DETECT-A-FIRE Heat Detectors

Size: px
Start display at page:

Download "DETECT-A-FIRE Heat Detectors"

Transcription

1 DETECT-A-FIRE Heat Detectors DETECT-A-FIRE thermal detectors are detection and release devices used for fire detection systems to activate alarms and actuate extinguishing systems. This rate compensated device combines the best features of both fixed temperature and rateof-rise detectors. Typically specified to 100 above ambient. Hawco European Master Distributor for Fenwal Products Specifications Contacts: Close on Rise Resistive Contact Rating: 5.0 Amps, 125 VAC,.5 Amps, 125 VDC, 2 Amps, 24 VDC, 1.0 Amps, 48 VDC Leads: 4 x 18AWG 6" Teflon insulated Dimensions: Weight: Dia 16mm 142g Fenwal Number Activation T emp 88 Versatile Mounting (Vertical or Horizontal) UL Certified / /-8 Colour Specifications Contacts: Close on Rise Resistive Contact Rating: 5.0 Amps, 125 AC, 0.5 Amps, 125 VDC, 2 Amps, 24 VDC, 1.0 Amps, 48 VDC Leads: 4 x 18AWG 6" Teflon insulated Dimensions: Weight: Versatile Mounting (Vertical or Horizontal) UL Certified Dia 16mm 142g Industrial Units Fenwal Number Activation T emp ±8.3 ±15 ±8.3 ±15 ±11.1 ±20 Colour Black Black Blue Red Red Green Fenwal ATEX Approved, Explosion Proof Heat Detectors ATEX Certified These heat detectors are ATEX approved for explosion proof applications and include the Industry standard Fenwal Detecta-Fire probes. With ingress protection to IP66, this type of heat detector is a popular choice for fire alarm and suppression systems on both Onshore and Offshore installations. Features ATEX approved EXII 1G/EXII 2G Certified EExd Zones 0, 1 & 2 Fenwal Intrinsically Safe Heat Detectors This heat detector has been designed for use in hazardous environments. These units are suitable for fire alarm and/or suppression systems in offshore and onshore applications including paint spray booths, flammable material stores, turbine rooms, extract ductwork and other hazardous areas throughout the oil & gas, petrochemical and process industries. Comprising a Fenwal rate-compensated detector with all-stainless steel external construction, mounted to either a type SM87 marine grade alloy enclosure (EExd version) or JB10 corrosion-free GRP enclosure (EExia, EExem/UL versions). The contact in the detector CLOSES at alarm temperature. For technical advice on your specific requirements, contact our expert consultants on +44 (0) or export@hawco.co.uk

2 Heat Detectors Marine Units Fenwal Number Activation Temp / / / / / / / /-12 ±8.3 ±15 ±8.3 ±15 ±11.1 ±20 ±13.9 ±25 Colour Black Black Blue Red Red Green Fire Detection Products Call the office for details on detector assemblies. These can be made to comply with ATEX approvals, intrinsically safe for off-shore applications or with weatherproof housings. Industrial Stainless Steel Fenwal Number Activation Temp Colour ±5.6 ±8.3 ±11.1 ±10 ±15 ±20 Blue Green Part Number Mounting box kit Hexagonal Retaining nut Gas Ignition Control Products from Fenwal Fenwal are well known throughout the industry for their high quality and reliability. The gas ignition control units are designed based on a manufacturer s application. These gas ignition control units include microprocessor-based technology and allow for precise monitoring, analysis and control of gas burners. Gas Ignition & Temperature Controls Specifications Area Classification: Non Hazardous Application: Weatherproof Detector Fitted: Junction Box: Hawke PL612 Electrical Rating: 24V dc Contact Action: Normally Open (Close on Fire) Cable Entry: 2 x M20 Terminal Block: Ambient Temperature: Rating: Weight: Size: Klippon BK6 Minus 40 to Plus 90 Deg C IP IP g approx Box - 240mm x 135mm x 75mm (W x L x H) Probe projects 115mm out of Box Model Number LWB-140 (60 Deg C) LWB-160 (75 Deg C) LWB-190 (88 Deg C) LWB-210 (99 Deg C) LWB-225 (107 Deg C) LWB-275 (135 Deg C) LWB-325 (163 Deg C) LWB-360 (183 Deg C) LWB-450 (232 Deg C)

