N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

Size: px
Start display at page:

Download "N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit"

Transcription

1 SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system FireFlex N 2 Blast description The FIREFLEX N2 Blast integrated system consists of an integrated SUREFIRE double interlock preaction automatic sprinkler system combined with a Nitrogen generating system, factory-assembled in a single cabinet. All the necessary components are integrated. The FIREFLEX N2 Blast is fully tested at factory. The FIREFLEX N2 Blast System uses the N2 Blast Nitrogen generator system Type 1 FPS-250 or FPS-750 system, made by South-Tek Systems. All the deluge valves are rated up to a maximum of 250 psi WWP (1724 kpa) max. and are available in the following diameters: 1½" (40 mm) 3" (80 mm) 6" (150 mm) 2" (50 mm) 4" (100 mm) Warning: 6" (150 mm) available with N2 Blast Type 1 FPS-750 only. Features Inhibits corrosion with 98%+ pure Nitrogen Trouble-free design for safe and easy application Available in 2 cabinet sizes Uses South-Tek N2 Blast Best value in nitrogen generation technology Limits the liability of early pipe replacement Uses the Viking deluge valve Trim is fully assembled and tested at the factory All trims are galvanized steel, Listed and Approved for 250 psi (17.2 bar) service maximum Quick connections to water supply and drain on left side, and sprinkler riser on top of unit, all available with grooved end or flanged fittings No open drain cup inside unit Separate unlocked access hatch to emergency manual release Compact, aesthetic and easy to move User-friendly standardized owner's manual with every unit Unique serial number on every unit Uses UL, ULC and/or FM Approved components Designed in accordance with NFPA Standards Sturdy 14 gauge steel cabinet painted fire red with oven baked polyester powder on phosphate base Textured rust proof finish Neoprene gasket on all doors to eliminate vibrations Manufactured under ISO-9001 quality control procedures Prewired to the Viking VFR-400 releasing control panel 1 of 16 FM-076D-0-125C

2 SUREFIRE double c/w N 2 Blast Nitrogen generating system System configurations SUREFIRE Double Interlock Preaction combined with N2 Blast Type 1 FPS-250 (250 gallons system) SUREFIRE Double Interlock Preaction combined with N2 Blast Type 1 FPS-750 (750 gallons system) Systems hydraulic limitations The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FireFlex Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations. Piping Equivalent Lengths w/o System size Usage Range shut off valve (in.) (gpm) Piping Equivalent Lengths c/w shut off valve (m.) (ft.) (m.) (ft.) GPM 1½ Sequence of operation Drain 250 PSIG w.p. SUREFIRE operation 1. The activation of the electric detection AND the opening of an automatic sprinkler is necessary to cause the deluge valve actuation. 2. The activation of the electric detection alone will not cause water to enter the system piping. 3. The opening of an automatic sprinkler OR damage to system piping without the detection condition satisfied will activate the "very low air" alarm pressure switch, The normally open solenoid valve (F2) will be activated but water will not enter the system piping. 4. Activation of the electric detection AND the "very low air" alarm pressure switch will activate will activate solenoid valves (F1) & (F2), causing the deluge valve to open and allowing water to enter the system piping. The alarm pressure switch (C1) will activate. Water will flow out of any open sprinklers and/or any openings on the system. 5. Operation of the emergency manual release will depressurize the priming chamber, causing the deluge valve to open and allowing water to enter the system piping and water will discharge through any open sprinklers.the alarm pressure switch (C1) will activate. 6. When AC Power and DC power supplied by the back up batteries is lost, the system shall fail-safe and function as a dry pipe system. The normally open solenoid will remain open, and the pneumatic actuator is the only device holding the priming water in the priming chamber. When a sprinkler operates, air pressure is lost and the pneumatic actuator opens. Priming water is drained from the priming chamber, causing the deluge valve to open and allowing water to enter the system piping. The alarm pressure switch will activate. Water will flow out of any open sprinklers and/or any openings on the system. 7. Trouble condition on detection zones, or "very low air" alarm zone, or the normally closed solenoid output disables the normally open solenoid and the pneumatic actuator is the only device holding the priming water in the priming chamber. When a sprinkler operates, air pressure is lost and the pneumatic actuator opens. Priming water is drained from the priming chamber, causing the deluge valve to open and allowing water to enter the system piping. The alarm pressure switch will activate. Water will flow out of any open sprinklers and/or any openings on the system. N2 Blast Nitrogen generator system operation 1. The initial air supply fill of the piping system within 30 minutes as per NFPA 13 is accomplished using the initial fill air compressor. This compressor is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the sprinkler system piping. It is factory-set at 20 and 35 psi for the cut-in and cut-out pressures respectively. There is a "low air" supervisory pressure switch which monitors system piping air/nitrogen pressure at all times. It is factory-set at 25 psi to provide a "low air" supervisory signal and 23 psi to provide a "very low air" supervisory signal. 2. The nitrogen generation/maintenance air compressor is supplied as an integral part of the STS N 2-Blast Nitrogen Generation System. It is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the nitrogen storage tank. It is factory-set at 65 psi and 75 psi for the cut-in and cut-out pressures respectively. The Viking D-2 Air Pressure Maintenance Device is installed and factory-adjusted to 35 psi (normal system air/nitrogen pressure) downstream of the nitrogen storage tank. As the system continually purges with Nitrogen, the APMD will continually draw from the Nitrogen storage tank to maintain supervisory pressure (35 psi). Should the N 2-Blast generator run for more than 6 hours consecutively, the Leak Detection System (LDS) will automatically shut it down and activate a trouble contact. 3. The air and nitrogen supply systems are fully integrated and fully automatic in the FireFlex - N 2-Blast. No shutoff or bypass valve is required. The nitrogen generator is equipped with a BlastOff Leak Detection System (LDS). Should the nitrogen generator compressor fail or a leak occur that can not be compensated by the nitrogen generating system, the preaction system air compressor will act as a back-up and start-up at 20 psi system pressure. FM-076D-0-125C 2 of 16

