1 Center for Life Safety Education Fire Sprinklers 101 Introduction, Building Codes, and Water Supplies Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National Fire Protection Association, Quincy, MA This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. Things to Know Before You Even Open NFPA 13
2 Three CRITICAL Considerations 1. Choosing the Correct Sprinkler Standard: NFPA 13/13R/13D 2. Water Supply & Arrangement appropriate to the selected standard and adequate to meet the system demand for flow and pressure 3. Occupancy Classification though not yet discussed in detail, Occupancy Classifications per NFPA 13 are not the same as those found in the Building Code but they drive decisions about sprinkler system design 2
3 Introduction Sprinklers & Sprinkler Systems Sprinklers and sprinkler systems are relatively simple in nature but with an incredible track record for success in fire control or even suppression in many cases. Sprinkler heads are individually heat activated devices, which when connected to a system of pipes, can deliver water directly to a fire area. Added benefits include the ability to attach alarm signaling devices to indicate water flow in a system 3
4 Sprinkler System Demand The sprinkler system is not designed to deliver water to the entire building at the same time but rather it is designed to deliver a specific volume of water to a specifically selected floor area. This area corresponds to a set of prescribed density/area curves found in NFPA 13. These curves relate to Occupancy Uses, Storage Arrangements or Special Occupancy Uses defined in NFPA 13 4 Building Floor Plan on Site
5 Big Picture System Demand vs Water Supply 1 - Water Supply Curve 2A - Hose Demand 2B - Sprinkler Demand P = psi and Q = gpm 5
6 SPRINKLER DESIGN & SUBMITTAL CHALLENGES Fire Sprinkler work is normally a design-build function where the contractor must determine the design criteria, prepare a layout of the piping system taking into account the structure, other system components and a critical evaluation of the water supply. Even when a specification is provided, the bidding sprinkler contractor must verify every aspect of the design prescribed before proceeding 6
7 Submittal Requirements All model codes require an applicant to submit plans for review and approval prior to starting work on new or remodeled systems. UFC/NFPA 1 - Section 1.1 IBC Section NFPA Section NFPA 13 Section & NFPA 13 is the standard for the Installation of Sprinkler Systems. 7
8 Submittal Plans & Related Items You should expect to see a minimum of three sets of plans, plus related Hydraulic Calculations Catalog Cut Sheets for equipment Seismic Calculations for bracing in Earthquake Zones 8
9 The Authority Having Jurisdiction NFPA defines the AHJ as an individual or organization having authority to accept or reject the system or its components. There is almost always more than one AHJ on any project including the Owner or Developer, an Insurance Carrier and of course, the municipal authority 9
10 Levels of Acceptability While both the code enforcement official and the insurance company can be considered authorities having jurisdiction under the NFPA definition, Insurance carriers are interested in protecting their risk in terms of exposure and liability they often do this by modifying rates charged to cover a building and it s contents. They are not enforcing an adopted code, which is the responsibility of the Municipal AHJ. 10
11 Sources of Info or Help NFPA 13 Handbook provides commentary along with Annex materials on the same page along with corresponding text. questions to: AFSA Technical Services Department via e mail or telephone AFSA sponsored Sprinkler Forum then click on link. 11
12 Informal Interpretations Committee members may be contacted for informal interpretations of a standard. AFSA offers direct assistance through multiple sources available at: 12
13 Formal Interpretations Formal Interpretations require canvassing of the entire committee - followed by a review period and a 2 nd vote of committee members Formal Interpretations take months to process often times, a project is completed before an answer is provided. 13
14 ROP & ROC Reports The Technical Committee meetings produce reports addressing each proposal submitted to a committee and their actions with comments on each proposal Often, these reports can offer insight to the committee s intent on a given subject which would be the same result as a canvassing for a formal interpretation. 14
15 Codes and Standards Building & Fire Codes direct WHERE and WHEN Standards tell us WHAT and HOW WHEN: By occupancy and size Trade-offs Not required - still must comply 15
