Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.
|
|
- Rosalyn Hamilton
- 5 years ago
- Views:
Transcription
1 Memphis Housing Authority High Rise Fire Alarm Upgrades Questions from Contractors (Through Addendum #2) Communications Systems, Inc.: Legend 1. DL - Dome light symbol should be on the tenant emergency system. See revised sheet E0.1 in 2. B - Bell light symbol should be on the tenant emergency system. See revised sheet E0.1 in 3. PS - Pull string symbol should be on the tenant emergency system. See revised sheet E0.1 in 4. Horn / Strobe occupant notification device should be speaker/strobe. See revised sheet E0.1 in Drawing E1.1-BA 1. Flow and tamper switches on floors shown on demolition not shown on new plans. See revised sheets E1.1-BA and E1.2-BA in 2. Fire phone jack shown on 1 st Floor by FACP which has main fire phone in FACP. See revised sheet E1.1-BA in 3. Fire Pump Building not shown on prints/monitor points or tamper switches. See revised sheet E1.1-BA in 4. Solenoid valves and tampers not shown for elevator with stunt trips. See revised sheet E1.1-BA in 5. Elevator machine room in penthouse not shown with smoke detectors and recall relays. See revised sheet E1.2-BA in 6. Existing smoke on rear door of elevator #1 not shown on new drawing. See revised sheet E1.1-BA in
2 7. ADA units on 2 nd, 3 rd floor not shown for apartments 202,203,204,205,206,302,303,304,305,306. Shows one ada unit on floors 5-14 on new plans; shows apartments 513. See revised sheet E1.1-BA in Barry Homes, Borda Towers, Jefferson Square, Venson Center 1. Missing fire pump monitor and tamper switches. See revised sheets in 2. Missing elevator equipment room, smoke and heat detectors, recall relays, shunt trip relays, solenoid valves and tamper switches. See revised sheets in Barry Homes 1. Missing waterflow and tamper switches on all floors. See revised sheets E1.1-BA and E1.2-BA in 2. ADA units on floors 5-14 are on 2 nd and 3 rd floors; apartments , and have smoke detectors in living room and bedroom. See revised sheet E1.1-BA in Borda Towers 1. Missing waterflow and tamper switches on all floors. See revised sheet E1.1-BO in Jefferson Square 1. Pull station in basement at service area exit not shown. (Exits on current fire alarm system). See revised sheet E1.1-JS in 2. Door holder shown on all doors on stairwells not shown on basement west stairwell. See revised sheet E1.1-BA in 3. ADA units on floors 2, 3 and 4 apartments 200, 201,215,216,212 and on 3 rd floor apt 300,312, and on the 4 th floor apt 400 and 401. See revised sheet E1.1-BA in Venson Center 1. Tamper switches shown but waterflow switches not shown on all floors. See revised sheets E1.1-VC and E1.2-VC in
3 2. ADA units on floors 2, 3 and 4 apartments and on 3 rd floor apt 309,311,313 and on the 4 th floor apt 409,411, and 413. See revised sheet E1.1-VC in Barry Towers 1. Lobby pull station shown on E1.1-BA is in glass area along with speaker/strobe not enough room on frame to mount properly. See revised sheet E1.1-BA in 2. Magnetic door holders shown on floors 2 4, 5-14 on end of corridor do not exist. See revised sheets E1.1-BA and E1.2-BA in 3. Most of fire rating tags on doors and frames have been painted (problem with inspectors in past). Note: On all buildings. Provide new fire rating tags as required by inspector. 4. Strobe light on existing speaker/strobe not visible in elevator area on new plan. Add strobe. See revised sheet E1.1-BA in 5. Note: Doors on stairs floors 2-14 swing into stairwell on south end. See revised sheets E1.1-BA and E1.2-BA in 6. Pull station needs to be added floors 2-14(Distance Exceeds 200 ). See revised sheets E1.1-BA and E1.2-BA in Borda Towers 1. Door holders on north stairs open to breezeway (closed in wall on E1.1-Bo) Outside air exposed to sprinkler standpipe in stairwell on all floors. See revised sheet E1.1-BO in 2. Speaker/strobes in lobby has strobe blocked to lounge by wall shown on plan (A strobe is on lounge north wall existing). See revised sheet E1.1-BO in 3. Placement of fluorescent lights are a problem of placing smoke and stairs on south end. Smoke detectors must be at least 3 feet from fixtures to prevent false data pulses from electronic ballasts. See revised sheet E0.1 in Jefferson Square 1. Door holders shown on doors to service area are to outside ramp from basement. See revised sheet E1.1-JS in