3 DETECT-A-FIRE Detection and Release Devices FEATURES Repeatable - self-restoring, nothing to replace, testable Rugged - withstands shock and vibration Versatile - various temperature settings available Durable - long lasting stainless steel shell Economical - wide spacings reduce installation costs Factory set Internal contact area hermetically sealed in stainless steel shell ROHS Compliant APPLICATIONS Protection of schools, factories, offices, libraries, etc. Power generation Gas station islands Paint spray booths Range hoods Engine compartments DESCRIPTION DETECT-A-FIRE detectors are the heart of many fire protection systems. These highly reliable devices have been a standard for over 65 years. Thousands of these detectors are in use controlling the release of extinguishants such as clean agents, CO 2, water, or dry chemicals. In some systems the device is used as an ALARM device, to sense overheat or fire and alert personnel. DETECT-A-FIRE detectors have met with wide acceptance because they are designed with RATE COMPENSATION. This provides a unique advantage over both fixed temperature and rate-of-rise types of detectors because only the DETECT-A-FIRE detector accurately senses the surrounding air temperature regardless of the fire growth rate. At precisely the pre-determined danger point, the system is activated. Fixed temperature detectors must be completely heated to alarm temperature and therefore a disastrous lag in time may occur with a fast rate fire. Rate-of-rise devices, on the other hand, are triggered by the rate of increase in ambient temperature and are subject to false alarms caused by harmless, transient thermal gradients such as the rush of warm air from process ovens. The secret of the unit s sensitivity is in the design (Figure 1). The outer shell is made of a rapidly expanding alloy which closely follows changes in surrounding air temperature. The inner struts are made of a slower expanding alloy. Designed to resist thermal energy absorption and sealed inside the shell, the struts follow temperature changes more slowly. A slow rate fire (Figure 2) will heat the shell and struts together. At the set point, the unit will trigger, actuating the alarm or releasing the extinguishant. A transient rush of warm air up to 40/min. may expand the shell, but not enough to trigger the unit. By ignoring transient warm air excursions, the DETECT-A-FIRE detector virtually eliminates false alarms prevalent with rate-of-rise devices. If a fast rate fire (Figure 3) starts, the shell will expand rapidly. The struts will close, actuating the alarm and/or releasing the agent. The faster the fire rate of growth, the sooner the DETECT-A-FIRE detector will react. Figure 1. READY Figure 2. SLOW FIRE Figure 3. FAST FIRE F Effective: May 2014

4 HORIZONTAL DETECT-A-FIRE DETECTOR SPECIFICATIONS Horizontal DETECT-A-FIRE detectors are designed for locations where appearance is a factor. The attractive, functional design lends physical protection of the unit while making it suitable for commercial, industrial, mercantile public buildings, institutions and marine applications in non-hazardous locations (those classified as ordinary under the National Electric Code). Flush mounted units are designed to fit standard 4-inch octagonal electric boxes and surface mounting units are designed to mount directly on ceilings or on 4-inch electrical junction boxes. Canadian Electrical Codes requires mounting only to an electrical junction box. HORIZONTAL MODELS ONLY TABLE 1 Model No. (See Table 2 for X ) 12-X X X X Contact Operation on Temperature Rise Opens 325 (Max) Closes 325 (Max) Approx. Weight per Unit 10 oz 10 oz Electrical Rating (Resistive Only) 0.5 amps 125 VDC 2.0 Amps 24 VDC 1.0 Amps 48 VDC Model 12-X X is a normally closed device and does not meet the requirements of NFPA-72 for use as an initiating device. TABLE 2 X Setting Spacings (in feet) UL ULc FM RTI Color A / Quick Black A / Quick Black A / Fast A / Fast A / Fast B Fast Blue B Fast Red HORIZONTAL DESIGNS 2 F Effective: May 2014

5 VERTICAL DETECT-A-FIRE DETECTOR SPECIFICATIONS Vertical DETECT-A-FIRE detectors are designed for use in both ordinary or hazardous locations. For ordinary use, they may be mounted to any approved junction box with 7/8 diameter opening by using 1/2-14 NPT mounting nuts. The device may be wired in or out of conduit, depending on local preferences and codes. To facilitate supervision of system wiring, four lead wires are provided on normally open vertical units (that close on temperature rise). Per UL requirements, when mounted in a suitable fitting, instruments are Underwriters Laboratory and Underwriters Laboratory of Canada listed and Factory Mutual approved for hazardous locations. VERTICAL MODELS TABLE 3: MODEL NUMBER 27120*, X Setting Spacings (in feet) UL ULc FM RTI Color E / Quick Black E / Quick Black E / Fast E / Fast E / Fast F 275 ± Fast Blue F 325 ± Fast Red F 360 ± V-Fast Red G 450 ± V-Fast Red G 500 ± V-Fast Green H 600 ±20 N/A V-Fast H 725 ±20 N/A V-Fast *27120 is a normally closed device and does not meet the requirements of NFPA-72 for use as an initiating device. TABLE 4: MODEL NUMBER 28020*, X Setting Spacings (in feet) UL ULc FM RTI Color E / V-Fast Black E / V-Fast Black E / V-Fast E / V-Fast E / V-Fast F 275 ± V-Fast Blue F 325 ± V-Fast Red F 360 ± V-Fast Red G 450 ± V-Fast Green G 500 ± V-Fast H 600 ±20 N/A V-Fast H 725 ±20 N/A V-Fast Note: For clean agents and CO2 suppression systems, ceiling spacing 20 ft. apart unless otherwise specified. Note: is a 2-wire device and RTI is not applicable. * is a normally closed device and does not meet the requirements of NFPA-72 for use as an initiating device. VERTICAL DESIGNS (HEXAGONAL HEAD) VERTICAL DESIGNS (COUPLING HEAD) F Effective: May 2014

