DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
|
|
- Stella Harvey
- 5 years ago
- Views:
Transcription
1 Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Introduction Page 3 Application Description 3 Design Considerations *5 Application Details 9 Main Function 9 Location *9 Graphic Representation 10 Point List 11 GX-9100 Printouts 12 * Indicates those sections where changes have occurred since the last printing Johnson Controls, Inc. 1 Code No. LIT
2 2 DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
3 Introduction Application Description This application is designed to perform a weekly test of two dedicated stairwell pressurization fans automatically. An advisory is issued if, within a specified time, the status feedback indicator from a fan does not equal the fan command sent by Metasys. Notes: This application note presents only an example of a smoke control strategy. Realize that since every building is unique, the details of applying the strategy will vary. This application note, then, is offered to assist you in developing an application that will be appropriate for your project. Elevator shafts should be treated like stairwells and be positively pressurized to prevent vertical migration of smoke through the building. Even though this application does not consider elevator shaft pressurization, you may want to include this type of control if the building uses elevators. This application contains a Pressurization Test process and an Alarm Logic process. The Pressurization Test process is triggered once a week by the DX Time Schedule. This process issues start commands to the two stairwell pressurization fans. The process remains in a waiting state from the time that the fans are started until the wait timer expires. After the process On time has continued long enough to show that all systems are operational, the process sends a stop command to each of the stairwell pressurization fans. The Alarm Logic process is triggered if any of the following occurs: A stairwell fan goes into alarm during the pressurization test. An alarm situation would occur if the fan feedback does not equal the fan command. The operator tests the alarm process manually. If either fan is in alarm and it is in the testing schedule and the Reset is false, the Sonalert (Model Number PD ) is energized. Depending on the system s Report Router configuration, advisory text (Critical 1) may be sent to the Report Manager and to the NC Direct Printer. An alarm message is sent to the Report Router/Alarm Management feature, indicating that the fan s feedback did not equal command. The alarm processing flag is then set to False. DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans 3
4 If a weekly test has energized the Sonalert, you can reset the Sonalert using the Fire Fighter s Smoke Control Station (FSCS) or Fire Operator Workstation (OWS). Command the Reset object to On. The Alarm Logic PLC sends a Reset command to the Sonalert output. Command the Reset object to Off so that the next alarm will latch. Regardless of fan states, the manual alarm test always sets the alarm. 4 DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
5 Design Considerations Keep the following considerations in mind when designing a Weekly Testing of Dedicated Stairwell Pressurization Fans smoke control application. In addition, please refer to the Smoke Control Technical Bulletin (LIT ) in this manual. For information on the definition and the initial configuration of the Programmable Logic Controllers (PLCs) and the program modules, use the GX-9100 software configuration tool. You can find important instructions and guidelines for using this application in How to Use the Metasys Smoke Control Library (LIT ), located in the Smoke Control section of this manual. You must define tag names for all points. You must define a hardware location for each object. You must schedule the Pressurization Test process to run once a week. However, do not schedule the Alarm Logic process to trigger. The two ways to use the Scheduling feature to trigger the Pressurization Test process are: - Schedule via the DX-9100/9120 time schedule, or - Schedule via the OWS (override TSnOUT) The Alarm Logic process has four triggers, each designated by a required connection block. The triggers are: - Alarm Status for Stairwell Fan Number 1 (SF1_Alm) for Stairwell Pressurization Fan Number 1. An alarm occurs when the output does not match the feedback. - Alarm Status for Stairwell Fan Number 2 (ST2_Alm) is for Stairwell Pressurization Fan Number 2. - Alm_Test is used to activate the sonalert. - Reset is used to silence the sonalert. DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans 5
