Standard Operating Procedure Ottawa Fire Services. Fire Operations- Structural Fire Incidents SUBJECT. Fire Alarm Systems (Silence/Reset) - Revised

Size: px
Start display at page:

Download "Standard Operating Procedure Ottawa Fire Services. Fire Operations- Structural Fire Incidents SUBJECT. Fire Alarm Systems (Silence/Reset) - Revised"

Transcription

1 CLASSIFICATION # SOP FI Fire Operations- Structural Fire Incidents SUBJECT Fire Alarm Systems (Silence/Reset) - Revised AUTHORITY Fire Chief Policy (OFS) personnel, before leaving a building, shall make every effort to ensure fire alarm systems are operational. If this is not possible, then follow-up measures shall be taken. Purpose To detail procedures for OFS personnel when dealing with fire alarm systems (silence/reset) Scope All OFS personnel Procedure RULES A Notice to Owner/Occupant form shall be issued whenever there is a problem with a building fire alarm system, as detailed in the Notice to Owner/Occupant form. An issued Notice to Owner/Occupant form shall be posted on a clipboard that is kept in the station watch room. In occupied buildings, when a fire alarm system is silenced, Command shall ensure that Building Supervisory Staff are directed to make arrangements to have the alarm system repaired. (see Part 5 of this SOP) ACTIONS 1.0 Officer/Member in Charge s Duties at a Fire Alarm Call 1.1 If system was silenced before arrival of OFS, it is possible that Building Supervisory Staff could not locate an emergency condition and has silenced the system. 1.2 The Officer/Member in Charge shall have a crew check the building for the source of the alarm activation before attempting to have the alarm reset. 1.3 If there is no evidence of fire, then an attempt to reset the fire alarm system may be requested. 1.4 If the system cannot be reset, then fire crews should recheck for activated pull stations, smoke detectors, or heat detectors. Issue Date: October 15, 2002 Last Revision: April 2, 2008 Page 1 of 5

2 1.5 If the system cannot be reset, then the system shall be left in the silenced mode and a Notice to Owner/Occupant form shall be issued. The Building Supervisory staff shall post a fire watch until the system is returned to normal operational mode. 1.6 Record on Notice to Owner/Occupant form who silenced/reset the fire alarm system (name, address, telephone #). 2.0 Resetting Fire Alarm Systems 2.1 Building Supervisory Staff on scene. The Officer/Member in Charge shall: Direct/assist Building Supervisory Staff to reset the fire alarm system. Check the annunciator panel to see that it is in normal operating status (non alarm) before leaving scene. 2.2 Building Supervisory Staff not on scene. The Officer/Member in Charge shall: Obtain keys from the lock box and reset the fire alarm system. Check the annunciator panel to see that it is in normal operating status (non alarm) before leaving scene. 2.3 Building Supervisory Staff on scene and the Officer/Member in Charge cannot access panel. The Office/Member in Charge shall: Refer to part 4 of this SOP. 3.0 Silencing Fire Alarm Systems (The fire alarm system cannot be reset or building supervisory staff would like to investigate problem before attempting reset) Note building has been examined and no apparent fire exists. 3.1 Building Supervisory Staff on scene. The Officer/Member in Charge shall: Direct/assist Building Staff/Management to silence the fire alarm system. Advise Building Staff/Management that their alarm system must be serviced immediately. Issue a Notice to Owner/Occupant form. 3.2 Building Supervisory Staff not on scene. The Officer/Member in Charge and a firefighter shall: Obtain keys from the lock box and silence the fire alarm system. Leave a Notice to Owner/Occupant form: o With a responsible occupant, if possible. o At the building staff/management office. 4.0 No Access To Reset a Fire Alarm System 4.1 Occupants in building. The Officer/Member in Charge shall: Request that building occupants contact building supervisory staff in order that fire alarm system keys can be brought to the building. Request that Dispatch attempt to contact building supervisory staff in order that fire Issue Date: October 15, 2002 Last Revision: April 2, 2008 Page 2 of 5