16 Sprinkler Standards NFPA 13 D The Standard for One & Two Family Dwellings and Manufactured Homes NFPA 13 R The Standard for Residential Occupancies Up To and Including Four-Stories in Height NFPA 13 The Standard for Installation of Fire Sprinkler Systems Decisions are also driven by the Building Code 16
17 Code Issues for 13R Trades-offs Few restrictions Basements and building height Ignored Mixed Occupancies Not allowed 17
18 Codes & Standards HOW systems are installed. IBC does provide some installation criteria: Type V and balconies for 13R Seismic and secondary water supply WHERE installed Limited / Partial / Throughout Omission of protection (full 13 system) NFPA 13 IBC - Chap 9 A building is considered to be sprinklered through-out even with omission of sprinklers from specific allowable areas (including NFPA 13R) 18
19 Water Supplies - General Every automatic sprinkler system must have at least one source of reliable, automatic water supply. Most common is the municipal water supply connection The prescribed method of connection to a water supply varies between NFPA 13, 13R and 13D 19
20 Water Supply - 13D 20 Preferred 13D Water Supply Reprinted with permission from NFPA 13D, Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, Copyright 2007, National Fire Protection Association, Quincy, MA This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. 20 Acceptable & Most Common Arrangement
21 NFPA 13D - Purpose To provide a sprinkler system that aids in the detection and control of residential fires and thus provides improved protection against injury, life loss, and property damage. A sprinkler system designed and installed in accordance with this standard shall be expected to prevent flashover (total involvement) in the room of fire origin, where sprinklered, and to improve the chance for occupants to escape or be evacuated. The layout, calculation, and installation of systems installed in accordance with this standard shall only be performed by people knowledgeable and trained in such systems. 21
22 NFPA 13D Water Supply Requirements Systems designed per NFPA 13D are required to have a 10- minute (minimum) water supply. The basis for design is to calculate a discharge rate of water flow at the two sprinklers that are most remote or farthest from the water source. The flow required is calculated at a predetermined pressure, based upon the manufacturer s catalog cut sheet. NFPA 13 D systems are considered successful when all occupants of the residence are safely evacuated from the home, even if the building burns to the ground. 22
23 NFPA 13R For residential buildings up to and including 4-stories in height only This standard is also a life-safety system intended to prevent flashover and provide time for residents to escape the building and some PROPERTY protection. Many areas of a building required to be protected in a building designed to the NFPA 13 standard are omitted from the 13R designed system, such as attics, small closets and small bathrooms. 23
24 Water Supply 13R 24 Preferred 13R Water Supply Reprinted with permission from NFPA 13R, Installation of Sprinkler Systems in Residential Occupancies Up To and Including Four Stories in Height, Copyright 2007, National Fire Protection Association, Quincy, MA This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. 24 Acceptable 13R Water Supply
25 NFPA 13R Water Supply Arrangements Water Supply main piping installed per the IPC only NFPA 24 and/or NFPA 13 requirements for underground pipe installation do not apply to NFPA 13 R system water supplies. The allowance is intended to keep costs down and make life safety systems more affordable and reasonable for developers and end users. 25
26 NFPA 13 NFPA 13 provides minimum requirements for the design and installation of automatic fire sprinkler systems and exposure protection sprinkler systems. This is an important distinction because much is left to the designer, the Owner and the AHJ to determine and agree upon in order to determine an appropriate level of protection. Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National Fire Protection Association, Quincy, MA This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. 26
27 NFPA 13 Scope & Purpose To provide a reasonable degree of protection for life and property from fire through standardization of design, installation, and testing requirements for sprinkler systems, including private fire service mains, based on sound engineering principles, test data, and field experience. NFPA 13 is primarily a prescriptive-based standard 27
28 About NFPA Standards NFPA Standards and Codes are consensus-based documents, meaning that all users are invited to participate in the process by submitting proposals for changes to the document. The proposal form is the last printed page of every NFPA standard. Each proposal is reviewed and considered by the appropriate committee, with public comment periods provided to insure a fair review of every proposal and comment. 28
