Are there any policies regarding outlets that contain USB ports?

Size: px
Start display at page:

Download "Are there any policies regarding outlets that contain USB ports?"

Transcription

1 Answers to the Questions Mark J. Blackburn, P.E., CFPS February, 2016 Question 1 Are there any policies regarding outlets that contain USB ports? There is no direct reference in code about these types of outlets These outlets are considered to be Tamper-Resistant UL or ccsaus listed 498 and 1310 National Electrical Code requirements NFPA 70 requirements 1999 Edition: no specific requirements 2008 Edition: Section Tamper- Resistant Receptacles in Dwelling Units in areas specified in Section HTML/SectionDisplay.jsp?secti on=

2 Question 2 Can there be storage rooms? If so, what are their requirements? Yes IBC Life Safety Code Sprinklered? Yes needs to be smoke tight No 1 hour Fire Resistance Rated Enclosure jpg?dimensions=154x207 3 Question 3 Please explain air fresheners in rooms. Is there an issue concerning Scents lights/deodorizers There are no official code requirements Local infection control limits on aerosols in areas with immune suppressed patients (generated by the facility) No open flame No heating unit (plug-in) Clearance from combustibles ade/products/productshots/canadaenglish/clean-linensolid-air-fresheneren.jpg?sc_lang=en-ca M3-IL._SL1500_.jpg 4 2

3 Question 4 What is the wait time before a facility calls after the battery is unplugged from a fire panel? NFPA Edition trouble signals required by and their restoration shall be automatically indicated and recorded at the proprietary supervising station within 200 seconds 2007 Edition 00.jpg trouble signals and their restoration to normal shall be indicated within 200 seconds at the locations identified in or indication of primary power failure trouble signals transmitted to a supervising station shall be delayed in accordance with Unless prohibited by the AHJ, supervising station fire alarm systems shall be arranged to delay transmission of primary power failure signals for a period ranging from 60 to 180 minutes 5 Question 5 When did the fire marshal start requiring documentation of the operator number with the alarm company for fire drills, both before when the system is taken off line, and after when the system is put back on line? The 2002 edition of NFPA 72 is the first edition requiring notification of impairment status rs/4766/screenshots/116013/shot_ jpg requires notification when a part of the fire alarm system becomes impaired requires notification when the impairment period is completed or discontinued 6 3

4 Question 6 Please explain the portion of the code on Generators. Where does the (panic) shutdown switch need to be located when the generator is outside? NFPA Edition 2008 Edition B6: where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied NFPA Edition kphoto.com/canstock jpg A : for systems located outdoors, the manual shutdown should be located external to the weatherproof enclosure and should be appropriately identified 2005 Edition A : for Level 1 and Level 2 systems located outdoors, the manual shutdown should be located external to the weatherproof enclosure and should be appropriately identified 7 Question 7 Is the FSES Survey still available to solve regulatory problems? It cannot be used for sprinkler related issues, but a known facility had a waiver in the past for a 2 story building with unprotected combustible construction and is now being told a new building is needed. Could a FSES Survey help with this situation? Yes. If the previous waiver was based on hardship only, it may not be continually granted. A waiver granted through the FSES process is found to provide an equivalent level of safety and may be accepted. 8 4

5 Question 8 Is there a requirement to conduct disaster drills (other than fire drills) in Nursing Homes and/or Assisted Living Facilities? ess.com/2014/04/ _2a8f7 0ff12_b.jpg FGI : In locations with recognized potential for hurricanes, tornadoes, flooding, earthquakes, or other regional disasters, the need to protect the life safety of all residential health, care, and support facility occupants and the potential need for continuing services following such a disaster shall be considered during project planning and design :Disaster Preparedness Plan A disaster preparedness plan for the new construction or renovation project shall be included in the RSRA report This plan shall include disaster planning risk mitigation recommendations prepared by the interdisciplinary team that addresses the following: Resident placement and relocation Standards for barriers and other protective measures required to protect areas of refuge from identified potential disasters 9 Question 9 Please explain the power strip use requirements in CMS s S&C:14-46-LSC This categorical waiver describes that NFPA edition contains provisions on the use of power strips that could result in unreasonable hardship for providers/suppliers Determines that the 2012 edition of the Life Safety Code achieves adequate alternative levels of protection Permits the use of power strips in existing/new health care facility patient care areas as long as: In compliance with all applicable 2012 LSC power strip requirements all other 2000 LSC electrical system and equipment provisions Residential care facilities that do not use line-operated electrical appliances for diagnostic, therapeutic, or monitoring purposes are not subjected to the more restrictiveness NFPA 99 requirements regarding the use of power strips in patient care areas/rooms Resident rooms using line-operated patient care-related electrical equipment in the patient care vicinity must comply with the NFPA 99 power strip requirement and may elect to utilize this waiver Cert-Letter pdf - amazon.com/ima ges/i/41amf69r5 WL.jpg 10 5

