SAF-BCF SECOND REVISIONS WITH STATEMENTS

Size: px
Start display at page:

Download "SAF-BCF SECOND REVISIONS WITH STATEMENTS"

Transcription

1 Page 196 of ] Second Revision No. 153-NFPA [ New Section after Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level of exit discharge, including determination of stories in height as addressed in 4.6.3, the level of exit discharge shall be permitted to be the combination of floor levels as addressed in , , or One floor level located not more than three stair risers above the level of exit discharge shall be permitted to be considered part of the level of exit discharge One floor level located not more than three stair risers below the level of exit discharge shall be permitted to be considered part of the level of exit discharge Where one floor level is located above the level of exit discharge, another floor level is located below the level of exit discharge, and not more than a total of three stair risers separate the upper level from the lower level, the two floor levels shall be permitted to be considered part of the level of exit discharge The provisions of , , and shall not be used in combination with each other. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 15:01:28 EDT 2013 Statement The Life Safety code currently does not provide guidance in occupancies having multiple levels separated by a relatively short run of stairs (3, 4, 5, 6, etc). Short runs of stairs are most frequently found in multi-level homes (bilevel, tri-level, split-level, etc) and are often present in day-care homes, daycare centers, small residential board and care, educational, business and of course one- and two-family dwellings. This concept could theoretically be used for any occupancy to address requirements for short runs of stairs that would prohibitively require separation or enclosure. The committee revised the 8 riser threshold down to 3 risers to avoid the potential for a chimney effect and to avoid additional floors from being added to the level of exit discharge. Page 1 of 28

2 Page 197 of 331 Public Comment No. 48-NFPA [New Section after ] Page 2 of 28

3 Page 198 of 331 Second Revision No. 176-NFPA [ Section No [Excluding any Sub-Sections] ] No door in any means of escape, other than those meeting the requirement of or, , or shall be locked against egress when the building is occupied. Organization: National Fire Protection Assoc Submittal Date: Mon Jul 01 14:14:14 EDT 2013 Statement The proposed revisions is needed for correlation with the proposed new (SR-169). Page 3 of 28

4 Page 199 of 330 8/27/2013 Second Revision No. 169-NFPA [ New Section after ] Door-locking arrangements shall be permitted where the clinical needs of residents require specialized security measures or where residents pose a security threat, provided all of the following conditions are met: (1) Staff can readily unlock doors at all times in accordance with (2) The building is protected by an approved automatic sprinkler system in accordance with (3) The provision of for conversions is not be permitted to be used Doors located in the means of egress and permitted to be locked in accordance with shall comply with all of the following: (1) Provisions shall be made for the rapid removal of occupants by means of one of the following: (a) (b) (c) Remote control of locks from within the locked building Keying of all locks to keys carried by staff at all times Other such reliable means available to staff at all times (2) Only one locking device shall be permitted on each door. Organization: National Fire Protection Assoc Submittal Date: Mon Jul 01 12:34:44 EDT 2013 Statement Persons with Alzheimer's and dementia-related diseases often live in board and care facilities. Such individuals may be prone to wandering and are at considerable risk if they exit the building. Allowing locking against the means of egress is necessary for the safety of the facility residents, as is already recognized in NFPA 101 Chapter 18 for hospitals and nursing homes. This language is intended to balance the need for locking to protect the resident and the need to exit in an emergency by limiting when such locking devices are allowed and ensuring they release automatically and immediately in an emergency. Page 4 of 28

5 Page 200 of 330 Public Comment No. 85-NFPA [New Section after ] Page 5 of 28 8/27/2013

6 Page 201 of 331 Second Revision No. 156-NFPA [ Section No ] Alcohol-based hand-rub dispensers in accordance with shall be permitted. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 15:52:50 EDT 2013 Statement Provision relocated to in response to correlating committee note on FR304. Page 6 of 28

7 Page 202 of 331 Second Revision No. 157-NFPA [ Section No ] Reserved Alcohol-Based Hand-Rub Dispensers. Alcohol-based hand-rub dispensers in accordance with shall be permitted. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 15:53:49 EDT 2013 Statement Provision relocated from in response to correlating committee note on FR304. Page 7 of 28