29 NFPA 13 Water Supply Requirements The water supply for a system designed for NFPA 13 requirements is based upon the design criteria established for an Occupancy Classification, a Storage Application or a Special Design Criteria selection as decided by the designer of the system The amount of water needed is determined by hydraulically calculating the volume of water needed to deliver a prescribed density to an area of coverage and determining the amount of pressure needed to deliver the water volume. This demand for water and pressure is compared to the available water supply to ensure an adequate amount of water is available for the system to function as designed. 29
30 Flow Test Data Verify that water supply exceeds system demand (D x A + Hose Allowance = minimum flow) Verify flow test information Who provided the data or who performed the test; was it witnessed or not witnessed? How old is the test data most AHJ s require a test be within 6 or 12 months. 30
31 Water Supply Considerations A flow test must be conducted to determine the available water supply, which is plotted on a graph. The flow test must consider: Location and elevation of test gauge Flow location Static pressure Residual pressure Flow Date, time Other sources of water supply, such as water storage tanks. 31
32 Flow Test Data Critical Consideration: Location of test relative to point of connection Make sure the water supply is from the same water main as the one being connected to Elevation of test versus system point of connection.433 psi per ft of elevation change 32
33 Water Supply Flow Test Procedures For further information on water supply testing, see NFPA 291, Recommended Practice for Fire Flow Testing and Marking of Hydrants. NFPA 13 Annex B also provides data on water supply testing Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National Fire Protection Association, Quincy, MA This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. 33
34 Safety Margin (10%) Water supplies change with time and wear and occupancies change as well As communities develop, available water supplies change A safety margin is recommended though the value of that margin will vary by circumstance and community 34
Sprinkler Permit Applications
REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations
More informationReview of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings
Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured
More informationSTATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT
STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device
More informationPLAN REVIEW CHECKLIST
PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor
More informationCommittee Input No. 28-NFPA 13R-2013 [ Global Input ]
Page 1 of 6 Committee Input No. 28-NFPA 13R-2013 [ Global Input ] 6.2.2 Outside Dwelling Units. 6.2.2.1 All sprinklers used outside of the dwelling units shall be in accordance with 6.2.2 7.2 and 7.3.
More informationFire Protection Coffee Break Training August 2016
Fire Protection Coffee Break Training August 2016 Agenda Introduction - Phelan NFPA 13 versus NFPA 13R systems for Residential Occupancies - Homa NFPA 72 Record of Completion - Homa Questions and Answers
More informationFIRE SPRINKLER SYSTEMS POLICY
FIRE SPRINKLER SYSTEMS POLICY Revised 1/1/17 DESIGN AND SUBMITTAL REQUIREMENTS All new and existing fire sprinkler systems within the jurisdiction of the City Fire Department shall meet all of the applicable
More informationNarrative Reports As Regulated by 780 CMR, Section 903.0
EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for
More informationMay 1, Dear Fire Suppression System Contractor/Designer:
CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 Fax (406) 582-2355 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790
More informationFIRE SPRINKLER SYSTEMS POLICY
FIRE SPRINKLER SYSTEMS POLICY VERSION 1.012/2015 FIRE SPRINKLER SYSTEMS Design and Submittal requirements All new and existing fire sprinkler systems within the jurisdiction of the City of San Mateo Fire
More informationWhat You Need to Know about Residential Sprinkler Design
What You Need to Know about Residential Sprinkler Design Melisa Rodriguez, P.E., NICET IV Design Services Supervisor, Fire Safety melisa.rodriguez@uponor.com www.uponor-usa.com The Residential Sprinkler
More informationPROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE
PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated
More informationTable OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
More informationSPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.
STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920
More informationSlide 1. Slide 2 Instructor. Slide 3. NFPA 25 The Owner s Manual. Roles & Responsibilities DISCLAIMER
Slide 1 NFPA 25 The Owner s Manual Roles & Responsibilities Presented by: Bob Caputo Slide 2 Instructor Bob is the Executive Vice President of Compliance Solutions with Telgian Corporation. He is the Chairman
More informationWhat Builders Need to Know about Residential Sprinkler Design
What Builders Need to Know about Residential Sprinkler Design Melisa Rodriguez, P.E., NICET IV Design Services Supervisor, Fire Safety melisa.rodriguez@uponor.com www.uponor-usa.com Agenda Brief history
More informationFire Sprinkler System Design and Installation Requirements
Fire Sprinkler System Design and Installation Requirements The Park City Fire Service District (PCFD) and Park City Municipal Corporation (PCMC) have made the following amendments to the State of Utah
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Installation of Residential Fire Sprinkler Systems STANDARD #C-002 EFFECTIVE 03-19-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationAmerican Fire Sprinkler Association. An Introduction to the IBC and IFC
American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler
More informationMontgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040
Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler
More informationPublic Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationSUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%
210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent
More informationM E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The
More informationCOMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE
COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm
More informationCITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS
CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS Fire Protection Systems includes the following: Alternate Fire Suppression Systems Atrium Fire Protection Systems Automatic Fire Sprinkler
More informationMinimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016
1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationRESIDENTIAL MULTI-USE FIRE SPRINKLER SYSTEMS PERMIT SUBMITTAL REQUIREMENTS
History: RESIDENTIAL MULTI-USE FIRE SPRINKLER SYSTEMS PERMIT SUBMITTAL REQUIREMENTS Per the City adopted 2009 IRC, section R313, automatic fire sprinkler systems are required for all one and two family
More informationPort of St Helens SIA Aircraft Hanger Scappoose, OR
Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance
More informationUnderstanding and Applying NFPA 25
Understanding and Applying NFPA 25 Texas Edition Learning Objectives Describe the scope of NFPA 25. Distinguish between sprinkler system problems that fall within the scope of NFPA 25 and those that do
More informationReport on First Revision June 2014 NFPA 5000
5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee
More informationFIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS
Department of Fire Rescue & Emergency Services Fire Marshal s Office Dania Beach District 103 West Dania Beach Blvd. Dania Beach, Florida 33004 Office: (954)342-4262 Fax: (954)342-4265 FIRE SPRINKLER SHOP
More informationD. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe
More informationFire Sprinkler Submittal Requirements and Acceptance Testing
Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Sprinkler Submittal Requirements and Acceptance Testing To all Registered
More informationTHE BASICS OF BUILDING FIRE PROTECTION DESIGN. RES Symposium April 18, 2017
THE BASICS OF BUILDING FIRE PROTECTION DESIGN RES Symposium April 18, 2017 PRESENTER S BACKGROUND Ted Sherwood, PE, CFPS, LEED AP 5 years as a Code Enforcement Official and Division Head supervising all
More informationMcMAHON FP200 OUTAGAMIE COUNTY ADMINISTRATION CENTER S. WALNUT & W. 8TH, APPLETON, WI ALTERATION / ADDITION
4/5/017 1:58:50 PM C. 1445 DRIVE NEENAH, WI 54956 EXISTING JUSTICE CENTER IS FULLY SPRINKLED C. EXISTING FIRE PUMP BASEMENT LEVEL EXISTING FDC FOR DRY STANDPIPE IN STAIRWELL SHALL BE DEMOLISHED, SEE FP
More informationSeptember 30, Dear Fire Suppression System Contractor/Designer:
CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790 Phone (406) 582-2375
More informationWestern Michigan University Facilities Management Engineering Division
Western Michigan University Facilities Management Engineering Division Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG21-1 Fire Suppression Systems & Equipment I. GENERAL... 1 A. General
More informationFire-Rated Glazing Changes in 2012 International Building Code (IBC)
Glass Informational Bulletin Fire-Rated Glazing Changes in 2012 International Building Code (IBC) Introduction In 2010, the International Code Council (ICC) adopted several changes regarding fire-rated
More informationSecond Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement
Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationFire Prevention Coffee Break Training. February 2017
Fire Prevention Coffee Break Training February 2017 Agenda FDC s - Lund Standpipes - Phelan Fire Alarm Testing Phelan/Dooley Questions and Answers Open Forum Standpipe requirement Standpipes are required
More informationWEST VIRGINIA UNIVERSITY
WEST VIRGINIA UNIVERSITY Environmental Health and Safety (SOP) WV State Fire Marshal (SFM) Project Plans Review Process & Procedures West Virginia University Environmental Health & Safety Page 1 of 10
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationAUTOMATIC FIRE SPRINKLER SYSTEMS
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system
More informationASCR2, ASCR4, ASC2, ASR2, ASD2
STUDY GUIDE ASCR2, ASCR4, ASC2, ASR2, ASD2 SPRINKLER ASSESSMENTS June 14, 2017 REV4 This document contains sample questions to help participants study for the Automatic Sprinkler assessments. Other documents
More informationM E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationCirculation Report for SIG-TMS Comments Document # 72
1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15
More informationSTRUCTURAL BUILDING COMPONENTS MAGAZINE September/October 2003
STRUCTURAL BUILDING COMPONENTS MAGAZINE September/October 2003 The Other Building Code: NFPA 5000 by Kelly Gutting, TPI TPI Technical Director Could NFPA 5000 be coming soon to a jurisdiction near you?
