La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

Size: px
Start display at page:

Download "La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual"

Transcription

1 La Marche Manufacturing Company Option 16 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain the newest version of the manual at Bradrock Dr. Des Plaines, IL CPN Instruction Drawing Number: P25-LOPT16SERIES-1 i Tel: Fax: Revision A07 Rev. Date: 03/17 ECN: 21360

2 1.0 Option 16 Series Operation 1.1 General Description The 16 series option includes the LED user-interface display panel which has eleven functional LED indicators on the front panel. One LED is used to indicate Equalize mode, one LED is to indicate AC voltage, five LEDs are used for various alarms, and four LEDs are used for display indications. The display also has a High Voltage Shutdown alarm reset push button and an Equalize/Select toggle switch. Figure 1A LED Display Showing System Output Voltage (while in Float mode) Toggling down on the Equalize/Select switch changes the display. The four green meter-select LEDs that are mounted horizontally on the bottom of the display indicate the display status. The following items can be displayed and have an LED indicator: DC Volts Displays the output DC voltage. DC Amps Displays the output DC amperage. Timer Mode Shows what Equalize timer mode the charger is currently set for. Figure 1B Display Diagram NOTE: In 16J, 16Q, 46T, and 46U option, the two LEDs will also be provided on the door as positive ground and negative ground alarm indicators. Refer to Figure 2. In 16P and 16T option, an audible alarm with silence switch will be provided on the front panel. Figure 2 Negative and Positive Ground LEDs (On Front Panel 16J/Q/T/U Option) EQ Time In Float mode, displays the set Equalize time. In Equalize mode, counts down from the Equalize set time. When the charger is in Equalize mode, the yellow Equalize LED will be on and the voltage will change to the set Equalize value. Refer to Figure 3A. Toggling down on the Equalize/Select switch until the green EQ TIME LED is on will change the display to indicate the Equalize timer countdown. Refer to Figure 3B. Figure 3A LED Display Showing System Output Voltage (while in Equalize Mode) Figure 3B LED Display Showing Equalize Timer Countdown 2

3 1.2 Selecting the Charging Mode The digital display used in the 16 Series has two modes for DC output voltage; Float mode and Equalize mode. Float charging mode is used for all normal battery charging needs. Equalize mode is used when it is necessary to Equalize (or balance) the level of charge across all cells present in the battery. One LED is used to indicate Equalize mode on the front panel. There is no Float LED indicator. If the charger is in Float mode, simply toggle up the Equalize/Select switch to change into Equalize mode. If the charger is in Equalize mode, it will automatically switch back to Float mode after the designated Equalize time cycle is complete; alternatively, the charger can be manually switched to Float mode by toggling the Equalize/Select switch. 2.0 Alarms The available alarms for the 16 Series are: Low Voltage1, Low Voltage2, End of Discharge, High Voltage, Low Current, High Voltage Shutdown, Positive Ground, Negative Ground, AC Power Failure, and Summary. The corresponding alarm LED will illuminate when an alarm is triggered, if applicable. Figures 4A 4E illustrate the alarm relays provided on the 198 relay board. Each set of alarm relays have two sets of form C contacts which function identical to each other. Not all alarm relays function the same; refer to Table 1 for the logic of each relay. Figure 4A (16J/T Option) Figure 4B (16E/G/P Option) Figure 4C (16L Option) S2A-198 Relay Information Relay Function High DC Voltage Shutdown Low DC Current High DC Voltage Low DC Voltage 1/ Low DC Voltage 2 (End of Discharge) AC Power Failure Summary Positive Ground Negative Ground Logic Energize On Fail De-Energize On Fail Energize On Fail De-Energize On Fail De-Energize On Fail De-Energize On Fail Energize On Fail Energize On Fail Figure 4D (16Q Option) Figure 4E (16U Option) NOTE: See schematic or manual cover page to determine which alarm option is included. Table 1 3