8 Page 203 of 331 Second Revision No. 179-NFPA [ Section No ] Doors. Doors in means of egress shall meet all of the following criteria: (1) Doors complying with shall be permitted. (2) Doors within individual rooms and suites of rooms shall be permitted to be swinging or sliding. (3) No door, other than those meeting the requirement of (4) or, (5), or (6), shall be equipped with a lock or latch that requires the use of a tool or key from the egress side. (4) Delayed-egress locks in accordance with shall be permitted. (5) Access-controlled egress door assemblies in accordance with shall be permitted. (6) Door-locking arrangements shall be permitted where the clinical needs of residents require specialized security measures or where residents pose a security threat, provided both of the following conditions are met: (a) Staff can readily unlock doors at all times in accordance with (7) ) (b) The building is protected by an approved automatic sprinkler system in accordance with (7) Doors located in the means of egress that are permitted to be locked under other provisions of Chapter 32, other than those meeting the requirement of (4) or (5), shall have adequate provisions made for the rapid removal of occupants by means such as remote control of locks, keying of all locks to keys carried by staff at all times, or other such reliable means available to staff at all times. (8) Only one such locking device, as described in (7)(6), shall be permitted on each door. Organization: National Fire Protection Assoc Submittal Date: Mon Jul 01 14:20:00 EDT 2013 Statement Page 8 of 28

9 Page 204 of 330 8/27/2013 Persons with Alzheimer's and dementia-related diseases often live in board and care facilities. Such individuals may be prone to wandering and are at considerable risk if they exit the building. Allowing locking against the means of egress is necessary for the safety of the facility residents, as is already recognized in NFPA 101 Chapter 18 for hospitals and nursing homes. This language is intended to balance the need for locking to protect the resident and the need to exit in an emergency by limiting when such locking devices are allowed and ensuring they release automatically and immediately in an emergency. Public Comment No. 86-NFPA [Section No ] Page 9 of 28

10 Page 205 of 331 Second Revision No. 158-NFPA [ Section No ] Alcohol-based hand-rub dispensers in accordance with shall be permitted. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 15:55:08 EDT 2013 Statement Provision relocated to in response to correlating committee note on FR305. Page 10 of 28

11 Page 206 of 331 Second Revision No. 194-NFPA [ Section No ] * Within a smoke compartment, where residential or commercial cooking equipment is used to prepare meals for 30 or fewer persons, one cooking facility shall be permitted to be open to the corridor, provided that Compliance with shall not be required where all of the following conditions are met: (1) Residential or commercial cooking equipment in a single kitchen per smoke compartment is used to prepare meals for 30 or fewer persons. (2) The portion of the board and care facility served by the cooking facility is limited to 30 beds and is separated from other portions of the board and care facility by a smoke barrier constructed in accordance with and with through (3) The cooktop or range is equipped with a range hood of a width at least equal to the width of the cooking surface, with grease baffles or other greasecollecting and clean-out capability. (4)* The hood systems have a minimum airflow of 500 cfm (14,000 L/min). (5) The hood systems that are not ducted to the exterior additionally have a charcoal filter to remove smoke and odor. (6) The cooktop or range complies with all of the following: (a) (b) (c) The cooktop or range is protected with a fire suppression system listed in accordance with ANSI/ UL 300, Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, or is tested and meets all requirements of UL 300A, Extinguishing System Units for Residential Range Top Cooking Surfaces, in accordance with the applicable testing document's scope. A manual release of the extinguishing system is provided in accordance with Section 10.5 of NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. An interlock is provided to turn off all sources of fuel and electrical power to the cooktop or range when the suppression system is activated. (7)* The use of solid fuel for cooking is prohibited. (8)* Deep-fat frying is prohibited. (9) Portable fire extinguishers in accordance with NFPA 96 are located in all kitchen areas. (10) * A switch meeting all of the following is provided: (a) (b) (c) A locked switch, or a switch located in a restricted location, is provided within the cooking facility that deactivates the cooktop or range. The switch is used to deactivate the cooktop or range whenever the kitchen is not under staff supervision. The switch is on a timer, not exceeding a 120-minute capacity, that automatically deactivates the cooktop or range, independent of staff action. Page 11 of 28