3 SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Standard equipments Releasing control panel 120 VAC / 60 Hz, 165VA. 12VDC / 12Ah batteries. (factory installed) 12VDC / 18Ah batteries. (optional) The releasing control panel integrated into the TOTALPAC 3 cabinet is Viking's Model VFR-400. This panel includes four Class B, programmable detection zones (optional Class A); two Class B supervisory zones and four Class B, programmable output circuits (optional Class A). It is also provided with menu driven programming, including a specific program assigned at the factory. The panel is compatible with many types of fire alarm & supervisory devices such as linear heat detectors, spottype heat and smoke detectors, water flow and release indicators, low and high air pressure switches, manual pull stations. The releasing control panel also includes an alphanumeric display with 2 lines of 16 characters describing all the system conditions, as well as a set of red and yellow LED lamps individually indicating each of the alarm and trouble conditions of the system Easy to operate control buttons are also provided to activate and operate the system's various functions. Releasing circuit disconnect switch The releasing circuit disconnect switch is used to disable the releasing solenoid. When the key is set to Disable, the releasing solenoid will be disconnected from the control panel s releasing circuit, causing a trouble signal and preventing accidental discharge during maintenance or inspection. Deluge valve The Viking Model F-1 Deluge Valve is a quick-opening, differential diaphragm flood valve with one moving mechanism. The deluge valve is used to control water flow in preaction sprinkler systems. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The deluge valve clapper opens to allow water to flow into the system Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this vale is to manually shutoff the preaction system. 3 of 16 FM-076D-0-125C

4 SUREFIRE double c/w N 2 Blast Nitrogen generating system Standard equipments (continued) Preaction riser check valve The Viking 1-½ and 2 spring loaded In-Line check valve is a general purpose rubber-faced check valve approved for use in fire-service systems. The Spring Loaded In-Line check valve is manufactured with a brass body, brass seat, and a rubber-faced clapper assembly. The Viking 3, 4 and 6 Easy Riser Swing check valve is a general purpose rubber-faced check valve approved for use in fire service systems. The valve is for use in preaction system risers. Low air supervisory switch The low pressure switches monitors the pressure within the sprinkler piping should a loss pressure of the air below 25PSI occurs, the pressure switch contacts transfer indicating low air supervisory signal. Should a loss pressure of the air below 23PSI occurs, the pressure switch contacts transfer indicating low air alarm signal. POTTER PS40-2A Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking Deluge Valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly. Alarm pressure switch The alarm pressure switch monitors the water flow within the sprinkler piping. Should the Deluge Valve clapper opens to allow water to flow into the sprinkler piping. The alarm pressure switch will activate, indicating a water flow signal POTTER PS10-1A IN OUT FM-076D-0-125C 4 of 16

5 SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Standard equipments (continued) N2 Blast Nitrogen generator South-Tek Systems utilizes Membrane technology in the N2-Blast Corrosion Inhibiting Systems in order to efficiently separate Nitrogen molecules from the air we breathe. Membrane technology, used in our smaller applications, has a simple air flow design, is wall-mounted and easy to service. PSA technology is more cost effective and energy efficient in larger Fire Protection Systems, those requiring more Nitrogen to compensate for the NFPA acceptable leak rate. BlastOff Leak detection system Unless the leak rate is catastrophic, the supervisory low pressure alarm on the FPS will not activate. Minor leaks cause the air compressor and N2-Blast to run excessively in order to maintain supervisory pressure. The unnecessary additional run-time decreases the lifespan of the equipment. The Patent Pending BlastOff - Leak Detection System is designed to detect significant leaks before they compromise the FPS and the Nitrogen Generation System. It has an internal audible alarm and dry contact for wiring into the Building Monitoring System (BMS) and will also alarm if the air compressor or the N2- Blast is not working properly. Nitrogen generator storage cylinder Type 1 Nitrogen Generation Systems include a 16 gallon Nitrogen receiver tank (12.2 dia x 44.8 H). Nitrogen generated by the N2-Blast is stored in the tank, and then sent to the sprinkler system through the Nitrogen air pressure maintenance device. N2 Blast AutoPurge System High purity Nitrogen must be equally distributed throughout the entire sprinkler piping system in order to effectively inhibit corrosion. The Patent Pending AutoPurge System provides a low volume, constant purge of Nitrogen within sprinkler piping. The rate in which gas is evacuated from the sprinkler piping is within NFPA guidelines and allows breathing to occur. The AutoPurge System also assists in drying out the residual water from a hydro test. Computational Fluid Dynamics modeling proves that this is the most effective way to ensure that high purity Nitrogen reaches all branches within the sprinkler piping. Install one AutoPurge System per system at a high point. There is a Label on one side of the housing that lists the proper setting for a variety of zone sizes. The Label list: Gallons in Zone, and APS Flow Setting. The Flow Setting is labeled from A-E and has three Settings in between each letter. Nitrogen generator air pressure maintenance device FIREFLEX N2 Blast use the Viking Model D-2 Air Pressure Maintenance Device (APMD) which is a pressure regulator that automatically reduces the supply air pressure to a preset requirement when connected to a constantly maintained air supply. The APMD is used to regulate the nitrogen pressure to 35 psi in the sprinkler piping at the specified system pressure for FIREFLEX N2 Blast Single interlock preaction system. 5 of 16 FM-076D-0-125C