6 Question 10 What is the difference between a semi-annual and a 6 month inspection interval? Semi-annual inspection interval is inspecting the system twice a year. Each test can occur within a 6- month period of time (i.e. February, November) 6 month inspection interval is inspecting the system once every six months (i.e. January and July) wpcontent/uploads/2013/10/6months. jpg 11 Question 11 Who is the Authority Having Jurisdiction? CMS? State Fire Marshal? Local Fire Department? Assisted Living Facilities: State Fire Marshal Nursing Homes: State Fire Marshal Centers for Medicare and Medicaid Services (CMS) If federally funded A8VNnEBkAJs/Ukttt6Ts9YI/AA AAAAAABKE/oWYHHG7Pq6o/ s1600/ribbon.jpg x.shtml 12 6

7 Question 12 Where can we get copies of the LSC Books, International Fire Codes, and all related manuals? What do you recommend facilities have on hand? Recommended codes NFPA 101 (2000) NFPA 25 (2008) NFPA 72 (2010) NFPA 13 (2010) ICC Codes NFPA Codes: png _t.png ers.jpg 13 Question 13 Must smoke barriers run continuously to the roof deck of a roof/ceiling assembly? Yes, smoke barriers must be continuous from floor to for floor/ceiling or roof above Do not confuse smoke barriers with smoke partitions 14 7

8 Question 14 What is the minimum time length to run a generator to fulfill a monthly load test? What type of emergency lighting is needed? NFPA Edition 7.9 requires emergency lighting in all means of egress including exit access (corridors), exits (stairs) and exit discharge (exterior walkway to public way) Emergency Generator Required to be inspected weekly Required to run under load monthly for a minimum of 30 minutes Q.shtml 15 Question 15 What areas of a building do not need to be sprinklered? NFPA Edition Section 8.15 Special Situations Concealed Spaces Noncombustible and limited-combustible construction with minimal combustible loading having no access Vertical Shafts Noncombustible and limited-combustible nonaccessible vertical duct, electrical, or mechanical shafts Stairways /power-clipart-powerthumb_clipart_free.png Stair towers where the exterior walls are at least 50% open and it is constructed entirely of noncombustible construction 16 8

9 Question 15 (Cont.) Spaces Under Ground Floors, Exterior Docks, and Platforms (where all of the following is met) Nonaccessible for storage purposes and is protected against accumulation of wind-borne debris The space contains no equipment (ex: conveyers or fuel-fired heating uints) The floor over the space is of tight construction No combustible or flammable liquids or materials that under fire conditions would convert into combustible or flammable liquids are processed, handled, or stored on the floor above Exterior Roofs, Canopies, Porte-Cocheres, Balconies, Decks, or Similar Projections Constructed with noncombustible, limited-combustible, or fire retardant-treated wood material Omitted from exterior exit corridors when the walls are at least 50% open and is entirely of noncombustible construction Dwelling Units Bathrooms Sprinklers ARE required in limited care facilities and nursing homes (as defined in NFPA 101) 17 Question 15 (Cont.) Electrical Equipment Rooms (where all of the following s met) The room is dedicated to electrical equipment only Only dry-type electrical equipment is used Equipment is installed in a 2-hour fire-rated enclosure No combustible storage is permitted to be stored in the room Duct Protection In vertical risers located outside the building, provided the riser does not expose combustible material or the interior of the building and the horizontal distance between the hood outlet and the vertical riser is at least 25ft Additional exceptions exist if the system is designed per NFPA 13R assisted living only 18 9

