TECHNICAL INSTRUCTIONS

Size: px
Start display at page:

Download "TECHNICAL INSTRUCTIONS"

Transcription

1 TECHNICAL INSTRUCTIONS 12-Month Maintenance Procedures These instructions apply to the following BMK boiler models (Standard & Dual Fuel): Benchmark 1.5LN Benchmark 2.0LN Benchmark 3.0LN Benchmark 750 Benchmark 1000 Benchmark 1500 Benchmark 2000 Benchmark 2500 Benchmark 3000 For AERCO Benchmark Boilers (Kit# ) DISCLAIMER The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including, but not limited to, implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual, nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of these materials. Revised 11/20/2014 VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 1 of 28

2 Table of Contents 1. GENERAL Maintenance Kit INFORMATION Annual Maintenance Procedure Overview Maintenance Kit Contents Kit Tools & Materials Requirements Tools Test Equipment Expendable Materials BMK1.5LN / 2.0LN / 3.0LN Preliminary Procedures Burner Maintenance BMK1.5/2.0/ Burner Maintenance Procedures - BMK3.0LN Igniter-Injector Replacement - BMK3.0LN Flame Detector Replacement - BMK Burner Maintenance - BMK1.5LN/2.0LN Igniter-Injector Replacement - BMK1.5/ Flame Detector Replacement - BMK1.5/ BMK750 & BMK Replacing the Igniter-Injector and Flame Detector Condensate Trap Maintenance BMK1500 & BMK Replacing the Igniter-Injector and Flame Detector Condensate Trap Maintenance BMK2500 & BMK Replacing the Igniter-Injector and Flame Detector Condensate Trap Maintenance Condensate Trap Maintenance All Models Condensate Trap Installation Locations Replacing the Condensate Trap O-Ring New Style Trap Replacing the Condensate Trap O-Ring & Orifice Gasket Old Style Trap Low Water Cutoff (Lwco) Integrity Test Low Water Cutoff (LWCO) - Capacitor Electrical Short Test Low Water Cutoff (LWCO) - Standard C-More Test Final Reassembly & Testing - ALL MODELS Reassembly and Set-Up Following Annual Maintenance Final Testing Following Annual Maintenance VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 2 of 28

3 1. GENERAL MAINTENANCE KIT INFORMATION 1.1 Annual Maintenance Procedure Overview The Annual Maintenance procedure includes the following actions: Replace igniter-injector and flame detector (with gasket). Clean and inspect the condensate trap. Replace trap O-ring (and orifice gasket for older style trap). Test the Low Water Cutoff (LWCO) probe for electrical shorts Maintenance Kit Contents The Annual Maintenance Kit P/N is comprised of the following components: Maintenance Kit Contents Flame Detector P/N (1 each) Igniter- Injector P/N (1 each) Flame Detector Gasket P/N (1 each) Condensate Trap O-Ring P/N (1 each) Condensate Trap Orifice Gasket P/N (1 each) P/N Annual Maintenance Kit Bill of Materials Item Qty P/N Description IGNITER/INJECTOR REPLACEMENT KIT: 1 x IGNITER-INJECTOR P/N x NUT, COMPRESSION P/N x WASHERS, CLOCKING (INDEXING) P/N x LUBRICANT, ANTI-SEIZE P/N Flame Detector Flame Detector Gasket Condensate Trap O-Ring Condensate Trap Orifice Gasket (0.25 I.D.) VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 3 of 28

4 The Igniter/Injector replacement assembly kit (P/N 58023) is comprised of the parts as shown in Figure 1. Figure 1: Igniter/Injector Assembly (P/N 58023) Components Kit Tools & Materials Requirements Tools Only common hand tools are required to perform the annual maintenance tasks described in this bulletin Test Equipment No test equipment is required to perform the annual maintenance tasks included in this Technical Service Bulletin. However, following completion of these tasks, the Benchmark Boiler should be tested using the combustion calibration procedures specified in the applicable O & M Manuals Expendable Materials The expendable materials required to perform the annual maintenance procedures described in this bulletin include such items as: Anti-seize lubricant (P/N 58023) for igniter-injector threads (included in replacement kit). Cleaning solvents and materials for cleaning condensate trap. WARNING! High voltages are used to power these boilers and so it is required that all power applied to these boilers is removed first before performing any of the procedures described in this document. Serious personal injury or death may occur if this warning is not observed. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 4 of 28

5 2. BMK1.5LN / 2.0LN / 3.0LN 2.1 Preliminary Procedures Prior to performing the procedures in sections 5 and 6, perform the following preliminary set-up and disassembly procedures: NOTE This section applies only to BMK1.5LN, BMK2.0LN, BMK3.0LN boilers using the integrated igniter/injector assembly (P/N 58023). 1. At the front panel of the unit, set the ON/OFF switch on the C-More Control Panel to the OFF position. 2. Disconnect electrical power to the unit by turning off the external circuit breaker. 3. Turn off the external gas supply shutoff valve. 4. Remove the top panel(s) of the unit. Benchmark 1.5LN and 2.0LN Models contain one (1) top panel. Benchmark 3.0LN Models contain two (2) top panels. See Figure Remove the side panels of the unit. Benchmark 1.5LN and 2.0LN Models contain one (1) panel on each side. Benchmark 3.0LN Models contain two (2) panels on each side. See Figure To prevent burns, allow the unit to cool to a safe temperature before proceeding. Figure 2-1: Removable Covers for BMK1.5/2.0 (Left) and BMK3.0 (Right) VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 5 of 28

6 2.2 Burner Maintenance BMK1.5/2.0/3.0 Annual maintenance for the Benchmark Low NOx burners consists of replacing the igniterinjector and the flame detector (with gasket) in the burner assembly. All Benchmark Low NOx models utilize identical igniter-injectors (P/N 66026) and flame detector (P/N 66006) with gasket, (P/N 81048). Two basic low NOx burner designs are used in Benchmark Low NOx Boiler Models: Benchmark 3.0LN burner assemblies utilize aluminum burner housings and a mesh burner insert. The igniter-injector and flame detector are installed on the outlet flange of the burner housing. Figure 2-2 and 2-3 show a Benchmark 3.0LN burner assembly. Benchmark 1.5LN and Benchmark 2.0LN burner assemblies use compact designs which also include the blower and air/fuel valve for their respective boiler models. Although the outward appearance of these two burner assemblies look virtually identical, the Benchmark 2.0LN utilizes a larger diameter steel burner plate and a longer burner insert than the Benchmark 1.5LN burner assembly. The Benchmark 1.5LN and 2.0LN burner assemblies are shown in Figure 2-4. A version with RSI (Regulated Staged Ignition) is shown in Figure 2-5 to show how the RSI line is attached to the Staged Ignition assembly. The igniter-injector replacement procedures for Benchmark 3.0LN model differs slightly from the replacement procedures for Benchmark 1.5LN and 2.0LN units. These differences are due to mounting orientations and replacement torque differences. However, the corresponding replacement procedures for Benchmark 1.5LN and 2.0LN models are in fact identical. Therefore, the burner maintenance procedures are divided into two (2) paragraphs. Paragraph 5.1 covers Benchmark 3.0LN model. Paragraph 5.2 covers Benchmark 1.5LN and 2.0LN models. Figure 2-2: Benchmark 3.0LN Burner Assembly Top View VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 6 of 28

7 Figure 2-3: BMK 3.0LN Burner Assembly Isometric View (Removed from Boiler) Figure 2-4: BMK 1.5LN and BMK 2.0LN Burner Assemblies (Removed from Boiler) VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 7 of 28

8 NOTE Newer BMK 1.5 and BMK 2.0 units may have an RSI (Regulated Staged Ignition) line installed at the Staged Ignition Assembly. Instructions for maintenance are the same. Figure 2-5 shows the configuration of the RSI on BMK 1.5 and BMK 2.0 boilers. Figure 2-5: BMK 1.5LN and BMK 2.0LN Burner Assemblies (Showing RSI Line Installed at Staged Ignition Assembly) 2.3 Burner Maintenance Procedures - BMK3.0LN Igniter-Injector Replacement - BMK3.0LN The igniter-injector is installed on the burner housing outlet flange as shown in Figures 2-2, 2-3, 2-4, 2-5, and 2-6. In addition to providing the ignition spark required to light the burner, this component also contains a gas injector tube which connects to the staged ignition assembly. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 8 of 28