6 MOUNTING DETECT-A-FIRE detectors are not position sensitive. Horizontal and vertical detectors refer to the most common mounting configuration for that unit. However each type can be mounted either horizontally or vertically depending on the application and installation requirements. TABLE 5 Notes: Hazardous Locations Class I, Groups A, B, C and D; Class II, Groups E, F and G Class I, Groups B, C and D; Class II Groups E, F and G Detector Type 12-X X X X X X a. DETECT-A-FIRE temperature preset at factory only. b. In applications where corrosion is suspect, care should be taken to protect the DETECT-A-FIRE detector to realize optimal performance and maximum life. Consult factory for fluorocarbon coating option. c. Up to #18 AWG Teflon insulated wire used on units. Above #16 AWG TGGT insulated wire used on units. d. For field wiring requirements please refer to DAF installation instructions. e. Per UL521 requirements - low temperature exposure test is -22 (-30 C). f. DETECT-A-FIRE detectors are designed for long life expectancy, however due to various field conditions it is required that the detectors be tested annually per NFPA guidelines or local fire codes. g. Replace DETECT-A-FIRE after any fire or heat related event, any mechanical damage, or after 10 years of continuous service. h. UL of Canada labeling available upon request. Fitting Required For UL & ULC Listing and FM Approval Mount detector to a suitable listed fitting in accordance with National Electric Code and/or local authority having jurisdiction. CONSTRUCTION Stainless steel shell sensing element. Cold rolled steel mounting facility. Off- finish. TEMPERATURE SETTING SELECTION Fenwal suggests selecting a DETECT-A-FIRE with a temperature setting a minimum of 100 above the maximum ambient temperature expected. Table 6 shows three categories of fire detection devices and their relative response levels for reaction to three different rateof-rise conditions. Statistics indicate that 97% of all fires fall within these categories. TABLE 6 Type of Device Rate Compensated DETECT-A-FIRE Detector Fixed Temperature Rate-of-Rise MODIFICATIONS Under 10/ Min FIRST Rate-Of-Rise Between 10-40/Min FIRST Over 40/Min SECOND but at selected protection level SECOND SECOND THIRD Will not operate unless fixed temperature supplement at 165 is provided, then it is THIRD in sequence Will not operate unless fixed temperature supplement at 165 is provided then it is THIRD in sequence FIRST but may be a false alarm XXX, Fluorocarbon coating, available on , , , models only (500 max.) for better corrosion resistance. AGENCY LISTINGS Fenwal DETECT-A-FIRE detectors are UL and ULC listed and FM approved as fire detection thermostats (close on temperature rise) and as releasing devices (open on temperature rise). TABLE 7 Agency File Number Location UL S492 Ordinary UL E19310 Hazardous ULC CS341-E Ordinary and Hazardous FM J.I. OV2HO.AE Hazardous FM Ordinary UL S2410 Ordinary (600 & 725) UL E89599 Hazardous (600 & 725) 4 F Effective: May 2014

7 TABLE 8 DETECT-A-FIRE PART SELECTION GUIDE Model Number Mounting Head Material Shell Material Contact Operation on Temperature Rise Electrical Rating (Resistive Only) Approximate Weight per Unit 12-X X Brass Type 300 Stainless Steel Opens (450 Max) 5 oz. 12-X X Brass Type 300 Stainless Steel Closes Type 300 Stainless Steel 12X Type 300 Stainless Steel Opens (450 Max) 12-X Type 300 Stainless Steel Closes 2.0 Amps 24 VDC 1.0 Amps 48 VDC 2.0 Amps 24 VDC 1.0 Amps 48 VDC 5 oz. 5 oz. 5 oz. TABLE 9 STOCKED MODELS AND TEMPERATURE SETTINGS (SUGGESTED SETTING A MINIMUM OF 100 ABOVE THE MAXIMUM EXPECTED AMBIENT) Temperature Setting () Model X X X 12-X X 12-X X X 12-X X X 12-X X X X X 12-X X X X X X X X X X X 12-X X X X: Indicates a stock unit Model P/N Model Type Contacts Horizontal Flush Mount Horizontal Surface Mount TABLE 10 DETECT-A-FIRE DETECTOR - RESPONSE TIME INDEX (RTI) Temperature (Set point) Response Time Index (ft-s) 1/2 RTI Classification 140 F (60 C), 160 F (71 C) 110 QUICK RTI Rated Spacing (20 X 20) ft (6 x 6) m Old Rated Spacing (25 x 25) ft (8 x 8) m Horizontal Flush Mount Horizontal Surface Mount 140 (60 C), 160 (71 C), 190 (88 C), 210 (99 C), 225 (107 C), 275 (135 C), 325 (163 C) 148 FAST (25 x 25) ft (8 x 8) m (25 x 25) ft (8 x 8) m Vertical Brass Head Vertical Stainless Head Vertical Brass Coupling Head Vertical Stainless Coupling Head 140 (60 C), 160 (71 C), 190 (88 C), 210 (99 C), 225 (107 C), 275 (135 C), 325 (163 C), 360 (182 C), 450 (232 C), 500 (260 C), 600 (316 C), 725 (385 C) 99 (140, 160) 148 (190, 210, 225, 275, 325, 360, 450, 500, 600, 725) V-FAST (30 X 30) ft (9 x 9) m Note: Spaces shown are distances between units on smooth ceilings, the distances from partitions or walls would be half that shown. Authority having LOCAL jurisdiction should be consulted before installation. (25 x 25) ft (8 x 8) m F Effective: May 2014