3 alarm system keys can be brought to the building. Leave a Notice to Owner/Occupant form: o With a responsible occupant, if possible. o At the building staff/management office. If Building Supervisory Staff cannot be contacted, then the Officer/Member in Charge shall advise occupants that the alarms will ring until Building Supervisory Staff can be contacted and that they should be alert for signs of fire until the alarm system has been reset. 4.2 No occupants in building. Access cannot be made to the building (no lock box). The Officer/Member in Charge shall: Check the exterior of the building and check the interior for signs of fire through any available windows. Request that Dispatch attempt to contact building supervisory staff in order that fire alarm system or access keys can be brought to the building. If building supervisory staff cannot be contacted, then a Notice to Owner/Occupant form shall be left at the front door of the building and all OFS vehicles may clear the scene. Request for Inspection form to be sent to Prevention Division. 5.0 Notice to Owner/Occupant form follow-up. 5.1 The Officer/Member in Charge shall check the appropriate clipboard every morning for any unresolved incident (e.g. panel showing trouble) and the annunciator panel of these buildings shall be inspected by the day shift within 24 hours. If the annunciator panel is in normal operating status, the Officer/Member in Charge shall indicate the date of recheck and the results and forward the completed the Notice to Owner/Occupant Form to the Fire Prevention Division. If the annunciator panel still indicates a status other than normal, the Officer/Member in Charge shall indicate the date of recheck and the results and forward the completed Notice to Owner/Occupant form attached to a Request for Inspection form explaining the problem and providing contact phone numbers to the Fire Prevention Division by inter office mail for action. 5.2 Rural: Sector Chiefs shall arrange any follow-up inspections required when a Notice to Owner/Occupant form has been issued. The Sector Chief/Fire Prevention Officer responsible for that rural area shall inspect these buildings within 24 hours of occurrence. If the annunciator panel is in normal operating status, the Sector Chief /Fire Prevention Officer responsible for that rural area, or Officer/Member in Charge, shall indicate the date of recheck and the results and forward the completed Notice to Owner/Occupant form to the Fire Prevention Division. If the annunciator panel still indicates a status other than normal, the Sector Chief or Officer/Member in Charge shall indicate the date of recheck and the results and forward the completed Notice to Owner/Occupant form attached to a Request for Inspection form explaining the problem and provide contact phone numbers to the Issue Date: October 15, 2002 Last Revision: April 2, 2008 Page 3 of 5

4 Fire Prevention Division by inter-office mail for action. The Fire Prevention Division shall file both the Notice to Owner/Occupant and the Request for Inspection forms. 6.0 Private Residences (Monitored Smoke Alarm Systems) 6.1 Alarm sounding no answer at the door: Command shall: o Ensure that the exterior perimeter of the building has been checked for signs of smoke or fire. o Ensure that windows and door leading to the interior of the building have been visually examined for smoke or fire conditions inside the building. 6.2 Command shall not: o Authorize any activity that may cause damage to the building without clear indications that a fire condition exists within the structure. 6.3 Issue Notice to Owner/Occupant form. RESPONSIBILITIES Command shall: Check the annunciator panel to see that it is clear, before leaving scene. Issue Notice to Owner/Occupant form when required. Command shall ensure that buildings are thoroughly checked before leaving the scene. Command shall ensure that all attempts have been made to reach a key holder. Station Officer shall recheck buildings that have been issued Notice to Owner/Occupant form. Command shall notify Ottawa Police Services if forcible entry has been made. Dispatch shall: Attempt to contact Building Staff/Management, when requested, so that fire alarm system keys can be brought to the building. The Fire Prevention Division shall: Follow-up with Building Supervisory Staff when a Notice to Owner/Occupant form and Request for Inspection form is received from Suppression. File all Notice to Owner/Occupant forms that are submitted. File all Request for Inspection forms once completed. References and Related Areas Of Interest Ontario Fire Code Section (1) Issue Date: October 15, 2002 Last Revision: April 2, 2008 Page 4 of 5

5 (Original signed by Fire Chief Larabie) R. Larabie Fire Chief, Branch Community and Protective Services City of Ottawa It is understood that this procedure may not address all circumstances. Conditions may exist that require some type of deviation by the Incident Commander. Decisions should always be based on experience, the safety of the public and the safety of personnel. Issue Date: October 15, 2002 Last Revision: April 2, 2008 Page 5 of 5

6 SIGN OFF SHEET- STANDING OPERATING PROCEDURE SOP #: FI Fire Alarm Systems (Silence/Reset) - Revised A Platoon B Platoon Print Name Signature Print Name Signature C Platoon D Platoon Print Name Signature Print Name Signature (please sign after reading above noted SOP)

Standard Operating Procedure Ottawa Fire Service. Major Case File Management

Standard Operating Procedure Ottawa Fire Service. Major Case File Management Standard Operating Procedure Ottawa Fire Service Classification # SOP PR 04.2-2008 Prevention Fire Investigation Major Case File Management Subject Authority Policy Fire Chief Ottawa Fire Services (OFS)

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

Standard Operating Procedure Ottawa Fire Services. Fire Safety Plan Approval - Revised

Standard Operating Procedure Ottawa Fire Services. Fire Safety Plan Approval - Revised Policy Standard Operating Procedure Ottawa Fire Services CLASSIFICATION # SOP PR 03.1-2003 REV Prevention- Safety Plans SUBJECT Fire Safety Plan Approval - Revised AUTHORITY Fire Chief Ottawa Fire Services

More information

Travis County Emergency Services District #1 Standard Operating Guidelines

Travis County Emergency Services District #1 Standard Operating Guidelines Section Policy Number Effective Date C C8 07/05/2015 Policy Issued As Reference Policy # Overhaul B1, C1, TBD Subject Approval: Overhaul Donald Norman, Fire Chief PURPOSE This standard operating guideline

More information

Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH. General. Requirements for a Fire Watch

Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH. General. Requirements for a Fire Watch Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH General This information is provided to clarify the requirements for a fire watch. A fire watch is the action of a person or persons

More information

Truro Police Department. Fire Emergencies. Policy Number: OPS-9.02 Effective Date: June 1, 2000 REFERENCE:

Truro Police Department. Fire Emergencies. Policy Number: OPS-9.02 Effective Date: June 1, 2000 REFERENCE: Truro Police Department Fire Emergencies Policy Number: OPS-9.02 Effective Date: June 1, 2000 REFERENCE: Accreditation Standards: Mass. Gen. Law: Chap. 89 sec 7A, 268 sec 32A Other: Policy: It is the policy

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.6.54 Control Number: A.0 Effective Date: TITLE: PROPRIETARY

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 High Rise On Scene Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 High Rise On Scene Revised Truck Module Page 1 of 5 HIGH RISE FIRE ON SCENE The Truck Module 1000.00 sections are designed to be companion documents to EOM section 503.00 Objectives The objective of this section is to explain the

More information

Town of Cochrane Policy

Town of Cochrane Policy Town of Cochrane Policy Policy No.: Policy Title: Approval Date: Revision Date: Department: 1401-01 Fire Department Lock Box Program January 22, 1996 September 24, 2007 Community and Protective Services

More information

DAVIS POLICE DEPARTMENT

DAVIS POLICE DEPARTMENT DAVIS POLICE DEPARTMENT ROBBERY AND BURGLARY ALARM RESPONSE Policy and Procedure 2.22-A Index as: DEPARTMENT MANUAL Robbery Alarms Burglary Alarms Alarms I. STATEMENT OF ISSUE It is essential that police

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

I. It shall be the responsibility of the department officers to implement this operating guideline.

I. It shall be the responsibility of the department officers to implement this operating guideline. Procedure Effective Date Rescinds HIGH RISE INCIDENTS New Reference FIRE CHIEFS ASSOCIATION OF CENTRAL OHIO Page 1 of 11 NORWICH TOWNSHIP FIRE DEPARTMENT SOG# 8 Purpose: The purpose of this procedure is

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2 FIRE SAFETY PLAN BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089 DATE: 15-August-10 FPO #2 INDEX Introduction 2 Locations of Fire Safety Plans 3 Forward 4 Audit of Building Data 5-6 Fire Fighting

More information

ELEVATOR RESCUE PROCEDURE

ELEVATOR RESCUE PROCEDURE ELEVATOR RESCUE PROCEDURE Office of Environmental Health & Safety December 2013 Table of Contents I. Purpose:... 3 II. Scope:... 3 III. Responsibility:... 3 IV. Types of Emergencies:... 3 V. Definitions:...

More information

Carbon Monoxide Alarm Response Guide. High Country Training Center Training On Demand

Carbon Monoxide Alarm Response Guide. High Country Training Center Training On Demand Carbon Monoxide Alarm Response Guide High Country Training Center Training On Demand Objectives Look at Home CO detectors Everything you do and don t want to know about CO detectors Fire Department CO

More information

Fire Inspection Frequently Asked Questions

Fire Inspection Frequently Asked Questions Fire Inspection Frequently Asked Questions What authority does the City have to conduct Fire Inspections? Kirby Fire Marshal conducts fire/safety inspections based on a Fire Code requirement that all commercial,

More information

TG FIRE DRILLS. Office of the Fire Marshal and Emergency Management

TG FIRE DRILLS. Office of the Fire Marshal and Emergency Management FIRE DRILLS Office of the Fire Marshal and Emergency Management Preface This guideline updates TG-01-2004 published in October 2004. Portions of the guideline have been changed to reflect the current requirements

More information

Structural Firefighting Policy

Structural Firefighting Policy Section Policy Number Effective Date C C1 09/01/2015 Policy Issued As Reference Policy # B1-B4, B6, C2-C10, C12, D1, and TBD Subject Approval: Policy Donald Norman, Fire Chief PURPOSE The purpose of this

More information

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS TEN STEP PROCESS PREPARING FIRE SAFETY PLANS STEP 1 CONDUCT FIRE SAFETY AUDIT IDENTIFY BUILDING FEATURES AND HUMAN RESOURCES. STEP 2 APPOINTMENT OF SUPERVISORY STAFF IDENTIFY TRAINED SUPERVISORY STAFF

More information

REED COLLEGE DEPARTMENT OF COMMUNITY SAFETY DEPARTMENTAL DIRECTIVE CSO FIRE & FIRE ALARM SYSTEM RESPONSE GUIDELINES

REED COLLEGE DEPARTMENT OF COMMUNITY SAFETY DEPARTMENTAL DIRECTIVE CSO FIRE & FIRE ALARM SYSTEM RESPONSE GUIDELINES CSO FIRE & FIRE ALARM SYSTEM RESPONSE GUIDELINES Source: Departmental Directive issued by the CS Director. Original publication: January 27, 2011 Latest review & revision: August 2018 Departmental Policy

More information

TABLE OF CONTENTS 8. ANNEX B

TABLE OF CONTENTS 8. ANNEX B TABLE OF CONTENTS 8. ANNEX B... 8-1 8.1 PURPOSE...8-1 8.2 SITUATION AND ASSUMPTIONS...8-1 8.2.1 SITUATION...8-1 8.2.2 ASSUMPTIONS...8-1 8.3 GENERAL PROCEDURES AND RESPONSIBILITIES... 8-2 8.3.1 CARE AND

More information

Department of School Safety and Security MONTGOMERY COUNTY PUBLIC SCHOOLS Rockville, Maryland