9 Figure 2-6: Benchmark3.0LN Burner Assembly Front View Igniter-injector replacement for a BMK 3.0LN is accomplished as follows: 1. Disconnect the cable from the igniter-injector. 2. Using a 7/16 open-end wrench, disconnect the compression nut securing the gas injector tube of the igniter-injector to the elbow of the staged ignition assembly. Disconnect the staged ignition assembly from the igniter-injector. 3. Next, loosen and remove the igniter-injector from the burner housing using a 1" open-end wrench. 4. Prior to installing the replacement igniter-injector, high temperature, conductive, anti-seize lubricant must be applied to the igniter-injector threads. A small tube of this lubricant is included in the igniter-injector replacement kit (P/N 58023). NOTE The igniter-injector replacement kit (P/N 58023) contains a compression nut with a built-in ferrule. In addition, 3 clocking (indexing) washers are included. These washers may be needed to properly position the gas injector tube of the igniter-injector as described in the following step. 5. Install the replacement igniter-injector in the burner housing and hand-tighten. If necessary, use the indexing washers provided in the kit to properly position the gas injector tube within the 120 angle shown in Figure 2-7. Torque the igniter-injector to 80 to 90 in-lbs. However, if the burner housing was replaced just prior to replacing the igniterinjector, torque to 15 ft.-lbs., then loosen and re-tighten to 6.5 to 7.5 ft.-lbs. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 9 of 28

10 Figure 2-7: Benchmark 3.0LN Burner Assembly Partial Top View 7. Connect the staged ignition assembly to the gas injector tube of the igniter-injector by securing the compression nut to the elbow of the staged ignition assembly. Position the staged ignition solenoid so it is not contacting any other components of the burner assembly or heat exchanger. 8. Reconnect the igniter-injector cable. This completes the replacement of the igniter-injector Flame Detector Replacement - BMK3.0 Fire Detector and gasket replacement for the BMK 3.0LN is accomplished as follows: 1. Disconnect the lead wire from the flame detector. 2. Remove the two (2) screws securing the flame detector to the burner housing (Figure 2-6). The flame detector is secured to the burner housing with one (1) #10-32 screw and one (1) #8-32 screw. 3. Remove the flame detector and gasket from the burner housing flange. 4. Install the replacement flame detector (P/N 66006) and gasket (P/N 81048) provided in the maintenance kit. 5. Reconnect the flame detector wire lead. This completes the flame detector replacement. 2.4 Burner Maintenance - BMK1.5LN/2.0LN The burner maintenance procedures for the Benchmark 1.5LN and 2.0LN are identical. Replace the boiler igniter-injector and flame detector as described in paragraphs and respectively Igniter-Injector Replacement - BMK1.5/2.0 The igniter-injector is installed on the steel burner plate of each Benchmark 1.5LN and 2.0LN unit as shown in Figure 2-6. In addition to providing the ignition spark required to light the burner, this component also contains a gas injector tube which connects to the staged ignition assembly of each boiler. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 10 of 28

11 Igniter-injector replacement for the BMK 1.5LN and BMK 2.0LN is accomplished as follows: 1. Disconnect the cable from the igniter-injector. 2. Refer to the partially exploded view in Figure 2-8. Using a 7/16 open-end wrench, disconnect the compression nut securing the gas injector tube of the igniter-injector to the elbow of the staged ignition assembly. Disconnect the staged ignition assembly from the igniter-injector. Figure 2-8: BMK 1.5LN/2.0LN Igniter-Injector & Flame Detector Mounting Details 3. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end wrench. 4. Prior to installing the replacement igniter-injector, high temperature, conductive, anti-seize lubricant must be applied to the igniter-injector threads. A small tube of this lubricant is included in the igniter replacement kit (P/N 58023). NOTE The igniter replacement kit (P/N 58023) contains a compression nut with a built-in ferrule. In addition, 3 clocking (indexing) washers are included. These washers may be needed to properly position the gas injector tube of the igniter-injector as described in the following step. 5. Reinstall the igniter-injector in the burner plate. If necessary, install 1, 2 or 3 clocking washers to properly position the gas injector tube within the 120 angle shown in Figure 2-9. Torque the igniter-injector to 15 ft-lbs. Do not over tighten. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 11 of 28

12 Figure 2-9: Benchmark 1.5LN or 2.0LN Igniter-Injector Orientation 6. Connect the staged ignition assembly to the gas injector tube of the igniter-injector by securing the compression nut to the elbow of the staged ignition assembly. Position the staged ignition solenoid so it is not contacting any other components of the burner assembly or heat exchanger. 7. Reconnect the igniter-injector cable. This completes the replacement of the igniterinjector Flame Detector Replacement - BMK1.5/2.0 The flame detector (P/N 66006) and gasket (P/N 81048) are installed on the burner plate (see Figures 2-4, 2-5 and 2-8). Component replacement is accomplished as follows: 1. Disconnect the lead wire from the flame detector. 2. Remove the two (2) screws securing the flame detector to the burner plate (Figure 2-8). The flame detector is secured to the plate with one (1) #10-32 screw and one (1) #8-32 screw. 3. Remove the flame detector and gasket from the burner plate. 4. Install the replacement flame detector (P/N 66006) and gasket (P/N 81048) provided in the maintenance kit. Secure the detector in place using the two screws removed in step Reconnect the flame detector wire lead. This completes the flame detector replacement. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 12 of 28

13 3. BMK750 & BMK Replacing the Igniter-Injector and Flame Detector The instructions in this section show how to replace the igniter-injector, flame detector, and flame detector gasket for the BMK750 and BMK1000 boilers. Replacing the IGNITER-INJECTOR AND FLAME DETECTOR 1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from the unit by turning off power at the breaker. 2. Shut off the external gas supply valve to the unit. 3. Remove the panels from the top and sides of the unit, exposing the intake manifold and blower plenum. 4. Disconnect the electrical cable from the igniter-injector terminal (Figure 3-1). Blower Flame detector Flame detector Gasket O 2 Sensor Staged Ignition Solenoid Igniter-Injector Terminal Igniter-Injector Burner Plate Burner Upper Head Figure 3-1: Igniter-Injector & Flame Detector Locations 5. Use a 7/16 wrench to disconnect the compression nut securing the igniter-injector s gas injector tube to the elbow of the staged ignition assembly and then disconnect the staged ignition solenoid from the igniter-injector (Figure 3-2). O 2 Sensor Elbow Staged Ignition Solenoid Compression Nut Igniter Terminal Igniter-Injector Figure 3-2: Igniter-Injector Disassembly VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 13 of 28

14 Replacing the IGNITER-INJECTOR AND FLAME DETECTOR - Continued 6. Use a 1" wrench to remove the igniter-injector from the burner plate. 7. Disconnect the flame detector lead wire, remove the two (2) #10-32 Phillips head screws securing the flame detector to the burner plate (Figure 3-3), and then remove the flame detector and gasket and discard them. Retain screws for reassembly. Flame Detector Figure 3-3: Flame Detector Replacement Flame Detector Gasket 8. Install the new igniter-injector, included with the kit, onto the burner plate. Use zero to three indexing washers, as needed, so that the igniter-injector s gas injector tube is positioned within the 120 angle range shown below. Torque the igniter-injector to in-lbs. DO NOT over tighten. O 2 Sensor Gas Injector Tube 120 Igniter- Injector Figure 3-4: Igniter-Injector Orientation (viewed from above looking down) 9. Connect the igniter-injector s gas injector tube to the elbow of the staged ignition solenoid with the new compression nut, included with the kit. 10. Reconnect the igniter-injector cable. 11. Install the new flame detector and flame detector gasket, included with the kit, onto the burner plate, securing them with the Phillips head screws removed during disassembly (see Figure 3-3). 12. Reconnect the flame detector lead wire. 3.2 Condensate Trap Maintenance See Chapter 6 for condensate trap maintenance procedures. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 14 of 28