8 Figure 4. Optional Explosion Proof Enclosure, P/N Note: Complies with NEC Class I, Groups A, B, C, D, Class II, Group E,F,G, Class III, and U.L. Standard 886. Explosion Proof Enclosure must be purchased separately from the DETECT-A-FIRE. HOW TO ORDER 1. Select the DETECT-A-FIRE detector model from specifications in Table 1 for horizontal DAF or Table 8 for Vertical DETECT- A-FIRE. 2. Refer to temperature rating chart in Table 2 for horizontal DETECT-A-FIRE or Table 3 and 4 for Vertical DETECT-A-FIRE, select temperature setting required and add this number to base catalog number. EXAMPLE: Vertical DETECT-A-FIRE detector set to close at 225. Specifications are subject to change without notice.this literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product s suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or have a particular problem or question, contact KIDDE-FENWAL, INC. F Rev AB 2014 Kidde-Fenwal, Inc. Fenwal Controls, Kidde-Fenwal Inc. 400 Main Street Ashland, MA Tel: 800-FENWAL-1 Fax:

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices DAF DETECT-A-FIRE DAF DETECT-A-FIRE Detection and Release Devices FEATURES Repeatable - resets itself, nothing to replace, testable Rugged - withstands shock and vibration Versatile - offers various temperature

More information

SPECIFICATION: ARGONITE Engineered Fire Suppression System

SPECIFICATION: ARGONITE Engineered Fire Suppression System 1. GENERAL SPECIFICATION 1.1 A total flooding, clean agent, fire suppression system, filled with Argonite agent shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition. 1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection 1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in

More information

Spark Electrodes/Flame Sensors

Spark Electrodes/Flame Sensors Spark Electrodes/Flame Sensors For Gas Ignition Systems July 2016 DESCRIPTION Fenwal electrodes and sensors are an integral part of the ignition system for gas-fired equipment and ensure reliable ignition,

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS SERIES 35-65 24 VAC Microprocessor-Based Hot Surface Ignition Control F-35-65 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings* 120/240

More information

AlarmLine Addressable Linear Heat Detector

AlarmLine Addressable Linear Heat Detector Line Addressable Linear Heat Detector P/N 7-0001-00 Effective: March 2008 K-7-02 FEATURES UL Listed FM Approved CSFM MEA (pending) Low-cost interface between Line sensor cable and control panel accepting

More information

AlarmLine Linear Heat Detector

AlarmLine Linear Heat Detector 7.01 7/11/2000 8:1 AM Page 1 CP Scan#1:Desktop Folder:hold:90 Catalog:7.01.job: 7.01 AlarmLine Linear Heat Detector FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-703 120 VAC Microprocessor-Based Intermittent Pilot Ignition Control F-35-703 July 2016 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

FM-200 In-Cabinet Series

FM-200 In-Cabinet Series 1. GENERAL SPECIFICATION 1.1 A total flooding, In-Cabinet fire suppression system, employing FM-200 superpressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by

More information

WFDE Series Waterflow Detector

WFDE Series Waterflow Detector WFDE Series Waterflow Detector The System Sensor WFDE series is compatible with pipe diameters ranging from 50mm through 200mm and can be mounted in a vertical or horizontal position. Features Compliant

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA) R SERIES 35-70 120 VAC Microprocessor-Based Direct Spark Ignition Control F-35-70 November 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116279 (LR 025993_0_000) Issued to: General Monitors, Incorporated 26776 Simpatica Circle Lake Forest, California 92630 USA Attention: Larry Vlagea The

More information

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION AnaLASER II Detector High-Sensitivity Smoke Detector (HSSD ) F-89-250 FEATURES Air Sampling Smoke Detector for Early Warning Applications Two Versions Available: Standard Detector and Ultra Detector STANDARD

More information

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-61 24 VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay F-35-61 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20

Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20 Electronic Pressure Measurement Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20 Applications Chemical, Petrochemical

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116284 (LR 064969_0_00) Issued to: Mine Safety Appliances Company North American Division 1000 Cranberry Woods Dr Cranberry Township, Pennsylvania 16066-5296

More information

Badger Universal Control Head

Badger Universal Control Head Badger Universal Control Head P/N: 60-120099-002 FEATURES For Use in: Range Guard Commercial Cooking Fire Suppression Systems Industry Guard Industrial Fire Suppression Systems Pneumatic Release of up

More information

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to

More information

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Product Description The Reliable Model JL-14 Early Suppression Fast Response