Department of School Safety and Security MONTGOMERY COUNTY PUBLIC SCHOOLS Rockville, Maryland Department of School Safety and Security MONTGOMERY COUNTY PUBLIC SCHOOLS Rockville, Maryland Shelter-In-Place Guidelines for a Chemical, Biological, or Radiological Incident and Exposure to Hazardous

More information

FIREFIGHTER II: FIRE DEPARTMENT COMMUNICATIONS COMMUNICATIONS: SKILL SHEET #2 Define and Demonstrate Fire Department Radio Procedure

FIREFIGHTER II: FIRE DEPARTMENT COMMUNICATIONS COMMUNICATIONS: SKILL SHEET #2 Define and Demonstrate Fire Department Radio Procedure NFPA 1001: 6.2.2 FIREFIGHTER II: FIRE DEPARTMENT COMMUNICATIONS COMMUNICATIONS: SKILL SHEET #2 Define and Demonstrate Fire Department Radio Procedure OBJECTIVE Trainee shall define and demonstrate prescribed

More information

Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition.

Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition. Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition. Revised 02/10/2017 Alabama Fire College Firefighter II Instructional JPR Verification Sheet Full Name: Fire Department:

More information

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance It is ordained by the Town Council of the Town of New Shoreham

More information

Emergency Planning and Preparedness

Emergency Planning and Preparedness Emergency Planning and Preparedness Writing an Emergency Evacuation Plan A thorough emergency plan will include the following components: The procedure for reporting emergencies The procedure for relocating

More information

Austin Independent School District Police Department Policy and Procedure Manual

Austin Independent School District Police Department Policy and Procedure Manual Austin Independent School District Police Department Policy and Procedure Manual Policy 4.08A Emergency/Non-Emergency Response - Vehicle I. POLICY (7.15.1; 7.26.1 TPCAF) The AISD Police Department s primary

More information

St. Vincent s Health System Page 1 of 6

St. Vincent s Health System Page 1 of 6 St. Vincent s Health System Page 1 of 6 TITLE: Fire Plan Code Red FACILITY: St. Vincent s East FUNCTION: ORIGINATING DEPT: HOSPITAL SHARED POLICY? EFFECTIVE DATE: _X Yes No DOCUMENT NUMBER: 801 ORIGINATION

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Venue Emergency Response Plan (VERP)

Venue Emergency Response Plan (VERP) Venue Emergency Response Plan (VERP) Event: Venue: Date: Event Manager: Safety Officer: Who has responsibility for ensuring volunteers have been trained on this plan? Have Event Team volunteers been trained

More information

SAMPLE FIRE SAFETY PLAN. ABC Manufacturing Ltd. 123 Main Street Steinbach, Manitoba. Prepared by: John Smith Last reviewed: Bill Jones 2014

SAMPLE FIRE SAFETY PLAN. ABC Manufacturing Ltd. 123 Main Street Steinbach, Manitoba. Prepared by: John Smith Last reviewed: Bill Jones 2014 SAMPLE FIRE SAFETY PLAN ABC Manufacturing Ltd. 123 Main Street Steinbach, Manitoba Prepared by: John Smith 2011 Last reviewed: Bill Jones 2014 Page 1 of 19 Table of Contents 1. Building Information 2.

More information

Property Name & Address [ Property Name ] - [ Property Address ]

Property Name & Address [ Property Name ] - [ Property Address ] Emergency Procedure FIRE Property Name & Address [ Property Name ] - [ Property Address ] Purpose To ensure effective response and evacuation, by the property s Emergency Response Organization, to a fire

More information

FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe

FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe FIRE SAFETY PLAN Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA May / 2017 Prepared by: Chris Pancoe TABLE OF CONTENTS Contents A. BUILDING AUDIT:... 3 BUILDING DESCRIPTION... 3 1. Level

More information

BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS

BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS Note: For information on OOS Fire Alarms please see Inspectional

More information

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION SECTION: UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION INITIATOR: DALE SAUNDERS REVISION DATE: September 2015 1. Program Description 2. Scope 3. Definitions

More information

Commercial Remodel/ Add On Rules and Regulations

Commercial Remodel/ Add On Rules and Regulations Commercial Remodel/ Add On Rules and Regulations Public Works and Community Development Department City of Shenandoah 29955 I-45 North Shenandoah, Texas 77381 281-298-5522 www.shenandoahtx.us Construction

More information

SUBJECT FIRE OPERATIONS GUIDELINE (F.O.G.) #F510 Issued: 1/2014 Last Revision: 1/2014 Pages: 9 By Order Of: J.S. Thompson, Fire Chief

SUBJECT FIRE OPERATIONS GUIDELINE (F.O.G.) #F510 Issued: 1/2014 Last Revision: 1/2014 Pages: 9 By Order Of: J.S. Thompson, Fire Chief THE COLONY FIRE DEPARTMENT FIRE OPERATIONS GUIDELINE SUBJECT FIRE OPERATIONS GUIDELINE (F.O.G.) #F510 Issued: 1/2014 Last Revision: 1/2014 Pages: 9 By Order Of: J.S. Thompson, Fire Chief Review Reviewed