6 SUREFIRE double c/w N 2 Blast Nitrogen generating system Optional preaction equipments Shut-off valve & sight glass (optional) The Shut-off Valve & Sight Glass Option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the preaction system be tested under actual discharge conditions. Main drain valve Sight glass assembly Shut-off valve Riser check valve Semi-flange inlet / outlet (optional) When required by the user, FIREFLEX N2 Blast units can be provided in a semi-flanged configuration. The semi flanged option provides flanged fittings only on the water inlet pipe (left side) and on the system riser outlet. The drain manifold is provided with a threaded connection (left side). The rest of the fittings are the same as usual with the main components being provided in the standard flanged / grooved configuration. Flange fitting outside cabinet Point flashlight HERE Deluge valve Riser check valve Main water supply control valve Deluge valve FM-076Z-0-4B-1 Anti-column device option The model LD-1 anti-column device is an optional trim component designed for use with preaction sprinkler systems. The anti-column device automatically prevents an unwanted water column from establishing within the system riser. On preaction sprinkler systems the anticolumn device prevents water from columning downstream of the easy riser check valve. Threaded drain output Flange fitting outside cabinet FM-076Z-0-4B-2 Main water supply control valve From Sprinkler Riser To Drain Collector FM-061H-0-146A FM-076D-0-125C 6 of 16

7 SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Preaction system - Air supply Direct air compressor (Style A ) Used only for the sprinkler piping network of the preaction system. Air supply style "A" includes the air compressor mounted inside the FIREFLEX N2 Blast cabinets with its supervisory trim and options. Compressors are of the tankless, oiless piston type and are factory piped to the sprinkler system riser, all within the FIREFLEX N2 Blast cabinets. Compressors are available in four (4) sizes: 1/6HP 1/2HP 1/3HP 1HP This section replaced by Dehydrator option (when used) E4 (plugged with SureFire trim) Copper tubing TO OPTIONAL ACCELERATOR (plugged when not used) 2 TO DRAIN COLLECTOR 1 TO SPRINKLER RISER Pressure relief valve Compressor Service Factor Amp (S.F.A) rating Compressor Size (HP) 115Vac / 60Hz 230Vac / 60Hz 1/6 5.0 Amp. 2.5 Amp. 1/3 7.4 Amp. 3.7 Amp. 1/ Amp. 5.0 Amp Amp. 9.0 Amp. 115 / 220 Vac 60Hz Compressor selection Table: H.P 40 PSI System capacity to fill system to 20 PSI in 30 minutes * 1/ gal. 1/ gal. 1/ gal gal. * For systems with maximum water supply pressure up to 250 PSI (1724 kpa) WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. 3 TO PNEUMATIC ACTUATOR (plugged when not used) CONTRACTOR'S HYDROSTATIC TEST PORT (system side) FM-061H-0-118C Air Pressure Maintenance Device (Style B ) Used only for the sprinkler piping network of the preaction system, when an external air supply is provided by others (tank mounted compressor or plant air) and piped to the air inlet port of the unit. Air supply style "B" provides an Air Pressure Maintenance Device (APMD) trim, factory mounted in the FIREFLEX N2 Blast cabinets. This section replaced by Dehydrator option (when used) E4 (plugged with SureFire trim) TO PNEUMATIC ACTUATOR (plugged when not used) 3 Contractor external Air or Nitrogen connection TO OPTIONAL ACCELERATOR (plugged when not used) 1 TO SPRINKLER RISER FM-061H-0-119B CONTRACTOR'S HYDROSTATIC TEST PORT (system side) 7 of 16 FM-076D-0-125C

8 SUREFIRE double c/w N 2 Blast Nitrogen generating system Details & field wiring diagrams P & ID Autopurge System Sprinkler N2 Blast Compressor Preaction Compressor Air Maintenance Device/s (AMD/s) Supplied by Fireflex Riser towards the nozzles Tank Provided with brackets and Strap Low Air Pressure Switch Preaction Air Kit Preaction System Nitrogen Air FM-076D-0-125C 8 of 16

