Operation & Maintenance Manual

Size: px
Start display at page:

Download "Operation & Maintenance Manual"

Transcription

1 Operation & Maintenance Manual GDS-58XP Explosion-Proof Sample Draw System for Toxic & Combustible Gases GDS Corporation 2513 Hwy 646 Santa Fe, Texas (409) (409) (Fax)

2 GDS-58XP Sample Draw System Users Manual V2.1 CAUTION: FOR SAFETY REASONS THIS EQUIPMENT MUST BE OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND INSTRUCTION MANUAL COMPLETELY BEFORE OPERATING OR SERVICING. ATTENTION: POUR DES RAISONS DE SÉCURITÉ, CET ÉQUIPEMENT DOIT ÊTRE UTILISÉ, ENTRETENU ET RÉPARÉ UNIQUEMENT PAR UN PERSONNEL QUALIFIÉ. ÉTUDIER LE MANUE D INSTRUCTIONS EN ENTIER AVANT D UTILISER, D ENTRETENIR OU DE RÉPARER L ÉQUIPEMENT. NOTICE: THIS DOCUMENT CONTAINS LICENSED INFORMATION THAT IS THE INTELLECTUAL PROPERTY OF GDS CORP; ACCORDINGLY, IT IS AVAILABLE ONLY UNDER LICENSE FROM GDS CORP AND MAY NOT BE REPRODUCED, WHOLLY OR IN PART, BY ANY LICENSEE TO ANY OTHER PERSON OR ORGANIZATION WITHOUT THE EXPRESS WRITTEN PERMISSION OF GDS CORP. For further information about GDS Corp, please call (409) or support@gdscorp.com Copyright 2012 GDS Corp. All Rights Reserved P/N Page 2

3 GDS-58XP Users Manual V2.0 CONTENTS 1 GDS-58XP SAMPLE DRAW SYSTEM Description Features GDS-58XP SPECIFICATIONS HARDWARE INSTALLATION Installing the GDS-58XP INITIAL SETUP Flow Setup Adjust Alarm Levels Verify Remote Readings Initial Calibration OPERATION & MAINTENANCE Overview Calibration Sensor Removal / Replacement SPARE PARTS GDS-58XP Spare Parts GASMAX Spare Parts WARRANTY Overview APPENDIX MODBUS Registers...14 Page 3

4 GDS-58XP Sample Draw System Users Manual V Moisture Calculations GASMAX Configuration...15 Page 4

5 GDS-58XP Users Manual V2.0 GDS-58XP SAMPLE DRAW SYSTEM 1.1 Description Thank you for choosing the GDS Corp GDS-58XP Explosion Proof Sample Draw system. The GDS-58XP provides a safe and reliable way to pull toxic or combustible gas samples from a remote location for measurement by a local GASMAX II gas monitor. The GDS-58XP is recommended for use with any hydrocarbon or hydrogen-based combustible gas or any toxic gas, including reactive components such as chlorine, chlorine dioxide or hydrogen fluoride*. The GDS-58XP features a long life brushless DC pump with low-flow warning switch with 5A local relay contacts for Alarm 1, Alarm 2 and Sensor or Flow fault. The GDS-58XP is designed for use in Class I Division 1 hazardous areas. 1.2 Features Designed for Class I Division 1 Hazardous Areas Long life Brushless DC sample pump with fixed 1.3 liters-per-minute flow rate Integrated flow switch connected to local 5A fault relay Local relay contacts for optional light or warning sounder Standard non-isolated 4-20mA current loop output (source) Optional 110 / 220VAC input (requires additional matching XP enclosure) Standard MODBUS slave interface for remote monitoring of signal and flow status High resolution display shows engineering units and trend data Built-in user-prompted calibration Magnetic interface for non-intrusive operation in hazardous areas GDS-58XP for reactive gases not for use in hazardous areas. Page 5

6 GDS-58XP Sample Draw System Users Manual V2.1 1 GDS-58XP SPECIFICATIONS Input Power: +24VDC +/- 10%, 12.5W max. Sensor Type: Any GDS Corp Toxic, Combustible or PID Sensor Analog Output: Single 4-20mA calibrated current loop (source), Relay Output: Dual 5A programmable relays for Alarm 1 and Alarm 2; Single 5A relay contacts for Sensor Fault and/or Low Flow Warning Digital Output: RS-485 Two-wire Serial MODBUS Slave Interface Flow rate: 0.5 to 1.0 liters / minute (adjustable) Maximum sample distance: Approximately 100 ft / 33 m Inlet and Outlet Fittings: ¼ Compression Dimensions: (W) x 10.0 (H) x 6 (D) Weight 11 pounds / 4.9 KG Page 6

7 GDS-58XP Users Manual V2.0 2 HARDWARE INSTALLATION 3.1 Installing the GDS-58XP Install the GDS-58XP in a suitable location within 100 ft / 33 m of the intended sample location. The GDS-58XP features four mounting holes that can be used to securely attach the sample draw system to a bulkhead or wall. Make sure there is sufficient clearance to install the sample inlet tubing and sample outlet tubing (if used). Also make sure that the Run / Cal valve can operate freely and that access to the Cal Port is not blocked for any reason. Pump & Flow Switch GASMAX II Monitor Sample Inlet Run / Cal Valve Cal Port Sensor & Flow Cell Flow Meter Sample Outlet Figure 1 GDS-58XP Note: In order for low flow switch to operate properly, the GDS-58XP must be mounted vertically. Page 7