More information

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS I. GENERAL Heatrex Explosion-proof Pipe Thread Mounted Immersion Heaters are CSA approved

More information

Superior by Design The Kidde ADS TM FM-200 System

Superior by Design The Kidde ADS TM FM-200 System A UTC Fire & Security Company Superior by Design The Kidde ADS TM FM-200 System Engineered to Provide Exceptional Performance The Kidde ADS FM-200 System is an innovative system developed by Kidde engineers

More information

TrueAlarm Smoke Detectors

TrueAlarm Smoke Detectors UL, ULC Approved* TrueAlarm Smoke Detectors TrueAlarm Photoelectric Smoke Detector with TrueSense Smoke/Heat Detection Features detection. If any of these alarm conditions are experienced, an alarm is

More information

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE ANSUL INSTALLATION OPERATION AND MAINTENANCE MANUAL ANSUL AUTOMAN II-C RELEASING DEVICE 001799 This manual is intended for use with the ANSUL AUTOMAN II-C Releasing Device. Those who install, inspect,

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT 1. GENERAL SPECIFICATION 1.1 This specification outlines the requirements for a pre-engineered fire extinguishing system comprising Kidde Fire Systems WHDR Wet Chemical Fire Suppression System, Kidde APC

More information

POINTEK CLS 100 OINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS. Instruction Manual March 2001

POINTEK CLS 100 OINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS. Instruction Manual March 2001 POINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS Instruction Manual March 2001 OINTEK CLS 100 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect

More information

Smoke detection in hazardous areas:

Smoke detection in hazardous areas: WHITE PAPER Smoke detection in hazardous areas: What you need to know Smoke detection in hazardous areas requires detectors that operate effectively and safely in explosive environments. Having the correct

More information

SafEye OPEN-PATH GAS DETECTION SYSTEM XENON 700. We INVENTED it... We PERFECTED it! Patent No. US 5,281,816; US 6,061,141; EP

SafEye OPEN-PATH GAS DETECTION SYSTEM XENON 700. We INVENTED it... We PERFECTED it! Patent No. US 5,281,816; US 6,061,141; EP SafEye OPEN-PATH GAS DETECTION SYSTEM XENON 700 We INVENTED it... We PERFECTED it! Patent No. US 5,281,816; US 6,061,141; EP 0584389 LEL. METERS Open-path Gas Detection Concepts 40-meter path 7m wide cloud

More information

Ultrasonic Point Level Switches

Ultrasonic Point Level Switches see more at SORInc.com Request Quote Ultrasonic Point Level Switches Ultrasonic point level switches are a cost-effective solution for your applications. Installation requires mounting the sensor (threaded

More information

25W Hazardous Location Integrated LED Light Fixture Lumens - Low Profile - ATEX IEC CSA UL

25W Hazardous Location Integrated LED Light Fixture Lumens - Low Profile - ATEX IEC CSA UL 25W Hazardous Location Integrated LED Light Fixture - 3294 Lumens - Low Profile - ATEX IEC CSA UL Part #: HAL-19-25W-ITG-LED Page: 1 The Larson Electronics HAL-19-25W-ITG-LED 25 Watt Explosion Proof Low

More information

Model F1FR Series Quick Response Standard Spray

Model F1FR Series Quick Response Standard Spray Model F1FR 56 Types Standard Upright Standard Pendent Model F1FR 56 Recessed Types Standard Pendent/F1/F2/FP Model F1FR 56 Concealed Types Standard Pendent Listing & Approvals 1. Underwriters Laboratories

More information

ENERGY, OIL & GAS. astsensors.com macrosensors.com. Transducer & Transmitter Capabilities. Your sensor business partner...

ENERGY, OIL & GAS. astsensors.com macrosensors.com. Transducer & Transmitter Capabilities. Your sensor business partner... Transducer & Transmitter Capabilities Your sensor business partner... astsensors.com macrosensors.com About Us AST The mission of American Sensor Technologies, Inc. is to be your sensor business partner...

More information

Circulation Heaters Selection Guidelines

Circulation Heaters Selection Guidelines Selection Guidelines Selecting a Circulation Heater Application Factors Corrosion Policy Selecting the proper circulation heater component requires critical engineering judgement and careful evaluation

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

Description. Applications

Description. Applications CVEP PDS CVEP Convection for Hazardous Heater For Locations Hazardous Locations Convection Heater 1.8 to 9.0kW (T-2A) 280 C (536 F) 1.6 to 4.0kW (T-3A) 180 C (356 F) 1.8 to 9.0kW (T-2) 1.8 300 C to 9.0kW

More information

Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit

Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design N56 W16665 Ridgewood Drive Menomonee Falls, WI 53051 SBS-H2 Hydrogen Gas Detector Kit For battery charging rooms and other areas where

More information

Certification Supplement Manual

Certification Supplement Manual PROCESS ANALYSERS SERVOTOUGH FluegasExact (2700) Gas Analyser Certification Supplement Manual Part Number: 02700008D Revision: 2 Language: UK English Blank CONTENTS 1 INTRODUCTION 2 EC DECLARATION OF CONFORMITY