9 SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Cabinet with main components, shown without door(s) FM-06LM-0-1A-4 9 of 16 FM-076D-0-125C

10 SUREFIRE double c/w N 2 Blast Nitrogen generating system Trim diagram E4 F5 E9 FIELD CONNECTION TO SPRINKLER PIPING NETWORK To Air Supply System Trim C1 1 D2 F4 B10 B8 C2 B5 D3 F1 A1 B11 F2 F3 To Air Supply System Trim 2 B7 B6 D1 B9 B13 FIELD CONNECTION TO OPEN DRAIN (left side only) B12 B3 B4 B2 B1 FIELD CONNECTION TO WATER SUPPLY (left side only) TotalPac Base (shown without enclosure) CONTRACTOR'S HYDROSTATIC TEST PORT (water supply side) FM-076Z-0-64A Trim Components: A1 Deluge valve B1 Priming valve B2 Strainer B3 1/16" Restricted orifice B4 Spring loaded check valve B5 Alarm test valve B6 Flow test valve B7 Drip check valve B8 Drain check valve B9 Pressure operated relief valve (PORV) B10 Emergency release valve B11 Priming pressure water gauge & valve B12 Water supply pressure gauge & valve B13 Clapper check valve C1 C2 D1 D2 D3 E4 E9 F1 F2 F3 F4 F5 Alarm pressure switch Connection to water motor gong (strainer supplied by contractor) Water supply control valve Riser check valve Main drain valve Air supervisory pressure switch Float-check assembly N.C. Solenoid valve 24Vdc N.O. Solenoid valve 24Vdc Pneumatic actuator Pneumatic actuator pressure gauge 5/64" Restricted orifice FM-076D-0-125C 10 of 16

11 SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Wiring diagram TBB WIRING IN CLASS B / STYLE B TBA DETECTION ZONE 1 5.1K EOLR 1 LINE 2 NEUTRAL 3 GROUND 4 GROUND 5 NEUTRAL 6 LINE 7 LINE 8 NEUTRAL 9 GROUND 120VAC, 60Hz AIR COMPRESSOR 1HP MAX WITH AIR OPTION "A" ONLY Refer to Local Electrical Codes for wiring size. MANUAL PULL STATIONS ZONE 4 WIRING OF INPUT POWER SOURCE NAC1 SILENCEABLE ALARM 5.1K 5.1K EOLR EOLR CONTROL PANEL 100VA MAX N²BLAST UNIT 20A MAX Branch circuit for air compressor shall not be the same as the control panel power source. WIRING IN CLASS B / STYLE Y NAC2 NON SILENCEABLE WATERFLOW 5.1K EOLR C TROUBLE NO NC C ALARM NO NC C SUPERVISORY NO C TBA NOTES: Class A / Style D requires CA2Z modules. End-of-line devices are not required for Class A / Style D wiring. WATER FLOW NO 24VDC RESETTABLE OPTIONAL WIRING IN CLASS A / STYLE D DETECTION ZONE 1 MANUAL PULL STATIONS ZONE TBC 24VDC NON RESETTABLE RS SHIELD C MAIN VALVE NO NC LEGEND SMOKE DETECTOR HEAT DETECTOR MANUAL RELEASE BELL OR HORN DRY CONTACT END OF LINE RESISTOR CHICAGO OPTION LOS ANGELES OPTION C 9 OPTIONAL SHUT-OFF VALVE NO NC TBA POWER LIMITED 4-WIRE DETECTION CIRCUIT VDC COM UL-Listed 24VDC 4-Wire Smoke Detector CONTACTS RATED 3A, 30VDC RESISTIVE 24VDC COM UL-Listed 24VDC 4-Wire Smoke Detector 5.1K EOLR PAM-4 Power Supervisory Relay (EOL Relay) CONTACTS RATED: 5A, 1/6HP, 125/250VAC 0.5A, 250VDC 0.25A, 250VDC NOTE: Contact provided for connection to the building's central Fire Alarm Panel. NOTES: Control panel AC power source is supervised and non-power limited. All devices are shown in their normal supervisory state. Use dry contacts with power limited circuits only. FM-061H-0-235B Power Limited (supervised) Initiating Device Circuits Detection Zone 1, 2, 3, and 4. Max. loop resistance: 100 ohms End of line: 5.1K ohms, 1/4W Leave ELR (provided) on all unused circuits. Refer to Device Compatibility in the VFR-400 Releasing control panel Manual. Power Limited (supervised) Initiating Device Circuits Supervision Zone 1, and 2. Max. loop resistance: 100 ohms End of line: 5.1K ohms, 1/4W Leave ELR (provided) on all unused circuits. For dry contact supervisory devices such as tamper, low air, or high air switches. (Class-B only) Power Limited (supervised) Notification Appliance Circuits Output Circuit 1, 2, 3, and 4 Maximum operating voltage: 27Vdc (ripple: 0.3Vdc) Maximum usable current per circuit: 1.0A Total current available (all circuits): 2.5A Polarity is reversed in supervisory condition. Leave ELR (provided) on all unused circuits. Refer to Device Compatibility in the VFR-400 Releasing control panel Manual. Auxiliary Power 24Vdc Regulated Source Total current available: 0.2A Resettable for 4 wires smoke detectors WARNING Releasing control panel shall be supplied by a dedicated circuit breaker, as per NFPA 70, Section 760 and Canadian Electrical Code, Section of 16 FM-076D-0-125C