4 2.1 Alarm Contact Specifications Load Resistive Load (P.F. = 1) Contact Material Maximum Allowed Current Max. Operating Voltage and Current Max. Switching Capacity Min. Permissible Load Ag (Au clad) 2 A 0.5 A at 125 VAC 0.25 A at 125 VDC 2 A at 30 VDC VA 60 W 10 ua, 10 mvdc Table Alarm Definitions AC POWER FAILURE ALARM will trigger and the green AC ON LED will turn off if the AC power to the charger is lost for longer than 5 seconds. There is no AC Power Failure LED, only alarm contacts. The alarm will automatically reset when AC power is restored to the charger. When AC power is lost, the front panel display and indicators will remain powered by the connected batteries. LOW DCV1 ALARM will trigger and the red LOW DCV1 LED will turn on if the DC voltage falls below the specified voltage threshold of the alarm for longer than 5 seconds. The alarm will clear once the low DC voltage condition is no longer present. LOW DCV2 / END OF DISCHARGE ALARM will trigger and the red LOW DCV2 LED will turn on if the DC voltage falls below the specified voltage threshold of the alarm for longer than 5 seconds. The alarm will clear once the low DC voltage condition is no longer present. Some options will define this as an End of Discharge Alarm with a different threshold. HIGH DC VOLTAGE SHUTDOWN ALARM will trigger and the red HI V SHUT DOWN LED will turn on if the output DC voltage of the charger rises above the alarm threshold for longer than 20 seconds and there is load on the charger. If the high DC voltage shutdown alarm activates, the DC output of the charger shuts off to prevent irreversible damage to the battery. This alarm will stay latched until the charger is reset by isolating from all power sources or pushing the reset button. NOTE: This alarm will not trigger if there is a Low Current alarm present. HIGH DC VOLTAGE ALARM will trigger and the red HI V LED will turn on if the output DC voltage rises above the specified voltage threshold of the alarm for longer than 5 seconds. The alarm will clear once the high DC voltage condition is no longer present. LOW DC CURRENT ALARM will trigger and the red LO A LED will turn on if the output DC current of the charger falls below the alarm threshold for longer than 5 seconds. This alarm can be disabled if considered a nuisance alarm. SUMMARY ALARM will default trigger if any of the other alarms are triggered. There is no Summary alarm LED, only alarm contacts. The Low Current, AC Power Failure, and Ground Detection alarms can be removed from the Summary alarm, but are included by default. POSITIVE GROUND ALARM will trigger and the green POSITIVE GROUND LED will turn on if 1.2mA or greater current is measured between the positive terminal of the battery and earth ground for longer than 5 seconds. This LED is found on a separate circuit board. The alarm will clear once the positive ground fault is no longer present. NEGATIVE GROUND ALARM will trigger and the green NEGATIVE GROUND LED will turn on if 1.2mA or greater current is measured between the negative terminal of the battery and earth ground for longer than 5 seconds. This LED is found on a separate circuit board. The alarm will clear once the negative ground fault is no longer present. 4

5 Alarm Delay (sec.) Summary Selectable Clearing Threshold Alarming Threshold (V/C) LED Indication AC Power Failure 5 Yes Low Voltage 1 5 No 5% LA / 1.2 NC LO DCV1 Low Voltage 2 5 No End of Discharge 5 No 5% (shown DCV) 5% (shown DCV) LA / 1.2 NC LO DCV LA / 1.1 NC LO DCV2 High Voltage 5 No LA / 1.61 NC HI V High Voltage Shut Down 20 No LA / 1.65 NC HI V SHUTDOWN Low Current 5 Yes * * LO A Summary Other Alarms - Positive Ground 5 Yes - - POSITIVE GROUND Negative Ground 5 Yes - - NEGATIVE GROUND Table 3 Alarm Default Values and Indications * Low Current alarming threshold is dependent on shunt size V/C Volts per Cell, LA Lead Acid, NC Nickel Cadmium NOTE: These recommended parameters are set as factory default settings. If required, change the alarm threshold levels after verifying with battery manufacturer. 2.3 Alarm Connection Procedure Before making any alarm connections, ensure that the AC power is off at the main breaker. Verify that no voltage is present by using a voltmeter at all AC and DC terminals. For relays mentioned as ENERGIZED on alarm condition: If it is desired that the annunciator be active until the alarm triggers, connect the annunciator leads to the NC and C contacts of the desired alarm (located on the relay alarm contacts on S2A-198 board). If it is desired that the annunciator be deactivated until the alarm triggers, connect the annunciator leads to the NO and C contacts of the desired alarm. For relays mentioned as DE-ENERGIZED on alarm condition: If it is desired that the annunciator be active until the alarm triggers, connect the annunciator leads to the NO and C contacts of the desired alarm (located on the relay alarm contacts on S2A-198 board). If it is desired that the annunciator be deactivated until the alarm triggers, connect the annunciator leads to the NC and C contacts of the desired alarm. 5