15 4. BMK1500 & BMK Replacing the Igniter-Injector and Flame Detector The instructions below replace the igniter-injector and flame detector. Replacing the IGNITER-INJECTOR AND FLAME DETECTOR 1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from the unit by turning off power at the breaker. 2. Shut off the external gas supply valve to the unit. 3. Remove the panels from the top and sides of the unit, exposing the intake manifold and blower plenum. 4. Disconnect the electrical cable from the igniter-injector terminal (Figure 4-1). Burner Plate O2 Sensor Flame Detector & Gasket Staged Ignition Solenoid Blower Plenum Igniter-Injector Figure 4-1: Gasket, Igniter-Injector & Flame Detector Locations 5. Disconnect the compression nut securing the igniter-injector s gas injector tube to the elbow of the staged ignition assembly and then disconnect the staged ignition solenoid from the igniter-injector. Discard the old compression nut. 6. Use a 7/16 wrench to disconnect the compression nut securing the igniter-injector s gas injector tube to the elbow of the staged ignition assembly and then disconnect the staged ignition solenoid from the igniter-injector. Staged Ignition Solenoid Igniter-Injector Elbow Compression Nut Indexing Washers (0-3 as needed) Figure 4-2: Igniter-Injector Disassembly Flame Detector VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 15 of 28

16 Replacing the IGNITER-INJECTOR and FLAME DETECTOR - Continued 7. Use a 1" wrench to remove the igniter-injector from the blower plenum and discard it. 8. Install the new igniter-injector, included with the kit, onto the blower plenum. Use zero to three indexing washers, as needed, so that the igniter-injector s gas injector tube is positioned within the 120 angle range shown below. Torque the igniter-injector to in-lbs. DO NOT over tighten. O 2 Sensor Gas Injector Tube 120 Igniter-Injector Figure 4-3: Igniter-Injector Orientation (viewed from above looking down) 9. Connect the igniter-injector s gas injector tube to the elbow of the staged ignition solenoid with the new compression nut, included with the kit. 10. Reconnect the igniter-injector cable. 11. Disconnect the flame detector lead wire. 12. Disconnect the flame detector lead wire and then remove the two (2) #10-32 Phillips head screws securing the flame detector to the blower plenum. Flame Detector Gasket Flame Detector Figure 4-4: Flame detector Replacement 13. Remove the flame detector and gasket from the blower plenum and discard them. 14. Install the new flame detector and flame detector gasket, included with the kit, fastening them with the #10-32 Phillips head screws removed in step Reconnect the flame detector lead wire. 4.2 Condensate Trap Maintenance See Chapter 6 for condensate trap maintenance procedures. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 16 of 28

17 5. BMK2500 & BMK Replacing the Igniter-Injector and Flame Detector The instructions below replace the igniter-injector (P/N 58023). Replacing the IGNITER-INJECTOR and FLAME DETECTOR 1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from the unit by turning off power at the breaker. 2. Shut off the external gas supply valve to the unit. 3. Remove the panels from the top and sides of the unit, exposing the intake manifold and blower plenum. 4. Disconnect the electrical cable from the igniter-injector terminal (Figure 5-1). Blower Plenum Staged Ignition Solenoid O2 Sensor Igniter-Injector Burner Plate Flame Detector & Gasket Figure 5-1: Igniter-Injector & Flame Detector Locations 5. Use a 7/16 wrench to disconnect the compression nut securing the igniter-injector s gas injector tube to the elbow of the staged ignition assembly and then disconnect the staged ignition solenoid from the igniter-injector. Staged Ignition Solenoid Igniter-Injector Indexing Washers (0-3 as needed) Figure 5-2: Igniter-Injector Disassembly Elbow Compression Nut Flame Detector VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 17 of 28

18 Replacing the IGNITER-INJECTOR and FLAME DETECTOR - Continued 6. Use a 1" wrench to remove the igniter-injector from the blower plenum and discard it. 7. Install the new igniter-injector, included with the kit, onto the blower plenum. Use zero to three indexing washers, as needed, so that the igniter-injector s gas injector tube is positioned within the 120 angle range shown below. Torque the igniter-injector to in-lbs. DO NOT over tighten. O 2 Sensor Gas Injector Tube 120 Igniter-Injector Figure 5-3: Igniter-Injector Orientation (viewed from above looking down) 8. Connect the igniter-injector s gas injector tube to the elbow of the staged ignition solenoid with the new compression nut, included with the kit. 9. Reconnect the igniter-injector cable. 10. Disconnect the flame detector lead wire. 11. Disconnect the flame detector lead wire and then remove the two (2) #10-32 Phillips head screws securing the flame detector to the blower plenum. Flame Detector Gasket Flame Detector Figure 5-4: Flame detector Replacement 12. Remove the flame detector and gasket from the blower plenum and discard them. 13. Install the new flame detector and flame detector gasket, included with the kit, fastening them with the #10-32 Phillips head screws removed in step Reconnect the flame detector lead wire. 5.2 Condensate Trap Maintenance See Chapter 6 for condensate trap maintenance procedures. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 18 of 28

19 6. CONDENSATE TRAP MAINTENANCE ALL MODELS There are two types of condensate traps in service; an older and a newer style. The instructions in this section apply ONLY to the NEWER style condensate trap. For the older-style trap, see the next section. 6.1 Condensate Trap Installation Locations Below are images of the condensate trap installations by model. Trap Installations BMK750 / 1000 / 1500 / 2000 / 2500 / 3000 EXHAUST MANIFOLD ADAPTOR THUMBSCREW UNION (OLD STYLE ONLY) 3/4 NPT NIPPLES TOP COVER THUMB SREWS (4) CONDENSATE TRAP (NEW STLE SHOWN) 3/4 NPT NIPPLE HOSE CLAMP TO FLOOR DRAIN 1 DIAM. HOSE Figure 6-1: BMK750 / Condensate Trap Installation ADAPTOR THUMBSCREW TOP COVER THUMB SREWS (4) EXHAUST MANIFOLD CONDENSATE TRAP (NEW STLE SHOWN) 3/4 NPT NIPPLE HOSE CLAMP TO FLOOR DRAIN 1 DIAM. HOSE Figure 6-2: BMK1500 / 2000 / 2500 / 3000 Condensate Trap Installation VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 19 of 28

20 Trap Installations BMK1.5LN / 2.0LN / 3.0LN Figure 6-3: BMK1.5LN - Older and Newer Condensate Trap Installations Figure 6-4: BMK2.0LN - Older and Newer Condensate Trap Installations Figure 6-5: BMK3.0LN - Older and Newer Condensate Trap Installations VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 20 of 28

21 6.2 Replacing the Condensate Trap O-Ring New Style Trap These instructions show how to replace the condensate trap O-ring (P/N 84017), located under the condensate trap s cover. The condensate trap is attached to the exhaust manifold s condensate drain pipe. Replacing the Condensate Trap O-Ring - New Style 1. Disconnect the external condensate trap from the exhaust manifold drain pipe by loosening the thumb screw on the trap inlet. 2. Remove the hose connection from the outlet side of the condensate trap. 3/4" NPT Port THUMB SCREWS (4) COVER CONDENSATE TRAP O-RING INLET FLOAT GUIDE FLOAT INLET ADAPTER INLET O-RINGS OUTLET Figure 6-6: Newer-Style Condensate Trap Cross Section 3. Loosen the four (4) thumbscrews securing the top cover to the condensate trap. 4. Remove the old O-ring from the trap. 5. Remove the float and attached float guide from the condensate trap. 6. Thoroughly clean the trap, float, and float guide. Also inspect the drain piping for blockage. If the trap cannot be thoroughly cleaned, replace the trap. 7. After the above items have been inspected and thoroughly cleaned, reassemble the float and float guide into the trap. 8. Install the new O-ring from the kit (P/N 84017). 9. Secure the top cover to the trap with the four thumb screws removed in Step Reassemble the drain hose connection to the outlet of the trap, and then reconnect trap inlet to the exhaust manifold drain by tightening the thumbscrew on the trap inlet. See Figure 6-1 through 6-5. Important! When reinstalling the condensate trap, ensure that the trap inlet is level with or below the condensate outlet of the boiler. Use a suitable support to insure that the bottom surface of the trap is horizontal and level. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 21 of 28