4 2. Door holder on mechanical room is to secure locked area where fire pump is located. See revised sheet E1.1-JS in 3. Door holder to basement stairs fire door not shown. See revised sheet E1.1-JS in 4. Fluorescent light fixtures are in proximity of smoke detectors on elevators 1 st floor. See revised sheet E0.1 in 5. Pull station shown is located on glass area with narrow partition by mail area exit (1 st floor). Move to nearest wall. Relocate pull station as required. 6. Speaker/strobes in dining area strobes are blocked (Existing strobes on storage wall and west wall). See revised sheet E1.1-JS in Venson Center 1. Fluorescent fixture location won t allow placing smoke detector as shown on floors to keep 3 data interference from ballast. See revised sheet E0.1 in 2. Door not as shown on stairs west end on left, not right? Need clarification. Does not affect bid price. 3. Trash chute rooms are where restrooms are shown on floors 2-11 on E1.1-VC and E1.2- VC. See revised sheets E1.1-VC and E1.2-VC in 4. Visual strobe (existing) laundry room not shown on floors See revised sheets E1.1- VC and E1.2-VC in 5. Pull Station needs to be added on floors Distance exceeds 200. See revised sheets E1.1-VC and E1.2-VC in 6. 1 st floor door on west swings to center of stairwell blocking exit. Not part of this contract. Does not affect bid price. Nichols Fire & Security: 1. Drawings state to re use existing raceways but specs say to keep the existing system online until the new system is approved by AHJ, there is no way to do this by re using raceways. See revised sheet E0.1 in Contractor shall provide all new
5 conduits and new wiring for new fire alarm system. Contractor shall not reuse any existing conduits or wiring. 2. Drawings show only one fire fighter jack at each elevator lobby, these are typically required at the stairwell doors also? See revised sheets in 3. The drawings show an annunciator next to the FACP is this required or an error? Annunciator should be located as required by Code. Shown next to FACP for reference. 4. Also, Jonathan E, Nichols Fire & Security was at the pre-bid conference. He was signed in and actually obtained a set of plans. Can we please have our name listed as an attendee? Name will be listed as requested. SimplexGrinnell: 1. Fireman s Phone Jacks.Should be located in each stairwell. Shown only at Elevators. Are the EP s shown on the plans the fireman s phone jacks, or are they actually area of refuge stations, which would be independent of the fire alarm. See revised sheets in 2. Smoke Detectors are not shown in all apts. Smokes should also be in Living Rooms and Bedrooms of larger apts. This will greatly increase the amount of smokes shown on the plans. See revised sheets in 3. Notifications devices seem inadequate in areas especially some upper floors. Visuals should be within 15 feet in end of corridors. (Borda for example) See revised sheets in 4. Just to clarify, Is the call system to be audio(talkback), or just a tone/visual system? The pull string station does not support audio. They are only shown in the bathrooms. The spec is just a little confusing when it talks about audio.however I do see where it calls for this to be a Visual Only System. System is tone / visual only. There is no talkback feature included in system. 5. Some of the buildings show tampers/flows. Some do not.is this accurate. Are only some of the buildings sprinklered? See revised sheets in
6 Tyco: 1. Time Frame Completion? Is there any way you might extend the 250 calendar days? According to our Engineers, there is no way to reuse the conduit and keep the existing system up and running until completion of the new system. That being said, running all new conduit is very time consuming and feel there is no way to complete 4 buildings in that time frame working on 1 building at a time. Time frame has been extended. See revised specifications in Addendum #2. 2. Can we work on multiple buildings at a time? Contractor s will only be allowed to work in one building at a time initially. 3. Is there a secured storage for our equipment on site at each building? There will be a lay down area available, but the contractor will be responsible for the security of all their materials. See specifications. 