More information

Cumru Township Fire Department 4/27/10 Standard Operating Guidelines Page: 1 of 6 Section 15.07

Cumru Township Fire Department 4/27/10 Standard Operating Guidelines Page: 1 of 6 Section 15.07 Standard Operating Guidelines Page: 1 of 6 15.07 Scope: Commercial properties shall include businesses, schools and shops with very limited special hazards. 15.0701 First engine placement: Positioning

More information

FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES

FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES 10 FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES GENERAL 1- Demonstrate procedures for assuming and transferring command at an emergency scene, utilizing an incident management system. REFERENCE: NFPA 1001,

More information

Fire Evacuation Plan Health Sciences & Human Services Library. UMB POLICE or

Fire Evacuation Plan Health Sciences & Human Services Library. UMB POLICE or UMB POLICE - 711 or 410-706-3333 If you discover fire, smoke, or excessive heat inside your building, immediately: 1. Activate fire alarm by pulling manual fire alarm pull station (located near exits)

More information

STANDARD OPERATING PROCEDURES RESPONDING TO EMERGENCIES DEPARTMENT RESPONSE PROCEDURES EFFECTIVE: AUGUST 2007

STANDARD OPERATING PROCEDURES RESPONDING TO EMERGENCIES DEPARTMENT RESPONSE PROCEDURES EFFECTIVE: AUGUST 2007 STANDARD OPERATING PROCEDURES RESPONDING TO EMERGENCIES 208.002 DEPARTMENT RESPONSE PROCEDURES EFFECTIVE: AUGUST 2007 PURPOSE The purpose of this policy is to provide standard response procedures for members

More information

REPORT TO COUNCIL. DATE: August 1, 2006 REPORT NO.: FD SUBMITTED BY: Gordon (Shorty) Smith FILE NO.: Fire Chief

REPORT TO COUNCIL. DATE: August 1, 2006 REPORT NO.: FD SUBMITTED BY: Gordon (Shorty) Smith FILE NO.: Fire Chief REPORT TO COUNCIL DATE: August 1, 2006 REPORT NO.: FD 07-06 SUBMITTED BY: Gordon (Shorty) Smith FILE NO.: 6-1-1 Fire Chief SUBJECT: Fire Department Response and Activities July 2006 Emergency Responses:

More information

ARTICLE 4-13 ALARM SYSTEMS * Division 1. Generally

ARTICLE 4-13 ALARM SYSTEMS * Division 1. Generally ARTICLE 4-13 ALARM SYSTEMS * Division 1. Generally Sec. 4-13-1 Definitions Alarm site. The single premises or location (one (1) street address) served by an alarm system or systems that are under the control

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

Austin Independent School District Police Department Policy and Procedure Manual

Austin Independent School District Police Department Policy and Procedure Manual Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for

More information

BCGEU JOB DESCRIPTION MINISTRY OF FORESTS

BCGEU JOB DESCRIPTION MINISTRY OF FORESTS POSITION TITLE: Forest Protection Assistant BRANCH / REGION / DISTRICT: Protection Program, Fire Zones NOC CODE: 2223 SUPERVISOR S POSITION TITLE: Forest Protection Officer CURRENT CLASSIFICATION / GRID:

More information

Whitestown Fire Department Standard Operating Procedure

Whitestown Fire Department Standard Operating Procedure Whitestown Fire Department Standard Operating Procedure Title: Fire Investigation No: 6.01 Date: 7/29/2016 Adopted 8/1/16 Page: 1 of 1 Purpose: The purpose of the Fire Investigation Program is to investigate

More information

JEFFERSON COUNTY PUBLIC SCHOOLS FIRE WATCH PROGRAM

JEFFERSON COUNTY PUBLIC SCHOOLS FIRE WATCH PROGRAM 1 JEFFERSON COUNTY PUBLIC SCHOOLS FIRE WATCH PROGRAM PURPOSE: To minimize potential structural damages and to protect the life safety of all building occupants during periods when the automatic fire alarm

More information

FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE FIRE MEDICAL EMERGENCY

FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE FIRE MEDICAL EMERGENCY University of Maryland FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your

More information

San Ramon Valley Fire Protection District GREEN SHEET

San Ramon Valley Fire Protection District GREEN SHEET San Ramon Valley Fire Protection District GREEN SHEET Informational Summary Report of Serious San Ramon Valley Injury, Illness, Accident and Near-Miss Incident Near-Miss Incident Firefighters in close

More information

OAK GROVE SCHOOL DISTRICT SCHOOL SITE FIRE PREVENTION PLAN

OAK GROVE SCHOOL DISTRICT SCHOOL SITE FIRE PREVENTION PLAN OAK GROVE SCHOOL DISTRICT SCHOOL SITE FIRE PREVENTION PLAN PURPOSE To protect our employees, students, and occupants from the dangers of fire, Oak Grove School District has developed a fire prevention

More information

District of Sicamous. Fire Department Bylaw No. 126, Effective Date February 26, 1996

District of Sicamous. Fire Department Bylaw No. 126, Effective Date February 26, 1996 District of Sicamous Fire Department Bylaw No. 126, 1995 Effective Date February 26, 1996 Consolidated for Convenience Only This is a consolidated version of the parent bylaw that incorporates changes