8 GDS-58XP Sample Draw System Users Manual V2.1 DC Power: Connect a source of +24VDC, +/- 10% power to the power supply wiring terminals (See Fig 2). An external power switch and / or circuit protection device should be provided by the customer s wiring. If the area is considered hazardous then all explosion proof wiring recommendations, guidelines and regulations should be observed. PWR OUT 4-20 ECHEM OUT 4-20 LEL GND C2 C1 GASMAX I/O Power Supply P/N TP1 CATBEAD REF COM ACT +24VDC to TB2 #1 COM to TB2 #4 TB2 C8 C7 S1 TB1 O2/TOXIC: 4-20mA Output on TB2 #2 BRIDGE: 4-20mA Output in TB2 #3 Figure 2 GDS-58XP / GASMAX II Power Supply & Analog Signal Wiring Attach Note: If the optional P/N Class I Div 1 AC Power Supply is attached, connect the incoming AC wiring directly to the power supply Line, Neutral and Ground terminals. Analog Output: Connect the output 4-20mA current loop wiring to the appropriate controller or DCS input. If a TOXIC sensor is used (Oxygen, Hydrogen Sulfide, etc) then the output is taken from TB2, Pin #2. If a combustible or PID sensor is used, the output is taken from TB2, Pin #3. Alarm Relay Output: Alarm 1 ( Relay 1, TB1 Pins 1,2,3) and Alarm 2 ( Relay 2, TB1 Pins 4,5,6) contacts are located on the Relay / MODBUS board, attached to the back of the GASMAX II display (See Fig 3). These relays can be programmed via the main menu to close at preset signal levels, and can operate as either Alarm Above or Alarm Below contacts. Fault Relay Output: Relay 3 (TB1 Pins 7,8,9) is programmed to indicate a FAULT condition under the following circumstances: 1) Excessive negative sensor drift; 2) Sensor removed or 3) Flow switch dropout (low flow). If only a single wiring pair is available, the 4-20mA output can be routed through the FAULT relay. This will cause the current loop signal to be interrupted in the event of a low flow indication. Page 8

9 GDS-58XP Users Manual V2.0 Remote Alarm Reset TB3 P1 Relay 1 (K1) Relay 2 (K2) Relay 3 (K3) NO 1 C 2 NC 3 NO 4 C 5 NC 6 NO 7 C 8 NC 9 TB1 Assy: ST-48 Alarm / ModBus Option K1 K2 K A B S A B U1 J1 TB2 RS-485 A & B terminals are connected internally for easier IN / OUT cabling. S is no connect for shield to continue. A (Installs RS-485 Terminating Resistor) B (Omits RS-485 Terminating Resistor) Figure 3 GDS-58XP / GASMAX II Relay & MODBUS Wiring Attach MODBUS Output: The GASMAX II provides a two-wire RS-485 serial data link via TB2 Pins A & B. See the GASMAX II manual for more information on MODBUS registers and operation. Sample Inlet: Attach a length of tubing to the Sample Inlet using the supplied ¼ compression fitting. Note: If the sample location is excessively wet or dusty, GDS Corp recommends the installation of a coalescing or particulate filter on the intake end of the sample draw tubing. This will keep the particulate or moisture from being drawn into the sample tubing, sample draw pump and sensor. In the event the filter becomes clogged, the FLOW OK indication will be replaced by FAULT on the GASMAX II display and the Low Flow / Fault relay will energize. Sample Outlet: Attach a length of tubing to the Sample Outlet using the supplied ¼ compression fitting and route the tubing to a safe area. Note: Do not use more than 25ft of tubing and do not allow back pressure to build up in the sample flow cell. GDS Corp recommends that the outlet point be located no higher than 10 (3m) above the GDS- 58XP. Note: All GDS Corp sensors are designed to operate at ambient atmospheric pressure. Restricting the output in any way may create back pressure in the sensor flow cell that will generate erroneous readings and may damage the sensor if excessive pressure is present for long periods of time. Page 9

10 GDS-58XP Sample Draw System Users Manual V2.1 3 INITIAL SETUP 4.1 Flow Setup Once hardware installation is completed, apply power to the GDS-58XP and verify that the display is operational. Adjust the Sample Flow Meter to indicate 0.5 liters per minute of flow. If the flow meter does not indicate proper flow, check the inlet tubing for restrictions or blockage. To verify that the pump is running properly, set the Run / Cal valve to the CAL position (pointing to the RIGHT). The pump should be able to pull in excess of 1.0 liters / minute (full scale on the flow meter). If full scale flow cannot be obtained, check the sample outlet tubing for blockage. If normal flow cannot be obtained, contact GDS Corp. To check the Low Flow switch, set the Run / Cal valve to the blocked position (pointing straight up). The flow switch should activate and the FLOW OK message will be replaced by a FAULT indication. 4.2 Adjust Alarm Levels Using a magnetic wand, select the GASMAX Main Menu by placing the magnet next to the EDIT switch located on the lower right side of the GASMAX II display. Select ALARMs to adjust the levels, polarity on/off delays and other alarm-related settings. 4.3 Verify Remote Readings From the Main Menu, select DIAGNOSTICS. The GASMAX II will request an Access Code. Enter the access code by moving the magnetic wand over the UP key four times. The UP key is located on the upper left side of the GASMAX display. Activate the EDIT key to confirm. Select OUTPUT SIMULATION to set the 4-20mA signal to any value between 4ma (Zero) and 20mA (Full Scale). Confirm that the reading on the GASMAX matches the reading shown on any remote display or controller. Select RELAY TEST to activate the internal alarm relays and confirm that any remotely connected devices operate as expected. 4.4 Initial Calibration The GDS-58XP is now ready for initial calibration. See Section 5.2 for detailed instructions. Page 10

