EFBW series - BiWire Ultra control panel

Size: px
Start display at page:

Download "EFBW series - BiWire Ultra control panel"

Transcription

1 4.2 Control panels and repeater panels EFBW series - BiWire Ultra control panel Eaton s new BiWire Ultra fire detection system is unlike any other standard conventional system as the panel, conventional detectors, sounders and EN54-23 approved beacons all share the same zone wiring. This delivers significant savings in both cable and installation costs without sacrificing the systems capability. Supporting up to 52 devices per zone, all panels in the range have the facility to flash detector LED s to facilitate the location of any wiring faults. Features Choice of 2, 4 and 8 zone control panels Detectors and sounders share the same wiring One man test facility Class change input Interlink relay functionality for connecting 2 BiWire Ultra panels together Supports an expansion card for Fire Routing Equipment, Fire Protection Equipment and fire relays per zone. Modern and discreet enclosure Benefits EFBW2ZONE EFBW4ZONE EFBW8ZONE No. of zones Detectors per zone Maximum loading per zone mA 200mA 200mA Repeater Port Tailored to the size and need of the building Reduced cost of installation Simple system testing by a single fire alarm technician Capability to sound class change bell in schools Interlink relay allows for greater system flexibility Comprehensive protection for safety of building occupants

2 4.2 Control panels and repeater panels Technical specification Dimensions EFBW2ZONE EFBW4ZONE EFBW8ZONE Description 2 zone panel 4 zone panel 8 zone panel Specification Number of Zones Devices Per Zone Max of 32 Detectors and Manual Callpoints, Zone loading cannot exceed 200mA in alarm Maximum Loading Per Zone Standby Zone Voltage Alarm Zone Voltage Fuse Protection Per Zone End of Line Termination Fire, Fault & Interlink Relay 200mA Min: 22V DC, Max: 24V DC Min: 31V DC, Max: 33V DC 250mA PTC Standard panel connections EOLM-3 Only (Do not use EOLM-1 or EOLM-2) Type: Volt-Free, Single Pole Double Throw, Rating: 30V DC, 1A, Fuse 1.1A PTC Auxiliary Output V: 0V DC (Standby)/30V DC (Alarm +/-10%), Imax: 50mA, Fuse: 50mA PTC Class Change Short circuit to trigger input, open circuit to clear input Mains rating 230V Ah +10%/-15% 50Hz Battery rating 2 x 12V 5Ah Changeable power fuses Repeater Port Yes Environmental Operating temperature Relative humidity IP Rating Physical Weight (excluding batteries) Material Cabling Cable access Cable type Mains 1A anti surge Battery 6-3A anti surge -5 C to +40 C 93% +/-3% non-condensing IP kg PC ABS Front and Rear 29 x 20mm drill positions Slots for rear cable entry Firetuf FT120 / FP200 2 core 1.5mm, 2 screened fire rated cable, 500m (max per zone) Description Height (mm) Width (mm) Depth (mm) Complete Panel Backbox Status indication 1. When the fire panel enters a fault condition it will turn on the General Fault indicator and the appropriate fault indicator (refer to 8 for more details). The panel buzzer will sound a slow pulsing tone. 2. System Fault Severe failure of the panel, the service company must be contacted immediately. Repeater Fault Communication with a repeater panel has been lost 3. Battery Fault Battery voltage missing Mains Fault Mains supply missing 4. Battery Failure Battery impedance failure Charger Fault Charger voltage missing 5. Sounder Fault Short circuit or open circuit condition detected on the zone will prevent the activation of sounders if fitted on that zone 6. FRE Fault Short circuit or open circuit condition detected on the FRE output 7. FPE Fault Short circuit or open circuit condition detected on the FPE output 8. Detector Removed Fault A detector head has been removed Zone Fault Short circuit or open circuit condition detected on the zone. Catalogue numbers Description Eaton 2 zone BiWire Ultra panel EFBW2ZONE Eaton 4 zone BiWire Ultra panel EFBW4ZONE Eaton 8 zone BiWire Ultra panel EFBW8ZONE BiWire End of line module BWEOLM 2 zone relays + FRE/FPE BW0B2Z 4 zone relays + FRE/FPE BW0B4Z 8 zone relays + FRE/FPE BW0B4Z