6 3.0 Adjusting Parameters All equipment is shipped from the factory fully checked and adjusted based on the model number. Do not make any adjustments unless the equipment has been powered-up and the settings have been determined to be incorrect. If the settings have been determined to be incorrect, adjustments may be made as detailed below. 3.1 Customer Calibration Mode In Customer Calibration Mode, the customer can access and change various parameters. To access the Customer Calibration Mode, hold the Equalize/Select toggle switch up towards Equalize for about 5 seconds. After CAL appears on the LED display, immediately release the toggle switch. The parameters will automatically cycle every 5 seconds if no change is made. Once in calibration mode, the customer can raise and lower values with the same toggle switch. After the last setting is passed, the settings will automatically be saved. If a setting is accidentally passed over, the customer can press the reset push button and restart calibration from the beginning. The calibration settings are listed in order below with a brief description and default values. NOTE: Some chargers could have additional settings included in the Customer Calibration menu; contact La Marche for further explanation of settings not mentioned below. The Customer Calibration menu is as follows: Low Voltage 1 Alarm This setting changes the voltage threshold that causes the Low DC Voltage Alarm to activate. The default setting is 1.98 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default Low Voltage alarm setting of 47.5VDC) Low Voltage 2 Alarm This setting changes the voltage threshold that causes the Battery End of Discharge Alarm to activate. The default setting is 1.75 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default Battery End of Discharge alarm setting of 42VDC) EQ Timer Mode This setting changes the mode of the Equalize Timer. The Equalize timer mode determines when the charger will go into an Equalize charging cycle. The timer modes are Mode 0 (P0), Mode 1 (P1), Mode 2 (P2), Mode 3 (P3), and Mode 4 (P4). The default setting for the Equalize timer mode is Mode 0 (P0). The Equalize Timer Modes are discussed in further detail in Section 3.2. EQ Timer Setting This setting changes the amount of time that the charger remains in the Equalize charging cycle once activated. When an Equalize cycle is started, the charger will remain in Equalize mode until the time selected by this setting has passed. By default, the Equalize timer is set for 8 hours. The battery manufacturer documentation should be referenced for battery specific settings. High Voltage Shutdown Alarm This setting changes the voltage threshold that causes the High Voltage Shutdown Alarm to activate. The default setting is 2.50 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default High Voltage Shutdown alarm setting of 60VDC) High Voltage Alarm This setting changes the voltage threshold that causes the High Voltage Alarm to activate. The default setting is 2.45 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default High Voltage alarm setting of 58.8VDC) Low DC Current Alarm This setting changes the current threshold that causes the Low DC Current Alarm to activate. The default setting is dependant on the shunt size of the charger. This alarm can be disabled if considered a nuisance alarm by lowering the threshold value to OFF. 6