More information

ILED Aquarius CIRCLE-H Mk 2 Helideck Lighting System

ILED Aquarius CIRCLE-H Mk 2 Helideck Lighting System ILED Aquarius CIRCLE-H Mk 2 Helideck Lighting System Low Profile - Less than 25 mm Precision Machined Interlock Mounting System Special Anti-Slip Coating Upgrading Helicopter deck signalisation lighting

More information

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed. Page of 5. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK506 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor allows

More information

TrueAlarm ES Analog Sensing

TrueAlarm ES Analog Sensing TrueAlarm ES Analog Sensing UL, ULC, CSFM Listed; FM Approved* Features TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a TrueAlarm photoelectric,

More information

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor,

More information

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage Worldwide Contacts www.tyco-fire.com Series 2.8,.2, 5.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description IMPORTANT Always refer to Technical

More information

LC3000 Level Controller Installation and Maintenance Instructions

LC3000 Level Controller Installation and Maintenance Instructions 4025550/12 IM-P402-36 AB Issue 12 LC3000 Level Controller Installation and Maintenance Instructions 1. General safety information LC3000 NORM ALARM TEST 2. General product information 3. Installation 4.

More information

freedom residential pendent sprinkler vk466 (K5.2)

freedom residential pendent sprinkler vk466 (K5.2) Page 1 of 5 1. DESCRIPTION Viking Freedom Residential Pendent Sprinkler VK4 is a thermosensitive, glass-bulb residential sprinkler available in several different finishes and temperature ratings to meet

More information

PANELBOARD PROTECTION ON A GLOBAL SCALE

PANELBOARD PROTECTION ON A GLOBAL SCALE PANELBOARD PROTECTION ON A GLOBAL SCALE INTRODUCTION WHY? No matter what environment, location or power requirement, Appleton panelboards have you and your facility covered. From a petrochemical plant

More information

PILOT VALVE ENCLOSURES FOR HAZARDOUS LOCATIONS PENTAIR CLEAN AIR SYSTEMS

PILOT VALVE ENCLOSURES FOR HAZARDOUS LOCATIONS PENTAIR CLEAN AIR SYSTEMS PENTAIR CLEAN AIR SYSTEMS 3-VFD COMBINATION FLAME AND DUST IGNITION PROOF ENCLOSURES Goyen pilot valve enclosures for hazardous locations are available in a combination of flame proof and dust ignition

More information

PILOT VALVE ENCLOSURES FOR HAZARDOUS LOCATIONS

PILOT VALVE ENCLOSURES FOR HAZARDOUS LOCATIONS 3-VFD COMBINATION FLAME AND DUST IGNITION PROOF ENCLOSURES Goyen pilot valve enclosures for hazardous locations are available in a combination of flame proof and dust ignition proof assemblies, where,

More information

freedom residential concealed pendent sprinkler vk474 (K5.8)

freedom residential concealed pendent sprinkler vk474 (K5.8) Page of sprinkler vk7 (K5.) The Viking Corporation, 0 N Industrial Park Drive, Hastings MI 905 Telephone: 69-95-950 Technical Services: 77--56 Fax: 69--0 Email: techsvcs@vikingcorp.com. DESCRIPTION Viking

More information

freedom residential concealed pendent sprinkler VK488 (K3.0)

freedom residential concealed pendent sprinkler VK488 (K3.0) Page 1 of 6 sprinkler VK (K3.0) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 905 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK is a small highsensitivity

More information

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION DET-TRONICS SPECIFICATION DATA Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION The EQ2200UVHT UV Flame Detector is used with the Eagle Quantum

More information

Product Alert September 20, 2012

Product Alert September 20, 2012 Product Alert September 20, 2012 Type of Notification: Performance Related Concern FM Approvals has been made aware of a potential issue with Chemetron Fire System s Carbon Dioxide System Discharge Hose

More information

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

Electronic Flow Switches

Electronic Flow Switches Industries Electronic Flow Switches Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor

More information

Certificate of Compliance

Certificate of Compliance FF0002 Certificate of Compliance Certificate: 2385571 Project 2447891 Issued to: Mine Safety Appliances 1000 Cranberry Woods Drive Cranberry Township, PA 16066 USA Issued by: Jocelyn Jens Product Group

More information

freedom residential concealed pendent lead free sprinkler

freedom residential concealed pendent lead free sprinkler Page 1 of 6 Telephone: 269-95-9501 Technical Services: 77--56 Fax: 269-1-0 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Lead Free* Sprinkler VK70 is a small

More information

TrueAlarm Analog Sensing

TrueAlarm Analog Sensing UL, ULC Approved* TrueAlarm Analog Sensing TrueAlarm Analog Sensors Photoelectric and Heat; Standard Bases and Accessories Features TrueAlarm analog sensing provides: Digital transmission of analog sensor

More information

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932) Model MBEC-14 (SIN R6932) Features 1. Designed to be installed on piping that is supported by the primary structure, not the purlins. 2. Provides Extended Coverage Ordinary & Extra Hazard protection to

More information

+ + CHECKFIRE MARINE ELECTRIC DETECTION AND CONTROL SYSTEM. CHECKFIRE Marine Electric Detection and Control System (Part No.