11 GDS-58XP Users Manual V2.0 4 OPERATION & MAINTENANCE 5.1 Overview Standard maintenance for the GDS-58XP consists of periodic checks on flow settings and sensor calibrations. Each time a toxic sensor is calibrated, a Sensor Life reading will appear that gives an approximate indication of the remaining sensitivity. Sensor Life is not necessarily linear and a rapid reduction in the senor life reading can be due to temperature extremes, high levels of target gas, the presence of certain gases that poison toxic sensors and other environmental factors. Sensor life readings also appear for combustible or PID sensors, but as these sensors operate on different principles and/or contain microprocessors that compensate for aging effects, the values shown may not accurately represent sensor life over time. Always check the flow meter for the presence of moisture. In the event that moisture or liquid is drawn in the GDS-58XP, the entire unit should be disassembled and cleaned. In some cases the flow meter or flow switch may need to be replaced. If liquid is drawn into the GDS-58XP, always inspect the sensor for any sign of damage. 5.2 Calibration On average, calibration should be performed approximately every two to three months, depending on target gas and sensor performance. Obtain a cylinder of calibration gas that is approximately ½ scale (For example, for a ppm range, obtain 50 ppm gas). If it cannot be guaranteed that the ambient air contains no target gas, also obtain a cylinder of zero air. In addition, a fixed flow regulator (0.5 to 1.0 liters / minute) and connecting tubing are required. Finally, make sure you have a magnetic wand to activate the GASMAX II monitor user interface. Important: Using the magnetic wand, activate the NEXT key until the GASMAX shows the dual display screen (see Fig 4.). If the message FLOW OK message is shown on the TOP display, the unit contains a BRIDGE type sensor and calibration should be done to the BRIDGE/MA Channel ONLY. If the FLOW OK message is shown on the BOTTOM display, the unit contains a TOXIC sensor and calibration should be done on the O2/TOXIC Channel ONLY. Page 11

12 GDS-58XP Sample Draw System Users Manual V2.1 Set the Run / Cal valve to the CAL position (pointing to the RIGHT). If the area may contain ppm levels of the target gas, attach a cylinder of Zero Air to the cal port using the fixed flow regulator. Open the valve on the regulator and confirm that the flow meter indicates gas flow. Using the magnetic wand, activate the NEXT key until the GASMAX shows the dual display screen (see Fig 4.). Put the GASMAX II in CAL MODE by activating the CAL key (lower left) followed by the EDIT key to confirm. When the SELECT INPUT screen appears, select O2/TOXIC or BRIDGE/MA as necessary (see above). The display will indicate when to apply ZERO gas. Once the reading is stable, activate the EDIT key to confirm. The display will now say to apply SPAN gas. ALM RST UP/ ALM1 ALM2 FAIL NEXT 17.8 % O2 Def. 0 % LEL DOWN/CAL EDIT A1 A2 RXD RS485 TXD Remove the cylinder of zero air and attach the cylinder of calibration gas. Open the regulator and verity flow on the flow meter. Once the reading stabilizes, activate the SPAN key to confirm. If readings are within proper limits, the message CAL SUCCESSFUL will appear. Fig 4 Dual Display Mode. Disconnect the cylinder of calibration gas and set the Run / Cal valve to the Run position (pointing LEFT). 5.3 Sensor Removal / Replacement To remove & replace the GDS-58XP sensor: 1) Loosen and remove the stainless steel tubing that is attached to the sensor flow cell 2) Loosen the set screw located at the top of the sensor flow cell 3) Remote the flow cell by gently pulling down and twisting at the same time. 4) Unscrew the sensor head cover. Use sensor head wrench (p/n ) if stuck. 5) Remove the sensor by pulling straight down. DO NOT TWIST. 6) Install the new sensor by aligning the arrow on the sensor with the engraved arrow on the sensor head. Press UP to install sensor. DO NOT TWIST. 7) Reinstall the stainless steel sensor head cover. Tighten securely. 8) Reinstall the sensor flow cell. Use approved O-ring grease (p/n ) if necessary. 9) Reinstall the stainless steel tubing and tighten securely. 10) Verify operation and calibrate new sensor. Page 12

13 GDS-58XP Users Manual V2.0 5 SPARE PARTS 6.1 GDS-58XP Spare Parts Flow switch, non-explosive Pump, 24VDC brushless Flow meter, 0-1 liter / minute with adjustment Flashback arrestors Flow cell 6.2 GASMAX Spare Parts Display assembly Relay / MODBUS interface board Power supply board with ribbon cable and standoffs 6 WARRANTY 7.1 Overview The GDS-58XP electronics is warranted for a period of two years from date of shipment. The Sample Pump and Sensor are warranted for a period of one year from date of shipment. Toxic sensors have a limited shelf life and will lose sensitivity over time, even if not used. Combustible and PID sensors have no such shelf life limitations. Page 13

