902 MHz radio. The box contents
More informationDual Relay Multi-Technology Wall Switch Occupancy Sensors
Dual Relay Multi-Technology Wall Switch Occupancy Sensors The OSSMD line of dual relay multi-technology Decora style wall switch occupancy sensors features several models to provide automatic lighting
More informationARCHITECTURAL DIMMING PANEL - MAIN/SECONDARY
WATTSTOPPER ARCHITECTURAL DIMMIG PAEL - MAI/SECODARY High capacity forward phase dimming capabilities LCAP44x up to 48 loads per panel up to 30,720 watts @ 120V; 70, 912 watts @ 277V LCAP32x up to 24 loads
More information2017 Michigan Energy Code Changes Electrical Provisions-Commercial Michigan Energy Code Training and Implementation Program
2017 Michigan Energy Code Changes Electrical Provisions-Commercial Michigan Energy Code Training and Implementation Program CP-17-00111 2.0 Hour Commercial Program Course Number Pending CP-17-00111 Presenters
More informationSupporting the Requirements of EPAct 2005 Tax Deductions
Energy Saving from Greengate Supporting the Requirements of EPAct 2005 Tax Deductions Energy Policy Act of 2005 Never before has the need for energy efficiency been so important, nor the benefits of energy-saving
More informationMANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)
MANDATORY MEASURES CONTROLS (Reference: Sub-Chapter 4, Section 130.2) ADDITIONS AND ALTERATIONS Over 50% replaced Mandatory Controls 130.0, 130.2, 130.4 + Prescriptive Requirements LPD allowances of 140.7
More informationF series. echoflex. Slim Line Dimming Controller. Product Overview ER1S-FC
echoflex Powered by ETC ER1S-FC Slim Line Dimming Controller F series This guide covers the F series of the Complete Room Controller, model number ER1S-FCU equipped with a 902 MHz radio. The box contents
More informationAdvanced Lighting Solutions
Advanced Lighting Solutions Ben Koyle, LC, LEED Green Assoc. April 20, 2017 Learning Objective Gain a better understanding of the energy savings potential of LED luminaires and networked lighting control
More informationPhilips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ Tel
2015 Koninklijke Philips N.V. All rights reserved. Philips reserves the right to make changes in specifications and/or to discontinue any product at any time without notice or obligation and will not be
More informationArrow Hart. Universal Dimmers and Sensors. Eaton s Arrow Hart. Reliable lighting control for commercial installations
Eaton s Arrow Hart Commercial lighting controls Eaton s Arrow Hart Universal Dimmers and Sensors Reliable lighting control for commercial installations Arrow Hart Eaton s sensors and dimmers are cost -effective
More informationESL-IC Smart Room Control
Smart Room Control Agenda Room Control fundamentals and evolution Challenges The Smart Room Control approach Benefits Market applications Typical Configurations Summary Room Control System Fundamentals
More informationBest practices in lighting design to comply with California s Title 24 energy code
2 0 1 3 T I T L E 2 4, P A R T 6 Residential Lighting Best practices in lighting design to comply with California s Title 24 energy code KELLY CUNNINGHAM Outreach Director California Lighting Technology
More information