22 6.3 Replacing the Condensate Trap O-Ring & Orifice Gasket Old Style Trap These instructions explain how to replace the condensate trap O-ring (P/N 84017), located under the condensate trap s cover, the condensate trap orifice gasket (P/N 81092), and check and clean the trap. The condensate trap is attached to the exhaust manifold s condensate drain pipe using two nipples and a union. Replacing the Condensate Trap O-Ring & Orifice Gasket: Old Style 1. Disconnect the condensate trap from the exhaust manifold by removing the union between the connecting nipples (Figure 11). 2. Remove the drain hose connection from the outlet side of the condensate trap. 3. Loosen the four (4) thumbscrews securing the top cover to the condensate trap. Important! When reinstalling the condensate trap, ensure that the trap inlet is level with or below the condensate outlet of the boiler. Use a suitable support to insure that the bottom surface of the trap is horizontal and level. INLET ORIFICE GASKET OUTLET THUMB SCREWS (4) COVER CONDENSATE TRAP O-RING FLOAT GUIDE FLOAT Figure 13: Older-Style External Condensate Trap Cross Section 4. Remove the old O-ring from the trap and discard. 5. Remove the float and float guide from the condensate trap. 6. Remove the old orifice gasket from the trap and discard. 7. Thoroughly clean the trap, float, and float guide then inspect the drain piping for blockage. If the trap cannot be thoroughly cleaned, replace the trap. 8. After the above items have been inspected and thoroughly cleaned, install the new orifice gasket from the kit (P/N 81092), and then reinstall the float and float guide into the trap. 9. Install the new O-ring from the kit (P/N 84017). 10. Secure the top cover to the trap with the four thumb screws removed in Step Reassemble all piping and hose connections to the condensate trap inlet and outlet, and reconnect trap to exhaust manifold drain. See Figure 6-3 through 6-5. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 22 of 28

23 7. LOW WATER CUTOFF (LWCO) INTEGRITY TEST The LWCO probe features a capacitor assembly that should be tested for electrical shorts after performing all other annual maintenance tasks. The LWCO capacitor integrity test consists of two parts as described in the next two sections. The first procedure explains how to test for electrical shorting of the LWCO probe capacitor, while the second procedure instructs how to perform the standard Low Water Cutoff test using the C-More controls. The LWCO probe is located on the hot water outlet pipe of each BMK boiler model as shown in Figure 7-1. Hot Water Outlet Pipe Hot Water Outlet Pipe LWCO Probe BMK1.5LN Hot Water Outlet Pipe BMK2.0LN LWCO Probe BMK3.0LN LWCO Probe Hot Water Outlet Pipe Hot Water Outlet Pipe Hot Water Outlet Pipe LWCO Probe LWCO Probe BMK750 / 1000 BMK1500 / 2000 BMK2500 / 3000 LWCO Probe Figure 7-1: LWCO Probe Location for all BMK Boiler Models VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 23 of 28

24 Refer to Figure 7-2 for an illustration of the LWCO probe/capacitor assembly components. LWCO Probe LWCO Probe Terminal Plastic Acorn Nut Capacitor Assembly (Covered By Large Shrink Tubing) Connector (to Shell Harness) Figure 7-2: LWCO Probe Assembly Components 7.1 Low Water Cutoff (LWCO) - Capacitor Electrical Short Test This test determines if there is an electrical short between the LWCO capacitor and the heat exchanger. Perform the capacitor electrical short test as described below. 1. Turn OFF AC power to the unit. LWCO Capacitor Electrical Short Test WARNING! High voltages are used to power these units and so it is required that power applied to these units is removed first before performing the procedure described in this instruction. Serious personal injury or death may occur if this warning is not observed. (Continued) VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 24 of 28

25 LWCO Capacitor Electrical Short Test - Continued 2. Remove the Shell Harness Cable (male) connector from the P-5 (female) connector on the rear panel of the C-More controller (see Figure 7-3). Unplug Shell Harness Cable from P5 Connector Figure 7-3: Removing Shell Harness Cable from P5 Conn. on C-More Rear Panel 3. Using an ohmmeter, connect one ohmmeter probe to the LWCO capacitor terminal on the unit shell as shown on left in Figure Connect the second ohmmeter probe to Pin #6 of Shell Harness Connector (removed from the C-More controller) as shown on right in Figure 7-4. Connect 1 st Lead to LWCO Connect 2 nd Lead to PIN #6 Ohmmeter LWCO Probe Assembly 19-Pin Shell Harness Cable Connector Figure 7-4: Connecting Ohmmeter between LWCO Probe & Shell Harness Cable VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 25 of 28

26 LWCO Capacitor Integrity Test Cont. 5. Confirm that the ohmmeter does NOT read a short. NOTE If the ohmmeter reads a short, the capacitor assembly needs to be replaced. Replacement instructions can be found in the 24- Month Maintenance instructions or contact AERCO technical support for more information. 6. Remove both ohmmeter probes and reconnect the Shell Harness connector to the P5 connector on the rear of the C-More controller. 7.2 Low Water Cutoff (LWCO) - Standard C-More Test Perform the standard Low Water Cutoff test using the C-More controls as described below. 1. Turn on the AC power to the unit. Standard Low Water Cutoff C-More Test 2. Press the TEST switch on the C-More controller and confirm that the blinking "Low Water Level" message appears on the C-More display within 4 seconds. 3. Press the RESET key, followed by the Clear button, and confirm that the "Low Water Level" message is cleared. 8. FINAL REASSEMBLY & TESTING - ALL MODELS Upon completion of all annual maintenance tasks, reassemble the unit and perform the tests specified in paragraphs 7.1 and 7.2 of the appropriate manual. 8.1 Reassembly and Set-Up Following Annual Maintenance Following completion of the all required inspections and replacements, perform the following reassembly and setup procedures: 1. Turn ON the external circuit breaker to the unit. 2. At the front panel of the unit, set the ON/OFF switch on the C-More Control Panel to the ON position. 3. Press the LOW WATER LEVEL RESET button to reset the low water cutoff. 4. Press the CLEAR switch to reset the FAULT LED and clear any displayed error message. 5. Replace any sheet cover panels previously removed from the boiler. VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 26 of 28

27 8.2 Final Testing Following Annual Maintenance Upon completion of the annual maintenance procedures specified in this bulletin, perform the Combustion Calibration Tests specified in the applicable O & M Manual listed below: Benchmark Model Benchmark 1.5LN Benchmark 1.5LN, Dual-Fuel Benchmark 2.0LN Benchmark 2.0LN, Dual-Fuel Benchmark 3.0LN Benchmark 3.0LN, Dual Fuel Benchmark 750 / 1000 Benchmark 1500 / 2000 Benchmark 1500 / 2000 Dual-Fuel Benchmark 2500 / 3000 Benchmark 2500 / 3000 Dual-Fuel O & M Manual GF-120 GF-121 GF-123 GF-127 GF-116 GF-117 GF-130 GF-142 GF-144 GF-137 GF-145 VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 27 of 28

28 Change Log: Date Description Changed By 09/19/2014 Rev-A: Created Curtis Harvey 11/20/2014 Rev B: : removed item from kit and instructions in section 2.5 Chris Blair AERCO Technical Support: (Mon Fri, 8am-5pm EST) 1 (800) ( AERCO International, Inc., 2014 VD2: 11/20/2014 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York Phone: Page 28 of 28

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS 24-Month Maintenance Kit P/N 58025-06 For BMK2.0LN Boilers Description of Document: This TID provides the procedures to perform recommended 24-Month maintenance on the following