14 GDS-58XP Sample Draw System Users Manual V2.1 7 APPENDIX 8.1 MODBUS Registers The GASMAX II gas monitor provides more than 100 readable MODBUS variables. Shown below are three that can be used to read system values and alarm status. See the GASMAX manual for more information and a complete listing of MODBUS registers. Register Alias Read Value Notes D2A Raw Ch Output from O2/Toxic type sensors D2A Raw Ch Output from Bridge type sensors Alarm Status Word Bits See GMII manual for bit definitions Ch1 Sensor Life Calculated O2/Toxic sensor life % remaining Ch2 Sensor Life Calculated Bridge sensor life % remaining 8.2 Moisture Calculations When drawing a sample that contains significant moisture, it is important to understand how much moisture may be entrained within the coalescing filter. At 0.5 liters per minute, the GDS-58XP will draw approximately 720 liters (0.72 m 3 ) of sample in a 24 hour period*. Sample Temp Sample RH Water content, g/m 3 Total water content Total coalesced water in 24 hrs* 20 C / 68 F 40% RH 9.4 g/m g/m g = 0.09 oz 60% RH 9.4 g/m g/m g = 0.13 oz 80% RH 9.4 g/m g/m g = 0.18 oz 100% RH 9.4 g/m g/m g = 0.23 oz 30 C / 86 F 40% RH 30.4 g/m g/m g = 0.29 oz 60% RH 30.4 g/m g/m g = 0.44 oz 80% RH 30.4 g/m g/m g = 0.59 oz 100% RH 30.4 g/m g/m g = 0.73 oz 40 C / 104 F 40% RH 51 g/m 3 20 g/m g = 0.48 oz 60% RH 51 g/m 3 31 g/m g = 0.75 oz 80% RH 51 g/m 3 41 g/m g = 0.99 oz 100% RH 51 g/m 3 51 g/m g = 1.2 oz 50 C / 122 F 40% RH 83 g/m 3 33 g/m g = 0.8 oz 60% RH 83 g/m 3 50 g/m 3 36 g = 1.21 oz Page 14

15 GDS-58XP Users Manual V2.0 80% RH 83 g/m 3 66 g/m g = 1.6 oz 100% RH 83 g/m 3 83 g/m g = 2.0 oz For example, the standard filter will hold approximately 3 oz of coalesced water. At 20 C / 40% RH, the filter will need to be drained every 30 days. For a sample at 40 C and 80% RH, the filter may need to be drained every three days. For high moisture applications, GDS Corp recommends the combination coalescing / bypass filter that will remove moisture and particulate in a continuous stream. For ambient sources of sample gas, this may require the installation of an upstream pump to force the sample through the filter and bypass port. 8.3 GASMAX Configuration The GASMAX gas monitor is a two-channel device, and the GDS-58XP relies on the unused GASMAX channel to monitor the low flow switch and generate a relay contact closure (FAULT) if the low flow condition is detected. If a BRIDGE-type sensor is installed (Combustible, Infrared for Photoionization), then the flow switch is monitored by the O2/TOXIC channel (Ch1). If an oxygen deficiency or toxic gas sensor is installed, the flow switch is monitored by the BRIDGE/mA channel (Ch2). To properly configure the GASMAX in the event the display is replaced, or if a Cold Boot is necessary to restore proper functionality, the following settings will need to be made to the default settings: GDS-58XP with Oxygen or Toxic Gas Sensor: 1. Turn on the Bridge/mA Channel by holding the magnet over the NEXT key until the menu shows Enter Key Sequence menu. Enter four UP keys to access the XMITTER CONFIG menu. Select BRIDGE/mA and hit EDIT to turn the channel ON. Hit the NEXT key to exit. The GASMAX will reboot. 2. Setup EUNITS: Once the GASMAX reboots, hit the NEXT key unit the dual display appears. Hit EDIT once and then once again to access the Select Input menu. Select the O2/TOXIC channel and hit EDIT again. Under System Config, change the EUNITS to read FLOW OK. 3. Ensure that the flow switch is connected to the R and C terminals on TB2 on the back of the display module. Polarity is not important. GDS-58XP with Bridge/mA Combustible, Infrared or Photoionization Gas Sensor: 1. Setup EUNITS: Hit the NEXT key unit the dual display appears. Hit EDIT once and then once again to access the Select Input menu. Select the BRIDGE/mA channel and hit EDIT again. Under System Config, change the EUNITS to read FLOW OK. 2. Ensure that the flow switch is connected to the _ and terminals on TB1 on the Power Supply board attached to the back of the explosion proof enclosure. Polarity is not important. Page 15

Operation and Maintenance Manual

Operation and Maintenance Manual Operation and Maintenance Manual GDS-48 Remote Bridge Sensor for Combustible Gases AUTHORIZED DISTRIBUTOR: GasDetectorsUSA.com - Houston, Texas USA sales@gasdetectorsusa.com - 832-615-3588 CAUTION: FOR

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Operation and Maintenance Manual GASMAX II Single / Dual Channel Gas Monitor GDS Corp. 1245 Butler Road League City, TX 77573 409-927-2980 409-927-4180 (Fax) ww.gdscorp.com CAUTION: FOR SAFETY REASONS

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Operation and Maintenance Manual GDS-68XP Process Monitor for Low O 2 Applications GDS Corp 1245 Butler Road League City, TX 77573 409-927-2980 409-927-4180 (Fax) www.gdscorp.com CAUTION: FOR SAFETY REASONS

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Operation and Maintenance Manual GDS-IR Infrared Sensor for Combustible Gases & CO 2 GDS Corp. 2513 Hwy 646 Santa Fe, Texas 77510 409-927-2980 409-927-4180 (Fax) www.gdscorp.com CAUTION: FOR SAFETY REASONS

More information

Model OI-6000K Sensor Assembly

Model OI-6000K Sensor Assembly Model OI-6000K Sensor Assembly Operation Manual Revision 2.4w Product Overview The Otis Instruments, Inc. Model OI-6000K Gen II ambient air gas sensor assembly is a 2-relay wired (Notis) sensor assembly

More information

Model OI-6000K Sensor Assembly

Model OI-6000K Sensor Assembly Model OI-6000K Sensor Assembly Operation Manual Revision 2.0w Product Overview The Otis Instruments, Inc. Model OI-6000K Gen II ambient air gas sensor assembly is a 2-relay wired (Notis) sensor assembly

More information

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety GDS Corp gas monitors, controllers and sensors satisfy today s needs for safety and reliability in critical gas detection

More information

GLD-30 Gas Leak Detector

GLD-30 Gas Leak Detector GLD-30 Gas Leak Detector Installation, Operation & Maintenance General: The Archer Instruments GLD-30 is an ambient air monitor, used to detect the presence of a target gas (or gases) and to alert operators

More information

Model D12-IR. Digital Gas Transmitter...