12 Page 207 of 331 (11) Procedures for the use, inspection, testing, and maintenance of the cooking equipment are in accordance with Chapter 11 of NFPA 96, and the manufacturer s instructions are followed. (12) * Not less fewer than two ac-powered photoelectric smoke alarms, interconnected in accordance with and equipped with a silence feature, and in accordance with NFPA 72, National Fire Alarm and Signaling Code, are located not closer than 20 ft (6.1 m) and not farther than 25 ft (7.6 m) from the cooktop or range. (13) No smoke detector is located less than The smoke alarms required by (12) are permitted to be located outside the kitchen area where such placement is necessary for compliance with the 20 ft (6.1 m) from the cooktop or range minimum distance criterion. (14) A single system smoke detector is permitted to be installed in lieu of the smoke alarms required in (12), provided the following criteria are met: (a) (b) (c) (d) (e) (f) The detector is located not closer than 20 ft (6.1 m) and not farther than 25 ft (7.6 m) from the cooktop or range. The detector is permitted to initiate a local audible alarm signal only. The detector is not required to initiate a buildingwide occupant notification signal. The detector is not required to notify emergency forces. The local audible signal initiated by the detector is permitted to be silenced and reset by a button on the detector or by a switch installed within 10 ft (3.0 m) of the system smoke detector. System smoke detectors that are required to be installed in corridors or spaces open to the corridor other sections of this chapter are not used to meet the requirements of (12) and are located not closer than 25 ft (7.6 m) to the cooktop or range. Organization: National Fire Protection Assoc Submittal Date: Mon Jul 01 15:18:36 EDT 2013 Statement The proposed revision exempts cooking equipment from the protection requirements of where the specified criteria are met, consistent with requirements of Chs. 18 and 19 for cooking facilities open to corridors. It is noted that Ch. 32 already permits cooking facilities to be open to corridors (see related annex text). The added language was incorporated in Chapters 18/19 by a TIA. This section should match the language in Chapters 18/19 for the sake of consistency. Page 12 of 28

13 Page 208 of 331 Public Comment No. 113-NFPA [Section No ] Page 13 of 28

14 Page 209 of 331 Second Revision No. 159-NFPA [ Section No ] Reserved. Alcohol-Based Hand-Rub Dispensers. Alcohol-based hand-rub dispensers in accordance with shall be permitted. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 15:56:10 EDT 2013 Statement Provision relocated from in response to correlating committee note on FR305. Page 14 of 28

15 Page 210 of 331 Second Revision No. 155-NFPA [ New Section after ] Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level of exit discharge, including determination of stories in height as addressed in 4.6.3, the level of exit discharge shall be permitted to be the combination of floor levels as addressed in , , or One floor level located not more than three stair risers above the level of exit discharge shall be permitted to be considered part of the level of exit discharge One floor level located not more than three stair risers below the level of exit discharge shall be permitted to be considered part of the level of exit discharge Where one floor level is located above the level of exit discharge, another floor level is located below the level of exit discharge, and not more than a total of three stair risers separate the upper level from the lower level, the two floor levels shall be permitted to be considered part of the level of exit discharge The provisions of , , and shall not be used in combination with each other. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 15:30:06 EDT 2013 Statement The Life Safety code currently does not provide guidance in occupancies having multiple levels separated by a relatively short run of stairs (3, 4, 5, 6, etc). Short runs of stairs are most frequently found in multi-level homes (bilevel, tri-level, split-level, etc) and are often present in day-care homes, daycare centers, small residential board and care, educational, business and of course one- and two-family dwellings. This concept could theoretically be used for any occupancy to address requirements for short runs of stairs that would prohibitively require separation or enclosure. The committee revised the 8 riser threshold down to 3 risers to avoid the potential for a chimney effect and to avoid additional floors from being added to the level of exit discharge. Page 15 of 28