6 The wait timer in the pressurization test is defaulted to two minutes. To change the wait time, go to the time schedule and enter a new stop time, not to exceed the response time specified in National File Protection Agency (NFPA) 92-Smoke Control Systems. Check the size of the fan to determine the waiting time between Start and Stop commands. For more information, refer to the Engineering Data Manual (FAN 347). Advisory text is sent to the OWS critical alarm summary and, if configured by report router, to the NC direct printer. The critical alarm summary has a column for text messages and a column for alarm messages. Advisory text will appear in the Text message column. The Critical Alarm Warning box appears at the OWS when an object goes into alarm or changes state. Alarm messages will be displayed in the Critical Alarm Warning box. Each fan alarm turns on a Logic Result Status (LRS). Use the Report Router/Alarm Management feature to create alarm messages, and link the alarm messages to the LRS points. The alarm message may read: Alarm Number 1 - Feedback does not match the command sent. The schedule time for fan runtime must be greater than the alarm delay timers for each of the stairwell fan s outputs. To schedule a test from the OWS, map in a Digital Constant (DCO) and replace the reference to TS1OUT in the GX-9100 program with DCO. This application complies with the UL 864 UUKL Smoke Control Listing. However, you are responsible for ensuring that the application complies with state and local regulations, and is approved by the Authority Having Jurisdiction (AHJ). 6 DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
7 For UL compliance: The Fire OWS reports critical alarms based on the alarm condition, and the alarm can only be cleared by resetting from the Fire OWS or the FSCS. If the DIs are used for smoke control then DI1 must be jumpered and mapped to the Fire OWS as a normal state of On. When DI1 is off, a critical alarm must be issued at both the printer and the terminal. This indicates a binary input fuse failure that must be fixed immediately, because the DI is no longer accurate. Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.) You must map the Reset (DCO1) and Alm_Test (DCO2) objects to the Fire OWS. The sonalert must be mapped to indicate a critical alarm. To maintain UL 864 UUKL Smoke Control Listing, you must connect a printer model number PRN-3 or PRN-4 to the Fire OWS or directly to the Fire Network Control Module (NCM). For printer installation, refer to the manual included with the printer. Also, configure the Report Router/Alarm Management feature to route your alarm messages to the printer. For specific wiring requirements, refer to Metasys Smoke Control Wiring Technical Bulletin (LIT ). DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans 7
8 8 DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
9 Application Details Main Function Location This application performs a weekly test of two dedicated stairwell pressurization fans. An advisory is issued if, within a specified time, feedback from a fan does not equal the fan command. A weekly test of any dedicated smoke control equipment is a requirement of UL 864 UUKL and NFPA 92 Recommended Practice for Smoke Control Systems. The DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans application is located under the Fire/Security/ILC Conference of the Engineering Services Bulletin Board System (BBS). Once logged on the BBS, you can download the file to your computer. The application is also located on The Advisor. Follow the path Offices>SystemServicesMilwaukee>EngineeringServices>Fire&Security. DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans 9
10 Graphic Representation layout Figure 1: GX-9100 Graphic Layout 10 DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
11 Point List Table 1: Hardware I/O Requirements Input Requirements Hardware Name of Location Module Engineer Units Req? Description DI1 FUSE ALM/NOR Yes DI1 Fuse Monitor DI4 STFN1FB OFF/ON Yes Stairway Fan 1 Feedback DI5 STFN2FB OFF/ON Yes Stairway Fan 2 Feedback Output Requirements Hardware Name of Location Module Engineer Units Req? Description DO3 Sonalert OFF/ON Yes Sonalert DO4 STFN1 OFF/ON Yes Stairway Fan 1 DO5 STFN2 OFF/ON Yes Stairway Fan 2 Table 2: Software I/O Requirements Hardware Location Name of Module Engineer Units Req? Description LRS9 SF1_Alm OFF/ON Yes Alarm Fan 1 LRS10 SF2_Alm OFF/ON Yes Alarm Fan 2 DCO1 Reset OFF/ON Yes Smoke Test Reset DCO2 Alm_Test OFF/ON Yes Manual Alarm Test TS1OUT Autotest OFF/ON Yes DX Time Schedule LRS1 Alarm NOR/ALA Yes Sonalert DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans 11
12 GX-9100 Printouts Table 3 shows the automatic weekly schedule of the pressurization test. This test runs from 11:00 p.m. to 11:02 p.m. on Saturday. Table 3: Time Schedule (TS1) - Data TIME SCHEDULE (TS1) - Data User Name :Autotest Description :Test output External Extension --> Stop Time Event #4 00:00 External Forcing ON--> Days for Event #4 0 External Forcing OFF--> Start Time Event #5 00:00 Extension Time Stop Time Event #5 00:00 Start Time Event #1 23:00 Days for Event #5 Stop Time Event #1 23:02 Start Time Event #6 00:00 Days for Event #1 6 Stop Time Event #6 00:00 Start Time Event #2 00:00 Days for Event #6 Stop Time Event #2 00:00 Start Time Event #7 00:00 Days for Event #2 0 Stop Time Event #7 00:00 Start Time Event #3 00:00 Days for Event #7 Stop Time Event #3 00:00 Start Time Event #8 00:00 Days for Event #3 0 Stop Time Event #8 00:00 Start Time Event #4 00:00 Days for Event #8 12 DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