7 3.2 Equalize Timer Modes The 16 Series offers five different modes of Equalize charging operation. The Equalize mode can be viewed on the charger display by toggling the Equalize/Select switch until the green Timer Mode LED turns on. The Equalize mode can be changed via the Customer Calibration menu, refer to section 3.1. In all of the Equalize modes below, the charger will return to Float mode if the Equalize/Select toggle switch is toggled up or when it completes its full charge time. Mode 0 (Displayed As P0 ) Mode 0 is a manual Equalize cycle and is the default setting for the charger. When the charger is set for Mode 0, the Equalize cycle must be activated manually. Once activated, the Equalize timer will turn on and the Equalize "LED" will light. The length of the timer is eight hours by default and can be changed via Customer Calibration. After the timer cycles to zero, the charger will immediately return to Float mode. Equalize mode will not start again until it is manually activated by the user. Mode 1 (Displayed As P1 ) Mode 1 is an automatic Equalize cycle that activates every 7 days. The length of the Equalize cycle is determined by the timer setting. The length of the timer is eight hours by default and can be changed via Customer Calibration. When the Equalize timer expires, the charger will immediately return to Float mode. Equalize mode will restart again after 7 days. Mode 2 (Displayed As P2 ) Mode 2 is an automatic Equalize cycle that activates every 14 days. The length of the Equalize cycle is determined by the timer setting. The length of the timer is eight hours by default and can be changed via Customer Calibration. When the Equalize timer expires, the charger will immediately return to Float mode. Equalize mode will restart again after 14 days. Mode 3 (Displayed As P3 ) Mode 3 is an automatic Equalize cycle that activates every 30 days. The length of the Equalize cycle is determined by the timer setting. The length of the timer is eight hours by default and can be changed via Customer Calibration. When the Equalize timer expires, the charger will immediately return to Float mode. Equalize mode will restart again after 30 days. Mode 4 (Displayed As P4 ) Mode P4 is an automatic Equalize cycle that is triggered when the battery experiences a sizeable discharge. When the DC voltage drops below the Low Voltage alarm threshold, and exceeds the Low Voltage alarm time delay, Mode 4 is activated. However, the Equalize timer will only start and run the charger in Equalize mode for the duration set in the Equalize menu after the charger has raised the battery voltage high enough to clear the Low Voltage alarm. When the Equalize timer expires, the charger will immediately return to Float mode. 7

8 4.0 Display Calibration In order to calibrate the display voltage and current to match the measured values, two small potentiometers are provided, located on the bottom of the 225A display board. P1 potentiometer is used to calibrate the display voltage and P2 potentiometer is used to calibrate the display current. Please refer to figure 5. NOTE: Adjusting the potentiometers mentioned will NOT change the output of the charger; only the display values will be changed. P1 (VCAL) Display Voltage Adjustment P2 (LCAL) Display Current Adjustment Figure 5 Display Calibration 8

9 Document Control and Revision History Part Number: Instruction Number: P25-LOPT16SERIES-1 Issue ECN: / / / / / / / /01 9

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 46 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

TPSD. Installation and Operation Manual. Filtered Battery Charger Power Supply / Battery Eliminator

TPSD. Installation and Operation Manual. Filtered Battery Charger Power Supply / Battery Eliminator La Marche Manufacturing Company www.lamarchemfg.com TPSD Filtered Battery Charger Power Supply / Battery Eliminator Installation and Operation Manual 106 Bradrock Dr. Des Plaines 60018-1967 Tel: 847 299

More information

A77 Series. Microprocessor Controlled SCR Filtered/Battery Eliminator Filtered Charger. Installation and Operation Manual

A77 Series. Microprocessor Controlled SCR Filtered/Battery Eliminator Filtered Charger. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com A77 Series Microprocessor Controlled SCR Filtered/Battery Eliminator Filtered Charger Installation and Operation Manual This manual is subject to change

More information

La Marche Manufacturing Company A36D. Battery Charger / Power Supply. Installation and Operation Manual

La Marche Manufacturing Company   A36D. Battery Charger / Power Supply. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com A36D Battery Charger / Power Supply Installation and Operation Manual 106 Bradrock Dr. Des Plaines, IL 60018-1967 Tel: 847 299 1188 Fax: 847 299 3061

More information

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for A36D & TPSD Chargers with S2A-341S and S2A-383S communication cards. Option 21P,

More information

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS SCADA INTERFACE INSTRUCTIONS - OPTION 21S - FOR A36D/TPSD SYSTEMS with option 500 and 550. A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE OPTION 21S INSTRUCTIONS This manual is valid for A36D/TPSD Chargers

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

A77 SNMPv1 SCADA INTERFACE INSTRUCTIONS

A77 SNMPv1 SCADA INTERFACE INSTRUCTIONS A77 SNMPv1 SCADA INTERFACE OPTION 21X INSTRUCTIONS This manual is only valid for A77 Chargers equipped with the following: S2A-368S card with software version P368S0111 080116 MIB file P389S-21X4-00 S2A-389S