12 SUREFIRE double c/w N 2 Blast Nitrogen generating system Optional electrical equipment's Relay module ARM-44 The ARM-44 is an auxiliary relay module designed to operate with the Viking VFR-400 releasing control panel to provide 4 independent form C relay outputs. The 4 output circuits each have a dedicated relay. Each relay is rated for 3 amps at 24 volts DC resistive load. The relay module mounts directly to the back of the cabinet and is connected to the main board. All of the relay terminals are wired back to the field wiring junction box. A disable switch is available for disabling the relays when the system is being tested or serviced. Class A initiating device module CA2Z The Model CA2Z Class A Module is designed to be used with the Viking VFR-400 releasing control panel to convert from two (Class B) initiating device circuits to two (Class A) circuits. The module is to be mounted in the upper right hand corner of the panel. All the connections are wired back to the field wiring junction box. 24Vdc RS-485 P Remote Annunciator RA-4410-RC The RA RC remote annunciator is designed to operate with the Viking VFR-400 releasing control panel. There are 34 LED's to indicate a change in panel status. There is a buzzer on the annunciator that sounds for any trouble or supervisory condition. The release control panel supervises and communicates with the annunciator via separate connections for the RS-485 communication and the 24VDC power requirement of the RA-4410-RC. Separate cables should be used for power and communication. Shielded cable MUST be used for the RS-485 communication line. Class A Indicating Appliance Circuit Module The Model CAM Class A Module is designed to be used with the Viking VFR-400 releasing control panel to convert a single (Class B) indicating appliance circuit to a (Class A) circuit (one module is required for each indicating appliance circuit). After installing the CAM, the indicating circuit should be activated to ensure proper operation and connections. The module is provided with double-sided foam tape and should be mounted in the field wiring junction box so that the terminals are accessible. RA-4410-RC ZONE 1 OUTPUT 1 ZONE 1 OUTPUT 1 ZONE 2 OUTPUT 2 ZONE 2 OUTPUT 2 ZONE 3 OUTPUT 3 ZONE 4 OUTPUT 4 AC POWER SUPERVISORY ZONE 3 OUTPUT 3 POWER TROUBLE SYSTEM TROUBLE GROUND FAULT SUPERVISORY LAMP TEST TROUBLE COMMON ALM. SILENCE ALM. SILENCE STEADY : DISCHARGED FLASHING : PRE-DISCHARGE ZONE 4 OUTPUT 4 FM-076D-0-125C 12 of 16

13 SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Cabinet The FIREFLEX N2 Blast cabinet is made of sturdy 14 gauge steel. Refer to figure 4 for dimensions. All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with two doors, all provided with a neoprene gasket to avoid vibrations, giving the access to the pressure gauges reading and the manual emergency release. The cabinet assembly is pre-assembled, pre-wired, and factory tested under ISO-9001 conditions. Refer to figures 2 & 3 for installation and clearances details. Electrical junction boxes are integrated inside the cabinet for connection of the supervisory and alarm devices contacts. Knockouts are pre-punched for the installing contractor as indicated on figure 1. Figure 1 - knockouts details Top of Cabinet High voltage 2½" Low voltage 2½" Typ. 8½" 3¾" 3" FM-061H-0-68B-12 Figure 2 - Floor anchoring template F 5'' Ø3/4" E G FM-061H-1-49B-6 Size E F G 46" 15" 48" 25" 54" 21" 56" 27" Figure 3 - Required clearance 12'' MIN 12'' MIN 22'' MIN FM-061H-1-49B-7 Size A 46" 24" 54" 32" 13 of 16 FM-076D-0-125C

14 SUREFIRE double c/w N 2 Blast Nitrogen generating system Figure 4 - Cabinet dimensions D P TBA, TBB & TBC Q TBB TBA & TBC CONTROL PANEL (except for Remote Controlled Unit) CONTROL PANEL OPTIONAL SHUT-OFF VALVE ØB SPRINKLER RISER SCH.40 GROOVED OUTLET F SPRINKLER RISER SCH.40 GROOVED OUTLET S R N DRAIN - SCH.40 GROOVED OUTLET ØA ØC M WATER INLET SCH.40 GROOVED OUTLET G T FM-06LM-0-2A System Size A B C D E F G H J K L M N P Q R S T 1½" 2" 1½" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37½" 44¾" 50" 2" 2" 2" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37¾" 45" 50" 3" 4" 3" 2" 46" 25" 77¼" 4" 10" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 44" 47¾" 50" 4" 4" 4" 2" 54" 31" 81¼" 4" 10" 11½" 13¾" 3¾" 2½" 2½" 23¾" 11½" 48½" 53" 58" 6" 6" 6" 2" 54" 31" 81¼" 4" 11" 13" 13¾" 5¼" 2¾" 2¾" 25" 13" 59¼" 65¼ 58" Dimensions are nominal and may vary by ¼ FM-076D-0-125C 14 of 16