+ + CHECKFIRE MARINE ELECTRIC DETECTION AND CONTROL SYSTEM. CHECKFIRE Marine Electric Detection and Control System (Part No. CHECKFIRE Marine Electric CHECKFIRE MARINE ELECTRIC DETECTION AND CONTROL SYSTEM NAME 2016-JAN-30 REV. 03 PAGE 1 Installation, Inspection, and Maintenance Manual + + + + 002997 One Stanton Street / Marinette,

More information

Linear Heat Detection Engineering Specifications

Linear Heat Detection Engineering Specifications Linear Heat Detection Engineering Specifications July, 2007 SAFE Fire Detection Inc. 5915 Stockbridge Dr. Monroe, NC 28110 Phone: (704) 821-7920 Fax: (704) 821-4327 Website: www.safefiredetection.com E-mail:

More information

Explosion Proof LED Strobe Light - 4Hz Flash Rate - 10 Watts - Class I, Div. I - IP67

Explosion Proof LED Strobe Light - 4Hz Flash Rate - 10 Watts - Class I, Div. I - IP67 Explosion Proof LED Strobe Light - 4Hz Flash Rate - 10 Watts - Class I, Div. I - IP67 Part #: EPSLED-80 Page: 1 Made in Texas The EPSLED-80 Explosion Proof LED Strobe Light from Larson Electronics is UL

More information

TECHNICAL DATA. * Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0.

TECHNICAL DATA. * Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Page 1 of 6 Telephone: 269-95-9501 Technical Services: 77-3-56 Fax: 269-1-0 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK7 is a small high-sensitivity

More information

Circulation Heaters Selection Guidelines

Circulation Heaters Selection Guidelines Selection Guidelines Selecting a Circulation Heater Application Factors Corrosion Policy Selecting the proper circulation heater component requires critical engineering judgement and careful evaluation

More information

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed. Page 1 of 6 1. DESCRIPTION Viking Freedom Residential Horizontal Sidewall Sprinkler VK486 is a small, thermosensitive, glass-bulb residential sprinkler available in several different finishes and temperature

More information

Fire Sprinkler Freeze Protection Design / Install Guide

Fire Sprinkler Freeze Protection Design / Install Guide Fire Sprinkler Freeze Protection Design / Install Guide Page 1 of 23 Fire Sprinkler System Freeze Protection Design / Install Guide CONTENTS Introduction Page 3 System Overview Page 4 Fire Suppression

More information

SBS-H2. Hydrogen Gas Detector Kit. For battery charging rooms and other areas where hydrogen gas may be present

SBS-H2. Hydrogen Gas Detector Kit. For battery charging rooms and other areas where hydrogen gas may be present SBS-H2 Hydrogen Gas Detector Kit For battery charging rooms and other areas where hydrogen gas may be present INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS Protects Life, Property, and Profits Compliant

More information

SECTION COMMERCIAL-KITCHEN HOODS

SECTION COMMERCIAL-KITCHEN HOODS SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber

More information

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices DAF DETECT-A-FIRE DAF DETECT-A-FIRE Detection and Release Devices LICO HDL, the junction-box FEATURES Repeatable - resets itself, nothing to replace, testable Rugged - withstands shock and vibration Versatile

More information

freedom residential horizontal sidewall lead free sprinkler VK4840 (k4.2)

freedom residential horizontal sidewall lead free sprinkler VK4840 (k4.2) Page 1 of 5 1. DESCRIPTION Viking Freedom Residential Horizontal Sidewall Lead Free* Sprinkler VK4840 is a small, thermosensitive, glass-bulb residential sprinkler available in several different finishes

More information

VDC. Wireless AC Voltage Detection Sensor. The Leader in Low-Cost, Remote Monitoring Solutions. General Description. Monnit Sensor Core Specifications

VDC. Wireless AC Voltage Detection Sensor. The Leader in Low-Cost, Remote Monitoring Solutions. General Description. Monnit Sensor Core Specifications 1-50 The Leader in Low-Cost, Remote Monitoring Solutions Wireless AC Voltage Detection Sensor VDC 1-50 VOLT General Description The wireless AC voltage detection sensor can interface with other devices

More information

Explosion Proof Light Watt Metal Halide - Class 1 Div 1 & Class 2 Div 1

Explosion Proof Light Watt Metal Halide - Class 1 Div 1 & Class 2 Div 1 Explosion Proof Light - 400 Watt Metal Halide - Class 1 Div 1 & Class 2 Div 1 Part #: EPL-HB-400W-MH Made in the USA The EPL-HB-400W-MH metal halide, hazardous area light fixture from Larson Electronics

More information

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK500 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

Annubar Flowmeter Series

Annubar Flowmeter Series Reference Manual Appendix B Approvals Annubar Flowmeter Series Hazardous Locations Installations.................. page B-1 Rosemount 3051SFA Product Certifications.......... page B-1 Rosemount 3095MFA