3 EFBW5IN1DET - BiWire Ultra detector 5 in 1 The BiWire Ultra range offers a multi-mode, 5 in 1 detector, approved to both EN54 parts 5 & 7, which covers many building needs. It s quick and simple to install with a stylish low profile design. The detector is mounted on our standard conventional base (FXN520). Each detector is fitted with a 360 viewable LED for indication. This 5 in 1 detector can be configured to operate as either an optical detector, photo-thermal detector or 1 of 3 heat detector modes (rate of rise and 2 fixed heat models) using the four position switches located at the back of the detector. The EFBW5IN1DET is certified for use in all 5 modes. Features Five modes in one detector Offers a range of sensor types 360 indicator LED using lightpipe technology Positive lock indication Easy to maintain/service Benefits Suitable for a broad range of applications Wide viewing angle for increased LED visibility Quick and simple to install Discreet design for incorporation into any decor

4 Technical specification Dimensions EFBW5IN1DET Description Detector 5 in 1 Standards EN54 Part 5 & Dia Supply ratings Operating voltage 15V DC to 30V DC Standby current Startup current 30µA (max) 340µA (max) D1 D2 Alarm current 25mA (max) Fixing information Mounting position Ceiling in open areas Mounting options Surface mount with FXN520 base Area coverage 100m² (subject to local standards) System wiring 2 Core Environmental Operating temperature -20ºC to 75ºC (dependent on setting) Humidity (non condensing) 0 to 93% Dia (mm) D1 (mm) D2 (mm) Physical Construction Colour Dimensions excl base (dia x depth) Dimensions incl base (dia x depth)) Ingress protection EMC Compatibility Suitable for use with PC/ABS White 104mm x 42mm 104mm x 55mm IP40 CE Marked Eaton s BiWire Ultra fire system Performance Feature Optical smoke mode Photothermal mode Rate of rise mode Fixed heat 77 C mode Fixed heat 92 C mode Area coverage 100m 2 100m 2 50m 2 50m 2 50m 2 (subject to local standards) Heat class N/A A2S A1R BS CS Alarm temperature N/A 60 C 60 C 77 C 92 C Installation 1. Detectors are fixed and wired via common mounting base. 2. Cable entry into base can be rear or side. 3. A locking facility is provided which can be activated if required to prevent unauthorised detector removal without the use of a special tool. 4. Positive click mechanism incorporated to provide clear indication when detector is correctly located in base. User interface 1. Red LED to indicate alarm condition. 2. Amber LED to indicate chamber fault/drift compensation limit. 3. All wiring connections are via a common mounting base (supplied separately). Catalogue numbers Description Detector 5 in 1 Standard base EFBW5IN1DET FXN520

5 EF5021BW range - BiWire Ultra base sounder & base sounder VAD The BiWire Ultra base sounder and base sounder VAD can be used both with a detector or as a stand alone device. The base sounder and base sounder VAD are certified to EN54-3 and EN54-23 respectively. The base sounder and base sounder VAD both incorporate a detector mounting base allowing a detector to be fitted directly to the base, or alternatively a cover plate can be used to provide a dedicated, discreet stand alone device. Features Available in both sounder only and sounder VAD Certified to EN54-3 & EN54-23 Cover plate (optional) Benefits Offers a compact design and reduces time of installation of the base with the detector Easy to maintain and service Standalone base sounder or base sounder VAD offers the flexibility of use with or without the detector

6 Technical specification Dimensions EF5021BWS / EF5021BWSB Supply Voltage (Alarm) 25.5~35 Vdc Supply Voltage (Standby) 18~25.5 Vdc Cable Size/type 0.5~2.5mm / FIRETUF, FP200 or MICC Standby Current (BiWire Mode) <15μA Current (High Volume) Sdr Only = 4.7mA, AV = 11mA Current (Low Volume) Sdr Only = 2.6mA, AV = 8.7mA Sound Output (High Volume) 90 +/- 3dB(A) Sound Output (Low Volume) 80 +/- 3dB(A) Operating Temperature -10 to +55ºC (93% ± 3%RH) Material ABS / PC FR Plastic Environmental Category IP21C Tones 3 Flash Rate 0.5Hz (Not applicable to EF5021BWS) Flash On Period 60ms (Not applicable to EF5021BWS) Dia D Dia (mm) D (mm) Installation Standard connections 1. Installation is simple using first fix base. 2. First fix base is fixed to mounting surface via 2 fixings holes. 3. Cables enter through aperture in base (rear entry only) 4. Main body is then clipped into place on base, main body locks into place when pressed into position. 5. Cables pass through aperture in sounder body and terminate at the front. 6. Connections are to connector block on front of main sounder body. System functionality 1. Volume and tone are set by control panel, no need to access sounder to alter setting. 2. Soft addressed. Compatible Conventional Control Panelsl -ZONE + + VE - VE LED 3 E 4 remote indicator (optional) 2 1 LED 3 E 4 EOLM-1 end of line monitor device Catalogue numbers Description BiWire Ultra base sounder BiWire Ultra base sounder VAD Cover Plate (Pack of 5) EF5021BWS EF5021BWSB CASC