More information

Westerville, OH Code of Ordinances. CHAPTER 969 Alarm Systems

Westerville, OH Code of Ordinances. CHAPTER 969 Alarm Systems Westerville, OH Code of Ordinances CHAPTER 969 Alarm Systems 969.01 Definitions. 969.02 Alarm user permit required. 969.03 Application for alarm user permits. 969.04 Renewal. 969.05 System standards. 969.06

More information

Fire System Impairment Policy

Fire System Impairment Policy Fire System Impairment Policy Purpose: To establish procedures to be followed, when a fire protection or suppression system is taken out of service, due to construction, alteration, power outage, repair,

More information

dss PHILADELPHIA POLICE DEPARTMENT DIRECTIVE 4.11

dss PHILADELPHIA POLICE DEPARTMENT DIRECTIVE 4.11 dss PHILADELPHIA POLICE DEPARTMENT DIRECTIVE 4.11 Issued Date: 01-24-94 Effective Date: 01-24-94 Updated Date: 11-09-16 SUBJECT: POLICE RESPONSE TO ALARM SYSTEMS 1. POLICY A. It will be the responsibility

More information

STONY HILL RURAL FIRE DEPARTMENT OPERATING GUIDELINES

STONY HILL RURAL FIRE DEPARTMENT OPERATING GUIDELINES STONY HILL RURAL FIRE DEPARTMENT OPERATING GUIDELINES Subject: Response to Alarms (DRAFT) Approved: Guideline Number: 1006 Date: 11-8-2011 Page: 1 of 6 1.0 PURPOSE To establish a procedure for the acknowledgement

More information

TULANE UNIVERSITY EMERGENCY ACTION PLAN

TULANE UNIVERSITY EMERGENCY ACTION PLAN TULANE UNIVERSITY EMERGENCY ACTION PLAN This is the Emergency Action Plan developed by Tulane University applicable for the prescribed building and department. It has been designed to assist personnel

More information

[Name/title] is the Alternate Safety Officer/ Alternate Emergency Coordinator.

[Name/title] is the Alternate Safety Officer/ Alternate Emergency Coordinator. Community Health Center ================================================================= Subject: EMERGENCY EVACUATION PROCEDURE ================================================================= Policy

More information

Dear Retirement Board Director:

Dear Retirement Board Director: Dear Retirement Board Director: We request that the Retirement Board recognize dispatchers and dispatch supervisors as being members of retirement group 2. We request this because municipal dispatchers

More information

Applying Performance-based Fire Alarm System Design Part 4

Applying Performance-based Fire Alarm System Design Part 4 Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Applying Performance-based Fire Alarm System Design Part 4 by Dean K. Wilson, P.E. Over the course of the last four issues I have continued to discuss

More information

RAMBLER PARK FIRE SAFETY INFORMATION

RAMBLER PARK FIRE SAFETY INFORMATION RAMBLER PARK FIRE SAFETY INFORMATION Parmenter Realty Partners 7557 Rambler Rd. Dallas, Texas 75231 214-373-9561 214-373-9620 (fax) RAMBLER PARK RAMBLER PARK FIRE SAFETY INFORMATION II. Objective To provide

More information

EMERGENCY OPERATIONS PLAN Revision 4.0

EMERGENCY OPERATIONS PLAN Revision 4.0 Annex A- Purpose To provide an overview of the responsibilities and the procedures whereby the notification of key University officials and the warning of the general public, Students and employees are

More information

GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS

GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS [Second Revised Edition] April, 2003 Issued by: Mechanical and Engineering Branch Room 500, Norquay Building

More information

University of Maryland FIRE EVACUATION PLAN

University of Maryland FIRE EVACUATION PLAN University of Maryland FIRE EVACUATION PLAN PLAZA PARKING GARAGE POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will immediately

More information

Building Emergency Response Scenario

Building Emergency Response Scenario Building Emergency Response Scenario Following is a use case scenario of a building fire incident and covers alert generation and propagation to dispatch followed by the first responder use of building

More information

Article 3: Police Regulated Occupations and Businesses. Division 37: Burglary, Robbery and Emergency Alarm Systems

Article 3: Police Regulated Occupations and Businesses. Division 37: Burglary, Robbery and Emergency Alarm Systems Article 3: Police Regulated Occupations and Businesses Division 37: Burglary, Robbery and Emergency Alarm Systems 33.3701 Definitions Defined words appear in italics. Except as otherwise provided, for

More information

Emergency Action Plan For Alumni Center 1507 Dana Avenue

Emergency Action Plan For Alumni Center 1507 Dana Avenue University Relations Division Department of Physical Plant Human Resources Community Building Institute Office of University Communications and Administrative Office Building Emergency Action Plan For

More information

Low Rise Residential occupancies are required to perform one fire safety training and one evacuation drill annually

Low Rise Residential occupancies are required to perform one fire safety training and one evacuation drill annually CITY AND COUNTY OF DENVER Department of Safety Fire Department Fire Prevention Division 745 W. Colfax Ave. Denver, CO 80204 p: 720.913.3474 f: 720.913.3587 September 13, 2017 TO: RE: Residential Low-Rise