More informationBest Practices Guide. for Residential Fire Sprinklers
Best Practices Guide for Residential Fire Sprinklers ver.2.0 / 1.16.2017 This guide was created by the Washington Fire Sprinkler Coalition with the purpose of uniting AHJs, fire sprinkler contractors,
More informationRESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY
RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY Plan Submittal and Inspection Requirements Revised 01/18/18 All residential fire sprinkler systems within the jurisdiction of the Fire Department shall meet all
More informationAssessment Overview. Updated March 29,
Compliance Services and Assessments, LC (Formerly Codes and Standards Assessments) Assessment Overview This manual provides general information on CSA assessments in addition to important terms and conditions.
More informationNFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014
NFPA 13 2016 Edition NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s Committees created the First Draft at meetings between July 2013 and December 2013 Balloting ended in early 2014 First Draft decisions
More informationFire Prevention Coffee Break Training. May 2017
Fire Prevention Coffee Break Training May 2017 Agenda Introduction Submittals - Phelan Changes to NFPA 13 - Phelan Questions and Answers Open Forum Please welcome our S ummer Intern Charlie Poppe Small
More informationPLAN REVIEW SUBMITTAL GUIDE
PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide
More informationNFPA 72 Code Changes vs 2013
NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996
More informationTETON COUNTY FIRE PROTECTION RESOLUTION FOR NEW SUBDIVISIONS 2008 Edition. Chapter I General Provisions
TETON COUNTY FIRE PROTECTION RESOLUTION FOR NEW SUBDIVISIONS 2008 Edition Chapter I General Provisions SECTION 1.1: TITLE. This Resolution shall be known as the Teton County Fire Protection Resolution
More informationMEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationSOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS
SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P-02-07 THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS March, 2007 Society of Fire Protection Engineers - 1 - Position
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe
More informationCHAPTER A-6 FIRE PROTECTION
CHAPTER A-6 FIRE PROTECTION 6.1 GENERAL 6.1.1 Scope 6.1.2 Purpose 6.1.3 Qualifications of Fire Prevention Engineer 6.1.4 Required Design 6.1.5 Critical Projects 6.2 APPLICABLE PUBLICATIONS 6.3 PRECONCEPT
More informationFire Prevention Coffee Break Training November 2014
Fire Prevention Coffee Break Training November 2014 Agenda Introduction/ What do we want? - Fire Marshal Lund FAQ s and Alternative Design FPE Phelan Permit to Inspect, Maintain, & Service FP Appliances
More informationUnderstanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training
Understanding, Applying and Enforcing NFPA 25 James D. Lake NFSA Director of Training When Sprinklers Are Ineffective Water did not reach fire 8% 7% 7% 5% 44% Not enough water released Damaged Component
More informationEgress Window. Requirements for Building Permit Application
Egress Window Requirements for Building Permit Application 1. Completed Building Permit application form with signature. 2. Submit two (2) copies of plans showing proposed designs and materials; plans
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:
More informationFire Department Access and Water Supply
Fire Department Access and Water Supply CHAPTER 18 Chapter 18 was reorganized for the 2003 edition and now includes most site design issues in one location. The access and fire lane requirements previously
More informationZurn Pex, Inc. Residential Fire Protection Presentation. PEX Plumbing, Radiant Heating and Residential Fire Protection Systems
Residential Fire Protection Presentation Zurn Pex, Inc PEX Plumbing, Radiant Heating and Residential Fire Protection Systems Matt Lawrence BDM-North Central Region 1 Presentation Outline I. IRC Mandate
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Sprinkler System
More informationAPPENDIX H (DESIGN SUBMISSION CRITERIA)
APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation
More informationNZS 4517:2010. New Zealand Standard. Fire sprinkler systems for houses. Superseding NZS 4517:2002 NZS 4517:2010
New Zealand Standard Fire sprinkler systems for houses Superseding NZS 4517:2002 NZS 4517:2010 NZS 4517:2010 COMMITTEE REPRESENTATION This Standard was prepared under the supervision of the P 4517 Committee,
More informationCodes And Standards Nfpa
Codes And Standards Nfpa 1 / 6 2 / 6 3 / 6 Codes And Standards Nfpa All codes & standards. Virtually every building, process, service, design, and installation is affected by NFPA s 275+ codes and standards.