More information

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd. F-2000 PC and AO OUTPUT BOARDS INSTRUCTION MANUAL Blue-White R Industries, Ltd. 500 Business Drive Huntington Beach, CA 92649 USA Phone: 714-89-8529 FAX: 714-894-9492 E mail: sales@blue-white.com or techsupport@blue-white.com

More information

A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS

A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS with 500 and 550 option. A36D/TPSD Modbus TCP SCADA INTERFACE OPTION 21Q INSTRUCTIONS This manual is valid for A36D/TPSD Chargers equipped

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

A77 SNMPv3 SCADA INTERFACE INSTRUCTIONS

A77 SNMPv3 SCADA INTERFACE INSTRUCTIONS A77 SNMPv3 SCADA INTERFACE OPTION 21X INSTRUCTIONS This manual is only valid for A77 Chargers equipped with the following: S2A-368S card with software version P368S0112 MIB file P389S-21X4-01-P368S0112

More information

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47) DIESEL ENGINE CONTROL UNIT DCU 205 - USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) 64 84 52 00 Fax: (+47) 64 84 52 12 office@auto-maskin.no - 1 - TABLE OF CONTENTS 1. INTRODUCTION TO THE DCU 205...4

More information

Installation and Operation Manual

Installation and Operation Manual SENTRY Protect Plus QUADPLEX PANEL Installation and Operation Manual For Hardwired Pumps Environment e Corporation Table of Contents 1 Overview...3 2 Sentry Protect Plus Quadplex Menu Flowchart...4 3 Wiring

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK Analox 1000 Series User Manual Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK T: +44 (0)1642 711400 F: +44 (0)1642 713900 W: www.analox.net E: info@analox.net

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Commercial and Light Industrial Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground

More information

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

Flopurge TS. Operation Manual

Flopurge TS. Operation Manual Flopurge TS Operation Manual Part Number 079-0204 Spectron Gas Control Systems United Kingdom Unit 4, Herald Court, University of Warwick Science Park, Coventry, CV4 7EZ +44 (0)24 7641 6234 sales@spectron-gcs.com

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input SCR/SCRF SERIES FLOAT BATTERY CHARGERS Industry s First Choice for Time-Tested Proven Reliability Single-Phase Input Three-Phase Input Applications for: Utility & General Industry Switchgear Engine starting

More information

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual BS-316 Gas detection control panel up to 16 inputs Installation operation manual Page 1 from 21 Contents 1 Operation instructions--------------------------------------------------------------------------------------------------------------------3

More information

MPT Electric Fire Pump Controller

MPT Electric Fire Pump Controller MPT Electric Fire Pump Controller Alarm Messages and Guide This manual provides alarm descriptions, troubleshooting steps, and alarm set point configuration information for Metron MPT Fire Pump Controllers

More information

VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL

VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL Copyrights 2007 Victron Energy B.V. All Rights Reserved This publication or parts thereof, may not be reproduced in any form, by any method, for any purpose.

More information

FDF Foam Pump Controllers Features

FDF Foam Pump Controllers Features FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input April 2006 SCR-SCRF Utility & General Industry Switchgear Alarm Systems Engine Starting Railroad Emergency

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK Installation Manual AQM-20 12vdc/24vdc Series Power Supplies AQM20 Supervised Power Supply/Charger 12vdc 20Amp/24vdc 10Amp Life Time Warranty Quality Manufactured in the USA AQM20 Features: The AQM20 has

More information

Flostop TS D7E and A8E. Operation Manual

Flostop TS D7E and A8E. Operation Manual Flostop TS D7E and A8E Operation Manual United Kingdom Spectron Gas Control Systems Ltd, Unit 4, ATU1, University of Warwick science Park, Coventry, +44 (0) 24 7641 6234 sales@spectron-gcs.com Germany