7 EF009, EF009SB - BiWire Ultra wall sounder & wall sounder VAD The BiWire Ultra wall sounder and wall sounder VAD offer low current consumption and high sound output. The BiWire Ultra range of sounders has been designed to meet the latest European Standards - EN54-3 and EN It is offered in two variants, sounder only or a combined sounder VAD. Features Ultra low current consumption Certified to EN54-3 and EN54-23 High sound output Weatherproof option Benefits Maximises number of devices on a system Certified for Fire use Ideal for large installations Easy to maintain and service

8 Technical specification EF009SB / EF009SBWP & EF009 / EF009WP Supply Voltage (BiWire Alarm) 25.5~35 Vdc Supply Voltage (BiWire Standby) 18~25.5 Vdc Supply Voltage (Conventional) 18~35 Vdc Cable Size/type 0.5~2.5mm / FIRETUF, FP200 or MICC Standby Current (BiWire Mode) <15μA Current (High Volume) Sdr Only = 4.8mA, AV = 11mA Current (Low Volume) Sdr Only = 2.6mA, AV = 8.7mA Sound Output (High Volume) 99 +/- 3dB(A) Sound Output (Low Volume) 89 +/- 3dB(A) Operating Temperature -25 to +70ºC (95%RH) Material ABS FR Plastic Environmental Category EF009SB: IP21C EF009SBWP: IP66 Tones 3 Flash Rate 0.5Hz (Not applicable to EF009(WP)) Flash On Period 60ms (Not applicable to EF009(WP)) Installation Dimensions 1. First fix mounting plate is fixed to wall. 2. Cable entry is from rear, or top/bottom. 3. Connections are to main sounder body. 4. Separate alarm line in and alarm line out terminals are provided. D H Interface options Sounder operates from nominal 24V dc supply and can be connected to any suitably rated conventional sounder circuit. Standard connections W Description H (mm) W (mm) D (mm) EF009 / EF009SB EF009WP / EF009SBWP Compatible Conventional Control Panel WARNING: Do NOT use high voltage testers if ANY equipment is connected to the system. Screen (Earth) must be continuous along entire length of cable. Catalogue numbers Description BiWire Ultra wall sounder BiWire Ultra wall sounder, weatherproof BiWire Ultra wall sounder VAD BiWire Ultra wall sounder VAD, weatherproof EF009 EF009WP EF009SB EF009SBWP

9 EF201BWCP, EF203BWCPWP - BiWire Ultra callpoints Two versions of the BiWire Ultra callpoints are available in this range, the EF201BWCP which can be either surface or flush mounted and the EF203BWCPWP which is a weatherproof version. Both the EF201BWCP and the EF203BWCPWP are compatible with the Eaton s BiWire Ultra range of fire systems. These callpoints are designed for fast and simple installation and are supplied as standard with a frangible glass element and a test key for ease of maintenance. A comprehensive range of accessories is available to maximise the functionality of the callpoint for particular applications. Features Fast fit clip on front cover Wide range of accessories Heavy duty terminals Two models available: - Internal - Weatherproof (IP65) Single tool for test and access Robust construction Benefits Quick and simple to install Easy to maintain and service Versatile installation Weatherproof variant suitable for outside use

10 Technical specification Supply Voltage Cable Size/type Standby Current Alarm Current Low Level Alarm Current Operating Temperature (EF201BWCP) Operating Temperature (EF203BWCPWP) Material Environmental Category LED Indicator EF201BWCP / EF203BWCPWP 18~35 Vdc 0.28mm² ~ 2.5mm² Cable shall comply with applicable standard <22μA 20mA 1mA -10 to +55ºC (95%RH) -25 to +70ºC (95%RH) ABS FR Plastic EF201BWCP: IP21C EF203BWCPWP: IP66 Red Dimensions W Standard connections COMMON 680Ω H Compatible Conventional Control Panel D Description H (mm) W (mm) D (mm) Flush mounted Surface mounted Weatherproof WARNING: Do NOT use high voltage testers if ANY equipment is connected to the system. Screen (Earth) must be continuous along entire length of cable Installation 1. Surface callpoint has standard rear BESA fixing facilities. In addition, back box can accept top or bottom surface entry cables. Surface callpoint can also be flush mounted. 2. Callpoint has test facility via special test key to prevent unauthorised operation. 3. Insertion of test key for test purposes and for cover removal is at bottom of callpoint to facilitate ease of access when mounted next to door architrave. 4. Test key is dual function, used to test callpoint operation by simulating activation and also to allow removal of clip on cover to gain access to element. 5. Element is held in place by clip on self locking cover which can only be removed by use of a special tool (callpoint test key). 6. Separate zone in and zone out terminals are provided for all connections. 7. Surface/flush callpoints are IP21C, weatherproof is IP66. User interface 1. To enable quick and simple installation, callpoints use a fast fit self locking clip on front cover which is very simple to fit, but once in place, can only be removed by use of a special key (supplied). 2. Callpoint is triggered by pressing against the element. Catalogue numbers Description Callpoint, surface/flush Callpoint, weatherproof Protective hinged cover Spacer plates (pack of 10) Recessing bezels (pack of 10) Resettable element kit (pack of 10) Spare break glasses (pack of 5) Callpoint keys (pack of 10) EF201BWCP EF203BWCPWP CXPC MBGSP MBGBEZ MBGREKIT FX5G MFBGKEY3