More information

LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions

LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions 4024750/9 IM-P402-44 AB Issue 9 LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Wiring 5

More information

FREEDOM RESIDENTIAL CONCEALED PENDENT LEAD FREE SPRINKLER VK4570 (K4.9) TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED PENDENT LEAD FREE SPRINKLER VK4570 (K4.9) TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Lead Free* Sprinkler VK450 is a small high-sensitivity solder link and lever residential sprinkler designed for installation on concealed

More information

Explosion Proof LED Light - Equivalent to Watt Metal Halide - Class 1 Division 2

Explosion Proof LED Light - Equivalent to Watt Metal Halide - Class 1 Division 2 Explosion Proof LED Light - Equivalent to 100-150 Watt Metal Halide - Class 1 Division 2 Part #: EPLC2-LED-150W Page: 1 Made in the USA The EPLC2-LED-150W LED hazardous area light fixture from Larson Electronics

More information

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001 SLATE Sub-Base Module R8001S9001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform

More information

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual 001799 This manual is intended for use with the ANSUL AUTOMAN Il-C Explosion-Proof Releasing Device.

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

ISIS SAFETY SYSTEM Installation guide

ISIS SAFETY SYSTEM Installation guide ISIS SAFETY SYSTEM Installation guide CAUTION This information is designed to help suitably qualified personnel install and operate Mechan Safety equipment. Before using this product, read this guide thoroughly

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 1655492 (219995) Issued to: R.C. Systems Co., Inc. 8621 Hwy 6 Hitchcock, Texas 77563 USA Attention: Roger Carter The products listed below are eligible to bear the

More information

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed. Page 1 of 5 1. PRODUCT DESCRIPTION Viking Freedom Residential Pendent Sprinkler VK458 is a small, thermosensitive, glass-bulb residential sprinkler available in several different finishes and temperature

More information

Installation Instructions for 116DEGEX-FJ-(R) AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations

Installation Instructions for 116DEGEX-FJ-(R) AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations Installation Instructions for 116DEGEX-FJ-(R) AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations CEILING 116EX-C 3/ CONDUIT ENTRIES PENDANT 116EX-P 3/ CONDUIT ENTRY 116EX-C (WALL MOUNTED)

More information

Page 1 of 7. Form No. F_ Rev Replaces Form No. F_ Rev 17.1 (added 205deg version)

Page 1 of 7. Form No. F_ Rev Replaces Form No. F_ Rev 17.1 (added 205deg version) Page 1 of 7 1. DESCRIPTION Viking Freedom Residential Concealed Horizontal Sidewall Sprinkler VK480 is a small high-sensitivity solder link and lever residential sprinkler designed for installation on

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

TECHNICAL DATA. The Viking Corporation s Web site at Overall Length (Sprinkler Body): 2-5/16 (59 mm)

TECHNICAL DATA. The Viking Corporation s Web site at Overall Length (Sprinkler Body): 2-5/16 (59 mm) Page 1 of 6 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK45 is a small highsensitivity glass bulb residential sprinkler for use with a domed cover assembly. The orifice design,

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 2007104 Master Contract: 223077 Issued to: Purge Solutions 2201 North Highway 35 Bypass Suite C Alvin, TX 77511 USA Attention: Wallace Trochesset The products listed

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE November 2, 2007 Sprinkler 113a 1. DESCRIPTION The Viking Standard Response High Challenge Upright Large-Drop Sprinkler VK540 is a thermosensitive, glass-bulb sprinkler intended for use in protecting high

More information

ANSUL TO-ANSUL. For more information... Check your local Yellow Pages for your authorized Ansul Restaurant Systems Distributor.

ANSUL TO-ANSUL. For more information... Check your local Yellow Pages for your authorized Ansul Restaurant Systems Distributor. For more information... Check your local Yellow Pages for your authorized Ansul Restaurant Systems Distributor. Or call Ansul direct at... 1-800-TO-ANSUL (Toll-Free USA/CAN) or 1-715-735-7411 USA FAX:

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

micromatic standard response Upright sprinkler VK100 (K5.6)

micromatic standard response Upright sprinkler VK100 (K5.6) Page 1 of 6 1. DESCRIPTION The Viking Micromatic Standard Response Upright VK100 Sprinkler is a small, thermosensitive, glass-bulb spray sprinkler available in several different finishes and temperature

More information

Explosion Proof UV/Visible Light Fluorescent Fixture - Paint Spray Booth, Rigs - Two Circuit Lamps

Explosion Proof UV/Visible Light Fluorescent Fixture - Paint Spray Booth, Rigs - Two Circuit Lamps Explosion Proof UV/Visible Light Fluorescent Fixture - Paint Spray Booth, Rigs - Two Circuit Lamps Part #: EPL-48-2L-T8-VISUVA Page: 1 The Larson Electronics EPL-48-2L-T8-VISUVA Explosion Proof UV/Visible

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information