13 Table 4 contains data for Timer 6. When the fans start or stop, the timers start. The output of the timers will go on (generate an alarm) if each fan status does not match within 60 seconds. If the status change occurs, the alarm will not sound. Table 4: Timer 6 Data TIMER (TIMER6) - Data User Name :Alm-Dly Description : TIMER #1 TYPE 4 TIMER #5 TYPE 0 Input Connection #1--> /STFN1 Input Connection #5--> Reset Connection #1--> /STFN1FB Reset Connection #5--> Time Period # Time Period # Time Units #1 0 Time Units #5 0 TIMER #2 TYPE 4 TIMER #6 TYPE 0 Input Connection #2--> STFN1 Input Connection #6--> Reset Connection #2--> STFN1FB Reset Connection #6--> Time Period # Time Period # Time Units #2 0 Time Units #6 0 TIMER #3 TYPE 4 TIMER #7 TYPE 0 Input Connection #3--> STFN2 Input Connection #7--> Reset Connection #3--> STFN2FB Reset Connection #7--> Time Period # Time Period # Time Units #3 0 Time Units #7 0 TIMER #4 TYPE 4 TIMER #8 TYPE 0 Input Connection #4--> /STFN2 Input Connection #8--> Reset Connection #4--> /STFN2FB Reset Connection #8--> Time Period # Time Period # Time Units #4 0 Time Units #8 0 DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans 13
14 Figure 2 shows the logic module ladder diagram for PLC1. LRS1 (Alarm) controls the sonalert. If the weekly schedule test is running (Autotest) and there is a fan alarm, the sonalert turns On. If the alarm is tested manually (Alm_Test), the sonalert turns On. If the reset is turned On, the sonalert turns Off. The Reset needs to be manually turned Off to process further alarms. Logic Module Ladder Diagram - PLC1 User Name : Description: SF1_Alm L Autotest Reset LRS1 SET SF2_Alm Alm-test L Autotest Reset L LRS1 RST plc1 Figure 2: Logic Module Ladder Diagram PLC1 14 DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
15 Figure 3 shows the logic module ladder diagram for PLC2. SF1-Alm and SF2-Alm are LRS9 and LRS10. These can be mapped as a normal state of Off (open) and generate a critical alarm when On. Logic Module Ladder Diagram - PLC2 User Name : Fan-Alm Description: SF1ALMOF L SF1-Alm ( ) SF1ALMON SF2ALMOF L SF2-Alm ( ) SF2ALMON plc2 Figure 3: Logic Module Ladder Diagram PLC2 DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans 15
16 Notes Controls Group FAN E. Michigan Street Metasys Network Technical Manual P.O. Box 423 Printed in U.S.A. Milwaukee, WI DX-9100/9120 Applications DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans
DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit
Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Introduction
More informationDX-9100/9120 Local Sonalert Logic
Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPICATION NOTE DX-9100/9120 ocal Sonalert ogic Introduction Page 3 Application Description *3 Design
More informationWeekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT
Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................
More informationWeekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture
Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................
More informationSingle Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture
Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Code No. LIT-1201736 Release 1.2 Issued January 10, 2005 Document Introduction.................................................
More informationMulti-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic
Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLCATN NT Multi-Story Building Floor Above/Floor Below Pressurization and xhaust Logic ntroduction Page 3
More informationMulti-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture
Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction.................................................
More informationWarehouse Smoke Exhaust and Reset Logic for a Rooftop Unit
Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLATN NTE Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit ntroduction Page 3 Application Description
More informationFire Operator Workstation (Fire OWS) User s Guide
Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of
More informationMetasys System Extended Architecture Smoke Control UL 864 UUKL Compliance
Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Code No. LIT-1201754 Release 1.2 Issued February 10, 2005 Document Introduction.................................................
More informationDX-9100 Applications from Engineering Services
System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications
More informationYork 25-Ton VAV Rooftop Unit
HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation
More informationMetasys System Extended Architecture Smoke Control System
Metasys System Extended Architecture Smoke Control System Technical Bulletin MS-NAE5510-0U Code No. LIT-1201684 Release 1.2 Issued February 10, 2005 Document Introduction.................................................