Industries. As a premier global manufacturing company, we believe that great brands are

Industries. As a premier global manufacturing company, we believe that great brands are JSB Fire Systems ONE COOPER Every day, thousands of people all over the world use products made by Cooper Industries. As a premier global manufacturing company, we believe that great brands are built on

More information

Eaton is a global leader with expertise in:

Eaton is a global leader with expertise in: JSB Fire Systems P o w e ring business worldwide As a global l diversified power management company, we help customers worldwide manage the power n e e d e dfor buildings, aircraft, trucks, cars, machinery

More information

Cooper Industries (UK) Ltd

Cooper Industries (UK) Ltd Menvier Fire Systems Powering business worldwide As a globall diversified power management company, we help customers worldwide manage the power needed for buildings, aircraft, trucks, cars, machinery

More information

Conventional systems Product Name

Conventional systems Product Name Product Name 56 EATON - FIRE AN VOICE ALARM SYSTEMS CF-CC2556 January 2015 Contents Contents Conventional fire systems Panels FXP4000 series panel 58 FXP5000 series panel 60 evices etectors and indicators

More information

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual BiWire Flexi BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual Contents Contents 1. INTRODUCTION... 4 1.1 Purpose...4 2. THE BIWIRE FLEXI FIRE DETECTION & ALARM

More information

Conventional Fire Detection

Conventional Fire Detection SECTI 4: page 1 Section 4: Conventional Fire Detection Contents System Architecture Control Panel Automatic & Manual Detection Manual Call Points Smoke Detectors Heat Detectors Beam Smoke Detectors Duct

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

Fire Product Catalog

Fire Product Catalog Additional Expansion Modules Fire Product Catalog CLEVER FIRE SOLUTIONS MA 1000 / Analog Addressable Fire Alarm Panel 1 Military Industry Public Buildings Industrial & Commercial Company Profile We are

More information

Xenex Conventional Fire Detection & Alarm System

Xenex Conventional Fire Detection & Alarm System SECTI 4: page 1 Section 4: Xenex Conventional Fire Detection & Alarm System SECTI 4: page 3 Xenex system architecture Beam Transmitter Beam Receiver End of Line Call Point Smoke Detector Smoke Detector

More information

The complete conventional fire warning system

The complete conventional fire warning system The complete conventional fire warning system www.espuk.com MAG2P 2 Zone Fire Panel 2 programmable zones Active end of line monitoring and head removal 30 fire detectors per zone Unlimited number of call

More information

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Contents Contents 1. INTRODUCTION... 3 1.1 Purpose...3 1.2 Definitions....3 Premises Management...

More information

Fire Signalling. Signalling Solutions

Fire Signalling. Signalling Solutions Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

Addressable and Conventional Fire Protection

Addressable and Conventional Fire Protection Addressable and Conventional Fire Protection Simply reliable F I R E P R O T E C T I O N The MAGPro and Fireline systems has been created to balance performance, reliability and aesthetics whilst being

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

4 wire conventional alarm system

4 wire conventional alarm system Scimitar 4 wire conventional alarm system from Channel Safety Systems Scimitar 4 wire conventional alarm system The Scimitar Fire Alarm Control System is a comprehensive range of high specification conventional

More information

Emergi-Lite Orbis detectors

Emergi-Lite Orbis detectors Emergi-Lite Orbis detectors Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofire systems. Non-addressable (conventional) smoke and heat sensors respond

More information

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices. FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001

