1 Guidance Note Additional Requirements for Watermist Systems Protecting High-rise Buildings
2 Additional Requirements for Watermist Systems Protecting High-rise Buildings SCOPE... 3 DESIGN PARAMETERS... 3 SUBDIVISION INTO ZONES... 3 HYDRAULIC PIPEWORK CALCULATION... 3 WATER SUPPLIES... 4 POWER SUPPLIES... 4 ADDITIONAL CONSIDERATIONS... 4 REFERENCE DOCUMENTS of 5
3 SCOPE This document sets the additional requirements for automatic water mist systems, for buildings in which the height difference between the highest and lowest water mist nozzles exceeds 45m. These apply to buildings falling under the fire hazard classification as detailed within BS EN 12845:2015 for ordinary hazard occupancy groups OH1 to OH3 (identified in table A.2). It is noted that these supplemental requirements are in addition to those defined within BS 8489 series or an equivalent recognised watermist standard. DESIGN PARAMETERS Assumed maximum areas of operation High-rise buildings shall be designed taking into account an assumed maximum area of operation (AMAO) of at least 216m². Note: VdS has advised on the design for high-rise buildings following the proven European OH1 design flux density, but using the OH3 (216m 2 ) dimensioning area. The new VdS water mist standard VdS 3188en will take the same approach. This is because from the fire hazard categorization perspective the fire load equals to OH1 definitions, but due to significant building height the required safety can be achieved by using 216m 2 dimensioning area. SUBDIVISION INTO ZONES The area covered by automatic water mist nozzles to be controlled by any zone valve set shall have the following restrictions: a) Similar to conventional sprinkler systems, water mist systems should be subdivided into zones, with a maximum of 200 automatic nozzles per zone or a plan area of 2400m 2, whichever is the lesser. b) The building shall be water mist-protected throughout* 1. c) The water mist zone should cover no more than one floor level, which may however d) include a mezzanine floor no greater than 100m 2. e) Car parks and areas involving the unloading and storage of goods should be covered by separate un-zoned systems* 1. HYDRAULIC PIPEWORK CALCULATION System piping shall be fully hydraulically designed taking into consideration the entire piping system to deliver the required water flow and pressure to the AMAO. 3 of 5
4 WATER SUPPLIES The system must have at least a single water supply with enhanced availability Single water supplies with enhanced availability are to be regarded as superior because of their higher degree of reliability. These include the following: a) Public water supply system with one or more pump modules, which is fed from two sides, each side is able to satisfy the pressure and flow rate requirements of the building; it has to be supplied by two or more water sources and may not be dependent on a single main water supply. The pump system must include at least one additional pump module as redundancy. b) Reservoirs which can hold the entire amount of water required. c) The pump system must include at least one additional pump module. d) The use of a booster pump is not allowed. POWER SUPPLIES The power supply must be provided from two independent sources. These can be the following: a) Public networks. b) Own power generation. c) Diesel engines. d) Back-up power generators. ADDITIONAL CONSIDERATIONS Watermist protection of high rise buildings should be done in consultation with the stakeholders including AHJ, F&RS and insurers and address any special considerations (such as combustible external cladding, and any fire strategy for the premises). Notes *1 Test data must be available to support watermist use for all hazard categories identified within the building. REFERENCE DOCUMENTS For further guidance please refer to the below publications. BS EN 12845:2015 Fixed firefighting systems automatic sprinkler systems design, installation and maintenance VdS 3188en VdS Guidelines for Water Mist Sprinkler Systems and Water Mist Extinguishing Systems (High Pressure Systems), Planning and Installation. 4 of 5
5 DISCLAIMER The information set out in this document is believed to be correct in the light of information currently available but it is not guaranteed and neither the Fire Industry Association nor its officers can accept any responsibility in respect of the contents or any events arising from use of the information contained within this document. Tudor House, Kingsway Business Park, Oldfield Road, Hampton, Middlesex TW12 2HD Tel: +44 (0) of 5
Watermist Fire Protection of Plant Rooms
Guidance Note Watermist Fire Protection of Plant Rooms SCOPE This document sets out the requirements for protection of plant rooms with watermist systems and should be read in conjunction with BS8489-1.