More informationMultistate Alarm. Introduction
Object Dictionary 1 Multistate Alarm Introduction The Multistate Alarm object adds the alarming capability for a Boolean or multistate attribute for any object, such as the Present Value of a Binary Input
More informationMetasys Integrator Cleaver-Brooks Application
Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Cleaver-Brooks Application lntroduction Page Application Details
More informationIntroduction. Introduction
M-Alarm User s Guide 1-1 Chapter 1 Introduction Introduction M-Alarm allows the user to view, store, and manipulate current alarms received by N1 or BACnet Object Linking and Embedding (OLE) for Process
More informationFire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43
Metasys etwork Technical Manual 636 Objects Section Technical Bulletin Issue Date 696 Fire System Objects Introduction Page *3 Description *3 Purpose *5 Capabilities *7 Functional Diagram *1 Operator Interface
More informationMetasys Integrator TITUS Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application
More informationReciprocating Chiller
HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence
More informationMetasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway
Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Code No. LIT-1201993 Software Release 2.1 Issued April 12, 2006 Supersedes July 20, 2005 Document Introduction.................................................
More informationMetasys Integrator Compu-Aire Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Compu-Aire Application lntroduction Page 3 Application Details
More informationSection 4: Operating Instructions
Section 4: Operating Instructions 4.1 Panel Control Buttons 4.1.1 Acknowledge/Step The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to steady and also changes
More informationP2000 and Metasys System Integration
P2000 and Metasys System Integration Product Bulletin Code No. LIT-12011781 Software Release 3.12 Issued June 20, 2013 Supersedes April 20, 2012 Refer to the QuickLIT Web site for the most up-to-date version
More informationFIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL
FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release
More informationControl/Communicator
Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality
More informationTEC210x-2 Series Networked Thermostats
Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment
More information2000 Series. Program Entry Guide. Control Panels
2000 Series EN Program Entry Guide Control Panels 2000 Series Program Entry Guide About This Manual EN 2 About This Manual This guide describes the programming parameters available to the 2000 Series Control
More informationMetasys Integrator Airflow Application
Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component
More informationEi600ZW Z-Wave Module for 10 Year Smoke Sensor with Siren
Ei600ZW Z-Wave Module for 10 Year Smoke Sensor with Siren Quick Start This device is a combination of a Z-Wave sensor (smoke sensor) and a Z-Wave actuator. Pressing the button 'Inclusion Button' for one
More informationTHE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL
S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE
More informationVerasys System Operation Overview Technical Bulletin
Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.
More informationMetasys Integrator Vilter Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 1294 APPLICATION NOTE Metasys Integrator Vilter Application lntroduction Page 3 Application Details *3
More informationP2000 and Metasys System Integration
P2000 and Metasys System Integration Product Bulletin Code No. LIT-12012141 Software Release 3.14 SP1 Issued June 23, 2017 The Johnson Controls P2000 Security Management System supports the integration
More informationTri-Stack Smart System
Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and
More informationMODEL B2 INSTALLATION MANUAL
RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and
More informationDocument No Issue 4 user manual
DX Document No. 996-148-000-4 Issue 4 user manual Dimension Series Table of Contents 1 INTRODUCTION... 5 1.1 NOTICE... 5 1.2 MODELS... 5 1.3 WARNINGS AND CAUTIONS... 7 1.4 NATIONAL APPROVALS... 7 1.5 EN54
More informationExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C
ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During
More informationD6500 reports are shown in typewriter style letters. For example, AC FAILED indicates the report sent when the panel reports an AC power failure.
Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be reliable. However, Radionics, Inc. assumes no responsibility for inaccuracies
More informationTC-9102 Applications
Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...
More informationTEC2100 Series Networked Thermostats
Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment
More informationD8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide
System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord
More informationGV2 Series Control Panels
GV2 Series Control Panels EN Owner's Manual Supplement System Requirements Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2000: UL Listed and Classified control unit Model
More informationFDG-008 and FDX-008. Fan Damper Control Modules. Installation and Operation Manual
FDG-008 and FDX-008 Fan Damper Control Modules TM TM NOTE: Use the FX-2000, FleX-Net or MMX Fire Alarm Control Panel Manual in conjunction with this document for complete installation information. Installation
More informationMADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL
RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating
More informationUse of the application program
Contents overview Use of the application program Use of the application program 1 1. Functional description 2 Switching on / off 2 Dimming brighter / darker 2 Dimming value (8 bit) 3 Status Switching (1
More informationUNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...
Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop
More informationABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE
ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE isocket Smart Relay is a complex Smart House system which is installed in the fuse cabinet (electric cabinet) in the house. We therefore assume that
More informationZM2 OPERATING AND MAINTENANCE INSTRUCTIONS
ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS CONTENTS 1. System Overview 2. User responsibilities 3. First Line controls and indications 3.1 Logging on to the fire alarm system 3.2 Checking system status
More informationFieldServer Driver - Serial FS Notifier NCA
Driver Version: 1.00 Document Revision: 15 Description FieldServer Driver - Serial FS-8700-98 Notifier NCA The NCA (Network Control Annunciator) Serial driver allows the FieldServer to record data from
More informationVersion 1.03 January-2002 USER S MANUAL
Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...
More informationZX1e ZX2e ZX5e. Document No Issue 01 user manual
ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL
More informationType 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B
PRODUCT BULLETIN SB 8001B Type 8001 ALARM ANNUNCIATOR TYPE8001 FEATURES 16 or 32 alarm points per flush mount enclosure Displays are backlit with long life LEDs and engraved to suit Dimmer controls built
More informationSEQUENCE OF OPERATIONS
SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,
More informationU ser's Guide PC6010
User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure
More informationRELEASE DEVICE CONTROLS
RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a
More informationVAC PLC. System Description
VAC PLC System Description Contents 1 General... 5 1.1 Expressions and phrases... 5 1.2 Locations... 5 1.3 Abbreviations and terms... 6 1.4 Function... 6 1.5 Parts... 7 1.5.1 PLC... 7 1.5.2 Point IO...
More informationF I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE
SAFE A N D SECURE Cornell 100 Elmwood Ave. Crestwood Industrial Park Mountaintop, PA 18707 Tel 800.233.8366 Fax 800.526.0841 Email: cornell@cornelliron.com O W N E R S M A N U A L M O D E L F I R E G A
More informationUsing the Room View Window
CIT5 User s Guide 4-1 Chapter 4 Introduction The Room View window uses a tabbed display to present the information about one selected room. This chapter describes the tabs and features of the Room View
More informationControl Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2
Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...
More informationSimplex Panel Interface Guide
Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.
More informationControl Panel User Guide (TO BE RETAINED BY THE USER)
Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-0585 Issue 7 Fike s policy is one of continual improvement
More informationACT2-CS Convenience Store Controller
Refrigeration Systems Technical Manual 804 Product Bulletins Section Product Bulletin Issue Date 0899 ACT2-CS Convenience Store Controller The ACT2-CS Convenience Store Controller is a fully programmable,
More informationQA16 Addressable System
QA16 Addressable System Operating Manual HORING LIH INDUSTRIAL CO., LTD. www.horinglih.com QA16 System Characteristics Each loop can connect with 250 devices. Easy system programming through PC to panel.
More information16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5
Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series
More informationRANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...
More informationNetwork Hardware and wiring (quiz)...
4120 Network/TSW (FA049) Course Agenda Day 1 Course Introduction (Presentation)... 8:00 am to 8:30 am Break Module 1 Installing and Configuring Network Software Applications 4120 New Network Programmer
More informationConventional Releasing Control Panel
s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:
More informationSEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR
SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front
More informationDAP III Zone Master User s Guide
DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP
More informationFrequently asked questions: Intelligent Transmitter Series
Frequently asked questions: Intelligent Transmitter Series The Wilcoxon family of Intelligent Transmitters, relay alarms, and communication modules can be used to implement low-cost online vibration monitoring
More informationIndependent Zone Control (I.Z.C.)
Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics
More informationDiscovery 4 Loop Analogue Addressable Control Panel (NVI & NVA series Protocols)
Nitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.) BETTER TO BE SAFE Discovery Analogue Addressable Fire Alarm Panels Discovery 4 Loop Analogue Addressable Control Panel (NVI & NVA
More informationX64 Wireless Training
X64 Wireless Training IDS Contents 1 Contents Features 3 Wireless Hardware 4 IDS & Duevi integration PCB 5 LED operation 5 Wireless Device Hardware setup 6 Location 260 7 LED Keypad Instructions 7 Adding
More informationTEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072
TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 Application Note 140-1042 Building Technologies Table of Contents Overview... 4 Hardware
More informationControl/Communicator Installation Manual
DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming
More informationManage Alarms. Before You Begin CHAPTER
CHAPTER 8 Manage Alarms This chapter contains the procedures for viewing and managing the alarms and conditions on a Cisco ONS 15454. Cisco Transport Controller (CTC) detects and reports alarms generated
More informationFire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96
Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 XL-2G Gold Product Overview 7 Zones (6 programmable + panic or keyswitch zone) Fast Loop Response
More informationCERTIFICATION BULLETIN
File: ULC Subject C100 ULC-G.5.2 CCF7 S500F/SC2 October 28, 2014 CERTIFICATION BULLETIN 2014-07 Second Edition ULC/ORD-C100-13 Smoke Control System Equipment To: Members of the ULC Advisory Committee Members
More informationHoneywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts
Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS Feature Charts Control Panels FEATURE CHART LYNX Plus (L3000) (Supported Feature) (Not Supported) N/A (Not Applicable) LYNX Touch (L5210)
More informationI/A Series A 2 Software FoxAlert Alarm Manager
Product Specifications I/A Series A 2 Software FoxAlert Alarm Manager PSS 21S-2B2 B4 Current Alarms Display Most Recent Alarms Display Summary Displays By Status Alarm History Display An Extensive Collection
More informationInstruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual
Instruction manual MTL process alarm equipment October 2016 CSM 725B rev 2 MTL RTK 725B Configuration Software Manual SECTION 1 - INTRODUCTION... 5 Basic Requirements... 5 SECTION 2 - SOFTWARE INSTALLATION...