More information

MINERVA MZX125 Digital Addressable Fire Detection System

MINERVA MZX125 Digital Addressable Fire Detection System DATASHEET MINERVA MZX125 Digital Addressable Fire Detection System The Minerva MZX125 is a highly featured digital addressable panel with a comprehensive but easy to operate user interface. The system

More information

Conventional Smoke Detectors KFAPO

Conventional Smoke Detectors KFAPO Kingfisher Company, inc. Conventional Smoke Detectors KFAPO Features: Wide operating voltage, 9-33 VDC Advanced electronic technology Flashing LED Magnetic test switch Proven detection performance Designed

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

ELECTRONIC SOUNDER STROBE Model : AVD-C407

ELECTRONIC SOUNDER STROBE Model : AVD-C407 ELECTRONIC SOUNDER STROBE Model : AVD-C407 MULTRON range of combination Electronic Sounders with Strobe Lights are designed to complement our Fire Alarm products both technically and aesthetically as an

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

Sita200plus. 200detectors. Single loop analogue addressable System

Sita200plus. 200detectors. Single loop analogue addressable System Single loop analogue addressable System Fast short circuit isolator in every device 15 combinations of smoke & heat detection modes Loop length up to 2km long with spurs INTELLIGENT FIRE TECHNOLOGY A D

More information

Overview. Wireless Overview QLD NSW VIC Fundamentals. Operation. Features.

Overview. Wireless Overview QLD NSW VIC Fundamentals. Operation. Features. Wireless Overview www.incitefire.com.au Overview Fundamentals FIREwave is a wireless based family of products which is fully integrated into Hochiki s renowned ESP intelligent hardwired system. This seamless

More information

Conventional Audible Visual Range

Conventional Audible Visual Range Conventional Audible Visual Range Visual Devices Non-Addressable Audible Visual Devices Base Sounder Honeywell s conventional audible visual devices operate over a wide input voltage range of 9 to 33VDC

More information

MINERVA MX. 800 Series Ancillary Equipment

MINERVA MX. 800 Series Ancillary Equipment An extensive range of ancillary modules has been specifically designed for use with the MX range of Fire Controllers. The 800 range of ancillary modules provide the MX Fire Controller with a wide degree

More information

Fire Signalling. Signalling Solutions

Fire Signalling. Signalling Solutions Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.

More information

four Vigilon Compact Analogue Addressable Fire Detection & Alarm System 4/1

four Vigilon Compact Analogue Addressable Fire Detection & Alarm System 4/1 four Vigilon Compact Analogue Addressable Fire Detection & Alarm System 4/1 ANALOGUE FIRE DETECTION VIGILON COMPACT FEATURES & BENEFITS four Keep it Simple All Vigilon devices connect onto the same 2

More information

Fire Signalling. Signalling Solutions

Fire Signalling. Signalling Solutions Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.

More information

Touch Screen 1 loop Addressable Fire Alarm Panel

Touch Screen 1 loop Addressable Fire Alarm Panel evolution 1 Touch Screen 1 loop Addressable Fire Alarm Panel The evolution 1 control panel offers complete compatibility with the award winning range of Nittan evolution detection and alarm devices and

More information

Opal TM AV Devices. Data Sheet. Benefits

Opal TM AV Devices. Data Sheet. Benefits Opal TM AV Devices Data Sheet Notifier s Opal AV (Audio Visual) range is designed to alert building occupants of an emergency. The Opal AV range of analogue addressable, loop powered, audible and visual

More information

Cooper Fire Systems. UL Listed Range

Cooper Fire Systems. UL Listed Range Cooper Fire Systems UL Listed Range UL Listed Fire Detection Equipment SIGNALING 4AC5 FIRE ALARM EQUIPMENT Underwriters Laboratories Inc. (UL) is an independent product safety certification organization,

More information

VIMPEX BS Evacuation. Fire Alarms EN Banshee. Beacons. FlashDome. Electronic Sounders. Audible Alarm

VIMPEX BS Evacuation. Fire Alarms EN Banshee. Beacons. FlashDome. Electronic Sounders. Audible Alarm VIMPEX Sounder Range Fire Alarms Banshee Electronic Sounders FlashDome EN 54-3 Evacuation Audible Alarm BS 5839-1 Beacons The range of sounders, beacons, sounder beacons and accessories represents the

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

Wireless Fire & Security Solutions. Fire Product Showcase

Wireless Fire & Security Solutions. Fire Product Showcase Wireless Fire & Security Solutions Fire Product Showcase 2 Contents Contents 3 Product Overview 4-5 Control Panels 6-8 Control Panel Accessories / Power Supplies 9-10 Wireless Infrastructure 11-12 Aerials

