Test report. NanoPhos coating system EPR and EEN. Name of client: NanoPhos SA. Date: Pages: 5 Encl.: 1 Ref: BP / KTO
|
|
- Loraine Barton
- 5 years ago
- Views:
Transcription
1 Test report NanoPhos coating system EPR and EEN Name of client: NanoPhos SA File no.: PFB10173A Date: Pages: 5 Encl.: 1 Ref: BP / KTO Danish Institute of Fire and Security Technology Jernholmen 12, DK-2650 Hvidovre Phone: dbi@dbi-net.dk Test Reg.no. 0012
2 Client information Client: Address: NanoPhos SA Technological & Science Park P.O. Box 519 Lavrio Greece The results relate only to the items tested. The test report should only be reproduced in extenso - in extracts only with a written agreement with this institute. Page 2 of 5
3 1. Product NanoPhos coating system: EPR (Epoxy Primer) and EEN (Enamel Epoxy) for steel. 2. Manufacturer The client is the manufacturer. 3. Test method The test specimens have been subjected to the standard fire test complying with the International Code for Application of Fire Test Procedures, 2010 Resolution MSC.307(88), 2010 FTP Code, Annex 1 Part 5: Test for surface flammability. Furthermore the test was carried out in accordance with the requirements of the Russian Maritime Register of Shipping, St. Petersburg, cf. Recognition Certificate of Testing Laboratory No valid until 19th September Sample DBI-Danish Institute of Fire and Security Technology received five test specimens of dimensions (length x width) 795 x 155 mm; thickness 3.35 mm. The specimens consisted of 3 mm thick steel sheets with white paint applied on one side. Weight per unit area: 23.9 kg/m 2 as determined by weight and measurements of the test specimens. Material specification (stated by the client) NanoPhos Coating System: EPR (EPOXY PRIMER) and EEN (ENAMEL EPOXY) Total layer thickness: 180 µm. Primer: 1 x 100 µm; Enamel: 1 x 80 µm. Further material specification was given by the client and has been filed at DBI under the file number below. 5. Conditioning The specimens were conditioned in accordance with paragraph 7.7 of appendix 1 to part 5. Page 3 of 5
4 6. Test results Date of test: Pilot flame: Impinging propane/air. No. of test runs: 3 The test results are shown in full detail in enclosure 1. Derived fire characteristics Test No Average Duration of test (s) Not applicable CFE (kw/m 2 ) Q sb (MJ/m 2 ) Q t (MJ) q p (kw) Burning droplets No Observations: None CFE: Q sb : Q t : q p : Critical flux at extinguishment Heat for sustained burning Total heat release Peak heat release rate Page 4 of 5
5 7. Conclusion The investigated sample of paint designated NanoPhos coating system EPR and EEN applied on steel in respectively 1 x 100 m and 1 x 80 µm (layer thickness) fulfils the surface flammability criteria for bulkhead, wall and ceiling linings as listed in IMO 2010 FTP Code Part 5 and is therefore considered to meet the requirement for low flame-spread in compliance with the relevant regulations in chapter II - 2 of the Convention. 8. Statement As the NanoPhos coating system EPR and EEN as applied, has a total heat release (Q t ) of not more than 0.2 MJ and a peak heat rate (q p ) of not more than 1.0 kw, it is considered to comply with the requirements of part 2 without further testing, cf. paragraph 2.7 of appendix 4 to part 5. (Reference to IMO 2010 FTP Code, paragraph 2.2 of annex 2.) 9. Note The test results relate only to the behavior of the test specimens of a product under the particular conditions of the test; they are not intended to be the sole criterion for assessing the potential fire hazard of the product in use. Ken Olesen B.Sc.Chem.Eng.Hon. Bjørn Petersen Laboratory Technician NanoPhos SA Technological & Science Park P.O. Box 519 Lavrio Greece Page 5 of 5