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

HAZARDOUS MATERIALS/WASTE EMERGENCY CONTINGENCY PLAN University of Southern Maine Portland Campus

HAZARDOUS MATERIALS/WASTE EMERGENCY CONTINGENCY PLAN University of Southern Maine Portland Campus HAZARDOUS MATERIALS/WASTE EMERGENCY CONTINGENCY PLAN University of Southern Maine Portland Campus Issued By: Office of Finance and Administration Name: Chief Financial Officer Effective Date: November

More information

TABLE OF CONTENTS Part 6 Legal Basis for Fire Safety Planning... 2

TABLE OF CONTENTS Part 6 Legal Basis for Fire Safety Planning... 2 TABLE OF CONTENTS Part 6 Legal Basis for Fire Safety Planning... 2 6.1] GENERAL... 2 6.2] EXCERPTS FROM 2012 BC FIRE CODE PART 2 BUILDING AND OCCUPANT FIRE SAFETY... 3 6.3] EXCERPTS FROM 2012 BC FIRE CODE

More information

STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT FROM: CHIEF ERIC JONES TO: ALL PERSONNEL

STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT FROM: CHIEF ERIC JONES TO: ALL PERSONNEL STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT DATE: February 21, 2018 NO: FROM: CHIEF ERIC JONES TO: ALL PERSONNEL INDEX: Emergency Vehicle Response Emergency Vehicle

More information

WELCOME TO ROSEVILLE UNIVERSITY

WELCOME TO ROSEVILLE UNIVERSITY WELCOME TO ROSEVILLE UNIVERSITY FIRE OPERATIONS 101 Welcome Introduction of the Roseville Fire Department Review our Operations Tour of the Fire Department Our Mission To preserve life and property Our

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building

More information

UNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW

UNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW PROCEDURE Emergency preparedness Issued with the authority of the Chief Commissioner and General Manager of Chief Commissioner signature Chief Executive Officer signature Sponsor Head of Risk Document

More information

FIRE PREVENTION PLAN EMERGENCY ACTION

FIRE PREVENTION PLAN EMERGENCY ACTION FIRE PREVENTION PLAN EMERGENCY ACTION 1.0 PURPOSE This Plan is presented for University employees to be informed so that they react safely and effectively during an emergency situation. The Plan also reinforces

More information

Guideline for Fire Safety Plan

Guideline for Fire Safety Plan Explosives Regulatory Division Division de la réglementation des explosifs G06-07 Guideline for Fire Safety Plan April 2014 1. REQUIREMENTS As part of the application for any storage licence for storing

More information

8. PRE-PLANNED FIRE AND EMS RESPONSE SYSTEMS

8. PRE-PLANNED FIRE AND EMS RESPONSE SYSTEMS 8. PRE-PLANNED FIRE AND EMS RESPONSE SYSTEMS Each municipality within Cumberland County will be required to submit and utilize pre-planned Fire and EMS Responses, commonly referred to as a "phantom box"

More information

HORNCASTLE ARENA 55 JACK HINTON DRIVE CHRISTCHURCH

HORNCASTLE ARENA 55 JACK HINTON DRIVE CHRISTCHURCH EMERGENCY PROCEDURES FOR HORNCASTLE ARENA 55 JACK HINTON DRIVE CHRISTCHURCH DATE : 11 August 2014 PREPARED BY: & Fire Safety Net Ltd (FSN) www.firesafetynet.co.nz FIRE EVACUATION SCHEME To comply c with

More information

Understanding and Managing Fire Safety in Housing Accommodation

Understanding and Managing Fire Safety in Housing Accommodation Understanding and Managing Fire Safety in Housing Accommodation Presented at: ONPHA 2015 Annual Conference October 17, 2015 Kevin j. Kelly, P.Eng, Technical Services Office of the Fire Marshal and Emergency

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 6 Utilities Electrical Emergencies Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 6 Utilities Electrical Emergencies Revised Truck Module Page 1 of 6 ELECTRICAL EMERGENCIES Classification of Voltage For firefighting purposes, voltage can be considered in one of two classes, either high or low. As a general rule, the larger the

More information

The 2012 Fire Suppression Rating Schedule (FSRS)

The 2012 Fire Suppression Rating Schedule (FSRS) The 2012 Fire Suppression Rating Schedule (FSRS) Summary of Changes March 21, 2017 How to Get a Copy of the FSRS Only FIRE CHIEFS may request a free copy of the FSRS. Submit (via e-mail only) an ATTACHED

More information

Travis County Emergency Services District #1 Standard Operating Guidelines

Travis County Emergency Services District #1 Standard Operating Guidelines PURPOSE CARBON MONOXIDE To establish a procedure for response to carbon monoxide (CO) incidents, to insure the safety of both the firefighters and the public, and to allow for safe incident mitigation.