More information

Door Release Power Supply

Door Release Power Supply www.protectingpeople.co.uk Door Release Power Supply Engineer / Installation Manual Document: VI55.1 Protecting People Printed : 04/03/2004-1 - Ventcroft Ltd Door Release Power Supply Engineer / Installation

More information

intelligent solutions

intelligent solutions Alco is one of the leading intelligent solution providers of Fire Detection System. Security System and Public Addressing System in the United States of America. Based in California since 1992, we have

More information

INPUT / OUTPUT MINI MODULES

INPUT / OUTPUT MINI MODULES INPUT / OUTPUT MINI MODULES APPLICATION The Addressable Control and Monitor mini modules are the latest technology for a loop powered module. Installed on the same loop with other devices such as detectors

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

Fire. DF6000 Control Panel. User Manual. Assessed to: ISO 9001:2000 Certification number: 714h/01

Fire. DF6000 Control Panel. User Manual. Assessed to: ISO 9001:2000 Certification number: 714h/01 Fire DF6000 Control Panel User Manual Assessed to: ISO 9001:2000 Certification number: 714h/01 Approved to: EN54-2 1997 & A1;2006 EN54-4:1997 & A1;2002 A2:2006 Document Drg Ref: PR200-04-513-15 Marketing

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

MINERVA MZX125. Digital Addressable Fire Detection System

MINERVA MZX125. Digital Addressable Fire Detection System A C C E S S C O N T R O L C C T V E A S R F I D F I R E P R O T E C T I O N I N T R U D E R A L A R M S DATA SHEET MINERVA MZX125 Digital Addressable Fire Detection System Features: Long term service and

More information

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation Sinteso Cerberus PRO FDA241, FDA221 ASD Aspirating smoke detector Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation Patented technology Early

More information

Analogue addressable devices

Analogue addressable devices Apollo XP95 Analogue addressable devices from Channel Safety Systems Apollo XP95 Analogue addressable devices The XP95 range of analogue addressable fire detectors is advanced in design, improved in performance

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

LF-4000 Series Conventional Fire Alarm Control Unit

LF-4000 Series Conventional Fire Alarm Control Unit LF-4000 Series Conventional Fire Alarm Control Unit Features: 1 to 36 Zone Control Panels Control Key Switch Easy Push Button Control Switches Zone Circuit Monitoring for Open and Short Sounder Circuit

More information

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules Application The Addressable Control and Monitor mini modules are the latest technology for a loop powered module. Installed on the same loop with other devices such as detectors and manual call points,

More information

Installation, Commissioning & Operating Manual

Installation, Commissioning & Operating Manual EN54 APPROVED 2-4 ZONE ALARMSENSE CONTROL PANEL Installation, Commissioning & Operating Manual 810a/05 Approved Document UI-ALS-01 Issue 2.0 0832 Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley

More information

CONTENTS NBM-06 Bell (6") Page 1

CONTENTS NBM-06 Bell (6) Page 1 CONTENTS NBM-06 Bell (6") - - - Page 1 NBM-08 Bell (8") - - - Page 1 LFB-24 Sounder Banshee - Page 2 VCT--NT Base Version Sounder Page 2 VCT--NT Wall Version Sounder Page 2 VRS1-R or W Bedhead Sounder

More information

C E R T I F I C AT LPCB I O N B O A R D P R E V E N T L O S S. Cooper Fire Systems

C E R T I F I C AT LPCB I O N B O A R D P R E V E N T L O S S. Cooper Fire Systems P R E V E N T L O S S I O N C E R T I F I C AT LPCB B O A R D I O N Cooper Fire Systems ONE COOPER Every day, thousands of people all over the world use products made by Cooper Industries. As a premier

More information

Intelligent addressable fire alarm control panel

Intelligent addressable fire alarm control panel Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity

More information

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range Fire Detection MINERVA Marine MX T2000 Panel Range Features: Enhances fire detection and eliminates unwanted alarms using fuzzy logic Assists fire fighting and training by providing on-screen risk management

More information

Protec. Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network. Fire Detection - Addressable Protec Protec Fire Detection Pty Ltd Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE CAUTION

More information

Opal TM AV Devices. Data Sheet. Benefits

Opal TM AV Devices. Data Sheet. Benefits Opal TM AV Devices Data Sheet Notifier s Opal AV (Audio Visual) range is designed to alert building occupants of an emergency. The Opal AV range of analogue addressable, loop powered, audible and visual