More informationGuidance Note. Visual Alarm Devices: Conflict between BS 5839 and EN 54-23
Guidance Note Visual Alarm Devices: Conflict between BS 5839 and EN 54-23 Visual Alarm Devices: Conflict between BS 5839 and EN 54-23 INTRODUCTION... 3 EXTENSION OF THE COEXISTENCE PERIOD FOR EN 54-23...
More informationTudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website:
Fact File No 0055 Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0)20 3166 5002 Website: www.fia.uk.com Watermist Systems 1. INTRODUCTION Over the past twenty
More informationFact File 78. Portable Fire Extinguishers under the ADR. Note: This Fact File supersedes Fact File 060 which is withdrawn
Fact File 78 Portable Fire Extinguishers under the ADR Note: This Fact File supersedes Fact File 060 which is withdrawn The European Agreement concerning the International Carriage of Dangerous Goods by
More informationGuidance Note FIA Application Guidance on BS :2015
Guidance Note FIA Application Guidance on BS 7273-4:2015 FIA Application Guidance on BS 7273-4:2015 1. INTRODUCTION... 3 2. OVERVIEW... 3 2.1. WHAT IS A DOOR RELEASE MECHANISM?...3 2.2. WHY INSTALL DOOR
More informationFact File 69 Fire Detection & Alarms
Fact File 69 Fire Detection & Alarms Revision of BS 5446-3 Detection and alarm devices for dwellings Part 3: Specification for fire alarm and carbon monoxide alarm systems for deaf and hard of hearing
More informationFact File 46 Guidance to recyclers on treatment of domestic ionisation chamber smoke detectors (ICSD)
Fact File 46 Guidance to recyclers on treatment of domestic ionisation chamber smoke detectors (ICSD) Guidance to recyclers on treatment of domestic ionisation chamber smoke detectors (ICSD) BACKGROUND...
More informationEnvironmental Guidance Foam Fire Extinguishers
Fact File 25 Environmental Guidance Foam Fire Extinguishers Environmental Guidance Foam Fire Extinguishers INTRODUCTION... 3 ENVIRONMENTAL ISSUES... 4 EXTINGUISHERS ON SITE... 5 EXTINGUISHERS OFF SITE/AT
More informationFarms and Similar Agricultural Facilities
Guidance Note Farms and Similar Agricultural Facilities This is information for FIA members and their customers, who have to determine the scale of provision of portable fire extinguishers on farms and
More informationThe requirements of BS Watermist Fire System standard and how to demonstrate compliance
The requirements of BS8489-1 Watermist Fire System standard and how to demonstrate compliance Bob Whiteley C. Eng.; F.I.Mech.E.; M.I.Fire E.; B.Tech(Hons) Chair: BSI Watermist Working Group Overview What
More informationFact File 39 Environmental Guidance
Fact File 39 Environmental Guidance Foam Fire Extinguisher Disposal Foam Fire Extinguisher Disposal INTRODUCTION... 3 ENVIRONMENTAL ISSUES... 4 FOAM EXTINGUISHERS... 5 HANDLING OF EXTINGUISHERS OFF SITE/AT
More informationEnvironmental Guidance Fire Fighting Powder and Powder Fire Extinguishers
Fact File 26 Environmental Guidance Fire Fighting Powder and Powder Fire Extinguishers Environmental Guidance Fire Fighting Powder and Powder Fire Extinguishers INTRODUCTION... 3 TYPES OF FIRE EXTINGUISHING
More informationFact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems:
Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility and connectivity assessment of system components Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility
More informationGuidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment
Guidance Note Guidance Document on Best Practice for Fire Detector Testing/Test Equipment Guidance Document on Best Practice for Fire Detector Testing/Test Equipment 1. SCOPE OF THIS DOCUMENT... 3 2. COMPETENCY
More informationFact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems
Fact File 75 Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems INTRODUCTION... 3 BACKGROUND...