15 15 of 16 FM-076D-0-125C

16 1935, Lionel-Bertrand Blvd. Boisbriand QC Canada J7H 1N8 Tel.: Fax: Toll Free: Web: FM-076D-0-125C 16 of 16

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit FireFlex N 2 Blast description The FIREFLEX N2 Blast integrated system consists of an integrated double interlock Electric/Pneumatic release preaction automatic sprinkler system combined with a Nitrogen

More information

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system FireFlex N 2 Blast description The FIREFLEX N2 Blast integrated system consists of an integrated double interlock

More information

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical

More information

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components

More information

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components

More information

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TotalPac 3 Firecyle III Deluge Remote controlled system

TotalPac 3 Firecyle III Deluge Remote controlled system (Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical

More information

TotalPac 3 Wet pipe system c/w retard chamber

TotalPac 3 Wet pipe system c/w retard chamber DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of an integrated wet type sprinkler riser assembly with retard chamber, totally pre-assembled, prewired and

More information

TotalPac 3 Deluge, Electric release Self-contained system

TotalPac 3 Deluge, Electric release Self-contained system (Optional) DESRIPTION This TOTALPA 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical

More information

TotalPac X Single interlock SUREFIRE system

TotalPac X Single interlock SUREFIRE system DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a trim totally preassembled, pre-wired and factory tested. All electrical and mechanical components of

More information

TotalPac X Firecycle III Preaction Double interlock system

TotalPac X Firecycle III Preaction Double interlock system DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a multicycling Firecycle III system trim totally pre-assembled, pre-wired and factory tested. All electrical

More information

FireFlex DUAL Double Interlock, Self-contained system

FireFlex DUAL Double Interlock, Self-contained system FireFlex DUAL description The FireFlex DUAL integrated system consists of an integrated Double interlock preaction automatic sprinkler system combined with a clean agent fire extinguishing system, factory-assembled

More information

TotalPac 3 Single interlock Preaction, Electric release Self-contained system

TotalPac 3 Single interlock Preaction, Electric release Self-contained system (Optional) DESRIPTION This TOTALPA integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

TotalPac 3 Non interlock Preaction, Electric release Self-Contained system

TotalPac 3 Non interlock Preaction, Electric release Self-Contained system (Optional) DESRIPTION This TOTALPA integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical and

More information

FireFlex 1230 Self-contained system

FireFlex 1230 Self-contained system FireFlex 1230 description The FireFlex 1230 integrated system consists of a clean agent fire extinguishing system, factoryassembled in a cabinet and integrating all the components necessary for a complete

More information

TOTALPAC2 Integrated Fire Protection System

TOTALPAC2 Integrated Fire Protection System TOTALPAC2 Integrated Fire Protection System Page 1 of 8 General 1. Applicable Standards The TOTALPAC2 Surefire complies with the following standards: - NFPA-13 Sprinkler Systems; - NFPA-15 Water Spray

More information

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E Advanced Integrated Fire Protection Systems TOTALPAC 2 Owner's Operation and Maintenance Manual FIRECYCLE III September 2009 FM-086G-0-5E TOTALPAC2 OWNER'S OPERATION & MAINTENANCE MANUAL Manufactured by

More information

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014 January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE Page 1 of 12 1. (Refer to Figures 1-7.) Viking supervised Single-Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system piping

More information

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT Project No: 3049157 Class: 1011/1012/1013 Product Type: Deluge and Preaction Sprinkler Systems Product

More information

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types: Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Preaction Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. Page 1 of 9 1. (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally held closed by supervisory

More information

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types: Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Preaction Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE Page 1 of 12 1. DESCRIPTION (Refer to Figures 1-6.) Viking Electric/Pneu-Lectric Double Interlocked Preaction Systems utilize a Viking deluge valve, pneumatic supervision of the automatic sprinkler system,

More information

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA. 319a. January 27, 2012 January 27, 2012 319a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally

More information

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar) Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

Worldwide Contacts.

Worldwide Contacts. Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE January 27, 2012 311a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system.

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5 Page 1 of 5 1. SYSTEM DESCRIPTION Viking supervised, single interlocked preaction pre-primed systems utilize a Viking Deluge Valve (A.1) and a hydraulically pressurized automatic sprinkler system. The

More information

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

Pre-Pack INTEGRATED PRE-ACTION SYSTEM Pre-Pack INTEGRATED PRE-ACTION SYSTEM HD FIRE PROTECT TECHNICAL DATA MODEL Pre-Pack SIZE DELUGE VALVE MODEL RISER CHECK VALVE MODEL WATER MOTOR GONG BELL MAXIMUM WORKING PRESSURE SYSTEM END CONNECTION

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance Instructions for Installation, Operation, Care and Maintenance Bulletin 733 Rev. F Model DDX PrePaK, Type D Preaction System 4 (100mm), 6 (150mm) & 8 (200mm) Single Interlock - Electric Release Double