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS 24-Month Maintenance Kit P/N 58025-04 For BMK3.0LN Boilers Description of Document: This TID provides the procedures to perform recommended 24-Month maintenance on the following

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS Benchmark 3.0LN 24-Month Maintenance Kit# 58015-04 This kit applies to units with an Ignitor and a separate gas injector. For units with an Ignitor-Injector (P/N 58023), see Kit

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS Annual Maintenance Kit For Benchmark 750-1000 Boilers Maintenance Flame Detector P/N 66034 Ignitor- Injector P/N 58023 Gasket P/N 81048 Condensate Trap O-Ring P/N 84017 Condensate

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS 24-Month Maintenance Kit P/N 58015-02 For BMK2.0 (Nozzle Mix) Description of Document: This TID provides the procedures to perform recommended 24-Month maintenance on the following

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS Annual Maintenance Kit Instructions For Benchmark 6000 Boilers Kit Number 58025-11 Main Flame Detector P/N 65150 Ignitor Rod P/N 66100 Compression Nut with Ferrule 3/8 OD P/N 56071

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TID-0137_0A TECHNICAL INSTRUCTIONS AM Series Boiler Heat Exchanger Maintenance & Replacement For all models of AM Series Boilers, Including: Boilers: AM 399B AM 500B AM 750B AM 1000B Water Heaters: AM

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TID-0004_0A TECHNICAL INSTRUCTIONS Hardware Procedure: Coil and Riser Replacement Procedures for All Styles of A, B, C, and D Indirect-Fired Water Heaters Applies to: Indirect-Fire Water Heaters. Description

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS AERCO Serial Number & Code Plate Locations This document provides instructions for finding the serial numbers and code plates on AERCO products. Serial Number Sample Benchmark Code

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS Hardware Procedure: AERCO Buffer Tank Installation and Maintenance Applies to: Any applicable water heater/boiler piping system arrangement. Description of Document: This provides

More information

Detailed Cleaning Instructions

Detailed Cleaning Instructions NY Thermal Inc. Tel: (06) 67-6000 Toll Free: 1-800-688-27 Fax: 1-06-432-113 Web: www.ntiboilersl.com Email: info@ntiboilers.com Style Heat Exchanger occupants or, death. This boiler must be serviced by

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS Carbon Monoxide Detector Installation Instructions TECHNICAL INSTRUCTIONS Carbon Monoxide Detector Installation Instructions This document provides instructions for installing the Carbon Monoxide Detector

More information

Heat Exchanger Block Replacement Instructions

Heat Exchanger Block Replacement Instructions Series 1-4 Gas-fired water boiler Heat Exchanger Block Replacement Instructions Ultra-80 S1-4 Heat Exchanger Block Replacement Kit, Part No. 383-500-773 Ultra-105 S1-4 Heat Exchanger Block Replacement

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS AERCO Condensate Neutralization Tank For Neutralizing Condensate Waste from Gas Burning Boilers & Water Heaters Condensate Neutralizer Tank Kit PART DESCRIPTION Condensate Neutralization

More information

HX Field Replacement Kit

HX Field Replacement Kit Quantity Kit Part Number Description PE 110 Natural Gas Stainless Steel Condensate Pan PT 110 Natural Gas Polypropylene Condensate Pan Model PE 110 LP Stainless Steel Condensate Pan PT 110 LP Polypropylene

More information

STOP! Read this notice. STOP! Read before proceeding. These instructions are for gas conversion of the Evergreen boiler only.

STOP! Read this notice. STOP! Read before proceeding. These instructions are for gas conversion of the Evergreen boiler only. Series Identification Read the boiler rating label to determine the size and series number. CONDENSING GAS BOILER 220/299/300/399 Gas Conversion Instruction for Evergreen 220, 299/300 and 399 boilers Natural

More information

A HEATER KIT With Diesel Engine Connection Fittings

A HEATER KIT With Diesel Engine Connection Fittings A-12142 HEATER KIT With Diesel Engine Connection Fittings Figure 1 (General Layout and Parts I.D.) Page 1 of 6 Read these instructions and identify all components. Please retain these instructions for

More information

Installation Instructions for the PITCO Self-Cleaning Burner System

Installation Instructions for the PITCO Self-Cleaning Burner System IMPORTANT FOR FUTURE REFERENCE Please complete this information and retain these instructions for the life of the equipment: Model #: Serial #: Date Upgraded: Technician: Installation Instructions for

More information

VENTING APPLICATION GUIDE

VENTING APPLICATION GUIDE VENTING APPLICATION GUIDE Natural Gas or Propane Modulating & Condensing Boilers and Water Heaters This document applies to the following models: Boilers AM 399B AM 500B AM 750B AM 1000B Gas-Fired Boilers

More information

DRAIN WATER TEMPERING INSTALL

DRAIN WATER TEMPERING INSTALL 208/230 V DRAIN WATER TEMPERING KIT - 06401-002-59-99 460 V DRAIN WATER TEMPERING KIT - 06401-004-56-12 WARNING WARNING This kit should be installed only by qualified service personnel to reduce the risk

More information

INSTALLATION INSTRUCTIONS John Deere One Series; 1023E, 1025R and 1026R Models A HEATER KIT. Figure 1 (General Layout and Parts I.D.

INSTALLATION INSTRUCTIONS John Deere One Series; 1023E, 1025R and 1026R Models A HEATER KIT. Figure 1 (General Layout and Parts I.D. A-11978 HEATER KIT Figure 1 (General Layout and Parts I.D.) Read these instructions and identify all components. Please retain these instructions for future reference and parts ordering information. Refer

More information

MFC Series Boiler Vent and Combustion Air Guide

MFC Series Boiler Vent and Combustion Air Guide Pre-Installation Application Guide MFC Series Boiler Vent and Combustion Air Guide Applies to Models 3000 through 10000 Exhaust venting, combustion air and piping Requirements for MFC Series boilers Other

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists.

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists. Replacement parts Replacement parts must be purchased through a local Weil-McLain distributor. When ordering, specify boiler model and size and include description and part of replacement part. Results

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

Instruction Sheet LTR - Low Water Cutoff for Hot Water Boilers

Instruction Sheet LTR - Low Water Cutoff for Hot Water Boilers SUPERSEDES: Revision F Dated December 17, 2012 #5401179-REV G PLANT ID 001-3907 Instruction Sheet LTR - Low Water Cutoff for Hot Water Boilers Listings/Approvals EFFECTIVE: June1, 2017 102-338 UL GUIDE

More information

OR Replacement Instructions Heat Exchanger Assembly, ASME

OR Replacement Instructions Heat Exchanger Assembly, ASME NY Thermal Inc. Tel: (506) 657-6000 Toll Free: 1-800-688-2575 Fax: 1-506-432-1135 Web: www.nythermal.com Email: info@nythermal.com Applicable Boiler Models Ti100-150(C) (ASME Models) Ti200 Lx150(ASME Models)

More information

Product Support Bulletin

Product Support Bulletin MODEL: SUBJECT: CONVENTIONAL, W/ C7 CAT ENGINE WEBASTO TSL-17 HEATER Body DATE: APRIL 13, 2004 INDEX: 6 PAGE: 1 OF 16 Before you start this procedure, perform Freightliner Service Bulletin #20-7 first.