More informationFact File 15 Ionisation Chamber Smoke Detectors and The Radioactive Material (Road Transport) Regulations 2002
Fact File 15 Ionisation Chamber Smoke Detectors and The Radioactive Material (Road Transport) Regulations 2002 Ionisation Chamber Smoke Detectors and The Radioactive Material (Road Transport) Regulations
More informationGuidance on Video Smoke Detection Technology (VSD)
Guidance Note Guidance on Video Smoke Detection Technology (VSD) Guidance on Video Smoke Detection Technology (VSD) SCOPE... 3 INTRODUCTION... 4 WHAT IS VSD?... 5 STANDARDS... 7 GENERAL GUIDANCE ON THE
More informationInstallation and Maintenance Requirements
Installation and Maintenance Requirements Water Mist Systems in Buildings John Sinclair Compco Fire Systems This Presentation Will Cover: 1. Water mist systems for buildings and local applications 2. Products
More informationWater Mist in Care Homes & Hospitals in the Nordic Territory. Henrik Johansson
Water Mist in Care Homes & Hospitals in the Nordic Territory Henrik Johansson AquaMist AquaSonic Twin Fluid Technology 7 Bar Atomizer: a Super Sonic Generator creating droplets 20 50 times smaller than
More informationTudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website: EQUALITY ACT 2010
Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0)20 3166 5002 Website: www.fia.uk.com EQUALITY ACT 2010 1. INTRODUCTION This Fact File aims to highlight some
More informationCase study: EconAqua water mist sprinkler system
1.1 Minimax's Econ Aqua low pressure mist system Low pressure water mist extinguishing system based on sprinkler technology with particularly low consumption of water, thus providing great benefits for
More informationGuidance Note. Fire Alarm Detector Applications and Documentation of the Selection
Guidance Note Fire Alarm Detector Applications and Documentation of the Selection Fire Alarm Detector Applications and Documentation of the Selection INTRODUCTION... 3 FLOW CHART FOR THE SELECTION OF...
More informationFIA Guidance on Manual Call Point - Protection - False Alarm Mitigation
Guidance Note FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation FIA Guidance on Manual Call Point - Protection False Alarm Mitigation 1. INTRODUCTION... 3 2. BS 5839-1 RECOMMENDATIONS...
More informationHow to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?
Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through
More informationBS 5839: Part THE CHANGES
BS 5839: Part 1 2013 THE CHANGES INTRODUCTION This document has been created to summarise the main changes that have been made to the BS 5839 Part 1 2013. This data is correct at the time of publication
More informationFixed fire protection solutions
Risk Engineering Fixed fire protection solutions At a glance Fixed fire protection can reduce the severity of fire events and positively impact Risk Engineering Assessments. To provide an effective solution
More informationFactors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment
Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Hong-Zeng (Bert) Yu FM Global 16 th International Water Mist Conference September 21-22, 2016 Vienna,
More informationThe Route to Third Party Certification
www.fia.uk.com INTRODUCTION If you work in any part of the fire safety industry you will at least have heard of Third Party Certification (TPC) but you may not be too sure what it is. Even if you work
More informationGuidance Document on Caravan and Camping Sites Fire Safety Equipment Requirements
Guidance Document on Caravan and Camping Sites Fire Safety Equipment Requirements FIA Guidance for the Fire Protection Industry This Guidance Note is intended as a general guidance and is not a substitute
More informationMORE THAN JUST FIRE PROTECTION
MORE THAN JUST FIRE PROTECTION VID Fire-Kill is a world leading innovative developer and manufac turer of water based firefighting products, specializing in fixed water based systems utilizing environmental
More informationSTANDARDS FOR ACTIVE FIRE PROTECTION. Stewart Kidd Loss Prevention Consultancy Ltd
STANDARDS FOR ACTIVE FIRE PROTECTION Stewart Kidd Loss Prevention Consultancy Ltd This presentation will consider: The risks to both new and existing buildings which can be countered by active fire protection
More informationMSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017
Procedure Number: E1-03 Revision Date: 02/16/2017 References: S. T. Brady, CDR, Chief, Engineering Division a. National Fire Protection Association (NFPA) 750, 1996 Edition, Standard on Water Mist Fire
More informationSafer.Smarter.Tyco. Watermist fire protection Technology you can trust
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust / 2 / / 3 / Trust in Tyco Tyco s AquaMist Systems Tyco Fire Protection Products helps to keep people, property and the environment
More informationFire Sprinkler Courses
Fire Sprinkler Courses BS 9251: Residential and Domestic Systems BS EN 12845: Commercial Systems Xact Consultancy and Training Limited T: 01386 277980 F: 0845 0941 887 qualifications@xact.org.uk www.xact.org.uk
More informationFire protection for buildings
Fire protection for buildings HI-FOG high-pressure water mist Ghelamco Group Protecting people, property and business continuity A fire in a building can lead to serious consequences. Even a harmless fire
More informationThe Science Behind Water Mist Protection of Typical Building Hazards
The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested
More informationSOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS.
SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P-01-05 THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS October, 2005 Society of Fire Protection Engineers - 1 - Position Statement
More informationLegal Requirements. There is no general legal requirement to install sprinklers. in places of work
01 A sprinkler system is a pipework distribution system charged with water, with a network of heatsensitive sprinkler heads supplied via a tank/reservoir or a water main. If the temperature rises above
More informationExtended Coverage Sidewall Sprinklers
VdS Guidelines for water extinguishing systems VdS 2100-28en Extended Coverage Sidewall Sprinklers Requirements and Test Methods VdS 2100-28en : 2011-05 (01) Publishing house: VdS Schadenverhütung GmbH
More informationCertificate No: EWS534
Certificate No: EWS534 Plumis Automist Smartscan Hydra Description of Product This is an assessment of the Plumis Automist multiroom Smartscan Hydra targeted fire suppression system. The system utilises
More informationAustralian Standard. Fire hydrant installations. Part 1: System design, installation and commissioning AS
AS 2419.1 1994 (Incorporating Amendment Nos 1 and 2) AS 2419.1 1994 Australian Standard Fire hydrant installations Part 1: System design, installation and commissioning This Australian Standard was prepared
More informationFixed Fire Protection Getting it right, Ensuring Performance and Value
Fixed Fire Protection Getting it right, Ensuring Performance and Value 18 th May 2017 Stuart Lloyd, EngTech TIFireE Principal Risk Engineer Practice Leader Fire Protection Engineering Zurich Risk Engineering
More informationApproved products and systems for water mist systems and VdS 3188 for planning and installation
Approved products and systems for water mist systems and VdS 3188 for planning and installation Stefan Kratzmeir, VdS Schadenverhütung VdS, 2017 Content Who is VdS? Integrated concept for reliable and
More informationAustralian Standard. Water mist fire protection systems System design, installation and commissioning AS
AS 4587 1999 Australian Standard Water mist fire protection systems System design, installation and commissioning This Australian Standard was prepared by Committee FP/12, Aqueous Fire Protection Systems.