More information1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Pumps Patti
More informationContren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters
Contren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters (Published jointly by American Fire Sprinkler Association and the National Center for Construction Education and Research.)
More information1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)
1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors) 1. What is the minimum diameter for a non-hydraulically calculated Class III fire standpipe that is part of a combined
More informationTRI-LAKES MONUMENT FIRE PROTECTION DISTRICT
TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter
More informationCubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM
SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly
More informationSACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET
SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET 1 SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT
More informationService Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT
58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the
More informationDeluge/Preaction Systems Annotated Instructor s Guide
Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-07 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection
More informationNational Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance
More informationDeluge/Preaction Systems Annotated Instructor s Guide
Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-13 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection
More informationDEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL
DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL RULES AND REGULATIONS CONCERNING 8 CCR 1507-57 BUILDING AND FIRE CODE ENFORCEMENT AND CERTIFICATION OF INSPECTORS FOR LIMITED GAMING
More informationCommercial Application/Plan Review Submittal Checklist
Commercial Application/Plan Review Submittal Checklist The following checklist has been compiled to assist in expediting the commercial plan review and permit issuance process. Please take a moment to
More informationRecommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region
Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing
More informationMAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and
More informationSECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents
SECTION 01410 PART I - GENERAL 1.01 SECTION INCLUDES A. Relationship between Code, Ordinances, Standards and Contract Documents B. Applicable Codes, Laws and Ordinances C. Project Inspections D. Office
More informationUBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6
Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance
More informationI. INTRODUCTION Codes, Rules, Laws, & Requirements
I. INTRODUCTION 1.03 Codes, Rules, Laws, & Requirements A. Buildings and sites are to be designed in conformance to the applicable requirements of the following: 1. The Texas Engineering Practice Act and
More informationCONTENTS. B. System Design and Performance Requirements
13730 Security Access This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationPlan Submittal Checklist
City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project
More informationREVISION RECORD FOR THE STATE OF CALIFORNIA EMERGENCY SUPPLEMENT
REVISION RECORD FOR THE STATE OF CALIFORNIA EMERGENCY SUPPLEMENT January 1, 2011 2010 Title 24, Part 9, California Fire Code PLEASE NOTE: The date of this supplement is for identification purposes only.
More informationPlease think twice about printing this matrix. You can it, along with your ballot to or
Page Line Clause E/G Organization Comment (rationale) ii Foreword E GWM Recommend inserting the following text between the first and second paragraphs, Fire Alarm Systems shall be installed in accordance
More informationDEPARTMENT OF PUBLIC SAFETY. Division of Fire Prevention and Control 8 CCR FIRE SUPPRESSION RULES
DEPARTMENT OF PUBLIC SAFETY Division of Fire Prevention and Control 8 CCR 1507-11 FIRE SUPPRESSION RULES STATEMENT OF BASIS, STATUTORY AUTHORITY, AND PURPOSE Pursuant to Section 24-33.5-1203.5, C.R.S.,
More information