Model D12-IR. Digital Gas Transmitter... Model D12-IR Digital Gas Transmitter... ATI s Series D12 gas transmitter line now includes a versatile Infrared system that can be configured for LEL or select toxic gases. The D12-IR utilizes a compact

More information

Air Check EX LEL Gas Monitor Instruction Manual

Air Check EX LEL Gas Monitor Instruction Manual Air Check EX LEL Gas Monitor Instruction Manual PureAire Monitoring Systems, Inc. 1140 Ensell Road Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 www.pureairemonitoring.com

More information

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors Ultima X Series Gas Monitors Versatile fixed instruments provide continuous monitoring of many hazardous gases using catalytic, electrochemical, and infrared gas detection methods. HART Protocol is now

More information

SIL 2. Ultima X Series Gas Monitors CERTIFIED

SIL 2. Ultima X Series Gas Monitors CERTIFIED Ultima X Series Gas Monitors 5 Now with SIL 2 CERTIFIED Products Versatile fixed instruments provide continuous monitoring of many hazardous gases using catalytic, electrochemical, and infrared gas detection

More information

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification 1.0 This specification details the attributes and operating characteristics of the MSA Ultima X Series sensors/transmitters.

More information

RK-HC-04 M2A Transmitter Operator s Manual

RK-HC-04 M2A Transmitter Operator s Manual 65-2649RK-HC-04 M2A Transmitter Operator s Manual Part Number: 71-0327 Revision: B Released: 9/20/18 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

M2A Transmitter Operator s Manual

M2A Transmitter Operator s Manual M2A Transmitter Operator s Manual Part Number: 71-0305RK Revision: F Released: 1/8/18 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before operating instrument.

More information

SEC 2000 Millenium Infrared Gas Detector

SEC 2000 Millenium Infrared Gas Detector SEC 2000 Millenium Infrared Gas Detector Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 Email: sales@sensorelectronic.com

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Toxic Gas Detection. Model F12. Toxic Gas Detection

Toxic Gas Detection. Model F12. Toxic Gas Detection Toxic Gas Detection Model F12 Toxic Gas Detection Smart Sensor Technology The Series F12 Gas Transmitter is an Intrinsically Safe (IS) version of our explosion-proof D12 transmitter. In its standard form,

More information

INSTRUCTION MANUAL BUCKEYE DETECTION SYSTEMS MODEL BFT-48 TRANSMITTER

INSTRUCTION MANUAL BUCKEYE DETECTION SYSTEMS MODEL BFT-48 TRANSMITTER BFT-48 User Manual INSTRUCTION MANUAL BUCKEYE DETECTION SYSTEMS MODEL BFT-48 TRANSMITTER Warning: Read & understand contents of this manual prior to operation. Failure to do so could result in serious

More information

M2 Transmitter Operator s Manual

M2 Transmitter Operator s Manual M2 Transmitter Operator s Manual Part Number: 71-0107RK Revision: D Released: 10/7/10 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before operating instrument.

More information

OLCT 700 & 710. Certifications FIXED GAS DETECTION. Better detection. Better protection.

OLCT 700 & 710. Certifications FIXED GAS DETECTION. Better detection. Better protection. FIXED GAS DETECTION OLCT 700 Series OLCT 700/710 industrial gas detection sensors are a new generation of intelligent sensor modules that incorporate and integrate several leading edge improvements. &

More information

RKA-LEL Sample Draw Combustible Gas Detector

RKA-LEL Sample Draw Combustible Gas Detector 35-3000RKA-LEL Sample Draw Combustible Gas Detector Specifications Table 1 lists specifications for the sample draw combustible gas detector. Table 1: Specifications Target Gas Input Power Combustible

More information

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES USER INSTRUCTIONS FOR THE CHEMGARD INFRARED GAS MONITOR SERIES To completely customize the specification to your exact application, modification to the

More information

FX-SMT Series INSTRUCTION MANUAL P/N THERMO ELECTRON CORPORATION ENVIRONMENTAL INSTRUMENTS 27 FORGE PARKWAY FRANKLIN MASSACHUSETTS 02038

FX-SMT Series INSTRUCTION MANUAL P/N THERMO ELECTRON CORPORATION ENVIRONMENTAL INSTRUMENTS 27 FORGE PARKWAY FRANKLIN MASSACHUSETTS 02038 FX-SMT Series INSTRUCTION MANUAL P/N 71-0085 THERMO ELECTRON CORPORATION ENVIRONMENTAL INSTRUMENTS 27 FORGE PARKWAY FRANKLIN MASSACHUSETTS 02038 (866) 282-0430 Toll Free (508) 520-0430 International (508)

More information

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head 4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head NET DRAFT version 2.1-2008 Pag. 1 4-20mA Cyber - DRAFT version 2.1-2008 Pag.