More information

Series 65 Product Guide MAN 3036

Series 65 Product Guide MAN 3036 Series 65 Product Guide MAN 3036 TABLE OF CONTENTS Page No. 1 Ionisation Smoke Detector... 1 1.1 Operating Principles:... 1 1.2 Product Codes... 2 1.3 Integrating Version:... 2 1.4 Options:... 2 1.5 Safety

More information

Wireless Fire & Security Solutions. Fire Product Showcase

Wireless Fire & Security Solutions. Fire Product Showcase Wireless Fire & Security Solutions Fire Product Showcase 2 Contents Contents 3 FireCell Overview 4-5 Taktis Control Panel Overview 6 Taktis Control Panels & Accessories 7-8 Syncro AS Control Panel Overview

More information

Evolution Analogue Addressable Fire System

Evolution Analogue Addressable Fire System Addressable Fire System optimum fire safety systems solutions High speed FSK protocol, uniquely resistant to noise Up to 254 addresses per loop for flexible system design Built to exceptional marine standards

More information

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual VoCALL - CFVCC5 Compact 5 Line Exchange Unit Installation & Commissioning Manual Introduction A VoCALL Emergency Voice Communications System (EVCS) is a fixed, secure, bi-directional, full duplex voice

More information

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

FIREBETA EXTINGUISHING CONTROL PANEL (ECP) F I R E D E T E C T I O N A N D C O N T R O L FIREBETA EXTINGUISHING CONTROL PANEL (ECP) Three versions: 2 areas of detection and 1 area extinguishing 4 areas of detection and 1 area extinguishing 4 areas

More information

DF6000 INSTALLATION MANUAL. Document Drg Ref PR CPR F1141. Assessed to ISO 9001:2008 Certification number 714w/01

DF6000 INSTALLATION MANUAL. Document Drg Ref PR CPR F1141. Assessed to ISO 9001:2008 Certification number 714w/01 DF6 INSTALLATION MANUAL 9 832 CPR F1141 Eaton Electrical Systems Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB TEL: +44 () 132 321541 FAX: +44 () 132 3322 QUALITY MANAGEMENT Assessed to ISO

More information

Conventional Leaflets

Conventional Leaflets Conventional Leaflets Panels Last updated October 1999 Make leaflet selection by clicking on appropriate bookmark Return to Menu Installation and Basic Commissioning guide for the range of 1,2,4 and 8

More information

Fire detection and alarm system Installation instructions

Fire detection and alarm system Installation instructions Fire detection and alarm system Installation instructions Installation instructions Table of Contents Table of Contents ------------------2 Preface -----------------------3 Associated Documents 3 Conventions

More information

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0)

More information

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4 FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT -201-7-3 Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

CONVENTIONAL >FIRE DETECTION C400 SYSTEM FIRE DETECTION

CONVENTIONAL >FIRE DETECTION C400 SYSTEM FIRE DETECTION FIRE DETECTION >FIRE DETECTION CONVENTIONAL C400 SYSTEM FIRE DETECTION EFFICIENT AND MODULAR Elkron fire detection systems protect your business and grow with it Elkron's conventional fire detection range

More information

Protec. Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network

Protec. Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network Protec Protec Fire Detection plc Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE

More information

CF3000 INSTALLATION MANUAL. Document Drg Ref PR CPR F1140. Assessed to ISO 9001:2008 Certification number 714w/01

CF3000 INSTALLATION MANUAL. Document Drg Ref PR CPR F1140. Assessed to ISO 9001:2008 Certification number 714w/01 CF3 INSTALLATION MANUAL 9 832 CPR F114 Eaton Electrical Systems Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB TEL: +44 () 132 321541 FAX: +44 () 132 3322 QUALITY MANAGEMENT Assessed to ISO 91:28

More information

An introduction to... Sigma

An introduction to... Sigma An introduction to... Sigma XT+ Sigma XT+ Overview The Sigma XT+ 21000 series are the latest additions to the Sigma family of control equipment from Kentec Electronics Limited. The Sigma XT+ range combines

More information

good things in small packages

good things in small packages FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with

More information

Precept Marine Control Panel Application Guide

Precept Marine Control Panel Application Guide Precept Marine Control Panel Application Guide Contents Page 1.0 Cabinet Specifications 2 2.0 Panel Hardware Specifications 5 3.0 Panel Configuration 8 4.0 Technical Specifications 8 5.0 Battery Sizes

More information

AP200 SERIES INTELLIGENT ALARM DEVICES

AP200 SERIES INTELLIGENT ALARM DEVICES Tech Data Sheet D017GB1 Fire Detection /01 AP00 SERIES INTELLIGENT ALARM DEVICES Intelligent AP00 series alarm devices for FX NET fire detection system The intelligent AP00 series alarm devices are used