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

DCN: COMMUNICATIONS MANUAL CHAPTER 1 January 1, 1997 ALARM TRANSMISSION SYSTEMS

DCN: COMMUNICATIONS MANUAL CHAPTER 1 January 1, 1997 ALARM TRANSMISSION SYSTEMS CHAPTER 1 January 1, 1997 ALARM TRANSMISSION SYSTEMS TABLE OF CONTENTS 1.0 INTRODUCTION...1 1.1 BARS (Box Alarm Readout Systems) ALARM BOXES...1 1.2 ERS (Emergency Reporting System) ALARM BOXES...2 1.3

More information

a) Establishment of emergency procedures to be followed at the time of an emergency;

a) Establishment of emergency procedures to be followed at the time of an emergency; 5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing

More information

SEVERE WEATHER & FIRE EMERGENCY PROCEDURES

SEVERE WEATHER & FIRE EMERGENCY PROCEDURES TUSCARAWAS COUNTY HEALTH DEPARTMENT SEVERE WEATHER & FIRE EMERGENCY PROCEDURES Version: 2018.9 Date Originally Adopted: 3/8/2017 Date of Last Revision: 3/8/2018 Date of Last Review: 3/8/2018 CONTENTS STATEMENT

More information

Outline. Standards of Coverage. ICS Features 2/12/2016 ICS

Outline. Standards of Coverage. ICS Features 2/12/2016 ICS Outline Fire Department Operations Standards of Coverage What does it look like in your town? Standard Assignment House Fire, Commercial Fire, Smoke in Structure Incident Command System Arrival Reports

More information

OXNARD FIRE DEPARTMENT Fire Watch Guidelines

OXNARD FIRE DEPARTMENT Fire Watch Guidelines OXNARD FIRE DEPARTMENT Fire Watch Guidelines What is a Fire Watch? A Fire Watch is a temporary measure intended to ensure continuous and systematic surveillance of an activity, building or portion thereof

More information

Fire Evacuation Plan Bressler Research Building. UMB POLICE or

Fire Evacuation Plan Bressler Research Building. UMB POLICE or UMB POLICE - 711 or 410-706-3333 If you discover fire, smoke, or excessive heat inside your building, immediately: 1. Activate fire alarm by pulling manual fire alarm pull station (located near exits)

More information

Emergency Action Fire Prevention Plan

Emergency Action Fire Prevention Plan Emergency Action Fire Prevention Plan Table of Contents Section Title Page 1.0 Purpose 2 2.0 Scope and Application 2 3.0 Responsibilities 2-3 University Safety Coordinator 2-3 Department Heads, Supervisors

More information

New School Construction: Safe School Opening. OAR and IOR Joint Training February 17, 2005

New School Construction: Safe School Opening. OAR and IOR Joint Training February 17, 2005 New School Construction: Safe School Opening OAR and IOR Joint Training February 17, 2005 1 Purpose Provide information on process moving from construction to occupancy and opening schools 2 School Opening

More information

Fire Department Orientation / Organization

Fire Department Orientation / Organization Fire Department Orientation / Organization Objectives Identify the organization of the fire department. Identify the basic firefighter s role as a member of the fire service. Identify the mission of the

More information

Rapid Intervention Team

Rapid Intervention Team 3.2.1.2 Rapid Intervention Team YOUR ORGANIZATION STANDARD OPERATING PROCEDURES/GUIDELINES TITLE: Rapid Intervention Team NUMBER: 3.2.1.2 PREPARED BY: SECTION/TOPIC: Fire Suppression Risk Management ISSUE

More information

Should you have further questions, please feel free to contact the Fire Prevention Branch.

Should you have further questions, please feel free to contact the Fire Prevention Branch. Fire Prevention Branch Fire Hall # 5 200 Saprae Creek Trail Fort McMurray, AB T9H 4P1 November 8 th, 2017 RE: PERMIT REQUIRED TO WORK ON SPECIAL FIRE SUPPRESSION SYSTEMS IN THE RMWB All annual special

More information

FROM: CITY MANAGER DEPARTMENT: POLICE FIRE SUMMARY OF REDWOOD CITY FIRE/COMMUNITY ALERTING SYSTEM (TELEMINDER) FAILURE

FROM: CITY MANAGER DEPARTMENT: POLICE FIRE SUMMARY OF REDWOOD CITY FIRE/COMMUNITY ALERTING SYSTEM (TELEMINDER) FAILURE TO: HONORABLE CITY COUNCIL FROM: CITY MANAGER DEPARTMENT: POLICE FIRE DATE: APRIL 23, 2007 CMR:219:07 SUBJECT: SUMMARY OF REDWOOD CITY FIRE/COMMUNITY ALERTING SYSTEM (TELEMINDER) FAILURE This is an informational

More information

ALTA LOMA RIDING CLUB EMERGENCY RESPONSE TEAM ANIMAL EVAC ORGANIZATIONAL CHART EVAC GROUP SUPERVISOR

ALTA LOMA RIDING CLUB EMERGENCY RESPONSE TEAM ANIMAL EVAC ORGANIZATIONAL CHART EVAC GROUP SUPERVISOR ANIMAL EVAC ORGANIZATIONAL CHART EVAC GROUP SUPERVISOR CALL TEAM UNIT LEADER EVAC UNIT LEADER --------- ANIMAL FACILITY UNIT LEADER CALL TEAMS EVAC TEAM #1 EVAC TEAM #2 EVAC TEAM #3 EVAC TEAM #4 SECURITY

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information