More information

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock Bulletin 740 Rev. A Model DDX PrePaK, Type D Preaction System 2 (50mm), 2-1/2" (65mm) & 3 (80mm) Sizes Instructions for Single Interlock Installation, Operation, Double Interlock Care and Maintenance 10

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release Deluge System Pneumatic Release Deluge System Pneumatic Release When the fixed temperature release () is activated by fire, pressure in the release system escapes from the open device, allowing the pneumatic

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

Deluge & Preac tion Systems

Deluge & Preac tion Systems Deluge & Preaction Systems Deluge Systems are normally used in special hazard installations where water must be applied to an entire area for protection. They use open sprinklers or spray nozzles attached

More information

Operation & Maintenance Manual

Operation & Maintenance Manual Operation & Maintenance Manual FM-0723-0-02 A Integrated Compressed Air Foam System with Manual Release Owner's Operation and Maintenance Manual FM-0723-0-03 A OWNER'S OPERATION & MAINTENANCE MANUAL FireFlex

More information

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

More information

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE HD FIRE PROTECT TECHNICAL DATA SIZE DELUGE VALVE CHECK VALVE SPRINKLER ALARM RELEASE PANEL 50, 80, 100, 150 & 200 NB Model H3, UL Listed

More information

1935, Lionel-Bertrand Blvd. Boisbriand, Quebec, Canada J7H 1N8 Tel.: (450) Fax: (450) Toll Free: (866)

1935, Lionel-Bertrand Blvd. Boisbriand, Quebec, Canada J7H 1N8 Tel.: (450) Fax: (450) Toll Free: (866) Systems Inc 1935, Lionel-Bertrand Blvd. Boisbriand, Quebec, Canada J7H 1N8 Tel.: (450) 437-3473 Fax: (450) 437-1930 Toll Free: (866) 347-3353 - www.fireflex.com AC Power Partial Disable Acknowledge Alarm

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE HD FIRE PROTECT TECHNICAL DATA SIZE DELUGE VALVE CHECK VALVE SPRINKLER ALARM RELEASE PANEL 50, 80, 100, 150 & 200 NB Model H3, UL Listed

More information

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole. September 8, 2000 Dry 132 a 1. PRODUCT NAME High Pressure Dry System Manufactured 2000-2. MANUFACTURER The Viking Corporation 210 N Industrial Park Road Hastings MI 49058 U.S.A. Telephone: (616) 945-9501

More information

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION HD FIRE PROTECT TECHNICAL DATA SIZE DELUGE VALVE CHECK VALVE SPRINKLER ALARM RELEASE PANEL 50, 80, 100, 150 & 200 NB Model H3, UL

More information

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description The TYCO VIZOR Electronic Dry Pipe Accelerator (EDPA) is

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

ECS Protector Nitrogen Generator PGEN-40FK/PGEN-50FK/PGEN-60FK PGEN-40M/PGEN-50M/PGEN-60M

ECS Protector Nitrogen Generator PGEN-40FK/PGEN-50FK/PGEN-60FK PGEN-40M/PGEN-50M/PGEN-60M ECS Protector PGEN-40/PGEN-50/PGEN-60 (PGEN-40E/PGEN-50E/PGEN-60E) For use under U.S. Patents 8,720,591, 9,144,700 and 9,186,533 Specifications Dimensions (cabinet): Dimensions (incl. bypass): Weight:

More information

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE Page 1 of 8 1. DESCRIPTION Viking Deluge Systems utilize a Viking Deluge Valve to control the water supply to system piping equipped with open sprinklers and/or spray nozzles. The system piping remains

More information

OPEN SPRINKLER SYSTEM

OPEN SPRINKLER SYSTEM OPEN SPRINKLER SYSTEM Introduction Competence and innovation driven by consistent market development and customer requirements have shaped the successful development of the SHIELD Brand. The extensive

More information

Commercial and Light Industrial Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground

More information

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-10/(PGEN-10E)

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-10/(PGEN-10E) ECS Pre-Engineered Wall Mount PGEN-10/(PGEN-10E) Specifications For use under U.S. Patents 8,720,591, 9,144,700 and 9,186,533 Cabinet Dimensions: Weight Temperature Range: Power Supply: Power Consumption:

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-3M Bermad Electro-Pneumatically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with

More information

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0 CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES DIVISION 21 FIRE SUPPRESSION PART 1 GENERAL 1.01 DESCRIPTION A. Provide UL listed, FM approved listed fire protection specialties or accessories as required by either the equipment manufacturer or the

More information

Model DDX Deluge Valve

Model DDX Deluge Valve Model DDX Deluge Valve Bulletin 510 Bulletin 510 Features 1. Differential type, simple, lightweight, dependable construction. 2. Simply and easily trimmed for releasing by: Manual pull stations Wet pilot

More information

ECS Protector Nitrogen Generator. ECS Protector Nitrogen Generator PGEN-30. Specifications