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming

More information

OPERATION & MAINTENANCE MANUAL GUARDIAN SPACE PRESSURE MONITOR WITH REMOTE AUXILLARY ALARM

OPERATION & MAINTENANCE MANUAL GUARDIAN SPACE PRESSURE MONITOR WITH REMOTE AUXILLARY ALARM OPERATION & MAINTENANCE MANUAL GUARDIAN SPACE PRESSURE MONITOR WITH REMOTE AUXILLARY ALARM PARAGON CONTROLS INCORPORATED P.O. BOX 99 FORESTVILLE, CALIFORNIA 95436-0099 (707) 579-1424 /SPM REV. 7, 7/24/09

More information

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger

More information

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER PNEUMERCATOR Liquid Level Control Systems Electronic Systems Excluding LC2000 And TMS Series MAINTENANCE & TROUBLESHOOTING GUIDE 400 300 500 FUEL LEVEL LEAK MONITOR 1 200 600 OIL/GAS NORMAL WATER PNEUMERCATOR

More information

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 INTRODUCTION Thank you for purchasing the Hokkim Integrated Automatic Mains Failure Control Board model HAMF- 8 or HAMF-4. We shall

More information

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY Introduction.

More information

Product Manual SZ1144

Product Manual SZ1144 Product Manual SZ1144 Refrigeration Temperature Monitor Communicating Controls Description The SZ1144 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Introduction. OM-THA2

Introduction. OM-THA2 Introduction. The OM-THA2 is a multi-function product that monitors Temperature, Humidity and Dew Point, provides alarms for out of range conditions, and continuously logs data. It consists of a base unit

More information

ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL

ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL SAFETY WARNING Please Refer to the Safety Warning in Section 7.1 regarding the chemicals in the oxygen sensor Analox Sensor Technology

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

FLOAT BATTERY CHARGERS

FLOAT BATTERY CHARGERS FLOAT BATTERY CHARGERS UNFILTERED SCR SERIES FILTERED SCRF SERIES SINGLE PHASE INPUT THREE PHASE INPUT Applications for: UTILITY & GENERAL INDUSTRY Switchgear Engine Starting Emergency Lighting Alarm Systems

More information

Addendum for STI-6406 with Dual Access Control

Addendum for STI-6406 with Dual Access Control Addendum for STI-6406 with Dual Access Control Description: This system contains a STI-6400 with a DPDT key switch to be mounted on one side of a door or wall; and a similar looking housing, also with

More information

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000 SERVICE INSTRUCTIONS FOR Fire Alarm System MINI-2000 Version 1.3 02.04.1998 Jari Ollila Tom Brunberg Oy Esmi Ab Copyright Oy ESMI Ab, 1991... 1998 The copyright to the documentation herein is the property

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input SCR/SCRF SERIES FLOAT BATTERY CHARGERS Industry s First Choice for Time-Tested Proven Reliability Single-Phase Input Three-Phase Input Applications for: Utility & General Industry Switchgear Engine starting

More information

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TPC VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIADI&O062705 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 7,8

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

Setup & Operation Index

Setup & Operation Index SENTRY PreSTAT SIMPLEX PANEL Installation and Operation Manual Environment One Corporation Setup & Operation Index Setup & Operation Index...2 Sentry PreSTAT Menu Flowchart...3 Overview...3 Wiring Instructions...5

More information

AL800ULADA. NAC Power Extender. Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

Batt-Safe Battery String Monitoring System

Batt-Safe Battery String Monitoring System Batt-Safe Battery String Monitoring System Technical White Paper October 2010 Introduction Battery monitoring systems are categorized as either cell monitors or string monitors. Battery cell monitors provide

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps TT-1023 1/97 INSTALLATION INSTRUCTIONS Original Issue Date: 2/94 Model: 6-2000 kw Market: Industrial Subject: Flush- or Surface-Mount Remote Annunciator Kits PA-293991 and PA-293991-SD The remote annunciator

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16

STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16 ST-97106N Revised 07-04 Section 25 (00-02-0283) STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16 Certain danger to human safety and to equipment may occur if some equipment

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-46 8/05 INSTALLATION INSTRUCTIONS Original Issue Date: 8/05 Model: Automatic Transfer Switches equipped with MPAC 500 Controls Market: ATS Subject: External Alarm Module (EAM) Kit GM38795-KP Introduction

More information

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Instruction Manual Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Manual PCT-3000 Revision 9/2014 The PCT-3000 series control console incorporates