10 Question 16 Is it acceptable to test the Generator under load monthly and exercise weekly? CMS S&C NFPA 101 (2000) Section requires emergency generators and standby power systems as per NFPA 110 (1999) NFPA 110 (1999) Section requires diesel-powered generators that do not meet monthly testing requirements (Section 6-4.2) to be run annually with various loads for a total of 2 continuous hours NFPA 110 (2010) requires for total test duration of 1 hour and 30 minutes Needs to be in compliance with all other applicable NFPA 110 (1999) provisions and Section NFPA 110 (1999) Section 6-4.2: Generator sets in Level 1 and Level 2 service shall be exercised at least once monthly for a minimum of 30 minutes, using one of the following methods: Under operating temperature conditions or at not less than 30% of the EPS nameplate rating Loading that maintains the minimum exhaust gas temperatures as recommended by the manufacturer NFPA 110 (2010) Section : Diesel-powered EPS installations shall be exercised monthly with the available EPSS load and shall be exercised annually with the supplemental loads at not less than 50% of the EPS nameplate kw rating for 30 continuous minutes and at not less than 75% of the EPS nameplate kw rating for 1 continuous hour for a total test duration of not less than 1.5 continuous hours Cert-Letter pdf 19 Question 17 How often is the testing of GFI s required and is this something that is checked during the Fire Marshal visit? NFPA 110 (2008) Section C: shall be performance tested when first installed on site A written record of this test shall be made and be available to the AHJ NFPA 99 (2012) Section : when equipment ground-fault protection is first installed, each level shall be performance-tested to ensure compliance with Section : Electrical circuit tests shall include the following: Ground-fault check to verify that no conductors are grounded to the chamber 20 10

11 Question 18 O2 Cylinders in a resident room: Are there only two E cylinders (one in use and one back-up) allowed in a room at one time? CMS S&C Up to 300 cubic feet of nonflammable medical gas may be accessible as operational supply rather than storage, when properly secured An individual container of medical gas placed in a patient room for as needed (but regular) individual use is not required to be stored in an enclosure, when properly secured If the resident does not need the use of oxygen for an extended period of time, such as several days, then the medical gas container should be removed from the room and properly secured in an approved storage room original/c-p-p.jpg? Question 19 O2 Cylinders in a resident room: What are the storage requirements of C cylinders? Am I within the requirements if there is one in use and three more stored in the room? Much like the previous answer, Up to 300 cubic feet of nonflammable medical gas may be accessible as operational supply rather than storage, when properly secured the gas may be located outside of an enclosure (per smoke compartment) at locations open to the corridor such as at a nurse s station or in a corridor (not obstructing the use of the corridor) au/images/thumbnails/2/320/320/c -size.png 22 11

12 QUESTIONS? Contact Mark J. Blackburn, P.E., CFPS For More Information Visit 23 12

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Agency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014

Agency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014 Agency for Health Care Administration Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014 CMS S&C Letter Interpretation CMS- S&C: 13-58-LSC Dated: 08/30/2013 Several Categorical LSC

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

Iowa State Fire Marshal

Iowa State Fire Marshal Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards

More information

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey. Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the

More information

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1 Building Codes & Standards for Healthcare Building Codes and Standards AHJs Codes Defend in Place Walls Sprinklers Fire Alarm Important Dates for Healthcare Facilities 7/5/16 NFPA Life Safety Code 101

More information

Center for Clinical Standards and Quality /Survey & Certification Group

Center for Clinical Standards and Quality /Survey & Certification Group DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality /Survey

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services Life Safety Code Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services danilo.concepcion@stjoe.org 714-771-8944 The findings and conclusions in this presentation are

More information

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING SUMMARY PROVER'S PLAN OF CORRECTION K 000 INITIAL COMMENTS K 000 A Life Safety Code Survey was conducted by the State Fire Marshal beginning on May 9th, 2017 and ending on May 10th, 2017. Adair Acute Care

More information

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in

More information

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Issued June 28, 207 Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Nursing Care Center (NCC) Accreditation Program Standard

More information

LIFE SAFETY CODE MAINTENANCE MANUAL

LIFE SAFETY CODE MAINTENANCE MANUAL LIFE SAFETY CODE MAINTENANCE MANUAL 1 P a g e Table of Contents Introduction 3 Alcohol Based Hand Rub (ABHR) Dispensers 4 Corridor Walls 4 Corridor Width 5 Doors 5 Electrical 6 Elevators & Dumbwaiters

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work. 3610 COMMERCE DR SUITE 817 BALTIMORE MD 21227 P 410.737.8677 F 410.737.8688 www.haifire.com May 5, 2014 Review of Regulations 42 CFR Parts 403, 416, 418, 460, 482, 483 and 485 Medicare and Medicaid Programs;

More information

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA Adoption of 2012 Life Safety Code Health Care Facilities Code Kenneth Daily, LNHA kenn@qissurvey.com CMS Announcement May 2016 Life Safety Code Health Care Code Effective July 5 th Numerous changes many

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Defend In Place 2012 IFC Overview of Institutional Occupancies