More information

RK-04 M2 Transmitter Operator s Manual

RK-04 M2 Transmitter Operator s Manual 65-2610RK-04 M2 Transmitter Operator s Manual Part Number: 71-0294RK Revision: 0 Released: 12/27/13 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR SAFETY MANUAL SIL 2 Certified Model FP-700 Combustible Hydrocarbon Gas Sensor Version 2.0 1 SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR This manual addresses the specific requirements and recommendations

More information

Pump-Down Controller MODEL 4052

Pump-Down Controller MODEL 4052 Pump-Down Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4052 Pump-Down

More information

Controllers. Instruction Manual WARNING

Controllers. Instruction Manual WARNING Controllers Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any piece of

More information

Pump-Up Controller MODEL 4062

Pump-Up Controller MODEL 4062 Pump-Up Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4062 Pump-Up

More information

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual Toxic and Explosive Smart Gas Monitor PN 151022/151023 Installation and User Manual Quest Controls, Inc. 208 9 th Street Dr. West Palmetto, FL 34221 www.questcontrols.com Phone: (941) 729-4799 Fax: (941)

More information

Inc Series Digital Gas Detector/Controller. Operation Manual

Inc Series Digital Gas Detector/Controller. Operation Manual 5 Series Digital Gas Detector/Controller Operation Manual TABLE OF CONTENTS 1. 2. 3. 4. 5. 6. 7. General Description 1.1 Applications 1.2 Features Model Selection Guide Characteristics Installation 4.1

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro A d e v i h c r D c o n e m u WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship

More information

Model TS4000. Intelligent Sensor for Toxic Gas Detection

Model TS4000. Intelligent Sensor for Toxic Gas Detection Model TS4000 Intelligent Sensor for Toxic Gas Detection The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

M2 Rig Monitor Operator s Manual

M2 Rig Monitor Operator s Manual M2 Rig Monitor Operator s Manual Part Number: 71-0234RK Revision: D Released: 9/30/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before operating instrument.

More information

SECTION 1 (Page 2) Introduction, standard accessories and mounting specifications.

SECTION 1 (Page 2) Introduction, standard accessories and mounting specifications. HGM300 / RDM800 Refrigerant Monitoring System Instruction 3015-4149 Installation & Operation Mini Manual Rev. 5 November 2004 SECTION 1 (Page 2) Introduction, standard accessories and mounting specifications.

More information

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE DSGH Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE Revision History Revision History Version of manual Description Date 1.0 Initial release 051025 1.1

More information

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual 65-2434RK Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0061RK Edition: First, Revision C Released: December 2001 65-2434RK CO Transmitter 1 Product Warranty RKI Instruments, Inc., warranties

More information

Instruction Manual WARNING

Instruction Manual WARNING Controllers Instruction Manual WARNING THIS MANAUL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any piece of

More information

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR 1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR IMPORTANT: Please read these installation and operating instructions completely and carefully before

More information

RK-05 Carbon Monoxide Detector Operator s Manual

RK-05 Carbon Monoxide Detector Operator s Manual 65-2433RK-05 Carbon Monoxide Detector Operator s Manual Part Number: 71-0189RK Revision: 0 Released: 5/17/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

Danfoss gas detection unit Type GD Heavy Duty

Danfoss gas detection unit Type GD Heavy Duty Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx

More information

ADDENDUM. xwatch Explosion-Proof Camera with X-Series Flame Detectors DESCRIPTION GENERAL APPLICATION INFORMATION

ADDENDUM. xwatch Explosion-Proof Camera with X-Series Flame Detectors DESCRIPTION GENERAL APPLICATION INFORMATION ADDENDUM xwatch Explosion-Proof Camera with X-Series Flame Detectors DESCRIPTION The xwatch Explosion-Proof Camera is available as a factory installed option with any of the Det Tronics X Series line of

More information

INSTRUCTION MANUAL MODEL C2 PROTECTOR FOUR CHANNEL CONTROLLER. (Revision 2.2; Beginning Firmware 1.13)

INSTRUCTION MANUAL MODEL C2 PROTECTOR FOUR CHANNEL CONTROLLER. (Revision 2.2; Beginning Firmware 1.13) C2 QUAD PROTECTOR Channel Controller Users Manual INSTRUCTION MANUAL MODEL C2 PROTECTOR FOUR CHANNEL CONTROLLER (; Beginning Firmware 1.13) Warning: Read & understand contents of this manual prior to operation.

More information

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

Air Check O 2 Sample Draw Monitor

Air Check O 2 Sample Draw Monitor Air Check O 2 Sample Draw Monitor Instruction Manual PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 pureairemonitoring.com

More information

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications SAFETY MANUAL Intelligent Sensors for H 2 S Gas Applications The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

Model IR4000M. Multi-Point Monitor. Instruction Manual 12-10

Model IR4000M. Multi-Point Monitor. Instruction Manual 12-10 Multi-Point Monitor The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors.