ECS Protector Nitrogen Generator. ECS Protector Nitrogen Generator PGEN-30. Specifications ECS Protector PGEN-30 Specifications Dimensions (cabinet): 24 (W) X 12 (D) X 53 (H) Width (incl. bypass): 33 Weight: Power Supply: Power Consumption: Gas Connections: Drain Connection: 152 lbs 120v/1 phase/60hz

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-3/(PGEN-3E) PGEN-5/(PGEN-5E)

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-3/(PGEN-3E) PGEN-5/(PGEN-5E) ECS Pre-Engineered Wall Mount PGEN-3/(PGEN-3E) PGEN-5/(PGEN-5E) Specifications For use under U.S. Patents 8,720,591, 9,144,700 and 9,186,533 Cabinet Dimensions: Weight Temperature Range: Power Supply:

More information

Electric Release Panel Wiring Tips

Electric Release Panel Wiring Tips R IPS CARBO STEEL PIPE FIRE PROTECTIO PRODUCTS Electric Release Panel Wiring Tips 30.4 VICTAULIC IS A ISO 900 CERTIFIED COMPAY Model PDRP-00 Releasing Panels are compact single enclosure units containing

More information

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM ANNEXUREIII D: FIRE PROTECTION SYSTEM SECTION ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Supply, Installation, testing and commissioning of Analogue Addressable Fire Alarm Control panel with battery backup

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

INTELLIGENT FIRE ALARM CONTROL PANEL

INTELLIGENT FIRE ALARM CONTROL PANEL INTELLIGENT FIRE ALARM CONTROL PANEL FX-2000 SERIES Description Mircom s FX-2000 Series Intelligent Analog Fire Alarm Control Panel is designed to provide maximum flexibility of analog system requirements

More information

SECTION PREACTION SPRINKLER SYSTEMS

SECTION PREACTION SPRINKLER SYSTEMS PART 1 GENERAL SECTION 211316 - PREACTION SPRINKLER SYSTEMS 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Discontinued Product

Discontinued Product SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS The Victaulic Series 759 alarm check valve works as a check valve by preventing the reverse flow of water from the system piping to the water supply. The valve

More information

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems STEVEN WOLIN, VICE PRESIDENT, PRODUCT TECHNOLOGY & COMPLIANCE ANTONIO LUIS, TECHNICAL SERVICES MANAGER RELIABLE AUTOMATIC SPRINKLER

More information

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays AEGIS Conventional Fire Alarm-Suppression Control Unit FEATURES Agency Approvals FM Approved FM Approved to ANSI/UL 864, 9th edition FM Approved to ULC-S527-99 Other domestic U.S. approvals/listings pending/

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE October 10, 2008 Deluge Devices 281a 1. PRODUCT DESCRIPTION The Viking Model C-1 is a rate-of-rise releasing device for use on hydraulic and pneumatic release systems controlling operation of Viking deluge

More information

good things in small packages

good things in small packages FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with

More information

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

Release Control Fire Alarm Systems

Release Control Fire Alarm Systems SYSTEM ABORT PUSH AND HOLD COIL SUPERVISION MODULE (2 AMP) 2081-9046 RED INSTALLATION INSTRUCTIONS 574-437 REV YEL NAC+ MAINTAIN 1/4" SEPARATION BETWEEN POWER LIMITED (RED/) AND NONPOWER S LIMITED (YEL/)

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold Features NEMA 4 solid metal enclosure Factory installed neoprene gasket 0-90 second field replaceable pneumatic retard 350 PSI system pressure rated Synchronized switch action Waterflow switches that are

More information

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82  ASTM A 216 WBC. DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA NORMAL SIZE MATERIAL SEVICE PRESSURE THREADED OPENING MOUNTING FACTORY HYDOSTATIC TEST PRESSURE FLANGE CONNECTION WET PILOT SPRINKLER HEIGHT LIMITATION NET WEIGHT

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) PATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) NAC ETENDER SUPPLIES Installation Instructions 273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations Worldwide Contacts www.tyco-fire.com AQUAMIST Mist Control Center (MCC) Pump Skid Unit General Description Center (MCC) Pump Skid Unit is a preassembled, self-contained, control center for Ultra Low Flow

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations Worldwide Contacts www.tyco-fire.com AQUAMIST Mist Control Center (MCC) Pump Skid Unit General Description Center (MCC) Pump Skid Unit is a preassembled, self-contained, control center for Ultra Low Flow

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description. Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description The TYCO RAPID RESPONSE Model RCP-1 Residential

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature AutoTest VSR (VSR-AT) (EU) Features Assembled in USA 0-30 second field replaceable electronic retard Two SPDT (Form C) switch contacts Weatherproof Easy to read wire terminal designations Easy to read

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

TECHNICAL DATA. model c-2

TECHNICAL DATA. model c-2 Page 1 of 6 1. PRODUCT DESCRIPTION The Viking Model C-2 is a rate-of-rise releasing device for use on hydraulic and pneumatic release systems controlling operation of Viking deluge valves on deluge or

More information

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description CONVENTIONAL FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements. SECTION 21 13 13 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes labor and materials for the installation of a hydraulically calculated automatic, wet-pipe sprinkler

More information