More information

HOT WATER BOILER ( MBH)

HOT WATER BOILER ( MBH) GAS-FIRED DIRECT VENT CONDENSING HOT WATER BOILER (25-200 MBH) Repair PARTS MANUAL P/N 24000523, Rev. C [09/08] TABLE OF CONTENTS I. Circulator Pumps (Optional)...2 II. Burner Assembly...3 III. Boiler

More information

Corn Flame Energy Corn Stove Model 3000

Corn Flame Energy Corn Stove Model 3000 Corn Flame Energy Corn Stove Model 3000 Installation and Operation Guide Read thoroughly before starting installation Save this manual for future reference SAFETY NOTICE If this stove is not properly installed,

More information

Installation Instructions

Installation Instructions ---751,---754,---755,---756 Condensing Heat Exchanger Kit Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation,

More information

INSTALLATION GUIDE Dual Fuel Ranges

INSTALLATION GUIDE Dual Fuel Ranges INSTALLATION GUIDE Dual Fuel Ranges Contents Wolf Dual Fuel Ranges......................... 3 Safety Instructions............................ 4 Dual Fuel Range Specifications.................. 5 Dual Fuel

More information

Ultra Boiler Series 1 & 2 Jacket Parts

Ultra Boiler Series 1 & 2 Jacket Parts GAS Ultra Boiler Series 1 & 2 Jacket Parts 9 10 8 6 7 1 5 2 3 Fig. Part Description Model Mfr. 1 383-500-135 Jacket Front Door 595-000-000 595-000-001 595-000-002 595-000-003 Panel Door Jacket Plastic

More information

NOZZLE MIX COMBINATION BURNER NMC200 SERIES

NOZZLE MIX COMBINATION BURNER NMC200 SERIES NOZZLE MIX COMBINATION BURNER NMC200 SERIES INSTRUCTIONS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its

More information

Single stage operation oil burner

Single stage operation oil burner Installation & Operating Manual Single stage operation oil burner WARNING NON-RETROFIT APPLICATIONS If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow

More information

Service Bulletin Trucks Date Number Page

Service Bulletin Trucks Date Number Page Mack Trucks, Inc. Allentown, PA USA (Does not apply to Mack Trucks Australia) (Supersedes SB215025 dated 03/27/07) Service Bulletin Trucks Date Number Page 11/04/08 SB215025 1(25) Cooling System Revisions

More information

Model SSV-399 GAS BOILER PARTS, KITS & OPTIONAL ACCESSORIES

Model SSV-399 GAS BOILER PARTS, KITS & OPTIONAL ACCESSORIES Model SSV-399 GAS BOILER PARTS, KITS & OPTIONAL ACCESSORIES Ordering Instructions Order Parts through your nearest supplier. When ordering parts, obtain Model Number and Serial Number from data plate on

More information

FIREPLACE INSTALLATION

FIREPLACE INSTALLATION CHECK GAS TYPE Use proper gas type for the fireplace unit you are installing. If you have conflicting gas types, do not install fireplace. See retailer where you purchased the fireplace for proper fireplace

More information

INSTALLATION OF DURAVENT POLYPRO SINGLE WALL POLYPROPYLENE VENTING SYSTEMS

INSTALLATION OF DURAVENT POLYPRO SINGLE WALL POLYPROPYLENE VENTING SYSTEMS SUPPLEMENT VENTING INSTRUCTIONS FOR INSTALLATION AND OPERATION INSTRUCTION MANUALS FOR THE FOLLOWING PRODUCT TYPES: HIGH EFFICIENCY CONDENSING COMMERCIAL, COMMERCIAL POWER DIRECT VENT, LIGHT DUTY COMMERCIAL

More information

Single stage operation oil burner

Single stage operation oil burner Installation & Operating Manual Single stage operation oil burner WARNING NON-RETROFIT APPLICATIONS If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow

More information

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists.

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists. gas-fired water boiler Manual Replacement parts Replacement parts must be purchased through a local Weil-McLain distributor. When ordering, specify boiler model and size and include description and part

More information

AFUE 95% Heating Input 50,000 to 200,000 Btuh

AFUE 95% Heating Input 50,000 to 200,000 Btuh PRODUCT SPECIFICATIONS WATER HEATERS / BOILERS GWM-IE Gas-Fired, Modulating, Condensing, Wall Hung Hot Water Boiler Bulletin No. 210650 March 2018 Supersedes December 2015 AFUE 95% Heating Input 50,000

More information

TopTier tm. Modular Brewing Stand. Operation, Assembly & Maintenance Manual

TopTier tm. Modular Brewing Stand. Operation, Assembly & Maintenance Manual TopTier tm Modular Brewing Stand Operation, Assembly & Maintenance Manual Congratulations on your purchase, and thank you for selecting the TopTier tm brewing stand from Blichmann Engineering. We are confident

More information

Power Direct Vent PDV(S&T) Models

Power Direct Vent PDV(S&T) Models COMMERCIAL REPLACEMENT PARTS LIST Power Direct Vent PDV(S&T) Models Includes Hydrojet Total Performance System Effective: January, 2012 ECO 7731 NOTE: BOTH MODEL AND SERIAL NUMBERS ARE REQUIRED FOR ORDERING

More information

USER MANUAL (1 of 2)

USER MANUAL (1 of 2) GF-205-LA INSTALLATION and STARTUP GUIDE Natural Gas, Propane Gas, or Dual Fuel Fired Modulating, Condensing Boilers 750, 1000, 1500, 2000, 2500, and 3000 MBH Boilers Initial Release: 01/02/2018 USER MANUAL

More information

GM9T SERIES 2-STAGE (STYLE B) UPFLOW NATURAL GAS FURNACES - 90%

GM9T SERIES 2-STAGE (STYLE B) UPFLOW NATURAL GAS FURNACES - 90% GM9T SERIES 2-STAGE (STYLE B) UPFLOW NATURAL GAS FURNACES - 90% HVAC SERVICE PARTS Supersedes: 035-20716-001 Rev. A (0205) 035-20716-001 Rev. B (1005) 1 of 8 Figure 1: UPFLOW 2-STAGE NATURAL GAS FURNACES

More information

Installation Manual. Models 99168, 99169, 99170

Installation Manual. Models 99168, 99169, 99170 Wet-Rated Globe Fitter Installation Manual Compatible with: 2xxxx Types A - Z 51000-58999 fan series 59500-59999 fan series Select Casablanca Fans Models 99168, 99169, 99170 BEFORE YOU BEGIN Read entire

More information

IMAGE V. Parts and Service Manual

IMAGE V. Parts and Service Manual IMAGE 0V Section II Parts and Service Manual (88B) CLARKE TECHNOLOGY Image Operator's Manual Page AUTHORIZED PERSONNEL MAINTENANCE To Access Pump Motor. Remove brush housing from machine. See "Brush Motor

More information

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL 3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL EFFECTIVE JULY 30, 2014 Superseding All Previous Parts Lists. The Company reserves the right to make substitution in the event that items specified

More information

CYCLONE XHE - MODEL BTH-300A/400A See Page 2

CYCLONE XHE - MODEL BTH-300A/400A See Page 2 POWERED ANODE ASSEMBLY See Page 8 COMMERCIAL WATER HEATER PARTS LIST Model BTH-300A Model BTH-400A Series 974/975 OPERATING CONTROL WIRING See Page 4 CYCLONE XHE - MODEL BTH-300A/400A See Page 2 GAS VALVE

More information

JOHN DEERE GATOR HPX/XUV 2 PASSENGER HEATER INSTALLATION INSTRUCTIONS (p/n: 9PH20S30)

JOHN DEERE GATOR HPX/XUV 2 PASSENGER HEATER INSTALLATION INSTRUCTIONS (p/n: 9PH20S30) P. 1 of 12 JOHN DEERE GATOR HPX/XUV 2 PASSENGER HEATER INSTALLATION INSTRUCTIONS (p/n: 9PH20S30) Item: Qty: Description: 1 2 1 x 1 x 5/8 Tee Fitting 2 2 Plastic Snap-in Hose Grommet 3 4 1-1/2" Hose Clamps

More information

PIPING APPLICATION GUIDE

PIPING APPLICATION GUIDE TAG-0074_0B Natural Gas or Propane Modulating & Condensing Boilers and Water Heaters PIPING APPLICATION GUIDE Applies to the following models: Boilers AM 399B AM 500B AM 750B AM 1000B 399 / 500 / 750 /

More information

ACQUITY UPLC HT Column Heater Instructions

ACQUITY UPLC HT Column Heater Instructions ACQUITY UPLC HT Column Heater Instructions Note: This document is an addendum to Revision C of the ACQUITY UPLC System Operator s Guide. Contents: Topic Page Overview 1 Connecting the cable 4 Installing

More information

Instruction Manual - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity

Instruction Manual - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity 100 PPD (2 kg/h) Chlorine or Sulfur Dioxide 250 & 500 PPD (5 & 10 kg/h) Chlorine or Sulfur Dioxide Anti-Siphon Ejector

More information

BOILER APPLICATION GUIDE for:

BOILER APPLICATION GUIDE for: T MFC Series Boiler Application Guide GF-148-B TECHNICAL APPLICATION GUIDE BOILER APPLICATION GUIDE for: Piping and Controls, Water Quality, and Single/Multi Installations Applies to MFC Series Models:

More information

9. Check condensate piping for sagging and/or leakage. Repair any sags or leaks before restoring power to the appliance.

9. Check condensate piping for sagging and/or leakage. Repair any sags or leaks before restoring power to the appliance. 77 Do not install the condensate assembly if a component is lost or missing. Replace the entire assembly. Failure to follow this warning could result in property damage, serious personal injury, or death.