16 Page 211 of 331 Public Comment No. 49-NFPA [New Section after ] Page 16 of 28

17 Page 212 of 331 Second Revision No. 192-NFPA [ Section No [Excluding any Sub-Sections] ] No door in any means of escape, other than those meeting the requirement of or, , or , shall be locked against egress when the building is occupied. Organization: National Fire Protection Assoc Submittal Date: Mon Jul 01 14:49:39 EDT 2013 Statement The revision is needed to correlate with the new (SR- 186). Page 17 of 28

18 Page 213 of 330 8/27/2013 Second Revision No. 186-NFPA [ New Section after ] Door-locking arrangements shall be permitted where the clinical needs of residents require specialized security measures or where residents pose a security threat, provided all of the following conditions are met: (1) Staff can readily unlock doors at all times in accordance with (2) The building is protected by an approved automatic sprinkler system in accordance with Doors that are located in the means of egress and are permitted to be locked in accordance with shall comply with all of the following: (1) Provisions shall be made for the rapid removal of occupants by means of one of the following: (a) (b) (c) Remote control of locks from within the locked building Keying of all locks to keys carried by staff at all times Other such reliable means available to staff at all times (2) Only one locking device shall be permitted on each door. Organization: National Fire Protection Assoc Submittal Date: Mon Jul 01 14:38:40 EDT 2013 Statement Persons with Alzheimer's and dementia-related diseases often live in board and care facilities. Such individuals may be prone to wandering and are at considerable risk if they exit the building. Allowing locking against the means of egress is necessary for the safety of the facility residents, as is already recognized in NFPA 101 Chapter 18 for hospitals and nursing homes. This language is intended to balance the need for locking to protect the resident and the need to exit in an emergency by limiting when such locking devices are allowed and ensuring they release automatically and immediately in an emergency. Public Comment No. 87-NFPA [New Section after ] Page 18 of 28

19 Page 215 of 331 Second Revision No. 160-NFPA [ Section No ] Alcohol-based hand-rub dispensers in accordance with shall be permitted. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 15:58:14 EDT 2013 Statement Provision relocated to in response to correlating committee note on FR306. Page 19 of 28

20 Page 216 of 331 Second Revision No. 161-NFPA [ Section No ] Reserved. Alcohol-Based Hand-Rub Dispensers. Alcohol-based hand-rub dispensers in accordance with shall be permitted. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 16:01:19 EDT 2013 Statement Provision relocated from in response to correlating committee note on FR306. Page 20 of 28

21 Page 217 of 331 Second Revision No. 193-NFPA [ Section No ] Doors. Doors in means of egress shall be as follows: (1) Doors complying with shall be permitted. (2) Doors within individual rooms and suites of rooms shall be permitted to be swinging or sliding. (3) No door in any means of egress, other than those meeting the requirement of (4) or, (5), or (6), shall be locked against egress when the building is occupied. (4) Delayed-egress locks in accordance with shall be permitted. (5) Access-controlled egress door assemblies in accordance with shall be permitted. (6) Door-locking arrangements shall be permitted where the clinical needs of residents require specialized security measures or where residents pose a security threat, provided both of the following conditions are met: (a) Staff can readily unlock doors at all times in accordance with (7). (b) The building is protected by an approved automatic sprinkler system in accordance with (7) Doors located in the means of egress that are permitted to be locked under other provisions of Chapter 33, other than those meeting the requirement of (4) or (5), shall have adequate provisions made for the rapid removal of occupants by means such as remote control of locks, keying of all locks to keys carried by staff at all times, or other such reliable means available to staff at all times. (8) Only one such locking device, as described in (7), shall be permitted on each door. (9) Revolving doors complying with shall be permitted. Organization: National Fire Protection Assoc Submittal Date: Mon Jul 01 14:58:19 EDT 2013 Statement Page 21 of 28

22 Page 218 of 331 Persons with Alzheimer's and dementia-related diseases often live in board and care facilities. Such individuals may be prone to wandering and are at considerable risk if they exit the building. Allowing locking against the means of egress is necessary for the safety of the facility residents, as is already recognized in NFPA 101 Chapter 18 for hospitals and nursing homes. This language is intended to balance the need for locking to protect the resident and the need to exit in an emergency by limiting when such locking devices are allowed and ensuring they release automatically and immediately in an emergency. Public Comment No. 88-NFPA [Section No ] Page 22 of 28