Defend In Place 2012 IFC Overview of Institutional Occupancies Defend In Place 2012 IFC Overview of Institutional Occupancies ICC Course No. ICC CEU s = 0.50 SCFA Course 8506-15-0 Nathan Ellis Cell: 864-812-5183 Nathan.Ellis@llr.sc.gov Institutional Occupancies Course

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS The York County Department of Fire Safety reviews all commercial building plan submittals for compliance with the 2015 International

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2

More information

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD. Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago

More information

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities Fire & Life Safety Code Compliance Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities LTC, Skilled Nursing Facilities COMMON LIFE SAFETY DEFICIENCIES

More information

ASCs & LSC. Alice Epstein, DFASHRM, FNAHQ

ASCs & LSC. Alice Epstein, DFASHRM, FNAHQ , DFASHRM, FNAHQ Disclaimer The purpose of this presentation is to provide information, rather than advice or opinion. It is accurate to the best of the speaker's knowledge as of the date of the presentation.

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

FHCA 2014 Annual Conference & Trade Show

FHCA 2014 Annual Conference & Trade Show FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion

More information

Department of Health Life Safety Code Update

Department of Health Life Safety Code Update Department of Health Life Safety Code Update Presented by: Charlie Schlegel, Director Division of Safety Inspection Overview CMS Adoption of the 2012 Life Safety Code (LSC) and 2012 Health Care Facilities

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common

More information

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure

More information

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICE Form Approved OMB Exempt FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

More information

Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates

Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates Issued September 20, 2017 Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Home Care (OME) Accreditation

More information

Compliance w/ the 2012 Life Safety Code

Compliance w/ the 2012 Life Safety Code Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides

More information

10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION

10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION Enjoy Your TJC Survey Bill H. McCully CHFM SASHE Senior Consultant MSL Healthcare Partners PREPARATION 1 Top Eight Most Cited Standards (George Mills) EC News May 2015 Top Citations EC.02.06.01 56% EC.02.05.01

More information

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012) 1. K62 Automatic Sprinkler Systems - Automatic sprinkler systems are continuously maintained in reliable operating condition and are inspected and tested periodically. 18.7.6, 19.7.6, 4.6.12, NFPA 13,

More information

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1 Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

FIRE AND SAFETY PROJECT REVIEW REPORT

FIRE AND SAFETY PROJECT REVIEW REPORT 1. A001 2. A001 3. A001 4. D102/103 5. A102/103 *VA enforces/applies the National Fire Protection Association (NFPA) 101 (current edition is 2015) and not the International Building Code (IBC). Ideally

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet

Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet This document is used for frequently cited Life Safety Code violations. This is not an all-inclusive list and is intended for reference only.

More information

Osceola County Department of Fire Rescue and Emergency Medical Services

Osceola County Department of Fire Rescue and Emergency Medical Services St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies

More information

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets

More information

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for

More information

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Form Approved OMB No. 0938-0242 1. (A) PROVER NUMBER 1. (B) MEDICA I.D. NO. 1. HOSPITAL

More information

CHILD CARE CENTER INSPECTION CHECKLIST 06C

CHILD CARE CENTER INSPECTION CHECKLIST 06C CHILD CARE CENTER INSPECTION CHECKLIST 06C OCCUPANCY-SPECIFIC FIRE S November 2006: Kansas State Fire Marshal Page: 29 November 2006: Kansas State Fire Marshal Page: 30 CHILD CARE CENTERS & PRESCHOOLS

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 HCFMO Harris County Fire Marshal M.S. Montgomery Fire Marshal FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 EFFECTIVE JANUARY 1, 2007 These guidelines

More information

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT

More information

FIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid

FIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 1. (A) PROVER NUMBER PART I Life & Safety Code, New and Existing

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 133 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - Y1001 - Awareness of the

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Emergency Planning for Institutional Facilities

Emergency Planning for Institutional Facilities Emergency Planning for Institutional Facilities Pacific ADA Emergency Preparedness Webinars Presented by: Kimberly Paarlberg, ICC Based on the 2015 edition of the International Building Code (IBC) and

More information

Washoe County Department of Social Services

Washoe County Department of Social Services SECTION 30 FIRE AND LIFE SAFETY REQUIREMENTS 30.1 Authority to inspect. The facility shall meet all fire and life safety standards. Fire department inspectors shall have authority to enter, for purposes

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers, NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101