More information

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES Prem1er EVACS16 VOICE ALARM CONTROL PANEL 4 16 ZONES Installation Manual Approved Document No: GLT.MAN-141 PAGE 1 INDEX INDEX... 2 Summary... 3 Safety information & use of this manual... 5 Installation

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

CONVENTIONAL AUDIBLE VISUAL

CONVENTIONAL AUDIBLE VISUAL Fast Installation, Safe Evacuation CONVENTIONAL AUDIBLE VISUAL www.kac.co.uk Setting the Standard with ENscape EN54-23 and how it affects you EN54-23 is a new European standard for Visual Alarm Devices

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax:

More information

Our technology, your peace-of-mind. Product list

Our technology, your peace-of-mind. Product list Our technology, your peace-of-mind Product list 2018 Detnov Security started its activity in 2007 in Barcelona. We are a company specialized in the development and manufacture of fire alarm systems for

More information

Evacuate everyone Sonos Pulse & Nexus Pulse

Evacuate everyone Sonos Pulse & Nexus Pulse Evacuate everyone Sonos Pulse & Nexus Pulse Available through distribution: www.discountfiresupplies.co.uk Tel: 01792 452 700 EN54-23 Fire Beacons In a fire, everyone matters. Sonos Pulse and Nexus Pulse

More information

Intelligent Single Loop Fire Alarm Control Panel

Intelligent Single Loop Fire Alarm Control Panel Intelligent Single Loop Fire Alarm Control Panel The CAX-CTL-1L Intelligent Single Loop Fire Alarm Control Panel is a member of the industry leading Axis AX Series Intelligent Fre Alarm Control Panels

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF

More information

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note Product Overview: The Pertronic F4 Remote LED Mimic / Aux Relay Module F4-RMAX is an optional extra for the Pertronic F4 conventional 4-zone fire alarm panel. This board enables the fire alarm panel to

More information

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

EN54-23 Beacons & Sounder Beacons

EN54-23 Beacons & Sounder Beacons EN54-23 Beacons & Sounder Beacons In a fire, everyone matters. Sonos Pulse and Nexus Pulse fire beacons ensure that all personnel are notified of fire emergencies. With Pulse Alert Technology, buildings

More information

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards. 4100S The operation and functions described in this manual are available from Software Version 4100S-023-013 onwards. Specifications: Item Specification Details Enclosure Steel IP30 Dimensions H x W x

More information

UL Systems. UL intelligent addressable systems Product Name

UL Systems. UL intelligent addressable systems Product Name Product Name UL Systems Underwriters Laboratories Inc. (UL) is an independent product safety certification organisation, established in 1894, to develop standards and test procedures for products, materials,

More information

2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL

2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL OM_FC_DUO-CEL_APP 2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL FIRE DETECTION/ALARM PANEL Application Guide PAGE 1 of

More information

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL CONTENTS 1. INTRODUCTION. 3 1.1 HANDLING THE PCBS 1.2 USING THIS MANUAL

More information

EMERGENCY LIGHTING SYSTEM

EMERGENCY LIGHTING SYSTEM EMERGENCY LIGHTING SYSTEM 1300 INCITE www.incitefire.com.au PRODUCT CATALOGUE EXIT-EMERGENCY LIGHTING AN EXTRA LOW VOLTAGE EXIT & EMERGENCY LIGHTING SYSTEM FIREscape is a revolutionary emergency lighting

More information

7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management

7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management Reyrolle Protection Devices 7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management 7XG3130 - RA30 Optical Arc Fault Sensor Features Compact rugged design One or two optical detectors High speed arc

More information

1) This manual covers 4400, 5400 and 6400 fire alarm systems. The differences are described in the appropriate sections.

1) This manual covers 4400, 5400 and 6400 fire alarm systems. The differences are described in the appropriate sections. ISSUES ISSUE DATE DETAILS OF CHANGE CHANGED BY 1 16/02/00 ORIGINAL ISSUE - 2 16/01/01 TABLES 2 & 3 UPDATED, ADDED TABLE 4 PWD 3 12/09/01 ADDITIONAL INFORMATION PWD 4 29/11/02 TABLES 2, 3 & 4 UPDATED &

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

Accessible Toilet Alarm

Accessible Toilet Alarm N C 9 5 1 D E S I G N & I N S T A L L A T I O N G U I D E Accessible Toilet Alarm This equipment must be installed and maintained by a suitably skilled and technically competent person. This document provides

More information

Industrial Signalling

Industrial Signalling Industrial Signalling Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place. Product Range

More information