23 Page 219 of 331 Second Revision No. 162-NFPA [ Section No ] Alcohol-based hand-rub dispensers in accordance with shall be permitted. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 16:02:29 EDT 2013 Statement Provision relocated to in response to correlating committee note on FR307. Page 23 of 28

24 Page 220 of 331 Second Revision No. 195-NFPA [ Section No ] * Within a smoke compartment, where residential or commercial cooking equipment is used to prepare meals for 30 or fewer persons, one cooking facility shall be permitted to be open to the corridor, provided that Compliance with shall not be required where all of the following conditions are met: (1) Residential or commercial cooking equipment in a single kitchen per smoke compartment is used to prepare meals for 30 or fewer persons. (2) The portion of the board and care facility served by the cooking facility is limited to 30 beds and is separated from other portions of the board and care facility by a smoke barrier constructed in accordance with and with through (3) The cooktop or range is equipped with a range hood of a width at least equal to the width of the cooking surface, with grease baffles or other greasecollecting and clean-out capability. (4)* The hood systems have a minimum airflow of 500 cfm (14,000 L/min). (5) The hood systems that are not ducted to the exterior additionally have a charcoal filter to remove smoke and odor. (6) The cooktop or range complies with all of the following: (a) (b) (c) The cooktop or range is protected with a fire suppression system listed in accordance with ANSI/UL 300, Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, or is tested and meets all requirements of UL 300A, Extinguishing System Units for Residential Range Top Cooking Surfaces, in accordance with the applicable testing document's scope. A manual release of the extinguishing system is provided in accordance with Section 10.5 of NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. An interlock is provided to turn off all sources of fuel and electrical power to the cooktop or range when the suppression system is activated. (7)* The use of solid fuel for cooking is prohibited. (8)* Deep-fat frying is prohibited. (9) Portable fire extinguishers in accordance with NFPA 96 are located in all kitchen areas. (10) * A switch meeting all of the following is provided: (a) (b) (c) A locked switch, or a switch located in a restricted location, is provided within the cooking facility that deactivates the cooktop or range. The switch is used to deactivate the cooktop or range whenever the kitchen is not under staff supervision. The switch is on a timer, not exceeding a 120-minute capacity, that automatically deactivates the cooktop or range, independent of staff action. Page 24 of 28

25 Page 221 of 331 (11) Procedures for the use, inspection, testing, and maintenance of the cooking equipment are in accordance with Chapter 11 of NFPA 96, and the manufacturer s instructions are followed. (12) * Not less No fewer than two AC ac -powered photoelectric smoke alarms, interconnected in accordance with , and equipped with a silence feature, and in accordance with NFPA 72, National Fire Alarm and Signaling Code, are located not closer than 20 ft (6.1 m) and not farther than 25 ft (7.6 m) from the cooktop or range. (13) No smoke detector is located less than The smoke alarms required by (12) are permitted to be located outside the kitchen area where such placement is necessary for compliance with the 20 ft (6.1 m) from the cooktop or range minimum distance criterion. (14) The smoke compartment is protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. A single system smoke detector is permitted to be installed in lieu of the smoke alarms required in (12), provided the following criteria are met: (a) (b) (c) (d) (e) (f) The detector is located not closer than 20 ft (6.1 m) and not farther than 25 ft (7.6 m) from the cooktop or range. The detector is permitted to initiate a local audible alarm signal only. The detector is not required to initiate a buildingwide occupant notification signal. The detector is not required to notify emergency forces. The local audible signal initiated by the detector is permitted to be silenced and reset by a button on the detector or by a switch installed within 10 ft (3.0 m) of the system smoke detector. System smoke detectors that are required to be installed in corridors or spaces open to the corridor other sections of this chapter are not used to meet the requirements of (12) and are located not closer than 25 ft (7.6 m) to the cooktop or range. Organization: National Fire Protection Assoc Submittal Date: Mon Jul 01 15:40:08 EDT 2013 Statement Page 25 of 28