More information

Review of Revisions to NFPA 1, 2015 Edition

Review of Revisions to NFPA 1, 2015 Edition James S Peterkin, PE, LEED AP Senior Fire Protection Engineer TLC Engineering for Architecture Anthony Apfelbeck, CFPS, CBO, CFO, FM, FIFireE, MPA Building and Fire Official City of Altamonte Springs,

More information

THE HEALTHCARE ENVIRONMENT UPDATE. Anne M. Guglielmo, Engineer Engineering Department The Joint Commission. Copyright, The Joint Commission

THE HEALTHCARE ENVIRONMENT UPDATE. Anne M. Guglielmo, Engineer Engineering Department The Joint Commission. Copyright, The Joint Commission 2013 THE HEALTHCARE ENVIRONMENT UPDATE Anne M. Guglielmo, Engineer Engineering Department The Joint Commission Standard/NPSG 2012 Non Compliance 2013 Non Compliance (1 st Six Months) RC.01.01.01 61% 55%

More information

Written Fire Safety Plans

Written Fire Safety Plans Written Fire Safety Plans 2012 LSC KATHARINE ACHOR SEPTEMBER 2016 NFPA Standard: 2012 NFPA 101, 19.1.1.3.1 All health care facilities shall be designed, constructed, maintained, and operated to minimize

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION

COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION Document # GI-16 Page 1 of 7 Large Family Day Care Homes Large family day care homes are licensed for day

More information

Wausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records

Wausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records VIOLATION Code AISLES/EXITS NFPA 1-14.13.2.1 NFPA 1-14.4.1 NFPA 1-14.4.2.1 NFPA 101-7.10.9 Violation Codes Description Aisles and Exits Emergency Lighting Working Required emergency lighting systems shall

More information

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO 80303 303-494-3735 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3

More information

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly. SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.

More information

School Fire Safety Checklist

School Fire Safety Checklist Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

Fire and Life Safety Review Form

Fire and Life Safety Review Form Exits/Egress Fire and Life Safety Review Form 1. Doors shall swing in the direction of egress travel where serving and occupancy load of 50 or more. IFC 1010.1.2.1 2. Egress shall be readily openable from

More information

Health Care Engineers Fire & Life Safety Boot Camp

Health Care Engineers Fire & Life Safety Boot Camp Health Care Engineers Fire & Life Safety Boot Camp MINNESOTA HEALTH CARE ENGINEERS ASSOCIATION FALL CONFERENCE SEPTEMBER 11, 2014 GARY SCHROEDER HEALTH CARE FIRE INSPECTOR MINNESOTA STATE FIRE MARSHAL

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 130 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC

More information

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary

More information

FIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid

FIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 2. NAME OF FACILITY 2. (A) MULTIPLE CONSTRUCTION (BLDGS) 3. SURVEY

More information

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street?

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street? PRE-INSPECTION CHECKLIST THE FOLLOWING INFORMATION IS PROVIDED TO YOU TO ASSIST YOUR FACILITY IN BECOMING COMPLIANT WITH THE NEW YORK STATE FIRE CODE, LOCAL LAWS, AND ORDINANCES GOVERNING THE TOWN OF BABYLON.

More information

1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time.

1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time. Sprinkler 1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time. 2. Does the annual sprinkler head inspection have to be done by a licensed technician

More information

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) 2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) Reference: Documents referenced for this bulletin are as follows: San

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL

STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL Larry Hogan Governor Boyd K. Rutherford Lt. Governor 1201 Reisterstown Road Pikesville, MD 21208 410-653-8980 Fax 410-653-8988

More information

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT

More information

Procedure DESCRIPTION/OVERVIEW

Procedure DESCRIPTION/OVERVIEW Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 98 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC surveyor's determination

More information

EC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10

EC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10 MSL Healthcare Partners, Inc. Wild Card EPs Paraphrase K-tag # EC.02.04.03 EP 14 All other electrical K-920 equipment in patient care vicinity NFPA 992012, Chapter 10 K-924 K-928 K-931 K-tag Description

More information

Washington State Department of Health Construction Review Services

Washington State Department of Health Construction Review Services Washington State Department of Health Construction Review Services Steve Pennington, Plans Reviewer/ Inspector Janet Smoot, Plans Reviewer Clynn Wilkinson, Plans Reviewer 1 S-2 F-1 A B I-2 I-2 B ACF 2

More information

EC 5.10 FIRE PREVENTION MANAGEMENT

EC 5.10 FIRE PREVENTION MANAGEMENT EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively

More information

The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101):

The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): 1.1.1 Title. NFPA 101, Life Safety Code, shall be known as the Life Safety Code, is cited as such, and shall

More information