6 FIRE TEST PROCEDURES FOR SURFACE FLAMMABILITY OF BULKHEAD, CEILING, DECK FINISH MATERIALS AND PRIMARY DECK COVERINGS. Sponsor: NanoPhos SA Date of test: Product: Coating system EPR and EEN Substrate: Steel sheet 3 mm Layer thickness of product: Primer: 100 m Enamel: 80 m Test results Test 1: Time to ignition : 155 s Time to flameout : 502 s Extent of burn (mm) : 235 Critical flux at extinguishment (kw/m²) : Heat for ignition (MJ/m²) : Average heat for sustained burning (MJ/m²) : Peak heat release rate (kw) : 0.82 Time to peak heat release rate : 362 s Total heat release (MJ) : Test 2: Time to ignition : 137 s Time to flameout : 476 s Extent of burn (mm) : 220 Critical flux at extinguishment (kw/m²) : Heat for ignition (MJ/m²) : Average heat for sustained burning (MJ/m²) : Peak heat release rate (kw) : 0.79 Time to peak heat release rate : 637 s Total heat release (MJ) : Test 3: Time to ignition : 160 s Time to flameout : 538 s Extent of burn (mm) : 230 Critical flux at extinguishment (kw/m²) : Heat for ignition (MJ/m²) : Average heat for sustained burning (MJ/m²) : Peak heat release rate (kw) : 0.82 Time to peak heat release rate : 713 s Total heat release (MJ) : 0.16 Surface flammability criteria, 2010 FTP Code, Annex 1, part 5 Bulkhead, wall and ceiling linings Floor coverings / Prim. deck coverings CFE (kw/m 2 ) Q sb (MJ/m 2 ) Q t (MJ) Q p (kw) CFE (kw/m 2 ) Q sb (MJ/m 2 ) Q t (MJ) Q p (kw) Burning droplets: None 10 None Enclosure 1 of 1
Test Report Reg.no 12.
cd?l DANAK ~ Test Report Reg.no 12. Macroplast UK 8303 B60 Fileno: PFl 7707b Seda! No: 9474 Ref: BP/MPA Ene!.: 7 Henkel KGaA The results relate only to the items tested. The test report should only be
More informationAdditional Reaction to Fire Classification Report
Additional Reaction to Fire Classification Report MDF Plate Client: Teknos A/S File no.: PCA10461Aad Date: 2018-01-09 Pages: 5 Encl.: 3 Ref: MPA / JAG Notified Body No. 0845 Danish Institute of Fire and
More informationTest Report: ICL/H18/9039 Rev 1
Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk
More informationASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process
ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process 2010 IMO FTP Code Revisions Parts 2, 5, 7, 8, 9 & 10 Presented by: Juan Manuel Flores, P.E. Date:
More informationForbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.
Return address: P.O. box 337, 7500 AH Enschede, TNO Centre for Textile Research Ariënsplein 3 7511 JX ENSCHEDE Forbo Flooring Attn. Mr. A. Tijhof Postbus 13 1560 AA Krommenie Report Sponsor : Contractor,
More informationIMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:
IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2 Smoke & Toxicity Test WF Report Number: 166040 Date: 13 th August 2007 Test Sponsor: Fiba Tech Industries Ltd. 0249 Page 2 of 13 Bodycote warringtonfire
More informationIMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES
INTERNATIONAL MARITIME ORGANIZATION E IMO SUB-COMMITTEE ON FIRE PROTECTION 46th session Agenda item 5 FP 46/5 30 November 2001 Original: ENGLISH UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED
More informationBCTC CARPET TECHNICAL CENTRE
Wira House West Park Ring Road Leeds, LS16 6QL Tel: +44 (0)113 259 1999 Fax: +44 (0)113 278 0306 Web: http://www.bttg.co.uk/bctc Email: CSLeeds@bttg.co.uk 7 September 2010 Page 1 of 7 Client: Rectory Farm
More informationIMO Resolution MSC 61(67): Annex 1: Part 2
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IMO Resolution MSC 61(67): Annex 1: Part
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com CLASSIFICATION CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE
More informationIMO COMPREHENSIVE REVIEW OF THE FIRE TEST PROCEDURES CODE
INTERNATIONAL MARITIME ORGANIZATION E IMO SUB-COMMITTEE ON FIRE PROTECTION 50th session Agenda item 10 FP 50/10/1 25 October 2005 Original: ENGLISH COMPREHENSIVE REVIEW OF THE FIRE TEST PROCEDURES CODE
More informationTest Report: ICL/CR15/11/087
Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationBS EN ISO : 2010
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationContact person Date Reference Page Richard Johansson P (2) Fire Research
issued by an Accredited Testing Laboratory Contact person Richard Johansson 215-8-13 5P4413 1 (2) Fire Research +46 1 516 56 75 richard.johansson@sp.se 12 ISO/IEC 1725 Sklejka-Pisz Paged S.A Ul. kwiatowa
More informationBS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2002 Fire Tests For
More informationBS EN ISO : 2010
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Fire Tests For Determination Of The Burning
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationBS EN ISO : 2010
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination
More informationC-01 FIRE DECKS AND BULKHEADS
Guideline No.: C-01(201510) C-01 FIRE DECKS AND BULKHEADS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification no.
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Sponsor Prepared by P.O. Box 118 NL-2394 ZG HAZERSWOUDE Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280
More informationRESOLUTION MSC.101(73) (adopted on 5 December 2000) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR APPLICATION OF FIRE TEST PROCEDURES
RESOLUTION MSC.101(73) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR APPLICATION OF FIRE TEST PROCEDURES THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationAnalysis Report
Prestige Carpets bvba Dhr. Dirk Santens Klein Frankrijk 38 9600 RONSE Your notice of Your reference Date 19-06-2013 24-07-2013 Required tests : Identification number T1309624 Information given by the client
More informationTFI Report Classification
TFI Report Classification of the Reaction to Fire according to EN 13501-1:2010 Customer Stuttgarter Straße 75 74321 Bietigheim-Bissingen GERMANY Product resilient floor covering Product 1: Scala 55 Connect
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationCERTIFICATE OF FIRE APPROVAL
LR427.201.12 CERTIFICATE OF FIRE APPROVAL This is to certify that The product detailed below will be accepted f compliance with the applicable Lloyd s Register Rules and Regulations and with the International
More information1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c
1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire
More informationGlobal Requirements for the Fire Protection of Ships. Dr Janet Murrell Warrington Certification Ltd
Global Requirements for the Fire Protection of Ships Dr Janet Murrell Warrington Certification Ltd Arch Timber 3 rd Castleford June 2011 International Maritime Organisation (IMO) International Maritime
More informationRESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO
MSC 84/24/Add.2 RESOLUTION MSC.265(84) OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization
More informationEN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com EN 45545-2: 2013 Summary Test Report Requirement
More informationEU Declaration of Conformity
...Innovative liquid vaporizing and gas mixing solutions EU Declaration of Conformity WE, Algas-SDI 151 South Michigan Street Seattle, WA 98108 USA Declare, solely under own responsibility, that the product
More informationBS EN : 2001 & IEC :2000
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 60695-2-11: 2001 & IEC 60695-2-11:2000
More informationBenefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.