More information

Industrial Grade Gas Detection Detecting The Difference

Industrial Grade Gas Detection Detecting The Difference detcon inc. Industrial Grade Gas Detection Detecting The Difference PO Box 8067 The Woodlands, TX 77387 888-367-4286 (toll free) 713-559-9200 281-292-2860 (fax) sales@detcon.com Catalog #CB-0409 www.detcon.com

More information

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ] ULTIMA XL/XT Series Gas Monitors [ Ultimate Features Extreme Design ] Cost effective fixed installation gas monitors with HART Field Communications Protocol. Single-sensor units use catalytic, electrochemical

More information

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6 Digital Gas Transmitters with Auxiliary s & Control Specifications subject to change without notice. USA 181011 Page 1 of 5 DESCRIPTION Digital RS-485 communicating, addressable toxic and combustible gas

More information

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM User Instructions For The Model 5200 Gas Monitor System To completely customize the specifications to your exact application, modifications to the following

More information

Air Check Ex O 2 Deficiency Monitor

Air Check Ex O 2 Deficiency Monitor Air Check Ex O 2 Deficiency Monitor Instruction Manual Part number 99020 PureAire Monitoring Systems, Inc. 1140 Ensell Road Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free:

More information

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System SAFETY MANUAL Open Path Hydrocarbon Gas Monitoring System The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11 Table of Contents 1. OVERVIEW... 3 2. SYSTEM LAYOUT... 4 3. SPECIFICATIONS... 8 3.1 SYSTEM COMPONENTS...9 3.2 PLC INPUTS AND OUTPUTS...9 3.3 FUNCTION KEYS...10 3.4 DEFAULT SET POINTS AND TIMERS...10 4.

More information

Universal Gas Transmitter

Universal Gas Transmitter er Universal Gas Transmitter User Manual Document No. 360-0087-02 (Revision R0) P Sensidyne, LP 1000 112th Circle N, Suite 100 St. Petersburg, Florida 33716 USA 800-451-9444 +1 727-530-3602 +1 727-539-0550

More information

HALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL

HALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL HALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL S E R I A L N O. M O D E L N O. T e m p. R a n g e 1 - = > 6 0 o F 2 - = 4 0-6 0 o F 3 - = < 4 0 o F - G a s T y p e 1 - R -1 1 2

More information

DIGITAL METERS Large Display Temperature Meters Instruction Manual

DIGITAL METERS Large Display Temperature Meters Instruction Manual DIGITAL METERS Large Display Temperature Meters PD755 PD756 PD757 Handles Thermocouple & RTD Inputs with Simplicity J, K, T, E, R, & S Thermocouples 100 Ω Platinum RTD (0.00385 or 0.00392 curve) Large

More information

Warranty Registration

Warranty Registration WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship and materials for a period

More information

GAS PLUS ALARM SYSTEM

GAS PLUS ALARM SYSTEM GAS PLUS -IR SERIES 4688-IR COMBUSTIBLE GAS OR CARBON DIOXIDE TRANSMITTER GAS PLUS -IR TRANSMITTER SERIES 4688-IR COMBUSTIBLE GAS OR CARBON DIOXIDE TRANSMITTER The Scott Gas Plus -IR Model 4688 IR Gas

More information

Model TS4000H. Intelligent Sensor for Toxic Gas Detection

Model TS4000H. Intelligent Sensor for Toxic Gas Detection Model TS4000H Intelligent Sensor for Toxic Gas Detection The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

Models TX-KE and TX-KP Toxic Gas Transmitters

Models TX-KE and TX-KP Toxic Gas Transmitters Models TX-KE and TX-KP Toxic Gas Transmitters Instruction Manual PureAire Monitoring Systems, Inc. 557 Capital Dr. Lake Zurich, IL. 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 www.pureairemonitoring.com

More information

RK Multi Point Detector Operator s Manual

RK Multi Point Detector Operator s Manual 65-2480RK Multi Point Detector Operator s Manual Part Number: 71-0198RK Revision: C Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor

Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor INSTRUCTIONS Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor APPLICATION The Det-Tronics Nanotechnology Metal Oxide Semiconductor (NTMOS) Hydrogen Sulfide (H 2 S) stand-alone gas sensor

More information

Model SM100. Aspirated Sampling Module

Model SM100. Aspirated Sampling Module Aspirated Sampling Module The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General

More information

Model 1000 H 2 S E-Chem/ CO 2 Process Analyzer

Model 1000 H 2 S E-Chem/ CO 2 Process Analyzer 24VDC OUT 2.1A 18-36 VDC IN Model 1000 H 2 S E-Chem/ CO 2 Process Analyzer + + SAMPLE FLOW AIR FLOW SAMPLE FLOW Operator s Installation and Instruction Manual Detcon Model 1000 H 2 S/CO 2 Analyzer consists

More information

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control. Détecteur de gaz OLCT80 Detectors-Transmitters for Flammable, Toxic Gases and Oxygen Non-intrusive operation via intrinsically safe infrared remote control Disponible en version déportée, ADF ou de SI

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors Dräger Polytron 5700 Fixed Gas Detector Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors Dräger Polytron 5700 Including e-box for increased safety wiring The Dräger

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TPC VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIADI&O062705 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 7,8

More information

RK-02 Multi Point Detector Operator s Manual

RK-02 Multi Point Detector Operator s Manual 65-2485RK-02 Multi Point Detector Operator s Manual Part Number: 71-0237RK Revision: A Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

INSTRUCTION MANUAL Detcon Model DM-700

INSTRUCTION MANUAL Detcon Model DM-700 INSTRUCTION MANUAL Detcon DM-700 Toxic Gas Sensors DM-700 O 2 Deficiency Sensors This manual covers all ranges of electrochemical and O 2 deficiency sensors offered in the Detcon Product Line DETCON, Inc.

More information

RAM3 Remote Alarm Module

RAM3 Remote Alarm Module RAM3 Remote Alarm Module INSTRUCTIONS Installation and Operation of the AMC-RAM3 with AMC Monitors IMPORTANT: Please read this installation and operating instructions completely and carefully before starting.