4. When working in the tenant units will there be specifying times that we can perform the work? Do we have to schedule the work with the MHA for each individual unit? A 72 hour notice is required before working in any of the tenants rooms. A schedule will have to be set up to let the tenants know when we will be working on their floor or room. 5. Will we be provided with a representative of the MHA to accompany us when we enter the tenant units? We want to make sure that we are covered against any fraudulent claims over property damage. A MHA representative will be available to let the contractors in the rooms and a sign off sheet will be made available for the tenants to sign off on once the contractor has left the room. 6. Is there an allowance for damaged ceiling tiles when demoing the existing fire alarm system? Or will that need to be included in the bid? A MHA representative will be available to let the contractors in the rooms and a sign off sheet will be made available for the tenants to sign off on once the contractor has left the room. State Systems, Inc.: 1. When working in the tenant units will there be specifying times that we can perform the work? Do we have to schedule the work with the MHA for each individual unit? Times will be Monday through Friday from 8:00 AM to 5:00 PM. MHA will have a schedule of work coordinate with the building staff and contractors. 2. Will we be provided with a representative of the MHA to accompany us when we enter the tenant units? We want to make sure that we are covered against any fraudulent claims over property damage. The building engineer will be available throughout the duration of each job.
7 3. Is there an allowance for damaged ceiling tiles when demoing the existing fire alarm system? Or will that need to be included in the bid? See revised sheet E0.1 in Questions from Contractors (From Addendum #2 through Addendum #3) Siemens Industry, Inc.: 1. Does the Area of Rescue and Call Emergency system have to be in a FULL CONDUIT SYSTEM? If so this will really add an extreme cost to the bid. Please advise. Or can we using exiting conduit if applicable or conduit for the Riser (vertical) only? I do not see this addressed in the specs or the plans. If this can be verified at this time it would be much appreciative. See revised sketch E0.1-A in Addendum #3. 2. Addendum 2 plans Sheet E.01 shows Tenant Emergency System Connection to Bell There are no Bells showing on the drawings. We believe this was meant to say Connection to DL dome lite as these lights are shown on the drawings. Please Clarify. The symbol is featured on the demolition drawings for the existing bell system. There are no new bells on the drawings for the new fire alarm system. 3. It has been brought to my attention that Addendum 2 does not address the full intent of the Fire Alarm change out. Addendum 2 states that the New Fire Alarm system shall be in place, new wire, new conduit etc. fully operational system. We are not to use any of the existing Conduit/raceways/paths/back boxes/wire. Once approved by Local and State Inspectors then the DEMO of the existing Fire Alarm system can take place. This issue with this is that it does not address how the Sprinkler system will interface to the new system. You cannot interface or connect any of the Flows, tampers, PIV s and Fire Pump devices to the new Fire Alarm System as these devices are already connected to the existing Fire System. You cannot have the Sprinkler devices connected to the Existing and New System at the same time. This would also be the same issue with Duct Detectors but I do not believe there are any duct detectors on this project. Please let me know what the intent is on how to address the interface the Sprinkler devices to the new Fire System. See revised sketch E0.1-A in Addendum #3. Nichols Fire & Security: 1. Specifications require that Contractor must have been in business under their current name for a minimum of 10 years. Is there any flexibility with this requirement? MHA will accept bids from a contractor if they have been in the industry for a minimum of 10 years and can provide insurance and a bid bond as required.