Benefiting Government, Industry and the Public Through Innovative Science and Technology Barry L. Badders, Jr. P.E. 7 December 2011 Part 1 Non-Combustibility Test Part 3 Test for A, B,, and F Class Divisions
More informationTFI Report Reaction to fire test
TFI Report 450740-07 Reaction to fire test For the classification according to EN 13501-1:2010 Customer GÜLSEVEN HALI GÜLSEVEN TEKSTIL KIMYA GIDA SAN. TIC. LTD. STI Ahi Evran Sanayi Sitesi Istiklal Caddesi
More informationCLASSIFICATION REPORT
CLASSIFICATION REPORT NUMBER 251.C.1804.020.EN.01 Work sheet: 21801003 DATE OF ISSUE April 10 th, 2018 NOTIFIED BODY PAGE TEST SPECIMEN CONCERNING TO APPLICANT DATE/S OF TEST AUTORIZED SIGNATORIES Notified
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Sponsor Prepared by P.O. Box 70 NL-5750 AB DEURNE Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280 CB
More informationNotified Body No.: 0575 G U A D N L. SJq
ONV.GL XAMINA i ION C.R i 11-ICA Certificate No: MEDB00000AT Application of: Council Directive 96/98/EC of 20 December 1996 an Marine Equipment as amended by directive 2014/93/EU, issued as "Forskrift
More informationTech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5
INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation Testing Protocol
More informationTest on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in
INFRASTRUCTURE TECHNOLOGIES Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in accordance with AS/NZS 3837:1998 Fire Testing Report Author: Heherson Alarde Report Number:
More informationei DG UV Test EC-Type Examination (Module B) Certificate
European notified body Identification number 0736 ei DG UV Test Prüf- und Zertifizierungsstelle BG Verkehr Dienststelle Schiffssicherheit EC-Type Examination (Module B) Certificate Certificate No. 100.185
More informationREACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013
SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT No. RA140063 ACCORDING TO THE EUROPEAN STANDARD NF EN 135011+A1:2013 Notification by the French Government
More informationIntertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008
Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,
More informationBS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited
BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 153420 Date: 28 th April 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 153420 BS 476: Part
More informationAdditional reaction to fire classification report No H
Additional reaction to fire classification report. 12700H Owner of the additional classification report Antalis International 8 Rue de Seine 92517 Boulogne Billancourt Cedex France Introduction This additional
More informationPRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona
Architectural Testing PRODUCT PERFORMANCE TEST REPORT Report No.: D7226.01-121-24 Test Date: May 29, 2014 Rendered to: Natural Light Energy Systems Phoenix, Arizona PRODUCT TYPE: Tubular Daylight Device
More informationTFI Report Classification
TFI Report Classification of the Reaction to Fire according to EN 13501-1:2010 Customer Unilin bvba, Division Flooring Ooigemstraat 3 8710 Wielsbeke BELGIUM Product wall covering Wall covering This report
More informationJuly 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798
July 22, 2009 Stewart Audio Inc Brian Mccormick Po Box 4058 Mountain View, CA 94040 Our Reference: Subject: File SV17764 / Project 09CA34798 UL Standard 2043, Third Edition "Fire for Heat and Visible Smoke
More informationREACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013
SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT ACCORDING TO THE EUROPEAN STANDARD NF EN 13501-1+A1:2013 Notification by the French Government to the European
More informationAbrasion Resistance of Fluoropolymer and polyester Coatings
Abrasion Resistance of Fluoropolymer and polyester Coatings British Standards British Standard 476 refers to fire tests on building materials and structures. The parts of this standard that are of most
More informationDRY CHEMICAL POWDER SYSTEM REQUIREMENTS TO COMPLY WITH THE LATEST IMO IGC CODE AND EUROPEAN COUNCIL CLARIFICATIONS
DRY CHEMICAL POWDER SYSTEM REQUIREMENTS TO COMPLY WITH THE LATEST IMO IGC CODE AND EUROPEAN COUNCIL CLARIFICATIONS Tested down to Tested in long pipes 19 Published 18 November, 2016 Joe Blogs, Survitec
More information4, DG UV Test. EC-Type Examination (Module B) Certificate. A.1/3.11 a - "A" Class divisions, fire integrity