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationMORE THAN JUST FIRE PROTECTION
MORE THAN JUST VID Fire-Kill is a world leading innovative developer and manufac turer of waterbased firefighting products, specializing in fixed water-based systems utilizing environmental friendly firefighting
More informationand Sprinkler System in Resalat Tunnel of Tehran
CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home
More informationProven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist
Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Water Mist for Transformer Fire Protection
More informationReport on First Revision November 2013 NFPA 750
750 FR1 (Chapter 2) Recommendation: Update the following references: Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard
More informationTECHNICAL DATA 1. PRODUCT NAME 2. DISTRIBUTOR 3. INTRODUCTION 4. FIELD OF APPLICATION 5. TECHNICAL DATA. Page 1 of 6
Page 1 of 6 1. PRODUCT NAME Viking Model EM Low Pressure Mist Nozzle System VK824, 125 Spray Pattern, K Factor Metric = 12.0, US = 0.82, Viking P/N - 13633 VK825, 95 Spray Pattern, K Factor Metric = 7.0,
More informationWatermist Systems. Versatile, Affordable Water Mist Fire Suppression. your TRUSTED partner in fire safety
Watermist Systems Versatile, Affordable Water Mist Fire Suppression your TRUSTED partner in fire safety A New Era in Water-Based Fire Protection Water is the safe, natural way to extinguish a fire. But,
More informationApproval of water mist systems in buildings
on Danish Guideline Approval of water mist systems in buildings Back ground Contents of the publication Introduction Water mist in buildings Classification test Risk classes Components Systems Installers
More informationAS 2419 OVERVIEW OF PROPOSED CHANGES. Gary Nenadovich Director G N Consulting
AS 2419 OVERVIEW OF PROPOSED CHANGES Gary Nenadovich Director G N Consulting Disclaimer FPA Australia's policy is one of continuous improvement, details of products, procedures or methods described within
More informationFollowing are the systems proposed as per NBC & Local Fire Authority:
1. OBJECTIVES AND STRATEGIES OF THE FIRE PROTECTION DESIGN This report describes the design parameters, system requirements of fire protection system for mixed occupancy (Assembly + Business) building
More informationInterfacing Fire Alarm, Sprinkler and Elevator Systems
1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators
More informationAssociation of Irish Risk Management An Introduction to Sprinklers 12th September 2012
Association of Irish Risk Management An Introduction to Sprinklers 12th September 2012 Introduction Welcome Presenters National Sprinkler Company Agenda The development of sprinkler protection an historical
More informationWAS STARTED BY CARLOS BAHAMONDES MASAFIERRO
WWW.WATERMIST.CL WWW.WATERMIST.CL WAS STARTED BY CARLOS BAHAMONDES MASAFIERRO ALTHOUGH SOLUTIONS SUCH AS THESE ARE NOW MORE IMPORTANT THAN EVER IN TIMES OF SEVERE DROUGHT, CARLOS BAHAMONDES MASAFIERRO
More informationCode of Practice for Design, Installation, Commissioning & Maintenance of Duct Smoke Detector (DSD) Systems
Code of Practice for Design, Installation, Commissioning & Maintenance of Duct Smoke Detector (DSD) Systems Issue 1.0 Page 1 of 35 Fire Industry Association Code of Practice for Design, Installation, Commissioning
More informationThis document is a preview generated by EVS
TECHNICAL SPECIFICATION SPÉCIFICATION TECHNIQUE TECHNISCHE SPEZIFIKATION CEN/TS 14972 May 2008 ICS 13.220.20 English Version Fixed firefighting systems - Watermist systems - Design and installation Installations
More informationI wish I could protect my business with the most suitable Water Mist solution to fit my needs.
I wish I could protect my business with the most suitable Water Mist solution to fit my needs. Wish granted! Tyco AquaMist systems are a versatile and highly efficient fire-fighting resource, featuring
More informationThe EN54 Part 2 and 4 Fire System
Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire
More informationPREVENT SYSTEMS WHEN SAFETY IS TAKEN SERIOUSLY
SUPPLIER OF LOW PRESSURE WATER MIST TECHNOLOGY FOR FIRE SUPPRESSION WWW.PREVENT-SYSTEMS.COM PREVENT SYSTEMS WHEN SAFETY IS TAKEN SERIOUSLY PREVENT SYSTEMS 1 OUR HISTORY INNOVATION The history about our
More informationISO 6183 INTERNATIONAL STANDARD. Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation
INTERNATIONAL STANDARD ISO 6183 Second edition 2009-06-15 Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation Équipement de protection contre l'incendie
More informationFire Sprinkler Courses
Fire Sprinkler Courses BS 9251: Residential and Domestic Systems BS EN 12845: Commercial Systems Xact Consultancy and Training Limited T: 01386 277980 F: 0845 0941 887 qualifications@xact.org.uk www.xact.org.uk
More informationPolicy for the Supply of Water to Automatic Fire Sprinkler Systems. October 2014
Policy for the Supply of Water to Automatic Fire Sprinkler Systems October 2014 Contents Introduction... 3 Principles... 3 Aims of the Policy... 3 Roles and Responsibilities... 4 Water Supply Arrangements
More informationWATER MIST CONVENTION AND EXHIBITION
INTERNATIONAL WATER MIST ASSOCIATION IWMA SEMINARS S ON WATER MIST TECHNOLOGY DUBAI INTERNATIONAL CONVENTION AND EXHIBITION CENTRE Water mist fire protection: The most innovative fire fighting technology
More informationWater mist fire suppression systems. Minifog ProCon Low-pressure water mist system
Water mist fire suppression systems Minifog ProCon Minifog ProCon Low-pressure water mist system IRE PROTECTION Efficient even for non-enclosed equipment Minifog ProCon systems by Minimax use innovative
More informationTraining Courses. The most comprehensive technical fire safety training programme.