8 State Systems, Inc.: 1. Thanks for your time this morning to hear my concerns over the specifications on the upcoming MHA 4 Building Bid Project. The specification of concern is on page E.01, Item #3 Fire Alarm Changeover-Sequence of Operations, #12 Contractor Shall Provide New Conduit and New Conductors For All New Fire Alarm Devices. Place Entire New System Into Operation Prior To Taking Existing Fire Alarm System Offline. New Fire Alarm Circuits Shall Not Be Loaded To More Than 70% Capacity To Allow For Additional Devices If Required By Fire Marshal. This note will cause the Memphis Housing Authority to spend additional funding that is not required. There are multiple vendors, that will be bidding on this project, that can utilize existing conduits. I would recommend changing this note. See revised sketch E0.1-A in Addendum #3. Questions from Contractors (From Addendum #3 to Addendum #4) SimplexGrinnell: 1. The drawings show a symbol for an Area of Rescue handset in the stairwells. This is a separate system from the fire alarm system. I do not see a spec for anything on the Area of Rescue. Since Area Rescue is a separate system, I don t see where it would go on the bid form, unless it is considered part of the fire alarm. The Area of Rescue would be an active two way voice system. The fire alarm system is a one way voice system aside from the fireman s phones. Can I please get some clarification on this? The sequence of operations includes a graphic workstation and a printer. Are these actual requirements for this project? See revised sketch E0.1-B in Addendum #4. 2. Are the graphic workstations and printers in the sequence of operations actual requirements? Yes, graphic workstations and printers are included in the project. 3. Is the area of refuge is indeed intended to be a separate system, as it is, where does it go on the bid form. Is it included in the fire alarm price? Yes, include the area of refuge systems in the fire alarm prices.
ADDENDUM NO. 1. for. MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140. Marquette, Michigan.
ADDENDUM NO. 1 for MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140 Marquette, Michigan December 12, 2016 TO: ALL BIDDERS OF RECORD This addendum forms a part of
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationSCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL
SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm
More informationInspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY
FIRE ALARM INSPECTION AND TESTING SUMMARY PAGE PER 2013 NFPA 72 Inspector: Jim Smith Test Date: 5/22/2014 PROPERTY INFORMATION Name of Property: Windsor Tower Owner of Property: Jim Gibbs Properties Address:
More informationRE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan
ADDENDUM NO. 2 RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan TO: All Bidders Gentlemen: You are hereby directed to make the following changes in the Project Manual and/or
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved
More informationCombining Old and New Systems in Existing Buildings and Other Retrofit Tales. By Paul Jewett CFAA Technician Number 11
Combining Old and New Systems in Existing Buildings and Other Retrofit Tales By Paul Jewett CFAA Technician Number 11 Combining Old and New Systems in Existing Buildings and Other Retrofit Tales Disclaimer
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More information2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This
More informationSmoke Detector Activation of any smoke detector shall start the alarm verification mode.
Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,
More informationDivision 28 - Electronic Safety and Security
Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For 2018 Sample Inspection Report 123 Main Street Building Phone - (615) 337-9710 Anywhere, State 90009 Tested to NFPA 72 Standards This Inspection
More informationFire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016
Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the
More informationFull Service Central Station Fire Alarm Listing Evaluation
Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm
More informationUniversity Design Standard Fire Alarm Systems
1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 86 - BROOKLYN, 220 IRVING AVENUE, New York, 11237 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-14
More informationElectronic Safety and Security
28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 174 - QUEENS, 65-10 DIETERLE CRESCENT, New York, 11374 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-01-25
More informationSCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003
SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved SCO # 1Punch listed items were noted below on
More informationNOTICE TO ALL FIRMS. Bid RFI Questions and Answers
Purchasing Department 227 West 27 th Street New York, NY 10001 Purchasing Dept. Tel. 212-217-3630 Purchasing Dept. Fax 212-217-3631 Purchasing@fitnyc.edu NOTICE TO ALL FIRMS Date: March 8, 2018 To: From:
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Anywhere, USA 30303 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable
More informationGENERAL AREAS OF INSPECTION
This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that
More informationMANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO
MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite
More informationDIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM
DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,
More informationNYC Department of Education
Building Assessment Survey 2017-2018 Asset: NEW SCH FOR ARTS AND SCIENCE - X, 965 LONGWOOD AVENUE, New York, 10459 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-01 8:13 AM 2017-12-01
More informationFIRE & LIFE SAFTEY STANDARD
Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationOSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM
OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 314 - BROOKLYN, 330 59 STREET, New York, 11220 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-23
More informationIN2 Digital, Addressable Fire-alarm System
Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Digital, Addressable Fire-alarm System Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals
More information109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:
109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr
More informationSECTION : FIRE ALARM & DETECTION SYSTEMS
SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction
More information2018 NICET Code Transition Changes
2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes
More informationFire Alarm and Life Safety System Inspection Certificate
www.fleenorsecurity.com 3 Morgan Court Johnson City, TN 37604 (423) 282-3755 Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Johnson City, TN 37604
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationSECTION FIRE DETECTION AND ALARM
PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Section 15300 for requirements regarding fire protection systems. 1.2 SCOPE OF SECTION: This section contains the requirements for equipment and installation
More informationRocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO
Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO 80303 303-494-3735 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3
More informationFIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)
INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationFIRE AND SAFETY PROJECT REVIEW REPORT
1. A001 2. A001 3. A001 4. D102/103 5. A102/103 *VA enforces/applies the National Fire Protection Association (NFPA) 101 (current edition is 2015) and not the International Building Code (IBC). Ideally
More informationBrighton Area Fire Authority
615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following
More informationSANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More informationSECTION ADDRESSABLE FIRE ALARM SYSTEM
SECTION 16723 ADDRESSABLE FIRE ALARM SYSTEM 1 PART 1 GENERAL 1.1 DESCRIPTION A. This section outlines the requirements for the installation, programming and configuration of Addressable Fire Alarm System
More informationNFPA Changes
Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 135 - QUEENS, 207-11 89TH AVENUE, New York, 11427 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20
More informationHIGH-RISE RETROFIT ORDINANCES - NO and NO
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 56 - STATEN ISLAND, 250 KRAMER AVE., New York, 10309 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-20
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 59 ANNEX - BRONX, 2120 QUARRY RD, New York, 10457 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-02-12
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance
More informationFire Alarm, Water Flow Alarm & Signaling Systems
Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving
More informationSECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM
SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat
More informationSome information I have read tells me to evacuate immediately in case of fire. Fire In Your Residential Building. To Go?? To Stay??
Fire In Your Residential Building To Go?? or To Stay?? Your safety depends on the right decision. Your fire safety is your responsibility! If you live in an apartment or condominium, your safety also depends
More informationCITY OF FARMINGTON 800 Municipal Drive Farmington, NM (505) Fax (505)
CITY OF FARMINGTON 800 Municipal Drive Farmington, NM 87401-2663 (505) 599-1373 Fax (505) 599-1377 http://www.fmtn.org IMMEDIATE ATTENTION Construction Services for Municipal Operations Center Expansion
More informationEVACUATION PLAN Solvang Retirement 1202 Jacobs Drive Eugene, OR 97402
EVACUATION PLAN Solvang Retirement 1202 Jacobs Drive Eugene, OR 97402 Purpose The purpose of this plan is to establish procedures for the systematic, safe, and orderly evacuation of the building at 1202
More informationPre-Bid Meeting Minutes 2018 A & E RFP February 6, :00 a.m.
Attendees: Pre-Bid Meeting Minutes 2018 A & E RFP February 6, 2019 10:00 a.m. Anthony Shomin Sue Martin Architectural & Engineer Professionals KCKHA Modernization Coordinator KCKHA Modernization Admin.
More informationCommercial Application/Plan Review Submittal Checklist
Commercial Application/Plan Review Submittal Checklist The following checklist has been compiled to assist in expediting the commercial plan review and permit issuance process. Please take a moment to
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationChanges to this Division since the last issuance are indicated with yellow highlighted text.
Table of Contents 28 10 00 ELECTRONIC ACCESS CONTROL AND INTRUSION DETECTION... 2 A. GENERAL... 2 B. DESIGN REQUIREMENTS... 2 C. CONSTRUCTION REQUIREMENTS... 3 28 20 00 ELECTRONIC SURVEILLANCE... 4 A.