26 Page 222 of 331 The proposed revision exempts cooking equipment from the protection requirements of where the specified criteria are met, consistent with requirements of Chs. 18 and 19 for cooking facilities open to corridors. It is noted that Ch. 33 already permits cooking facilities to be open to corridors (see related annex text). The added language was incorporated in Chapters 18/19 by a TIA. This section should match the language in Chapters 18/19 for the sake of consistency. Public Comment No. 114-NFPA [Section No ] Page 26 of 28

27 Page 223 of 331 Second Revision No. 163-NFPA [ Section No ] Special Provisions. (Reserved) (Reserved) Alcohol-Based Hand-Rub Dispensers. Alcohol-based hand-rub dispensers in accordance with shall be permited. Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 16:03:44 EDT 2013 Statement Provision relocated from in response to correlating committee note on FR307. Page 27 of 28

28 Page 320 of 331 Second Revision No. 164-NFPA [ Section No. A ] A It is not the intent to prohibit furniture in corridors and spaces open to corridors, provided that the minimum required width is maintained. Storage is not permitted in corridors or spaces open to corridors. It is also not the intent to require corridors to be defined by a change in flooring texture, material, or color to separate it them from areas allowed to be open to corridors. Cooking facilities complying with are permitted to be open to corridors. Sleeping rooms are required to be separated from means of egress in accordance with Organization: National Fire Protection Assoc Submittal Date: Fri Jun 28 16:07:17 EDT 2013 Statement The revision clarifies the committee's intent with regard to separation of means of egress. Requiring cooking facility separation is a common misapplication of the code. Page 28 of 28

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions

More information

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA This report is provided for information only. BMHA is not asking for Adhoc Health Care to sponser as

More information

First Revision No NFPA [ Section No ]

First Revision No NFPA [ Section No ] of 45 10/21/2015 8:54 AM First Revision No. 3501-NFPA 101-2015 [ Section No. 3.3.190.1 ] 3.3.196.1* Ambulatory Health Care Occupancy. An occupancy used to provide services or treatment simultaneously to

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

E25 (D) Automatic controls for general means of egress lighting

E25 (D) Automatic controls for general means of egress lighting Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 47 10/21/2015 9:37 AM First Revision No. 5041-NFPA 101-2015 [ Global Input ] Throughout the document, change electrically controlled egress door assemblies to door hardware-release of electrically locked

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work. 3610 COMMERCE DR SUITE 817 BALTIMORE MD 21227 P 410.737.8677 F 410.737.8688 www.haifire.com May 5, 2014 Review of Regulations 42 CFR Parts 403, 416, 418, 460, 482, 483 and 485 Medicare and Medicaid Programs;

More information

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments

More information

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

BCAC Egress Work Group

BCAC Egress Work Group 2015 Group A Code Change Cycle Copyright 2014 International Code Council, Inc. BCAC item E-17.1 E?? 15 1006.2.1, 1006.3 1006.2.1 Egress based on occupant load and common path of egress travel distance.

More information

ICC Committee on Health Care Hospitals and Nursing Homes Group A Draft Proposals Revised Copyright 2017 International Code Council, Inc.

ICC Committee on Health Care Hospitals and Nursing Homes Group A Draft Proposals Revised Copyright 2017 International Code Council, Inc. ICC Committee on Health Care Hospitals and Nursing Homes Group A Draft Proposals Revised 11-16-2017 Copyright 2017 International Code Council, Inc. Work groups are: G/MOE - General/Means of egress Chair:

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM 2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211

More information

Defend In Place 2012 IFC Overview of Institutional Occupancies

Defend In Place 2012 IFC Overview of Institutional Occupancies Defend In Place 2012 IFC Overview of Institutional Occupancies ICC Course No. ICC CEU s = 0.50 SCFA Course 8506-15-0 Nathan Ellis Cell: 864-812-5183 Nathan.Ellis@llr.sc.gov Institutional Occupancies Course

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

Residential Care Facilities Requirements

Residential Care Facilities Requirements Development Services Department Building Division 311 Vernon Street Roseville, California 95678-2649 Residential Care Facilities Requirements SUBMITTAL REQUIREMENTS: Note: These requirements are in addition