More informationTebis application software
5 Tebis application software STG51x Radio smoke detector STG54x Radio heatstroke Electrical / Mechanical characteristics: see product information Product reference Designation ETS version TP device RF
More information6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL
6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)
More informationCELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL
Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...
More informationTrueAlarm Fire Alarm Systems
OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK
More informationReplaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge
Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays
More informationUser s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0
User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8
More informationSummit 3208GLD USER MANUAL. Electronics Line
Summit 3208GLD USER MANUAL Electronics Line Table of Contents 1: Introduction... 2 2: Overview... 3 3: Keypad Functions... 4 3.1: Keypads... 4 3.2: 3108 LCD Keypad Layout... 4 4: Basic System Operation...
More informationLaptop / PC Programming Manual
Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup
More informationMR3CCUHV Temperature/Defrost Control
Master Catalog 125 Temperature Controls Section A Product/Technical Bulletin Issue Date 0401 MR3CCUHV Temperature/Defrost Control The MR3CCUHV Temperature/Defrost Control is designed to control the temperature
More informationSolution Guide. UUKL Smoke Control System. 1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview
Solution Guide UL 864, 9th Edition, UUKL Smoke Control Listing Overview Applications Distech Controls UUKL smoke control system can be used for: Dedicated smoke control applications: Used exclusively for
More informationINTELLIGENT FIRE ALARM CONTROL PANEL
INTELLIGENT FIRE ALARM CONTROL PANEL FX-2000 SERIES Description Mircom s FX-2000 Series Intelligent Analog Fire Alarm Control Panel is designed to provide maximum flexibility of analog system requirements
More informationChallenge: Migrate Legacy BAS with Smoke Control
Application Integration Best Practices and Lessons Learned Legacy BAS Upgraded Without a Single Hour of Downtime This article shares lessons learned and best practices in retaining an existing smoke control
More informationMed Touch Master Alarm
Submittal Data Sheet Features The Powerex Med Touch Master Alarm Panel monitors and displays normal and alarm conditions from up to 128 remote medical gas source signals and provides alarm conditions as
More informationManage Alarms. Before You Begin CHAPTER
CHAPTER 9 Manage Alarms This chapter contains the procedures for viewing and managing the alarms and conditions on a Cisco ONS 15454 SDH. Cisco Transport Controller (CTC) detects and reports SDH alarms
More informationExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling
ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence
More informationSERIES 3000 INTELLIGENT FIRE ALARM CONTROL PANEL ENGINEERING PROGRAMING MANUAL TABLE OF CONTENTS.. 1 INTRODUCTION.. 3 SYSTEM POWER UP.
SERIES 3000 INTELLIGENT FIRE ALARM CONTROL PANEL ENGINEERING PROGRAMING MANUAL TABLE OF CONTENTS.. 1 INTRODUCTION.. 3 SYSTEM POWER UP. 3 1 PANEL SWITCHES. 3 FIRE ZONE LAMP 4 OTHER LAMPS 4 MULTIPLEX OUTPUT.
More informationCommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET
CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or
More informationManage Alarms. Before You Begin CHAPTER
CHAPTER 7 This chapter explains how to view and manage the alarms and conditions on a Cisco ONS 15310-CL. Cisco Transport Controller (CTC) detects and reports SONET alarms generated by the Cisco ONS 15310-CL
More informationOperation Manual Fighter ProVision Software. Version: 0.0 Revision: 1
Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User
More information