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 81 ANNEX (OLD 75) - QUEENS, 511 SENECA AVENUE, New York, 11385 Inspection Id Inspection Type Time In Last Edited EE : Electrical
More informationM001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings
1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationCOUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III
SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationMichigan State University Construction Standards FIRE DETECTION AND ALARM PAGE
PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationFloor Warden Training
Floor Warden Training June 2013 501 BOYLSTON STREET Floor LIFE Warden SAFETY TRAINING Training Agenda You are Needed Building Overview Fire and Life Safety Systems General Evacuation and Relocation Duties
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationI. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018
Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire
More informationBOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015
Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 127 - BROOKLYN, 7805 7 AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-30
More informationUSAutomatic Sprinkler Corporation
Inspection Report Information For CITY OF WESTFIELD - PUBLIC SAFETY Prepared by: T.Hughes, C.Gibbs a fire protection company Sheet 1 of 2 Phone: (317) 573-8160 Fax: (317) 573-8161 110370 REPORT OF INSPECTION
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 371 (OLD 615) - BROOKLYN, 355 37 STREET, New York, 11232 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-23
More informationSECTION 907 FIRE ALARM AND DETECTION SYSTEMS
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More informationEmergency Evacuation Plan. Tiffany Tower Plot W2 Jumeirah Lakes Towers
Emergency Evacuation Plan Tiffany Tower Plot W2 Jumeirah Lakes Towers September 2017 TABLE OF CONTENTS 1.0 I N T R O D U C T I O N... 1 2.0 B U I L D I N G I N F O R M A T I O N... 1 3.0 F I R E S Y S
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationFire Protection Coffee Break Training May 2016
Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers
More informationYou are required to READ ALL PAGES. of this application
Fire/Smoke/Heat/CO Application Checklist You are required to READ ALL PAGES of this application NEW ROCHELLE FIRE DEPARTMENT 90 Beaufort Pl, New Rochelle, NY 10801 - (914) 654-2213 APPLICATION FOR FIRE/SMOKE/HEAT/CO
More informationCITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1
CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-07
More informationNYC Department of Education
Asset: P.S. 5 - BROOKLYN, 820 HANCOCK STREET, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-25 8:54 AM 2018-06-04 10:18 AM Asset Data Type of Service Does Interactive
More informationFOR LEASE ROCKWOOD OFFICE PARK
WILMINGTON, DE 19809 www.cbre.us/rockwood 11 PROPERTY HIGHLIGHTS Owner: Asset Manager: Address: Rockwood Office Park Associates, L.P. AIG Global Real Estate Investment Group 501, 503 & 505 Carr Road Site:
More informationBurnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:
Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean
More informationInterfacing Fire Alarm, Sprinkler and Elevator Systems
1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationDIGITAL, ADDRESSABLE FIRE ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationNYC Department of Education
Asset: LEARNING SUPPORT CENTER - K, 1665 ST. MARKS AVENUE, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-07 1:06 PM 2018-05-10 12:20 PM Asset Data Type of Service
More informationAdvanced Fire Alarm Systems Training Program Outline (5 Day)
Advanced Fire Alarm Systems Training Program Outline (5 Day) Day 1 Prescriptive and Performance-Based Design Understand the methodology in accessing the threat of fire within a structure. Know the difference
More informationCITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST
CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:
More informationCDB Life Safety Upgrades Facility Wide Choate Mental Health and Development Center Anna, Union County, Illinois
BIDDING & CONTRACT REQUIREMENTS DATE: June 27, 2014 State of Illinois CAPITAL DEVELOPMENT BOARD Architechniques, Ltd. Mark Feldhake, AIA, LEED AP 817 S. Park Ave. Herrin, Illinois 62948 TO: PROSPECTIVE
More informationDemonstration and Training of MEP Systems Page 1 of 15
Page 1 of 15 Last Update: May 17, 2018 A. General: 1. Demonstrations and Training of various MEP and other systems is very important to BSU Facilities, especially on new building or major renovation projects.
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationWORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES
1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: PS 152 ANNEX -BROOKLYN, 1087 OCEAN AVENUE, New York, 11210 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 364 - BROOKLYN, 1426 FREEPORT LOOP, New York, 11239 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-16
More information