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-1500T DUAL FUEL CONSTRUCTION HEATER

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-1500T DUAL FUEL CONSTRUCTION HEATER OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For F-1500T DUAL FUEL CONSTRUCTION HEATER CERTIFIED FOR USE IN CANADA AND U.S.A. As per Standard ANSI Z83.7 2000/ CSA 2.14 2000 Gas Fired

More information

USER MANUAL Installation, Operation, and Maintenance

USER MANUAL Installation, Operation, and Maintenance Covers all 1B+ II models including units with pneumatically controlled valve (Type CXT-P) or with an Electronic Control System (ECS) and electronically controlled valve (CXT-E): B+03 B+04 B+05 B+06 B+07

More information

Ti/Lx 150 ASME HX ASSEMBLY

Ti/Lx 150 ASME HX ASSEMBLY # NY Thermal Inc. Tel: (506) 657-6000 Toll Free: 1-800-688-2575 Fax: 1-506-432-1135 Web: www.nythermal.com Email: info@nythermal.com Installation Instructions Applicable Boiler Models Ti100 ASME Ti150(C)

More information

GV Series 4 Section Assembly

GV Series 4 Section Assembly GV Series 4 Section Assembly 192 Current Service Parts GV Series 4 Section Assembly Fig. No. Part No. Description Size Notes 1 322-200-280 Section Assembly, GV-3 (Repair Kit Required) 3 1 322-200-281 Section

More information

GM9V SERIES 2-STAGE VARIABLE SPEED UPFLOW CONDENSING NATURAL GAS FURNACES (1st Gen (Style D) and 2nd Gen, STYLE B)

GM9V SERIES 2-STAGE VARIABLE SPEED UPFLOW CONDENSING NATURAL GAS FURNACES (1st Gen (Style D) and 2nd Gen, STYLE B) www.source1parts.com HVAC SERVICE PARTS GM9V SERIES 2-STAGE VARIABLE SPEED UPFLOW CONDENSING NATURAL GAS FURNACES (1st Gen (Style D) and 2nd Gen, STYLE B) Supersedes: 035-21326-001 Rev. A (0207) 035-21326-001

More information

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER OPERATING MANUAL MODEL AIR 500TM AIR DRYER Puregas, LLC 226-A Commerce St. Tel: 800-52-535 Broomfield, Colorado Fax: 303-657-2205 P/N P0255 REV A, 02/9/4 TABLE OF CONTENTS.0 GENERAL... 3 2.0 SPECIFICATIONS...

More information

Description Model Weil-McLain part number. Vent Termination Kit for 3" Stainless Steel All

Description Model Weil-McLain part number. Vent Termination Kit for 3 Stainless Steel All Replacement parts Figure 96 Miscellaneous parts Description Model Weil-McLain part number Vent Termination Kit for 3" PVC All 383-500-397 Vent Termination Kit for 3" Stainless Steel All 382-200-430 Vent

More information

B-14G. for series number with jm or j

B-14G. for series number with jm or j B-G boilerless steamer REPLACEMENT PARTS LIST for series number with jm or j Effective june, 0 Superseding All Previous Parts Lists. The Company reserves the right to make substitution in the event that

More information

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System 1 Revised 11/18/10 2320 Lakecrest Drive, Pekin IL 61554 PH. (888) 747-4389 Fax (309) 495-0625 Website: www.getzequipment.com LIMITED

More information

Model 53 Macerator Pump Installation, Operation, Repair Manual

Model 53 Macerator Pump Installation, Operation, Repair Manual Model 53 Macerator Pump Installation, Operation, Repair Manual THE FOLLOWING ARE CAUTIONARY STATEMENTS THAT MUST BE READ AND FOLLOWED DURING BOTH INSTALLATION AND OPERATION WARNING: Raritan Engineering

More information

GM9S SERIES UPFLOW CONDENSING NATURAL GAS FURNACES (STYLE J)

GM9S SERIES UPFLOW CONDENSING NATURAL GAS FURNACES (STYLE J) www.source1parts.com HVAC SERVICE PARTS GM9S SERIES UPFLOW CONDENSING NATURAL GAS FURNACES (STYLE J) Supersedes: 035-21080-001 Rev. D (0207) 035-21080-001 Rev. E (0507) 1 of 12 31 29 26 5 10 39 69 24 11

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Bulletin 422 Model E Alarm Check Valve Bulletin 422 Instructions for Installation, Operation, Care and Maintenance DN100, DN150, DN200 SIZE Model E with E2 Euro Trim The Reliable Automatic Sprinkler Co.,

More information

WARNING. Failure to install this kit within the guidelines might adversely affect safety, performance, component life and warranty coverage.

WARNING. Failure to install this kit within the guidelines might adversely affect safety, performance, component life and warranty coverage. ! WARNING WARNING: This kit should be installed only by qualified service personnel to reduce the risk of electric shock, serious injury, or fire. A plumbing permit and the services of a licensed plumber

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVN/P-400 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per Standard ANSI Z83.7/CSA 21.4 2000 Gas Fired Construction

More information

Service Parts, Kits and Accessories

Service Parts, Kits and Accessories The parts identification guides on the following pages have been designed to give a quick reference to component parts used on pilot ignition agricultural building heaters. The guides identify components

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-400 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per CSA B140.8 Portable Oil Fired Heaters / CSA B140.02003

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Web Site: http//www.atomic4.com e-mail: thomas.stevens@cox.net INSTALLATION INSTRUCTIONS INDIGO ELECTRONICS AT-4T THERMOSTAT KIT ATOMIC 4 - ELECTRIC FWC This Indigo Thermostat Kit is designed for use with

More information

USER MANUAL (1 of 2)

USER MANUAL (1 of 2) GF-205 INSTALLATION and STARTUP GUIDE Natural Gas, Propane Gas, or Dual Fuel Fired Modulating, Condensing Boilers 750, 1000, 1500, 2000, 2500, and 3000 MBH Boilers Latest Update: 11/29/2017 USER MANUAL

More information

DF400/DF600. Construction Heaters. Installation and Maintenance Manual

DF400/DF600. Construction Heaters. Installation and Maintenance Manual 342 N. Co. Rd. 400 East Valparaiso, IN 46383 219-464-8818 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. DF400/DF600 Construction

More information

FC9V SERIES 2-STAGE VARIABLE SPEED UPFLOW CONDENSING NATURAL GAS FURNACES (1st Gen, Style D and 2nd Gen, Style B)

FC9V SERIES 2-STAGE VARIABLE SPEED UPFLOW CONDENSING NATURAL GAS FURNACES (1st Gen, Style D and 2nd Gen, Style B) www.source1parts.com HVAC SERVICE PARTS FC9V SERIES 2-STAGE VARIABLE SPEED UPFLOW CONDENSING NATURAL GAS FURNACES (1st Gen, Style D and 2nd Gen, Style B) Supersedes: Nothing, See Back 035-21322-001 Rev.