More information

RKA-03 Sample-Draw Detector Head

RKA-03 Sample-Draw Detector Head 35-3010RKA-03 Sample-Draw Detector Head Part Number: 71-0134RK Revision: E Released: 6/5/17 rkiinstruments.com WARNING Read and understand this instruction manual before operating detector. Improper use

More information

SenSmart Universal Gas Detector Series

SenSmart Universal Gas Detector Series SenSmart Universal Gas Detector Series Installation Guide Flammable & Toxic Gas Detectors Smart Alarm Controllers Fire & Gas System Engineering Technical Service & Support Warning: Read & understand contents

More information

ChemScan mini Analyzer for Low Ammonia Monitoring Installation, Operation and Maintenance Manual

ChemScan mini Analyzer for Low Ammonia Monitoring Installation, Operation and Maintenance Manual ChemScan mini Analyzer for Low Ammonia Monitoring Installation, Operation and Maintenance Manual asaanalytics.com ChemScan mini Low Ammonia Analyzer O&M Manual - Rev 223K TABLE OF CONTENTS ANALYZER DESCRIPTION

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

D12-17 % LEL Gas Transmiter

D12-17 % LEL Gas Transmiter O & M Manual D12-17 % LEL Gas Transmiter Home Office European Office Analytical Technology, Inc. ATI (UK) Limited 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park Collegeville, PA 19426 Delph New

More information

RK Hydrogen Sulfide Transmitter Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual 65-2331RK Hydrogen Sulfide Transmitter Operator s Manual Part Number: 71-0176RK Revision: B Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

Fixed Gas Detector User Manual Installation Operation Configuration Troubleshooting

Fixed Gas Detector User Manual Installation Operation Configuration Troubleshooting Fixed Gas Detector User Manual Installation Operation Configuration Troubleshooting March 28, 2016 Version 1 Product Leadership Training Service Reliability WARRANTY POLICY Bacharach, Inc. warrants this

More information

FLT93 Installation, Operation and Troubleshooting Guide

FLT93 Installation, Operation and Troubleshooting Guide FLT93 Installation, Operation and Troubleshooting Guide Pre-Installation A. To get the best results from the instrument, the instrument should be mounted 20 pipe diameters downstream from any valve, pipe

More information

Combustible Gas/Hydrogen Sulfide Sample-Draw Detector Operator s Manual

Combustible Gas/Hydrogen Sulfide Sample-Draw Detector Operator s Manual 35-3001-07 Combustible Gas/Hydrogen Sulfide Sample-Draw Detector Operator s Manual Part Number: 71-0411 Revision: 0 Released: 8/7/17 www.rkiinstruments.com WARNING Read and understand this instruction

More information

Model FMD. Field Mounted Display Module

Model FMD. Field Mounted Display Module Field Mounted Display Module The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General

More information

Combustible Gas Sample-Draw Detector Operator s Manual

Combustible Gas Sample-Draw Detector Operator s Manual 35-3001-01 Combustible Gas Sample-Draw Detector Operator s Manual Part Number: 71-0282RK Revision: A Released: 8/3/17 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

RKA-06 Sample-Draw Detector

RKA-06 Sample-Draw Detector 35-3010RKA-06 Sample-Draw Detector Part Number: 71-0207RK Revision: E Released: 6/5/17 rkiinstruments.com WARNING Read and understand this instruction manual before operating detector. Improper use of

More information

Safe Operation Manual. Honeywell IQ Force Gas Detector

Safe Operation Manual. Honeywell IQ Force Gas Detector Safe Operation Manual Honeywell IQ Force Gas Detector Honeywell Analytics 800-663-4164 403-248-9226 Fax 403-575-3708 03JUN2012 P/N 50105843-047 Version 01 http://www.honeywell.com HONEYWELL IQ Force PERSONAL

More information

Module Features are-configurable, no module jumpers to set

Module Features are-configurable, no module jumpers to set December 2011 PACSystems* RX3i Isolated Thermocouple Input Module, 6 Channels, IC695ALG306 Isolated Thermocouple Input Module, 12 Channels, IC695ALG312 Isolated Thermocouple Input module IC695ALG306 provides

More information

Air Check O 2 Deficiency Monitor

Air Check O 2 Deficiency Monitor Air Check O 2 Deficiency Monitor Instruction Manual PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 pureairemonitoring.com

More information

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08 GasScanner 8C Eight Channel Monitor Operator s Manual MINT-0281-XX Rev. A 01/29/08 Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials,

More information

Universal Gas Monitoring System

Universal Gas Monitoring System Universal Gas Monitoring System Document No. 360-0126-01 (Revision F) Sensidyne, LP 1000 112 TH Circle N, Suite 100 St. Petersburg, Florida 33716 USA 800-451-9444 +1 727-530-3602 +1 727-539-0550 [fax]

More information

QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR

QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR QAS-10000 SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR INSTALLATION, OPERATION AND MAINTENANCE MANUAL QUATROSENSE ENVIRONMENTAL LTD. 5935 OTTAWA STREET, PO BOX 749, RICHMOND, ONTARIO, CANADA. K0A

More information

IGD.CO.UK

IGD.CO.UK APPLICATION DATA SHEET S p e c i f i c a t i o n 2 SO22 WWW.-..UK Control Systems Transmitters Sensors Accessories TOCSIN 700+ D e t e c t o r Website: C o n t r o l P a n e l - Wall mounting or 19 Rack

More information

Improve Performance and Reduce Maintenance Costs. Model Q45D. Dissolved Oxygen Monitor...

Improve Performance and Reduce Maintenance Costs. Model Q45D. Dissolved Oxygen Monitor... Improve Performance and Reduce Maintenance Costs Model Q45D Dissolved Oxygen Monitor... Why Throw Away Money? Why Throw Away Money? ATI s Model Q45D Dissolved Oxygen monitor is designed to provide reliable

More information