European notified body Identification number 0736 4, DG UV Test Prüf- und Zertifizierungsstelle BG Verkehr Dienststelle Schiffssicherheit EC-Type Examination (Module B) Certificate Certificate No. 100.190
More informationReport VNLF Test Report
Report VNLF 081158.1 Test Report Applicant KLEEN-TEX Industries in Europa GmbH Münchner Straße 21 6330-Kufstein Austria Reference Mrs. Antje Schlegel Application Determination ofthe burning behaviour according
More informationPERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome
PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA
More informationBS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests
More informationApplicable international instruments for construction, performance and testing requirements 1
Product Coverage For Mutual Recognition Life saving appliances Lifebuoy self-activating smoke signals (pyrotechnics) Rocket parachute flares (pyrotechnics) Hand flares (pyrotechnics) Buoyant smoke signals
More informationTEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota
Architectural Testing TEST REPORT Report No.: D7913.05-121-24 Rendered to: 3M COMPANY St. Paul, Minnesota PRODUCT TYPE: Window Film SERIES/MODEL: 3M Scotchshield Ultra 800 TEST METHOD: ASTM E 84-11a, Standard
More informationBS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited
BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 158117 Date: 13 th October 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 158117 BS 476:
More informationREACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013
SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT ACCORDING TO THE EUROPEAN STANDARD NF EN 13501-1+A1:2013 Notification by the French Government to the European
More informationAnalysis Report
Forbo Flooring Coral nv Dhr. Jan van Galen Postbus 17 1560 AA KROMMENIE Nederland Your notice of Your reference Date 08-02-2016 23-02-2016 Analysis Report 16.00634.08 Required tests : Identification number
More informationInternational Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.
International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.800(19) Magnus Arvidson SP Fire Research SP Technical Research Institute
More informationVescom bv Sint-Jozefstraat AV Deurne Nederland
Page 1/5 Vescom bv Sint-Jozefstraat 20 5753 AV Deurne Nederland Your notice of Your reference Date 25-09-2017 20-10-2017 Required tests : IMO - 2010 FTP Code Annex 1 - Fire test procedures - Part 8 IMO
More informationCPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation
CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation Speaker: Dr. L. K. Sze, Lipmann Technical Director of Date: 23 January, 2018 Disclaimer:
More informationNew European Fire Testing Classification for Construction Products
New European Fire Testing Classification for Construction Products THE BENCHMARK IN FIRE TESTING EU Construction Products Directive The EU Construction Products Directive (CPD), is the basis of construction
More informationBS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy
BS 476: Part 7: 1997 on K-Flex IN Clad Foil Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, 36 20877 RONCELLO (MB) Italy 30 th October 2012 0578 Page 1 of 6 Prepared on behalf of BRE Global
More informationREACTION TO FIRE TESTS FOR BUILDING PRODUCTS DETERMINATION OF THE HEAT OF COMBUSTION ACCORDING TO STN EN ISO 1716: 2003
mgr. Dušan BERNÁT Fire and Research Institute Ministry of Interior of the Slovak Republic REACTION TO FIRE TESTS FOR BUILDING PRODUCTS DETERMINATION OF THE HEAT OF COMBUSTION ACCORDING TO STN EN ISO 1716:
More informationClassification of Fire Performance of Wall and Ceiling Lining Materials
Classification of Fire Performance of Wall and Ceiling Lining Materials Using the Method of Kokkala, Thomas and Karlsson Reference: Kokkala, M.A. Thomas, P.H. and Karlsson, B. Rate of Heat Release and
More informationReview Fire Test Report
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Review Fire Test Report Determination of
More informationBS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More information26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1007 26 June 2001 GUIDELINES FOR THE
More informationBS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 1716: 2010 Determination Of The
More informationGUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS
12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety
More informationBS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.
BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions WF Report Number: 147709 Test Sponsor: FTC - Fabbrica Trentina Conduttori
More informationWARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier
Page 1 of 27 Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Test Sponsor Saveguard (UK) Limited Warrington Fire Research Centre Ltd.,
More informationBS 476: Part 6: 1989+A1:2009
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 6: 1989+A1:2009 Method Of Test
More informationIEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IEC 60331-11-21 Method of test defined in
More informationTEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria
TEST REPORT Report No.: E6736.01-121-24 Test Date: May 6, 2015 Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria PRODUCT TYPE: Max Exterior F-Quality SERIES/MODEL: Décor. 0085 TEST METHOD:
More informationNF X : Parts 1, 2, 3, 4 & 5
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com NF X 10-702: Parts 1, 2, 3, 4 & 5 Fire test
More informationAnnex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005
Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D-PL-11035-03-00 according to DIN EN ISO/IEC 17025:2005 Period of validity: 25.10.2017 to 24.10.2022 Holder of certificate: DMT
More informationFull-scale test of fire detection in a facade using heat detection cable and flame detector
Report Full-scale test of fire detection in a facade using heat detection cable and flame detector Author: Kristian Hox RISE Fire Research RISE-rapport Full-scale test of fire detection in a facade using
More informationReaction to fire classification report No C-rev.1
Reaction to fire classification report. 17241C-rev.1 Owner of the classification report Distributor: Vescom bv Churchilllaan 10 Sint Jozefstraat 20 5705 BK Helmond 5750 AB Deurne The Netherlands The Netherlands
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More informationFirst Revision No. 6-NFPA [ Section No. 2.2 ]
Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon
More informationCAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?
CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? Marcelo M. Hirschler GBH International, USA ABSTRACT The results of three
More informationApproval of water mist systems in buildings
on Danish Guideline Approval of water mist systems in buildings Back ground Contents of the publication Introduction Water mist in buildings Classification test Risk classes Components Systems Installers
More informationCERTIFICATE OF APPROVAL No CF 5236 EMVER PAINTS INDUSTRIES LLC
CERTIFICATE OF APPROVAL No CF 5236 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Jebel Ali Industrial
More informationBS 476: Part 6: 1989+A1:2009
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 6: 1989+A1:2009 Method Of Test
More informationIMO FP 53 Report. Lloyd s Register report on the 53 rd session of IMO Fire Protection Sub-Committee. 16 th March, 2009
IMO FP 53 Report Lloyd s Register report on the 53 rd session of IMO Fire Protection Sub-Committee 16 th March, 2009 Hot topics: Consideration continues on inerting to prevent fire and explosion on small
More informationReaction to fire classification report No C
Reaction to fire classification report. 17911C Owner of the classification report Tapetex B.V. Distributor: Vescom bv Churchilllaan 10 Sint Jozefstraat 20 5705 BK Helmond 5750 AB Deurne The Netherlands
More informationRESOLUTION MSC.61(67) (adopted on 5 December 1996) ADOPTION OF THE INTERNATIONAL CODE FOR APPLICATION OF FIRE TEST PROCEDURES
RESOLUTION MSC.61(67) TIlE MARITIME SAFETY COMMITTEE. RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee. RECOGNIZING the need
More information26 June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1002 26 June 2001 GUIDELINES ON ALTERNATIVE
More informationStar Princess Safety Centre. Annex A
Star Princess Safety Centre Annex A Star Princess Safety Centre Star Princess has a highly automated system for managing ship emergencies. Sensors within the ship monitor the operation of key systems including
More informationRESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS
RESOLUTION MSC.292(87) THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee, NOTING resolution MSC.98(73)
More informationGuidance on the construction of CO 2 systems
Translation. Only the Danish document has legal validity. Guidance no. 9515 of 9 July 2014 issued by the Danish Maritime Authority Guidance on the construction of CO 2 systems 1. Introduction Notice B
More informationIMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G Ref. T4/4.01 IMO E MSC/Circ.914 4 June 1999 GUIDELINES FOR THE APPROVAL
More information4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 IMO E Ref.: T4/4.01 MSC.1/Circ.1272 4 June 2008 GUIDELINES FOR THE APPROVAL OF FIXED WATER-BASED
More informationSIGMADEK, LTD. FIRE TEST REPORT
SIGMADEK, LTD. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON ALUMINUM EXTRUSION DECK BOARD C/W PORCELAIN TILE INSERT REPORT NUMBER H5331.01-121-24 TEST DATE 09/13/17 ISSUE DATE 10/03/17 RECORD RETENTION
More information