Training Courses The most comprehensive technical fire safety training programme www.fia.uk.com What s inside? 4 Why should I choose the FIA for my training? 5 Terms and Conditions Fire Detection & Alarms
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and
More informationReport on First Revision June 2014 NFPA 5000
5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee
More informationWater Mist v Sprinklers
Water Mist v Sprinklers 15 th November 2018 Gary Howe EngTech FIFireE MIFPO Senior Fire Protection Engineer Zurich Risk Engineering Photo source: Stuart Lloyd, Zurich Zurich Fire Protection BS8489 FIA
More informationRetrofitting AFSS in Social Housing Highrises
East Midlands Retrofitting AFSS in Social Housing Highrises Stewart Kidd, MA, MSc, FIFireE, FIFSM Special Projects Consultant, BAFSA Protecting people, property and the environment Coroners Guidance following
More informationHI-FOG for buildings. Technical introduction. Protecting people, property and business continuity. Jussi Tiainen
HI-FOG for buildings Technical introduction Jussi Tiainen Protecting people, property and business continuity Contents Introduction to HI-FOG...3 How HI-FOG fights fire...4 Principles of HI-FOG system
More informationHigh-Pressure Water Mist systems for the protection of shopping centres in historical city centres
Danfoss Fire Fighting High-Pressure Water Mist systems for the protection of shopping centres in historical city centres Presenter: Antonio Terio October 25 th 2017, IWMC Rome 1 Introduction & Background
More informationNew Approaches to Design for Fire Safety - Residential sprinklers, open plan flat layouts and water mist
New Approaches to Design for Fire Safety - Residential sprinklers, open plan flat layouts and water mist Dr Corinne Williams Fire Safety Group Probyn Miers Event Tuesday 20 th July 2010, London Contents
More informationWater Mist System. Principle of Water mist evolves from combination of 3 main effects:
Water Mist System - by T R A Krishnan 1. Introduction A water mist system is a fire suppression system that, when activated, will discharge a spray of water droplets from a nozzle (or array of nozzles).
More informationPage 1 of 12 Input No. 62-NFPA 409-2013 [ Section No. 3.3.9 ] 3.3.9 Hangar Building Cluster. A group of buildings with more than one area for the storage and servicing of aircraft and all attached or contiguous
More informationNFPA 45 NFPA 211 NFPA 1600
NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA
More informationMSC Guidelines for Automatic Sprinkler Systems
S. J. Kelly, CDR, Chief of Engineering Division References a. Title 46 CFR 56.20, 56.50 & 56.60 (Subchapter F) b. National Fire Protection Association (NFPA) 13, 1996 Edition, Installation of Sprinkler
More informationUpdate on European Standardization Work
Update on European Standardization Work 16th International Water Mist Conference 21st & 22nd September 2016 in Vienna, Austria Joachim Böke Minimax Viking GmbH Industriestraße 10/12 23840 Bad Oldesloe
More informationFact File 66. Guide to Beam Smoke Detectors
Fact File 66 Guide to Beam Smoke Detectors Guide to Beam Smoke Detectors INTRODUCTION... 3 TERMINOLOGY... 4 PURPOSE OF BEAM DETECTORS... 5 PROS AND CONS OF BEAM DETECTORS... 6 FUNDAMENTAL PRINCIPLES OF
More informationFireward Fixed Fire Fighting System. For Open Areas & Enclosed Risks fireward.co.uk
Fireward Fixed Fire Fighting System For Open Areas & Enclosed Risks 0800 151 0249 Email: sales@fireward.co.uk fireward.co.uk Industry Specific Solutions At Fireward we pride ourselves in the provision
More informationCERTIFICATE OF FIRE APPROVAL
LR427.201.12 CERTIFICATE OF FIRE APPROVAL This is to certify that The product detailed below will be accepted f compliance with the applicable Lloyd s Register Rules and Regulations and with the International
More informationAutomatic Sprinkler Systems Care and Maintenance
0-0.0 January 2012 Country of Origin: United Kingdom Automatic Sprinkler Systems Care and Maintenance Introduction...1 Weekly Inspection and Tests...2 Monthly Inspection and Tests...3 Service and Maintenance
More informationDEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS
Section 400.000 Suppression Systems The purpose of this guide is to assist the Incident Commander (IC), Fire Officers and Firefighters with the planning of effective operations for supporting water-based
More informationFire Protection for Printing Machines with High Pressure Water Mist
Fire Protection for Printing Machines with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Case Study PRINOVIS Printing Company - PRINOVIS is Europe s
More informationSUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%
210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent
More informationCO 2 Fire Extinguishing Systems
Guidelines for Fire Extinguishing Systems Planning and Installation Content 0 Foreword... 10 0.1 Application of the VdS guidelines... 10 1 General... 10 1.1 Scope... 10 1.2 Aims... 11 1.3 Description...
More informationStandards and third party certification
Protecting People, Property and the Planet Standards and third party certification Nigel Firkins Content Developer, Fire Suppression BRE/NFCC Fire Protection Seminar Fit for purpose and reliable in service?
More informationREVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS
REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav
More informationTechnologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230
Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec
More informationWatermist Systems Compliance with Current Fire Safety Guidance
Technical Guidance Note Watermist Systems Compliance with Current Fire Safety Guidance Issue No 1: February 2012 ISBN 0-9552628-9-5 The UK Watermist Co-ordination Group is formed from representatives drawn
More informationMoving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design
Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System Part 1: Concept Design 2 Amy L. Porter, P.E. (TX,VA, NM) AND Michael Wojcik, P.E. (AZ, CO, MA,
More informationIMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G Ref. T4/4.01 IMO E MSC/Circ.914 4 June 1999 GUIDELINES FOR THE APPROVAL
More informationTN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco.
TN-25 Tunnel Fire Protection System Safer. Smarter. Tyco. Expert Fire Protection for Tunnels Tyco provides a complete fire protection solution to protect the infrastructure of tunnels. Whether it is rail,
More informationApplication of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE
Application of BS 8489 to the Protection of Generator Enclosures IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE Agenda Generator Enclosure Characteristics Generator Fire Characteristics Machinery
More informationVELMIST. System Mgły Wodnej Niskociśnieniowej
VELMIST System Mgły Wodnej Niskociśnieniowej VID Fire-Kill Innovative Solutions FM Approved Low Pressure Watermist nozzles for commercial and industrial applications. Complete range of Low Pressure Watermist
More informationNZS 4510:2008 Incorporating Amendment No. 1. New Zealand Standard. Fire hydrant systems for buildings. Superseding NZS 4510:1998 NZS 4510:2008
New Zealand Standard Fire hydrant systems for buildings Superseding NZS 4510:1998 NZS 4510:2008 Incorporating Amendment No. 1 NZS 4510:2008 Committee Representation This Standard was prepared under the
More informationProCon PC-M Low Pressure Water Mist System. for Machinery Spaces and Object Protection
ProCon PC-M Low Pressure Water Mist System for Machinery Spaces and Object Protection Fire protection Protection of a wide range of risks ProCon PC-M systems use innovative low pressure water mist technology.
More informationSprinkler systems. A presentation for fire brigade staff
Sprinkler systems A presentation for fire brigade staff Sprinkler systems Content Sprinkler system benefits Operation by fire brigade FAQ System description Basic system design Sprinkler systems In this
More information