More information

CSD-1 COMMERCIAL BOILER CONTROLS

CSD-1 COMMERCIAL BOILER CONTROLS SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS CSD- COMMERCIAL BOILER CONTROLS P/N 400043, Rev. A [/03] CSD- COMMERCIAL BOILER CONTROLS! WARNING Fire, explosion, asphyxiation and electrical shock

More information

Benchmark 2.0LN Gas Fired Low NOx Boiler System

Benchmark 2.0LN Gas Fired Low NOx Boiler System Benchmark 2.0LN Low NOx Gas-Fired Boiler USER MANUAL GF-0LN OMM-0023_0A Applicable To Serial Numbers G-05-393 and above Benchmark 2.0LN Gas Fired Low NOx Boiler System Condensing, Modulating Forced Draft,

More information

INSTALLATION GUIDELINES

INSTALLATION GUIDELINES IMPORTANT: To ensure this product is installed properly, you must read and follow these guidelines. The owner/user of this product must keep this information for future reference. This product must be

More information

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual Armstrong J Series, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual This bulletin should be used by experienced personnel as a guide to the installation

More information

Oil TRIANCO. EuroStar Range BURNER DETAILS TRIANCO - OIL BURNER. To be retained by householder

Oil TRIANCO. EuroStar Range BURNER DETAILS TRIANCO - OIL BURNER. To be retained by householder TRIANCO Oil TRIANCO - OIL BURNER BURNER DETAILS EuroStar Range To be retained by householder TECHNICAL DATA NOZZLE OUTPUT MODEL Output Burner Nozzle Pump Model pressure CO 2 (%) EUROSTAR UTILITY 50/65

More information

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS Replacement parts Figure 92 Propane conversion kits and instructions Boiler model DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE The WM97+ maintenance kit includes components that

More information

Please read this manual completely before attempting to install, operate or service this equipment.

Please read this manual completely before attempting to install, operate or service this equipment. Service Manual POWER OVEN OFF COOL DOWN COOK LIGHT OFF OVEN READY TEMPERATURE GAS CONVECTION OVEN TIME GAS SHUTOFF ON OFF MODELS 6/13 THE OVEN E SERIES Please read this manual completely before attempting

More information

Installation Instructions Part No , Part No Part No

Installation Instructions Part No , Part No Part No Torsion-Flex Motor mount for PSC motors and Rigid-Mount for ECM motors Replacement Kit Cancels: New Installation Instructions Part No. 327752-401, Part No. 327753-401 Part No. 327754-401 IIK-310A-45-11

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-200 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per CSA B140.8 Portable Oil Fired Heaters / CSA B140.02003

More information

COMPRESSED AIR DRYER. SAFETY... Page 2 MAINTENANCE... Page 5. INSTALLATION... Page 3 PARTS AND KITS... Page 6

COMPRESSED AIR DRYER. SAFETY... Page 2 MAINTENANCE... Page 5. INSTALLATION... Page 3 PARTS AND KITS... Page 6 OWNERS MANUAL BOSS COMPRESSED AIR DRYER Distributed by Air & Vacuum Process, Inc. Phone: 281-866-9700 Fax: 281-866-9717 Email: sales@airvacuumprocess.com SAFETY... Page 2 MAINTENANCE... Page 5 INSTALLATION...

More information

WARNING DESCRIPTION PART NUMBER QTY PLUMBING, DYNATEMP DRAIN QUENCH BRACKET, THERMOSTAT DRAIN QUENCH

WARNING DESCRIPTION PART NUMBER QTY PLUMBING, DYNATEMP DRAIN QUENCH BRACKET, THERMOSTAT DRAIN QUENCH ! WARNING WARNING: This kit should be installed only by qualified service personnel to reduce the risk of electric shock, serious injury, or fire. A plumbing permit and the services of a licensed plumber

More information

FL9M SERIES MODULATING CONDENSING UPFLOW NATURAL GAS FURNACES (STYLE A)

FL9M SERIES MODULATING CONDENSING UPFLOW NATURAL GAS FURNACES (STYLE A) www.source1parts.com HVAC SERVICE PARTS FL9M SERIES MODULATING CONDENSING UPFLOW NATURAL GAS FURNACES (STYLE A) Supersedes: 035-21211-001 Rev. C (1106) 035-21211-001 Rev. D (0708) 1 of 8 33 31 5 10 41

More information

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314)

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314) DRY AIR SYSTEMS, INC. 2655 Metro Boulevard Maryland Heights, Missouri 63043 (314) 344-1114 fax (314) 344-0677 HD SERIES DRIERS TABLE OF CONTENTS WHY AN AIR DRYER 3 WHAT IS A DESICCANT AIR DRYER 3 Desiccant

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-400TRLT INDIRECT FIRED HEATER TRAILER

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-400TRLT INDIRECT FIRED HEATER TRAILER OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-400TRLT INDIRECT FIRED HEATER TRAILER CERTIFIED FOR USE IN CANADA AND U.S.A. As per CSA B140.8 Portable Oil Fired Heaters / CSA

More information

Installation Instructions Part No

Installation Instructions Part No Heat Exchanger Cell Kit Cancels: New Installation Instructions Part No. 326600-751 IIK-310A-45-6 6-02 NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Installing

More information

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING FLAME115 INFRARED HEATER SERVICE MANUAL INDEX 1. CONTROLS AND COMPONENTS 2. FLAME CONTROL CYCLES 3. MAINTENANCE SCHEDULE 4. TROUBLESHOOTING GUIDE 5. REPAIR PROCEDURES 1. FAN MOTOR ASSEMBLY 2. FUEL FILTER

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION ELECTRIC HEAT S THRU 05 5 THRU Supersedes: (9) (00) 0-5 FOR SINGLE PACKAGE CONDITIONERS THRU TON SINGLE PACKAGE HEAT PUMPS THRU 5 TON GENERAL This instruction contains all the

More information

INSTRUCTION BULLETIN

INSTRUCTION BULLETIN INSTRUCTION BULLETIN No. 340853 Machine: M20 / T20 Published: 12-2015 Rev. 03 NOTE: DO NOT DISCARD the Parts List from the Instruction Bulletin. Place the Parts List in the appropriate place in the machine

More information

INSTALLATION INSTRUCTIONS # BURNER ASSEMBLY REPLACEMENT

INSTALLATION INSTRUCTIONS # BURNER ASSEMBLY REPLACEMENT INSTALLATION INSTRUCTIONS # 00-858726 BURNER ASSEMBLY REPLACEMENT C24GA BURNER ASSEMBLY REPLACEMENT Verify steamer has a K3 relay (1, Fig. 1) installed. If K3 relay is not in steamer, one must be installed

More information

PS9 SERIES (STYLE B) UPFLOW NATURAL GAS FURNACES - 90%

PS9 SERIES (STYLE B) UPFLOW NATURAL GAS FURNACES - 90% PS9 SERIES (STYLE B) UPFLOW NATURAL GAS FURNACES - 90% HVAC SERVICE PARTS Supersedes: 035-20712-001 Rev. B (1005) 035-20712-001 Rev. C (1105) 1 of 12 Figure 1: UPFLOW NATURAL GAS FURNACES (90%) FIG ITEM

More information

Low Water Cutoff (LWCO) IQ Option Card p/n , for Hot Water Boilers

Low Water Cutoff (LWCO) IQ Option Card p/n , for Hot Water Boilers Low Water Cutoff (LWCO) IQ Option Card p/n 102711-01, 102714-01 for Hot Water Boilers Instruction Sheet 102-360 APPLICATION The Low Water Cutoff (LWCO) IQ Option Cards are advanced, microprocessor based

More information

LNB 1000 Series Low Nox Burner

LNB 1000 Series Low Nox Burner Installation and Service Instructions ARNIN: If the information in these instructions is not followed exactly, a fi re or explosion may result, causing property damage, personal injury or death. In the

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

Installation and Maintenance "L" and "LS" Series

Installation and Maintenance L and LS Series Installation and Maintenance "L" and "LS" Series IB-43-E This bulletin should be used by experienced personnel as a guide to the installation and maintenance of "L" and "LS" Series ultra capacity float

More information