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Page 1 of 5 1/29/2016 4:08 PM. First Correlating Revision No. 3-NFPA [ Section No ] Submitter Information Verification

Page 1 of 5 1/29/2016 4:08 PM. First Correlating Revision No. 3-NFPA [ Section No ] Submitter Information Verification First Correlating Revision No. 3-NFPA 101-2016 [ Section No. 6.1.8.1.1 ] 6.1.8.1.1* Definition One- and Two-Family Dwelling Unit. A building that contains not more than two dwelling units, with independent

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

Emergency Planning for Institutional Facilities

Emergency Planning for Institutional Facilities Emergency Planning for Institutional Facilities Pacific ADA Emergency Preparedness Webinars Presented by: Kimberly Paarlberg, ICC Based on the 2015 edition of the International Building Code (IBC) and

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

CHILD CARE CENTER INSPECTION CHECKLIST 06C

CHILD CARE CENTER INSPECTION CHECKLIST 06C CHILD CARE CENTER INSPECTION CHECKLIST 06C OCCUPANCY-SPECIFIC FIRE S November 2006: Kansas State Fire Marshal Page: 29 November 2006: Kansas State Fire Marshal Page: 30 CHILD CARE CENTERS & PRESCHOOLS

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

First Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM

First Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM 3 of 326 11/21/2013 1:03 PM First Revision No. 88-NFPA 72-2013 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 70, National Electrical Code, 2011 2014 edition. NFPA 96, Standard

More information

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control 11-27-12 This document is designed as a summary guide using IFC requirements for the provisions associated with exiting,

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February

More information

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 Several medical care definitions were created and revised in Chapter 2 of the 2012 IBC, as well as through the occupancy descriptions, and

More information

Large Family Daycare Guideline

Large Family Daycare Guideline Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose

More information

Chapter 2: Definitions

Chapter 2: Definitions FLORIDA BUILDING CODE Existing Buildings 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison JUMP TO CHAPTER (click chapter

More information

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting. Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/28/2015 10:41 AM First Revision No. 6036-NFPA 5000-2015 [ Global Input ] Throughout the document, change door electrically controlled egress door assemblies to hardware-release of electrically

More information

AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE

AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE This report includes 6 code change proposals from the Adhoc Health Care, Means of Egress committee

More information

FHCA 2014 Annual Conference & Trade Show

FHCA 2014 Annual Conference & Trade Show FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector

More information

AHC Meeting #7 July 12-13, Occupancy WG Report

AHC Meeting #7 July 12-13, Occupancy WG Report AHC Meeting #7 July 12-13, 2012 Part 1: CTC public comments on I-1/I-2 Condition designations..page 1 Part 2; AHC public comments on I-2 Condition designations Page 6 Part 3: Approved code change G244

More information

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 130 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other

More information

For additional information regarding R-3.1 residential care facilities please contact (951)

For additional information regarding R-3.1 residential care facilities please contact (951) Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K0100 - General Requirements - Other Title General Requirements - Other General Requirements - Other List in the REMARKS

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 98 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC surveyor's determination

More information

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary

More information

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document

More information

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA Adoption of 2012 Life Safety Code Health Care Facilities Code Kenneth Daily, LNHA kenn@qissurvey.com CMS Announcement May 2016 Life Safety Code Health Care Code Effective July 5 th Numerous changes many

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

AHC MEETING #4 PART I ROUND 1 ISSUES CODE CHANGES

AHC MEETING #4 PART I ROUND 1 ISSUES CODE CHANGES AHC MEETING #4 MOE WORK GROUP REPORT & NOTES FROM AHC # 4 (IBC Chapters 4, 10 & 11) This appendix is based on the AHC s review of the noted Work group Report at AHC Meeting # 4. Meeting # 4 of the AHC

More information

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES West Metro Fire Rescue Life Safety Division 433 South Allison Parkway Lakewood, Colorado 80226 (303) 989-4307 Fax (303)

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Guideline Title: Residentially Based Care Facilities Group

More information

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225. Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.1) House Name Date Address Inspector(s) No. of Residents

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common

More information