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

CM-RQE70 PIR REQUEST TO EXIT DETECTOR

CM-RQE70 PIR REQUEST TO EXIT DETECTOR Door Activation Devices CM-RQE70 PIR REQUEST TO EXIT DETECTOR THIS PACKAGE INCLUDES (1) Wiring Harness (2) #6 x 3/4" Screws (2) 3/16" Wall Plugs (6) Wire Nuts (2) 's BP7175 1. GENERAL DESCRIPTION Camden

More information

Pump Logic User Manual CB-1000 P/N ILK-CB1000-1

Pump Logic User Manual CB-1000 P/N ILK-CB1000-1 Pump Logic User Manual CB-1000 P/N ILK-CB1000-1 STATEMENT OF LIMITED WARRANTY The limited warranty applicable to this product is set forth in USFilter Control Systems standard terms of sale that are made

More information

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08 GasScanner 8C Eight Channel Monitor Operator s Manual MINT-0281-XX Rev. A 01/29/08 Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials,

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

ANALOX 3000 Carbon Monoxide Monitor

ANALOX 3000 Carbon Monoxide Monitor ANALOX 3000 Carbon Monoxide Monitor User Manual Analox Sensor Technology Ltd 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT T: +44 (0)1642 711400 F: +44 (0)1642 713900 W: www.analox.net

More information

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller Gas Safety Products Installation, operating and maintenance 11/18/2015 American Gas Safety LLC 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Power Supply....

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit PRODUCT INSTRUCTIONS Fire Door Control Panel (FDCP) Floats Rd, Wythenshawe, Manchester. M23 9WB T: 44 (0)161 945 4561 F: 44 (0)161 945 4566 Stock Code Description Doc No: PI115 00133 00134 Ellard Fire

More information

NS (A) ECN

NS (A) ECN Installation and Operation Instructions Mark IIXG Diesel Engine Fire Pump Controllers FTA00 NS00-50(A) ECN 237793 Table of Contents INTRODUCTION... MOUNTING CONTROLLER... Wall Mount... - 2 Floor/Base Plate

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE DSGH Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE Revision History Revision History Version of manual Description Date 1.0 Initial release 051025 1.1

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point Medium - Control - System Franke & Haqenest GmbH Borngasse 1a * 04600 Altenburg Tel: 03447-499 313-0 Fax: 03447-499 313-6 email: info@mcs-gaswarnanlagen.de MCS User Guide MCS GasController Microprocessor

More information

CM-RQE70A PIR REQUEST TO EXIT DETECTOR

CM-RQE70A PIR REQUEST TO EXIT DETECTOR Door Activation Devices CM-RQE70A PIR REQUEST TO EXIT DETECTOR THIS PACKAGE INCLUDES (2) #6 x 3/4" Screws (2) 3/16" Wall Plugs (2) MOV's BP7175 1. GENERAL DESCRIPTION Camden CM-RQE70A Request-to-Exit Sensor

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

MTRA-FSP Level Control Relay. Installation & Operation Manual

MTRA-FSP Level Control Relay. Installation & Operation Manual MTRA-FSP Level Control Relay Installation & Operation Manual This Manual is the support documentation for the installation, commissioning and operation of the MTRA-FSP Level Control Relay. Document Revision

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

Motorised Infrared Optical Beam Smoke Detector. User Guide

Motorised Infrared Optical Beam Smoke Detector. User Guide Motorised Infrared Optical Beam Smoke Detector User Guide EN 1. General Information 50cm 50cm 8-100m Ensure clear line of sight from Detector to Reflector Mount on solid surfaces (structural wall or girder)

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

Instruction Manual Model A

Instruction Manual Model A 706 Bostwick Avenue, Bridgeport, CT 06605 TEL: 203-368-6751 FAX: 203-368-3747 1-800-566-6822 www.devarinc.com Instruction Manual Model 18-232A LOOP POWERED ALARM MANUAL NO. 990029 MODEL 18-232A LOOP POWERED

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,

More information

Ammonia Leak Detector Manual

Ammonia Leak Detector Manual Ammonia Leak Detector Manual Document No. 70-PHW-1023-R2.5 No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical,

More information